Grundfos UPE 2000 Series, UPE 100-120 FZ, UPED 80-120 FZ, UPE 80-120 FZ, UPED 100-120 FZ Installation And Operating Instructions Manual

GRUNDFOS INSTRUCTIONS
UPE Series 2000
UPE(D) 80-120 FZ, UPE 100-120 FZ
Installation and operating instructions
UPE Series 2000
Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Deutsch (DE)
Montage- und Betriebsanleitung. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Appendix 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table of contents
3
Declaration of conformity
Declaration of Conformity
GB: EC declaration of conformity
We, Grundfos, declare under our sole responsibility that the products UPE(D) Series 2000, to which this declaration relates, are in conformity with these Council directives on the approximation of the laws of the EC member states: – Machinery Directive (2006/42/EC).
Standard used: EN 809: 2009.
– Low Voltage Directive (2006/95/EC).
Standards used: EN 60335-1: 2002 and EN 60335-2-51: 2003.
– EMC Directive (2004/108/EC).
Standard used: EN 61800-3.
DE: EG-Konformitätserklärung
Wir, Grundfos, erklären in alleiniger Verantwortung, dass die Produkte UPE(D) Series 2000, auf die sich diese Erklärung bezieht, mit den folgenden Richtlinien des Rates zur Angleichung der Rechtsvorschriften der EU-Mitgliedsstaaten übereinstimmen: – Maschinenrichtlinie (2006/42/EG).
Norm, die verwendet wurde: EN 809: 2009.
– Niederspannungsrichtlinie (2006/95/EG).
Normen, die verwendet wurden: EN 60335-1: 2002 und EN 60335-2-51: 2003.
– EMV-Richtlinie (2004/108/EG).
Norm, die verwendet wurde: EN 61800-3.
Bjerringbro, 15th March 2011
Svend Aage Kaae Technical Director
Grundfos Holding A/S
Poul Due Jensens Vej 7
8850 Bjerringbro, Denmark
Person authorised to compile technical file and
empowered to sign the EC declaration of conformity.
4
English (GB) Installation and operating instructions
Caution
Note
Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
2. General description
3. Applications
3.1 Pumped liquids
4. Installation
4.1 Positioning the pump
4.2 Mounting the pressure sensor
4.3 Control box positions
4.4 Twin-head pumps
4.5 Non-return valve
4.6 Insulation
4.7 Frost protection
5. Electrical connection
5.1 Ferrite core
5.2 Wiring diagram
6. Start-up
6.1 Venting the pump
7. Functions
7.1 Control modes
7.2 Control of twin-head pumps
7.3 Selection of control mode
7.4 Max. or min. curve duty
7.5 Constant-curve duty
7.6 Temperature influence
7.7 Indicator lights
7.8 External fault indication
7.9 External analog 0-10 V controller
7.10 External forced control
7.11 Deactivating the control panel
7.12 Bus communication
7.13 Remote control
8. Setting the pump
8.1 Factory settings
8.2 Control panel
8.3 R100
8.4 Menu OPERATION
8.5 Menu STATUS
8.6 Menu INSTALLATION
8.7 Priority of settings
9. Fault finding
10. Megging
10.1 Megging of UPE pumps
10.2 High-voltage test
11. Service kits
12. Technical data
13. Disposal
Warning Prior to installation, read these
installation and operating instructions. Installation and operation must comply
5 5 6
6
6
6 6 6 7 7 7 7
7
7
1. Symbols used in this document
8
9
9
10
10 10 11 12 12 13 13 14
2. General description
14 15
The Grundfos UPE(D) FZ is a range of circulator
15
pumps with differential-pressure control enabling adjustment of the pump performance to the actual
15
system requirements. In many systems, this will
15
reduce the power consumption considerably, reduce
16
noise from thermostatic valves and similar fittings,
16
and improve the control of the system.
16
The desired head can be set on the pump control
18
panel.
20
These instructions apply to the pump types
20
UPE(D) 80-120 FZ and UPE 100-120 FZ.
21
The pump offers the following functions:
22
Proportional-pressure control (factory setting).
23 24
24
Constant-pressure control.
24
25 26
Constant-curve duty.
26
with local regulations and accepted codes of good practice.
Warning The use of this product requires
experience with and knowledge of the product. Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety. Children must not use or play with this product.
Warning If these safety instructions are not
observed, it may result in personal injury!
If these safety instructions are not observed, it may result in malfunction or damage to the equipment!
Notes or instructions that make the job easier and ensure safe operation.
The pump head is changed in accordance with the flow demand. The desired head can be set on the pump control panel.
A constant head is maintained, irrespective of the flow demand. The desired head can be set on the pump control panel.
The pump runs at a constant speed on or between the max. and min. curves.
English (GB)
5
Temperature influence.
Note
Note
English (GB)
The pump head varies depending on the liquid temperature.
External fault signal via a potential-free output.
External analog control of head or speed from
an external 0-10 V signal transmitter.
External forced control via inputs for
– start/stop – min. curve.
Bus communication.
The UPE(D) FZ circulator pumps incorporate an input for bus communication. The pump can be controlled and monitored by a building management system.
Remote control.
The pump can be operated with the Grundfos R100 remote control.
3. Applications
The UPE(D) FZ circulator pumps are designed for circulating liquids in heating systems.
The UPE(D) FZ range is suitable for
• systems with a constant flow where it is
desirable to optimise the setting of the pump duty point.
• systems with variable flow-pipe temperatures.
3.1 Pumped liquids
Thin, clean, non-aggressive and non-explosive liquids, not containing solid particles, fibres or mineral oil.
In heating systems, the water should meet the requirements of accepted standards on water quality in heating systems, for example the German standard VDI 2035.
Warning The pump must not be used for the
transfer of flammable liquids, such as diesel oil, petrol or similar liquids.
4.2 Mounting the pressure sensor
Mount the pressure sensor only after the pump has been installed in the system.
See fig. 1.
1. Place the O-ring in the seat of the pump housing.
2. Place the sensor housing without damaging the O-ring.
3. Fit and tighten the two screws.
Fig. 1 Mounting the pressure sensor
4.3 Control box positions
The control box must only be turned to the positions shown on page 310.
The arrows show the allowed/possible flow directions.
4.3.1 Changing the control box position
Warning Before any dismantling of the pump,
the system must be drained, or the isolating valves on either side of the pump must be closed, as the pumped liquid may be scalding hot and under high pressure.
TM04 4631 1809
4. Installation
4.1 Positioning the pump
The arrow on the pump housing indicates the liquid flow direction through the pump.
Warning Make sure that persons cannot
accidentally come into contact with the hot surfaces of the pump.
The pump must be installed with the motor shaft horizontal.
See mounting dimensions at the end of these instructions.
6
Fig. 2 Correct control box position
Change the control box position as follows:
1. Slacken the cable clamp of the pressure sensor.
2. Remove the four screws holding the pump head.
3. Turn the pump head to the desired position.
4. Refit the four screws and tighten securely.
5. Adapt the pressure sensor cable, and tighten the cable clamp.
Warning Make sure that the pressure sensor
cable cannot come into contact with the pump head.
TM04 4633 1809
4.4 Twin-head pumps
Twin-head pumps offer these operating modes:
• alternating operation
• standby operation
• synchronous operation
• single-pump operation.
4.4.1 Master pump and slave pump
The master pump will always be the pump to the right when seen from the control box end and the pump is pumping upwards. See fig. 3, pos. 1.
Fig. 3 Master pump (1) and slave pump (2)
4.5 Non-return valve
If a non-return valve is fitted in the pipe system (fig. 4), it must be ensured that the minimum discharge pressure is always higher than the closing pressure of the valve. This is especially important in proportional-pressure control mode (reduced head at low flows).
Fig. 4 Non-return valve
4.6 Insulation
If the pump is insulated without using Grundfos insulating kits, it must be ensured that the differential-pressure and temperature sensor in the pump housing is not covered.
4.7 Frost protection
If the pump is not being used during periods of frost, the necessary steps must be taken to prevent frost bursts.
5. Electrical connection
The electrical connection and protection must be carried out according to local regulations.
Warning Never make any connections in the
pump control box unless the power supply has been switched off for at least 5 minutes. The indicator light must be off. See fig. 6, pos. 21.
The earth terminal of t he pump m ust be earthed.
The pump must be connected to an external mains switch with a minimum contact gap of 3 mm in all poles.
Earthing or neutralisation can be used for protection against indirect contact.
Megging must be carried out as described in section 10. Megging.
If the pump is connected to an electric
TM04 4629 1809TM02 0640 0301
• The pump requires no external motor protection.
• Check that the supply voltage and frequency
5.1 Ferrite core
Install the ferrite core as shown below.
installation where an earth leakage circuit breaker (ELCB) is used as an additional protection, this circuit breaker must trip out when earth fault currents with DC content (pulsating DC) and smooth DC earth fault currents occur.
The earth leakage circuit breaker must be marked with these symbols:
correspond to the values stated on the pump nameplate.
English (GB)
Fig. 5 Ferrite core installed
TM04 9584 4610
7
5.2 Wiring diagram
English (GB)
Fig. 6 Internal view of the control box
TM04 4634 4709
Pos. Description
A, Y, B Terminal block for GENIbus
T Terminal block for twin-head pump
D Terminal block for pressure and temperature sensor on the pump (standard)
1, 2 (START/STOP)
3, 4 (MIN.)
5, 6 (0-10 V)
7, 8 (ALARM) Terminal block for remote alarm contact. Maximum load: 250 VAC, 5 A.
9, 10, 11
12, 13, 14
15 Motor earthing screw
16, 17 Terminals for connection of motor protector, white lead (T1, T2)
18 Terminal for control panel
8
Terminals for external start/stop (connect only contacts with no voltage)
Terminals for min. curve input (connect only contacts with no voltage)
Terminals for external analog input 0-10 VDC Terminal 5 = +10 V Terminal 6 = 0 V
Terminals for supply voltage, 1 x 230 V, 50-60 Hz Terminal 9 = Line (L) Terminal 10 = Earth ( ) Terminal 11 = Neutral (N)
Terminals for connection of motor cables Terminal 12 = brown lead Terminal 13 = grey lead Terminal 14 = black lead
19 Control panel retaining screws
Note
Vent screw
20 Terminal for fan
21 High-voltage indicator
22 Terminal for screened motor cable
23 Fan
Note:
• All cables used must be heat-resistant up to at least +85 °C.
• All cables used must be installed in accordance with EN 60204-1.
Warning Wires connected to
• outputs 7 and 8,
• inputs 1 to 6,
supply terminals and
differential-pressure and
temperature sensor
must be separated from each other and from the supply by reinforced insulation.
All wires connected to a terminal block must be tied up at the terminals.
Concerning demands on signal wires and signal transmitters, see section 12. Technical data.
6. Start-up
Do not start the pump until the system has been filled with liquid and vented. Furthermore, the required minimum inlet pressure must be available at the pump inlet. See section 12. Technical data.
The system cannot be vented through the pump.
6.1 Venting the pump
Vent the pump before start-up. See fig. 7.
Warning When the vent screw is slackened,
scalding hot liquid under high pressure may escape. Care must be taken to ensure that the escaping liquid does not cause personal injury or damage to other components.
English (GB)
Fig. 7 Venting the pump
The pump may be noisy, when first switched on, due to air remaining in the pump. This noise should cease after a few minutes running.
After start-up, set the desired operating mode and possibly pump head.
TM04 4635 1809 - TM04 4636 180 9
9
7. Functions
2
H
Q
H
Q
H
set
H
set
H
set
Proportional pressure
Constant pressure
Slave pump Master pump
English (GB)
Some functions can only be selected with the Grundfos R100 remote control. Where and how the various settings are made appear from section 8. Setting the pump.
7.1 Control modes
The UPE(D) FZ pumps can be set to the control mode which is most suitable for the individual system.
Two control modes are available:
• proportional pressure (factory setting)
• constant pressure.
Proportional-pressure control
To be set on the control panel or with the R100. The pump head is reduced at falling water demand
and increased at rising water demand. See fig. 8. This is the factory setting as, in most cases, this is
the optimum control mode, and at the same time it consumes the least energy.
Constant-pressure control
To be set on the control panel or with the R100. The pump maintains a constant pressure,
irrespective of water demand. See fig. 8.
Fig. 8 Pressure control
7.2 Control of twin-head pumps
The factory setting can be changed with the R100.
Fig. 9 Master and slave pumps
Four operating modes are available. The selection of operating mode depends on whether reliability, lifetime or performance has top priority.
Alternating operation (factory setting).
Pump operation alternates every 24 hours. If the power supply to the pump has been switched off, any of the pumps may start when the power supply is switched on again. Reaction in case of fault: In case of fault in one pump, the duty pump will operate continuously as a single-head pump.
Standby operation.
The master pump is operating continuously. Every 25 hours the slave pump will start and run for approx. 10 seconds to prevent it from seizing up. Reaction in case of fault: If the master pump stops due to a fault, the slave pump will operate continuously as a single-head pump.
Synchronous operation.
The pumps are operating at the same motor frequency. This operating mode is suitable if the flow demand exceeds the flow of one pump. Reaction in case of fault: In case of fault in one pump, the duty pump will operate continuously as a single-head pump.
Single-pump operation.
The pumps are operating completely independently of each other without internal communication, but the twin-head cable must be connected. All functions of each pump are identical to those of a single-head pump.
All the other functions mentioned in sections
7.1 Control modes to 7.13 Remote control are possible in the four operating modes.
7.2.1 Why select single-pump operation
Select single-pump operation
• when the twin-head pump is to be controlled or
TM00 5546 4596TM04 4629 1809
monitored by a Grundfos pump management system.
• in all other situations where the master and slave pumps are to operate independently of each other as two single-head pumps.
7.2.2 R100 remote control
Single-pump operation is to be selected with the R100. See section 8.6.6 Twin-head pump.
7.2.3 Operation in parallel
In single-head operation mode, the pumps must never run at the same time, unless the pump is controlled by a Grundfos pump management system.
7.2.4 Setting the slave pump
When single-pump operation mode has been selected, the slave pump settings will correspond to the settings of the last working pump.
10
Loading...
+ 22 hidden pages