Grundfos UP Series 200, UP 43-110, UP 43-70, UP 53-46, UP 53-45 Installation And Operating Instructions Manual

GRUNDFOS INSTRUCTIONS
UP Series 200
Installation and operating instructions
In-line, wet-rotor, single-speed, circulator pumps UP 43-70, UP 43-110, UP 53-45, UP 53-46
3
UP Series 200
English (US)
Installation and operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Español (MX)
Instrucciones de instalación y operación . . . . . . . . . . . . . . . . . . . . . . . . 16
Français (CA)
Notice d'installation et de fonctionnement . . . . . . . . . . . . . . . . . . . . . . . 28
4
English (US)
English (US) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
Page
1. Limited warranty
Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions.
To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.
1. Limited warranty
4
2. Introduction
5
2.1 Safety warning
5
2.2 Electrical work
5
3. Pre-installation checklist
5
3.1 Confirm you have the correct pump
5
3.2 Check the condition of the pump
5
3.3 Verify electrical requirements
5
3.4 Pumped liquid requirements
6
4. Installation procedures
6
4.1 Electrical preparation
6
4.2 Piping considerations
7
4.3 Connect the pump
7
4.4 Electrical connection
8
5. Starting the pump
9
5.1 Vent the piping system
9
5.2 Voltage selection
9
6. Troubleshooting
10
6.1 Fault finding chart
10
6.2 Preliminary checks
11
6.3 Current measurement
11
6.4 Insulation resistance (lead-to-ground)
12
6.5 Winding resistance (line-to-line)
12
6.6 Winding resistance chart
13
7. Replacing components
14
7.1 Removing the pump head
14
7.2 Fitting the pump head
14
7.3 Replacing the terminal box or capacitor
15
8. Disposal
15
Warning Prior to installation, read these
installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
This booklet should be left with the owner of the pump for future reference and information regarding its operatio n.
5
English (US)
2. Introduction
2.1 Safety warning
2.1.1 Read this booklet
This booklet is designed to help a certified installer install, begin operation of and troubleshoot the Grundfos UP Series 200 pumps. The booklet should be left with the owner of the pump for future reference and information regarding its operation. Should the owner experience any problems with the pump, a certified professional should be contacted.
2.2 Electrical work
All electrical work should be performed by a qualified electrician in accordance with the latest edition of the National Electrical Code, local codes and regulations.
3. Pre-installation checklist
3.1 Confirm you have the correct pump
Read the pump nameplate to make sure it is the one you ordered.
Compare the pump's nameplate data and its performance curve (for head, GPM, etc.) with the application in which you plan to install it.
Will the pump do what you expect it to do?
3.2 Check the condition of the pump
The shipping carton your pump came in is specially designed around your pump during production to prevent damage.
As a precaution, it should remain in the carton until you are ready to install it. At that point, look at the pump and examine it for any damage that may have occurred during shipping.
Examine any other parts of the shipment as well for any visible damage.
3.3 Verify electrical requirements
Verification of the power supply should be made to be certain the voltage, phase and frequency match that of the pump motor. The proper operating voltage and other electrical information can be found on the pump nameplate.
These motors are designed to run on ± 10 % of the rated voltage.
Wiring diagrams can be found inside the terminal box cover and later in these installation and operating instructions. If voltage variations are larger than ± 10 %, do not operate the pump.
Warning A faulty motor or wiring can cause
electric shock that could be fatal, whether touched directly or conducted through standing water. For this reason, proper grou nding of the pump to the power supply's grounding terminal is required for safe installation and operation.
In all installations, the above­ground metal plumbing should be connected to the power supply ground as described in Article 250-80 of the National Electrical Code.
6
English (US)
3.4 Pumped liquid requirements
The pump can be used to circulate the following liquids:
potable hot water
water for hydronic heating
water/glycol mixtures up to 50/50
cooling water. In domestic hot-water systems it is advisable to
use bronze pumps (UP Series 200 or UPS model) only for water with a degree of hardness lower than 14 grains per gallon of hardness. For water with a higher degree of hardness, a direct­coupled TP pump is recommended. If the pump is installed in a heating system, the water should meet the requirements of accepted standards on water quality in heating systems.
In water/glycol mixtures, in order to prevent the glycol from degrading, temperatures above those for which the liquid is rated should be avoided and time spent at high temperatures minimized.
It is also important that the system is cleaned and flushed prior to the installation of the glycol mixture.
In order to avoid problems with corrosion or precipitation, the glycol liquids should be checked and maintained regularly. If further dilution of the supplied glycol is required, follow the requirements of the supplier of the glycol.
DEXCOOL
®
is a registered trademark of General Motors Corporation, used under license by Texaco Lubricants NA.
The pump is lubricated and cooled by the pumped liquid. Therefore, the pumped liquid must always be allowed to circulate through the pump. Extended periods without circulation will cause premature wear to the bearings and excessive motor heat. The pumped liqui d must also meet the following requirements:
Minimum inlet pressure (during operation)
Liquid temperature range
Continuously: 14 °F (-10 °C) up to 230 °F (110 °C).
Intermittent: < 284 °F (140 °C) for short periods of time.
Domestic hot water: < 140 °F (60 °C).
4. Installation procedures
4.1 Electrical preparation
Terminal box position
At the bottom of the stator, closest to the pump housing, there are eight drain holes to allow condensed water to escape. The drain holes must not be blocked. The drain holes must point downwards. The terminal box must therefore point upwards in one of the positions shown in fig. 1. The following terminal box positions apply whether the piping is mounted vertically or horizontally.
Fig. 1 Possible terminal box positions
Caution
The UP Series 200 pump is intended for use with water only.
Caution
Glycol with the trade name DEXCOOL
®
can damage the pump.
UP
model
At these liquid temperatures
167 °F/
75 °C
194 °F/
90 °C
230 °F/
110 °C
[psi] hf [psi] hf [psi] hf
UP
43-70
0.7 1.6 4.8 11.0 15.4 35.6
UP
43-110
3.6 8.3 8.2 18.9 18.9 43.7
UP
53-45
2.9 6.7 7.5 17.3 18.1 41.6
UP
53-46
1.1 2.5 5.8 13.3 16.4 37.7
Warning Never make any connections in the
pump terminal box unless the power supply has been switched off.
TM03 7296 4706