Single-stage in-line pumps with integrated variable frequency drive
Installation and operating instructions
Page 2
English (US)
English (US) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
1.Symbols used in this document
2.Limited warranty
3.Abbreviations and definitions
4.General information
4.1Radio communication
4.2Battery
5.Delivery and handling
5.1Delivery
5.2Handling
6.Applications
6.1Pumped liquids
7.Operating conditions
7.1Maximum number of starts and stops
7.2Alternating operation of twin-head pumps
7.3Liquid temperature
7.4Ambient temperature
7.5Operating pressure/test pressure
7.6Inlet pressure
7.7Electrical data
7.8Sound pressure level
7.9Environment
7.10Installation altitude
7.11Air humidity
7.12Motor cooling
8.Mechanical installation
8.1Pipework
8.2Terminal box positions
8.3Fitting of pump head
8.4Base plate
8.5Insulation
8.6Frost protection
8.7Ensuring motor cooling
8.8Outdoor installation
9.Electrical installation
9.1Protection against electric shock, indirect contact
9.2Power supply
9.3Additional protection
9.4Connection terminals
9.5Signal cables
9.6Bus connection cable
10.Startup
10.1Flushing the pipe system
10.2Priming
10.3Starting
10.4Shaft seal run-in
11.User interfaces
12.Standard control panel
12.1Setpoint setting
13.Advanced control panel
13.1Menu structure
13.2Menu overview for advanced control panel
14.Grundfos GO Remote
14.1Communication
14.2Menu overview for Grundfos GO Remote
15.Description of selected functions
15.1Setpoint
15.2Operating mode
15.3Set manual speed
Page
10
10
10
11
12
16
16
16
16
16
17
17
17
18
18
20
20
21
23
23
24
26
26
26
26
15.4Control mode
15.5FLOWLIMIT
15.6Automatic Night Setback
15.7Analog inputs
3
3
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
6
6
6
6
6
6
6
7
7
8
8
9
9
9
9
9
15.8Pt100/1000 inputs
15.9Digital inputs
15.10 Digital inputs/outputs
15.11 Relay outputs
15.12 Analog output
15.13 Controller settings
15.14 Operating range
15.15 Setpoint influence
15.16 Monitoring functions
15.17 Special functions
15.18 Communication
15.19 General settings
16.Assist
16.1Multi-pump setup
17.Selection of control mode
18.Changing the position of the control panel
19.Bus signal
20.Priority of settings
21.Grundfos Eye
22.Signal relays
23.Maintenance and service
23.1Maintenance
23.2Service
24.Fault finding
25.Megging
26.Technical data, single-phase motors
26.1Supply voltage
26.2Leakage current
27.Technical data, three-phase motors
27.1Supply voltage
27.2Leakage current
28.Inputs/outputs
29.Other technical data
29.1Torques
29.2Sound pressure level
30.Disposal
26
31
31
31
31
32
32
33
33
33
34
35
38
38
38
39
39
39
40
42
43
43
44
45
46
46
46
47
48
48
48
48
48
48
48
48
49
49
49
49
2
Page 3
Warnin g
Caution
Note
Note
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
1. Symbols used in this document
Warnin g
If these safety instructions are not observed,
it may result in personal injury.
Warnin g
If these instructions are not observed, it may lead
to electric shock with consequent risk of serious
personal injury or death.
Warnin g
The surface of the product may be so hot that
it may cause burns or personal injury.
Warnin g
Risk of dropping objects which may cause
personal injury.
Warnin g
Escaping vapor involves the risk of personal
injury.
If these safety instructions are not observed,
it may result in malfunction or damage to the
equipment.
Notes or instructions that make the job easier
and ensure safe operation.
2. Limited warranty
Products manufactured by GRUNDFOS PUMPS CORPORATION
(Grundfos) are warranted to the original user only to be free of
defects in material and workmanship for a period of 24 months
from date of installation, but not more than 30 months from date
of manufacture. Grundfos' liability under this warranty shall be
limited to repairing or replacing at Grundfos' option, without
charge, F.O.B. Grundfos' factory or authorized service station,
any product of Grundfos' manufacture. Grundfos will not be liable
for any costs of removal, installation, transportation, or any other
charges which may arise in connection with a warranty claim.
Products which are sold but not manufactured by Grundfos are
subject to the warranty provided by the manufacturer of said
products and not by Grundfos' warranty. Grundfos will not be
liable for damage or wear to products caused by abnormal
operating conditions, accident, abuse, misuse, unauthorized
alteration or repair, or if the product was not installed in
accordance with Grundfos' printed installation and operating
instructions.
To obtain service under this warranty, the defective product must
be returned to the distributor or dealer of Grundfos' products from
which it was purchased together with proof of purchase and
installation date, failure date, and supporting installation data.
Unless otherwise provided, the distributor or dealer will contact
Grundfos or an authorized service station for instructions.
Any defective product to be returned to Grundfos or a service
station must be sent freight prepaid; documentation supporting
the warranty claim and/or a Return Material Authorization must
be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES
ARISING FROM INSTALLATION, USE, OR ANY OTHER
CAUSES. THERE ARE NO EXPRESS OR IMPLIED
WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND
THOSE WARRANTIES DESCRIBED OR REFERRED TO
ABOVE.
Some jurisdictions do not allow the exclusion or limitation of
incidental or consequential damages and some jurisdictions do
not allow limit actions on how long implied warranties may last.
Therefore, the above limitations or exclusions may not apply to
you. This warranty gives you specific legal rights and you may
also have other rights which vary from jurisdiction to jurisdiction.
English (US)
3
Page 4
English (US)
Note
Note
3. Abbreviations and definitions
AIAnalog input.
ALAlarm, out of range at lower limit.
AOAnalog output.
AUAlarm, out of range at upper limit.
The ability to draw current into the terminal and
guide it towards GND in the internal circuitry.
The ability to push current out of the terminal
and into an external load which must return it
to GND.
Grundfos Digital Sensor.
Factory-fitted sensor in some Grundfos pumps.
Ground fault circuit interrupter.
(USA and Canada).
Low voltage with the risk of electric shock if the
terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, except earth faults in other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, including earth faults in other
circuits.
Single-head TPE2 pump without factory-fitted
differential-pressure and temperature sensor.
Twin-head TPE2 D pump without factory-fitted
differential-pressure and temperature sensor.
Single-head TPE3 pump with factory-fitted
differential-pressure and temperature sensor.
Twin-head TPE3 D pump with factory-fitted
differential-pressure and temperature sensor.
Some variants of these products and all products
sold in China and Korea have no possibility of
radio communication according to local
legislation.
This product can communicate with the Grundfos GO Remote
and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required.
Only Grundfos-approved external antennas may be connected to
this product, and only by a Grundfos-approved installer.
4.2 Battery
Pumps fitted with the advanced functional module (FM 300)
incorporate a Li-ion battery. The Li-ion battery complies with the
Battery Directive (2006/66/EC). The battery does not contain
mercury, lead and cadmium.
5. Delivery and handling
5.1 Delivery
The pump is delivered from the factory in a carton with a wooden
bottom, which is specially designed for transport by fork-lift truck
or a similar vehicle.
5.2 Handling
Warnin g
TPE2 D, TPE3 D: The centrally positioned thread
of the pump housing must not be used for lifting
purposes as the thread is placed below the
center of gravity of the pump.
Lift the pump by means of nylon straps. See figs 1 and 2.
TM05 7914 1613TM05 7915 1613
Fig. 1 TPE2, TPE3
4. General information
These installation and operating instructions apply to the
Grundfos TPE2 (D) and TPE3 (D) pumps.
The pumps are fitted with frequency-controlled
permanent-magnet motors for single-phase or three-phase power
supply connection.
4.1 Radio communication
This product incorporates a radio module for remote control
which is a class 1 device and can be used anywhere in the EU
member states without restrictions.
For use in USA and Canada, see page 50.
4
Fig. 2 TPE2 D, TPE3 D
Page 5
6. Applications
Note
Note
The pumps are designed to circulate hot or cold water in:
• heating systems
• district heating plants
• air-conditioning systems
• cooling systems.
In addition, the pumps are used for liquid transfer and water
supply in:
• washing systems
• domestic hot-water systems
• industrial systems in general.
To ensure optimum operation, the sizing range of the system
must fall within the performance range of the pump.
6.1 Pumped liquids
Warnin g
If the pump is used for a liquid which is
hazardous, it will be classified as contaminated.
In such cases, the proper precautions must be
taken to avoid injury to health when operating or
working on the pump.
The pump is suitable for thin, clean, non aggressive and
nonflammable liquids, not containing solid particles or fibers that
may attack the pump mechanically or chemically.
Examples:
• central heating system water (the water should meet the
requirements of accepted standards on water quality in
heating systems)
• cooling liquids
• domestic hot water
• industrial liquids
• softened water.
The pumping of liquids with a density and/or kinematic viscosity
higher than that of water will cause the following:
• a considerable pressure drop
• a drop in hydraulic performance
• a rise in power consumption.
In such cases, fit the pump with a bigger motor. If in doubt,
contact Grundfos.
The EPDM O-rings fitted as standard are primarily suitable for
water.
If the water being pumped contains minerals, synthetic oil,
chemicals, or any liquids other than water, choose the O-rings
accordingly.
7. Operating conditions
7.1 Maximum number of starts and stops
The number of starts and stops via the power supply must not
exceed four times per hour.
When switched on via the power supply, the pump will start after
approx. 5 seconds.
If you want a higher number of starts and stops, use the input for
external start/stop when starting/stopping the pump.
When started via an external on/off switch, the pump will start
immediately.
7.2 Alternating operation of twin-head pumps
On twin-head pumps, the duty and backup pumps must be
alternated on a regular basis, i.e. once a week, to ensure an even
distribution of the operating hours on both pumps. As default, the
pumps alternate automatically. See section 16.1 Multi-pump
setup.
If you use twin-head pumps for pumping domestic hot water, the
duty and backup pumps must be alternated on a regular basis,
i.e. once a day, to avoid blocking of the backup pump due to
deposits (calcareous deposits, etc.). As default, the pumps
alternate automatically. See section 16.1 Multi-pump setup.
7.3 Liquid temperature
-13 °F (-25 °C) up to 248 °F (+120 °C).
The maximum liquid temperature depends on the mechanical
shaft seal type and the pump type.
Depending on the cast-iron version and the pump application, the
maximum liquid temperature may be limited by local regulations
and laws.
The maximum liquid temperature is stated on the pump
nameplate.
If the pump is operating with liquids at high
temperatures, the life of the shaft seal may be
reduced. It may be necessary to replace the shaft
seal more often.
7.4 Ambient temperature
7.4.1 Ambient temperature during storage and transportation
-22 to 140 °F (-30 to +60 °C).
7.4.2 Ambient temperature during operation
-4 to 122 °F (-20 to +50 °C).
The motor can operate with the rated power output (P2) at
122 °F (50 °C), but continuous operation at higher temperatures
will reduce the expected product life. If the motor is to operate at
ambient temperatures between 122 and 140 °F (50 and 60 °C),
select an oversized motor. Contact Grundfos for further
information.
English (US)
7.5 Operating pressure/test pressure
The pressure test has been made with water containing
anti-corrosive additives at a temperature of +68 °F (+20 °C).
Operating pressureTest pressure
[bar][psi][bar][psi]
1014515218
5
Page 6
English (US)
Caution
1
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.91
0.90
0.89
0.88
0
0
3281 3937 4593 5249 5906 6562 7218
[ft]
P2
[%]
7.6 Inlet pressure
To ensure optimum and quiet pump operation, the inlet pressure
(system pressure) must be adjusted correctly. See table on
page 51.
For the calculation of specific inlet pressures, contact the local
Grundfos company or see the data booklet for TP(D), TPE(D),
TPE2 (D) and TPE3 (D) on www.grundfos.us.
7.7 Electrical data
See sections 26. Technical data, single-phase motors and
27. Technical data, three-phase motors.
For specific motor data, see the motor nameplate.
7.8 Sound pressure level
The sound pressure level of the pump is lower than 70 dB(A).
7.9 Environment
Non-aggressive and non-explosive atmosphere.
7.10 Installation altitude
The motor must not be installed more than
6562 ft (2000 m) above sea level.
Installation altitude is the height above sea level of the installation
site.
• Motors installed up to 3281 ft (1000 m) above sea level can be
loaded 100 %.
• Motors installed more than 3281 ft (1000 m) above sea level
must not be fully loaded due to the low density and
consequent low cooling effect of the air. See fig. 3.
7.11 Air humidity
Maximum air humidity: 95 %.
If the air humidity is constantly high and above 85 %, one of the
drain holes in the drive-end flange must be open. See section
5. Delivery and handling.
7.12 Motor cooling
To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate cooling is
ensured. See section 8.7 Ensuring motor cooling.
• The temperature of the cooling air must not exceed
122 °F (50 °C).
• Keep cooling fins and fan blades clean.
TM05 6400-U.S. 1013
Fig. 3 Derating of motor output power (P2) in relation to
altitude above sea level
6
Page 7
8. Mechanical installation
Note
Note
Caution
Installation
WasherPump
11.81" [300 mm]
Caution
Caution
Warnin g
When pumping hot or cold liquids, make sure
that persons cannot accidentally come into
contact with hot or cold surfaces.
In order to maintain the UL mark, additional
installation procedures must be followed.
See page 50.
Install the pump in a dry well-ventilated, but frost-free position.
When installing pumps with oval bolt holes in the pump flange,
use washers as shown in fig. 4.
Fig. 4 Use of washers for oval bolt holes
Arrows on the pump housing show the direction of flow of liquid
through the pump.
You can install the pump in horizontal or vertical pipes.
The motor must never fall below the horizontal
plane.
For inspection and removal of motor or pump head, a clearance
of 11.81" (300 mm) is required above the motor. See fig. 5.
Fig. 5 Required clearance above the motor
If the liquid temperature falls below the ambient temperature,
condensation may form in the motor during inactivity. In this case,
make sure that one of the drain holes in the motor flange is open
and points downwards. See fig. 7.
Fig. 7 Drain hole in motor flange
If twin-head pumps are used for pumping liquids with a
temperature below 32 °F (0 °C), condensed water may freeze
and cause the coupling to get stuck. You can solve the problem
by installing heating elements. Whenever possible, install the
TM01 0683 1997
pump with the motor shaft in horizontal position. See fig. 6.
Observe the conditions in section 11. User
interfaces.
8.1 Pipework
Fit isolating valves on either side of the pump to avoid draining
the system if the pump needs to be cleaned or repaired.
The pump is suitable for pipeline mounting, provided that the
pipes are adequately supported on either side of the pump.
Single-head pumps are designed for pipeline mounting only.
Twin-head pumps are prepared for installation on a mounting
bracket or base plate.
When installing the pipes, make sure that the pump housing is
not stressed by the pipework.
The suction and discharge pipes must be of an adequate size,
taking the pump inlet pressure into account.
To avoid sediment build-up, do not fit the pump at the lowest point
of the system.
Install the pipes so that air locks are avoided, especially on the
suction side of the pump. See fig. 8.
TM05 7916 1613TM05 7983 1713
English (US)
TM05 7917 1613
Twin-head pumps installed in horizontal pipes must be fitted with
an automatic air vent in the upper part of the pump housing.
See fig. 6.
The automatic air vent is not supplied with the pump.
Fig. 6 Automatic air vent
TM00 2263 0195
Fig. 8 Correct pipework on the suction side of the pump
The pump must not run against a closed
discharge valve as this will cause an increase in
temperature/formation of steam in the pump
which may cause damage to the pump.
If there is any risk of the pump running against a closed discharge
valve, ensure a minimum liquid flow through the pump by
connecting a bypass/a drain to the discharge pipe. You can for
instance connect the drain to a tank. A minimum flow rate equal
to 10 % of the flow rate at maximum efficiency is needed at all
times.
Flow rate and head at maximum efficiency are stated on the
pump nameplate.
7
Page 8
English (US)
A
8.2 Terminal box positions
Warnin g
Before starting work on the pump, make sure that
the power supply has been switched off for at
least 5 minutes. Make sure that the power supply
cannot be accidentally switched on.
8.3 Fitting of pump head
Warnin g
Before starting work on the pump, make sure that
the power supply has been switched off for at
least 5 minutes. Make sure that the power supply
cannot be accidentally switched on.
Warnin g
If the pump head has been lifted partly or
completely from the pump housing, pay special
attention when fitting the pump head again.
See 8.3 Fitting of pump head.
Warnin g
When loosening the clamp, do not drop the pump
head. See fig. 9.
Warnin g
When loosening the clamp, there is a risk of
escaping vapor. See fig. 9.
The terminal box can be turned to any position. Change the
terminal box position as follows:
1. Loosen the clamp securing the pump head to the pump
housing. See fig. 9.
Warnin g
If the pump head has been lifted partly or
completely from the pump housing, pay special
attention when fitting the pump head again.
See instructions below.
Warnin g
Do not drop the pump head. See fig. 9.
Warnin g
When loosening the clamp, there is a risk of
escaping vapor. See fig. 9.
If for some reason the pump head has been lifted from the pump
housing, follow the following procedure in order to mount the
pump head correctly:
1. Visually check that the neck ring is centered in the pump
housing. See fig. 10.
Fig. 9 Clamp (A)
2. Turn the pump head to the required position.
3. Check the following before you tighten the clamp:
– The contact face of the pump housing and that of the pump
head must be in full contact.
– Position the clamp correctly in the flange recess of both the
Pumps which are not being used during periods of frost must be
drained to avoid damage.
8.7 Ensuring motor cooling
In order to ensure sufficient cooling of the motor,
the distance (D) between the end of the fan cover
and a wall or other fixed objects must always be
at least 2.0" (50 mm), irrespective of motor size.
See fig. 14.
TM06 0724 0814
English (US)
8.4 Base plate
Twin-head pumps have tapped holes in the bottom of the pump
housing. The holes can be used for mounting a base plate.
8.5 Insulation
Do not insulate the motor stool as this will trap
any vapor escaping from the shaft seal, thus
causing corrosion. Covering the motor stool with
insulation will also make inspection and service
difficult.
Follow the guidelines in fig. 13 when insulating the pump.
Fig. 13 Insulation of TPE2, TPE3 pumps
Fig. 14 Minimum distance (D) from the motor to a wall or other
fixed objects
8.8 Outdoor installation
When installed outdoors, the motor must be provided with a
suitable cover to avoid condensation on the electronic
components. See fig. 15.
When fitting a cover to the motor, observe the
guideline in section 8.7 Ensuring motor cooling.
The cover must be sufficiently large to ensure that the motor is
not exposed to direct sunlight, rain or snow. Grundfos does not
supply covers. We therefore recommend that you have a cover
built for the specific application. In areas with high air humidity,
we recommend that you enable the built-in standstill heating
function.
TM05 7918 1613
Fig. 15 Examples of covers (not supplied by Grundfos)
Carry out the electrical connection according to local regulations.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Warnin g
Before making any connections in the terminal
box, make sure that the power supply has been
switched off for at least 5 minutes. Make sure that
the power supply cannot be accidentally
switched on.
The motor must be connected to an external
all-pole power supply switch according to local
regulations.
The motor must be grounded and protected
against indirect contact in accordance with local
regulations.
If the power supply cable is damaged, it must be
replaced by the manufacturer, the manufacturer's
service partner or a similarly qualified person.
The user or the installer is responsible for the
installation of correct grounding and protection
according to local regulations. All operations
must be carried out by a qualified electrician.
9.1 Protection against electric shock, indirect contact
9.2 Power supply
9.2.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
The wires in the motor terminal box must be as short possible
except for the separated ground conductor which must be so long
that it is the last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 26.1 Supply voltage.
TM05 4034 1912TM05 3494 1512
Fig. 16 Example of a power supply-connected motor with
power supply switch, backup fuse and additional
protection
Warnin g
The motor must be grounded and protected
against indirect contact in accordance with local
regulations.
9.1.1 Protection against power supply voltage transients
The motor is protected against power supply voltage transients in
accordance with EN 61800-3.
9.1.2 Motor protection
The motor requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking.
Fig. 17 Power supply connection, single-phase motors
10
Page 11
9.2.2 Three-phase supply voltage
Caution
Note
Note
L1
L2
L3
L2
L1
L3
PE
GFCI
Note
Note
Note
Note
ELCB
(GFCI)
ELCB
(GFCI)
• 3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE.
In order to avoid loose connections, ensure that
the terminal block for L1, L2 and L3 is pressed
home in its socket when the supply cable has
been connected.
Corner grounding is not allowed for supply
voltages above 3 x 480 V, 60 Hz.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated earth conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 27.1 Supply voltage.
Fig. 18 Example of a power supply-connected motor with
power supply switch, backup fuses and additional
protection
9.3 Additional protection
9.3.1 Single-phase motors
If the motor is connected to an electric installation where an earth
leakage circuit breaker (ELCB) or ground fault circuit
interrupter (GFCI) is used as additional protection, this circuit
breaker or interrupter must be marked with the following symbol:
When an earth leakage circuit breaker or ground
fault circuit interrupter is selected, the total
leakage current of all the electrical equipment in
the installation must be taken into account.
The leakage current of the motor can be found in section
26.2 Leakage current.
9.3.2 Three-phase motors
If the motor is connected to an electric installation where an earth
leakage circuit breaker (ELCB) or ground fault circuit interrupter
(GFCI) is used as additional protection, this circuit breaker or
interrupter must be of the following type:
• It must be suitable for handling leakage currents and cutting-in
with short pulse-shaped leakage.
• It must trip out when alternating fault currents and fault
TM05 3942 1812TM05 3495 1512
currents with DC content, i.e. pulsating DC and smooth DC
fault currents, occur.
For these motors an earth leakage circuit breaker or ground fault
circuit interrupter, type B, must be used.
This circuit breaker or interrupter must be marked with the
following symbols:
English (US)
Fig. 19 Power supply connection, three-phase motors
When you select an earth leakage circuit breaker
or ground fault circuit interrupter, take into
account the total leakage current of all the
electrical equipment in the installation.
You find the leakage current of the motor in section 27.2 Leakage
current.
Protection against phase unbalance
The motor must be connected to a power supply with a quality
corresponding to IEC 60146-1-1, class C, to ensure correct motor
operation at phase unbalance.
This also ensures long life of the components.
11
Page 12
English (US)
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
P
:
n
W
g
g
t
:
DE
:
k
g
g
D
:
amb
:
:
FAA
V
:
T
T
E
C
T
yp
yp
e
:
P.N.
:
U
:
1/1
:
HzP
I
p
p
:
:
PB
FM
HMICIM
VARIANT
Hp
rpm
::
:
:
PB
:
:
C
:
H
p
m
Note
Note
Note
Note
9.4 Connection terminals
The descriptions and terminal overviews in this section apply to
both single-phase and three-phase motors.
For maximum tightening torques, see section Torques, page 49.
The number of terminals depends on the functional module (FM).
You can identify the fitted module on the motor nameplate.
See fig. 20.
The advanced functional module is only available as an option.
The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 21.
Digital input 1 is factory-set to be start/stop input
where open circuit will result in stop.
A jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if digital
input 1 is to be used as external start/stop or any
other external function.
As a precaution, the wires to be connected to the
connection groups below must be separated
from each other by reinforced insulation in their
entire lengths.
• Inputs and outputs
TM05 7928 1613
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by safety extra-low voltage
(SELV), thus ensuring protection against electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
Power supply voltages up to 250 VAC can be connected to
this output.
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
– Signal relay 2:
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
• Power supply (terminals N, PE, L or L1, L2, L3, PE).
A galvanically safe separation must fulfil the requirements for
reinforced insulation including creepage distances and
clearances specified in EN 61800-5-1.
* If you use an external supply source, there must be a
connection to GND.
Fig. 21 Connection terminals, FM 300 (option)
21LiqTec sensor input 1
LiqTec sensor input
(white conductor)
Ground
20GND
(brown and black
conductors)
22LiqTec sensor input 2
LiqTec sensor input
(blue conductor)
Digital input/output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
TM05 3509 3512
5+5 V
Supply to potentiometer
and sensor
6GNDGround
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
8+24 VSupply
26+5 V
Supply to potentiometer
and sensor*
23GNDGround
25GDS TX
24GDS RX
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
13
Page 14
English (US)
Note
Note
Note
Note
9.4.2 Connection terminals, standard functional module
(FM 200)
The standard module has these connections:
• two analog inputs
• two digital inputs or one digital input and one open-collector
output
• Grundfos Digital Sensor input and output
• two signal relay outputs
• GENIbus connection.
See fig. 22.
Digital input 1 is factory-set to be start/stop input
where open circuit will result in stop.
A jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if digital
input 1 is to be used as external start/stop or any
other external function.
As a precaution, the wires to be connected to the
connection groups below must be separated
from each other by reinforced insulation in their
entire lengths.
• Inputs and outputs
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by safety extra-low voltage
(SELV), thus ensuring protection against electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
Power supply voltages up to 250 VAC can be connected to
this output.
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
– Signal relay 2:
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
• Power supply (terminals N, PE, L or L1, L2, L3, PE).
A galvanically safe separation must fulfil the requirements for
reinforced insulation including creepage distances and
clearances specified in EN 61800-5-1.
14
Page 15
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
Terminal TypeFunction
NC
C1Common
NO
Normally closed
contact
Normally open
contact
Signal relay 1
(LIVE or SELV)
English (US)
* If an external supply source is used, there must be a
connection to GND.
Fig. 22 Connection terminals, FM 200
NC
C2Common
NO
Normally closed
contact
Normally open
contact
Signal relay 2
(SELV only)
Digital input/output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6GNDGround
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
TM05 3510 3512
8+24 VSupply
26+5 V
Supply to potentiometer and
sensor*
23GNDGround
25GDS TX
Grundfos Digital Sensor
output
24GDS RXGrundfos Digital Sensor input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
15
Page 16
English (US)
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
Caution
Caution
A
Y
B
A
Y
B
1
2
1
2
Motor
9.5 Signal cables
• Use screened cables with a cross-sectional area of
min. 20 AWG and max. 16 AWG (0.5 mm
for external on/off switch, digital inputs, setpoint and sensor
signals.
• Connect the screens of the cables to frame at both ends with
good connection. The screens must be as close as possible to
the terminals. See fig. 23.
Fig. 23 Stripped cable with screen and wire connections
• Screws for frame connections must always be tightened
whether a cable is fitted or not.
• The wires in the motor terminal box must be as short as
possible.
2
and max. 1.5 mm2)
9.6 Bus connection cable
9.6.1 New installations
For the bus connection, use a screened 3-core cable with a
cross-sectional area of min. 20 AWG and max. 16 AWG (0.5 mm
and max. 1.5 mm
• If the motor is connected to a unit with a cable clamp which is
identical to the one on the motor, connect the screen to this
cable clamp.
• If the unit has no cable clamp as shown in fig. 24, leave the
screen unconnected at this end.
Fig. 24 Connection with screened 3-core cable
2
).
9.6.2 Replacing an existing motor
• If a screened 2-core cable is used in the existing installation,
connect the cable as shown in fig. 25.
Fig. 25 Connection with screened 2-core cable
• If a screened 3-core cable is used in the existing installation,
follow the instructions in section 9.6.1 New installations.
10. Startup
TM02 1325 4402 TM05 3973 1812
10.1 Flushing the pipe system
The pump is not designed to pump liquids
containing solid particles such as pipe debris
and welding slag. Before starting up the pump,
clean the pipe system thoroughly, and flush and
fill it with clean water.
The warranty does not cover any damage caused
by flushing the pipe system by means of the
2
10.2 Priming
Closed systems or open systems where the liquid level is
above the pump inlet
1. Close the discharge isolating valve and loosen the air vent
screw in the motor stool. See fig. 26.
2. Slowly open the isolating valve in the suction pipe until a
steady stream of liquid runs out of the vent hole.
3. Tighten the air vent screw and completely open the isolating
valve(s).
pump.
Do not start the pump until it has been filled with
liquid and vented. To ensure correct venting, the
vent screw should point upwards.
Warnin g
Pay attention to the direction of the vent hole,
and make sure that the escaping hot or cold
liquid does not cause injury to persons or
damage to the equipment.
TM02 8842 0904
16
Page 17
Open systems where the liquid level is below the pump inlet
The suction pipe and the pump must be filled with liquid and
vented before you start the pump.
1. Close the discharge isolating valve and open the isolating
valve in the suction pipe.
2. Loosen the air vent screw. See fig. 26.
3. Remove the plug from one of the pump flanges, depending on
the pump location.
4. Pour liquid through the priming port until the suction pipe and
the pump are filled with liquid.
5. Replace the plug and tighten securely.
6. Tighten the air vent screw.
The suction pipe can to some extent be filled with liquid and
vented before it is connected to the pump. You can also install a
priming device before the pump.
Fig. 26 Position of air vent screw
10.3 Starting
1. Before starting the pump, completely open the isolating valve
on the suction side of the pump and leave the discharge
isolating valve almost closed.
2. Start the pump. See section 11. User interfaces.
3. Vent the pump during starting by loosening the air vent screw
in the motor stool until a steady stream of liquid runs out of the
vent hole. See fig. 26.
Warnin g
Pay attention to the direction of the vent hole,
and make sure that the escaping hot or cold
liquid does not cause injury to persons or
damage to the equipment.
4. When the pipe system has been filled with liquid, slowly open
the discharge isolating valve until it is completely open.
10.4 Shaft seal run-in
The seal faces are lubricated by the pumped liquid, meaning that
there may be a certain amount of leakage from the shaft seal.
When the pump is started up for the first time, or when a new shaft
seal is installed, a certain run-in period is required before the
leakage is reduced to an acceptable level. The time required for
this depends on the operating conditions, i.e. every time the
operating conditions change, a new run-in period will be started.
Under normal conditions, the leaking liquid will evaporate. As a
result, no leakage will be detected.
However, liquids such as kerosene will not evaporate. The leakage
may therefore be seen as a shaft seal failure.
11. User interfaces
Warnin g
The product may be so hot that only the buttons
must be touched to avoid burns.
Pump settings can be made by means of the following user
interfaces:
Control panels
• Standard control panel.
See section 12. Standard control panel.
• Advanced control panel.
See section 13. Advanced control panel.
Remote controls
TM05 7922 1613
• Grundfos GO Remote.
See section 14. Grundfos GO Remote.
If you switch-off the power supply to the pump, the settings will be
stored.
Factory settings
TPE2 (D) pumps have been factory-set to constant-curve control
mode. See section 12.1.2 Pump in constant-curve control mode.
The setpoint value corresponds to 100 %, of maximum pump
performance. See data booklet or WebCAPS.
TPE3 (D) pumps have been factory-set to AUTO
mode. See section 15.4.1 AUTOADAPT.
ADAPT
English (US)
control
17
Page 18
English (US)
1
2
3
4
5
Stop
4.3
8.5
psi
H
Q
12. Standard control panel
This control panel is fitted as standard on TPE2 (D) pumps.
Fig. 27 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
2-Light fields for indication of setpoint.
3Changes the setpoint.
4
5
Shows the operating status of the pump.
See section 21. Grundfos Eye for further
information.
Enables radio communication with the
Grundfos GO Remote and other products of
the same type.
Makes the pump ready for operation/starts
and stops the pump.
Start:
If you press the button when the pump is
stopped, the pump will only start if no other
functions with higher priority have been
enabled. See section 20. Priority of settings.
Stop:
If you press the button when the pump is
running, the pump will always be stopped.
When the pump is stopped via this button, the
"Stop" text next to the button will illuminate.
12.1 Setpoint setting
Set the desired setpoint of the pump by pressing or .
The light fields on the control panel will indicate the setpoint set.
12.1.1 Pump in differential-pressure control mode
The following example applies to a pump in an application where
a pressure sensor gives a feedback to the pump. If you retrofit the
sensor to the pump, you must set it up manually as the pump
does not automatically register a connected sensor.
Figure 28 shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 4.3 psi (3 m) with a sensor
measuring range from 0 to 8.5 psi (0 to 6 m). The setting range is
equal to the sensor measuring range.
TM05 4848 3512
TM06 1116 1714TM05 4895 2812
Fig. 28 Setpoint set to 4.3 psi (3 m), differential-pressure
control
12.1.2 Pump in constant-curve control mode
In constant-curve control mode, the pump performance will lie
between the maximum and minimum curve of the pump.
See fig. 29.
Fig. 29 Pump in constant-curve control mode
18
Page 19
Setting to maximum curve:
H
Q
H
Q
•Press
of the pump (top light field flashes). When the top light field is
on, press
• To change back, press
setpoint is indicated.
Example: Pump set to maximum curve.
Figure 30 shows that the top light field is flashing, indicating
maximum curve.
Fig. 30 Maximum curve duty
Setting to minimum curve:
•Press
of the pump (bottom light field flashes). When the bottom light
field is on, press
flashing.
• To change back, press continuously until the desired
setpoint is indicated.
Example: Pump set to minimum curve.
Figure 31 shows that the bottom light field is flashing, indicating
minimum curve.
continuously to change over to the maximum curve
for 3 seconds until the light field starts flashing.
continuously until the desired
continuously to change over to the minimum curve
for 3 seconds until the light field starts
12.1.3 Start/stop of pump
Start the pump by pressing
until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is stopped, the
"Stop" text next to the button will illuminate. You can also stop the
pump by continuously pressing
are on.
If you have stopped the pump by pressing , it can only be
given free to operation by pressing again.
If you have stopped the pump by pressing , it can only be
restarted by pressing .
You can also stop the pump with the Grundfos GO Remote or via
a digital input set to "External stop". See section 20. Priority of
settings.
12.1.4 Resetting of fault indications
You can reset a fault indication in one of the following ways:
• Via the digital input if it has been set to "Alarm resetting".
• Briefly press or
setting of the pump.
TM05 4896 2812TM05 4897 2812
You cannot reset a fault indication by pressing or
buttons have been locked.
• Switch off the power supply until the indicator lights are off.
• Switch the external start/stop input off and then on again.
• With the Grundfos GO Remote.
or by continuously pressing
until none of the light fields
on the pump. This will not change the
English (US)
if the
Fig. 31 Minimum curve duty
19
Page 20
English (US)
1
2
3
4
5
6
Note
Note
13. Advanced control panel
This control panel is fitted as standard on TPE3 (D) pumps.
TPE2 (D) pumps can be fitted with the advanced control panel as
an option.
Fig. 32 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
2-Graphical color display.
Shows the operating status of the pump.
See section 21. Grundfos Eye for further
information.
13.1 Menu structure
The pump incorporates a startup guide which is started at the first
startup. After the startup guide, the four main menus will appear
in the display.
1. Home
This menu shows up to four user-defined parameters with
shortcuts or a graphical illustration of a Q/H performance curve.
2. Status
This menu shows the status of the pump and system as well as
warnings and alarms.
You cannot make any settings in this menu.
3. Settings
This menu gives access to all setting parameters. A detailed
setting of the pump can be made in this menu.
See section 15. Description of selected functions.
4. Assist
TM05 4849 1013
This menu enables assisted pump setup, provides a short
description of the control modes and offers fault advice.
See section 16. Assist.
3Goes one step back.
Navigates between main menus, displays and
digits.
When the menu is changed, the display will
always show the top display of the new menu.
4
Navigates between submenus.
Saves changed values, resets alarms and
expands the value field.
Enables communication with the Grundfos GO
Remote.
Makes the pump ready for operation/starts and
stops the pump.
Start:
If you press the button when the pump is
stopped, the pump will only start if no other
5
functions with higher priority have been
enabled. See section 20. Priority of settings.
Stop:
If you press the button when the pump is
running, the pump will always be stopped.
When you stop the pump via this button, the
"Stop" text next to the button will illuminate.
6Goes to the "Home" menu.
20
Page 21
13.2 Menu overview for advanced control panel
13.2.1 Main menus
HomeTPE3 (D)TPE2 (D)
●●
StatusTPE3 (D)TPE2 (D)
Operating status●●
Operating mode, from●●
Control mode●●
Pump performance●●
Actual controlled value●●
Max. curve and duty point●-
Resulting setpoint●●
Liquid temperature●-
Speed●●
Acc. flow and specific energy●●
Power and energy consumption●●
Measured values●●
Analog input 1●●
Analog input 2●●
Analog input 3●
Pt100/1000 input 1●
Pt100/1000 input 2●
Analog output●
Warning and alarm●●
Actual warning or alarm●●
Warning log●●
Alarm log●●
Heat energy meter●-
Heat power●-
Heat energy●-
Flow rate●-
Volume●-
Hours counter●-
Temperature 1●-
Temperature 2●-
Differential temp.●-
Operating log●●
Operating hours●●
Trend data●-
Fitted modules●●
Date and time--
Product identification●●
Motor bearing monitoring●●
Multi-pump system●●
System operating status●●
System performance●●
System input power and energy●●
Pump 1, multi-pump sys.●●
Pump 2, multi-pump sys.●●
Pump 3, multi-pump sys.●●
1)
Only available if an advanced functional module is fitted.
1)
1)
1)
1)
1)
●
1)
●
1)
●
1)
●
English (US)
21
Page 22
English (US)
SettingsTPE3 (D)TPE2 (D)SectionPage
Setpoint●●15.1 Setpoint26
Operating mode●●15.2 Operating mode26
Set manual speed●●15.3 Set manual speed26
Control mode●●15.4 Control mode26
FLOW
LIMIT
●●15.5 FLOWLIMIT31
Automatic Night Setback●-15.6 Automatic Night Setback31
Analog inputs●●15.7 Analog inputs31
Analog input 1, setup●●
Analog input 2, setup●●
Analog input 3, setup●
1)
1)
●
Built-in Grundfos sensor●-
Pt100/1000 inputs●
Pt100/1000, setup●
1)
1)
1)
●
1)
●
15.8 Pt100/1000 inputs31
Digital inputs●●15.9 Digital inputs32
Digital input 1, setup●●
Digital input 2, setup●
1)
1)
●
Digital inputs/outputs●●15.10 Digital inputs/outputs32
Motor bearing maintenance●●
Limit-exceeded function-●15.16.1 Limit-exceeded function38
Special functions●●15.17 Special functions38
Pulse flow meter setup-●15.17.1 Pulse flow meter setup38
Ramps-●15.17.2 Ramps38
Standstill heating●●
Communication●●15.18 Communication38
Pump number●●15.18.1 Pump number38
Enable/disable radio communication●●15.18.2 Enable/disable radio communication38
General settings●●15.19 General settings39
1)
Only available if an advanced functional module is fitted.
AssistTPE3 (D)TPE2 (D)SectionPage
Assisted pump setup●●
Setup, analog input●●
Setting of date and time-Multi-pump setup●●16.1 Multi-pump setup39
Description of control mode●●
Assisted fault advice●●
22
Page 23
14. Grundfos GO Remote
+
+
+
1
2
3
The pump is designed for wireless radio or infrared
communication with the Grundfos GO Remote.
The Grundfos GO Remote enables setting of functions and gives
access to status overviews, technical product information and
actual operating parameters.
The Grundfos GO Remote offers the following mobile
interfaces (MI). See fig. 33.
Fig. 33 Grundfos GO Remote communicating with the pump
Pos. Descr ipt ion
via radio or infrared connection (IR)
Grundfos MI 202:
Add-on module which can be used in conjunction with an
1
Apple iPhone or iPod with 30-pin connector and iOS 5.0
or later, e.g. fourth generation iPhone or iPod.
Grundfos MI 204:
Add-on module which can be used in conjunction with an
Apple iPhone or iPod with Lightning connector, e.g. fifth
2
generation iPhone or iPod.
(The MI 204 is also available together with an Apple iPod
touch and a cover.)
Grundfos MI 301:
Separate module enabling radio or infrared
communication. The module can be used in conjunction
3
with an Android or iOS-based smart device with
Bluetooth connection.
English (US)
TM06 0744 0914
14.1 Communication
When the Grundfos GO Remote communicates with the pump,
the indicator light in the middle of the Grundfos Eye will flash
green. See section 21. Grundfos Eye.
Communication must be established using one of these
communication types:
• radio communication
• infrared communication.
14.1.1 Radio communication
Radio communication can take place at distances up to
30 meters. It is necessary to enable communication by
pressing or on the pump control panel.
14.1.2 Infrared communication
When communicating via infrared light, the Grundfos GO Remote
must be pointed at the pump control panel.
23
Page 24
English (US)
14.2 Menu overview for Grundfos GO Remote
14.2.1 Main menus
DashboardTPE3 (D)TPE2 (D)
●●
StatusTPE3 (D)TPE2 (D)
Resulting setpoint●●
Actual controlled value●●
Motor speed (rpm, %)●●
Power consumption●●
Energy consumption●●
Acc. flow, specific energy●●
Operating hours●●
Liquid temperature●-
Analog input 1●●
Analog input 2●●
Analog input 3●
Pt100/1000 input 1●
Pt100/1000 input 2●
Analog output●
Digital input 1●●
Digital input 2●
Digital in/output 3●●
Digital in/output 4●
Fitted modules●●
Trend data●-
Heat energy meter●-
1)
Only available if an advanced functional module is fitted.
1)
1)
1)
1)
1)
1)
1)
●
1)
●
1)
●
1)
●
1)
●
1)
●
24
Page 25
SettingsTPE3 (D)TPE2 (D)SectionPage
Setpoint●●15.1 Setpoint26
Operating mode●●15.2 Operating mode26
Control mode●●15.4 Control mode26
Date and time●
1)
1)
●
Flow limit●-15.5 FLOWLIMIT31
Automatic Night Setback●-15.6 Automatic Night Setback31
Temperature influence●-15.15.3 Temperature influence37
Buttons on product●●15.19.3 Enable/disable settings39
Controller●●15.13 Controller settings33
Operating range●●15.14 Operating range34
Ramps-●15.17.2 Ramps38
Pump number●●15.18.1 Pump number38
Radio communication●●15.18.2 Enable/disable radio communication38
Analog input 1●●
15.7 Analog inputs31Analog input 2●●
Analog input 3●
Pt100/1000 input 1●
Pt100/1000 input 2●
1)
1)
1)
Digital input 1●●
Digital input 2●
1)
Digital in/output 3●●
Digital in/output 4●
Predefined setpoint●
Analog output●
1)
1)
1)
1)
●
1)
●
1)
●
1)
●
1)
●
1)
●
1)
●
15.8 Pt100/1000 inputs31
15.9 Digital inputs32
15.10 Digital inputs/outputs32
15.15.2 Predefined setpoints37
15.12 Analog output33
External setpoint funct.●●15.15.1 External setpoint influence35
Signal relay 1●●
Signal relay 2●●
Limit 1 exceeded -●
Limit 2 exceeded -●
15.11 Relay outputs33
15.16.1 Limit-exceeded function38
Standstill heating●●
Motor bearing monitoring●●
Service●●
Store settings●●
Recall settings●●
Undo●●
Pump name●●
Unit configuration●●
1)
Only available if an advanced functional module is fitted.
The setpoint for all control modes, except AUTO
FLOW
, can be set in this submenu when the desired control
ADAPT
mode has been selected. See section 15.4 Control mode.
15.2 Operating mode
Possible operating modes:
• Normal
The pump runs according to the selected control mode.
• Stop
The pump stops.
• Min.
The minimum curve mode can be used in periods in which a
minimum flow is required.
This operating mode is for instance suitable for manual night
setback if "Automatic Night Setback" is not desired.
• Max.
The maximum curve mode can be used in periods in which a
maximum flow is required.
This operating mode is for instance suitable for systems with
hot-water priority.
• Manual
The pump is operating at a manually set speed.
See section 15.3 Set manual speed.
The pump can be set to operate according to the maximum or
minimum curve, like an uncontrolled pump. See fig. 34.
Fig. 34 Maximum and minimum curves
15.3 Set manual speed
The pump speed can be set in %. When the operating mode has
been set to "Manual", the pump will run at the set speed.
The operating mode must be set to "
before a control mode can be enabled.
You can change the setpoint for all control modes, except
ADAPT
and FLOW
ADAPT
AUTO
"Settings" when you have selected the desired control mode.
15.4.1 AUTO
,in the "Setpoint" submenu under
ADAPT
Pump variantAUTO
TPE3 (D)●
TPE2 (D)-
The AUTO
control mode continuously adapts the pump
ADAPT
performance according to the actual system characteristic.
You cannot set the setpoint manually.
Fig. 35 AUTO
When you have enabled the AUTO
will start with the factory setting, H
performance to A
ADAPT
. See fig. 35.
1
control mode, the pump
ADAPT
= H
fac
, and then adjust its
set1
When the pump registers a lower head on the max. curve, A
AUTO
lower control curve, H
pump will adjust its performance to A
function will automatically select a correspondingly
ADAPT
. If the valves in the system close, the
set2
.
3
A1:Original duty point.
:Lower registered head on the max. curve.
A
2
TM00 5547 0995
:Original setpoint setting.
H
set1
:New setpoint after AUTO
H
set2
:Factory setting.
H
fac.
H
The AUTO
control where the control curves have a fixed origin, H
The AUTO
: A fixed value of 5 ft (1.5 m).
auto_min
control mode is a form of proportional-pressure
ADAPT
control mode has been developed specifically
ADAPT
:New duty point after AUTO
A
3
ADAPT
ADAPT
control.
control.
for heating systems and Grundfos do not recommend it for
air-conditioning and cooling systems.
Normal
ADAPT
"
2
auto_min
TM05 7910 1613
, the
.
26
Page 27
15.4.2 FLOW
Note
Note
H
Q
Q
max
25 %
90 %
H
auto_min
H
fac
Q
fac
Setting range
H
Q
Hset
Hset
2
p
H
Q
p
p
Pump variantFLOW
ADAPT
ADAPT
TPE3 (D)●
TPE2 (D)-
When you select FLOW
ensure that the flow never exceeds the entered FLOW
The setting range for FLOW
, the pump will run AUTO
ADAPT
is 25 to 90 %, of the Q
LIMIT
pump.
The factory setting of the FLOW
AUTO
See fig. 36.
factory setting meets the maximum curve.
ADAPT
Do not set the FLOW
dimensioned duty point.
is the flow where the
LIMIT
lower than the
LIMIT
ADAPT
LIMIT
max
and
value.
of the
Example
• Factory-fitted differential-pressure sensor.
English (US)
Fig. 38 Proportional pressure
15.4.4 Constant pressure
Pump variantConstant pressure
TPE3 (D)TPE2 (D)●
The pump maintains a constant discharge pressure,
independently of the flow rate. See fig. 39.
Fig. 36 FLOW
ADAPT
15.4.3 Proportional pressure
Pump variantProportional pressure
TPE3 (D)●
TPE2 (D)-
The pump head is reduced at decreasing water demand and
increased at rising water demand. See fig. 37.
This control mode is especially suitable in systems with relatively
large pressure losses in the distribution pipes. The head of the
pump will increase proportionally to the flow in the system to
compensate for the large pressure losses in the distribution
pipes.
The setpoint can be set with an accuracy of 0.33 ft (0.1 m).
The head against a closed valve is half the setpoint, H
set
.
TM05 7912 1613
TM05 7901 1613
Fig. 39 Constant pressure
This control mode requires an external pressure sensor as shown
in the examples below:
Examples
• One external pressure sensor.
Fig. 40 Constant pressure
TM05 7909 1613
Fig. 37 Proportional pressure
27
Page 28
English (US)
H
Q
t
t
t
t
H
Q
p
p
p
p
p
p
p
p
p
15.4.5 Constant temperature
15.4.6 Constant differential pressure
Pump variantConstant temperature
TPE3 (D)●
TPE2 (D)●
This control mode ensures a constant temperature.
Constant temperature is a comfort control mode that can be used
in domestic hot-water systems to control the flow to maintain a
fixed temperature in the system. See fig. 41. When this control
mode is used, no balancing valves must be installed in the
system.
Fig. 41 Constant temperature
This control mode requires either an internal or external
temperature sensor as shown in the examples below:
Examples
• Factory-fitted temperature sensor (only TPE3 (D)).
Pump variant
Constant differential
pressure
TPE3 (D)●
TPE2 (D)●
The pump maintains a constant differential pressure,
independently of the flow in the system. See fig. 43. This control
mode is primarily suitable for systems with relatively small
pressure losses.
TM05 7900 1613
Fig. 43 Constant differential pressure
This control mode requires either an internal or external
differential-pressure sensor or two external pressure sensors as
shown in the examples below:
The pump maintains a constant differential temperature in the
system and the pump performance is controlled according to this.
See fig. 45.
Fig. 45 Constant differential temperature
This control mode requires either two temperature sensors or one
external differential-temperature sensor as shown in the
examples below:
Examples
• Factory-fitted temperature sensor and an external
temperature sensor (only TPE3 (D)).
Pump variantConstant flow rate
TPE3 (D)TPE2 (D)●
The pump maintains a constant flow in the system, independently
of the head. See fig. 47.
TM05 7954 1713
Fig. 47 Constant flow rate
This control mode requires an external flow sensor as shown
below:
Example
• One external flow sensor.
English (US)
TM05 7955 1713
• Two external temperature sensors.
• One external differential-temperature sensor.
Fig. 46 Constant differential temperature
Fig. 48 Constant flow rate
29
Page 30
English (US)
H
Q
L
L
Note
Note
H
Q
H [%]
Q 80 %
100 %
Limited max. curve
15.4.9 Constant level
15.4.10 Constant other value
Pump variantConstant level
TPE3 (D)TPE2 (D)●
The pump maintains a constant level, independently of the flow
rate. See fig. 49.
Fig. 49 Constant level
This control mode requires an external level sensor.
The pump can control the level in a tank in two ways:
• as an emptying function where the pump draws the liquid from
the tank.
• as a filling function where the pump pumps the liquid into the
tank.
See fig. 50.
The type of level control function depends on the setting of the
built-in controller. See section 15.13 Controller settings.
Examples
• One external level sensor.
– emptying function.
Pump variantConstant other value
TPE3 (D)TPE2 (D)●
Any other value is kept constant.
15.4.11 Constant curve
Pump variantConstant curve
TPE3 (D)TPE2 (D)●
You can set the pump to operate according to a constant curve,
like an uncontrolled pump. See fig. 51.
You can set the desired speed in % of maximum speed in the
range from 25 to 100 %.
TM05 7941 1613
TM05 7957 1713
Fig. 51 Constant curve
Depending on the system characteristic and the
duty point, the 100 % setting may be slightly
smaller than the pump's actual maximum curve
even though the display shows 100 %. This is due
to power and pressure limitations built into the
pump. The deviation varies according to pump
type and pressure loss in the pipes.
• One external level sensor.
– filling function.
Fig. 50 Constant level
30
TM05 7913 1613
Fig. 52 Power and pressure limitations influencing the max.
curve
Page 31
15.5 FLOW
Note
Note
H
Q
Q
max
Q
max
Q
limit
25 %
90 %
Setting range
LIMIT
15.7 Analog inputs
Available inputs depending on the functional module fitted in the
Pump variantFLOW
TPE3 (D)●
TPE2 (D)-
FLOW
LIMIT
• Enable FLOW
•Set FLOW
LIMIT
LIMIT
.
function.
LIMIT
pump:
Function (terminal)
FM 200
(standard)
FM 300
(advanced)
Analog input 1, setup (4)●●
Analog input 2, setup (7)●●
Analog input 3, setup (14)-●
English (US)
To set up an analog input, make the settings below.
Function
The analog inputs can be set to these functions:
• Not active
• Feedback sensor
• Ext. setpoint influence
See section 15.15 Setpoint influence
• Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
TM05 7908 1613
in the system by the sensor connected to the actual analog input.
Fig. 53 FLOW
The FLOW
control modes:
LIMIT
function can be combined with the following
LIMIT
• Prop. press.
• Con. diff. press.
• Con. diff. temp.
• Const. temp.
• Const. curve.
A flow-limiting function ensures that the flow never exceeds the
entered FLOW
The setting range for FLOW
pump.
The factory setting of the FLOW
AUTO
ADAPT
See fig. 36.
value.
LIMIT
is 25 to 90 % of the Q
LIMIT
is the flow where the
LIMIT
factory setting meets the maximum curve.
max
of the
15.6 Automatic Night Setback
Pump variantAutomatic Night Setback
Unit
Available measuring units:
ParameterPossible units
Pressureft, psi, bar, m, kPa
Pump flowgpm, m
3
/h, l/s, yd3/h
Liquid temperature°F, °C
Other parameter%
Electrical signal
Select signal type (0.5 - 3.5 V, 0-5 V*, 0-10 V, 0-20 mA or 4-20 mA).
Sensor range, min. value
Set the minimum value of the connected sensor.
Sensor range, max. value
Set the maximum value of the connected sensor.
15.8 Pt100/1000 inputs
Available inputs depending on the functional module fitted in the
pump:
TPE3 (D)●
TPE2 (D)-
Once you have enabled Automatic Night Setback , the pump
automatically changes between normal duty and night setback
(duty at low performance).
Changeover between normal duty and night setback depends on
the flow-pipe temperature.
The pump automatically changes over to night setback when the
built-in sensor registers a flow-pipe temperature drop of more
than 18 to 27 °F (10 to 15 °C) within approx. two hours.
The temperature drop must be at least 1.8 °F/min (0.1 °C/min).
Changeover to normal duty takes place without a time lag when
the temperature has increased by approx. 18 °F (10 °C).
You cannot enable Automatic Night Setback
when the pump is in constant-curve mode.
Function (terminal)
Pt100/1000 input 1, setup (17 and 18)-●
Pt100/1000 input 2, setup (18 and 19)-●
Function
The Pt100/1000 inputs can be set to these functions:
• Not active
• Feedback sensor
• Ext. setpoint influence
See section 15.15 Setpoint influence
• Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system.
FM 200
(standard)
FM 300
(advanced)
31
Page 32
English (US)
15.9 Digital inputs
Available inputs depending on the functional module fitted in the
pump:
15.10 Digital inputs/outputs
Available inputs/outputs depending on the functional module
fitted in the pump:
Function (terminal)
Digital input 1, setup (2 and 6)●●
Digital input 2, setup (1 and 9)-●
To set up a digital input, make the settings below.
Function
Select one of these functions:
• Not active
When set to "Not active", the input has no function.
• External stop
When the input is deactivated (open circuit), the pump will
stop.
• Min. (minimum speed)
When the input is activated, the pump will run at the set min.
speed.
• Max. (maximum speed)
When the input is activated, the pump will run at the set max.
speed.
• External fault
When the input is activated, a timer will be started. If the input
is activated for more than 5 seconds, the pump will be stopped
and a fault will be indicated.
• Alarm resetting
When the input is activated, a possible fault indication will be
reset.
• Dry running
When this function has been selected, lack of inlet pressure or
water shortage can be detected.
When lack of inlet pressure or water shortage (dry running) is
detected, the pump will be stopped. The pump cannot restart
as long as the input is activated.
This requires the use of an accessory, such as these:
– a pressure switch installed on the suction side of the pump
– a float switch installed on the suction side of the pump.
• Accumulated flow
When this function has been selected, the accumulated flow
can be registered. This requires the use of a flowmeter which
can give a feedback signal as a pulse per defined flow of
water.
See section 15.17.1 Pulse flow meter setup.
• Predefined setpoint digit 1 (applies only to digital input 2)
When digital inputs are set to predefined setpoint, the pump
will operate according to a setpoint based on the combination
of the activated digital inputs.
See section 15.15.2 Predefined setpoints.
The priority of the selected functions in relation to each other
appears from section 20. Priority of settings.
A stop command will always have the highest priority.
FM 200
(standard)
FM 300
(advanced)
Function (terminal)
Digital input/output 3,
setup (10 and 16)
Digital input/output 4,
setup (11 and 18)
To set up a digital input/output, make the settings below.
Mode
You can set the digital input/output 3 and 4 to act as digital input
or digital output:
• Digital input
• Digital output.
Function
You can set the digital input/output 3 and 4 to these functions:
The pump incorporates two signal relays for potential-free
signalling. See section 22. Signal relays for further information.
You can configure the signal relays to be activated by one of the
following incidents:
• Ready
• Operation
• Alarm
• Warning
• Limit 2 exceeded*
• Limit 1 exceeded*
• Pump running
• Relubricate
• Control of external fan
• Not active.
* Only TPE2 (D).
15.12 Analog output
Whether the analog output is available or not, depends on the
functional module fitted in the pump:
Function (terminal)
FM 200
(standard)
Analog output-●
To set up the analog output, make the settings below.
Output signal
• 0-10 V
• 0-20 mA
• 4-20 mA.
Function of analog output
• Actual speed
• Actual value
• Resulting setpoint
• Motor load
• Motor current
• Limit 1 exceeded*
• Limit 2 exceeded*
• Flow rate
* Only TPE2 (D).
FM 300
(advanced)
Pump variantController settings
TPE3 (D)●
TPE2 (D)●
The pumps have a factory default setting of gain (Kp) and integral
time (T
).
i
However, if the factory setting is not the optimum setting, you can
change the gain and the integral time:
• Set the gain (K
• Set the integral-action time (T
3600 s.
) within the range from 0.1 to 20.
p
) within the range from 0.1 to
i
If you have selected 3600 s, the controller will function as a
P controller.
Furthermore, you can set the controller to inverse control.
This means that if the setpoint is increased, the speed will be
reduced. In the case of inverse control, set the gain (K
the range from -0.1 to -20.
) within
p
Guidelines for setting of PI controller
The tables below show the recommended controller settings:
Differential-pressure
control
K
p
T
i
0.50.5
L1 < 16.4 ft (5 m): 0.5
0.5
L1 > 16.4 ft (5 m): 3
L1 > 32.8 ft (10 m): 5
L1 = Distance ft (m) between pump and sensor.
English (US)
33
Page 34
English (US)
L2
t
L2
t
t
L2
t
t
t
L2
Q
p
p
Note
Note
L
L
Max. speed (fixed)
User-set max. speed
Operating range
User-set min. speed
Min. speed (fixed)
24 %
12 %
0 %
67 %
100 %
K
p
Temperature control
Heating
system
Cooling
1)
system
2)
0.5-0.510 + 5L2
0.5-0.530 + 5L2
1)
In heating systems, an increase in pump performance will
result in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance will
result in a drop in temperature at the sensor.
L2 = Distance ft (m) between heat exchanger and sensor.
Differential-temperature
control
K
p
-0.510 + 5L2
Level controlK
T
i
p
T
i
-2.5100
2.5100
General rules of thumb
If the controller is too slow-reacting, increase K
.
p
If the controller is hunting or unstable, dampen the system by
reducing K
or increasing Ti.
p
15.14 Operating range
Pump variantOperating range
T
i
TPE3 (D)●
TPE2 (D)●
Set the operating range as follows:
• Set the minimum speed within the range from fixed minimum
speed to user-set maximum speed.
• Set the maximum speed within the range from user-set
minimum speed to fixed maximum speed.
The range between the user-set minimum and maxumum speeds
is the operating range. See fig. 54.
L2 = Distance ft (m) between heat exchanger and sensor.
Flow controlK
0.50.5
Constant-pressure controlK
0.50.5
0.10.5
Speeds below 25 % may result in noise from the
shaft seal.
p
p
T
i
T
i
TM00 6785 5095
Fig. 54 Example of min. and max. settings
34
Page 35
15.15 Setpoint influence
Note
Note
100
0
0
17.4
29
[PSI]
Setpoint influence [%]
External
setpoint
signal [%]
Actual
input
signal
Actual setpoint
Setpoint
Upper value
Lower value
100
0
100
20406080
Setpoint influence [%]
External input
[%]
100
0
100
20406080
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
15.15.1 External setpoint influence
Pump variantSetpoint influence
TPE3 (D)●
TPE2 (D)●
You can influence the setpoint by an external signal, either via
one of the analog inputs or, if you fit an advanced functional
module, via one of the Pt100/1000 inputs.
Before you can enable the "
of the analog inputs or Pt100/1000 inputs to
"
External setpoint function
See sections 15.7 Analog inputs and
15.8 Pt100/1000 inputs.
If more than one input has been set up for setpoint influence, the
function will select the analog input with the lowest number, for
example "Analog input 2", and ignore the other inputs, for
example "Analog input 3" or "Pt100/1000 input 1".
Example
See fig. 55.
At a lower sensor value of 0 psi, a set setpoint of 29 psi and an
external setpoint of 60 %, the actual setpoint is 0.60 x (29 - 0) + 0
= 17.4 psi.
Actual setpoint = actual input signal x (setpoint - lower value) +
lower value.
0100
Digital inputs
".
", set one
You can select these functions:
• Not active
When set to "Not active", the setpoint will not be influenced
from any external function.
• Linear function
The setpoint is influenced linearly from 0 to 100 %. See fig. 56.
Fig. 56 Linear function
•"Linear with Stop" and "Linear with Min."
– Linear with Stop
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 57.
– Linear with Min.
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Min.".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 57.
English (US)
TM05 6280 4612TM05 6281 4612
Fig. 55 Example of setpoint influence
The table below gives an overview of the types of setpoint
influence and the availability depending on pump type.
Type of setpoint influence
Not active●●
Linear function●●
Linear with Stop-●
Linear with Min.●●
Inverse function-●
Inverse with Stop-●
Inverse with Min.-●
Influence table-●
Influence table with Stop at Min.-●
Influence table with Stop at Max.-●
Pump type
TPE3 (D)TPE2 (D)
TM06 0854 1014
Fig. 57 "Linear with Stop" and "Linear with Min."
35
Page 36
English (US)
100
0
100
20406080
Setpoint influence [%]
External input [%]
100
0
100
20406080
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
100
0
100
20406080
Setpoint influence [%]
External
input [%]
100
0
100
20406080
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
• Inverse function
The setpoint is influenced inversely from 0 to 100 %.
See fig. 58.
Fig. 58 Inverse function
•"Inverse with Stop" and "Inverse with Min."
– Inverse with Stop
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Stop".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal".
See fig. 59.
– Inverse with Min.
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal".
See fig. 59.
• Influence table
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
TM05 6283 4612TM05 6283 4612
TM05 6284 4612TM05 6285 4612
Fig. 60 Influence table
• Influence table with Stop at Min.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 61.
Fig. 59 "Inverse with Stop" and "Inverse with Min."
36
Fig. 61 Influence table with Stop at Min.
Page 37
• Influence table with Stop at Max.
100
0
100
20406080
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
Note
Note
H
T [°F]
30 %
68122176
T [°C]
205080
100 %
H
actual
T
actual
H
Q
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating mode
will be changed back to "Normal".
See fig. 62.
Fig. 62 Influence table with Stop at Max.
15.15.2 Predefined setpoints
15.15.3 Temperature influence
Pump variantTemperature influence
TPE3 (D)●
TPE2 (D)-
When you enable this function in proportional- or
constant-pressure control mode, the setpoint for head will be
reduced according to the liquid temperature.
Temperature influence can be set to function at liquid
temperatures below +176 °F or +122 °F (80 °C or 50 °C).
These temperature limits are called T
. The setpoint is
max.
reduced in relation to the head set (= 100 %) according to the
characteristics below.
TM05 6286 4612
Fig. 63 Select the measured parameter of Pt100/1000 input 2
English (US)
TM05 7946 1613
Pump variantPredefined setpoints
TPE3 (D)●
TPE2 (D)●
Seven predefined setpoints can be set and activated by
combining the input signals to digital inputs 2, 3 and 4 as shown
in the table below.
The actual liquid temperature T
to be reduced from 100 % to H
= +176 °F (+80 °C) has been
max.
causes the setpoint for head
actual
.
actual
The temperature influence function requires the following:
• Proportional-pressure, constant-pressure or constant-curve
control mode.
• Pump installed in flow pipe.
• System with flow-pipe temperature control.
Temperature influence is suitable for the following systems:
• Systems with variable flows (for example two-pipe heating
systems) in which the enabling of the temperature influence
function will ensure a further reduction of the pump
performance in periods with small heating demands and
consequently a reduced flow-pipe temperature.
• Systems with almost constant flows (for example one-pipe
heating systems and underfloor heating systems), in which
variable heating demands cannot be registered as changes in
the head as is the case with two-pipe heating systems. In such
systems, you can only adjust the pump performance by
enabling the temperature influence function.
Selection of T
max.
In systems with a dimensioned flow-pipe temperature of:
• up to and including +131 °F (+55 °C),
select T
• above +131 °F (+55 °C), select T
= +122 °F (+50 °C)
max.
= +176 °F (80 °C).
max.
You cannot use the temperature influence
function in air-conditioning and cooling systems.
37
Page 38
English (US)
Rated
Ramp-upRamp-down
Speed
Time
Minimum
Initial rampFinal ramp
Maximum
15.16 Monitoring functions
15.16.1 Limit-exceeded function
Pump variantLimit-exceeded function
TPE3 (D)TPE2 (D)●
This function can monitor set limits of analog values. It will react if
the values exceed the limits. Each limit can be set as a maximum
or minimum value. For each of the monitored values, you must
define a warning limit and an alarm limit.
The function makes it possible to monitor two different locations
in a pump system at the same time. For instance the pressure at
a consumer and the pump discharge pressure. This ensures that
the discharge pressure does not reach a critical value.
If the value exceeds the warning limit, a warning is given. If the
value exceeds the alarm limit, the pumps will be stopped.
You can set a delay between the detection of an exceeded limit
and the activation of a warning or an alarm. You can also set a
delay for resetting a warning or an alarm.
You can reset a warning automatically or manually.
Furthermore, you canset whether the system is to restart
automatically after an alarm, or if the alarm must be reset
manually. Restarting can be delayed by an adjustable time.
You can also set a startup delay ensuring that the system reaches
a steady state before the function becomes active.
15.17.2 Ramps
Pump variantRamps
TPE3 (D)TPE2 (D)●
The setting of ramps is only relevant in the case of constant-curve
operation.
The ramps determine how quickly the motor can accelerate and
decelerate, respectively, during start/stop or setpoint changes.
The following can be set:
• acceleration time, 0.1 to 300 s
• deceleration time, 0.1 to 300 s.
The times apply to the acceleration from stop to rated speed and
the deceleration from rated speed to stop, respectively.
At short deceleration times, the deceleration of the motor may
depend on load and inertia as there is no possibility of actively
braking the motor.
If the power supply is switched off, the deceleration of the motor
will only depend on load and inertia.
15.17 Special functions
15.17.1 Pulse flow meter setup
Pump variantPulse flow meter setup
TPE3 (D)TPE2 (D)●
You can connect an external pulse flowmeter to one of the digital
inputs in order to register the actual and accumulated flows.
Based on this, you can also calculate the specific energy btu/lb
3
(kWh/m
To enable a pulse flowmeter, set one of the digital-input functions
to "Accumulated flow" and set the pumped volume per pulse.
See section 15.9 Digital inputs.
).
TM03 9439 0908
Fig. 64 Ramp-up and ramp-down
15.18 Communication
15.18.1 Pump number
Pump variantPump number
TPE3 (D)●
TPE2 (D)●
You can allocate a unique number to the pump. This makes it
possible to distinguish between pumps in connection with bus
communication.
15.18.2 Enable/disable radio communication
Pump variantPump number
TPE3 (D)●
TPE2 (D)●
You can set the radio communication to either enabled or
disabled.
38
Page 39
15.19 General settings
Note
Note
16. Assist
Pump variantGeneral settings
TPE3 (D)●
TPE2 (D)●
15.19.1 Language
A number of languages is available.
Measuring units are automatically changed according to selected
language.
15.19.2 Units
In this menu you can select between US and SI units. The setting
can be made generally for all parameters or customized for each
individual parameter.
15.19.3 Enable/disable settings
In this display, you can disable the possibility of making settings
for protective reasons.
To unlock the pump and allow settings, press
and simultaneously for at least 5 seconds.
15.19.4 Delete history
In this menu you can delete the following historic data:
• Delete work log.
• Delete heat energy data.
• Delete energy consumption.
15.19.5 Define Home display
In this menu you can select whether the "Home" display should
show various user-defined parameters or a graphical illustration
of a performance curve with the actual duty point of the pump.
15.19.6 Display settings
In this menu you can adjust the display brightness and define
whether or not the display should turn off if no buttons have been
activated for a period of time.
15.19.7 Store actual settings
In this menu you can store the actual settings for later use.
15.19.8 Recall stored settings
In this menu you can recall the last stored settings that the pump
will then use.
15.19.9 Run startup guide
The startup guide will guide you through the general settings of
the pump.
16.1 Multi-pump setup
Pump variantMulti-pump setup
TPE3 (D)●
TPE2 (D)●
The multipump function enables the control of single-head pumps
connected in parallel or twin-head pumps without the use of
external controllers. The pumps in a multipump system
communicate with each other via the wireless GENIair connection
or the wired GENI connection.
You set up a multipump system via a selected pump, i.e. the
master pump (first selected pump). You can connect all Grundfos
pumps with a wireless GENIair connection to the multipump
system.
The multipump functions are described in the following sections.
16.1.1 Alternating operation
Only one pump is operating at a time.
The change from one pump to the other depends on time or
energy. If a pump fails, the other pump will take over
automatically.
Pump system:
• Twin-head pump.
• Two single-head pumps connected in parallel.
The pumps must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
16.1.2 Backup operation
One pump is operating continuously. The backup pump is
operated at intervals to prevent seizing up. If the duty pump stops
due to a fault, the backup pump will start automatically.
Pump system:
• Twin-head pump.
• Two single-head pumps connected in parallel.
The pumps must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
16.1.3 Cascade operation
Cascade operation ensures that the pump performance is
automatically adapted to the consumption by switching pumps on
or off. The system thus runs as energy-efficiently as possible with
a constant pressure and a limited number of pumps.
When a twin-head pump is running in constant-pressure control
mode, the second pump head will start at 90 % and stop at 50 %
performance.
All pumps in operation will run at equal speed. Pump changeover
is automatic and depends on energy, operating hours and fault.
Pump system:
• Twin-head pump.
• Two to four single-head pumps connected in parallel.
The pumps must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
• The control mode must be set to "Const. pressure" or "Const. curve".
English (US)
39
Page 40
English (US)
H
Q
H
Q
H
Q
Hset
Hset
2
H
Q
17. Selection of control mode
System applicationSelect this control mode
AUTO
ADAPT
Recommended for most heating systems, especially in systems with relatively large pressure
losses in the distribution pipes. See description under proportional pressure.
In replacement situations where the proportional-pressure duty point is unknown.
The duty point has to be within the AUTO
automatically makes the necessary adjustment to the actual system characteristic.
This setting ensures minimum energy consumption and low noise level from valves, which
reduces operating costs and increases comfort.
operating range. During operation, the pump
ADAPT
The FLOW
This control mode is suitable for systems where you want a maximum flow limit, FLOW
The pump continuously monitors and adjusts the flow, thus ensuring that the selected
FLOW
LIMIT
Main pumps in boiler applications where a steady flow through the boiler is required. No extra
control mode is a combination of AUTO
ADAPT
is not exceeded.
ADAPT
and FLOW
LIMIT
.
.
LIMIT
energy is used for pumping too much liquid into the system.
In systems with mixing loops, you can use the control mode to control the flow in each loop.
Benefits:
• Enough water for all loops at peak load conditions if each loop has been set to the right
maximum flow.
• The dimensioned flow for each zone (required heat energy) is determined by the flow from
the pump.
This value can be set precisely in the FLOW
throttling valves.
control mode without the use of pump
ADAPT
• When the flow is set lower than the balancing valve setting, the pump will ramp down instead
of losing energy by pumping against a balancing valve.
• Cooling surfaces in air-conditioning systems can operate at high pressure and low flow.
In systems with relatively large pressure losses in the distribution pipes and in air-conditioning
and cooling systems.
• Two-pipe heating systems with thermostatic valves and
– very long distribution pipes
– strongly throttled pipe balancing valves
– differential-pressure regulators
– large pressure losses in those parts of the system through which the total quantity of water
flows (for example boiler, heat exchanger and distribution pipe up to the first branching).
• Primary circuit pumps in systems with large pressure losses in the primary circuit.
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and
– dimensioned for natural circulation
– small pressure losses in those parts of the system through which the total quantity of water
flows (for example boiler, heat exchanger and distribution pipe up to the first branching) or
– modified to a high differential temperature between flow pipe and return pipe (for example
district heating).
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing valves.
• Primary circuit pumps in systems with small pressure losses in the primary circuit.
FLOW
ADAPT
Proportional pressure
Constant differential pressure
40
Page 41
System applicationSelect this control mode
H
Q
H
Q
Q
set
H
Q
H
Q
Constant temperature and constant
In systems with a fixed system characteristic.
Examples:
• one-pipe heating systems
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
You can use FLOW
with advantage to control the maximum circulation flow.
LIMIT
differential temperature
English (US)
If you install an external controller, the pump is able to change from one constant curve to
another, depending on the value of the external signal.
You can also set the pump to operate according to the maximum or minimum curve, like an
uncontrolled pump:
• You can use the maximum curve mode in periods in which a maximum flow is required.
This operating mode is for instance suitable for hot-water priority.
• You can use the minimum curve mode in periods in which a minimum flow is required.
This operating mode is for instance suitable for manual night setback if you do not want
Automatic Night Setback.
In systems requiring a constant flow, independently of pressure drop.
Examples:
• chillers for air-conditioning
• heating surfaces
• cooling surfaces.
In systems requiring a constant tank level, independently of the flow rate.
Examples:
• process water tanks
• boiler condensate tanks.
Constant curve
Constant flow rate
Constant level
In systems with pumps operating in parallel.
The multipump function enables the control of single-head pumps connected in parallel (two to
four pumps) and twin-head pumps without the use of external controllers. The pumps in a
multipump system communicate with each other via the wireless GENIair connection or the
wired GENI connection.
"Assist" menu
"Multi-pump setup"
41
Page 42
English (US)
Note
Note
18. Changing the position of the control panel
You can turn the control panel 180 °. Follow the instructions
below.
1. Loosen the four screws (TX25) holding the terminal box cover.
Fig. 65 Loosening the screws
2. Remove the terminal box cover.
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
Fig. 68 Turning the plastic cover
5. Reposition the plastic cover correctly on the four rubber
TM05 5351 3612TM05 5352 3612TM05 5353 3612
pins (pos. C). Make sure that the locking tabs (pos. A) are
placed correctly.
TM05 5354 3612TM05 5355 3612TM05 5356 3612
Fig. 66 Removing the terminal box cover
3. Press and hold in the two locking tabs (pos. A) while gently
lifting the plastic cover (pos. B).
Fig. 67 Lifting the plastic cover
Fig. 69 Re-positioning the plastic cover
6. Fit the terminal box cover, and make sure that it is also turned
180 ° so that the buttons on the control panel are aligned with
the buttons on the plastic cover.
Tighten the four screws (TX25) with 3.69 lbf-ft (5 Nm).
Fig. 70 Fitting the terminal box cover
42
Page 43
19. Bus signal
Note
Note
The motor enables serial communication via an RS-485 input.
The communication is carried out according to the Grundfos
GENIbus protocol and enables connection to a building
management system or another external control system.
Via a bus signal, you can remote-set motor operating parameters,
such as setpoint and operating mode. At the same time, the
motor can, via the bus, provide status information about important
parameters, such as actual value of control parameter, input
power and fault indications.
Contact Grundfos for further information.
If you use a bus signal, the number of settings
available via the Grundfos GO Remote will be
reduced.
20. Priority of settings
You can always set he motor to operation at maximum speed or
to stop with the Grundfos GO Remote.
If you enable two or more functions at the same time, the motor
will operate according to the function with the highest priority.
Example: If, via the digital input, the motor has been set to
maximum speed, the motor control panel or the Grundfos GO
Remote can only set the motor to "Manual" or "Stop".
The priority of the settings appears from the table below:
* If the bus communication is interrupted, the motor will resume its previous operating mode, for example "Stop", selected with the
Grundfos GO Remote or on the motor control panel.
Grundfos GO Remote or
control panel on motor
Digital inputBus communication
43
Page 44
English (US)
A
21. Grundfos Eye
The Grundfos Eye indicate the operating condition of the motor
on the control panel. See fig. 71, pos. A.
TM05 5993 4312
Fig. 71 Grundfos Eye
Grundfos EyeIndicationDescription
No lights on.
Two opposite green indicator lights
rotating in the direction of rotation of the
motor when seen from the non-drive end.
Two opposite green indicator lights
permanently on.
One yellow indicator light rotating in the
direction of rotation of the motor when
seen from the non-drive end.
One yellow indicator light permanently on.
Two opposite red indicator lights flashing
simultaneously.
The green indicator light in the middle
flashes quickly four times.
The green indicator light in the middle
flashes continuously.
The green indicator light in the middle is
permanently on.
The green indicator light in the middle
flashes quickly while the Grundfos Go
Remote is exchanging data with the motor.
It will take a few seconds.
Power off.
Motor not running.
Power on.
Motor running.
Power on.
Motor not running.
Warning.
Motor running.
Warning.
Motor stopped.
Alarm.
Motor stopped.
Remote control with the Grundfos GO Remote via
radio.
The motor is trying to communicate with the
Grundfos GO Remote. The motor in question is
highlighted in the Grundfos GO Remote display to
inform the user of the location of the motor.
When the motor in question is selected in the
Grundfos GO Remote menu, the green indicator light
in the middle will flash continuously. Press on the
motor control panel to allow remote control and data
exchange via the Grundfos GO Remote.
Remote control with the Grundfos GO Remote via
radio.
The motor is communicating with the Grundfos GO
Remote via radio connection.
Remote control with the Grundfos GO Remote via
infrared light.
The motor is receiving data from the Grundfos GO
Remote via infrared communication.
44
Page 45
22. Signal relays
NCNOCNCNOCNCNOCNCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNOCNCNO
C
C
NO NC
C
NO NC
NCNOCNCNOCNCNO
C
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
NCNOCNCNOCNCNO
C
C
NO NC
NCNO
C
The motor has two outputs for potential-free signals via two
internal relays.
The signal outputs can be set to "Operation", "Pump running",
"Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table
below:
English (US)
DescriptionGrundfos Eye
Power off.
Off
Pump running in "Normal"
mode.
Green, rotating
Pump running in "Manual"
mode.
Green, rotating
Pump in operating mode
"Stop".
Green, steady
Warning, but the pump is
running.
Yellow, rotating
Contact position for signal relays when activated
Operation
Pump
running
ReadyAlarmWarning
Operating
mode
-
Normal, Min.
or Max.
Manual
Stop
Normal, Min.
or Max.
Warning, but the pump is
running in "Manual" mode.
Warning, but the pump
was stopped via "Stop"
command.
Alarm, but the pump is
running.
Alarm, but the pump is
running in "Manual" mode.
Pump stopped due to an
alarm.
Manual
Yellow, rotating
Stop
Yellow, steady
Normal, Min.
or Max.
Red, rotating
Manual
Red, rotating
Stop
Red, flashing
45
Page 46
English (US)
23. Maintenance and service
Warnin g
Before starting work on the pump, make sure that
the power supply has been switched off for at
least 5 minutes. Make sure that the power supply
cannot be accidentally switched on.
Warnin g
Make sure that the escaping water does not
cause injury to persons or damage to the
equipment.
Warnin g
If the pump is used for a liquid which is injurious
to health, it will be classified as contaminated.
In such cases, the proper precautions must be
taken to avoid injury to health when operating or
working on the pump.
23.1 Maintenance
23.1.1 Pump
The pump is maintenance-free.
If the pump is to be drained for a long period of inactivity, inject a
few drops of silicone oil on the shaft between the motor stool and
the coupling. This will prevent the shaft seal faces from sticking.
23.1.2 Motor
The motor must be checked at regular intervals. It is important to
keep the motor clean in order to ensure adequate ventilation.
If the pump is installed in a dusty environment, clean and check
the pump regularly.
23.2 Service
If Grundfos is requested to service the pump, it must be cleaned
before it is returned.
If proper cleaning is not possible, all relevant information about
the pumped liquid must be provided.
If the above is not fulfilled, Grundfos can refuse to accept the
pump for service.
Possible costs of returning the pump are to be paid by the
customer.
23.2.1 Integral shaft/coupling
TPE2 and TPE3 pumps have integral shaft/coupling.
We recommend that you do not remove the motor.
If the motor has been removed, it is necessary to remove the
motor stool in order to refit the motor correctly. Otherwise the
shaft seal may be damaged.
23.2.2 Blanking flanges
For twin-head pumps, a blanking flange with a pump housing
gasket is available. See fig. 72.
Fig. 72 Fitting the blanking flange
If one pump requires service, the blanking flange is fitted to allow
the other pump to continue operating.
TM05 7921 1613
46
Page 47
24. Fault finding
Warnin g
Before removing the terminal box cover or
removing/dismantling the pump, make sure that
the power supply has been switched off for at
least 5 minutes. Make sure that the power supply
cannot be accidentally switched on.
Warnin g
Make sure that the escaping water does not
cause injury to persons or damage to the
equipment.
FaultCause/remedy
1. Motor does not run when started.a) Supply failure.
b) Fuses blown.
c) Motor defective.
2. Motor alarm when the power supply is switched on.a) Supply failure.
b) Cable connection loose or faulty.
c) Motor winding defective.
d) Pump mechanically blocked.
3. Occasional motor alarm.a) Supply voltage periodically too low or too high.
b) Differential pressure across pump too low.
4. No motor alarm, but the pump does not run.a) Check the power supply.
b) Check fuses.
5. Pump capacity not constant.a) Pump inlet pressure too low.
b) Suction pipe/pump partly blocked by impurities.
c) Pump draws in air.
6. Pump runs but delivers no water.a) Suction pipe/pump blocked by impurities.
b) Foot or non-return valve blocked in closed position.
c) Leakage in suction pipe.
d) Air in suction pipe or pump.
7. Pump runs backwards when switched off.*a) Leakage in suction pipe.
b) Foot or non-return valve defective.
c) Foot or non-return valve blocked in open or partly open position.
8. Leakage in shaft seal.a) Shaft seal defective.
9. Noise.a) Pump is cavitating.
b) Pump does not rotate freely (frictional resistance) because of incorrect
pump shaft position.
c) Resonance in the installation.
d) Foreign bodies in the pump.
English (US)
* In twin-head pump installations, the backup pump will often rotate slowly.
47
Page 48
English (US)
Caution
25. Megging
Megging of an installation incorporating MGE
motors is not allowed, as the built-in electronics
may be damaged.
26. Technical data, single-phase motors
26.1 Supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Recommended fuse size
Motor size
[hp (kW)]
Min.
[A]
Max.
[A]
0.25 - 1.0 (0.12 - 0.75)610
1.5 - 2.0 (1.1 - 1.5)1016
You can use standard as well as quick-blow or slow-blow fuses.
26.2 Leakage current
Earth leakage current < 3.5 mA (AC supply).
Earth leakage current < 10 mA (DC supply).
The leakage currents are measured in accordance with
EN 61800-5-1:2007.
27. Technical data, three-phase motors
27.1 Supply voltage
• 3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Recommended fuse size
Motor size
[hp (kW)]
0.25 - 1.5 (0.12 - 1.1)66
2.0 - 3.0 (1.5 - 2.2)610
Standard as well as quick-blow or slow-blow fuses may be used.
27.2 Leakage current
Motor size
[hp (kW)]
1.0 - 3.0 (0.75 - 2.2)
(supply voltage < 400 V)
1.0 - 3.0 (0.75 - 2.2)
(supply voltage > 400 V)
The leakage currents are measured in accordance with
EN 61800-5-1:2007.
Min.
[A]
Leakage current
[mA]
< 3.5
< 5
Max.
[A]
28. Inputs/outputs
Ground reference (GND)
All voltages refer to GND.
All currents return to GND.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in severely
reduced operating reliability and motor life:
Relay 1:
Maximum contact load: 250 VAC, 2 A or 30 VDC, 2 A.
Relay 2:
Maximum contact load: 30 VDC, 2 A.
GENI terminals: -5.5 to 9.0 VDC or < 25 mADC.
Other input/output terminals: -0.5 to 26 VDC or < 15 mADC.
Digital inputs (DI)
Internal pull-up current > 10 mA at V
Internal pull-up to 5 VDC (currentless for V
Certain low logic level: V
Certain high logic level: V
< 1.5 VDC.
i
> 3.0 VDC.
i
Hysteresis: No.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
Maximum cable length: 1640 ft (500 m)
Open-collector digital outputs (OC)
Current sinking capability: 75 mADC, no current sourcing.
Load types: Resistive or/and inductive.
Low-state output voltage at 75 mADC: Max. 1.2 VDC.
Low-state output voltage at 10 mADC: Max. 0.6 VDC.
Overcurrent protection: Yes.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
Maximum cable length: 1640 ft (500 m)
Analog inputs (AI)
Voltage signal ranges:
• 0.5 - 3.5 VDC, AL AU.
• 0-5 VDC, AU.
•0-10 VDC, AU.
Voltage signal: R
> 100 kΩ at 77 °F (+25 °C).
i
Leak currents may occur at high operating temperatures.
Keep the source impedance low.
Current signal ranges:
• 0-20 mADC, AU.
• 4-20 mADC, AL AU.
Current signal: R
= 292 Ω.
i
Current overload protection: Yes. Change to voltage signal.
Measurement tolerance: - 0/+ 3 % of full scale (max.-point
coverage).
Screened cable: 20-16 AWG (0.5 - 1.5 mm
Maximum cable length: 1640 ft (500 m) (excl. potentiometer).
Potentiometer connected to +5 V, GND, any AI:
Use maximum 10 kΩ.
Maximum cable length: 328 ft (100 m).
= 0 VDC.
i
> 5 VDC).
i
2
).
2
).
2
).
48
Page 49
Analog output (AO)
Current sourcing capability only.
Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes.
Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (max-point coverage).
Screened cable: 20-16 AWG (0.5 - 1.5 mm
Maximum cable length: 1640 ft (500 m)
Pt100/1000 inputs (PT)
Temperature range:
• Minimum -22 °F (-30 °C) (88 Ω/882 Ω).
• Maximum 356 °F (+180 °C) (168 Ω/1685 Ω).
Measurement tolerance: ± 2.7 °F (1.5 °C).
Measurement resolution: < 0.54 °F (0.3 °C).
Automatic range detection (Pt100 or Pt1000): Yes.
Sensor fault alarm: Yes.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs*
Use Grundfos LiqTec sensor only.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
Power supplies (+5 V, +24 V)
+5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC (sourcing only).
• Overload protection: Yes.
•Sensor.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC (sourcing only).
• Overload protection: Yes.
Digital outputs (relays)
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 20-12 AWG (0.5 - 2.5 mm
Maximum cable length: 1640 ft (500 m)
Bus input
Grundfos GENIbus protocol, RS-485.
Screened 3-core cable: 20-16 AWG (0.5 - 1.5 mm
Maximum cable length: 1640 ft (500 m)
2
).
2
).
2
).
2
).
2
).
29. Other technical data
EMC (electromagnetic compatibility)
EN 61800-3.
Residential areas, unlimited distribution, corresponding to
CISPR 11, class B, group 1.
Industrial areas, unlimited distribution, corresponding to
CISPR 11, class A, group 1.
Contact Grundfos for further information.
Maximum tightening torques for the terminals can be found in
section 29.1 Torques, page 50.
1.4.3 Line reactors
Maximum line reactor size must not exceed 1.5 mH.
1.4.4 Fuse size/circuit breaker
If a short-circuit occurs, the pump can be used on a mains supply
delivering not more than 5000 RMS symmetrical amperes, 600 V
maximum.
Motor size
[hp (kW)]
0.50 to 3.0
(0.25 to 2.2)
Fuses
When the motor is protected by fuses, they must be rated for
480 V. Maximum sizes are stated in the table above.
Motors up to and including 3.0 hp (2.2 kW) require class K5 UR
fuses.
Circuit breaker
When the pump is protected by a circuit breaker, this must be
rated for a maximum voltage of 480 V. The circuit breaker must
be of the "inverse time" type.
The interrupting rating (RMS symmetrical amperes) must not be
less than the values stated in the table above.
1.4.5 Overload protection
Degree of overload protection provided internally by the drive, in
percent of full-load current: 102 %.
Fuse sizeCircuit breaker type/model
25 A25 A / inverse time
TM05 7572 1213TM05 7573 1213
50
Subject to alterations.
Page 51
Appendix
US: Inlet pressure stated in bar relative pressure (pressure gauge value measured on the suction side of the pump)