Grundfos UNILIFT KP 150, UNILIFT KP 250, UNILIFT KP 350, UNILIFT CC 7, UNILIFT CC 5 Installation And Operating Instructions Manual

...
UNOLIFT, DUOLIFT
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
English (GB) Installation and operating instructions

English (GB)

Original installation and operating instructions
These installation and operating instructions describe Grundfos Unolift and Duolift lifting stations. They apply to the tank and installation kits. For detailed information on installing and operating the pumps and controller, see the installation and operating instructions supplied with these products.
Sections 1-4 give the information necessary to be able to unpack, install and start up the product in a safe way.
Sections 5-12 give important information about the product, as well as information on service, fault finding and disposal of the product.
CONTENTS
Page
1. General information
1.1 Symbols used in this document
1.2 Symbols on the product
2. Receiving the product
2.1 Transporting the product
2.2 Inspecting the product
2.3 Scope of delivery
3. Installing the product
3.1 General guidelines
3.2 Mechanical installation
3.3 Tools
3.4 Installation overview
3.5 Positioning the product
3.6 Installing the tank
3.7 Drilling holes for the pipes
3.8 Fitting the cable glands
3.9 Fitting the vent port
3.10 Connecting the vent pipe
3.11 Connecting the inlet pipes
3.12 Installing the pump
3.13 Installing the pump connecting pipes
3.14 Installing the level sensor tube
3.15 Installing an alarm float switch
3.16 Installing the outlet pipes
3.17 Installing a diaphragm pump
3.18 Installing the controller
3.19 Electrical connection
3.20 Setting the controller before startup
4. Starting up the product
4.1 Starting up a product with a controller
4.2 Starting up a product without a controller
5. Storing the product
6. Product introduction
6.1 Product overview
6.2 Applications
6.3 Pumped liquids
6.4 Automatic operation
6.5 Identification
6.6 Diaphragm pump
6.7 Level sensor tube
7. Operating the product
7.1 Setting the start levels
8. Starting up the product after standstill
9. Servicing the product
10. Taking the product out of operation
11. Technical data
11.1 Operating conditions
11.2 Material
11.3 Electrical data
11.4 Dimensions and weights
12. Fault finding the product
13. Disposing of the product
2
2 2
3
3

1. General information

3 3

1.1 Symbols used in this document

5
5 6 7 7 7 7 7 8 8 8 8
9 10 12 12

1.2 Symbols on the product

12 14 14 14 14
15
15 15
15
15
15 16 16 16 16 16
Read this document before installing the product. Installation and operation must comply with local regulations and accepted codes of good practice.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
European conformity
16
17
17
19
19
20
20
20 20 20 20
21
21
2

2. Receiving the product

Caution

2.1 Transporting the product

WARNING
Falling objects
Death or serious personal injury
- Secure the product during transportation to prevent it from tilting or falling down.
CAUTION
Back injury
Minor or moderate personal injury
- Get assistance from another person or use lifting equipment to carry the product.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.

2.2 Inspecting the product

1. Check that the product is as ordered.
2. Check that no visible parts have been damaged.
3. If parts are damaged or missing, contact your local Grundfos sales company and refer to the product numbers in section 2.3 Scope of delivery.

2.3 Scope of delivery

The scope of delivery depends on your order. Pumps, tank and pipes are supplied separately and must be assembled.
If used for a liquid which is injurious to health or toxic, the pump will be classified as contaminated.
Before the pump is returned to Grundfos for service, the safety declaration at the end of these instructions must be filled in by authorised personnel and attached to the pump in a visible position.
If Grundfos is requested to service the pump, it must be cleaned before it is returned.
If proper cleaning is not possible, all relevant information about the pumped liquid must be provided.
If the above is not fulfilled, Grundfos can refuse to accept the pump for service.
Possible costs of returning the pump are to be paid by the customer.
The safety declaration can be found at the end of these instructions (only in English).
2.3.1 Description of kits
Tank
Designation
Tank 1 1
Cover with gasket 1 2
Screw, M8 x 30 12 24
Washer 12 24
Fastening bracket for level sensor tube
Screw for fixing the tank 4 4
Expansion anchor for fixing the tank
Socket seal, DN 40 1 1
Socket seal, DN 100 1 1
Quantity
270 litres 540 litres
22
44
English (GB)
3
English (GB)
Pump connecting pipes
Designation
KP/
CC
Quantity
SEG APB
Pump connecting pipes
Designation
KP/
CC
Quantity
SEG APB
Adapter, Rp 2 - R 1 1/2
Double nipple, R 2 - R 2
Nut, PVC, 2" 1 1 1
O-ring, 60, EPDM
Adapter 2 2 2
Stainless-steel clamp
Flexible connecting tube, 50
Elbow, 90 ° - 1 1
Flange, 50 - 1 -
Screw for flange
Washer for flange
11-
111
--1
222
111
-4-
-8-
Nut, M16, for flange
O-ring, 50, for flange
Unilift KP: Double nipple
Unilift CC: Adapter 1 1/2" - 1 1/4"
Unilift KP: Non-return flap valve
Thread tape 1 1 1
Vent port
Socket, PVC, 75 x 63 x 2"
Gasket, EPDM, 63
Nut, PVC, 2" 1 1 1
Other components
Schuko plug 1 - 1
Cable gland, M20
Cable gland, M25
* The kit for pump connecting pipes contains a
non-return valve for the Unilift KP pump. The Unilift CC pump is supplied with a non-return valve.
-4-
-1-
1--
1--
1*
111
111
212
-1-
4
Accessories
We recommend the following accessories.
Outlet pipe
Quantity
Designation
Non­return valve
Double nipple
Isolating valve
Union nut - - 2 2
T-piece, PVC, 90 °
Elbow, PVC, 90 °
Pipe, 50, 2 m
Unolift Duolift
CC/KPAPB/
-* 1 -* 2
-135
1111
--11
--22
--11
SEG
CC/KPAPB/
SEG

3. Installing the product

3.1 General guidelines

The guidelines for correct mechanical installation of lifting station are according to EN 12056-4.
• If the lifting station is installed in a basement with recurrent penetration of groundwater, we recommend that you install a drainage pump in a separate pump sump below floor level. In some countries the drainage pump is mandatory. If there is only a risk of penetrating groundwater, we recommend that you install a float switch outside the lifting station and connect it to a controller which indicates high-level alarm in case of flooding.
• Fix the tank to the floor.
• We recommend that you connect a diaphragm pump to the tank to be able to empty the tank manually.
• All outlet pipes from the lifting station, diaphragm pump and drainage pump must have a backflow loop, i.e. a bend above the local backflow level. Commonly, the highest point of the bend must be above street level. See fig. 2.
• Surface water must not be discharged into the lifting station inside the building. Collect and discharge surface water outside the building.
• Install a non-return valve at the outlet of the lifting station to prevent backflow.
• Fit isolating valves at the inlet and outlet of the lifting station.
• The volume of the outlet pipe above the non­return valve up to the backflow loop must be smaller than the effective tank volume. See pos. 7 in figures 1 and 2.
• In general, a lifting station for black wastewater must be vented above roof level. However, it is permitted to lead the vent pipe into the main building ventilation system. Place special two­way venting valves outside the building.
• If the wastewater is discharged into a collecting line, the collecting line must have a filling ratio of at least h/d = 0.7. The collecting line must be at least one nominal diameter bigger after the outlet pipe connection.
• Use 45 ° bends to avoid deposits in the pipes.
English (GB)
Thread tape
* The Unilift CC pump is supplied with a non-return
valve.
1111
5

3.2 Mechanical installation

6
2
3
4
5
1
7
16
3
4
5
7
English (GB)
3.2.1 Tank inlets
We recommend that you connect the inlet pipes to the top inlets of the tank. This prevents backflow and deposits in the inlet pipe, and enables a high start level of the pump. A high start level increases the effective tank volume and reduces the number of start/stops of the pumps.
Fig. 1 Installation example with a tank in a sump and with a controller. The diaphragm pump is not
shown.
3.2.2 Location
Install the lifting station in a properly lit and vented room with 60 cm free space around all parts to be serviced and operated.
The tank must not be exposed to direct sunlight. UV light can affect the properties of its composite material, resulting in a shorter life.
The product is designed for indoor operation. If installed outside, the lifting station must be placed in a closed pit.
The tank can be flooded and may be installed in a basement with risk of penetrating groundwater.
Pos. Designation
1 Isolating valve, inlet
2 Controller
3 Drainage pump
4
5 Isolating valve, outlet
6 Vent pipe
7 Backflow loop
TM06 5789 0216
Non-return valve, outlet
Pos. Designation
1 Isolating valve, inlet
3 Drainage pump
Non-return valve,
4
outlet
5 Isolating valve, outlet
Fig. 2 Installation example with a tank on the basement floor. The diaphragm pump is not shown.
6 Vent pipe
7 Backflow loop
TM06 5790 0216
6

3.3 Tools

• Thread tape
•glue. Not supplied with the product:
• drilling machine
• drilling bits: ∅20, ∅25
• hole saw: ∅40, ∅100
• deburring tool for polyethylene.

3.4 Installation overview

Depending on your product type, you must go through different steps to install your lifting station. You may need to go through additional steps if you have ordered accessories.
Lifting station with pumps with float switches
1. Fix the tank to the floor.
2. Drill holes for the inlet pipes.
3. Connect the inlet pipes to the tank.
4. Fit the vent port and the cable glands.
5. Set the start levels by adjusting the cable length of the float switch.
6. Install the pumps in the tank.
7. Fit the pump connecting pipes.
8. Connect the vent pipe.
9. Connect the outlet pipes.
Lifting station with controller
1. Fix the tank to the floor.
2. Drill holes for the inlet pipes.
3. Connect the inlet pipes to the tank.
4. Fit the vent port and the cable glands.
5. Install the pumps in the tank.
6. Fit the level sensor tube in the tank.
7. Fit the pump connecting pipes.
8. Connect the vent pipe.
9. Connect the outlet pipes.

3.5 Positioning the product

CAUTION
Back injury
Minor or moderate personal injury
- Get assistance from another person or use lifting equipment to carry the product.

3.6 Installing the tank

Fix the tank to the floor to prevent uplift and twist. Use the mounting brackets to fix the tank with screws.
Fig. 3 Fixing the tank to the floor

3.7 Drilling holes for the pipes

CAUTION
Sharp element
Minor or moderate personal injury
- Wear protective gloves.
The tank has three or four holes, 100, for the inlet pipes, depending on the size. The tank also has a hole, 40, for the diaphragm pump. See section
6.1 Product overview. These holes must be drilled to
be used. Holes for the outlet pipes, the vent port and the
minimum required cable glands are open.
1. Determine which inlets you want to use. See sections 3.2.1 Tank inlets and 7.1 Setting the
start levels.
2. Drill holes with a hole saw. The diameter of the hole saw must be the same as the diameter of the pipe.
Inlet: 100
Hole for diaphragm pump: ∅40
3. Deburr the holes.
English (GB)
TM06 5780 0116
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.
Position the tank so that all components are easily accessible during operation and maintenance.
TM06 5851 0216
Fig. 4 Drilling holes for pipes
7

3.8 Fitting the cable glands

English (GB)
Choose the appropriate cable gland:
Cable gland for Unilift pumps: M20
Cable gland for SEG pumps: M25
Cable gland for level sensor hose: M20
Fig. 5 Fitting the cable glands

3.9 Fitting the vent port

1. Fit the gasket on the socket.
2. Fit the nipple in the hole on top of the tank.
3. Fit the nut inside the tank and tighten it.

3.10 Connecting the vent pipe

The vent pipe is not supplied with the product. You can connect your vent pipe to the vent port in
three different ways:
• By means of a PVC vent pipe with an outer diameter of 63 mm and glue.
• By means of a flexible pipe connection with an inner diameter of 75 mm and with clamps. A flexible pipe connection with clamps is available as an accessory.
• By means of a PP double nipple with an inner diameter of 75 mm. The nipple must comply with EN 1451.

3.11 Connecting the inlet pipes

You can connect three or four inlet pipes to the tank, depending on the tank size. First you must drill the holes. See section 3.7 Drilling holes for the pipes.
1. Fit the socket seal in the inlet.
2. Connect the isolating valve to the inlet pipe. The isolating valve is an accessory. Product number
96615831.
TM06 5779 0116TM06 5924 0316
3. Insert the inlet pipe into the socket seal.
Fig. 6 Fitting the vent port
8
TM06 5859 0216
Fig. 7 Connecting an inlet pipe with an
isolating valve
Loading...
+ 18 hidden pages