Grundfos TPE3, TPE2, TPE2 D, TPE3 D Installation And Operating Instructions Manual

Page 1
GRUNDFOS INSTRUCTIONS
TPE2 (D), TPE3 (D)
Single-stage in-line pumps with integrated variable frequency drive
Installation and operating instructions
Page 2

English (US)

English (US) Installation and operating instructions
Original installation and operating instructions.
1. Symbols used in this document
2. Limited warranty
3. Abbreviations and definitions
4. General information
4.1 Radio communication
4.2 Battery
5. Delivery and handling
5.1 Delivery
5.2 Handling
6. Applications
6.1 Pumped liquids
7. Operating conditions
7.1 Maximum number of starts and stops
7.2 Alternating operation of twin-head pumps
7.3 Liquid temperature
7.4 Ambient temperature
7.5 Operating pressure/test pressure
7.6 Inlet pressure
7.7 Electrical data
7.8 Sound pressure level
7.9 Environment
7.10 Installation altitude
7.11 Air humidity
7.12 Motor cooling
8. Mechanical installation
8.1 Pipework
8.2 Terminal box positions
8.3 Fitting of pump head
8.4 Base plate
8.5 Insulation
8.6 Frost protection
8.7 Ensuring motor cooling
8.8 Outdoor installation
9. Electrical installation
9.1 Protection against electric shock, indirect contact
9.2 Power supply
9.3 Additional protection
9.4 Connection terminals
9.5 Signal cables
9.6 Bus connection cable
10. Startup
10.1 Flushing the pipe system
10.2 Priming
10.3 Starting
10.4 Shaft seal run-in
11. User interfaces
12. Standard control panel
12.1 Setpoint setting
13. Advanced control panel
13.1 Menu structure
13.2 Menu overview for advanced control panel
14. Grundfos GO Remote
14.1 Communication
14.2 Menu overview for Grundfos GO Remote
15. Description of selected functions
15.1 Setpoint
15.2 Operating mode
15.3 Set manual speed
Page
10
10 10 11 12 16 16
16
16 16 17 17
17 18
18
20
20 21
23
23 24
26
26 26 26
15.4 Control mode
15.5 FLOWLIMIT
15.6 Automatic Night Setback
15.7 Analog inputs
3 3 4 4
4 4
4
4 4
5
5
5
5 5 5 5 5 6 6 6 6 6 6 6
7
7 8 8 9 9 9 9 9
15.8 Pt100/1000 inputs
15.9 Digital inputs
15.10 Digital inputs/outputs
15.11 Relay outputs
15.12 Analog output
15.13 Controller settings
15.14 Operating range
15.15 Setpoint influence
15.16 Monitoring functions
15.17 Special functions
15.18 Communication
15.19 General settings
16. Assist
16.1 Multi-pump setup
17. Selection of control mode
18. Changing the position of the control panel
19. Bus signal
20. Priority of settings
21. Grundfos Eye
22. Signal relays
23. Maintenance and service
23.1 Maintenance
23.2 Service
24. Fault finding
25. Megging
26. Technical data, single-phase motors
26.1 Supply voltage
26.2 Leakage current
27. Technical data, three-phase motors
27.1 Supply voltage
27.2 Leakage current
28. Inputs/outputs
29. Other technical data
29.1 Torques
29.2 Sound pressure level
30. Disposal
26 31 31 31 31 32 32 33 33 33 34 35 38 38 38 39
39
39
40 42 43 43 44 45 46
46 46
47 48 48
48 48
48
48 48
48 49
49 49
49
2
Page 3
Warnin g
Caution
Note
Note
Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.

1. Symbols used in this document

Warnin g If these safety instructions are not observed,
it may result in personal injury.
Warnin g If these instructions are not observed, it may lead
to electric shock with consequent risk of serious personal injury or death.
Warnin g The surface of the product may be so hot that
it may cause burns or personal injury.
Warnin g Risk of dropping objects which may cause
personal injury.
Warnin g Escaping vapor involves the risk of personal
injury.
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Notes or instructions that make the job easier and ensure safe operation.

2. Limited warranty

Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions.
To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.
English (US)
3
Page 4
English (US)
Note
Note

3. Abbreviations and definitions

AI Analog input. AL Alarm, out of range at lower limit. AO Analog output. AU Alarm, out of range at upper limit.
Current sinking
Current sourcing
DI Digital input. DO Digital output. ELCB Earth leakage circuit breaker. FM Functional module.
GDS
GENIbus Proprietary Grundfos fieldbus standard.
GFCI
GND Ground. Grundfos Eye Status indicator light.
LIVE
OC
PE Protective earth.
PELV
SELV
TPE2
TPE2 D
TPE3
TPE3 D
The ability to draw current into the terminal and guide it towards GND in the internal circuitry.
The ability to push current out of the terminal and into an external load which must return it to GND.
Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps.
Ground fault circuit interrupter. (USA and Canada).
Low voltage with the risk of electric shock if the terminals are touched.
Open collector: Configurable open-collector output.
Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except earth faults in other circuits.
Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including earth faults in other circuits.
Single-head TPE2 pump without factory-fitted differential-pressure and temperature sensor.
Twin-head TPE2 D pump without factory-fitted differential-pressure and temperature sensor.
Single-head TPE3 pump with factory-fitted differential-pressure and temperature sensor.
Twin-head TPE3 D pump with factory-fitted differential-pressure and temperature sensor.
Some variants of these products and all products sold in China and Korea have no possibility of radio communication according to local legislation.
This product can communicate with the Grundfos GO Remote and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only Grundfos-approved external antennas may be connected to
this product, and only by a Grundfos-approved installer.

4.2 Battery

Pumps fitted with the advanced functional module (FM 300) incorporate a Li-ion battery. The Li-ion battery complies with the Battery Directive (2006/66/EC). The battery does not contain mercury, lead and cadmium.

5. Delivery and handling

5.1 Delivery

The pump is delivered from the factory in a carton with a wooden bottom, which is specially designed for transport by fork-lift truck or a similar vehicle.

5.2 Handling

Warnin g TPE2 D, TPE3 D: The centrally positioned thread
of the pump housing must not be used for lifting purposes as the thread is placed below the center of gravity of the pump.
Lift the pump by means of nylon straps. See figs 1 and 2.
TM05 7914 1613TM05 7915 1613
Fig. 1 TPE2, TPE3

4. General information

These installation and operating instructions apply to the Grundfos TPE2 (D) and TPE3 (D) pumps.
The pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase power supply connection.

4.1 Radio communication

This product incorporates a radio module for remote control which is a class 1 device and can be used anywhere in the EU member states without restrictions.
For use in USA and Canada, see page 50.
4
Fig. 2 TPE2 D, TPE3 D
Page 5

6. Applications

Note
Note
The pumps are designed to circulate hot or cold water in:
• heating systems
• district heating plants
• air-conditioning systems
• cooling systems. In addition, the pumps are used for liquid transfer and water
supply in:
• washing systems
• domestic hot-water systems
• industrial systems in general. To ensure optimum operation, the sizing range of the system
must fall within the performance range of the pump.

6.1 Pumped liquids

Warnin g If the pump is used for a liquid which is
hazardous, it will be classified as contaminated. In such cases, the proper precautions must be taken to avoid injury to health when operating or working on the pump.
The pump is suitable for thin, clean, non aggressive and nonflammable liquids, not containing solid particles or fibers that may attack the pump mechanically or chemically.
Examples:
• central heating system water (the water should meet the requirements of accepted standards on water quality in heating systems)
• cooling liquids
• domestic hot water
• industrial liquids
• softened water.
The pumping of liquids with a density and/or kinematic viscosity higher than that of water will cause the following:
• a considerable pressure drop
• a drop in hydraulic performance
• a rise in power consumption.
In such cases, fit the pump with a bigger motor. If in doubt, contact Grundfos.
The EPDM O-rings fitted as standard are primarily suitable for water.
If the water being pumped contains minerals, synthetic oil, chemicals, or any liquids other than water, choose the O-rings accordingly.

7. Operating conditions

7.1 Maximum number of starts and stops

The number of starts and stops via the power supply must not exceed four times per hour.
When switched on via the power supply, the pump will start after approx. 5 seconds.
If you want a higher number of starts and stops, use the input for external start/stop when starting/stopping the pump.
When started via an external on/off switch, the pump will start immediately.

7.2 Alternating operation of twin-head pumps

On twin-head pumps, the duty and backup pumps must be alternated on a regular basis, i.e. once a week, to ensure an even distribution of the operating hours on both pumps. As default, the pumps alternate automatically. See section 16.1 Multi-pump
setup.
If you use twin-head pumps for pumping domestic hot water, the duty and backup pumps must be alternated on a regular basis, i.e. once a day, to avoid blocking of the backup pump due to deposits (calcareous deposits, etc.). As default, the pumps alternate automatically. See section 16.1 Multi-pump setup.

7.3 Liquid temperature

-13 °F (-25 °C) up to 248 °F (+120 °C). The maximum liquid temperature depends on the mechanical
shaft seal type and the pump type. Depending on the cast-iron version and the pump application, the
maximum liquid temperature may be limited by local regulations and laws.
The maximum liquid temperature is stated on the pump nameplate.
If the pump is operating with liquids at high temperatures, the life of the shaft seal may be reduced. It may be necessary to replace the shaft seal more often.

7.4 Ambient temperature

7.4.1 Ambient temperature during storage and transportation
-22 to 140 °F (-30 to +60 °C).
7.4.2 Ambient temperature during operation
-4 to 122 °F (-20 to +50 °C). The motor can operate with the rated power output (P2) at
122 °F (50 °C), but continuous operation at higher temperatures will reduce the expected product life. If the motor is to operate at ambient temperatures between 122 and 140 °F (50 and 60 °C), select an oversized motor. Contact Grundfos for further information.
English (US)

7.5 Operating pressure/test pressure

The pressure test has been made with water containing anti-corrosive additives at a temperature of +68 °F (+20 °C).
Operating pressure Test pressure
[bar] [psi] [bar] [psi]
10 145 15 218
5
Page 6
English (US)
Caution
1
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.91
0.90
0.89
0.88
0
0
3281 3937 4593 5249 5906 6562 7218
[ft]
P2 [%]

7.6 Inlet pressure

To ensure optimum and quiet pump operation, the inlet pressure (system pressure) must be adjusted correctly. See table on page 51.
For the calculation of specific inlet pressures, contact the local Grundfos company or see the data booklet for TP(D), TPE(D), TPE2 (D) and TPE3 (D) on www.grundfos.us.

7.7 Electrical data

See sections 26. Technical data, single-phase motors and
27. Technical data, three-phase motors.
For specific motor data, see the motor nameplate.

7.8 Sound pressure level

The sound pressure level of the pump is lower than 70 dB(A).

7.9 Environment

Non-aggressive and non-explosive atmosphere.

7.10 Installation altitude

The motor must not be installed more than 6562 ft (2000 m) above sea level.
Installation altitude is the height above sea level of the installation site.
• Motors installed up to 3281 ft (1000 m) above sea level can be loaded 100 %.
• Motors installed more than 3281 ft (1000 m) above sea level must not be fully loaded due to the low density and consequent low cooling effect of the air. See fig. 3.

7.11 Air humidity

Maximum air humidity: 95 %. If the air humidity is constantly high and above 85 %, one of the
drain holes in the drive-end flange must be open. See section
5. Delivery and handling.

7.12 Motor cooling

To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate cooling is
ensured. See section 8.7 Ensuring motor cooling.
• The temperature of the cooling air must not exceed 122 °F (50 °C).
• Keep cooling fins and fan blades clean.
TM05 6400-U.S. 1013
Fig. 3 Derating of motor output power (P2) in relation to
altitude above sea level
6
Page 7

8. Mechanical installation

Note
Note
Caution
Installation
Washer Pump
11.81" [300 mm]
Caution
Caution
Warnin g When pumping hot or cold liquids, make sure
that persons cannot accidentally come into contact with hot or cold surfaces.
In order to maintain the UL mark, additional installation procedures must be followed. See page 50.
Install the pump in a dry well-ventilated, but frost-free position. When installing pumps with oval bolt holes in the pump flange,
use washers as shown in fig. 4.
Fig. 4 Use of washers for oval bolt holes
Arrows on the pump housing show the direction of flow of liquid through the pump.
You can install the pump in horizontal or vertical pipes.
The motor must never fall below the horizontal plane.
For inspection and removal of motor or pump head, a clearance of 11.81" (300 mm) is required above the motor. See fig. 5.
Fig. 5 Required clearance above the motor
If the liquid temperature falls below the ambient temperature, condensation may form in the motor during inactivity. In this case, make sure that one of the drain holes in the motor flange is open and points downwards. See fig. 7.
Fig. 7 Drain hole in motor flange
If twin-head pumps are used for pumping liquids with a temperature below 32 °F (0 °C), condensed water may freeze and cause the coupling to get stuck. You can solve the problem by installing heating elements. Whenever possible, install the
TM01 0683 1997
pump with the motor shaft in horizontal position. See fig. 6.
Observe the conditions in section 11. User
interfaces.

8.1 Pipework

Fit isolating valves on either side of the pump to avoid draining the system if the pump needs to be cleaned or repaired.
The pump is suitable for pipeline mounting, provided that the pipes are adequately supported on either side of the pump.
Single-head pumps are designed for pipeline mounting only. Twin-head pumps are prepared for installation on a mounting
bracket or base plate. When installing the pipes, make sure that the pump housing is
not stressed by the pipework. The suction and discharge pipes must be of an adequate size,
taking the pump inlet pressure into account. To avoid sediment build-up, do not fit the pump at the lowest point
of the system. Install the pipes so that air locks are avoided, especially on the
suction side of the pump. See fig. 8.
TM05 7916 1613TM05 7983 1713
English (US)
TM05 7917 1613
Twin-head pumps installed in horizontal pipes must be fitted with an automatic air vent in the upper part of the pump housing. See fig. 6.
The automatic air vent is not supplied with the pump.
Fig. 6 Automatic air vent
TM00 2263 0195
Fig. 8 Correct pipework on the suction side of the pump
The pump must not run against a closed discharge valve as this will cause an increase in temperature/formation of steam in the pump which may cause damage to the pump.
If there is any risk of the pump running against a closed discharge valve, ensure a minimum liquid flow through the pump by connecting a bypass/a drain to the discharge pipe. You can for instance connect the drain to a tank. A minimum flow rate equal to 10 % of the flow rate at maximum efficiency is needed at all times.
Flow rate and head at maximum efficiency are stated on the pump nameplate.
7
Page 8
English (US)
A

8.2 Terminal box positions

Warnin g Before starting work on the pump, make sure that
the power supply has been switched off for at least 5 minutes. Make sure that the power supply cannot be accidentally switched on.

8.3 Fitting of pump head

Warnin g Before starting work on the pump, make sure that
the power supply has been switched off for at least 5 minutes. Make sure that the power supply cannot be accidentally switched on.
Warnin g If the pump head has been lifted partly or
completely from the pump housing, pay special attention when fitting the pump head again. See 8.3 Fitting of pump head.
Warnin g When loosening the clamp, do not drop the pump
head. See fig. 9.
Warnin g When loosening the clamp, there is a risk of
escaping vapor. See fig. 9.
The terminal box can be turned to any position. Change the terminal box position as follows:
1. Loosen the clamp securing the pump head to the pump housing. See fig. 9.
Warnin g If the pump head has been lifted partly or
completely from the pump housing, pay special attention when fitting the pump head again. See instructions below.
Warnin g Do not drop the pump head. See fig. 9.
Warnin g When loosening the clamp, there is a risk of
escaping vapor. See fig. 9.
If for some reason the pump head has been lifted from the pump housing, follow the following procedure in order to mount the pump head correctly:
1. Visually check that the neck ring is centered in the pump housing. See fig. 10.
Fig. 9 Clamp (A)
2. Turn the pump head to the required position.
3. Check the following before you tighten the clamp: – The contact face of the pump housing and that of the pump
head must be in full contact.
– Position the clamp correctly in the flange recess of both the
pump head and the pump housing. See fig. 12.
Tightening torque: 5.9 lbf-ft (± 0.75) (8 Nm (± 1)).
TM06 0721 0814
TM06 0722 0814TM06 0723 0814
Fig. 10 Centering of neck ring
2. Gently lower the pump head with rotor shaft and impeller into the pump housing. See fig. 11.
Fig. 11 Lowering of pump head
8
Page 9
3. Check the following before you tighten the clamp:
Caution
A
B
C
Note
Note
Note
Note
D
– The contact face of the pump housing and that of the pump
head must be in full contact.
– Position the clamp correctly in the flange recess of both the
pump head and the pump housing. See fig. 12.
Tightening torque: 5.9 lbf-ft (± 0.75) (8 Nm (± 1)).
Fig. 12 Positioning of clamp ring

8.6 Frost protection

Pumps which are not being used during periods of frost must be drained to avoid damage.

8.7 Ensuring motor cooling

In order to ensure sufficient cooling of the motor, the distance (D) between the end of the fan cover and a wall or other fixed objects must always be at least 2.0" (50 mm), irrespective of motor size. See fig. 14.
TM06 0724 0814
English (US)

8.4 Base plate

Twin-head pumps have tapped holes in the bottom of the pump housing. The holes can be used for mounting a base plate.

8.5 Insulation

Do not insulate the motor stool as this will trap any vapor escaping from the shaft seal, thus causing corrosion. Covering the motor stool with insulation will also make inspection and service difficult.
Follow the guidelines in fig. 13 when insulating the pump.
Fig. 13 Insulation of TPE2, TPE3 pumps
Fig. 14 Minimum distance (D) from the motor to a wall or other
fixed objects

8.8 Outdoor installation

When installed outdoors, the motor must be provided with a suitable cover to avoid condensation on the electronic components. See fig. 15.
When fitting a cover to the motor, observe the guideline in section 8.7 Ensuring motor cooling.
The cover must be sufficiently large to ensure that the motor is not exposed to direct sunlight, rain or snow. Grundfos does not supply covers. We therefore recommend that you have a cover built for the specific application. In areas with high air humidity, we recommend that you enable the built-in standstill heating function.
TM05 7918 1613
Fig. 15 Examples of covers (not supplied by Grundfos)
TM05 5236 3512
TM05 7919 1613
Pos. Description
A Without insulation B Correct insulation C Incorrect insulation
9
Page 10
English (US)
Note
Note
GFCI

9. Electrical installation

Carry out the electrical connection according to local regulations. Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Warnin g Before making any connections in the terminal
box, make sure that the power supply has been switched off for at least 5 minutes. Make sure that the power supply cannot be accidentally switched on.
The motor must be connected to an external all-pole power supply switch according to local regulations.
The motor must be grounded and protected against indirect contact in accordance with local regulations.
If the power supply cable is damaged, it must be replaced by the manufacturer, the manufacturer's service partner or a similarly qualified person.
The user or the installer is responsible for the installation of correct grounding and protection according to local regulations. All operations must be carried out by a qualified electrician.

9.1 Protection against electric shock, indirect contact

9.2 Power supply

9.2.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
The wires in the motor terminal box must be as short possible except for the separated ground conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 26.1 Supply voltage.
TM05 4034 1912TM05 3494 1512
Fig. 16 Example of a power supply-connected motor with
power supply switch, backup fuse and additional protection
Warnin g The motor must be grounded and protected
against indirect contact in accordance with local regulations.
9.1.1 Protection against power supply voltage transients
The motor is protected against power supply voltage transients in accordance with EN 61800-3.
9.1.2 Motor protection
The motor requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.
Fig. 17 Power supply connection, single-phase motors
10
Page 11
9.2.2 Three-phase supply voltage
Caution
Note
Note
L1
L2
L3
L2
L1
L3
PE
GFCI
Note
Note
Note
Note
ELCB (GFCI)
ELCB (GFCI)
• 3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE.
In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in its socket when the supply cable has been connected.
Corner grounding is not allowed for supply voltages above 3 x 480 V, 60 Hz.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 27.1 Supply voltage.
Fig. 18 Example of a power supply-connected motor with
power supply switch, backup fuses and additional protection

9.3 Additional protection

9.3.1 Single-phase motors
If the motor is connected to an electric installation where an earth leakage circuit breaker (ELCB) or ground fault circuit interrupter (GFCI) is used as additional protection, this circuit breaker or interrupter must be marked with the following symbol:
When an earth leakage circuit breaker or ground fault circuit interrupter is selected, the total leakage current of all the electrical equipment in the installation must be taken into account.
The leakage current of the motor can be found in section
26.2 Leakage current.
9.3.2 Three-phase motors
If the motor is connected to an electric installation where an earth leakage circuit breaker (ELCB) or ground fault circuit interrupter (GFCI) is used as additional protection, this circuit breaker or interrupter must be of the following type:
• It must be suitable for handling leakage currents and cutting-in
with short pulse-shaped leakage.
• It must trip out when alternating fault currents and fault
TM05 3942 1812TM05 3495 1512
currents with DC content, i.e. pulsating DC and smooth DC fault currents, occur.
For these motors an earth leakage circuit breaker or ground fault circuit interrupter, type B, must be used.
This circuit breaker or interrupter must be marked with the following symbols:
English (US)
Fig. 19 Power supply connection, three-phase motors
When you select an earth leakage circuit breaker or ground fault circuit interrupter, take into account the total leakage current of all the electrical equipment in the installation.
You find the leakage current of the motor in section 27.2 Leakage
current.
Protection against phase unbalance
The motor must be connected to a power supply with a quality corresponding to IEC 60146-1-1, class C, to ensure correct motor operation at phase unbalance.
This also ensures long life of the components.
11
Page 12
English (US)
Env.Type :
Serial no :
SF CL:
PF:
PB FM HMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
: :
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
P
:
n
W
g
g
t
:
DE
:
k
g
g
D
:
amb
:
:
FAA
V
:
T
T
E
C
T
yp
yp
e
:
P.N.
:
U
:
1/1
:
HzP
I
p
p
:
:
PB FM
HMI CIM
VARIANT
Hp
rpm
: :
: :
PB
:
:
C
:
H
p
m
Note
Note
Note
Note

9.4 Connection terminals

The descriptions and terminal overviews in this section apply to both single-phase and three-phase motors.
For maximum tightening torques, see section Torques, page 49. The number of terminals depends on the functional module (FM).
You can identify the fitted module on the motor nameplate. See fig. 20.
P.C.
INPU
in
eri
e
F
in
L
SF Am
F
Fig. 20 Identification of functional module
rp
IM
9.4.1 Connection terminals, advanced functional module
(FM 300)
The advanced functional module is only available as an option. The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 21.
Digital input 1 is factory-set to be start/stop input where open circuit will result in stop.
A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start/stop or any other external function.
As a precaution, the wires to be connected to the connection groups below must be separated from each other by reinforced insulation in their entire lengths.
Inputs and outputs
TM05 7928 1613
All inputs and outputs are internally separated from the power supply-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by safety extra-low voltage (SELV), thus ensuring protection against electric shock.
Signal relay outputs – Signal relay 1:
LIVE: Power supply voltages up to 250 VAC can be connected to this output. SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
– Signal relay 2:
SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE).
A galvanically safe separation must fulfil the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
12
Page 13
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
Terminal Type Function
Normally closed
NC
contact
Signal relay 1 (LIVE or SELV)C1 Common
NO Normally open contact
Normally closed
NC
contact
Signal relay 2 (SELV only)C2 Common
NO Normally open contact
18 GND Ground
Digital input/output,
11 DI4/OC2
configurable. Open collector: Max. 24 V
resistive or inductive. 19 Pt100/1000 input 2 Pt100/1000 sensor input 17 Pt100/1000 input 1 Pt100/1000 sensor input
Analog output: 12 AO
0-20 mA / 4-20 mA
0-10 V
9 GND Ground
Analog input: 14 AI3
0-20 mA / 4-20 mA
0-10 V
1 DI2 Digital input, configurable
English (US)
* If you use an external supply source, there must be a
connection to GND.
Fig. 21 Connection terminals, FM 300 (option)
21 LiqTec sensor input 1
LiqTec sensor input
(white conductor)
Ground 20 GND
(brown and black
conductors)
22 LiqTec sensor input 2
LiqTec sensor input
(blue conductor)
Digital input/output,
10 DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
TM05 3509 3512
5+5 V
Supply to potentiometer
and sensor
6 GND Ground A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
Supply to potentiometer
and sensor* 23 GND Ground
25 GDS TX
24 GDS RX
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
13
Page 14
English (US)
Note
Note
Note
Note
9.4.2 Connection terminals, standard functional module (FM 200)
The standard module has these connections:
• two analog inputs
• two digital inputs or one digital input and one open-collector
output
• Grundfos Digital Sensor input and output
• two signal relay outputs
• GENIbus connection.
See fig. 22.
Digital input 1 is factory-set to be start/stop input where open circuit will result in stop.
A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start/stop or any other external function.
As a precaution, the wires to be connected to the connection groups below must be separated from each other by reinforced insulation in their entire lengths.
Inputs and outputs
All inputs and outputs are internally separated from the power supply-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by safety extra-low voltage (SELV), thus ensuring protection against electric shock.
Signal relay outputs
– Signal relay 1:
LIVE: Power supply voltages up to 250 VAC can be connected to this output. SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
– Signal relay 2:
SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE).
A galvanically safe separation must fulfil the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
14
Page 15
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
Terminal Type Function
NC
C1 Common
NO
Normally closed contact
Normally open contact
Signal relay 1 (LIVE or SELV)
English (US)
* If an external supply source is used, there must be a
connection to GND.
Fig. 22 Connection terminals, FM 200
NC
C2 Common
NO
Normally closed contact
Normally open contact
Signal relay 2 (SELV only)
Digital input/output,
10 DI3/OC1
configurable. Open collector: Max. 24 V resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5+5 V
Supply to potentiometer and sensor
6 GND Ground A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
TM05 3510 3512
8 +24 V Supply
26 +5 V
Supply to potentiometer and sensor*
23 GND Ground
25 GDS TX
Grundfos Digital Sensor output
24 GDS RX Grundfos Digital Sensor input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
15
Page 16
English (US)
A
Y
B
A
Y
B
1
2
3
1
2 3
Motor
Caution
Caution
A
Y
B
A Y B
1
2
1
2
Motor

9.5 Signal cables

• Use screened cables with a cross-sectional area of min. 20 AWG and max. 16 AWG (0.5 mm for external on/off switch, digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to frame at both ends with good connection. The screens must be as close as possible to the terminals. See fig. 23.
Fig. 23 Stripped cable with screen and wire connections
• Screws for frame connections must always be tightened whether a cable is fitted or not.
• The wires in the motor terminal box must be as short as possible.
2
and max. 1.5 mm2)

9.6 Bus connection cable

9.6.1 New installations
For the bus connection, use a screened 3-core cable with a cross-sectional area of min. 20 AWG and max. 16 AWG (0.5 mm and max. 1.5 mm
• If the motor is connected to a unit with a cable clamp which is identical to the one on the motor, connect the screen to this cable clamp.
• If the unit has no cable clamp as shown in fig. 24, leave the screen unconnected at this end.
Fig. 24 Connection with screened 3-core cable
2
).
9.6.2 Replacing an existing motor
• If a screened 2-core cable is used in the existing installation, connect the cable as shown in fig. 25.
Fig. 25 Connection with screened 2-core cable
• If a screened 3-core cable is used in the existing installation, follow the instructions in section 9.6.1 New installations.

10. Startup

TM02 1325 4402 TM05 3973 1812

10.1 Flushing the pipe system

The pump is not designed to pump liquids containing solid particles such as pipe debris and welding slag. Before starting up the pump, clean the pipe system thoroughly, and flush and fill it with clean water.
The warranty does not cover any damage caused by flushing the pipe system by means of the
2

10.2 Priming

Closed systems or open systems where the liquid level is above the pump inlet
1. Close the discharge isolating valve and loosen the air vent
screw in the motor stool. See fig. 26.
2. Slowly open the isolating valve in the suction pipe until a
steady stream of liquid runs out of the vent hole.
3. Tighten the air vent screw and completely open the isolating
valve(s).
pump.
Do not start the pump until it has been filled with liquid and vented. To ensure correct venting, the vent screw should point upwards.
Warnin g Pay attention to the direction of the vent hole,
and make sure that the escaping hot or cold liquid does not cause injury to persons or damage to the equipment.
TM02 8842 0904
16
Page 17
Open systems where the liquid level is below the pump inlet
The suction pipe and the pump must be filled with liquid and vented before you start the pump.
1. Close the discharge isolating valve and open the isolating valve in the suction pipe.
2. Loosen the air vent screw. See fig. 26.
3. Remove the plug from one of the pump flanges, depending on the pump location.
4. Pour liquid through the priming port until the suction pipe and the pump are filled with liquid.
5. Replace the plug and tighten securely.
6. Tighten the air vent screw.
The suction pipe can to some extent be filled with liquid and vented before it is connected to the pump. You can also install a priming device before the pump.
Fig. 26 Position of air vent screw

10.3 Starting

1. Before starting the pump, completely open the isolating valve on the suction side of the pump and leave the discharge isolating valve almost closed.
2. Start the pump. See section 11. User interfaces.
3. Vent the pump during starting by loosening the air vent screw in the motor stool until a steady stream of liquid runs out of the vent hole. See fig. 26.
Warnin g Pay attention to the direction of the vent hole,
and make sure that the escaping hot or cold liquid does not cause injury to persons or damage to the equipment.
4. When the pipe system has been filled with liquid, slowly open the discharge isolating valve until it is completely open.

10.4 Shaft seal run-in

The seal faces are lubricated by the pumped liquid, meaning that there may be a certain amount of leakage from the shaft seal.
When the pump is started up for the first time, or when a new shaft seal is installed, a certain run-in period is required before the leakage is reduced to an acceptable level. The time required for this depends on the operating conditions, i.e. every time the operating conditions change, a new run-in period will be started.
Under normal conditions, the leaking liquid will evaporate. As a result, no leakage will be detected.
However, liquids such as kerosene will not evaporate. The leakage may therefore be seen as a shaft seal failure.

11. User interfaces

Warnin g The product may be so hot that only the buttons
must be touched to avoid burns.
Pump settings can be made by means of the following user interfaces:
Control panels
• Standard control panel.
See section 12. Standard control panel.
• Advanced control panel.
See section 13. Advanced control panel.
Remote controls
TM05 7922 1613
• Grundfos GO Remote.
See section 14. Grundfos GO Remote.
If you switch-off the power supply to the pump, the settings will be stored.
Factory settings
TPE2 (D) pumps have been factory-set to constant-curve control mode. See section 12.1.2 Pump in constant-curve control mode.
The setpoint value corresponds to 100 %, of maximum pump performance. See data booklet or WebCAPS.
TPE3 (D) pumps have been factory-set to AUTO mode. See section 15.4.1 AUTOADAPT.
ADAPT
English (US)
control
17
Page 18
English (US)
1
2
3
4
5
Stop
4.3
8.5
psi
H
Q

12. Standard control panel

This control panel is fitted as standard on TPE2 (D) pumps.
Fig. 27 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
2 - Light fields for indication of setpoint.
3 Changes the setpoint.
4
5
Shows the operating status of the pump. See section 21. Grundfos Eye for further information.
Enables radio communication with the Grundfos GO Remote and other products of the same type.
Makes the pump ready for operation/starts and stops the pump.
Start:
If you press the button when the pump is stopped, the pump will only start if no other functions with higher priority have been enabled. See section 20. Priority of settings.
Stop:
If you press the button when the pump is running, the pump will always be stopped. When the pump is stopped via this button, the "Stop" text next to the button will illuminate.

12.1 Setpoint setting

Set the desired setpoint of the pump by pressing or . The light fields on the control panel will indicate the setpoint set.
12.1.1 Pump in differential-pressure control mode
The following example applies to a pump in an application where a pressure sensor gives a feedback to the pump. If you retrofit the sensor to the pump, you must set it up manually as the pump does not automatically register a connected sensor.
Figure 28 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 4.3 psi (3 m) with a sensor measuring range from 0 to 8.5 psi (0 to 6 m). The setting range is equal to the sensor measuring range.
TM05 4848 3512
TM06 1116 1714TM05 4895 2812
Fig. 28 Setpoint set to 4.3 psi (3 m), differential-pressure
control
12.1.2 Pump in constant-curve control mode
In constant-curve control mode, the pump performance will lie between the maximum and minimum curve of the pump. See fig. 29.
Fig. 29 Pump in constant-curve control mode
18
Page 19
Setting to maximum curve:
H
Q
H
Q
•Press
of the pump (top light field flashes). When the top light field is on, press
• To change back, press
setpoint is indicated.
Example: Pump set to maximum curve. Figure 30 shows that the top light field is flashing, indicating
maximum curve.
Fig. 30 Maximum curve duty
Setting to minimum curve:
•Press
of the pump (bottom light field flashes). When the bottom light field is on, press flashing.
• To change back, press continuously until the desired
setpoint is indicated.
Example: Pump set to minimum curve. Figure 31 shows that the bottom light field is flashing, indicating
minimum curve.
continuously to change over to the maximum curve
for 3 seconds until the light field starts flashing.
continuously until the desired
continuously to change over to the minimum curve
for 3 seconds until the light field starts
12.1.3 Start/stop of pump
Start the pump by pressing until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is stopped, the "Stop" text next to the button will illuminate. You can also stop the pump by continuously pressing are on.
If you have stopped the pump by pressing , it can only be given free to operation by pressing again.
If you have stopped the pump by pressing , it can only be restarted by pressing .
You can also stop the pump with the Grundfos GO Remote or via a digital input set to "External stop". See section 20. Priority of
settings.
12.1.4 Resetting of fault indications
You can reset a fault indication in one of the following ways:
• Via the digital input if it has been set to "Alarm resetting".
• Briefly press or setting of the pump.
TM05 4896 2812TM05 4897 2812
You cannot reset a fault indication by pressing or buttons have been locked.
• Switch off the power supply until the indicator lights are off.
• Switch the external start/stop input off and then on again.
• With the Grundfos GO Remote.
or by continuously pressing
until none of the light fields
on the pump. This will not change the
English (US)
if the
Fig. 31 Minimum curve duty
19
Page 20
English (US)
1
2
3
4
5
6
Note
Note

13. Advanced control panel

This control panel is fitted as standard on TPE3 (D) pumps. TPE2 (D) pumps can be fitted with the advanced control panel as an option.
Fig. 32 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
2 - Graphical color display.
Shows the operating status of the pump. See section 21. Grundfos Eye for further information.

13.1 Menu structure

The pump incorporates a startup guide which is started at the first startup. After the startup guide, the four main menus will appear in the display.
1. Home
This menu shows up to four user-defined parameters with shortcuts or a graphical illustration of a Q/H performance curve.
2. Status
This menu shows the status of the pump and system as well as warnings and alarms.
You cannot make any settings in this menu.
3. Settings
This menu gives access to all setting parameters. A detailed setting of the pump can be made in this menu.
See section 15. Description of selected functions.
4. Assist
TM05 4849 1013
This menu enables assisted pump setup, provides a short description of the control modes and offers fault advice.
See section 16. Assist.
3 Goes one step back.
Navigates between main menus, displays and digits. When the menu is changed, the display will always show the top display of the new menu.
4
Navigates between submenus.
Saves changed values, resets alarms and expands the value field. Enables communication with the Grundfos GO Remote.
Makes the pump ready for operation/starts and stops the pump.
Start:
If you press the button when the pump is stopped, the pump will only start if no other
5
functions with higher priority have been enabled. See section 20. Priority of settings.
Stop:
If you press the button when the pump is running, the pump will always be stopped. When you stop the pump via this button, the "Stop" text next to the button will illuminate.
6 Goes to the "Home" menu.
20
Page 21

13.2 Menu overview for advanced control panel

13.2.1 Main menus
Home TPE3 (D) TPE2 (D)
●●
Status TPE3 (D) TPE2 (D)
Operating status ●●
Operating mode, from ●●
Control mode ●●
Pump performance ●●
Actual controlled value ●●
Max. curve and duty point -
Resulting setpoint ●●
Liquid temperature -
Speed ●●
Acc. flow and specific energy ●●
Power and energy consumption ●●
Measured values ●●
Analog input 1 ●●
Analog input 2 ●●
Analog input 3
Pt100/1000 input 1
Pt100/1000 input 2
Analog output
Warning and alarm ●●
Actual warning or alarm ●●
Warning log ●●
Alarm log ●●
Heat energy meter -
Heat power - Heat energy - Flow rate - Volume - Hours counter - Temperature 1 - Temperature 2 - Differential temp. -
Operating log ●●
Operating hours ●● Trend data -
Fitted modules ●● Date and time --
Product identification ●●
Motor bearing monitoring ●●
Multi-pump system ●●
System operating status ●●
System performance ●●
System input power and energy ●●
Pump 1, multi-pump sys. ●●
Pump 2, multi-pump sys. ●●
Pump 3, multi-pump sys. ●●
1)
Only available if an advanced functional module is fitted.
1)
1)
1)
1)
1)
1)
1)
1)
English (US)
21
Page 22
English (US)
Settings TPE3 (D) TPE2 (D) Section Page
Setpoint ●●15.1 Setpoint 26 Operating mode ●●15.2 Operating mode 26 Set manual speed ●●15.3 Set manual speed 26 Control mode ●●15.4 Control mode 26
FLOW
LIMIT
●●15.5 FLOWLIMIT 31
Automatic Night Setback - 15.6 Automatic Night Setback 31
Analog inputs ●●15.7 Analog inputs 31
Analog input 1, setup ●●
Analog input 2, setup ●●
Analog input 3, setup
1)
1)
Built-in Grundfos sensor -
Pt100/1000 inputs
Pt100/1000, setup
1)
1)
1)
1)
15.8 Pt100/1000 inputs 31
Digital inputs ●●15.9 Digital inputs 32
Digital input 1, setup ●●
Digital input 2, setup
1)
1)
Digital inputs/outputs ●●15.10 Digital inputs/outputs 32
Digital input/output 3, setup ●●
Digital input/output 4, setup
1)
1)
Relay outputs ●●15.11 Relay outputs 33
Relay output 1 ●●
Relay output 2 ●●
Analog output
Output signal
Function of analog output
1)
1)
1)
1)
1)
1)
15.12 Analog output 33
Controller settings ●●15.13 Controller settings 33 Operating range ●●15.14 Operating range 34 Setpoint influence ●●15.15 Setpoint influence 35
External setpoint function ●●15.15.1 External setpoint influence 35
Predefined setpoints
1)
1)
Temperature influence - 15.15.3 Temperature influence 37
Monitoring functions ●●15.16 Monitoring functions 38
Motor bearing monitoring ●●
Motor bearing maintenance ●● Limit-exceeded function - 15.16.1 Limit-exceeded function 38
Special functions ●●15.17 Special functions 38
Pulse flow meter setup - 15.17.1 Pulse flow meter setup 38 Ramps - 15.17.2 Ramps 38
Standstill heating ●●
Communication ●●15.18 Communication 38
Pump number ●●15.18.1 Pump number 38 Enable/disable radio communication ●●15.18.2 Enable/disable radio communication 38
General settings ●●15.19 General settings 39
1)
Only available if an advanced functional module is fitted.
Assist TPE3 (D) TPE2 (D) Section Page
Assisted pump setup ●●
Setup, analog input ●● Setting of date and time -­Multi-pump setup ●●16.1 Multi-pump setup 39
Description of control mode ●●
Assisted fault advice ●●
22
Page 23

14. Grundfos GO Remote

+
+
+
1
2
3
The pump is designed for wireless radio or infrared communication with the Grundfos GO Remote.
The Grundfos GO Remote enables setting of functions and gives access to status overviews, technical product information and actual operating parameters.
The Grundfos GO Remote offers the following mobile interfaces (MI). See fig. 33.
Fig. 33 Grundfos GO Remote communicating with the pump
Pos. Descr ipt ion
via radio or infrared connection (IR)
Grundfos MI 202: Add-on module which can be used in conjunction with an
1
Apple iPhone or iPod with 30-pin connector and iOS 5.0 or later, e.g. fourth generation iPhone or iPod.
Grundfos MI 204: Add-on module which can be used in conjunction with an Apple iPhone or iPod with Lightning connector, e.g. fifth
2
generation iPhone or iPod. (The MI 204 is also available together with an Apple iPod touch and a cover.)
Grundfos MI 301: Separate module enabling radio or infrared communication. The module can be used in conjunction
3
with an Android or iOS-based smart device with Bluetooth connection.
English (US)
TM06 0744 0914

14.1 Communication

When the Grundfos GO Remote communicates with the pump, the indicator light in the middle of the Grundfos Eye will flash green. See section 21. Grundfos Eye.
Communication must be established using one of these communication types:
• radio communication
• infrared communication.
14.1.1 Radio communication
Radio communication can take place at distances up to 30 meters. It is necessary to enable communication by pressing or on the pump control panel.
14.1.2 Infrared communication
When communicating via infrared light, the Grundfos GO Remote must be pointed at the pump control panel.
23
Page 24
English (US)

14.2 Menu overview for Grundfos GO Remote

14.2.1 Main menus
Dashboard TPE3 (D) TPE2 (D)
●●
Status TPE3 (D) TPE2 (D)
Resulting setpoint ●● Actual controlled value ●● Motor speed (rpm, %) ●● Power consumption ●● Energy consumption ●● Acc. flow, specific energy ●● Operating hours ●● Liquid temperature - Analog input 1 ●● Analog input 2 ●● Analog input 3 Pt100/1000 input 1 Pt100/1000 input 2 Analog output Digital input 1 ●● Digital input 2 Digital in/output 3 ●● Digital in/output 4 Fitted modules ●● Trend data - Heat energy meter -
1)
Only available if an advanced functional module is fitted.
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
24
Page 25
Settings TPE3 (D) TPE2 (D) Section Page
Setpoint ●●15.1 Setpoint 26 Operating mode ●●15.2 Operating mode 26 Control mode ●●15.4 Control mode 26 Date and time
1)
1)
Flow limit - 15.5 FLOWLIMIT 31 Automatic Night Setback - 15.6 Automatic Night Setback 31 Temperature influence - 15.15.3 Temperature influence 37 Buttons on product ●●15.19.3 Enable/disable settings 39 Controller ●●15.13 Controller settings 33 Operating range ●●15.14 Operating range 34 Ramps - 15.17.2 Ramps 38 Pump number ●●15.18.1 Pump number 38 Radio communication ●●15.18.2 Enable/disable radio communication 38 Analog input 1 ●●
15.7 Analog inputs 31Analog input 2 ●●
Analog input 3 Pt100/1000 input 1 Pt100/1000 input 2
1)
1)
1)
Digital input 1 ●● Digital input 2
1)
Digital in/output 3 ●● Digital in/output 4 Predefined setpoint Analog output
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
15.8 Pt100/1000 inputs 31
15.9 Digital inputs 32
15.10 Digital inputs/outputs 32
15.15.2 Predefined setpoints 37
15.12 Analog output 33
External setpoint funct. ●●15.15.1 External setpoint influence 35 Signal relay 1 ●● Signal relay 2 ●● Limit 1 exceeded - Limit 2 exceeded -
15.11 Relay outputs 33
15.16.1 Limit-exceeded function 38
Standstill heating ●● Motor bearing monitoring ●● Service ●● Store settings ●● Recall settings ●● Undo ●● Pump name ●● Unit configuration ●●
1)
Only available if an advanced functional module is fitted.
English (US)
Alarms and warnings TPE3 (D) TPE2 (D)
Alarm log ●● Warning log ●● "Reset alarm" button ●●
Assist TPE3 (D) TPE2 (D)
Assisted pump setup ●● Assisted fault advice ●● Multipump setup ●●
25
Page 26
English (US)
Q
H
Max.
Min.
Note
Note
Note
Note
H
Q
H
auto_min
H
fac
A
1
A
3
A
2
H
set1
H
set2

15. Description of selected functions

15.1 Setpoint

The setpoint for all control modes, except AUTO FLOW
, can be set in this submenu when the desired control
ADAPT
mode has been selected. See section 15.4 Control mode.

15.2 Operating mode

Possible operating modes:
Normal The pump runs according to the selected control mode.
Stop The pump stops.
Min. The minimum curve mode can be used in periods in which a minimum flow is required. This operating mode is for instance suitable for manual night setback if "Automatic Night Setback" is not desired.
Max. The maximum curve mode can be used in periods in which a maximum flow is required. This operating mode is for instance suitable for systems with hot-water priority.
Manual The pump is operating at a manually set speed. See section 15.3 Set manual speed.
The pump can be set to operate according to the maximum or minimum curve, like an uncontrolled pump. See fig. 34.
Fig. 34 Maximum and minimum curves

15.3 Set manual speed

The pump speed can be set in %. When the operating mode has been set to "Manual", the pump will run at the set speed.

15.4 Control mode

Possible control modes:
•AUTO
•FLOW
• Prop. press. (proportional pressure)
Const. pressure (constant pressure)
Const. temp. (constant temperature)
Con. diff. press. (constant differential pressure)
Con. diff. temp. (constant differential temperature)
Const. flow rate (constant flow rate)
Const. level (constant level)
Const. other val. (constant other value)
Const. curve (constant curve).
ADAPT
ADAPT
ADAPT
and
The operating mode must be set to " before a control mode can be enabled.
You can change the setpoint for all control modes, except
ADAPT
and FLOW
ADAPT
AUTO "Settings" when you have selected the desired control mode.
15.4.1 AUTO
, in the "Setpoint" submenu under
ADAPT
Pump variant AUTO
TPE3 (D) TPE2 (D) -
The AUTO
control mode continuously adapts the pump
ADAPT
performance according to the actual system characteristic.
You cannot set the setpoint manually.
Fig. 35 AUTO
When you have enabled the AUTO will start with the factory setting, H performance to A
ADAPT
. See fig. 35.
1
control mode, the pump
ADAPT
= H
fac
, and then adjust its
set1
When the pump registers a lower head on the max. curve, A AUTO lower control curve, H pump will adjust its performance to A
function will automatically select a correspondingly
ADAPT
. If the valves in the system close, the
set2
.
3
A1: Original duty point.
: Lower registered head on the max. curve.
A
2
TM00 5547 0995
: Original setpoint setting.
H
set1
: New setpoint after AUTO
H
set2
: Factory setting.
H
fac.
H
The AUTO control where the control curves have a fixed origin, H
The AUTO
: A fixed value of 5 ft (1.5 m).
auto_min
control mode is a form of proportional-pressure
ADAPT
control mode has been developed specifically
ADAPT
: New duty point after AUTO
A
3
ADAPT
ADAPT
control.
control.
for heating systems and Grundfos do not recommend it for air-conditioning and cooling systems.
Normal
ADAPT
"
2
auto_min
TM05 7910 1613
, the
.
26
Page 27
15.4.2 FLOW
Note
Note
H
Q
Q
max
25 %
90 %
H
auto_min
H
fac
Q
fac
Setting range
H
Q
Hset
Hset
2
p
H
Q
p
p
Pump variant FLOW
ADAPT
ADAPT
TPE3 (D) TPE2 (D) -
When you select FLOW ensure that the flow never exceeds the entered FLOW
The setting range for FLOW
, the pump will run AUTO
ADAPT
is 25 to 90 %, of the Q
LIMIT
pump. The factory setting of the FLOW
AUTO See fig. 36.
factory setting meets the maximum curve.
ADAPT
Do not set the FLOW dimensioned duty point.
is the flow where the
LIMIT
lower than the
LIMIT
ADAPT
LIMIT
max
and
value. of the
Example
• Factory-fitted differential-pressure sensor.
English (US)
Fig. 38 Proportional pressure
15.4.4 Constant pressure
Pump variant Constant pressure
TPE3 (D) ­TPE2 (D)
The pump maintains a constant discharge pressure, independently of the flow rate. See fig. 39.
Fig. 36 FLOW
ADAPT
15.4.3 Proportional pressure
Pump variant Proportional pressure
TPE3 (D) TPE2 (D) -
The pump head is reduced at decreasing water demand and increased at rising water demand. See fig. 37.
This control mode is especially suitable in systems with relatively large pressure losses in the distribution pipes. The head of the pump will increase proportionally to the flow in the system to compensate for the large pressure losses in the distribution pipes.
The setpoint can be set with an accuracy of 0.33 ft (0.1 m). The head against a closed valve is half the setpoint, H
set
.
TM05 7912 1613
TM05 7901 1613
Fig. 39 Constant pressure
This control mode requires an external pressure sensor as shown in the examples below:
Examples
• One external pressure sensor.
Fig. 40 Constant pressure
TM05 7909 1613
Fig. 37 Proportional pressure
27
Page 28
English (US)
H
Q
t
t
t
t
H
Q
p
p
p
p
p
p
p
p
p
15.4.5 Constant temperature
15.4.6 Constant differential pressure
Pump variant Constant temperature
TPE3 (D) TPE2 (D)
This control mode ensures a constant temperature. Constant temperature is a comfort control mode that can be used in domestic hot-water systems to control the flow to maintain a fixed temperature in the system. See fig. 41. When this control mode is used, no balancing valves must be installed in the system.
Fig. 41 Constant temperature
This control mode requires either an internal or external temperature sensor as shown in the examples below:
Examples
• Factory-fitted temperature sensor (only TPE3 (D)).
Pump variant
Constant differential
pressure
TPE3 (D) TPE2 (D)
The pump maintains a constant differential pressure, independently of the flow in the system. See fig. 43. This control mode is primarily suitable for systems with relatively small pressure losses.
TM05 7900 1613
Fig. 43 Constant differential pressure
This control mode requires either an internal or external differential-pressure sensor or two external pressure sensors as shown in the examples below:
Examples
• Factory-fitted differential-pressure sensor (only TPE3 (D)).
TM05 7901 1613
• One external temperature sensor.
Fig. 42 Constant temperature
• One external differential-pressure sensor.
• Two external pressure sensors.
Fig. 44 Constant differential pressure
28
Page 29
15.4.7 Constant differential temperature
H
Q
t
t
t
t
t
t
t
t
H
Q
Q
set
Q
15.4.8 Constant flow rate
Pump variant Constant differential temperature
TPE3 (D) TPE2 (D)
The pump maintains a constant differential temperature in the system and the pump performance is controlled according to this. See fig. 45.
Fig. 45 Constant differential temperature
This control mode requires either two temperature sensors or one external differential-temperature sensor as shown in the examples below:
Examples
• Factory-fitted temperature sensor and an external temperature sensor (only TPE3 (D)).
Pump variant Constant flow rate
TPE3 (D) ­TPE2 (D)
The pump maintains a constant flow in the system, independently of the head. See fig. 47.
TM05 7954 1713
Fig. 47 Constant flow rate
This control mode requires an external flow sensor as shown below:
Example
• One external flow sensor.
English (US)
TM05 7955 1713
• Two external temperature sensors.
• One external differential-temperature sensor.
Fig. 46 Constant differential temperature
Fig. 48 Constant flow rate
29
Page 30
English (US)
H
Q
L
L
Note
Note
H
Q
H [%]
Q 80 %
100 %
Limited max. curve
15.4.9 Constant level
15.4.10 Constant other value
Pump variant Constant level
TPE3 (D) ­TPE2 (D)
The pump maintains a constant level, independently of the flow rate. See fig. 49.
Fig. 49 Constant level
This control mode requires an external level sensor. The pump can control the level in a tank in two ways:
• as an emptying function where the pump draws the liquid from the tank.
• as a filling function where the pump pumps the liquid into the tank.
See fig. 50. The type of level control function depends on the setting of the
built-in controller. See section 15.13 Controller settings.
Examples
• One external level sensor. – emptying function.
Pump variant Constant other value
TPE3 (D) ­TPE2 (D)
Any other value is kept constant.
15.4.11 Constant curve
Pump variant Constant curve
TPE3 (D) ­TPE2 (D)
You can set the pump to operate according to a constant curve, like an uncontrolled pump. See fig. 51.
You can set the desired speed in % of maximum speed in the range from 25 to 100 %.
TM05 7941 1613
TM05 7957 1713
Fig. 51 Constant curve
Depending on the system characteristic and the duty point, the 100 % setting may be slightly smaller than the pump's actual maximum curve even though the display shows 100 %. This is due to power and pressure limitations built into the pump. The deviation varies according to pump type and pressure loss in the pipes.
• One external level sensor. – filling function.
Fig. 50 Constant level
30
TM05 7913 1613
Fig. 52 Power and pressure limitations influencing the max.
curve
Page 31
15.5 FLOW
Note
Note
H
Q
Q
max
Q
max
Q
limit
25 %
90 %
Setting range
LIMIT

15.7 Analog inputs

Available inputs depending on the functional module fitted in the
Pump variant FLOW
TPE3 (D) TPE2 (D) -
FLOW
LIMIT
• Enable FLOW
•Set FLOW
LIMIT
LIMIT
.
function.
LIMIT
pump:
Function (terminal)
FM 200
(standard)
FM 300
(advanced)
Analog input 1, setup (4) ●● Analog input 2, setup (7) ●● Analog input 3, setup (14) -
English (US)
To set up an analog input, make the settings below.
Function
The analog inputs can be set to these functions:
Not active
Feedback sensor
Ext. setpoint influence
See section 15.15 Setpoint influence
Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
TM05 7908 1613
in the system by the sensor connected to the actual analog input.
Fig. 53 FLOW
The FLOW control modes:
LIMIT
function can be combined with the following
LIMIT
• Prop. press.
Con. diff. press.
Con. diff. temp.
Const. temp.
Const. curve. A flow-limiting function ensures that the flow never exceeds the
entered FLOW The setting range for FLOW
pump. The factory setting of the FLOW
AUTO
ADAPT
See fig. 36.
value.
LIMIT
is 25 to 90 % of the Q
LIMIT
is the flow where the
LIMIT
factory setting meets the maximum curve.
max
of the

15.6 Automatic Night Setback

Pump variant Automatic Night Setback
Unit
Available measuring units:
Parameter Possible units
Pressure ft, psi, bar, m, kPa Pump flow gpm, m
3
/h, l/s, yd3/h
Liquid temperature °F, °C Other parameter %
Electrical signal
Select signal type (0.5 - 3.5 V, 0-5 V*, 0-10 V, 0-20 mA or 4-20 mA).
Sensor range, min. value
Set the minimum value of the connected sensor.
Sensor range, max. value
Set the maximum value of the connected sensor.

15.8 Pt100/1000 inputs

Available inputs depending on the functional module fitted in the pump:
TPE3 (D) TPE2 (D) -
Once you have enabled Automatic Night Setback , the pump automatically changes between normal duty and night setback (duty at low performance).
Changeover between normal duty and night setback depends on the flow-pipe temperature.
The pump automatically changes over to night setback when the built-in sensor registers a flow-pipe temperature drop of more than 18 to 27 °F (10 to 15 °C) within approx. two hours. The temperature drop must be at least 1.8 °F/min (0.1 °C/min).
Changeover to normal duty takes place without a time lag when the temperature has increased by approx. 18 °F (10 °C).
You cannot enable Automatic Night Setback when the pump is in constant-curve mode.
Function (terminal)
Pt100/1000 input 1, setup (17 and 18) - Pt100/1000 input 2, setup (18 and 19) -
Function
The Pt100/1000 inputs can be set to these functions:
Not active
Feedback sensor
Ext. setpoint influence
See section 15.15 Setpoint influence
Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured in the system.
FM 200
(standard)
FM 300
(advanced)
31
Page 32
English (US)

15.9 Digital inputs

Available inputs depending on the functional module fitted in the pump:

15.10 Digital inputs/outputs

Available inputs/outputs depending on the functional module fitted in the pump:
Function (terminal)
Digital input 1, setup (2 and 6) ●● Digital input 2, setup (1 and 9) -
To set up a digital input, make the settings below.
Function
Select one of these functions:
Not active When set to "Not active", the input has no function.
External stop When the input is deactivated (open circuit), the pump will stop.
Min. (minimum speed) When the input is activated, the pump will run at the set min. speed.
Max. (maximum speed) When the input is activated, the pump will run at the set max. speed.
External fault When the input is activated, a timer will be started. If the input is activated for more than 5 seconds, the pump will be stopped and a fault will be indicated.
Alarm resetting When the input is activated, a possible fault indication will be reset.
Dry running When this function has been selected, lack of inlet pressure or water shortage can be detected. When lack of inlet pressure or water shortage (dry running) is detected, the pump will be stopped. The pump cannot restart as long as the input is activated. This requires the use of an accessory, such as these:
– a pressure switch installed on the suction side of the pump – a float switch installed on the suction side of the pump.
Accumulated flow When this function has been selected, the accumulated flow can be registered. This requires the use of a flowmeter which can give a feedback signal as a pulse per defined flow of water. See section 15.17.1 Pulse flow meter setup.
Predefined setpoint digit 1 (applies only to digital input 2) When digital inputs are set to predefined setpoint, the pump will operate according to a setpoint based on the combination of the activated digital inputs. See section 15.15.2 Predefined setpoints.
The priority of the selected functions in relation to each other appears from section 20. Priority of settings.
A stop command will always have the highest priority.
FM 200
(standard)
FM 300
(advanced)
Function (terminal)
Digital input/output 3, setup (10 and 16)
Digital input/output 4, setup (11 and 18)
To set up a digital input/output, make the settings below.
Mode
You can set the digital input/output 3 and 4 to act as digital input or digital output:
Digital input
Digital output.
Function
You can set the digital input/output 3 and 4 to these functions:
Possible functions, digital input/output 3
Function if input Function if output
Not active
External stop
Min.
Max.
External fault
Alarm resetting
Dry running
Accumulated flow*
Predefined setpoint digit 2
* Only TPE2 (D).
Possible functions, digital input/output 4
Function if input Function if output
Not active
External stop
Min.
Max.
External fault
Alarm resetting
Dry running
Accumulated flow*
• Predefined setpoint digit 3
* Only TPE2 (D).
FM 200
(standard)
●●
-
Not active
Ready
Alarm
Operation
Pump running
Warning
Limit 1 exceeded*
Limit 2 exceeded*
Not active
Ready
Alarm
Operation
Pump running
Warning
Limit 1 exceeded*
Limit 2 exceeded*
FM 300
(advanced)
32
Page 33

15.11 Relay outputs

p
p
p
p
ǻS
L1
L1
ǻS

15.13 Controller settings

Function (terminal)
FM 200
(standard)
FM 300
(advanced)
Relay output 1 (NC, C1, NO) ●● Relay output 2 (NC, C2, NO) ●●
The pump incorporates two signal relays for potential-free signalling. See section 22. Signal relays for further information.
You can configure the signal relays to be activated by one of the following incidents:
Ready
Operation
Alarm
Warning
Limit 2 exceeded*
Limit 1 exceeded*
Pump running
Relubricate
Control of external fan
Not active.
* Only TPE2 (D).

15.12 Analog output

Whether the analog output is available or not, depends on the functional module fitted in the pump:
Function (terminal)
FM 200
(standard)
Analog output -
To set up the analog output, make the settings below.
Output signal
0-10 V
0-20 mA
4-20 mA.
Function of analog output
Actual speed
Actual value
Resulting setpoint
Motor load
Motor current
Limit 1 exceeded*
Limit 2 exceeded*
Flow rate
* Only TPE2 (D).
FM 300
(advanced)
Pump variant Controller settings
TPE3 (D) TPE2 (D)
The pumps have a factory default setting of gain (Kp) and integral time (T
).
i
However, if the factory setting is not the optimum setting, you can change the gain and the integral time:
• Set the gain (K
• Set the integral-action time (T 3600 s.
) within the range from 0.1 to 20.
p
) within the range from 0.1 to
i
If you have selected 3600 s, the controller will function as a P controller.
Furthermore, you can set the controller to inverse control. This means that if the setpoint is increased, the speed will be
reduced. In the case of inverse control, set the gain (K the range from -0.1 to -20.
) within
p
Guidelines for setting of PI controller
The tables below show the recommended controller settings:
Differential-pressure
control
K
p
T
i
0.5 0.5
L1 < 16.4 ft (5 m): 0.5
0.5
L1 > 16.4 ft (5 m): 3
L1 > 32.8 ft (10 m): 5
L1 = Distance ft (m) between pump and sensor.
English (US)
33
Page 34
English (US)
L2
t
L2
t
t
L2
t
t
t
L2
Q
p
p
Note
Note
L
L
Max. speed (fixed)
User-set max. speed
Operating range
User-set min. speed
Min. speed (fixed)
24 %
12 %
0 %
67 %
100 %
K
p
Temperature control
Heating
system
Cooling
1)
system
2)
0.5 -0.5 10 + 5L2
0.5 -0.5 30 + 5L2
1)
In heating systems, an increase in pump performance will result in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance will result in a drop in temperature at the sensor.
L2 = Distance ft (m) between heat exchanger and sensor.
Differential-temperature
control
K
p
-0.5 10 + 5L2
Level control K
T
i
p
T
i
-2.5 100
2.5 100
General rules of thumb
If the controller is too slow-reacting, increase K
.
p
If the controller is hunting or unstable, dampen the system by reducing K
or increasing Ti.
p

15.14 Operating range

Pump variant Operating range
T
i
TPE3 (D) TPE2 (D)
Set the operating range as follows:
• Set the minimum speed within the range from fixed minimum speed to user-set maximum speed.
• Set the maximum speed within the range from user-set minimum speed to fixed maximum speed.
The range between the user-set minimum and maxumum speeds is the operating range. See fig. 54.
L2 = Distance ft (m) between heat exchanger and sensor.
Flow control K
0.5 0.5
Constant-pressure control K
0.5 0.5
0.1 0.5
Speeds below 25 % may result in noise from the shaft seal.
p
p
T
i
T
i
TM00 6785 5095
Fig. 54 Example of min. and max. settings
34
Page 35

15.15 Setpoint influence

Note
Note
100
0
0
17.4
29
[PSI]
Setpoint influence [%]
External setpoint signal [%]
Actual
input
signal
Actual setpoint
Setpoint
Upper value
Lower value
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
Normal
Min. or
Stop
15.15.1 External setpoint influence
Pump variant Setpoint influence
TPE3 (D) TPE2 (D)
You can influence the setpoint by an external signal, either via one of the analog inputs or, if you fit an advanced functional module, via one of the Pt100/1000 inputs.
Before you can enable the " of the analog inputs or Pt100/1000 inputs to "
External setpoint function
See sections 15.7 Analog inputs and
15.8 Pt100/1000 inputs.
If more than one input has been set up for setpoint influence, the function will select the analog input with the lowest number, for example "Analog input 2", and ignore the other inputs, for example "Analog input 3" or "Pt100/1000 input 1".
Example
See fig. 55. At a lower sensor value of 0 psi, a set setpoint of 29 psi and an
external setpoint of 60 %, the actual setpoint is 0.60 x (29 - 0) + 0 = 17.4 psi.
Actual setpoint = actual input signal x (setpoint - lower value) + lower value.
0 100
Digital inputs
".
", set one
You can select these functions:
Not active When set to "Not active", the setpoint will not be influenced from any external function.
Linear function The setpoint is influenced linearly from 0 to 100 %. See fig. 56.
Fig. 56 Linear function
•"Linear with Stop" and "Linear with Min."
Linear with Stop
In the input signal range from 20 to 100 %, the setpoint is influenced linearly. If the input signal is below 10 %, the pump will change to operating mode "Stop". If the input signal is increased above 15 %, the operating mode will be changed back to "Normal". See fig. 57.
Linear with Min.
In the input signal range from 20 to 100 %, the setpoint is influenced linearly. If the input signal is below 10 %, the pump will change to operating mode "Min.". If the input signal is increased above 15 %, the operating mode will be changed back to "Normal". See fig. 57.
English (US)
TM05 6280 4612TM05 6281 4612
Fig. 55 Example of setpoint influence
The table below gives an overview of the types of setpoint influence and the availability depending on pump type.
Type of setpoint influence
Not active ●●
Linear function ●● Linear with Stop -
Linear with Min. ●● Inverse function - Inverse with Stop - Inverse with Min. - Influence table - Influence table with Stop at Min. - Influence table with Stop at Max. -
Pump type
TPE3 (D) TPE2 (D)
TM06 0854 1014
Fig. 57 "Linear with Stop" and "Linear with Min."
35
Page 36
English (US)
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
Normal
Min. or
Stop
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
Normal
Min. or
Stop
Inverse function The setpoint is influenced inversely from 0 to 100 %. See fig. 58.
Fig. 58 Inverse function
•"Inverse with Stop" and "Inverse with Min."
Inverse with Stop
In the input signal range from 0 to 80 %, the setpoint is influenced inversely. If the input signal is above 90 %, the pump will change to operating mode "Stop". If the input signal is reduced below 85 %, the operating mode will be changed back to "Normal". See fig. 59.
Inverse with Min.
In the input signal range from 0 to 80 %, the setpoint is influenced inversely. If the input signal is above 90 %, the pump will change to operating mode "Min.". If the input signal is reduced below 85 %, the operating mode will be changed back to "Normal". See fig. 59.
Influence table
The setpoint is influenced by a curve made out of two to eight points. There will be a straight line between the points and a horizontal line before the first point and after the last point.
TM05 6283 4612TM05 6283 4612
TM05 6284 4612TM05 6285 4612
Fig. 60 Influence table
Influence table with Stop at Min. The setpoint is influenced by a curve made out of two to eight points. There will be a straight line between the points and a horizontal line before the first point and after the last point. If the input signal is below 10 %, the pump will change to operating mode "Stop". If the input signal is increased above 15 %, the operating mode will be changed back to "Normal". See fig. 61.
Fig. 59 "Inverse with Stop" and "Inverse with Min."
36
Fig. 61 Influence table with Stop at Min.
Page 37
Influence table with Stop at Max.
100
0
100
20 40 60 80
Setpoint influence [%]
External input [%]
Normal
Min. or
Stop
Note
Note
H
T [°F]
30 %
68 122 176
T [°C]
20 50 80
100 %
H
actual
T
actual
H
Q
The setpoint is influenced by a curve made out of two to eight points. There will be a straight line between the points and a horizontal line before the first point and after the last point. If the input signal is above 90 %, the pump will change to operating mode "Min.". If the input signal is reduced below 85 %, the operating mode will be changed back to "Normal". See fig. 62.
Fig. 62 Influence table with Stop at Max.
15.15.2 Predefined setpoints
15.15.3 Temperature influence
Pump variant Temperature influence
TPE3 (D) TPE2 (D) -
When you enable this function in proportional- or constant-pressure control mode, the setpoint for head will be reduced according to the liquid temperature.
Temperature influence can be set to function at liquid temperatures below +176 °F or +122 °F (80 °C or 50 °C). These temperature limits are called T
. The setpoint is
max.
reduced in relation to the head set (= 100 %) according to the characteristics below.
TM05 6286 4612
Fig. 63 Select the measured parameter of Pt100/1000 input 2
English (US)
TM05 7946 1613
Pump variant Predefined setpoints
TPE3 (D) TPE2 (D)
Seven predefined setpoints can be set and activated by combining the input signals to digital inputs 2, 3 and 4 as shown in the table below.
Digital inputs
Setpoint
234
0 0 0 Normal setpoint 100Predefined setpoint 1 010Predefined setpoint 2 110Predefined setpoint 3 001Predefined setpoint 4 101Predefined setpoint 5 011Predefined setpoint 6 111Predefined setpoint 7
In the above example, T selected.
The actual liquid temperature T to be reduced from 100 % to H
= +176 °F (+80 °C) has been
max.
causes the setpoint for head
actual
.
actual
The temperature influence function requires the following:
• Proportional-pressure, constant-pressure or constant-curve control mode.
• Pump installed in flow pipe.
• System with flow-pipe temperature control.
Temperature influence is suitable for the following systems:
• Systems with variable flows (for example two-pipe heating systems) in which the enabling of the temperature influence function will ensure a further reduction of the pump performance in periods with small heating demands and consequently a reduced flow-pipe temperature.
• Systems with almost constant flows (for example one-pipe heating systems and underfloor heating systems), in which variable heating demands cannot be registered as changes in the head as is the case with two-pipe heating systems. In such systems, you can only adjust the pump performance by enabling the temperature influence function.
Selection of T
max.
In systems with a dimensioned flow-pipe temperature of:
• up to and including +131 °F (+55 °C), select T
• above +131 °F (+55 °C), select T
= +122 °F (+50 °C)
max.
= +176 °F (80 °C).
max.
You cannot use the temperature influence function in air-conditioning and cooling systems.
37
Page 38
English (US)
Rated
Ramp-up Ramp-down
Speed
Time
Minimum
Initial ramp Final ramp
Maximum

15.16 Monitoring functions

15.16.1 Limit-exceeded function
Pump variant Limit-exceeded function
TPE3 (D) ­TPE2 (D)
This function can monitor set limits of analog values. It will react if the values exceed the limits. Each limit can be set as a maximum or minimum value. For each of the monitored values, you must define a warning limit and an alarm limit.
The function makes it possible to monitor two different locations in a pump system at the same time. For instance the pressure at a consumer and the pump discharge pressure. This ensures that the discharge pressure does not reach a critical value.
If the value exceeds the warning limit, a warning is given. If the value exceeds the alarm limit, the pumps will be stopped.
You can set a delay between the detection of an exceeded limit and the activation of a warning or an alarm. You can also set a delay for resetting a warning or an alarm.
You can reset a warning automatically or manually. Furthermore, you canset whether the system is to restart
automatically after an alarm, or if the alarm must be reset manually. Restarting can be delayed by an adjustable time. You can also set a startup delay ensuring that the system reaches a steady state before the function becomes active.
15.17.2 Ramps
Pump variant Ramps
TPE3 (D) ­TPE2 (D)
The setting of ramps is only relevant in the case of constant-curve operation.
The ramps determine how quickly the motor can accelerate and decelerate, respectively, during start/stop or setpoint changes.
The following can be set:
• acceleration time, 0.1 to 300 s
• deceleration time, 0.1 to 300 s.
The times apply to the acceleration from stop to rated speed and the deceleration from rated speed to stop, respectively.
At short deceleration times, the deceleration of the motor may depend on load and inertia as there is no possibility of actively braking the motor.
If the power supply is switched off, the deceleration of the motor will only depend on load and inertia.

15.17 Special functions

15.17.1 Pulse flow meter setup
Pump variant Pulse flow meter setup
TPE3 (D) ­TPE2 (D)
You can connect an external pulse flowmeter to one of the digital inputs in order to register the actual and accumulated flows. Based on this, you can also calculate the specific energy btu/lb
3
(kWh/m To enable a pulse flowmeter, set one of the digital-input functions
to "Accumulated flow" and set the pumped volume per pulse. See section 15.9 Digital inputs.
).
TM03 9439 0908
Fig. 64 Ramp-up and ramp-down

15.18 Communication

15.18.1 Pump number
Pump variant Pump number
TPE3 (D) TPE2 (D)
You can allocate a unique number to the pump. This makes it possible to distinguish between pumps in connection with bus communication.
15.18.2 Enable/disable radio communication
Pump variant Pump number
TPE3 (D) TPE2 (D)
You can set the radio communication to either enabled or disabled.
38
Page 39

15.19 General settings

Note
Note

16. Assist

Pump variant General settings
TPE3 (D) TPE2 (D)
15.19.1 Language
A number of languages is available. Measuring units are automatically changed according to selected
language.
15.19.2 Units
In this menu you can select between US and SI units. The setting can be made generally for all parameters or customized for each individual parameter.
15.19.3 Enable/disable settings
In this display, you can disable the possibility of making settings for protective reasons.
To unlock the pump and allow settings, press and simultaneously for at least 5 seconds.
15.19.4 Delete history
In this menu you can delete the following historic data:
• Delete work log.
• Delete heat energy data.
• Delete energy consumption.
15.19.5 Define Home display
In this menu you can select whether the "Home" display should show various user-defined parameters or a graphical illustration of a performance curve with the actual duty point of the pump.
15.19.6 Display settings
In this menu you can adjust the display brightness and define whether or not the display should turn off if no buttons have been activated for a period of time.
15.19.7 Store actual settings
In this menu you can store the actual settings for later use.
15.19.8 Recall stored settings
In this menu you can recall the last stored settings that the pump will then use.
15.19.9 Run startup guide
The startup guide will guide you through the general settings of the pump.

16.1 Multi-pump setup

Pump variant Multi-pump setup
TPE3 (D) TPE2 (D)
The multipump function enables the control of single-head pumps connected in parallel or twin-head pumps without the use of external controllers. The pumps in a multipump system communicate with each other via the wireless GENIair connection or the wired GENI connection.
You set up a multipump system via a selected pump, i.e. the master pump (first selected pump). You can connect all Grundfos pumps with a wireless GENIair connection to the multipump system.
The multipump functions are described in the following sections.
16.1.1 Alternating operation
Only one pump is operating at a time. The change from one pump to the other depends on time or
energy. If a pump fails, the other pump will take over automatically.
Pump system:
• Twin-head pump.
• Two single-head pumps connected in parallel. The pumps must be of the same type and size. Each pump requires a non-return valve in series with the pump.
16.1.2 Backup operation
One pump is operating continuously. The backup pump is operated at intervals to prevent seizing up. If the duty pump stops due to a fault, the backup pump will start automatically.
Pump system:
• Twin-head pump.
• Two single-head pumps connected in parallel. The pumps must be of the same type and size. Each pump requires a non-return valve in series with the pump.
16.1.3 Cascade operation
Cascade operation ensures that the pump performance is automatically adapted to the consumption by switching pumps on or off. The system thus runs as energy-efficiently as possible with a constant pressure and a limited number of pumps.
When a twin-head pump is running in constant-pressure control mode, the second pump head will start at 90 % and stop at 50 % performance.
All pumps in operation will run at equal speed. Pump changeover is automatic and depends on energy, operating hours and fault.
Pump system:
• Twin-head pump.
• Two to four single-head pumps connected in parallel. The pumps must be of the same type and size. Each pump requires a non-return valve in series with the pump.
• The control mode must be set to "Const. pressure" or "Const. curve".
English (US)
39
Page 40
English (US)
H
Q
H
Q
H
Q
Hset
Hset
2
H
Q

17. Selection of control mode

System application Select this control mode
AUTO
ADAPT
Recommended for most heating systems, especially in systems with relatively large pressure losses in the distribution pipes. See description under proportional pressure. In replacement situations where the proportional-pressure duty point is unknown. The duty point has to be within the AUTO automatically makes the necessary adjustment to the actual system characteristic. This setting ensures minimum energy consumption and low noise level from valves, which reduces operating costs and increases comfort.
operating range. During operation, the pump
ADAPT
The FLOW This control mode is suitable for systems where you want a maximum flow limit, FLOW The pump continuously monitors and adjusts the flow, thus ensuring that the selected FLOW
LIMIT
Main pumps in boiler applications where a steady flow through the boiler is required. No extra
control mode is a combination of AUTO
ADAPT
is not exceeded.
ADAPT
and FLOW
LIMIT
.
.
LIMIT
energy is used for pumping too much liquid into the system. In systems with mixing loops, you can use the control mode to control the flow in each loop. Benefits:
• Enough water for all loops at peak load conditions if each loop has been set to the right maximum flow.
• The dimensioned flow for each zone (required heat energy) is determined by the flow from the pump. This value can be set precisely in the FLOW throttling valves.
control mode without the use of pump
ADAPT
• When the flow is set lower than the balancing valve setting, the pump will ramp down instead of losing energy by pumping against a balancing valve.
• Cooling surfaces in air-conditioning systems can operate at high pressure and low flow.
In systems with relatively large pressure losses in the distribution pipes and in air-conditioning and cooling systems.
• Two-pipe heating systems with thermostatic valves and
– very long distribution pipes – strongly throttled pipe balancing valves – differential-pressure regulators – large pressure losses in those parts of the system through which the total quantity of water
flows (for example boiler, heat exchanger and distribution pipe up to the first branching).
• Primary circuit pumps in systems with large pressure losses in the primary circuit.
• Air-conditioning systems with
– heat exchangers (fan coils) – cooling ceilings – cooling surfaces.
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and
– dimensioned for natural circulation – small pressure losses in those parts of the system through which the total quantity of water
flows (for example boiler, heat exchanger and distribution pipe up to the first branching) or
– modified to a high differential temperature between flow pipe and return pipe (for example
district heating).
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing valves.
• Primary circuit pumps in systems with small pressure losses in the primary circuit.
FLOW
ADAPT
Proportional pressure
Constant differential pressure
40
Page 41
System application Select this control mode
H
Q
H
Q
Q
set
H
Q
H
Q
Constant temperature and constant
In systems with a fixed system characteristic. Examples:
• one-pipe heating systems
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
You can use FLOW
with advantage to control the maximum circulation flow.
LIMIT
differential temperature
English (US)
If you install an external controller, the pump is able to change from one constant curve to another, depending on the value of the external signal. You can also set the pump to operate according to the maximum or minimum curve, like an uncontrolled pump:
• You can use the maximum curve mode in periods in which a maximum flow is required. This operating mode is for instance suitable for hot-water priority.
• You can use the minimum curve mode in periods in which a minimum flow is required. This operating mode is for instance suitable for manual night setback if you do not want Automatic Night Setback.
In systems requiring a constant flow, independently of pressure drop. Examples:
• chillers for air-conditioning
• heating surfaces
• cooling surfaces.
In systems requiring a constant tank level, independently of the flow rate. Examples:
• process water tanks
• boiler condensate tanks.
Constant curve
Constant flow rate
Constant level
In systems with pumps operating in parallel. The multipump function enables the control of single-head pumps connected in parallel (two to four pumps) and twin-head pumps without the use of external controllers. The pumps in a multipump system communicate with each other via the wireless GENIair connection or the wired GENI connection.
"Assist" menu
"Multi-pump setup"
41
Page 42
English (US)
Note
Note

18. Changing the position of the control panel

You can turn the control panel 180 °. Follow the instructions below.
1. Loosen the four screws (TX25) holding the terminal box cover.
Fig. 65 Loosening the screws
2. Remove the terminal box cover.
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
Fig. 68 Turning the plastic cover
5. Reposition the plastic cover correctly on the four rubber
TM05 5351 3612TM05 5352 3612TM05 5353 3612
pins (pos. C). Make sure that the locking tabs (pos. A) are placed correctly.
TM05 5354 3612TM05 5355 3612TM05 5356 3612
Fig. 66 Removing the terminal box cover
3. Press and hold in the two locking tabs (pos. A) while gently lifting the plastic cover (pos. B).
Fig. 67 Lifting the plastic cover
Fig. 69 Re-positioning the plastic cover
6. Fit the terminal box cover, and make sure that it is also turned 180 ° so that the buttons on the control panel are aligned with the buttons on the plastic cover. Tighten the four screws (TX25) with 3.69 lbf-ft (5 Nm).
Fig. 70 Fitting the terminal box cover
42
Page 43

19. Bus signal

Note
Note
The motor enables serial communication via an RS-485 input. The communication is carried out according to the Grundfos GENIbus protocol and enables connection to a building management system or another external control system.
Via a bus signal, you can remote-set motor operating parameters, such as setpoint and operating mode. At the same time, the motor can, via the bus, provide status information about important parameters, such as actual value of control parameter, input power and fault indications.
Contact Grundfos for further information.
If you use a bus signal, the number of settings available via the Grundfos GO Remote will be reduced.

20. Priority of settings

You can always set he motor to operation at maximum speed or to stop with the Grundfos GO Remote.
If you enable two or more functions at the same time, the motor will operate according to the function with the highest priority.
Example: If, via the digital input, the motor has been set to maximum speed, the motor control panel or the Grundfos GO Remote can only set the motor to "Manual" or "Stop".
The priority of the settings appears from the table below:
English (US)
Priority Start/stop button
1 Stop 2 Stop* 3 Manual 4 Max. speed* 5 Stop 6 Stop 7 Max. speed 8 Min. speed
9 Start 10 Max. speed 11 Min. speed 12 Min. speed 13 Start 14 Start
* If the bus communication is interrupted, the motor will resume its previous operating mode, for example "Stop", selected with the
Grundfos GO Remote or on the motor control panel.
Grundfos GO Remote or
control panel on motor
Digital input Bus communication
43
Page 44
English (US)
A

21. Grundfos Eye

The Grundfos Eye indicate the operating condition of the motor on the control panel. See fig. 71, pos. A.
TM05 5993 4312
Fig. 71 Grundfos Eye
Grundfos Eye Indication Description
No lights on.
Two opposite green indicator lights rotating in the direction of rotation of the motor when seen from the non-drive end.
Two opposite green indicator lights permanently on.
One yellow indicator light rotating in the direction of rotation of the motor when seen from the non-drive end.
One yellow indicator light permanently on.
Two opposite red indicator lights flashing simultaneously.
The green indicator light in the middle flashes quickly four times.
The green indicator light in the middle flashes continuously.
The green indicator light in the middle is permanently on.
The green indicator light in the middle flashes quickly while the Grundfos Go Remote is exchanging data with the motor. It will take a few seconds.
Power off. Motor not running.
Power on. Motor running.
Power on. Motor not running.
Warning. Motor running.
Warning. Motor stopped.
Alarm. Motor stopped.
Remote control with the Grundfos GO Remote via radio. The motor is trying to communicate with the Grundfos GO Remote. The motor in question is highlighted in the Grundfos GO Remote display to inform the user of the location of the motor.
When the motor in question is selected in the Grundfos GO Remote menu, the green indicator light in the middle will flash continuously. Press on the motor control panel to allow remote control and data exchange via the Grundfos GO Remote.
Remote control with the Grundfos GO Remote via radio. The motor is communicating with the Grundfos GO Remote via radio connection.
Remote control with the Grundfos GO Remote via infrared light. The motor is receiving data from the Grundfos GO Remote via infrared communication.
44
Page 45

22. Signal relays

NCNOCNCNOCNCNOCNCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNOCNCNO
C
C
NO NC
C
NO NC
NCNOCNCNOCNCNO
C
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
NCNOCNCNOCNCNO
C
C
NO NC
NCNO
C
The motor has two outputs for potential-free signals via two internal relays.
The signal outputs can be set to "Operation", "Pump running", "Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table below:
English (US)
Description Grundfos Eye
Power off.
Off
Pump running in "Normal" mode.
Green, rotating
Pump running in "Manual" mode.
Green, rotating
Pump in operating mode "Stop".
Green, steady
Warning, but the pump is running.
Yellow, rotating
Contact position for signal relays when activated
Operation
Pump
running
Ready Alarm Warning
Operating mode
-
Normal, Min. or Max.
Manual
Stop
Normal, Min.
or Max.
Warning, but the pump is running in "Manual" mode.
Warning, but the pump was stopped via "Stop" command.
Alarm, but the pump is running.
Alarm, but the pump is running in "Manual" mode.
Pump stopped due to an alarm.
Manual
Yellow, rotating
Stop
Yellow, steady
Normal, Min. or Max.
Red, rotating
Manual
Red, rotating
Stop
Red, flashing
45
Page 46
English (US)

23. Maintenance and service

Warnin g
Before starting work on the pump, make sure that
the power supply has been switched off for at
least 5 minutes. Make sure that the power supply
cannot be accidentally switched on.
Warnin g
Make sure that the escaping water does not
cause injury to persons or damage to the
equipment.
Warnin g If the pump is used for a liquid which is injurious
to health, it will be classified as contaminated. In such cases, the proper precautions must be taken to avoid injury to health when operating or working on the pump.

23.1 Maintenance

23.1.1 Pump
The pump is maintenance-free. If the pump is to be drained for a long period of inactivity, inject a
few drops of silicone oil on the shaft between the motor stool and the coupling. This will prevent the shaft seal faces from sticking.
23.1.2 Motor
The motor must be checked at regular intervals. It is important to keep the motor clean in order to ensure adequate ventilation. If the pump is installed in a dusty environment, clean and check the pump regularly.

23.2 Service

If Grundfos is requested to service the pump, it must be cleaned before it is returned.
If proper cleaning is not possible, all relevant information about the pumped liquid must be provided.
If the above is not fulfilled, Grundfos can refuse to accept the pump for service.
Possible costs of returning the pump are to be paid by the customer.
23.2.1 Integral shaft/coupling
TPE2 and TPE3 pumps have integral shaft/coupling. We recommend that you do not remove the motor.
If the motor has been removed, it is necessary to remove the motor stool in order to refit the motor correctly. Otherwise the shaft seal may be damaged.
23.2.2 Blanking flanges
For twin-head pumps, a blanking flange with a pump housing gasket is available. See fig. 72.
Fig. 72 Fitting the blanking flange
If one pump requires service, the blanking flange is fitted to allow the other pump to continue operating.
TM05 7921 1613
46
Page 47

24. Fault finding

Warnin g
Before removing the terminal box cover or
removing/dismantling the pump, make sure that
the power supply has been switched off for at
least 5 minutes. Make sure that the power supply
cannot be accidentally switched on.
Warnin g
Make sure that the escaping water does not
cause injury to persons or damage to the
equipment.
Fault Cause/remedy
1. Motor does not run when started. a) Supply failure. b) Fuses blown. c) Motor defective.
2. Motor alarm when the power supply is switched on. a) Supply failure. b) Cable connection loose or faulty. c) Motor winding defective. d) Pump mechanically blocked.
3. Occasional motor alarm. a) Supply voltage periodically too low or too high. b) Differential pressure across pump too low.
4. No motor alarm, but the pump does not run. a) Check the power supply. b) Check fuses.
5. Pump capacity not constant. a) Pump inlet pressure too low. b) Suction pipe/pump partly blocked by impurities. c) Pump draws in air.
6. Pump runs but delivers no water. a) Suction pipe/pump blocked by impurities. b) Foot or non-return valve blocked in closed position. c) Leakage in suction pipe. d) Air in suction pipe or pump.
7. Pump runs backwards when switched off.* a) Leakage in suction pipe. b) Foot or non-return valve defective. c) Foot or non-return valve blocked in open or partly open position.
8. Leakage in shaft seal. a) Shaft seal defective.
9. Noise. a) Pump is cavitating. b) Pump does not rotate freely (frictional resistance) because of incorrect
pump shaft position. c) Resonance in the installation. d) Foreign bodies in the pump.
English (US)
* In twin-head pump installations, the backup pump will often rotate slowly.
47
Page 48
English (US)
Caution

25. Megging

Megging of an installation incorporating MGE motors is not allowed, as the built-in electronics may be damaged.

26. Technical data, single-phase motors

26.1 Supply voltage

• 1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE. Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Recommended fuse size
Motor size
[hp (kW)]
Min.
[A]
Max.
[A]
0.25 - 1.0 (0.12 - 0.75) 6 10
1.5 - 2.0 (1.1 - 1.5) 10 16
You can use standard as well as quick-blow or slow-blow fuses.

26.2 Leakage current

Earth leakage current < 3.5 mA (AC supply). Earth leakage current < 10 mA (DC supply). The leakage currents are measured in accordance with
EN 61800-5-1:2007.

27. Technical data, three-phase motors

27.1 Supply voltage

• 3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE. Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Recommended fuse size
Motor size
[hp (kW)]
0.25 - 1.5 (0.12 - 1.1) 6 6
2.0 - 3.0 (1.5 - 2.2) 6 10
Standard as well as quick-blow or slow-blow fuses may be used.

27.2 Leakage current

Motor size
[hp (kW)]
1.0 - 3.0 (0.75 - 2.2)
(supply voltage < 400 V)
1.0 - 3.0 (0.75 - 2.2)
(supply voltage > 400 V)
The leakage currents are measured in accordance with EN 61800-5-1:2007.
Min.
[A]
Leakage current
[mA]
< 3.5
< 5
Max.
[A]

28. Inputs/outputs

Ground reference (GND)
All voltages refer to GND. All currents return to GND.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in severely reduced operating reliability and motor life:
Relay 1: Maximum contact load: 250 VAC, 2 A or 30 VDC, 2 A. Relay 2: Maximum contact load: 30 VDC, 2 A. GENI terminals: -5.5 to 9.0 VDC or < 25 mADC. Other input/output terminals: -0.5 to 26 VDC or < 15 mADC.
Digital inputs (DI)
Internal pull-up current > 10 mA at V Internal pull-up to 5 VDC (currentless for V Certain low logic level: V Certain high logic level: V
< 1.5 VDC.
i
> 3.0 VDC.
i
Hysteresis: No. Screened cable: 20-16 AWG (0.5 - 1.5 mm Maximum cable length: 1640 ft (500 m)
Open-collector digital outputs (OC)
Current sinking capability: 75 mADC, no current sourcing. Load types: Resistive or/and inductive. Low-state output voltage at 75 mADC: Max. 1.2 VDC. Low-state output voltage at 10 mADC: Max. 0.6 VDC. Overcurrent protection: Yes. Screened cable: 20-16 AWG (0.5 - 1.5 mm Maximum cable length: 1640 ft (500 m)
Analog inputs (AI)
Voltage signal ranges:
• 0.5 - 3.5 VDC, AL AU.
• 0-5 VDC, AU.
•0-10 VDC, AU. Voltage signal: R
> 100 kΩ at 77 °F (+25 °C).
i
Leak currents may occur at high operating temperatures. Keep the source impedance low.
Current signal ranges:
• 0-20 mADC, AU.
• 4-20 mADC, AL AU. Current signal: R
= 292 Ω.
i
Current overload protection: Yes. Change to voltage signal. Measurement tolerance: - 0/+ 3 % of full scale (max.-point
coverage). Screened cable: 20-16 AWG (0.5 - 1.5 mm Maximum cable length: 1640 ft (500 m) (excl. potentiometer). Potentiometer connected to +5 V, GND, any AI: Use maximum 10 kΩ. Maximum cable length: 328 ft (100 m).
= 0 VDC.
i
> 5 VDC).
i
2
).
2
).
2
).
48
Page 49
Analog output (AO)
Current sourcing capability only. Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes. Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes. Tolerance: - 0/+ 4 % of full scale (max-point coverage). Screened cable: 20-16 AWG (0.5 - 1.5 mm Maximum cable length: 1640 ft (500 m)
Pt100/1000 inputs (PT)
Temperature range:
• Minimum -22 °F (-30 °C) (88 Ω/882 Ω).
• Maximum 356 °F (+180 °C) (168 Ω/1685 Ω). Measurement tolerance: ± 2.7 °F (1.5 °C). Measurement resolution: < 0.54 °F (0.3 °C). Automatic range detection (Pt100 or Pt1000): Yes. Sensor fault alarm: Yes. Screened cable: 20-16 AWG (0.5 - 1.5 mm Use Pt100 for short wires. Use Pt1000 for long wires.
LiqTec sensor inputs*
Use Grundfos LiqTec sensor only. Screened cable: 20-16 AWG (0.5 - 1.5 mm
Power supplies (+5 V, +24 V) +5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC (sourcing only).
• Overload protection: Yes.
•Sensor.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC (sourcing only).
• Overload protection: Yes.
Digital outputs (relays)
Potential-free changeover contacts. Minimum contact load when in use: 5 VDC, 10 mA. Screened cable: 20-12 AWG (0.5 - 2.5 mm Maximum cable length: 1640 ft (500 m)
Bus input
Grundfos GENIbus protocol, RS-485. Screened 3-core cable: 20-16 AWG (0.5 - 1.5 mm Maximum cable length: 1640 ft (500 m)
2
).
2
).
2
).
2
).
2
).

29. Other technical data

EMC (electromagnetic compatibility)
EN 61800-3. Residential areas, unlimited distribution, corresponding to
CISPR 11, class B, group 1. Industrial areas, unlimited distribution, corresponding to
CISPR 11, class A, group 1. Contact Grundfos for further information.
Enclosure class
Standard: IP55 (IEC 34-5). Optional: IP66 (IEC 34-5).
Insulation class
F (IEC 85).

29.1 Torques

Terminal Thread size
L1, L2, L3, L, N M4 1.3 (1.8) NC, C1, C2, NO M2.5 0.4 (0.5) 1 to 26 and A, Y, B M2 0.4 (0.5)
Max. torque
[lbf-ft (Nm)]

29.2 Sound pressure level

The sound pressure level will be below 70 dB

30. Disposal

This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
The waste battery should be disposed of through the local collective services. If in doubt, contact your local Grundfos company.
Subject to alterations.
English (US)
49
Page 50

Appendix

Note
Note
Stop
Identification numbers
Identification numbers
Appendix

1. Installation in the USA and Canada

In order to maintain the cURus approval, follow these additional installation instructions. The UL approval is according to UL 1004-1.

1.1 Electrical codes

For USA
This product complies with the Canadian Electrical Code and the US National Electrical Code.
This product has been tested according to the national standards for Electronically Protected Motors:
CSA 22.2 100.04: 2009 (applies to Canada only). UL 1004-1: June 2011 (applies to USA only).
Pour le Canada Codes de l'électricité
Ce produit est conforme au Code canadien de l'électricité et au Code national de l'électricité américain.
Ce produit a été testé selon les normes nationales s'appliquant aux moteurs protégés électroniquement:
CSA 22.2 100.04: 2009 (s'applique au Canada uniquement). UL 1004-1: Juin 2011 (s'applique aux États-Unis uniquement).

1.2 Radio communication

For USA
This device complies with part 15 of the FCC rules and RSS210 of IC rules.
Operation is subject to the following two conditions:
• This device may not cause interference.
• This device must accept any interference, including interference that may cause undesired operation of the device.
Pour le Canada Communication radio
Ce dispositif est conforme à la partie 15 des règles de la FCC et aux normes RSS210 de l'IC.
Son fonctionnement est soumis aux deux conditions suivantes:
• Ce dispositif ne doit pas provoquer de brouillage préjudiciable.
• Il doit accepter tout brouillage reçu, y compris le brouillage pouvant entraîner un mauvais fonctionnement.

1.3 Identification numbers

For USA
Grundfos Holding A/S Contains FCC ID: OG3-RADIOM01-2G4.
For Canada
Grundfos Holding A/S Model: RADIOMODULE 2G4 Contains IC: 10447A-RA2G4M01.
Pour le Canada Numéros d'identification
Grundfos Holding A/S Modèle: RADIOMODULE 2G4 Contient IC: 10447A-RA2G4M01.
Location of identification numbers
Fig. 1 Identification numbers
Fig. 2 Identification numbers

1.4 Electrical connection

1.4.1 Conductors
Use 140/167 °F (60/75 °C) copper conductors only.
1.4.2 Torques
Maximum tightening torques for the terminals can be found in section 29.1 Torques, page 50.
1.4.3 Line reactors
Maximum line reactor size must not exceed 1.5 mH.
1.4.4 Fuse size/circuit breaker
If a short-circuit occurs, the pump can be used on a mains supply delivering not more than 5000 RMS symmetrical amperes, 600 V maximum.
Motor size
[hp (kW)]
0.50 to 3.0
(0.25 to 2.2)
Fuses
When the motor is protected by fuses, they must be rated for 480 V. Maximum sizes are stated in the table above.
Motors up to and including 3.0 hp (2.2 kW) require class K5 UR fuses.
Circuit breaker
When the pump is protected by a circuit breaker, this must be rated for a maximum voltage of 480 V. The circuit breaker must be of the "inverse time" type.
The interrupting rating (RMS symmetrical amperes) must not be less than the values stated in the table above.
1.4.5 Overload protection
Degree of overload protection provided internally by the drive, in percent of full-load current: 102 %.
Fuse size Circuit breaker type/model
25 A 25 A / inverse time
TM05 7572 1213TM05 7573 1213
50
Subject to alterations.
Page 51

Appendix

US: Inlet pressure stated in bar relative pressure (pressure gauge value measured on the suction side of the pump)
Pump type
p [psi (bar)]
68 °F (20 °C) 140 °F (60 °C) 194 °F (90 °C) 230 °F (110 °C) 248 °F (120 °C) 248 °F (120 °C)
TPE2, TPE3 (D) 40-80 1.5 (0.1) 1.5 (0.1) 2.9 (0.2) 13.1 (0.9) 21.8 (1.5) 45 (3.1) TPE2 (D), TPE3 (D) 40-120 1.5 (0.1) 1.5 (0.1) 2.9 (0.2) 13.1 (0.9) 21.8 (1.5) 45 (3.1) TPE2 (D), TPE3 (D) 40-150 1.5 (0.1) 1.5 (0.1) 7.3 (0.5) 17.4 (1.2) 26.1 (1.8) 49.3 (3.4) TPE2 (D), TPE3 (D) 40-180 1.5 (0.1) 1.5 (0.1) 8.7 (0.6) 18.9 (1.3) 27.6 (1.9) 50.8 (3.5) TPE2 (D), TPE3 (D) 40-200 1.5 (0.1) 2.9 (0.2) 10.2 (0.7) 20.3 (1.4) 29 (2.0) 52.2 (3.6) TPE2 (D), TPE3 (D) 40-240 1.5 (0.1) 4.4 (0.3) 11.6 (0.8) 21.8 (1.5) 30.5 (2.1) 53.7 (3.7) TPE2 (D), TPE3 (D) 50-60 1.5 (0.1) 1.5 (0.1) 7.3 (0.5) 17.4 (1.2) 26.1 (1.8) 49.3 (3.4) TPE2 (D), TPE3 (D) 50-80 1.5 (0.1) 4.4 (0.3) 11.6 (0.8) 21.8 (1.5) 30.5 (2.1) 53.7 (3.7) TPE2 (D), TPE3 (D) 50-120 5.8 (0.4) 8.7 (0.6) 16 (1.1) 26.1 (1.8) 34.8 (2.4) 58 (4.0) TPE2 (D), TPE3 (D) 50-150 8.7 (0.6) 11.6 (0.8) 18.9 (1.3) 29 (2.0) 37.7 (2.6) 60.9 (4.2) TPE2 (D), TPE3 (D) 50-180 10.2 (0.7) 13.1 (0.9) 20.3 (1.4) 30.5 (2.1) 39.2 (2.7) 62.4 (4.3) TPE2 (D), TPE3 (D) 50-200 13.1 (0.9) 16 (1.1) 23.2 (1.6) 33.4 (2.3) 42.1 (2.9) 65.3 (4.5) TPE2 (D), TPE3 (D) 50-240 13.1 (0.9) 16 (1.1) 23.2 (1.6) 33.4 (2.3) 42.1 (2.9) 65.3 (4.5) TPE2 (D), TPE3 (D) 65-60 1.5 (0.1) 1.5 (0.1) 2.9 (0.2) 13.1 (0.9) 21.8 (1.5) 45 (3.1) TPE2 (D), TPE3 (D) 65-80 1.5 (0.1) 1.5 (0.1) 4.4 (0.3) 16 (1.1) 24.7 (1.7) 47.9 (3.3) TPE2 (D), TPE3 (D) 65-120 1.5 (0.1) 2.9 (0.2) 8.7 (0.6) 20.3 (1.4) 29 (2) 52.2 (3.6) TPE2 (D), TPE3 (D) 65-150 1.5 (0.1) 2.9 (0.2) 10.2 (0.7) 21.8 (1.5) 30.5 (2.1) 53.7 (3.7) TPE2 (D), TPE3 (D) 65-180 4.4 (0.3) 7.3 (0.5) 14.5 (1.0) 26.1 (1.8) 34.8 (2.4) 56.6 (3.9) TPE2 (D), TPE3 (D) 65-200 8.7 (0.6) 11.6 (0.8) 18.9 (1.3) 30.5 (2.1) 39.2 (2.7) 60.9 (4.2) TPE2 (D), TPE3 (D) 80-40 1.5 (0.1) 1.5 (0.1) 4.4 (0.3) 14.5 (1) 23.2 (1.6) 46.4 (3.2) TPE2 (D), TPE3 (D) 80-120 1.5 (0.1) 4.4 (0.3) 13.1 (0.9) 21.8 (1.5) 30.5 (2.1) 53.7 (3.7) TPE2 (D), TPE3 (D) 80-150 1.5 (0.1) 4.4 (0.3) 13.1 (0.9) 21.8 (1.5) 30.5 (2.1) 53.7 (3.7) TPE2 (D), TPE3 (D) 80-180 4.4 (0.3) 7.3 (0.5) 16 (1.1) 24.7 (1.7) 33.4 (2.3) 56.6 (3.9) TPE2 (D), TPE3 (D) 100-40 1.5 (0.1) 1.5 (0.1) 5.8 (0.4) 16 (1.1) 24.7 (1.7) 45 (3.1) TPE2 (D), TPE3 (D) 100-120 1.5 (0.1) 1.5 (0.1) 8.7 (0.6) 18.9 (1.3) 27.6 (1.9) 50.8 (3.5) TPE2 (D), TPE3 (D) 100-150 1.5 (0.1) 2.9 (0.2) 10.2 (0.7) 20.3 (1.4) 29 (2) 52.2 (3.6) TPE2 (D), TPE3 (D) 100-180 1.5 (0.1) 4.4 (0.3) 11.6 (0.8) 21.8 (1.5) 30.5 (2.1) 53.7 (3.7)
Appendix
51
Page 52
52
Page 53
GRUNDFOS Kansas City
17100 West 118th Terrace Olathe, Kansas 66061 Phone: (913) 227-3400 Fax: (913) 227-3500
www.grundfos.us
Grundfos CBS Inc.
902 Koomey Road Brookshire, TX 77423 USA Phone: 281-994-2700 Toll Free: 1-800-955-5847 Fax: 1-800-945-4777
www.grundfosexpresssuite.com
GRUNDFOS Canada
2941 Brighton Road Oakville, Ontario L6H 6C9 Canada Phone: +1-905 829 9533 Telefax: +1-905 829 9512
www.grundfos.ca
GRUNDFOS México
Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto C.P. 66600 Apodaca, N.L. México Phone: 011-52-81-8144 4000 Fax: 011-52-81-8144 4010
www.grundfos.mx
Grundfos companies
Page 54
98653472 0115
ECM: 1150808
www.grundfos.com
www.grundfos.us
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S
Loading...