Grundfos UPE 2000 Series, UPE 100-120 FZ, UPED 80-120 FZ, UPE 80-120 FZ, UPED 100-120 FZ Installation And Operating Instructions Manual

GRUNDFOS INSTRUCTIONS
UPE Series 2000
UPE(D) 80-120 FZ, UPE 100-120 FZ
Installation and operating instructions
UPE Series 2000
Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Deutsch (DE)
Montage- und Betriebsanleitung. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Appendix 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table of contents
3
Declaration of conformity
Declaration of Conformity
GB: EC declaration of conformity
We, Grundfos, declare under our sole responsibility that the products UPE(D) Series 2000, to which this declaration relates, are in conformity with these Council directives on the approximation of the laws of the EC member states: – Machinery Directive (2006/42/EC).
Standard used: EN 809: 2009.
– Low Voltage Directive (2006/95/EC).
Standards used: EN 60335-1: 2002 and EN 60335-2-51: 2003.
– EMC Directive (2004/108/EC).
Standard used: EN 61800-3.
DE: EG-Konformitätserklärung
Wir, Grundfos, erklären in alleiniger Verantwortung, dass die Produkte UPE(D) Series 2000, auf die sich diese Erklärung bezieht, mit den folgenden Richtlinien des Rates zur Angleichung der Rechtsvorschriften der EU-Mitgliedsstaaten übereinstimmen: – Maschinenrichtlinie (2006/42/EG).
Norm, die verwendet wurde: EN 809: 2009.
– Niederspannungsrichtlinie (2006/95/EG).
Normen, die verwendet wurden: EN 60335-1: 2002 und EN 60335-2-51: 2003.
– EMV-Richtlinie (2004/108/EG).
Norm, die verwendet wurde: EN 61800-3.
Bjerringbro, 15th March 2011
Svend Aage Kaae Technical Director
Grundfos Holding A/S
Poul Due Jensens Vej 7
8850 Bjerringbro, Denmark
Person authorised to compile technical file and
empowered to sign the EC declaration of conformity.
4
English (GB) Installation and operating instructions
Caution
Note
Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
2. General description
3. Applications
3.1 Pumped liquids
4. Installation
4.1 Positioning the pump
4.2 Mounting the pressure sensor
4.3 Control box positions
4.4 Twin-head pumps
4.5 Non-return valve
4.6 Insulation
4.7 Frost protection
5. Electrical connection
5.1 Ferrite core
5.2 Wiring diagram
6. Start-up
6.1 Venting the pump
7. Functions
7.1 Control modes
7.2 Control of twin-head pumps
7.3 Selection of control mode
7.4 Max. or min. curve duty
7.5 Constant-curve duty
7.6 Temperature influence
7.7 Indicator lights
7.8 External fault indication
7.9 External analog 0-10 V controller
7.10 External forced control
7.11 Deactivating the control panel
7.12 Bus communication
7.13 Remote control
8. Setting the pump
8.1 Factory settings
8.2 Control panel
8.3 R100
8.4 Menu OPERATION
8.5 Menu STATUS
8.6 Menu INSTALLATION
8.7 Priority of settings
9. Fault finding
10. Megging
10.1 Megging of UPE pumps
10.2 High-voltage test
11. Service kits
12. Technical data
13. Disposal
Warning Prior to installation, read these
installation and operating instructions. Installation and operation must comply
5 5 6
6
6
6 6 6 7 7 7 7
7
7
1. Symbols used in this document
8
9
9
10
10 10 11 12 12 13 13 14
2. General description
14 15
The Grundfos UPE(D) FZ is a range of circulator
15
pumps with differential-pressure control enabling adjustment of the pump performance to the actual
15
system requirements. In many systems, this will
15
reduce the power consumption considerably, reduce
16
noise from thermostatic valves and similar fittings,
16
and improve the control of the system.
16
The desired head can be set on the pump control
18
panel.
20
These instructions apply to the pump types
20
UPE(D) 80-120 FZ and UPE 100-120 FZ.
21
The pump offers the following functions:
22
Proportional-pressure control (factory setting).
23 24
24
Constant-pressure control.
24
25 26
Constant-curve duty.
26
with local regulations and accepted codes of good practice.
Warning The use of this product requires
experience with and knowledge of the product. Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety. Children must not use or play with this product.
Warning If these safety instructions are not
observed, it may result in personal injury!
If these safety instructions are not observed, it may result in malfunction or damage to the equipment!
Notes or instructions that make the job easier and ensure safe operation.
The pump head is changed in accordance with the flow demand. The desired head can be set on the pump control panel.
A constant head is maintained, irrespective of the flow demand. The desired head can be set on the pump control panel.
The pump runs at a constant speed on or between the max. and min. curves.
English (GB)
5
Temperature influence.
Note
Note
English (GB)
The pump head varies depending on the liquid temperature.
External fault signal via a potential-free output.
External analog control of head or speed from
an external 0-10 V signal transmitter.
External forced control via inputs for
– start/stop – min. curve.
Bus communication.
The UPE(D) FZ circulator pumps incorporate an input for bus communication. The pump can be controlled and monitored by a building management system.
Remote control.
The pump can be operated with the Grundfos R100 remote control.
3. Applications
The UPE(D) FZ circulator pumps are designed for circulating liquids in heating systems.
The UPE(D) FZ range is suitable for
• systems with a constant flow where it is
desirable to optimise the setting of the pump duty point.
• systems with variable flow-pipe temperatures.
3.1 Pumped liquids
Thin, clean, non-aggressive and non-explosive liquids, not containing solid particles, fibres or mineral oil.
In heating systems, the water should meet the requirements of accepted standards on water quality in heating systems, for example the German standard VDI 2035.
Warning The pump must not be used for the
transfer of flammable liquids, such as diesel oil, petrol or similar liquids.
4.2 Mounting the pressure sensor
Mount the pressure sensor only after the pump has been installed in the system.
See fig. 1.
1. Place the O-ring in the seat of the pump housing.
2. Place the sensor housing without damaging the O-ring.
3. Fit and tighten the two screws.
Fig. 1 Mounting the pressure sensor
4.3 Control box positions
The control box must only be turned to the positions shown on page 310.
The arrows show the allowed/possible flow directions.
4.3.1 Changing the control box position
Warning Before any dismantling of the pump,
the system must be drained, or the isolating valves on either side of the pump must be closed, as the pumped liquid may be scalding hot and under high pressure.
TM04 4631 1809
4. Installation
4.1 Positioning the pump
The arrow on the pump housing indicates the liquid flow direction through the pump.
Warning Make sure that persons cannot
accidentally come into contact with the hot surfaces of the pump.
The pump must be installed with the motor shaft horizontal.
See mounting dimensions at the end of these instructions.
6
Fig. 2 Correct control box position
Change the control box position as follows:
1. Slacken the cable clamp of the pressure sensor.
2. Remove the four screws holding the pump head.
3. Turn the pump head to the desired position.
4. Refit the four screws and tighten securely.
5. Adapt the pressure sensor cable, and tighten the cable clamp.
Warning Make sure that the pressure sensor
cable cannot come into contact with the pump head.
TM04 4633 1809
4.4 Twin-head pumps
Twin-head pumps offer these operating modes:
• alternating operation
• standby operation
• synchronous operation
• single-pump operation.
4.4.1 Master pump and slave pump
The master pump will always be the pump to the right when seen from the control box end and the pump is pumping upwards. See fig. 3, pos. 1.
Fig. 3 Master pump (1) and slave pump (2)
4.5 Non-return valve
If a non-return valve is fitted in the pipe system (fig. 4), it must be ensured that the minimum discharge pressure is always higher than the closing pressure of the valve. This is especially important in proportional-pressure control mode (reduced head at low flows).
Fig. 4 Non-return valve
4.6 Insulation
If the pump is insulated without using Grundfos insulating kits, it must be ensured that the differential-pressure and temperature sensor in the pump housing is not covered.
4.7 Frost protection
If the pump is not being used during periods of frost, the necessary steps must be taken to prevent frost bursts.
5. Electrical connection
The electrical connection and protection must be carried out according to local regulations.
Warning Never make any connections in the
pump control box unless the power supply has been switched off for at least 5 minutes. The indicator light must be off. See fig. 6, pos. 21.
The earth terminal of t he pump m ust be earthed.
The pump must be connected to an external mains switch with a minimum contact gap of 3 mm in all poles.
Earthing or neutralisation can be used for protection against indirect contact.
Megging must be carried out as described in section 10. Megging.
If the pump is connected to an electric
TM04 4629 1809TM02 0640 0301
• The pump requires no external motor protection.
• Check that the supply voltage and frequency
5.1 Ferrite core
Install the ferrite core as shown below.
installation where an earth leakage circuit breaker (ELCB) is used as an additional protection, this circuit breaker must trip out when earth fault currents with DC content (pulsating DC) and smooth DC earth fault currents occur.
The earth leakage circuit breaker must be marked with these symbols:
correspond to the values stated on the pump nameplate.
English (GB)
Fig. 5 Ferrite core installed
TM04 9584 4610
7
5.2 Wiring diagram
English (GB)
Fig. 6 Internal view of the control box
TM04 4634 4709
Pos. Description
A, Y, B Terminal block for GENIbus
T Terminal block for twin-head pump
D Terminal block for pressure and temperature sensor on the pump (standard)
1, 2 (START/STOP)
3, 4 (MIN.)
5, 6 (0-10 V)
7, 8 (ALARM) Terminal block for remote alarm contact. Maximum load: 250 VAC, 5 A.
9, 10, 11
12, 13, 14
15 Motor earthing screw
16, 17 Terminals for connection of motor protector, white lead (T1, T2)
18 Terminal for control panel
8
Terminals for external start/stop (connect only contacts with no voltage)
Terminals for min. curve input (connect only contacts with no voltage)
Terminals for external analog input 0-10 VDC Terminal 5 = +10 V Terminal 6 = 0 V
Terminals for supply voltage, 1 x 230 V, 50-60 Hz Terminal 9 = Line (L) Terminal 10 = Earth ( ) Terminal 11 = Neutral (N)
Terminals for connection of motor cables Terminal 12 = brown lead Terminal 13 = grey lead Terminal 14 = black lead
19 Control panel retaining screws
Note
Vent screw
20 Terminal for fan
21 High-voltage indicator
22 Terminal for screened motor cable
23 Fan
Note:
• All cables used must be heat-resistant up to at least +85 °C.
• All cables used must be installed in accordance with EN 60204-1.
Warning Wires connected to
• outputs 7 and 8,
• inputs 1 to 6,
supply terminals and
differential-pressure and
temperature sensor
must be separated from each other and from the supply by reinforced insulation.
All wires connected to a terminal block must be tied up at the terminals.
Concerning demands on signal wires and signal transmitters, see section 12. Technical data.
6. Start-up
Do not start the pump until the system has been filled with liquid and vented. Furthermore, the required minimum inlet pressure must be available at the pump inlet. See section 12. Technical data.
The system cannot be vented through the pump.
6.1 Venting the pump
Vent the pump before start-up. See fig. 7.
Warning When the vent screw is slackened,
scalding hot liquid under high pressure may escape. Care must be taken to ensure that the escaping liquid does not cause personal injury or damage to other components.
English (GB)
Fig. 7 Venting the pump
The pump may be noisy, when first switched on, due to air remaining in the pump. This noise should cease after a few minutes running.
After start-up, set the desired operating mode and possibly pump head.
TM04 4635 1809 - TM04 4636 180 9
9
7. Functions
2
H
Q
H
Q
H
set
H
set
H
set
Proportional pressure
Constant pressure
Slave pump Master pump
English (GB)
Some functions can only be selected with the Grundfos R100 remote control. Where and how the various settings are made appear from section 8. Setting the pump.
7.1 Control modes
The UPE(D) FZ pumps can be set to the control mode which is most suitable for the individual system.
Two control modes are available:
• proportional pressure (factory setting)
• constant pressure.
Proportional-pressure control
To be set on the control panel or with the R100. The pump head is reduced at falling water demand
and increased at rising water demand. See fig. 8. This is the factory setting as, in most cases, this is
the optimum control mode, and at the same time it consumes the least energy.
Constant-pressure control
To be set on the control panel or with the R100. The pump maintains a constant pressure,
irrespective of water demand. See fig. 8.
Fig. 8 Pressure control
7.2 Control of twin-head pumps
The factory setting can be changed with the R100.
Fig. 9 Master and slave pumps
Four operating modes are available. The selection of operating mode depends on whether reliability, lifetime or performance has top priority.
Alternating operation (factory setting).
Pump operation alternates every 24 hours. If the power supply to the pump has been switched off, any of the pumps may start when the power supply is switched on again. Reaction in case of fault: In case of fault in one pump, the duty pump will operate continuously as a single-head pump.
Standby operation.
The master pump is operating continuously. Every 25 hours the slave pump will start and run for approx. 10 seconds to prevent it from seizing up. Reaction in case of fault: If the master pump stops due to a fault, the slave pump will operate continuously as a single-head pump.
Synchronous operation.
The pumps are operating at the same motor frequency. This operating mode is suitable if the flow demand exceeds the flow of one pump. Reaction in case of fault: In case of fault in one pump, the duty pump will operate continuously as a single-head pump.
Single-pump operation.
The pumps are operating completely independently of each other without internal communication, but the twin-head cable must be connected. All functions of each pump are identical to those of a single-head pump.
All the other functions mentioned in sections
7.1 Control modes to 7.13 Remote control are possible in the four operating modes.
7.2.1 Why select single-pump operation
Select single-pump operation
• when the twin-head pump is to be controlled or
TM00 5546 4596TM04 4629 1809
monitored by a Grundfos pump management system.
• in all other situations where the master and slave pumps are to operate independently of each other as two single-head pumps.
7.2.2 R100 remote control
Single-pump operation is to be selected with the R100. See section 8.6.6 Twin-head pump.
7.2.3 Operation in parallel
In single-head operation mode, the pumps must never run at the same time, unless the pump is controlled by a Grundfos pump management system.
7.2.4 Setting the slave pump
When single-pump operation mode has been selected, the slave pump settings will correspond to the settings of the last working pump.
10
7.3 Selection of control mode
Systems with specified control mode
If the pump control mode (proportional or constant pressure) and head have been specified for the system in which the pump is to be installed, set the pump as specified. See section 8. Setting the pump. If problems should arise, see section 9. Fault finding.
Systems with no specified control mode
If the pump control mode and head have not been specified for the system (for instance, an uncontrolled standard pump is replaced by the UPE pump), it is advisable to use the settings in the table below and in section 7.3.1 Setting in connection with pump replacement.
English (GB)
System type Description
1. Relatively great head losses in the boiler circuit and the distribution pipes.
2. Relatively small head losses in the boiler circuit and the distribution pipes.
a) Two-pipe
heating systems with thermostatic valves and with
b) Underfloor heating systems and one-pipe heating
systems with thermostatic valves and great head losses in the boiler circuit.
c) Primary circuit pumps in systems with great head
losses in the primary circuit.
a) Two-pipe
heating systems with thermostatic valves and with
b) Underfloor heating systems with thermostatic valves.
c) One-pipe heating systems with thermostatic valves or
pipe balancing valves.
d) Primary circuit pumps in systems with small head
losses in the primary circuit.
• a dimensioned pump head higher than 4metres,
• very long distribution pipes,
• strongly throttled pipe balancing valves,
• differential pressure regulators,
• great head losses in those parts of the system through with the total quantity of water flows (for example boiler, heat exchanger and distribution pipe up to the first branching) or
• low differential temperature.
• a dimensioned pump head lower than 2metres,
• dimensioned for natural circulation,
• small head losses in those parts of the system through with the total quantity of water flows (for example boiler, heat exchanger and distribution pipe up to the first branching) or
• modified to a high differential temperature (for example district heating).
Select this control mode
Proportional pressure
Constant pressure
11
7.3.1 Setting in connection with pump replacement
Q
H
Max.
Min.
Q
H
Max.
Min.
English (GB)
If an uncontrolled pump is to be replaced with a UPE(D) FZ pump, settings can be made according to the tables below.
Existing pump at maximum speed Existing pump at reduced speed
Existing
pump
Maximum
head
[m]
Setting of
head
UPE(D) FZ
Setting of control
[m]
3 2 Constant pressure 3 1.5 Constant pressure
4 2 Constant pressure 4 1.5 Constant pressure
5 2.5 Proportional pressure 5 2 Constant pressure
6 3 Proportional pressure 6 2 Constant pressure
7 3.5 Proportional pressure 7 2.5 Proportional pressure
8 4 Proportional pressure 8 3 Proportional pressure
9 4.5 Proportional pressure 9 3.5 Proportional pressure
10 5 Proportional pressure 10 3.5 Proportional pressure
11 5.5 Proportional pressure 11 4 Proportional pressure
12 6 Proportional pressure 12 4 Proportional pressure
Read the tables as follows:
• If the maximum head of the existing pump is 6 metres and the pump is running at maximum speed under normal operating conditions, it is recommended to set the pump to 3 metres and to select proportional pressure.
• If, however, the existing pump is running at a reduced speed, it is recommended to set the pump to 2 metres and to select constant pressure.
7.4 Max. or min. curve duty
To be set on the control panel, with the R100 or a building management system via bus. It is not possible to set max. curve duty via the external input.
The pump can be set to operate according to the max. or min. curve, like an uncontrolled pump. See fig. 10.
mode
Existing
pump
Maximum
head
[m]
Setting of
head
[m]
UPE(D) FZ
Setting of control
mode
The max. curve mode can be selected if an uncontrolled pump is required. See section
8.2 Control panel. In this operating mode, the pump will operate independently of an external controller, if installed.
The min. curve mode can be used in periods in which a minimum flow is required. This operating mode is for instance suitable for night-time duty.
7.5 Constant-curve duty
To be set with the R100. The pump can be set to operate according to a
constant curve, like an uncontrolled pump. Select one of the curves between the max. and min. curves. See fig. 11.
TM00 5548 4596
Fig. 11 Constant-curve duty
Fig. 10 Max. and min. curves
12
TM00 5547 4596
7.6 Temperature influence
30%
100%
80
50
20
H
H
Q
t [°C]
H
actual
T
actual
100 %
Note
30 %
To be set with the R100. When temperature influence is activated in
proportional- or constant-pressure control mode, the setpoint for head will be reduced according to the liquid temperature. It is possible to set temperature influence to function at liquid temperatures below 80 °C or below 50 °C. These temperature limits are called T the head set (= 100 %) according to the characteristics below.
Fig. 12 Temperature influence
In the above example, T selected. The actual liquid temperature T causes the setpoint for head to be reduced from 100 % to H
The temperature influence function requires:
• Proportional- or constant-pressure control mode.
• The pump must be installed in the flow pipe.
• System with flow-pipe temperature control, for
Temperature influence is suitable in
• systems with variable flows (for example
• systems with almost constant flows (for example
Selection of T
In systems with a flow-pipe temperature of
• up to and including 55 °C, select T
• above 55 °C, select T
. The setpoint is reduced in relation to
max.
= 80 °C has been
actual
max.
.
actual
example according to outdoor temperature.
two-pipe heating systems) in which the activation of the temperature influence function will ensure a further reduction of the pump performance in periods with small heating demands and consequently a reduced flow-pipe temperature.
one-pipe heating systems and underfloor heating systems) in which variable heating demands cannot be registered as changes in the head as is the case with two-pipe heating systems. In such systems, the pump performance can only be adjusted by activating the temperature influence function.
max.
= 50 °C.
max.
= 80 °C.
max.
7.7 Indicator lights
The two indicator lights are used for fault and operating indication.
For position on pump (fig. 14), see section
8.2 Control panel.
When the R100 remote control communicates with the pump, the red indicator light will flash rapidly.
Functions of indicator lights
Indicator lights
Fault (red)
Operation
(green)
Off Off
TM01 0626 1797
Off
Permanently onThe pump is
Off Flashing
Permanently
on
Permanently onPermanently
Permanently
on
Flashing
See also section 9. Fault finding.
Off
on
Description
The power supply has been switched off.
operating.
The pump has been set to stop.
The pump has stopped due to a fault. Restarting will be attempted. It may be necessary to restart the pump manually by resetting the fault indication.
The pump is operating, but it has been stopped due to a fault. Note: If there is no differential-pressure or temperature sensor signal, the pump will continue operating according to the max. curve.
The pump has been set to stop, but it has been stopped due to a fault.
English (GB)
13
7.8 External fault indication
78787878787
8
Note
89107654321
mVH
U
0
Min. curve
1
2
English (GB)
The pump incorporates a signal output for a potential-free fault signal via terminals 7 and 8.
Functions of signal output
Signal output
Description
The power supply has been switched off.
The pump is operating.
The pump has been set to stop.
The pump has stopped due to a fault. Restarting will be attempted. It may be necessary to restart the pump manually by resetting the fault indication.
The pump is operating, but it has been stopped due to a fault. Note: If there is no differential-pressure or temperature sensor signal, the pump will continue operating according to the max. curve.
The pump has been set to stop, but it has been stopped due to a fault.
The fault signal output is activated when the pump registers a fault. The fault signal relay is activated together with the red indicator light on the pump.
Resetting of fault indications
A fault indication can be reset in one of the following ways:
• Briefly press or on the pump. This will not influence the pump performance set.
• Briefly switch off the power supply to the pump.
• With the R100. See section 8.3 R100.
The fault indication cannot be reset until the cause of the fault has disappeared.
7.9 External analog 0-10 V controller
The pump has an input for an external 0-10 VDC analog signal transmitter (terminals 5 and 6). Via this input, the pump can be controlled by an external controller if the pump has been set to this control mode:
Constant curve.
The external analog signal will set the pump curve within the range from the min. curve to the constant curve selected according to the characteristic in fig. 13.
At an input voltage lower than 0.5 V, the pump will operate according to the min. curve. The setpoint cannot be changed. The setpoint can only be changed when the input voltage is higher than 0.5 V.
Fig. 13 Constant curve
Pos. Description
1 Maximum head/constant curve
2 Head set/constant curve
The min. curve input, terminals 3 and 4, must be short-circuited.
TM03 1648 2505
14
7.10 External forced co ntro l
Q
H
Q
H
Q
H
Q
H
Note
The pump incorporates inputs for external signals for the forced-control functions:
• start/stop of pump (terminals 1 and 2)
• min. curve duty (terminals 3 and 4).
During forced control, the light fields or indicator lights on the pump will show which function is active.
Functional diagram: Start/stop input
Start/stop
Normal duty
Stop
Functional diagram: Min. curve input
The min. curve input is only active if the start/stop input is short-circuited.
Min. curve
Normal duty
Min. curve
(night-time duty)
7.11 Deactivating the control panel
To be set with the R100. The buttons on the pump control panel can be
deactivated to prevent unauthorised persons from operating the pump.
7.12 Bus communication
The pump has a serial communication port which enables communication with the Grundfos Control MPC Series 2000, a CIM/CIU communication interface, a building management system or another type of external control system.
If a CIU unit is installed in the system, it is possible to establish communication between the pump and a main network via one of the following protocols:
•LON
• Profibus DP
• Modbus RTU
• BACnet MS/TP. For further details, see the installation and operating
instructions for the CIM and CIU. Via the bus signal, it is possible to remote-set pump
operating parameters, such as desired head, temperature influence and operating mode. At the same time, the pump can provide status information about important parameters, such as actual head, actual flow, power input and fault indications.
When the pump is controlled via a bus signal, the number of settings available on the pump control panel or via the R100 will be reduced.
The pump head and control mode can only be set via the bus signal. The pump control panel or the R100 can only set the pump to max. curve and to stop. However, an R100 is required if a number is to be allocated to the pump. See sections 8.6.5 Pump number and 8.7 Priority of settings.
7.13 Remote control
The pump is designed for wireless communication with the Grundfos R100 remote control. The R100 communicates with the pump via infrared light.
During communication, the R100 must be pointed at the pump control panel. When the R100 is communicating with the pump, the red indicator light will flash rapidly.
The R100 offers additional setting options and status displays for the pump. See section 8.3 R100.
English (GB)
15
8. Setting the pump
Buttons
Indicator lights
Light fields
English (GB)
For the setting of the pump, use
• control panel
• R100 remote control
• bus communication (not described in detail in these instructions. Contact Grundfos).
The table below shows the application of the individual operating units and in which section the function has been described.
Function
8.2 Control panel
Warning At high liquid temperatures, the pump
may be so hot that only the buttons should be touched to avoid burns.
The control panel (fig. 14) incorporates
• buttons for setting, and .
• light fields, yellow, for indication of control mode and pump head.
• indicator lights, green and red, for operating and fault indication. See section 7.7 Indicator l ights.
Control panel
Proportional-pressure control
Constant-pressure control 8.2.1 8.6.1 Setting of pump head 8.2.2 8.4.1 Max. curve duty 8.2.3 8.4.2 Min. curve duty 8.2.4 8.4.2 Constant-curve duty - 8.4.2 Temperature influence - 8.6.3
Resetting of fault indications
Activation/deactivation of pump buttons
Allocation of pump number - 8.6.5
Reading of various data ­Start/stop 8.2.5 8.4.2
"-" = not available with this operating unit.
8.2.1 8.6.1
8.2.6 8.4.3
- 8.6.4
8.5.1 -
8.5.7
8.1 Factory settings
Control mode
Head
Control of twin-head pump
UPE(D) 80-120 FZ
Proportional pressure
6 m at max. flow. See fig. 14.
Alternating operation
UPE 100-120 FZ
Proportional pressure
6 m at max. flow. See fig. 14.
-
R100
Fig. 14 Control panel
8.2.1 Control mode setting
Description of function, see section 7.1 Control modes.
When and are pressed simultaneously, the light fields will indicate the selected control mode:
Light fields Control mode
Top + bottom light
fields flashing
Middle light fields
flashing
None of the light
fields are on
If the buttons are pressed for more than 5 sec., the control mode will change over to constant pressure and proportional pressure respectively. This means that constant-curve duty is deactivated if selected with the R100.
Proportional pressure
Constant pressure
Constant curve
TM04 4693 1809
16
8.2.2 Setting of pump head
H m
Q
0
12
H m
QQ
0
12
The desired pump head is set by pressing or . The light fields on the control panel will indicate the
head set. The scaling is set to be approx. 1.2 metres per light
field. The table below shows examples of pump head
settings indicated by the light fields.
Constant-pressure control Proportional-pressure control
UPE 100-120 FZ
UPE(D) 80-120 FZ
Light fields 5 and 6 are activated, indicating a desired head of approx. 6.5 metres.
TM04 5871 4209
Light fields 5 and 6 are activated, indicating a desired head of approx. 6.5 metres.
English (GB)
TM04 5870 4209
17
8.2.3 Setting to max. curve duty
H m
Q
0
2
4
6
8
10
12
1
H m
Q
0
2
4
6
8
10
12
1
English (GB)
Description of function, see section 7.4 Max. or min. curve duty.
Press continuously to change over to the max. curve of the pump (top light field flashes). See fig. 15. To change back, press continuously until the desired head is indicated.
Fig. 15 Max. curve duty
8.2.4 Setting to min. curve duty
Description of function, see section 7.4 Max. or min. curve duty.
Press continuously to change over to the min. curve of the pump (bottom light field flashes). See fig. 16. To change back, press continuously until the desired head is indicated.
8.2.5 Start/stop of pump
Stop the pump by continuously pressing until none of the light fields are activated. When the pump is stopped, the green indicator light will be flashing.
Start the pump by continuously pressing until the desired head is indicated.
If the pump is to be inoperative for a period, it is recommended to use the start/stop input, the R100 or to switch off the power supply. In this way, the pump head setting will remain unchanged when the pump is to be started again.
8.2.6 Resetting of fault indications
To reset fault indications, briefly press or . This will not influence the pump performance set.
If the fault has not disappeared, the fault indication will reappear.
8.3 R100
TM04 4695 1909TM04 4696 1909
The pump is designed for wireless communication with the Grundfos R100 remote control. The R100 communicates with the pump via infrared light.
During communication, the R100 must be pointed at the pump control panel. When the R100 is communicating with the pump, the red indicator light will flash rapidly.
The R100 offers additional setting options and status displays for the pump.
The R100 displays are divided into four parallel menus. See fig. 17:
0. GENERAL, see operating instructions for the
R100
1. OPERATION
2. STATUS
3. INSTALLATION
The number stated at each individual display in fig. 17 refers to the section in which the display is described.
Fig. 16 Min. curve duty
18
0. GENERAL 1. OPERATION 2. STATUS 3. INSTALLATION
8.4.1 8.5.1 8.6.1
8.4.2 8.5.2 8.6.2
8.4.3 8.5.3 8.6.3
8.5.4 8.6.4
8.5.5 8.6.5
English (GB)
Fig. 17 Menu overview
8.5.6 8.6.6
8.5.7
19
8.4 Menu OPERATION
Note
English (GB)
When the communication between the R100 and the pump has been established, "Contact with" appears in the display. When the "arrow down" on the R100 is pressed, the OPERATION menu appears.
The display "Contact with" appears only once, i.e. when the R100 gets contact with the pump.
8.4.1 Setpoint
This display depends on the control mode selected in the display "Control mode" in the INSTALLATION menu.
If the pump is remote- or forced-controlled via external signals, the number of possible settings will be reduced. See section 8.7 Priority of settings. Attempts to change the settings will result in an indication in the display saying that the pump is remote-controlled and that changes therefore cannot be made.
The following example of display will appear if the pump is in proportional-pressure control mode.
Set the desired head. Furthermore, it is possible to select one of these
operating modes:
•Stop
• Min. (min. curve)
• Max. (max. curve). This display will be a little different in the case of
constant-pressure control or constant-curve duty. The actual duty point of the pump is indicated by
a square in the Q/H field. No indication at low flow.
8.4.2 Operating mode
8.4.3 Fault indications
If the pump is faulty, the cause will appear in this display.
Possible causes:
• Phase failure
• Pump blocked
• Undervoltage
• Defective pressure/temperature sensor
• Internal fault.
The fault indication can be reset in this display. If the fault cause has not disappeared when resetting is attempted, this will be indicated in the display.
8.5 Menu STATUS
The displays appearing in this menu are status displays only. It is not possible to change or set values.
The actual values in these displays are stated as a guide.
8.5.1 Actual setpoint
Field "Actual setpoint":
Actual setpoint of pump.
Field "corresponding to":
Actual setpoint in % of the setpoint set if the pump is connected to an external analog 0-10 V signal transmitter or if temperature influence or proportional-pressure control is activated.
8.5.2 Operating mode
Select an operating mode:
•Stop
• Min. (min. curve)
• Normal (proportional pressure, constant pressure or constant curve)
• Max. (max. curve).
20
This display shows the actual operating mode (Stop, Min., Normal or Max.) and where this was selected (Pump, R100, Bus or External).
8.5.3 Head and flow
Very low flows cannot be registered, and the R100 will show "<" in front of the lowest possible flow value of the pump in question.
8.5.4 Speed
The actual pump speed.
8.5.5 Liquid temperature
The actual temperature of the pumped liquid.
8.5.6 Power input and power consumption
This display does not apply to UPE(D) 80-120 FZ and UPE 100-120 FZ.
Actual power input and power consumption of the pump.
Power consumption is not calculated in UPE(D) 80-120 FZ and UPE 100-120 FZ.
8.5.7 Operating hours
8.6 Menu INSTALLATION
In this menu, the settings are chosen that should be considered when installing the pump.
8.6.1 Control mode
Description of function, see section 7.1 Control modes or 7.5 Constant-curve duty.
Select a control mode:
• Prop. pressure (proportional pressure),
• Const. pressure (constant pressure),
• Const. curve (constant curve). Setting of setpoint and curve is carried out in display
8.4.1 Setpoint in the OPERATION menu.
8.6.2 Min. curve
This display does not apply to UPE(D) 80-120 FZ and UPE 100-120 FZ.
Description of function, see section 7.4 Max. or min. curve duty.
In this display, it is possible to choose between two min. curves. The curve is used when the operating mode "Min. curve" is selected.
When controlling UPE(D) 80-120 FZ and UPE 100-120 FZ, only one min. curve is available.
8.6.3 Temperature influence
Description of function, see section 7.6 Temperature influence.
English (GB)
Number of operating hours of the pump. The value of operating hours is an accumulated
value and cannot be set to zero.
The temperature influence function can be activated in this display.
In the case of temperature influence, the pump must be installed in the flow pipe. It is possible to choose between maximum temperatures of 50 °C and 80 °C.
The temperature influence function will be active only in proportional- or constant-pressure control mode.
When the temperature influence is active, a small thermometer is shown in the display "Setpoint" in the OPERATION menu. See section 8.4.1 Setpoint.
21
English (GB)
Note
8.6.4 Buttons on pump
To prevent unauthorised persons from operating the pump, the function of the buttons and can be deactivated in this display. The buttons can be reactivated only with the R100.
The buttons can be set to:
•Active
•Not active.
8.6.5 Pump number
A number between 1 and 64 can be allocated to a pump or changed so that the R100 or a unit connected to the bus network can distinguish between two or more pumps.
The Grundfos Pump Management System 2000 can, however, only accept the numbers 1 to 8.
For further details, see the installation and operating instructions for the management system in question.
8.6.6 Twin-head pump
If the pump is controlled via bus, temperature influence cannot be set with the R100.
8.7 Priority of settings
The external forced-control signals will influence the settings available on the pump and with the R100. The pump can always be set to max. curve duty or to stop on the pump control panel or with the R100.
If two or more functions are activated at the same time, the pump will operate according to the function with the highest priority.
The priority of the settings is as shown in the tables below.
Without bus signal
Possible settings
Priority
1 Stop
2Max. curve
3 Stop
4 Min. curve Min. curve
5 Setting of head Setting of head
With bus signal
Priority
1 Stop
2 Max. curve
3 Stop Stop
4
5 Min. curve Min. curve
6
Pump control panel or R100
Possible settings
Pump
control
panel or
R100
External signals
External
signals
Bus
signal
Max.
curve
Setting of
head
This display can only be used in connection with twin-head pumps.
See also the document "Supplement to installation instructions".
22
9. Fault finding
Warning Before removing the control box cover, make sure that the power supply has been switched
off for at least 5 minutes. The pumped liquid may be scalding hot and under h igh pres sure. Before any remov al or
dismantling of the pump, the system must therefore be drained, or the isolating valves on either side of the pump must be closed.
See also section 7.7 Indicator lights.
Fault Cause Remedy
1. The pump is not running. None of the indicator lights are on.
2. The pump is not running. The green indicator light is flashing.
3. The pump has stopped due to a fault. The red indicator light is on, and the green indicator light is off.
4. The pump is operating, but has been stopped due to a fault. The red and green indicator lights are on.
5. The pump has been set to stop, but it has been stopped due to a fault. The red indicator light is on, and the green indicator light is flashing.
6. Noise in the system. The green indicator light is on.
7. Noise in the pump. The green indicator light is on.
a) One fuse in the installation is
blown.
b) The current-operated or
voltage-operated circuit breaker has tripped out.
c) The pump is defective. Repair or replace the pump.
The pump has been stopped in one of the following ways:
1. With the button.
2. With the R100.
3. External on/off switch in position off.*
4. Via bus signal.*
*The fault can be temporarily corrected by selecting max. curve duty on the
pump or with the R100 as external forced-control signals will be ignored.
a) Power supply failure
(for example undervoltage).
b) Pump blocked and/or impurities in
the pump.
c) Fault in electronics. Contact Grundfos.
a) The pressure and temperature
sensor is defective.
b) The pump has restarted
automatically after a temporary fault.
a) The pressure and temperature
sensor is defective.
b) The pump has restarted
automatically after a temporary fault.
a) Air in the system. Vent the system.
b) The flow is too high. Reduce the head (setpoint), and
c) The pressure is too high. Reduce the head (setpoint), and
a) Air in the pump. Vent the pump.
b) The inlet pressure is too low. Increase the inlet pressure, and/or
Replace the fuse.
Cut in the circuit breaker.
1. Start the pump by pressing .
2. Start the pump with the R100 or by pressing .
3. Switch on the on/off switch.*
4. Start the pump via bus signal.*
Check that the power supply falls within the specified range.
Remove the vent screw, turn the rotor with a screwdriver inserted into the slot in the shaft end, and/or dismantle and clean the pump.
Check sensor connection. Replace if necessary.
Reset the fault indication.
Check sensor connection. Replace, if necessary.
Reset the fault indication.
possibly change over to constant pressure.
possibly change over to proportional pressure.
check air volume in the expansion tank (if installed).
English (GB)
23
English (GB)
Note
Fault Cause Remedy
8. Insufficient heat in some places in the heating system.
The R100 can also be used for fault finding.
a) The flow is too low. Increase the head (setpoint) and/or
10. Megging
Megging of an installation incorporating an UPE pump is not allowed, as the built-in electronics may be damaged. If megging of the pump is necessary, the pump should be electrically separated from the installation.
Twin head pumps: The master and slave pumps must be megged separately.
Megging of the pump can be carried out as described below.
10.1 Megging of UPE pumps
See also section 5.2 Wiring diagram.
1. Switch off the power supply.
2. Remove the conductors from terminals L, N and earth (terminals 9, 10 and 11).
3. Short-circuit terminals L and N using a short wire.
4. Test between terminals L/N and earth. Maximum test voltage: 1000 VAC or 1500 VDC. Note: Never test between supply terminals (L and N).
Maximum permissible leakage current: <20mA.
5. Remove the short wire between terminals L and N.
6. Fit the supply wires to terminals L and N and the earth terminal.
7. Switch on the power supply.
10.2 High-voltage test
If it is necessary to high-voltage test the UPE pump, the megging instructions must be followed. See section 10. Megging.
change over to constant pressure.
24
11. Service kits
Warning Before starting work on the pump, make sure that the mains switch has been switched off.
It must be ensured that the power supply cannot be accidentally switched on.
The service kits can be ordered as required:
Service kit Pump type Product number
Pump head UPE(D) 80/100-120 FZ 97529251
Control box, complete UPE(D) 80/100-120 FZ 97529279
Sensor, complete UPE(D) 80/100-120 FZ 97529255
Connection cable UPED 80-120 FZ 97529293
Gasket kit UPE(D) 80/100-120 FZ 97529296
Fan UPE(D) 80/100-120 FZ 97564038
Air vent plug UPE(D) 80/100-120 FZ 97529299
Flap valve kit UPED 80-120 FZ 97822546
English (GB)
25
12. Technical data
Subject to alterations.
English (GB)
Supply voltage
1 x 230 V - 10 %/+ 6 %, 50/60 Hz.
Motor protection
The pump requires no external motor protection.
Enclosure class
IPX4D.
Relative air humidity
Maximum 95 %.
Ambient temperature
0 °C to +40 °C.
Temperature class
TF110 to EN 60335-2-51.
Liquid temperature
Maximum: +110 °C. Continuously: +2 °C to +95 °C.
Ambient temperature
[°C]
0 to 30 110
35 90
40 70
System pressure
The system pressure is indicated on the nameplate.
System pressure
Pump type
UPE(D) 80-120 FZ
UPE 100-120 FZ
Inlet pressure
The following minimum pressures must be available at the pump inlet during operation:
Pump type
UPE(D) 80-120 FZ
UPE 100-120 FZ
PN 6 PN 10 PN 16
[MPa] [MPa] [MPa]
0.6 4
0.6 4
[bar]/[M
Maximum liquid
temperature
1.0 1.6 8
1.0 1.6 8
Liquid temperature
75 °C 90 °C 110 °C
[bar]/[M
Pa]
0.6/
0.06
0.6/
0.06
Pa]
1.0/
0.1
1.0/
0.1
[°C]
Number of
bolt holes
[bar]/[M
Pa]
1.7/
0.17
1.7/
0.17
EMC (electromagnetic compatibility)
EN 61800-3. Electromagnetic disturbance, first environment (residential areas). Immunity to electromagnetic disturbance, second environment (industrial areas).
Sound pressure level
The sound pressure level of the pump is lower than 38 dB(A).
Leakage current
The pump mains filter will cause a discharge current to earth during operation. I
Inputs and outputs
Start/stop input External potential-free switch.
Min. curve input
Input for analog 0-10 V signal
Signal output
Bus input
Contact load: 5 V, 0.5 mA. Screened cable. Loop resistance: Maximum 130 Ω/km. Logical levels: Logical zero: U < 1.5 V. Logical one: U > 4.0 V.
External signal: 0-10 VDC. Maximum load: 1 mA. Screened cable.
Internal potential-free change-over contact. Maximum load: 250 V, 2 A, AC1. Minimum load: 5 V, 1 mA. Screened cable.
Grundfos bus protocol, GENIbus protocol, RS-485. Screened cable. Lead cross section:
0.25 - 1 mm Cable length: Maximum 1200 m.
leakage
< 3.5 mA.
2
.
13. Disposal
This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
26
Appendix 1
Appendix
UPE 80-120 FZ UPE 100-120 FZ
PN 6 PN 10 PN 16 PN 6 PN 10 PN 16
L1 360 360 360 450 450 450
L3 180 180 180 225 225 225 B1 131 131 131 135 135 135 B4 100 100 100 100 100 100 B5 131 131 131 135 135 135 B7 115 115 115 115 115 115 H1 98 98 98 120 120 120 H2 402 402 402 410 410 410 H3 500 500 500 530 530 530 D1 80 80 80 100 100 100 D2 128 128 128 160 160 160 D3 150/160 160 160 170 180 180 D4 200 200 200 220 220 220 D5 4 x 18 8 x 18 8 x 18 4 x 18 8 x 18 8 x 18
M 2 x M12 2 x M12 2 x M12 2 x M12 2 x M12 2 x M12
TM04 5955 1011
52
UPED 80-120 FZ
PN 6 PN 10 PN 16
L1 360 360 360
L2 150 150 150
L3 85 85 85 B2 125 125 125 B3 476 476 476 B4 235 235 235 B5 241 241 241 B6 120 120 120 B7 240 240 240 H1 98 98 98 H2 402 402 402 H3 500 500 500 D1 80 80 80 D2 128 128 128 D3 150 160 160 D4 200 200 200 D5 4 x 18 8 x 18 8 x 18
M 4 x M14 4 x M14 4 x M14
Appendix
TM04 5956 1011
53
Appendix
Fig. 1 Possible pump positions and flow directions
54
TM04 6038 4709 - TM04 6039 4709 - TM04 6040 4709 - TM04 6041 4709 - TM04 6042 4709 - TM04 6043 4709 - TM04 6044 4709 - TM04 6045 4709
Argentina
Grundfos companies
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Lote 34A 1619 - Garin Pcia. de Buenos Aires Phone: +54-3327 414 444 Telefax: +54-3327 411 111
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belorussia
Представительство ГРУНДФОС в Минске 220123, Минск, ул. В. Хоружей, 22, оф. 1105 Тел.: +(37517) 233 97 65, Факс: +(37517) 233 97 69
E-mail: grundfos_minsk@mail.ru
Bosnia/Herzegovina
GRUNDFOS Sarajevo Trg Heroja 16, BiH-71000 Sarajevo Phone: +387 33 713 290 Telefax: +387 33 659 079 e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 50/F Maxdo Center No. 8 XingYi Rd. Hongqiao development Zone Shanghai 200336 PRC Phone: +86-021-612 252 22 Telefax: +86-021-612 253 33
Croatia
GRUNDFOS CROATIA d.o.o. Cebini 37, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.grundfos.hr
Czech Republic
GRUNDFOS s.r.o. Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111 Telefax: +420-585-716 299
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Mestarintie 11 FIN-01730 Vantaa Phone: +358-3066 5650 Telefax: +358-3066 56550
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Park u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Lim­ited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800
Indonesia
PT GRUNDFOS Pompa Jl. Rawa Sumur III, Blok III / CC-1 Kawasan Industri, Pulogadung Jakarta 13930 Phone: +62-21-460 6909 Telefax: +62-21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. Gotanda Metalion Bldg., 5F, 5-21-15, Higashi-gotanda Shiagawa-ku, Tokyo 141-0022 Japan Phone: +81 35 448 1391 Telefax: +81 35 448 9619
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
México
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Veluwezoom 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
România
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундф ос Россия, 109544 Москва, ул. Школьная
39
Тел. (+7) 495 737 30 00, 564 88 00 Факс (+7) 495 737 75 36, 564 88 11
E-mail grundfos.moscow@grundfos.com
Serbia
GRUNDFOS Predstavništvo Beograd Dr. Milutina Ivkovića 2a/29 YU-11000 Beograd Phone: +381 11 26 47 877 / 11 26 47 496 Telefax: +381 11 26 48 340
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 24 Tuas West Road Jurong Town Singapore 638381 Phone: +65-6865 1222 Telefax: +65-6861 8402
Slovenia
GRUNDFOS d.o.o. Šlandrova 8b, SI-1231 Ljubljana-Črnuče Phone: +386 1 568 0610 Telefax: +386 1 568 0619 E-mail: slovenia@grundfos.si
South Africa
Corner Mountjoy and George Allen Roads Wilbart Ext. 2 Bedfordview 2008 Phone: (+27) 11 579 4800 Fax: (+27) 11 455 6066 E-mail: lsmart@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46(0)771-32 23 00 Telefax: +46(0)31-331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-1-806 8111 Telefax: +41-1-806 8115
Taiwan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
ТОВ ГРУНДФОС УКРАЇНА 01010 Київ, Вул. Московська 8б,
Тел.:(+38 044) 390 40 50 Фах.: (+38 044) 390 40 59
E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971-4- 8815 166 Telefax: +971-4-8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 8TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Usbekistan
Представительство ГРУНДФОС в Ташкенте 700000 Ташкент ул.Ус мана Носира 1-й тупик 5 Телефон : (3712) 55-68-15 Факс: (3712) 53-36-35
Addresses revised 29.09. 2010
Grundfos companies
Addresses revised 29.09.2010
Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence
97525626 0411
Repl. 97525626 0410
ECM: 1074518
The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.
www.grundfos.com
Loading...