Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
1. Symbols used in this document
Warning
If these safety instructions are not observed, it may
result in personal injury.
Warning
If these instructions are not observed, it may lead to
electric shock with consequent risk of serious
personal injury or death.
Warning
The surface of the product may be so hot that it may
cause burns or personal injury.
Warning
Risk of dropping objects which may cause personal
injury.
Warning
Escaping vapour involves the risk of personal injury.
If these safety instructions are not observed, it may
result in malfunction or damage to the equipment.
Notes or instructions that make the job easier and
ensure safe operation.
2. Abbreviations and definitions
AIAnalog input
ALAlarm, out of range at lower limit
AOAnalog output
AUAlarm, out of range at upper limit
The ability to draw current into the terminal and
guide it towards earth in the internal circuitry.
The ability to push current out of the terminal
and into an external load which must return it
to earth.
Grundfos Digital Sensor.
Factory-fitted sensor in some Grundfos pumps.
Ground fault circuit interrupter.
(USA and Canada).
Low voltage with the risk of electric shock if the
terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, except earth faults in other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, including earth faults in other
circuits.
Single-head pump without factory-fitted
differential-pressure and temperature sensor.
Twin-head pump without factory-fitted
differential-pressure and temperature sensor.
Single-head pump with factory-fitted
differential-pressure and temperature sensor.
Twin-head pump with factory-fitted
differential-pressure and temperature sensor.
English (GB)
3
Page 4
3. General information
Note
English (GB)
These installation and operating instructions apply to the
Grundfos TPE2, TPE2 D and TPE3, TPE3 D pumps.
The pumps are fitted with frequency-controlled
permanent-magnet motors for single-phase or three-phase mains
connection.
3.1 Radio communication
This product incorporates a radio module for remote control
which is a class 1 device and can be used anywhere in the EU
without restrictions.
For use in USA and Canada, see page 66.
Some variants of these products and all products
sold in China and Korea have no possibility of radio
communication according to local legislation.
This product can communicate with Grundfos GO and other
products of the same type via the built-in radio module.
In some cases, an external antenna may be required.
Only Grundfos-approved external antennas may be connected to
this product, and only by a Grundfos-approved installer.
3.2 Battery
Pumps with the advanced functional module, FM 300, incorporate
a Li-ion battery. The Li-ion battery complies with the Battery
Directive (2006/66/EC). The battery does not contain mercury,
lead and cadmium.
4. Delivery and handling
4.1 Delivery
The pump is delivered from the factory in a carton with a wooden
bottom, specially designed for transport by fork-lift truck or a
similar vehicle.
4.2 Handling
Warning
TPE2 D, TPE3 D: Do not use the centrally positioned
thread of the pump housing for lifting purposes as the
thread is placed below the centre of gravity of the
pump.
Lift the pump by means of nylon straps. See figures 1 and 2.
TM05 7914 1613TM05 7915 1613
Fig. 1 TPE2, TPE3
Fig. 2 TPE2 D, TPE3 D
4
Page 5
5. Applications
Note
Caution
Installation
Washer
Pump
300 mm
The pumps are designed to circulate hot or cold water in
residential, institutional and industrial applications:
• heating systems
• district heating plants
• central heating systems for blocks of flats
• air-conditioning systems
• cooling systems.
In addition, the pumps are used for liquid transfer and water
supply in for instance:
• washing systems
• domestic hot-water systems
• industrial systems in general.
To ensure optimum operation, the dimensioning range of the
system must fall within the performance range of the pump.
6. Mechanical installation
Warning
When pumping hot or cold liquids, make sure that
persons cannot accidentally come into contact with
hot or cold surfaces.
In order to maintain the UL mark, follow the
additional installation procedures. See page 66.
Install the pump in a dry well-ventilated, but frost-free position.
When installing pumps with oval bolt holes in the pump flange
(PN 6/10), use washers as shown in fig. 3.
English (GB)
5.1 Pumped liquids
Warning
If the pump is used for a liquid which is injurious to
health, it will be classified as contaminated. In such
cases, take proper precautions to avoid injury to
health when operating or working on the pump.
The pump is suitable for thin, clean, non-aggressive and
non-flammable liquids, not containing solid particles or fibres that
may attack the pump mechanically or chemically.
Examples:
• Central heating system water (the water must meet the
requirements of accepted standards on water quality in
heating systems)
• cooling liquids
• domestic hot water
• industrial liquids
• softened water.
The pumping of liquids with a density and/or kinematic viscosity
higher than that of water will have the following effects:
• a considerable pressure drop
• a drop in hydraulic performance
• a rise in power consumption.
In such cases, fit the pump with a bigger motor. If in doubt,
contact Grundfos.
The EPDM O-rings fitted as standard are primarily suitable for
water.
If the water contains mineral/synthetic oils or chemicals or if other
liquids than water are pumped, chose the O-rings accordingly.
TM01 0683 1997
Fig. 3 Use of washers for oval bolt holes
Arrows on the pump housing show the direction of flow of liquid
through the pump.
The pump can be installed in horizontal or vertical pipes.
The motor must never fall below the horizontal plane.
For inspection and removal of motor or pump head, a clearance
of 300 mm is required above the motor. See fig. 4.
TM05 7916 1613TM05 7983 1713
Fig. 4 Required clearance above the motor
Twin-head pumps installed in horizontal pipes must be fitted with
an automatic air vent in the upper part of the pump housing. See
fig. 5.
The automatic air vent is not supplied with the pump.
Fig. 5 Automatic air vent
5
Page 6
If the liquid temperature falls below the ambient temperature,
Caution
Caution
A
English (GB)
condensation may form in the motor during standstill. In this case,
make sure that one of the drain holes in the motor flange is open
and points downwards. See fig. 6.
Fig. 6 Drain hole in motor flange
If twin-head pumps are used for pumping liquids with a
temperature below 0 °C (32 °F), condensed water may freeze
and cause the coupling to get stuck. You can solve the problem
by installing heating elements. Whenever possible, install the
pump with the motor shaft in horizontal position. See fig. 5.
Observe the conditions in section 9. Operating
conditions.
6.1 Pipework
Fit isolating valves on either side of the pump to avoid draining
the system if the pump needs to be cleaned or repaired.
The pump is suitable for pipeline mounting, provided that the
pipework is adequately supported on either side of the pump.
Single-head pumps are designed for pipeline mounting only.
Twin-head pumps are prepared for installation on a mounting
bracket or base plate.
When installing the pipes, make sure that the pump housing is
not stressed by the pipework.
The inlet and outlet pipes must be of an adequate size, taking the
pump inlet pressure into account.
To avoid sediment build-up, do not fit the pump at the lowest point
of the system.
Install the pipes so that air locks are avoided, especially on the
inlet side of the pump. See fig. 7.
Fig. 7 Correct pipework on the inlet side of the pump
6.2 Terminal box positions
TM05 7917 1613
You can turn the terminal box to any position. Change the
terminal box position as follows:
1. Loosen the clamp securing the pump head to the pump
housing. See fig. 8.
Fig. 8 Clamp (A)
2. Turn the pump head to the required position.
3. Check the following before the clamp is tightened:
– The contact face of the pump housing and that of the pump
– The clamp must be positioned correctly in the flange recess
Torque: 8 Nm (± 1 Nm).
TM00 2263 0195
Warning
Before starting work on the pump, make sure that the
power supply has been switched off for at least 5
minutes. Make sure that the power supply cannot be
accidentally switched on.
Warning
If the pump head has been lifted partly or completely
from the pump housing, pay special attention when
fitting the pump head again. See section 6.3 Fitting
of pump head.
Warning
When loosening the clamp, do not drop the pump
head. See fig. 8.
Warning
When loosening the clamp, there is a risk of
escaping vapour. See fig. 8.
head must be in full contact.
of both the pump head and the pump housing. See fig. 11.
TM06 0721 0814
The pump must not run against a closed outlet valve
or this will cause an increase in
temperature/formation of steam in the pump which
may cause damage to the pump.
If there is any risk of the pump running against a closed outlet
valve, ensure a minimum liquid flow through the pump by
connecting a bypass or a drain to the outlet pipe. The drain can
for instance be connected to a tank. A minimum flow rate of 10 %
of the flow rate at maximum efficiency is needed at all times.
Flow rate and head at maximum efficiency are stated on the
pump nameplate.
6
Page 7
6.3 Fitting of pump head
Caution
A
B
C
Warning
Before starting work on the pump, make sure that the
power supply has been switched off for at least 5
minutes. Make sure that the power supply cannot be
accidentally switched on.
Warning
If the pump head has been lifted partly or completely
from the pump housing, pay special attention when
fitting the pump head again. See instructions below.
Warning
Do not drop the pump head. See fig. 8.
Warning
When loosening the clamp, there is a risk of
escaping vapour. See fig. 8.
If for some reason the pump head has been lifted from the pump
housing, follow the following procedure in order to mount the
pump head correctly:
1. Visually check that the neck ring is centred in the pump
housing. See fig. 9.
3. Check the following before you tighten the clamp:
– The contact face of the pump housing and that of the pump
head must be in full contact.
– The clamp must be positioned correctly in the flange recess
of both the pump head and the pump housing. See fig. 11.
Torque: 8 Nm (± 1 Nm).
English (GB)
TM06 0724 0814
Fig. 11 Positioning of clamp ring
6.4 Base plate
Twin-head pumps have tapped holes in the bottom of the pump
housing. You can use the holes for mounting a base plate.
6.5 Insulation
Fig. 9 Centring of neck ring
2. Gently lower the pump head with rotor shaft and impeller into
the pump housing. See fig. 10.
Do not insulate the motor stool as this will trap any
vapour escaping from the shaft seal, thus causing
corrosion. Covering the motor stool with insulation
will also make inspection and service difficult.
Follow the guidelines in fig. 12 when insulating the pump.
Drain pumps which are not being used during periods of frost to
avoid damage.
7
Page 8
6.7 Ensuring motor cooling
Note
Note
D
Note
English (GB)
In order to ensure sufficient cooling of the motor, the
distance (D) between the end of the fan cover and a
wall or other fixed objects must always be at least 50
mm (irrespective of motor size). See fig. 13.
7. Electrical installation
Carry out the electrical connection according to local regulations.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Warning
Before making any connections in the terminal box,
make sure that the power supply has been switched
off for at least 5 minutes. Make sure that the power
supply cannot be accidentally switched on.
Connect the motor to an external all-pole mains
switch according to local regulations.
Earth and protect the motor against indirect contact
in accordance with local regulations.
If the power supply cable is damaged, it must be
replaced by the manufacturer, the manufacturer's
service partner or a similarly qualified person.
Fig. 13 Minimum distance (D) from the motor to a wall or other
fixed objects
6.8 Outdoor installation
When you install the motor outdoors, provide the motor with a
suitable cover to avoid condensation on the electronic
components. See fig. 14.
When fitting a cover to the motor, observe the
guideline in section 6.7 Ensuring motor cooling.
The cover must be sufficiently large to ensure that the motor is
not exposed to direct sunlight, rain or snow. Grundfos does not
supply covers. We therefore recommend that you have a cover
built for the specific application. In areas with high humidity, we
recommend that you enable the built-in standstill heating
function.
Fig. 14 Examples of covers
TM05 5236 3512
The user or the installer is responsible for the
installation of correct earthing and protection
according to local regulations. All operations must be
carried out by a qualified electrician.
7.1 Protection against electric shock (indirect contact)
Warning
Earth and protect the motor against indirect contact
in accordance with local regulations.
Protective earth conductors must always have a yellow/green
(PE) or yellow/green/blue (PEN) colour marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage transients in
accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking.
TM05 7919 1613
8
Page 9
7.2 Mains supply
Note
Caution
Note
Note
L1
L2
L3
L2
L1
L3
PE
7.2.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
If the motor is supplied through an IT network, use a
dedicated IT network motor. Contact Grundfos.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated earth conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 27.1 Supply voltage.
Fig. 15 Example of a mains-connected motor with mains
switch, backup fuse and additional protection
7.2.2 Three-phase supply voltage
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE.
In order to avoid loose connections, ensure that the
terminal block for L1, L2 and L3 is pressed home in
its socket when you have connected the supply
cable.
Corner grounding is not allowed for supply voltages
above 3 x 480 V, 50/60 Hz.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
If the motor is supplied through an IT network, use a
dedicated IT network motor. Contact Grundfos.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated earth conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 28.1 Supply voltage.
TM05 4034 1912TM05 3494 1512
Fig. 17 Example of a mains-connected motor with mains
switch, backup fuses and additional protection
English (GB)
TM05 3942 1812TM05 3495 1512
Fig. 16 Mains connection, single-phase motors
Fig. 18 Mains connection, three-phase motors
9
Page 10
7.3 Additional protection
Note
Note
ELCB
(GFCI)
ELCB
(GFCI)
Note
Note
English (GB)
7.3.1 Single-phase motors
If the motor is connected to an electric installation where an earth
leakage circuit breaker (ELCB) or ground fault circuit interrupter
(GFCI) is used as additional protection, this circuit breaker or
interrupter must be marked with the following symbol:
When an earth leakage circuit breaker or ground
fault circuit interrupter is selected, take the total
leakage current of all the electrical equipment in the
installation into account.
You find the leakage current of the motor in section 27.2 Leakage
current.
7.3.2 Three-phase motors
If the motor is connected to an electric installation where an earth
leakage circuit breaker (ELCB) or ground fault circuit interrupter
(GFCI) is used as additional protection, this circuit breaker or
interrupter must be of the following type:
• It must be suitable for handling leakage currents and cutting-in
with short pulse-shaped leakage.
• It must trip out when AC fault currents and fault currents with
DC content, i.e. pulsating DC and smooth DC fault currents,
occur.
For these motors, use an earth leakage circuit breaker or ground
fault circuit interrupter, type B.
The circuit breaker or interrupter must be marked with the
following symbols:
When an earth leakage circuit breaker or ground
fault circuit interrupter is selected, take the total
leakage current of all the electrical equipment in the
installation into account.
You find the leakage current of the motor section 28.2 Leakage
current.
Protection against phase unbalance
Connect the motor to a power supply with a quality corresponding
to IEC 60146-1-1, class C, to ensure correct motor operation at
phase unbalance.
This also ensures long life of the components.
7.4 Connection terminals
The descriptions and terminal overviews in this section apply to
both single-phase and three-phase motors.
For maximum tightening torques, see section Torques, page 63.
The number of terminals depends on the functional module. See
section 22. Identifying the functional module.
7.4.1 Connection terminals, advanced functional module, FM
300
The advanced functional module is only available as an option.
The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector outputs
• Input and output for Grundfos Digital Sensor
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 19.
Digital input 1 is factory-set to be start/stop input
where open circuit will result in stop.
A jumper has been factory-fitted between terminals 2
and 6. Remove the jumper if digital input 1 is to be
used as external start/stop or any other external
function.
As a precaution, the wires to be connected to the
connection groups below must be separated from
each other by reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by safety extra-low voltage
(SELV), thus ensuring protection against electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
Mains supply voltages up to 250 VAC can be connected to
this output.
SELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or safety
extra-low voltage to the output.
– Signal relay 2:
SELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or safety
extra-low voltage to the output as desired.
• Mains supply, terminals N, PE, L or L1, L2, L3, PE
A galvanically safe separation must fulfil the requirements for
reinforced insulation including creepage distances and
clearances specified in EN 61800-5-1.
* If you use an external supply source, there must be a
connection to earth.
Fig. 19 Connection terminals, FM 300 (option)
Digital input or output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
TM05 3509 3512
4AI1
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer
and sensor
6GNDEarth
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDEarth
15+24 VSupply
8+24 VSupply
26+5 V
Supply to potentiometer
and sensor
23GNDEarth
25GDS TX
24GDS RX
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
11
Page 12
7.4.2 Connection terminals, standard functional module (FM
Note
Note
English (GB)
200)
The standard module has these connections:
• two analog inputs
• two digital inputs or one digital input and one open-collector
output
• Grundfos Digital Sensor input and output
• two signal relay outputs
• GENIbus connection.
See fig. 20.
Digital input 1 is factory-set to start/stop input where
an open circuit will result in stop.
A jumper has been factory-fitted between terminals 2
and 6. Remove the jumper if digital input 1 is to be
used as external start/stop or any other external
function.
As a precaution, the wires to be connected to the
connection groups below must be separated from
each other by reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and
galvanically separated from other circuits.
All control terminals are supplied by safety extra-low voltage
(SELV), thus ensuring protection against electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
Mains supply voltages up to 250 VAC can be connected to
this output.
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
– Signal relay 2:
SELV:
The output is galvanically separated from other circuits.
Therefore, the supply voltage or safety extra-low voltage
can be connected to the output as desired.
• Mains supply, terminals N, PE, L or L1, L2, L3, PE
A galvanically safe separation must fulfil the requirements for
reinforced insulation including creepage distances and
clearances specified in EN 61800-5-1.
12
Page 13
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
Terminal TypeFunction
NC
C1Common
NO
Normally closed
contact
Normally open
contact
Signal relay 1
(LIVE or SELV)
English (GB)
* If you use an external supply source, there must be a
connection to earth.
Fig. 20 Connection terminals, FM 200
NC
C2Common
NO
Normally closed
contact
Signal relay 2
(SELV only)
Normally open
contact
Digital input or output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6GNDEarth
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDEarth
15+24 VSupply
TM05 3510 3512
8+24 VSupply
26+5 V
Supply to potentiometer and
sensor
23GNDEarth
25GDS TX
Grundfos Digital Sensor
output
24GDS RXGrundfos Digital Sensor input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
13
Page 14
7.5 Signal cables
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
Caution
Caution
English (GB)
• Use screened cables with a cross-sectional area of minimum
0.5 mm
2
and maximum 1.5 mm2 for external on/off switch,
digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to frame at both ends with
good connection. The screens must be as close as possible to
the terminals. See fig. 21.
Fig. 21 Stripped cable with screen and wire connections
• Always tighten screws for frame connections whether a cable
is fitted or not.
• The wires in the motor terminal box must be as short as
possible.
7.6 Bus connection cable
7.6.1 New installations
For the bus connection, use a screened 3-core cable with a
cross-sectional area of minimum 0.5 mm
2
mm
.
• If the motor is connected to a unit with a cable clamp which is
identical to the one on the motor, connect the screen to this
cable clamp.
• If the unit has no cable clamp as shown in fig. 22, leave the
screen unconnected at this end.
Fig. 22 Connection with screened 3-core cable
2
and maximum 1.5
8. Startup
8.1 Flushing the pipe system
The pump is not designed to pump liquids containing
solid particles such as pipe debris and welding slag.
Before starting up the pump, clean the pipe system
thoroughly, and flush and fill it with clean water.
The warranty does not cover any damage caused by
flushing the pipe system by means of the pump.
8.2 Priming the pump
Do not start the pump until it has been filled with
liquid and vented. To ensure correct venting, the vent
screw should point upwards.
Closed systems or open systems where the liquid level is
above the pump inlet
1. Close the outlet isolating valve and loosen the vent screw in
TM02 1325 4402 TM05 3973 1812TM02 8842 0904
the motor stool. See fig. 24.
Warning
Pay attention to the direction of the vent hole, and
make sure that the escaping hot or cold liquid does
not cause injury to persons or damage to the
equipment.
2. Slowly open the isolating valve in the inlet pipe until a steady
stream of liquid runs out of the vent hole.
3. Tighten the vent screw and completely open the isolating
valve(s).
Open systems where the liquid level is below the pump inlet
The inlet pipe and the pump must be filled with liquid and vented
before the pump is started.
1. Close the outlet isolating valve and open the isolating valve in
the inlet pipe.
2. Loosen the vent screw. See fig. 24.
3. Remove the plug from one of the pump flanges, depending on
the pump location.
4. Pour liquid through the priming port until the inlet pipe and the
pump are filled with liquid.
5. Replace the plug and tighten securely.
6. Tighten the vent screw.
You can fill the inlet pipe with liquid and vent it before you connect
it to the pump. You can also install a priming device before the
pump.
7.6.2 Replacing an existing motor
• If a screened 2-core cable is used in the existing installation,
connect the cable as shown in fig. 23.
Fig. 23 Connection with screened 2-core cable
• If a screened 3-core cable is used in the existing installation,
follow the instructions in section 7.6.1 New installations.
14
TM05 7922 1613
Fig. 24 Position of vent screw
Page 15
8.3 Starting the pump
Note
1. Before starting the pump, completely open the isolating valve
on the inlet side of the pump and leave the outlet isolating
valve almost closed.
2. Start the pump. See section 10. User interfaces.
3. Vent the pump by loosening the vent screw in the motor stool
until a steady stream of liquid runs out of the vent hole. See
fig. 24.
Warning
Pay attention to the direction of the vent hole, and
make sure that the escaping hot or cold liquid does
not cause injury to persons or damage to the
equipment.
4. When the pipe system has been filled with liquid, slowly open
the outlet isolating valve until it is completely open.
8.4 Shaft seal run-in
The seal faces are lubricated by the pumped liquid, meaning that
there may be a certain amount of leakage from the shaft seal.
When the pump is started up for the first time, or when a new
shaft seal is installed, a certain run-in period is required before
the leakage is reduced to an acceptable level. The time required
for this depends on the operating conditions, i.e. every time the
operating conditions change, a new run-in period will be started.
Under normal conditions, the leaking liquid will evaporate. As a
result, no leakage will be detected.
However, liquids such as kerosene will not evaporate. The
leakage may therefore be seen as a shaft seal failure.
9. Operating conditions
9.1 Maximum number of starts and stops
The number of starts and stops via the power supply must not
exceed four times per hour.
When switched on via the power supply, the pump will start after
approx. 5 seconds.
If a higher number of starts and stops is desired, use the input for
external start/stop when starting/stopping the pump.
When started via an external on/off switch, the pump will start
immediately.
9.2 Alternating operation of twin-head pumps
On twin-head pumps, the duty and backup pumps must be
alternated on a regular basis, i.e. once a week, to ensure an even
distribution of the operating hours on both pumps. The pumps
alternate automatically. See section 14.47 Multipump setup
(Setup of multi-pump system).
If twin-head pumps are used for pumping domestic hot water, the
duty and backup pumps must be alternated on a regular basis,
i.e. once a day, to avoid blocking of the backup pump due to
deposits (calcareous deposits, etc.). The pumps alternate
automatically. See section 14.47 Multipump setup (Setup of
multi-pump system).
9.3 Liquid temperature
-25 °C (~ -13 °F) up to +120 °C (~ +248 °F).
The maximum liquid temperature depends on the shaft seal type
and the pump type.
Depending on the cast-iron version and the pump application, the
maximum liquid temperature may be limited by local regulations
and laws.
The maximum liquid temperature is stated on the pump
nameplate.
If the pump is used for liquids at high temperatures,
the life of the shaft seal and the built-in Grundfos
sensor may be reduced.
9.4 Ambient temperature
9.4.1 Ambient temperature during storage and transportation
-30 - +60 °C.
9.4.2 Ambient temperature during operation
-20 - +50 °C.
The motor can operate with the rated power output, P2, at 50 °C,
but continuous operation at higher temperatures will reduce the
expected product life. If the motor is to operate at ambient
temperatures between 50 and 60 °C, select an oversized motor.
Contact Grundfos for further information.
9.5 Operating pressure/test pressure
The pressure test has been made with water containing
anti-corrosive additives at a temperature of 20 °C (~ 68 °F).
Operating pressureTest pressure
Pressure stage
[bar][MPa][bar][MPa]
PN 660.6101.0
PN 6/PN 10101.0151.5
PN 16161.6242.4
9.6 Inlet pressure
To ensure optimum and quiet pump operation, the inlet pressure,
system pressure, must be adjusted correctly. See the table on
page 67.
For the calculation of specific inlet pressures, contact the local
Grundfos company or see the data booklet for TP, TPD, TPE,
TPED, TPE2, TPE2 D, TPE3 and TPE3 D on Grundfos Product
Center (https://product-selection.grundfos.com/).
9.7 Electrical data
See sections 27. Technical data, single-phase motors and
28. Technical data, three-phase motors.
For specific motor data, see the motor nameplate.
9.8 Sound pressure level
The sound pressure level of the pump is lower than 70 dB(A).
9.9 Environment
Non-aggressive and non-explosive atmosphere.
English (GB)
15
Page 16
9.10 Installation altitude
Caution
1
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.91
0.90
0.89
0.88
0
0
1000 1200 1400 1600 1800 2000 2200
[m]
P2[%]
Altitude [m]
P2
[%]
English (GB)
The motor must not be installed more than 2000
metres above sea level.
Installation altitude is the height above sea level of the installation
site.
• Motors installed up to 1000 metres above sea level can be
loaded 100 %.
• Motors installed more than 1000 metres above sea level must
not be fully loaded due to the low density and consequent low
cooling effect of the air. See fig. 25.
10. User interfaces
Warning
The product may be so hot that only the buttons are
to be touched.
You can make pump settings by means of the following user
interfaces:
Control panels
• Standard control panel.
See section 11. Standard control panel.
• Advanced control panel.
See section 12. Advanced control panel.
Remote controls
• Grundfos GO.
See section 13. Grundfos GO.
If the power supply to the pump is switched off, the settings will
be stored.
Factory settings
TPE2, TPE2 D pumps have been factory-set to constant-curve
control mode. See section 11.1.2 Pump in constant-curve control
mode.
The setpoint corresponds to 100 % of the maximum pump
performance. See data booklet or Grundfos Product Center.
TPE3, TPE3 D pumps have been factory-set to AUTO
control mode. See section 14.5.1 AUTOADAPT.
ADAPT
TM05 6400 4712
Fig. 25 Derating of motor output power (P2) in relation to
altitude above sea level
9.11 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %, one of the drain
holes in the drive-end flange must be open.
See section 6. Mechanic al installation.
9.12 Motor cooling
To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate cooling is
ensured. See section 6.7 Ensuring motor cooling.
• The temperature of the cooling air must not exceed 50 °C.
• Keep cooling fins and fan blades clean.
16
Page 17
11. Standard control panel
1
2
3
4
5
Stop
0
6
3
m
This control panel is fitted as standard on TPE2, TPE2 D pumps.
Fig. 26 Standard control panel
Pos.Symbol Description
Grundfos Eye
1
2-Light fields for indication of setpoint.
3
4
5
Shows the operating status of the pump.
For further information, see section
19. Grundfos Eye.
Changes the setpoint.
Resets warnings and alarms when you
press one of the buttons briefly.
Enables radio communication with
Grundfos GO and other products of the
same type.
When you try to establish radio
communication between the pump and
Grundfos GO or another pump, the green
indicator light in Grundfos Eye will flash
continuously. Press on the pump control
panel to enable radio communication with
Grundfos GO and other products of the
same type.
Makes the pump ready for operation or
starts/stops the pump.
Start:
If you press the button when the pump is
stopped, the pump will only start if you have
not enabled another function with higher
priority. See section 18. Priority of settings.
Stop:
If you press the button when the pump is
running, the pump will always stop. Then
the "Stop" text next to the button will
illuminate.
11.1 Setpoint setting
Set the desired setpoint of the pump by pressing or . The
light fields on the control panel will indicate the setpoint set.
11.1.1 Pump in differential-pressure control mode
The following example applies to a pump in an application where
a pressure sensor gives a feedback to the pump. If you retrofit the
sensor to the pump, set it up manually as the pump does not
automatically register a connected sensor.
Figure 27 shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 3 metres with a sensor measuring
range from 0 to 6 metres. The setting range is equal to the sensor
measuring range.
TM05 4848 3512
Fig. 27 Setpoint set to 3 metres, differential-pressure control
English (GB)
TM05 4894 3512
17
Page 18
11.1.2 Pump in constant-curve control mode
H
Q
H
Q
Note
H
Q
English (GB)
In constant-curve control mode, the pump performance will lie
between the maximum and minimum curve of the pump. See fig.
28.
Fig. 28 Pump in constant-curve control mode
Setting to maximum curve
•Press
of the pump. The top light field flashes. When the top light field
is on, press
flashing.
• To change back, press
setpoint is indicated.
Example
Pump set to maximum curve.
Figure 29 shows that the top light field is flashing, indicating
maximum curve.
continuously to change over to the maximum curve
for 3 seconds until the light field starts
continuously until the desired
Example
Pump set to minimum curve.
Figure 30 shows that the bottom light field is flashing, indicating
minimum curve.
Fig. 30 Minimum curve duty
11.1.3 Start/stop of pump
If you have stopped the pump by pressing and
TM05 4895 2812TM05 4896 2812
Start the pump by pressing
until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is stopped, the
"Stop" text next to the button is on. The pump can also be
stopped by continuously pressing
are on.
You can also stop the pump with Grundfos GO or via a digital
input set to "External stop". See section 18. Priority of settings.
11.1.4 Resetting of fault indications
Reset a fault indication in one of the following ways:
• Via the digital input if it has been set to "Alarm resetting".
• Briefly press or
setting of the pump.
A fault indication cannot be reset by pressing or
buttons have been locked.
• Switch off the power supply until the indicator lights are off.
• Switch the external start/stop input off and then on again.
• With Grundfos GO.
the "Stop" text on the control panel is illuminated, you
give it free to operation by pressing again.
If you have stopped the pump by pressing , you
restart it by pressing or by using Grundfos GO.
or by continuously pressing
until none of the light fields
on the pump. This will not change the
TM05 4897 2812
if the
Fig. 29 Maximum curve duty
Setting to minimum curve:
•Press
of the pump (bottom light field flashes). When the bottom light
field is on, press
flashing.
• To change back, press continuously until the desired
setpoint is indicated.
continuously to change over to the minimum curve
for 3 seconds until the light field starts
18
Page 19
12. Advanced control panel
1
2
3
4
5
6
Setpoint
5.00 bar
Operaring mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1234
56789
Home
This control panel is fitted as standard on TPE3, TPE3 D pumps.
It can be fitted on TPE2, TPE2 D pumps as an option.
Fig. 31 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
2-Graphical colour display
3Goes one step back.
4
5
Shows the operating status of the pump.
See section 19. Grundfos Eye for further
information.
Navigates between main menus, displays and
digits.
When the menu is changed, the display
always shows the top display of the new menu.
Navigates between submenus.
Changes value settings.
Note: If you have disabled the possibility to
make settings with the "Enable/disable
settings" function, then you can enable it
temporarily again by pressing these buttons
simultaneously for at least 5 seconds. See
section 14.31 Buttons on product
(Enable/disable settings).
Saves changed values, resets alarms and
expands the value field.
Enables radio communication with Grundfos
GO and other products of the same type.
When you try to a establish radio
communication between the pump and
Grundfos GO or another pump, the green
indicator light in Grundfos Eye will start
flashing. A note also appears in the pump
display stating that a wireless device wants to
connect to the pump. Press on the pump
control panel to enable radio communication
with Grundfos GO and other products of the
same type.
Makes the pump ready for operation/starts and
stops the pump.
Start:
If you press the button when the pump is
stopped, the pump will only start if you have
not enabled another function with higher
priority. See section 18. Priority of settings.
Stop:
If you press the button when the pump is
running, the pump will always stop. The "Stop"
text next to the button is on.
12.1 Home display
TM05 4849 1013
Fig. 32 Example of "Home" display
Pos. Symbol Description
"Home"
This menu shows up to four user-defined
1
parameters. You can select parameters shown
as shortcut icon , and when pressing ,
you will go directly to the "Settings" display for
the selected parameter.
"Status"
2-
This menu shows the status of the pump and
system as well as warnings and alarms.
"Settings"
This menu gives access to all setting
3-
parameters. You can make detailed settings of
the pump in this menu.
See section 14. Description of functions.
"Assist"
This menu enables assisted pump setup,
4-
provides a short description of the control
modes and offers fault advice.
See section 14.43 Assist.
5
6
7
Indicates that the pump has been stopped via
the
button.
Indicates that the pump is functioning as
master pump in a multipump system.
Indicates that the pump is functioning as slave
pump in a multipump system.
Indicates that the pump is operating in a
8
multipump system. See section
14.47 Multipump setup (Setup of multi-pump
system).
Indicates that the possibility to make settings
9
has been disabled for protective reasons. See
section 14.31 Buttons on product
(Enable/disable settings).
12.2 Startup guide
The pump incorporates a startup guide which is started at the first
startup. See section 14.40 Run start-up guide. After the startup
guide, the main menus appear in the display.
English (GB)
TM06 4516 2415
6Goes to the "Home" menu.
19
Page 20
12.3 Menu overview for advanced control panel
English (GB)
12.3.1 Main menus
Home
TPE3
TPE3 D
TPE2
TPE2 D
Multipump
system
●●●
Status
TPE3
TPE3 D
TPE2
TPE2 D
Multipump
system
SectionPage
Operating status
Operating mode, from
Control mode
Pump performance
Actual controlled value
Max. curve and duty point
Resulting setpoint
Liquid temp.-
Speed
Acc. flow and specific energy
Power and energy consumption
Measured values
Set date and time
Analog input 2
Analog input 3
Pt100/1000 input 1
Pt100/1000 input 2
Analog output
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
Warning and alarm
Actual warning or alarm
Warning log
Alarm log
Heat energy meter-14.1 Heat energy meter27
Heat power-
Heat energy-
Flow rate-
Volume-
Hours counter-
Temperature 1-
Temperature 2-
Differential temp.-
Operating log
Operating hours
Trend data
Fitted modules
Date and time
Product identification
Motor bearing monitoring
Multi-pump system--
System operating status--
System performance--
System input power and energy--
Pump 1, multi-pump system--
Pump 2, multi-pump system--
Pump 3, multi-pump system--
Pump 4, multi-pump system--
1)
Only available if an advanced functional module is fitted.
20
Page 21
Settings
TPE3
TPE3 D
TPE2
TPE2 D
Multipump
system
SectionPage
Setpoint14.2 Setpoint27
Operating mode14.3 Operating mode27
Set manual speed14.4 Set manual speed27
Control mode14.5 Control mode28
FLOW
Only available if an advanced functional module, FM 300, is fitted.
Enable/disable settings
Delete history14.32 Delete history45
Define Home display14.33 Define Home display45
Display settings14.34 Display settings45
Store actual settings
Recall stored settings
Run start-up guide14.40 Run start-up guide47
14.31 Buttons on product
(Enable/disable setti ngs)
14.35 Store settings (Store
actual settings)
14.36 Recall settings (Recall
stored settings)
45
46
46
Assist
Assisted pump setup14.44 Assisted pump setup47
Setup, analog input14.45 Setup, analog input48
Setting of date and time
Setup of multi-pump system
Description of control mode
Assisted fault advice14.49 Assisted fault advice50
TPE3
TPE3 D
TPE2
TPE DD
Multipump
system
SectionPage
14.46 Setting of date and
time
14.47 Multipump setup
(Setup of multi-pump
system)
14.48 Description of control
mode
48
48
50
22
Page 23
13. Grundfos GO
+
+
+
1
2
3
The pump is designed for wireless radio or infrared
communication with Grundfos GO.
Grundfos GO enables setting of functions and gives access to
status overviews, technical product information and actual
operating parameters.
Grundfos GO offers the following mobile interfaces, MI. See fig.
33.
Fig. 33 Grundfos GO communicating with the pump via radio
or infrared connection, IR
Pos.Description
Grundfos MI 202:
Add-on module which can be used in conjunction with
1
an Apple iPhone or iPod with 30-pin connector and iOS
5.0 or later, e.g. fourth generation iPhone or iPod.
Grundfos MI 204:
Add-on module which can be used in conjunction with
an Apple iPhone or iPod with Lightning connector, e.g.
2
fifth generation iPhone or iPod.
The MI 204 is also available together with an Apple
iPod touch and a cover.
Grundfos MI 301:
Separate module enabling radio or infrared
communication. The module can be used in
3
conjunction with an Android or iOS-based smart device
with Bluetooth connection.
English (GB)
TM06 0744 0914
13.1 Communication
When Grundfos GO initiates communication with the pump, the
indicator light in the middle of Grundfos Eye will flash green. See
section 19. Grundfos Eye.
On pumps fitted with an advanced control panel a text will appear
in the display saying that a wireless device is trying to establish
connection. Press on the pump in order to establish
connection with Grundfos GO or press
Establish communication using one of these communication
types:
• radio communication
• infrared communication.
13.1.1 Radio communication
Radio communication can take place at distances up to 30
metres. The first time Grundfos GO communicates with the pump,
you must establish communication by pressing or on the
pump control panel. Later when communication takes place, the
pump will be recognized by Grundfos GO and you can select the
pump from the "List" menu.
13.1.2 Infrared communication
When communicating via infrared light, Grundfos GO must be
pointed at the pump control panel.
to reject connection.
23
Page 24
13.2 Menu overview for Grundfos GO main menus
English (GB)
Dashboard
TPE3
TPE3 D
TPE2
TPE2 D
Multipump
system
Status
TPE3
TPE3 D
System mode--
TPE2
TPE2 D
Multipump
system
2)
SectionPage
Resulting setpoint
Resulting system setpoint--
Actual controlled value
2)
2)
Motor speed (rpm, %) -
Power consumption -
Power cons., sys.--
2)
Energy consumption
Energy cons., sys.--
Acc. flow, specific energy
2)
2)
Operating hours
Operating hours, system--
2)
Liquid temperature--
Analog input 1-
Analog input 2-
Analog input 3
Pt100/1000 input 1
Pt100/1000 input 2
Analog output
1)
1)
1)
1)
1)
1)
1)
1)
-
-
-
Digital input 1 -
Digital input 2
Digital in/output 3
Digital in/output 4
1)
1)
1)
1)
1)
1)
-
-
Fitted modules-
Trend data--
Heat energy meter--14.1 Heat energy meter27
Pump 1--
Pump 2--
Pump 3--
Pump 4--
1)
Only available if an advanced functional module, FM 300, is fitted.
2)
Only available if Grundfos GO is connected to a multipump system.
2)
2)
2)
2)
24
Page 25
Settings
TPE3
TPE3 D
TPE2
TPE2 D
Multipump
system
SectionPage
Setpoint14.2 Setpoint27
Operating mode14.3 Operating mode27
Control mode14.5 Control mode28
Date and time
1)
1)
14.29 Date and time (Set
date and time)
Flow limit-14.6 FLOWLIMIT33
Automatic Night Setback-
14.7 Automatic Night
Setback
Temperature influence-14.19 Temperature influence42
Buttons on product
Controller
14.31 Buttons on product
(Enable/disable settings)
14.47 Multipump setup
(Setup of multi-pump
system)
48
26
Page 27
14. Description of functions
t
R
t
F
kWh
tF: Flow-pipe temperature
tR: Return-pipe temperature
QHQ
H
Max.
Min.
Normal
Normal
Manual
Stop
14.1 Heat energy meter
Pump variantHeat energy meter
TPE3, TPE3 D
TPE2, TPE2 D-
The heat energy meter is a monitoring function that calculates the
heat energy consumption within a system. The built-in flow
estimation needed for the calculation has an inaccuracy of ± 10 %
of the maximum flow in the area down to 10 % flow and down to
12.5 % of the maximum head. The calculations are based on
water at a temperature of 20 °C. Also, the temperature
measurements needed for the calculation have some inaccuracy
depending on the sensor type. Therefore, you cannot use the
heat energy value for billing purposes. However, the value is
perfect for optimisation purposes in order to prevent excessive
energy costs caused by system imbalances.
The heat energy meter requires an additional temperature sensor
installed in the flow pipe or return pipe depending on where the
pump is installed.
14.3 Operating mode
Possible operating modes:
•Normal
The pump runs according to the selected control mode.
•Stop
The pump stops.
•Min.
The minimum curve mode can be used in periods in which a
minimum flow is required.
This operating mode is for instance suitable for manual night
setback if you do not want to use automatic night setback.
•Max.
The maximum curve mode can be used in periods in which a
maximum flow is required.
This operating mode is for instance suitable for systems with
hot-water priority.
• Manual
The pump is operating at a manually set speed. In "Manual"
the setpoint via bus is overruled. See section 14.4 Set manual
speed.
All operating modes are illustrated in the figure below.
English (GB)
Fig. 34 Example: Pump installed in the flow pipe and
additional temperature sensor installed in the return
pipe
14.2 Setpoint
You can set the setpoint for all control modes, except AUTO
and FLOW
desired control mode. See section 14.5 Control mode.
Factory setting
See section 31. Factory settings.
, in this submenu when you have selected the
ADAPT
ADAPT
TM06 1182 1814
Fig. 35 Operating modes
Factory setting
See section 31. Factory settings.
14.4 Set manual speed
This menu is only available in the advanced control panel. With
Grundfos GO, you set the speed via the "Setpoint" menu.
You can set the pump speed in % of the maximum speed. When
you have set the operating mode to "Manual", the pump will run
at the set speed.
The operating mode must be set to "Normal" before a
control mode can be enabled.
You can change the setpoint for all control modes, except
ADAPT
and FLOW
AUTO
"Settings" when you have selected the desired control mode.
,in the "Setpoint" submenu under
ADAPT
Factory setting
See section 31. Factory settings.
14.5.1 AUTO
ADAPT
Pump variantAUTO
TPE3, TPE3 D
TPE2,TPE2 D-
The AUTO
performance according to the actual system characteristic.
control mode continuously adapts the pump
ADAPT
Manual setting of the setpoint is not possible.
ADAPT
When the AUTO
will start with the factory setting, H
performance to A
control mode has been enabled, the pump
ADAPT
. See fig. 36.
1
fac
= H
, and then adjust its
set1
When the pump registers a lower head on the maximum curve,
, the AUTO
A
2
correspondingly lower control curve, H
system close, the pump will adjust its performance to A
function will automatically select a
ADAPT
set2
. If the valves in the
.
3
A1:Original duty point.
:Lower registered head on the maximum curve.
A
2
:New duty point after AUTO
A
3
:Original setpoint setting.
H
set1
:New setpoint after AUTO
H
set2
:Factory setting.
H
fac.
H
The AUTO
control where the control curves have a fixed origin, H
The AUTO
for heating systems and is not recommended for air-conditioning
: A fixed value of 1.5 m.
auto_min
control mode is a form of proportional-pressure
ADAPT
control mode has been developed specifically
ADAPT
ADAPT
ADAPT
control.
control.
auto_min
.
and cooling systems.
14.5.2 FLOW
Pump variantFLOW
ADAPT
ADAPT
TPE3, TPE3 D
TPE2, TPE2 D-
When FLOW
ensure that the flow never exceeds the entered FLOW
The setting range for FLOW
flow rate of the pump.
The factory setting of the FLOW
AUTO
ADAPT
37.
is selected, the pump will run AUTO
ADAPT
is 25 to 90 %, of the maximum
LIMIT
is the flow rate where the
LIMIT
ADAPT
LIMIT
and
value.
factory setting meets the maximum curve. See fig.
Fig. 36 AUTO
ADAPT
Do not set the FLOW
point.
TM05 7910 1613
lower than the sized duty
LIMIT
TM05 7912 1613
Fig. 37 FLOW
ADAPT
28
Page 29
14.5.3 Proportional pressure
H
Q
Hset
Hset
2
p
H
Q
p
p
14.5.4 Constant pressure
Pump variantProportional pressure
TPE3, TPE3 D
TPE2, TPE2 D-
The head of the pump is reduced at decreasing water demand
and increased at rising water demand. See fig. 38.
This control mode is especially suitable in systems with relatively
large pressure losses in the distribution pipes. The head of the
pump will increase proportionally to the flow in the system to
compensate for the large pressure losses in the distribution
pipes.
The setpoint can be set with an accuracy of 0.1 metre. The head
against a closed valve is half the setpoint.
Fig. 38 Proportional pressure
Example
• Factory-fitted differential-pressure sensor.
Pump variantConstant pressure
TPE3, TPE3 DTPE2, TPE2 D
We recommend this control mode if the pump is to deliver a
constant pressure, independently of the flow in the system. See
fig. 40.
Fig. 40 Constant pressure
This control mode requires an external differential-pressure
sensor as shown in the examples below. You can set the pressure
TM05 7909 1613
sensor in the "Assist" menu. See section 14.44 Assisted pump
setup.
Examples
• One external differential-pressure sensor.
English (GB)
TM05 7901 1613
Fig. 39 Proportional pressure
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
Fig. 41 Constant pressure
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
29
Page 30
14.5.5 Constant temperature
H
Q
t
t
t
t
H
Q
p
p
p
p
p
p
p
p
p
English (GB)
14.5.6 Constant differential pressure
Pump variantConstant temperature
TPE3, TPE3 D
TPE2, TPE2 D
This control mode ensures a constant temperature. Constant
temperature is a comfort control mode that can be used in
domestic hot-water systems to control the flow to maintain a fixed
temperature in the system. See fig. 42. When you use this control
mode, do not install any balancing valves in the system.
Fig. 42 Constant temperature
This control mode requires either an internal or external
temperature sensor as shown in the examples below:
Examples
• Factory-fitted temperature sensor. Only TPE3, TPE3 D.
Pump variant
Constant differential
pressure
TPE3, TPE3 D
TPE2, TPE2 D
The pump maintains a constant differential pressure,
independently of the flow in the system. See fig. 44. This control
mode is primarily suitable for systems with relatively small
pressure losses.
Fig. 44 Constant differential pressure
TM05 7900 1613
This control mode requires either an internal or external
differential-pressure sensor or two external pressure sensors as
shown in the examples below:
• One external differential-pressure sensor.
The pump uses the input from the sensor to control the
differential pressure.
You can set sensor manually or by using the "Assist" menu.
See section 14.44 Assi sted pump setup.
• Two external pressure sensors.
Constant differential-pressure control is achievable with two
individual pressure sensors. The pump uses the inputs from
the two sensors and calculates the differential pressure.
The sensors must have the same unit and must be set as
feedback sensors. You can set the sensors manually, sensor
by sensor, or by using the "Assist" menu. See section
14.44 Assisted pump setup.
Fig. 45 Constant differential pressure
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
30
Page 31
14.5.7 Constant differential temperature
H
Q
△t
t
t
t
t
t
t
t
H
Q
Q
set
Q
14.5.8 Constant flow rate
Pump variant
Constant differential
temperature
TPE3, TPE3 D
TPE2, TPE2 D
The pump maintains a constant differential temperature in the
system and the pump performance is controlled according to this.
See fig. 46.
Fig. 46 Constant differential temperature
This control mode requires either two temperature sensors or one
external differential-temperature sensor as shown in the
examples below.
The temperature sensors can either be analog sensors
connected to two of the analog inputs or two Pt100/Pt1000
sensors connected to the Pt100/1000 inputs, if these are
available on the specific pump.
The setup of the sensor can be made in the "Assist" menu under
"Assisted pump setup". See section 14.44 Assisted pump setup.
Pump variantConstant flow rate
TPE3, TPE3 DTPE2, TPE2 D
The pump maintains a constant flow in the system, independently
of the head. See fig. 48.
TM05 7954 1713
Fig. 48 Constant flow rate
This control mode requires an external flow sensor as shown
below:
Example
• One external flow sensor.
English (GB)
TM05 7955 1713
Examples
• Factory-fitted temperature sensor and an external
temperature sensor (only TPE3, TPE3 D).
• Two external temperature sensors.
Constant differential-temperature control is achievable with
two temperature sensors. The pump uses the inputs from the
two sensors and calculates the differential temperature.
The sensors must have the same unit and must be set as
feedback sensors. You can set the sensors manually, sensor
by sensor, or by using the "Assist" menu. See section
14.44 Assisted pump setup.
• One external differential-temperature sensor.
The pump uses the input from the sensor to control the
differential temperature.
You can set the sensor manually or by using the "Assist"
menu. See section 14.44 Assisted pump setup.
Fig. 49 Constant flow rate
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
Fig. 47 Constant differential temperature
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
31
Page 32
14.5.9 Constant level
H
Q
L
L
Note
H
Q
H [%]
Q [m
3
/h]80 %
100 %
Limited maximum curve
English (GB)
14.5.10 Constant other value
Pump variantConstant level
TPE3, TPE3 DTPE2, TPE2 D
The pump maintains a constant level, independently of the flow
rate. See fig. 50.
Fig. 50 Constant level
This control mode requires an external level sensor.
The pump can control the level in a tank in two ways:
• As an emptying function where the pump draws the liquid from
the tank.
• As a filling function where the pump pumps the liquid into the
tank.
See fig. 51.
The type of level control function depends on the setting of the
built-in controller. See section 14.15 Controller (Controller
settings).
Pump variantConstant other value
TPE3, TPE3 DTPE2, TPE2 D
Any other value is kept constant.
Use this control mode if you want to control a value which is not
available in the "Control mode" menu. Connect a sensor
measuring the controlled value to one of the analog inputs of the
pump. The controlled value will be shown in percentage of sensor
range.
14.5.11 Constant curve
Pump variantConstant curve
TPE3, TPE3 D
TPE2, TPE2 D
You can set the pump to operate according to a constant curve,
like an uncontrolled pump. See fig. 52.
You can set the desired speed in % of maximum speed in the
TM05 7941 1613
range from 13 to 100 %.
Examples
• One external level sensor.
– emptying function.
• One external level sensor.
– filling function.
Fig. 51 Constant level
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
TM05 7957 1713
Fig. 52 Constant curve
Depending on the system characteristic and the duty
point, the 100 % setting may be slightly smaller than
the actual maximum curve of the pump even though
the display shows 100 %. This is due to the power
and pressure limitations built into the pump. The
deviation varies according to pump type and
pressure loss in the pipes.
TM05 7913 1613
Fig. 53 Power and pressure limitations influencing the max.
curve
Controller settings
For recommended controller settings, see section
14.15 Controller (Controller settings).
32
Page 33
14.6 FLOW
Note
H
Q
Q
max
Q
max
Q
limit
25 %
90 %
Setting range
Pump variantFLOW
LIMIT
LIMIT
TPE3, TPE3 D
TPE2, TPE2 D-
FLOW
LIMIT
• Enable the FLOW
• Set the FLOW
Fig. 54 FLOW
The FLOW
control modes:
LIMIT
LIMIT
function can be combined with the following
LIMIT
LIMIT
.
function.
• Prop. pressure
• Con. diff. press.
• Con. diff. temp.
• Const. temp.
• Const. curve.
A flow-limiting function ensures that the flow never exceeds the
entered FLOW
The setting range for FLOW
pump.
The factory setting of the FLOW
AUTO
ADAPT
value.
LIMIT
is 25 to 90 % of the Q
LIMIT
is the flow where the
factory setting meets the maximum curve. See fig.
LIMIT
max
of the
37.
Factory setting
See section 31. Factory settings.
14.8 Analog inputs
Available inputs depending on the functional module fitted in the
pump:
Function (terminal)
FM 200*
(standard)
Analog input 1, setup (4)
Analog input 2, setup (7)
Analog input 3, setup (14)-
* See section 22. Identifying the functional module.
Set the analog input for a feedback sensor via the "Assisted
pump setup" menu. See section 14.44 Assisted pump setup.
If you want to set an analog input for other purposes, you can do
this manually.
You can set the analog inputs via the "Setup, analog input" menu.
See section 14.45 Setup, analog input.
If you perform the manual setting via Grundfos GO, you need to
enter the menu for the analog input under the "Settings" menu.
Function
The analog inputs can be set to these functions:
TM05 7908 1613
•Not active
• Feedback sensor
Sensor used for the selected control mode.
• Ext. setpoint infl.
See section 14.17 External setpoint function
• Other function.
FM 300*
(advanced)
English (GB)
14.7 Automatic Night Setback
Pump variantAutomatic Night Setback
TPE3, TPE3 D
TPE2, TPE2 D-
Once you have enabled automatic night setback, the pump
automatically changes between normal duty and night setback
(duty at low performance).
Changeover between normal duty and night setback depends on
the flow-pipe temperature.
The pump automatically changes over to night setback when the
built-in sensor registers a flow-pipe temperature drop of more
than 10 to 15 °C within approx. two hours. The temperature drop
must be at least 0.1 °C/min.
Changeover to normal duty takes place without a time lag when
the temperature has increased by approx. 10 °C.
Factory setting
See section 31. Factory settings.
You cannot enable Automatic Night Setback when
the pump is in constant-curve mode.
33
Page 34
Measured parameter
PTPTPT
PT
TT
TT
TT
Q
Q
DPT
DPTDPT
LTLT
DPT DTT
1
5
24
910
7
12
816 15
313614
11
English (GB)
Select one of the parameters, i.e. the parameter to be measured
in the system by the sensor connected to the actual analog input.
See fig. 55.
Fig. 55 Overview of sensor locations
Sensor function/measured parameterPos.
Inlet pressure1
Diff. press., inlet2
Liquid temperature3
Diff. press.,outlet4
Diff. press.,pump5
Operating mode6
Press. 2, external7
Diff. press., ext.8
Storage tank level9
Feed tank level10
Pump flow11
Flow, external12
Liquid temperature13
Temperature 114
Temperature 215
Date and time16
Ambient temp.Not shown
Other parameterNot shown
Unit
Available measuring units:
14.9 Built-in Grundfos sensor
Pump variantBuilt-in Grundfos sensor
TPE3, TPE3 D
TPE2, TPE2 D-
You can select the function of the built-in sensor in the "Built-in
Grundfos sensor" menu.
Set the "Built-in Grundfos sensor" via the "Assisted pump setup"
menu. See section 14.44 Assisted pump setup.
If you perform the setting manually in the advanced control panel,
you must enter the "Analog inputs" menu under the "Settings"
menu in order to access the "Built-in Grundfos sensor" menu.
If you perform the setting manually via Grundfos GO, you need to
enter the menu for the "Built-in Grundfos sensor" under the
"Settings" menu.
Function
TM06 2328 3914
You can set the built-in sensor to these functions:
• Grundfos diff.-pressure sensor
- Not active
- Feedback sensor
- Setpoint influence
- Other function.
• Grundfos temperature sensor
- Not active
- Feedback sensor
- Setpoint influence
- Other function.
Factory setting
See section 31. Factory settings.
ParameterPossible measuring units
Pressurebar, m, kPa, psi, ft
Levelm, ft, in
Flow ratem
Liquid temperature°C, °F
Other parameter%
Electrical signal
Select signal type:
• 0.5 - 3.5 V
•0-5 V
• 0-10 V
• 0-20 mA
• 4-20 mA
Sensor range, min. value
Set the minimum value of the connected sensor.
Sensor range, max. value
Set the maximum value of the connected sensor.
Factory setting
See section 31. Factory settings.
34
3
/h, l/s, yd3/h, gpm
Page 35
14.10 Pt100/1000 inputs
TT
TT
TT
3
12
Available inputs depending on the functional module fitted in the
pump:
Function (terminal)
Pt100/1000 input 1, setup (17
and 18)
Pt100/1000 input 2, setup (18
and 19)
FM 200*
(standard)
-
-
* See section 22. Identifying the functional module.
Set the Pt100/1000 input for a feedback sensor via the "Assisted
pump setup" menu. See section 14.44 Assisted pump setup.
If you want to set a Pt100/1000 input for other purposes, you can
do this manually.
You can set the analog inputs via the "Setup, analog input" menu.
See section 14.45 Setup, analog input.
If you perform the manual setting via Grundfos GO, you need to
enter the menu for the Pt100/1000 input under the "Settings"
menu.
Function
The Pt100/1000 inputs can be set to these functions:
• Not active
• Feedback sensor
• Ext. setpoint infl.
See section 14.17 External setpoint function
• Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system.
Select one of the parameters, i.e. the parameter to be measured
in the system by the Pt100/1000 sensor connected to the actual
Pt100/1000 input. See fig. 56.
Fig. 56 Overview of Pt100/1000 sensor locations
ParameterPos.
Liquid temp.1
Temperature 12
Temperature 23
Ambient temp.Not shown
Measuring range
-50 - +204 °C.
Factory setting
See section 31. Factory settings.
FM 300*
(advanced)
14.11 Digital inputs
Available inputs depending on the functional module fitted in the
pump:
Function (terminal)
FM 200*
(standard)
Digital input 1, setup (2 and 6)
Digital input 2, setup (1 and 9)-
* See section 22. Identifying the functional module.
To set a digital input, make the settings below.
Function
Select one of these functions:
•Not active
When set to "Not active", the input has no function.
• External stop
When the input is deactivated (open circuit), the pump will
stop.
• Min. (minimum speed)
When the input is activated, the pump will run at the set min.
speed.
• Max. (maximum speed)
When the input is activated, the pump will run at the set
maximum speed.
• External fault
When the input is activated, a timer will be started. If the input
is activated for more than 5 seconds, the pump will be stopped
and a fault will be indicated. This function depends on input
from external equipment.
• Alarm resetting
When the input is activated, a possible fault indication will be
reset.
• Dry running
When this function has been selected, lack of inlet pressure or
water shortage can be detected.
When lack of inlet pressure or water shortage (dry running) is
detected, the pump will be stopped. The pump cannot restart
as long as the input is activated.
This requires the use of an accessory, such as:
– a pressure switch on the inlet side of the pump
TM06 4012 1515
– a float switch on the inlet side of the pump.
• Accumulated flow
When this function has been selected, the accumulated flow
can be registered. This requires the use of a flowmeter which
can give a feedback signal as a pulse per defined flow of
water. See section 14.21 Pulse flowmeter setup.
• Predefined setpoint digit 1 (applies only to digital input 2)
When digital inputs are set to a predefined setpoint, the pump
will operate according to a setpoint based on the combination
of the activated digital inputs. See section 14.18 Predefined
setpoints.
The priority of the selected functions in relation to each other
appears from section 18. Priority of settings.
A stop command will always have the highest priority.
Factory setting
See section 31. Factory settings.
FM 300*
(advanced)
English (GB)
35
Page 36
14.12 Digital inputs/outputs
+ 24V
DO 3/4
External
controller
English (GB)
Available inputs or outputs depending on the functional module
fitted in the pump:
Function (terminal)
Digital input/output 3, setup (10
and 16)
Digital input/output 4, setup (11
and 18)
* See section 22. Identifying the functional module.
You can select if the interface must be used as input or output.
The output is an open collector and you can connect it to e.g. an
external relay or controller such as a PLC.
FM 200*
(standard)
-
FM 300*
(advanced)
Possible functions, digital input or output 4
Function if input
See details in section
14.11 Digital inputs
• Not active
• External stop
•Min.
•Max.
• External fault
• Alarm resetting
• Dry running
• Accumulated flow*
• Predefined setpoint 3
* Only TPE2, TPE2 D.
Factory setting
See section 31. Factory settings.
Function if output
See details in section
14.13 Signal relays 1 and 2
(Relay outputs)
• Not active
• Not active
• Ready
•Alarm
•Operation
• Pump running
• Warning
• Limit 1 exceeded*
• Limit 2 exceeded*
14.13 Signal relays 1 and 2 (Relay outputs)
Fig. 57 Example of configurable digital inputs or outputs
To set a digital input or output, make the settings below.
Mode
The digital input or output 3 and 4 can be set to act as digital input
or digital output:
• Digital input
• Digital output.
Function
The digital input or output 3 and 4 can be set to the functions
mentioned below.
* See section 22. Identifying the functional module.
The pump incorporates two signal relays for potential-free
signalling. For further information, see section 20. Signal relays.
Function
You can configure the signal relays to be activated by one of the
following incidents:
•Not active.
• Ready
The pump can be running or is ready to run and no alarms are
present.
•Alarm
There is an active alarm and the pump is stopped.
• Operating (Operation)
"Operating" equals "Running" but the pump is still in operation
when it has been stopped due to a warning.
• Running (Pump running)
• Warning
There is an active warning.
• Limit 1 exceeded*
When the "Limit 1 exceeded" function is activated, the signal
relay is activated. See section 14.20 Limit-exceeded function.
• Limit 2 exceeded*
When the "Limit 2 exceeded" function is activated, the signal
relay is activated. See section 14.20 Limit-exceeded function.
• Relubricate
• External fan control (Control of external fan)
When you select "External fan control", the relay is activated if
the internal temperature of the motor electronics reach a
preset limit value.
* Only TPE2, TPE2 D.
Factory setting
See section 31. Factory settings.
FM 200*
(standard)
FM 300*
(advanced)
36
Page 37
14.14 Analog output
Whether the analog output is available or not, depends on the
functional module fitted in the pump:
Function (terminal)
FM 200*
(standard)
Analog output-
* See section 22. Identifying the functional module.
The analog output enables the transfer of certain operating data
to external control systems.
To set the analog output, make the settings below.
Output signal
• 0-10 V
• 0-20 mA
• 4-20 mA.
Function of analog output
• Actual speed
Actual speed
Signal range
[%]
[V, mA]
0100200
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
the reading is a percentage of nominal speed.
• Actual value
Signal range
[V, mA]
Sensor
Actual value
min
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
The reading is a percentage of the range between sensor
sensor
max
.
• Resulting setpoint
Resulting setpoint
Signal range
[%]
[V, mA]
0100
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
The reading is a percentage of the external setpoint range.
FM 300*
(advanced)
Sensor
max
min
and
• Motor load
Motor load
Signal range
[%]
[V, mA]
0100200
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
Reading is a percentage of the range between 0 and 200 % of the
maximum permissible load at the actual speed.
• Motor current
Motor current
Signal range
[%]
[V, mA]
0100200
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
The reading is a percentage of the range between 0 % and 200 %
of the rated current (I
).
N
• Limit 1 exceeded and Limit 2 exceeded
This function is only available on TPE2, TPE2 D pumps.
Signal range
[V, mA]
Limit-exceeded function
Output not activeOutput active
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
Limit-exceeded function is typically used for monitoring of
secondary parameters in the system. If the limit is exceeded, an
output, warning or alarm is activated.
•Flow rate
Flow rate
Signal range
[%]
[V, mA]
0100200
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
The reading is a percentage of the range between 0 and 200 % of
the nominal flow (Q
nom
).
Factory setting
See section 31. Factory settings.
English (GB)
37
Page 38
14.15 Controller (Controller settings)
p
p
p
p
ǻS
L1
L1
ǻS
L2
t
L2
t
t
L2
t
t
t
L2
Q
p
p
L
L
English (GB)
Pump variant
Controller
(Controller settings)
TPE3, TPE3 D
TPE2, TPE2 D
The pumps have a factory default setting of gain (Kp) and integral
time (T
).
i
However, if the factory setting is not the optimum setting, you can
change the gain and the integral time:
• Set the gain (K
• Set the integral-action time (T
3600 s.
) within the range from 0.1 to 20.
p
) within the range from 0.1 to
i
If you select 3600 s, the controller will function as a P
controller.
Furthermore, you can set the controller to inverse control.
This means that if the setpoint is increased, the speed will be
reduced. In the case of inverse control, set the gain (K
the range from -0.1 to -20.
Guidelines for setting of PI controller
The tables below show the recommended controller settings:
Differential-pressure
control
K
p
) within
p
T
i
Differential-temperature
control
K
p
-0.510 + 5L2
L2: Distance [m] between heat exchanger and sensor.
Flow controlK
p
0.50.5
Constant-pressure controlK
p
0.50.5
T
i
T
i
T
i
0.50.5
0.5
L1: Distance [m] between pump and sensor.
K
p
Temperature control
Heating
system
Cooling
1)
system
0.5-0.510 + 5L2
L1 < 5 m: 0.5
L1 > 5 m: 3
L1 > 10 m: 5
T
2)
0.10.5
Level controlK
p
T
i
-2.5100
2.5100
i
General rules of thumb
If the controller is too slow-reacting, increase K
.
p
If the controller is hunting or unstable, dampen the system by
reducing K
or increasing Ti.
p
Factory setting
See section 31. Factory settings.
0.5-0.530 + 5L2
1)
In heating systems, an increase in pump performance will
result in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance will
result in a drop in temperature at the sensor.
L2: Distance [m] between heat exchanger and sensor.
38
Page 39
14.16 Operating range
Note
Note
Fixed maximum speed
User-set maximum speed
Operating range
User-set minimum speed
Fixed minimum speed
24 %
13 %
0 %
67 %
100 %
Note
100
0
100 %
0
1.2
2
[bar]
0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Actual
input
signal
(60 %)
External
setpoint
signal
Setpoint
Sensor max.
Sensor min.
Actual
Setpoint
100
0
100 %
0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
25
61
85
External
setpoint
signal
Speed [%]
Fixed
maximum
speed
Actual
input
signal
(60 %)
User-set min.
speed
Setpoint
Actual setpoint
Pump variantOperating range
TPE3, TPE3 D
TPE2, TPE2 D
Set the operating range as follows:
• Set the minimum speed within the range from fixed minimum
speed to user-set maximum speed.
• Set the maximum speed within the range from user-set
minimum speed to fixed maximum speed.
The range between the user-set minimum and maximum speeds
is the operating range. See fig. 58.
Speeds below 25 % may result in noise from the
shaft seal.
Example with constant pressure with linear influence
Actual setpoint: actual input signal x (setpoint - sensor min.) +
sensor min.
At a lower sensor value of 0 bar, a setpoint of 2 bar and an
external setpoint of 60 %, the actual setpoint is 0.60 x (2 - 0) + 0 =
1.2 bar.
English (GB)
TM06 4165 1615
Fig. 59 Example of setpoint influence with sensor feedback
Example with constant curve with linear influence
Actual setpoint: actual input signal x (setpoint - user-set minimum
speed) + user-set minimum speed.
At a user-set minimum speed of 25 %, a setpoint of 85 % and an
external setpoint of 60 %, the actual setpoint is 0.60 x (85 - 25) +
25 = 61 %. See fig. 60.
Fig. 58 Example of minimum and maximum settings
Factory setting
See section 31. Factory settings.
14.17 External setpoint function
Pump variantExternal setpoint function
TPE3, TPE3 D
TPE2, TPE2 D
You can influence the setpoint by an external signal, either via
one of the analog inputs or, if an advanced functional module is
fitted, via one of the Pt100/1000 inputs.
Before you can enable the External setpoint function,
you must set one of the analog inputs or Pt100/1000
inputs to Setpoint influence.
See sections 14.8 Analog inputs and
14.10 Pt100/1000 inputs.
If more than one input has been set to "Setpoint influence", the
function will select the analog input with the lowest number, for
example "Setting of pump", and ignore the other inputs, for
example "Analog input 3" or "Pt100/1000 input 1".
TM00 6785 5095
The maximum curve will in some cases be limited to
a lower speed. See fig. 53.
Fig. 60 Example of setpoint influence with constant curve
Factory setting
See section 31. Factory settings.
TM06 4525 2515
39
Page 40
14.17.1 Setpoint influence
100
0
100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Setpoint influence [%]
External input
100
0
20100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
100
0
100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Setpoint influence [%]
External input
English (GB)
The table below gives an overview of the types of setpoint
influence and the availability depending on pump type.
Setpoint influence
Not active
Linear function
Linear with Stop-
Linear with Min.
Inverse function-
Inverse with Stop-
Inverse with Min.-
Influence table-
Influence table with Stop at Min.-
Influence table with Stop at Max.-
You can select these functions:
• Not active
When set to "Not active", the setpoint will not be influenced
from any external function.
Linear function
•
The setpoint is influenced linearly from 0 to 100 %. See fig. 61.
Pump type
TPE3
TPE3 D
TPE2
TPE2 D
• "Linear with Stop" and "Linear with Min."
– Linear with Stop
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is above 15 %, the operating mode will be
changed back to "Normal". See fig. 62.
– Linear with Min.
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Min.".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal". See fig. 62.
Fig. 61 Linear function
40
TM06 4167 1615TM06 4168 1615
Fig. 62 "Linear with Stop" and "Linear with Min."
• Linear with Min.
The setpoint is influenced inversely from 0 to 100 %.
See fig. 63.
TM06 4166 1615
Fig. 63 Linear with Min.
Page 41
• "Inverse with Stop" and "Inverse with Min."
100
0
80
0
0.5
0
0
0
4
-50
100 %
3.5 V
5 V
10 V
20 mA
20 mA
204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
100
0
100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Setpoint influence [%]
External
input
100
0
20
0
0.5
0
0
0
4
-50
100 %
3.5 V
5 V
10 V
20 mA
20 mA
204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
100
0
800
0.5
0
0
0
4
-50
100 %
3.5 V
5 V
10 V
20 mA
20 mA
204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
– Inverse with Stop
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Stop".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal". See fig. 64.
– Inverse with Min.
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal". See fig. 64.
• Influence table with Stop at Min.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point. If
the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal". See fig. 66.
English (GB)
Fig. 64 "Inverse with Stop" and "Inverse with Min."
• Influence table
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
Fig. 66 Influence table with Stop at Min., example with five
points
• Influence table with Stop at Max.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point. If
TM06 4169 1615TM06 4170 1615
the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating mode
will be changed back to "Normal". See fig. 67.
TM06 4171 1615TM06 4172 1615
Fig. 65 Influence table, example with five points
Fig. 67 Influence table with Stop at Max., example with five
points
41
Page 42
Predefined setpoints
0
1
2
3
4
5
6
7
Digital input 4
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
Setpoint 6
Setpoint 7
Digital input 3
Digital input 2
Actual setpoint
Stop
Normal
setpoint
Note
H
T [°C]
30 %
205080
100 %
H
actual
T
actual
H
Q
14.18
English (GB)
Pump variantPredefined setpoints
TPE3, TPE3 D*
TPE2, TPE2 D*
This function is only available if an advanced functional module is
fitted in the pump:
Function (terminal)
FM 200*
(standard)
Predefined setpoints-
* See section 22. Identifying the functional module.
You can set and activate seven predefined setpoints by
combining the input signals to digital inputs 2, 3 and 4 as shown
in the table below.
Set the digital inputs 2, 3 and 4 to "Predefined setpoints" if all
seven predefined setpoints are to be used. You can also set one
or two of the digital inputs to "Predefined setpoints" but this will
limit the number of predefined setpoints available.
Figure 68 shows how you can use the digital inputs to set seven
predefined setpoints. Digital input 2 is open and digital inputs 3
and 4 are closed. If you compare with the table above, you can
see that "Predefined setpoint 6" is activated.
Fig. 68 Principle sketch showing how predefined setpoints
function
If all digital inputs are open, the pump will either stop or run at the
normal setpoint. Set the desired action with Grundfos GO or with
the advanced control panel.
Factory setting
See section 31. Factory settings.
FM 300*
(advanced)
14.19 Temperature influence
Pump variantTemperature influence
TPE3, TPE3 D
TPE2, TPE2 D-
When this function is enabled in proportional- or
constant-pressure control mode, the setpoint for head will be
reduced according to the liquid temperature.
Temperature influence can be set to function at liquid
temperatures below 80 or 50 °C. These temperature limits are
called T
100 %) according to the characteristics below.
Fig. 69 Temperature influence
In the above example, T
actual liquid temperature, T
be reduced from 100 % to H
The temperature influence function requires the following:
• proportional-pressure or constant-pressure control mode
• pump installed in flow pipe
• system with flow-pipe temperature control.
Temperature influence is suitable for the following systems:
• Systems with variable flows, for example two-pipe heating
systems, in which the enabling of the temperature influence
function will ensure a further reduction of the pump
performance in periods with small heating demands and
consequently a reduced flow-pipe temperature.
• Systems with almost constant flows (for example one-pipe
heating systems and underfloor heating systems) in which
variable heating demands cannot be registered as changes in
the head as is the case with two-pipe heating systems. In such
systems, the pump performance can only be adjusted by
enabling the temperature influence function.
Selecting the maximum temperature
In systems with a dimensioned flow-pipe temperature of:
• up to and including 55 °C, select T
• above 55 °C, select T
TM06 4269 1815
Factory setting
See section 31. Factory settings.
. The setpoint is reduced in relation to the head set (=
max.
= 80 °C has been selected. The
max.
, causes the setpoint for head to
actual
.
actual
= 50 °C
max.
max.
= 80 °C.
You cannot use the temperature influence function in
air-conditioning and cooling systems.
TM05 7911 1613
42
Page 43
14.20 Limit-exceeded function
1
2
44
56
3
A
Time [s]
Pump variantLimit-exceeded function
TPE3, TPE3 DTPE2, TPE2 D
This function can monitor a measured parameter or one of the
internal values such as speed, motor load or motor current. If a
set limit is reached, a selected action can take place. You can set
two limit-exceeded functions meaning that you can monitor two
parameters or two limits of the same parameter simultaneously.
The function requires setting of the following:
Measured
Here you set the measured parameter to be monitored.
Limit
Here you set the limit which activates the function.
Hysteresis band
Here you set the hysteresis band.
Limit exceeded when
Here you can set if you want the function to be activated when the
selected parameter exceeds or drops below the set limit.
• Above limit
The function is activated if the measured parameter exceeds
the set limit.
• Below limit
The function is activated if the measured parameter drops
below the set limit.
Action
If the value exceeds a limit, you can define an action. You can
select the following actions:
• No action
The pump remains in its current state. Use this setting if you
only want to have a relay output when the limit is reached. See
section 14.13 Signal relays 1 and 2 (Relay outputs).
• Warning/alarm
There is a warning.
•Stop
The pump stops.
•Min.
The pump reduces speed to minimum.
•Max.
The pump increases speed to maximum.
Detection delay
You can set a detection delay which ensures that the monitored
parameter stays above or below a set limit in a set time before the
function is activated.
Resetting delay
The resetting delay is the time from which the measured
parameter differs from the set limit including the set hysteresis
band and until the function is reset.
Example
The function is to monitor the outlet pressure of a pump. If the
pressure is below 5 bar for more than 5 seconds, a warning must
be given. If the outlet pressure is above 7 bar for more than 8
seconds, you must reset the warning.
Fig. 70 Limit exceeded (example)
Pos. Setting parameterSetting
1MeasuredOutlet pressure
2Limit5 bar
3Hysteresis band2 bar
4Limit exceeded whenBelow limit
5Detection delay5 seconds
6Resetting delay8 seconds
ALimit-exceeded function active-
-ActionWarning
Factory setting
See section 31. Factory settings.
14.21 Pulse flowmeter setup
Pump variantPulse flowmeter setup
TPE3, TPE3 DTPE2, TPE2 D
An external pulse flowmeter can be connected to one of the
digital inputs in order to register the actual and accumulated
flows. Based on this, the specific energy [kWh/m
calculated.
To enable a pulse flowmeter, one of the digital inputs must be set
to "Accumulated flow" and the pumped volume per pulse must be
set. See section 14.11 Digital inputs.
Factory setting
See section 31. Factory settings.
3
] can also be
English (GB)
TM06 4603 2515
43
Page 44
14.22 Ramps
Note
User set ramp-upUser set ramp-down
Speed
Time
User set
minimum
Fixed initial
ramp
Fixed final
ramp
user set
maximum
Fixed
maximum
0
Note
English (GB)
Pump variantRamps
TPE3, TPE3 DTPE2, TPE2 D
The ramps determine how quickly the motor can accelerate and
decelerate, during start/stop or setpoint changes.
The following can be set:
• acceleration time, 0.1 to 300 s
• deceleration time, 0.1 to 300 s.
The times apply to the acceleration from 0 rpm to maximum
(fixed) speed and the deceleration from maximum (fixed) speed
to 0 rpm.
At short deceleration times, the deceleration of the motor may
depend on load and inertia as there is no possibility of actively
braking the motor.
If the power supply is switched off, the deceleration of the motor
only depends on load and inertia.
Fig. 71 Ramp-up and ramp-down
Factory setting
See section 31. Factory settings.
14.23 Standstill heating
Pump variantStandstill heating
TPE3, TPE3 D
TPE2, TPE2 D
You can use the function to avoid condensation in humid
environments. When you set the function to "Active" and the
pump is in operating mode "Stop", a low AC voltage will be
applied to the motor windings. The applied voltage is not high
enough to make the motor rotate but will ensure that sufficient
heat is generated to avoid condensation in the motor including
the electronic parts in the drive.
Remember to remove the drain plugs and fit a cover
over the motor.
For further information, see section 6.8 Outdoor installation.
Factory setting
See section 31. Factory settings.
14.24 Motor bearing monitoring
You can set the motor bearing monitoring function to these
values:
•Active
•Not active
When the function is set to "Active", a counter in the controller will
start counting the mileage of the bearings.
The counter will continue counting even if the
function is changed to "Not active", but a warning will
not be given when it is time for replacement.
When the function is changed to "Active" again, the
accumulated mileage will again be used to calculate
the replacement time.
Factory setting
See section 31. Factory settings.
14.25 Service
Pump variantService
TPE3, TPE3 D
TPE2, TPE2 D
Time until next service (Motor bearing service)
This display shows when to replace the motor bearings. The
controller monitors the operating pattern of the motor and
calculates the period between bearing replacements.
Displayable values:
• in 2 years
• in 1 year
• in 6 months
• in 3 months
• in 1 month
TM03 9439 0908
• in 1 week
•Now
Bearing replacements
Indicates the number of bearing replacements that have been
done during the lifetime of the motor.
Bearings replaced (Motor bearing maintenance)
When the bearing monitoring function is active, the controller will
give a warning when the motor bearings are to be replaced.
When you have replaced the motor bearings, confirm this action
by pressing [Bearings replaced].
14.26 Number (Pump number)
Pump variant
TPE3, TPE3 D
TPE2,TPE2 D
A unique number can be allocated to the pump. This makes it
possible to distinguish between pumps in connection with bus
communication.
Factory setting
See section 31. Factory settings.
Number
(Pump number)
44
Page 45
14.27 Radio communication (Enable/disable radio
Note
Note
comm.)
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
You can set the radio communication to either enabled or
disabled. You can use this function in areas where radio
communication is not allowed.
IR communication will remain active.
Factory setting
See section 31. Factory settings.
Radio communication
(Enable/disable radio
comm.)
14.28 Language
Pump variantLanguage
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel.
In this menu you can select the desired language. A number of
languages is available.
14.29 Date and time (Set date and time)
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
The availability of this menu depends on the functional module
fitted in the pump:
Function (terminal)
Date and time-
* See section 22. Identifying the functional module.
You can set date and time as well as how they are to be shown in
the display:
• Select date format:
YYYY-MM-DD
DD-MM-YYYY
MM-DD-YYYY.
In this menu you can select between SI and US units. The setting
can be made generally for all parameters or customised for each
individual parameter.
Factory setting
See section 31. Factory settings.
14.31 Buttons on product (Enable/disable settings)
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
In this display, you can disable the possibility of making settings.
Grundfos GO
If you set the buttons to "Not active", the buttons on the standard
control panel will be disabled. If you set the buttons to "Not
active" on pumps with an advanced control panel, see below.
Advanced control panel
If you have disabled the settings, you can still use the buttons to
navigate through the menus but you cannot make changes in the
"Settings" menu.
When you have disabled the possibility to make settings, the
symbol will appear in the display.
Advanced control panel:
To unlock the pump and allow settings, press and
simultaneously for at least 5 seconds.
Standard control panel:
The button always remains active but you can
only unlock all other buttons on the pump with
Grundfos GO.
Factory setting
See section 31. Factory settings.
Buttons on product
(Enable/disable settings)
14.32 Delete history
Pump variantDelete history
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel.
In this menu, you can delete the following historic data:
• Delete work log.
• Delete heat energy data.
• Delete energy consumption.
14.33 Define Home display
Pump variantDefine Home display
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel.
In this menu, you can set the "Home" display to show up to four
user-set parameters.
14.34 Display settings
Pump variantDisplay settings
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel.
In this menu you can adjust the display brightness and set
whether or not the display is to turn off if no buttons have been
activated for a period of time.
English (GB)
45
Page 46
14.35 Store settings (Store actual settings)
Note
English (GB)
14.39 Connection code
Pump variantStore actual settings
TPE3, TPE3 D
TPE2, TPE2 D
Grundfos GO
In this menu, you can store the actual settings for later use in the
same pump or in other pumps of the same type.
Advanced control panel
In this menu, you can store the actual settings for later use in the
same pump.
14.36 Recall settings (Recall stored settings)
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Grundfos GO
In this menu, you can recall stored settings from a number of
previously stored settings that the pump will then use.
Advanced control panel
In this menu, you can recall the last stored settings that the pump
will then use.
Recall settings
(Recall stored settings)
14.37 Undo
Pump variantUndo
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in Grundfos GO.
In this display, you can undo all settings that have been made
with Grundfos GO in the current communication session. You
cannot undo a "Recall stored settings" action.
14.38 Pump name
Pump variantPump name
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in Grundfos GO.
In this display, you can give the pump a name. In this way, you
can easily identify the pump when connecting with Grundfos GO.
Factory setting
See section 31. Factory settings.
Pump variantConnection code
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in Grundfos GO.
You can setup a connection code to avoid having to press the
connection button each time and to restrict remote access to the
product.
Setting the code in the product using Grundfos GO
1. Connect Grundfos GO to the product.
2. In the product dashboard, select "Settings".
3. Choose "Connection code".
4. Enter the wanted code and press [OK].
The code must be a character string (ASCII).
You can always modify the code. The old code is not needed.
Setting the code in Grundfos GO
You can set a default connection code in Grundfos GO so that it
automatically attempts to connect to the selected product via this
code.
When you select a product with the same connection code in
Grundfos GO, Grundfos GO automatically connects to the
product and you do not have to press the connection button on
the module.
Set the default code in Grundfos GO in this way:
1. In the main menu, under "General", select "Settings".
2. Choose "Remote".
3. Enter the connection code in the field "Preset connection
code". The field now says "Connection code set".
You can always modify the default connection code by pressing
[Delete] and entering a new one.
If Grundfos GO fails to connect and ask you to press the
connection button on the product, it means that the product has
no connection code or has a different connection code. In this
case, you can only establish connection via the connection
button.
After setting a connection code, you must switch off
the product until the light in Grundfos Eye turns off
before you can use the new connection code.
Factory setting
See section 31. Factory settings.
46
Page 47
14.40 Run start-up guide
14.44 Assisted pump setup
Pump variantRun start-up guide
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel.
The startup guide automatically starts when you start the pump
for the first time.
You can always run the startup guide later via this menu.
The startup guide will guide you through the general settings of
the pump.
• Language. See section 14.28 Language.
• Select date format.*
See section 14.29 Date and time (Set date and time).
• Set date.*
See section 14.29 Date and time (Set date and time).
• Select time format.*
See section 14.29 Date and time (Set date and time).
• Set time.*
See section 14.29 Date and time (Set date and time).
• Setting of pump
– Go to Home
– Run with Constant curve/Run with Constant pressure.
See section 14.5 Control mode
– Go to "Assisted pump setup".
See section 14.44 Assisted pump setup.
– Return to factory settings.
* Applies only for pumps with advanced functional module, FM
300. For further information, see section 22. Identifying the
functional module.
14.41 Alarm log
This menu contains a list of logged alarms from the product. The
log shows the name of the alarm, when the alarm occurred and
when it was reset.
14.42 Warning log
This menu contains a list of logged warnings from the product.
The log shows the name of the warning, when the warning
occurred and when it was reset.
14.43 Assist
The menu consist of functions which take you through the steps
needed to set the pump.
Pump variantAssisted pump setup
TPE3, TPE3 D
TPE2, TPE2 D
The menu guides you through the following:
Setting of pump
• Selection of control mode. See page 28.
• Configuration of feedback sensors.
• Adjusting the setpoint. See page 27.
• Controller settings. See page 38.
• Summary of settings.
Example of how to use the "Assisted pump setup" for setting
up the pump to constant pressure:
Grundfos GO
1. Open the "Assist" menu.
2. Select "Assisted pump setup".
3. Select the control mode "Constant pressure".
4. Read the description of this control mode.
5. Select which analog input to use as sensor input.
6. Select sensor function according to where the sensor is
installed in the system. See fig. 55.
7. Select electrical input signal according to the sensor
specifications.
8. Select measuring unit according to the sensor specifications.
9. Set the minimum and maximum sensor values according to
the sensor specifications.
10. Set the desired setpoint.
11. Set the controller settings K
recommendations in section 14.15 Controller (Controller
settings).
12. Type the pump name.
13. Check the summary of settings and confirm them.
Advanced control panel
1. Open the "Assist" menu.
2. Select "Assisted pump setup".
3. Select the control mode "Const. pressure".
4. Select which analog input to be used as sensor input.
5. Select the measured parameter to be controlled. See fig. 55.
6. Select measuring unit according to the sensor specifications.
7. Set the minimum and maximum sensor values according to
the sensor specifications.
8. Select electrical input signal according to the sensor
specifications.
9. Set the setpoint.
10. Set the controller settings K
section 14.15 Controller (Controller settings).
11. Check the summary of settings and confirm them by pressing
[OK].
and Ti. See the
p
and Ti. See recommendations in
p
English (GB)
47
Page 48
14.45 Setup, analog input
English (GB)
This menu is only available in the advanced control panel.
Pump variantSetup, analog input
TPE3, TPE3 D
TPE2, TPE2 D
The menu guides you through the following:
Setup, analog input
• Analog inputs 1 to 3. See page 33.
• Pt100/1000 input 1 and 2. See page 35.
• Adjusting the setpoint. See page 27.
•Summary.
14.46 Setting of date and time
Pump variantSetting of date and time
TPE3, TPE3 D
TPE2, TPE2 D
This menu is only available in the advanced control panel.
Whether this menu is available or not, depends on the functional
module fitted in the pump:
Function (terminal)
Setting of date and time-
* See section 22. Identifying the functional module.
This menu will guide you through the following:
• Select date format. See section 14.29 Date and time (Set date
and time).
• Set date. See section 14.29 Date and time (Set date and
time).
• Select time format. See section 14.29 Date and time (Set date
and time).
• Set time. See section 14.29 Date and time (Set date and
time).
FM 200*
(standard)
FM 300*
(advanced)
14.47 Multipump setup (Setup of multi-pump system)
Multipump setup
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
The multipump function enables the control of two pumps
connected in parallel without the use of external controllers. The
pumps in a multipump system communicate with each other via
the wireless GENIair connection or the wired GENI connection.
A multipump system is set via a selected pump, i.e. the master
pump (first selected pump).
If two pumps in the system are configured with an outlet-pressure
sensor, both pumps can function as master pumps and take over
the master pump function if the other fails. This provides
additional redundancy in the multipump system.
The multipump functions are described in the following sections.
14.47.1 Alternating operation
Alternating operation functions as a duty/standby operating mode
and is possible with two pumps of same size and type connected
in parallel. The main purpose of the function is to ensure an even
amount of running hours and to ensure that the standby pump
takes over if the running pump stops due to an alarm.
Each pump requires a non-return valve in series with the pump.
You can choose between two alternating operation modes:
• Alternating operation, time
Pump changeover to the other is based on time.
• Alternating operation, energy
Pump changeover to the other is based on energy
consumption.
If the duty pump fails, the other pump will take over automatically.
14.47.2 Backup operation
Backup operation is possible with two pumps of same size and
type connected in parallel. Each pump requires a non-return
valve in series with the pump.
One pump is operating continuously. The backup pump is
operated for a short time each day to prevent seizing up. If the
duty pump stops due to a fault, the backup pump will start
automatically.
14.47.3 Cascade operation
Cascade operation ensures that the pump performance is
automatically adapted to the consumption by switching pumps on
or off. The system thus runs as energy-efficiently as possible with
a constant pressure and a limited number of pumps.
When a twin-head pump is running in constant-pressure control
mode, the second pump head will start at 90 % and stop at 50 %
performance.
All pumps in operation will run at equal speed. Pump changeover
is automatic and depends on energy, operating hours and fault.
Pump system:
• Twin-head pump.
• Two to four single-head pumps connected in parallel.
The pumps must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
The control mode must be set to "Const. pressure" or "Const.
curve".
(Setup of multi-pump
system)
48
Page 49
14.47.4 Setting a multipump system
Note
Note
Note
Note
You can set a multipump system in the following ways:
• Grundfos GO and wireless pump connection
• Grundfos GO and wired pump connection
• Advanced control panel and wireless pump connection
• Advanced control panel and wired pump connection
See step-by-step descriptions below.
Grundfos GO and wireless pump connection
1. Power on both pumps.
2. Establish contact to one of the pumps with Grundfos GO.
3. Set the needed analog and digital inputs via Grundfos GO
according to the connected equipment and the required
functionality. See section 14.44 Assisted pump setup.
4. Assign a pump name to the pump using Grundfos GO. See
section 14.38 Pump name.
5. Disconnect Grundfos GO from the pump.
6. Establish contact to the other pump.
7. Set the needed analog and digital inputs via Grundfos GO
according to the connected equipment and the required
functionality. See section 14.44 Assisted pump setup.
8. Assign a pump name to the pump using Grundfos GO. See
section 14.38 Pump name.
9. Select the "Assist" menu and "Multipump setup".
10. Select the desired multipump function. See section
14.47.1 Alternating operation and 14.47.2 Backup operation
above.
11. Press [>] to continue.
12. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
This step applies only if you have selected
"Alternating operation, time", and if the pumps are
fitted with FM 300.
13. Press [>] to continue.
14. Select "Radio" as the communication method to be used
between the two pumps.
15. Press [>] to continue.
16. Press "Select pump 2".
17. Select the pump from the list.
You can use the [OK] or button to identify the
pump.
18. Press [>] to continue.
19. Confirm the multipump setup by pressing [Send].
20. Press [Finish] in the "Setup complete" dialog box.
21. Wait for the green indicator light in the middle of Grundfos Eye
to light up.
The multipump system has now been set.
Grundfos GO and wired pump connection
1. Connect the two pumps with each other with a 3-core
screened cable between the GENIbus terminals A, Y, B.
2. Power on both pumps.
3. Establish contact to one of the pumps with Grundfos GO.
4. Set the needed analog and digital inputs via Grundfos GO
according to the connected equipment and the required
functionality. See section 14.44 Assisted pump setup.
5. Assign a pump name to the pump using Grundfos GO. See
section 14.38 P ump name .
6. Assign pump number 1 to the pump. See section
14.26 Number (Pump number).
7. Disconnect Grundfos GO from the pump.
8. Establish contact to the other pump.
9. Set the needed analog and digital inputs via Grundfos GO
according to the connected equipment and the required
functionality. See section 14.44 Assisted pump setup.
10. Assign a pump name to the pump using Grundfos GO. See
section 14.38 P ump name .
11. Assign pump number 2 to the pump. See section
14.26 Number (Pump number).
12. Select the "Assist" menu and choose "Multipump setup".
13. Select the desired multipump function. See section
14.47.1 Alternating operation and 14.47.2 Backup operation
above.
14. Press [>] to continue.
15. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
This step applies only if you have selected
"Alternating operation, time" and if the pumps are
fitted with FM 300.
16. Press [>] to continue.
17. Select "BUS cable" as the communication method to be used
between the two pumps.
18. Press [>] to continue.
19. Press "Select pump 2".
20. Select the additional pump from the list.
Use the [OK] or button to identify the additional
pump.
21. Press [>] to continue.
22. Press [Send].
23. Press [Finish] in the "Setup complete" dialog box.
24. Wait for the green indicator light in the middle of Grundfos Eye
to light up.
The multipump system has now been setup.
English (GB)
49
Page 50
Advanced control panel and wireless pump connection
Note
Note
English (GB)
1. Power on both pumps.
2. On both pumps, set the needed analog and digital inputs
according to the connected equipment and the required
functionality. See section 14.44 Assisted pump setup.
3. Select the "Assist" menu on one of the pumps and choose
"Setup of multi-pump system".
4. Press [>] to continue.
5. Select "Wireless" as the communication method to be used
between the two pumps.
6. Press [>] to continue.
7. Select the desired multipump function. See section
14.47.1 Alternating operation and 14.47.2 Backup operation
above.
8. Press [>] three times to continue.
9. Press [OK] to search for other pumps.
The green indicator light in the middle of Grundfos Eye will
flash on the other pumps.
10. Press the connect button on the pump which is to be added to
the multipump system.
11. Press [>] to continue.
12. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
This step applies only if you have selected
"Alternating operation, time" and if the pumps are
fitted with FM 300.
13. Press [>] to continue.
14. Press [OK].
The multipump function icons appear in the bottom of the
control panels.
The multipump system has now been set.
Advanced control panel and wired pump connection
1. Connect the two pumps with each other with a 3-core
screened cable between the GENIbus terminals A, Y, B.
2. Set the needed analog and digital inputs according to the
connected equipment and the required functionality. See
section 14.44 Assisted pump setup.
3. Assign pump number 1 to the first pump. See section
14.26 Number (Pump number).
4. Assign pump number 2 to the other pump. See section
14.26 Number (Pump number).
5. Select the "Assist" menu on one of the pumps and choose
"Setup of multi-pump system".
6. Press [>] to continue.
7. Select "Wired GENIbus" as the communication method to be
used between the two pumps.
8. Press [>] twice to continue.
9. Select the desired multipump function. See section
14.47.1 Alternating operation and 14.47.2 Backup operation.
10. Press [>] to continue.
11. Press [OK] to search for other pumps.
12. Select the additional pump from the list.
13. Press [>] to continue.
14. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
This step applies only if you have selected
"Alternating operation, time" and if the pumps are
fitted with FM 300.
15. Press [>] to continue.
16. Press [OK].
The multipump function icons will appear in the bottom of the
control panels.
The multipump system has now been setup.
Disabling the multipump function via Grundfos GO
1. Select the "Assist" menu.
2. Select "Multipump setup".
3. Select "Disable".
4. Press [>] to continue.
5. Confirm the multipump setup by pressing [Send].
6. Press [Finish].
The multipump function has now been disabled.
Disabling a multipump via advanced control panel
1. Select the "Assist" menu.
2. Select "Setup of multi-pump system".
3. Press [>] to continue.
4. Confirm No multi-pump function by pressing [OK].
5. Press [>] to continue.
6. Press [OK].
The multipump system has now been disabled.
14.48 Description of control mode
This menu is only available in the advanced control panel.
This menu describes each of the possible control modes. See
also section 14.5 Control mode.
14.49 Assisted fault advice
This menu gives guidance and corrective actions in case of pump
failures.
50
Page 51
15. Selecting control mode
H
Q
H
Q
H
Q
Hset
Hset
2
H
Q
H
Q
SystemSelect this control mode
Recommended for most heating systems, especially in systems with relatively large pressure
losses in the distribution pipes. See the description under proportional pressure.
In replacement situations where the proportional-pressure duty point is unknown.
The duty point has to be within the AUTO
automatically adjusts to the actual system characteristic.
operating range. During operation, the pump
ADAPT
This setting ensures minimum energy consumption and low noise level from valves, which
reduces operating costs and increases comfort.
AUTO
ADAPT
English (GB)
The FLOW
This control mode is suitable for systems where you want a maximum flow limit, FLOW
The pump continuously monitors and adjusts the flow, thus ensuring that the selected
FLOW
LIMIT
control mode is a combination of AUTO
ADAPT
is not exceeded.
ADAPT
and FLOW
LIMIT
.
.
LIMIT
Main pumps in boiler applications where a steady flow through the boiler is required. No extra
energy is used for pumping too much liquid into the system.
In systems with mixing loops, you can use the control mode to control the flow in each loop.
Benefits
• Enough water for all loops at peak load conditions if you have set each loop to the right
maximum flow.
• The dimensioned flow for each zone (required heat energy) is determined by the flow from
the pump.
You can set this value precisely in the FLOW
control mode without the use of throttling
ADAPT
valves.
• When the flow is set lower than the balancing valve setting, the pump will ramp down
instead of losing energy by pumping against a balancing valve.
• Cooling surfaces in air-conditioning systems can operate at high pressure and low flow.
In systems with relatively large pressure losses in the distribution pipes and in air-conditioning
and cooling systems.
• Two-pipe heating systems with thermostatic valves and
– very long distribution pipes
– strongly throttled balancing valves
– differential-pressure regulators
– large pressure losses in those parts of the system through which the total quantity of
water flows (for example boiler, heat exchanger and distribution pipe up to the first
branching).
• Primary circuit pumps in systems with large pressure losses in the primary circuit.
• Air-conditioning systems with
– heat exchangers (fan coils)
– cooling ceilings
– cooling surfaces.
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and
– dimensioned for natural circulation
– small pressure losses in those parts of the system through which the total quantity of
water flows (for example boiler, heat exchanger and distribution pipe up to the first
branching) or
– modified to a high differential temperature between flow pipe and return pipe (for example
district heating).
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or balancing valves.
• Primary circuit pumps in systems with small pressure losses in the primary circuit.
In systems with a fixed system characteristic.
Examples
• one-pipe heating systems
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
You can use FLOW
with advantage to control the maximum circulation flow.
LIMIT
FLOW
ADAPT
Proportional pressure
Constant differential pressure
Constant temperature and constant
differential temperature
51
Page 52
English (GB)
H
Q
Q
set
H
Q
H
Q
SystemSelect this control mode
If an external controller is installed, the pump is able to change from one constant curve to
another, depending on the external signal.
You can also set the pump to operate according to the maximum or minimum curve, like an
uncontrolled pump:
• You can use the maximum curve mode in periods in which a maximum flow is required.
This operating mode is for instance suitable for hot-water priority.
• You can use the minimum curve mode in periods in which a minimum flow is required.
This operating mode is for instance suitable for manual night setback if you do not want
automatic night setback.
Constant curve
In systems requiring a constant flow, independently of pressure drop.
Examples
• chillers for air-conditioning
• heating surfaces
• cooling surfaces.
In systems requiring a constant tank level, independently of the flow rate.
Examples
• process water tanks
• boiler condensate tanks.
In systems with pumps connected in parallel.
The multipump function enables the control of two to four single-head pumps connected in
parallel and twin-head pumps without the use of external controllers. The pumps in a
multipump system communicate with each other via the wireless GENIair connection or the
wired GENI connection.
Constant flow rate
Constant level
"Assist" menu
"Multipump setup"
52
Page 53
16. Changing the position of the control panel
Note
You can turn the control panel 180 °. Follow the instructions
below.
1. Loosen the four screws (TX25) that hold the terminal box
cover.
Fig. 72 Loosening the screws
2. Remove the terminal box cover.
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
English (GB)
TM05 5354 3612TM05 5355 3612TM05 5356 3612
Fig. 75 Turning the plastic cover
5. Position the plastic cover correctly on the four rubber pins (C).
Make sure that the locking tabs (A) are placed correctly.
TM05 5351 3612TM05 5352 3612TM05 5353 3612
Fig. 73 Removing the terminal box cover
3. Press and hold in the two locking tabs (A) while gently lifting
the plastic cover (B).
Fig. 74 Lifting the plastic cover
Fig. 76 Positioning the plastic cover
6. Fit the terminal box cover, and make sure that it is also turned
180 ° so that the buttons on the control panel are aligned with
the buttons on the plastic cover.
Tighten the four screws (TX25) with 5 Nm.
Fig. 77 Fitting the terminal box cover
53
Page 54
17. Bus signal
Note
English (GB)
The pump supports serial communication via an RS-485 input.
The communication is carried out according to Grundfos
GENIbus protocol and enables connection to other pumps as well
as a building management system or another external control
system.
Via a bus signal, you can remote-set pump operating parameters,
such as setpoint and operating mode. At the same time, the pump
can, via the bus, provide status information about important
parameters, such as actual value of control parameter, input
power and fault indications.
Contact Grundfos for further information.
If you use a bus signal, the number of settings
available via Grundfos GO will be reduced.
18. Priority of settings
You can always set the pump to stop by pressing on the
pump control panel. When the pump is not in "Stop" mode, you
can always stop the pump by continuously pressing .
Furthermore, you can set the pump to maximum speed by
continuously pressing . You can always set the pump to
operation at maximum speed or to stop with Grundfos GO.
If two or more functions are enabled at the same time, the pump
will operate according to the function with the highest priority.
Example
If, via the digital input, the pump has been set to maximum speed,
the pump control panel or Grundfos GO can only set the pump to
"Manual" or "Stop".
The priority of the settings appears from the table below:
PriorityStart/stop button
1Stop
2Stop*
3Manual
4Max. speed*
5Stop
6Stop
7Max. speed
8Min. speed
9Start
10Max. speed
11Min. speed
12Min. speed
13Start
14Start
* If the bus communication is interrupted, the pump will resume
its previous operating mode, for example "Stop", selected with
Grundfos GO or on the pump control panel.
Grundfos GO or control
panel on the motor
Digital inputBus communication
54
Page 55
19. Grundfos Eye
A
The operating condition of the pump is indicated by Grundfos Eye
on the control panel. See fig. 78, A.
Fig. 78 Grundfos Eye
Grundfos EyeIndicationDescription
English (GB)
TM05 5993 4312
No lights are on.
The two opposite green indicator lights are
rotating in the direction of rotation of the
pump when seen from the non-drive end.
The two opposite green indicator lights are
permanently on.
One yellow indicator light is rotating in the
direction of rotation of the pump when seen
from the non-drive end.
One yellow indicator light is permanently on.
The two opposite red indicator lights are
flashing simultaneously.
The green indicator light in the middle
flashes quickly four times.
The green indicator light in the middle
flashes continuously.
The power is off.
The pump is not running.
The power is on.
The pump is running.
The power is on.
The pump is not running.
Warning.
The pump is running.
Warning.
The pump has stopped.
Alarm.
The pump has stopped.
This is a feedback signal which the pump gives in
order to ensure identification of itself.
Grundfos GO or another pump is trying to
communicate with the pump. Press on the
pump control panel to allow communication.
The green indicator light in the middle is
permanently on.
The green indicator light in the middle
flashes quickly while Grundfos GO is
exchanging data with the pump. It will take a
few seconds.
Remote control with Grundfos GO via radio.
The pump is communicating with Grundfos GO
via radio connection.
Remote control with Grundfos GO via infrared
light.
The pump is receiving data from Grundfos GO via
infrared communication.
55
Page 56
20. Signal relays
NCNOCNCNOCNCNOCNCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNOCNCNO
C
C
NO NC
C
NO NC
NCNOCNCNOCNCNO
C
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
NCNOCNCNOCNCNO
C
C
NO NC
NCNO
C
English (GB)
The pump has two outputs for potential-free signals via two
internal relays.
You can set the signal outputs to "Operation", "Pump running",
"Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table
below:
DescriptionGrundfos Eye
Contact position for signal relays when activated
Operation
Pump
running
Digital
input
AlarmWarning
Operating
mode
The power is off.
The pump is running in
"Normal" mode.
The pump is running in
"Manual" mode.
The pump is in operating
mode "Stop".
Warning, but the pump is
running.
Warning, but the pump is
running in "Manual" mode.
Off
Green, rotating
Green, rotating
Green, steady
Yellow, rotating
Yellow, rotating
-
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
"Normal",
"Min." or
"Max."
"Manual"
Warning, but the pump
was stopped via "Stop"
command.
Alarm, but the pump is
running.
Alarm, but the pump is
running in "Manual" mode.
The pump has stopped
due to an alarm.
Yellow, steady
Red, rotating
Red, rotating
Red, flashing
"Stop"
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
56
Page 57
21. Installation of communication interface
Caution
A
B
B
C
D
A
A
A
B
A
module (CIM)
Always use an antistatic service kit when handling
electronic components. This will prevent static
electricity from damaging components.
When unprotected, place the component on the
antistatic cloth.
Fig. 79 Antistatic service kit
4. Remove the screw (fig. 82, A).
English (GB)
TM06 4082 1515TM06 4083 1515TM06 4195 1615
Fig. 82 Removing the screw
5. Fit the module by aligning it with the three plastic holders (fig.
83, A) and the connecting plug (fig. 83, B). Press home the
module using your fingers.
TM06 4462 2315
1. Disconnect the power supply to the pump.
2. Remove the terminal box cover by loosening the four screws
(fig. 80, A) and lifting the terminal box cover (fig. 80, B).
Fig. 80 Removing the terminal box cover
3. Remove the cover (fig. 81, A) by pressing the locking tab (fig.
81, B) and lifting the end of the cover (fig. 81, C). Then lift the
cover off the hooks (fig. 81, D).
Fig. 83 Align the module with plastic holders (A) and
connecting plug (B)
6. Fit and tighten the screw (fig. 82, A) with a torque of 1.3 Nm.
7. Make the electrical connections to the module as described in
the instructions delivered with the module.
8. Connect the cable screens of the bus cables to earth via one
of the earth clamps (fig. 84, A).
TM06 4081 1515TM06 4084 1515
Fig. 84 Connecting cable screens to earth
Fig. 81 Removing the cover
57
Page 58
9. Route the wires for the module. See the example in fig. 85.
Note
FCC
English (GB)
Fig. 85 Example of wire routing
10. Fit the cover.
11. If the module is supplied with an FCC label, then place this on
the terminal box. See fig. 86.
TM06 4085 1515TM05 7028 0413
Fig. 86 Position of FCC label
12. Fit the terminal box cover (fig. 80, B) and cross-tighten the
four screws (fig. 80, A) to 6 Nm.
Make sure that the terminal box cover is aligned with
the control panel. See section 16. Changing the
position of the control panel.
58
Page 59
22. Identifying the functional module
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
Hp
Hz
P2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
.
yyp
p
:
S
a
o
:
SF
C
:
P
:
n
W
g
g
t
:
DE
:
g
g
D
:
amb
:
:
FAA
P
.C.
:
PU
T
T
E
C
T
yp
yp
e
:
P.N.
:
U
n
:
:
f
n
P
S
p
p
:
:
PB
FM
HMICIM
VARIANT
Hp
rpm
::
:
:
PB
:
:
C
:
p
pm
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
Hp
Hz
P2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
.
yyp
p
:
S
a
o
:
SF
C
:
PF
:
Eff
n
W
g
g
t
:
DE
:
k
g
g
NDE
:
T
a
b
:
:
V
P
.C.
:
PU
T
T
E
C
T
yp
yp
e
:
P.N.
:
U
n:1/1
:
f
P
S
p
p
:
:
PBFM
HMI
CIM
VARIANT
Hp
rpm
:
:
::
PB
:
CIM
:
p
pm
FM
:
You can identify the module in one of the following ways:
Grundfos GO
Select the "Fitted modules" menu under "Status".
Pump display
If the pump is fitted with the advanced control panel, select "Fitted
modules" menu under "Status".
Motor nameplate
You can identify the module on the motor nameplate. See fig. 87.
IN
eri
k
i
e
F
i
L
F Am
F
r
/
IM
23. Identifying the control panel
You can identify the module in one of the following ways:
Grundfos GO
Select the "Fitted modules" menu under "Status".
Pump display
If the pump is fitted with the advanced control panel, select the
"Fitted modules" menu under "Status".
Motor nameplate
You can identify the control panel on the motor nameplate. See
fig. 88.
IN
eri
n
i
e
F
i
L
F Am
r
English (GB)
Fig. 87 Identification of functional module
VariantDescription
FM 200Standard functional module
FM 300Advanced functional module
TM06 1889 3314
TM06 4013 1415
Fig. 88 Identification of control panel
VariantDescription
HMI 200Standard control panel
HMI 300Advanced control panel
59
Page 60
24. Maintenance and service
English (GB)
Warning
Before starting work on the pump, make sure that the
power supply has been switched off for at least 5
minutes. Make sure that the power supply cannot be
accidentally switched on.
Warning
Make sure that the escaping water does not cause
injury to persons or damage to the equipment.
Warning
If the pump is used for a liquid which is injurious to
health, it will be classified as contaminated. In such
cases, the proper precautions must be taken to avoid
injury to health when operating or working on the
pump.
24.1 Maintenance
24.1.1 Pump
The pump is maintenance-free.
If the pump is to be drained for a long period of inactivity, inject a
few drops of silicone oil on the shaft between the motor stool and
the coupling. This will prevent the shaft seal faces from sticking.
24.1.2 Motor
Check the motor at regular intervals. It is important to keep the
motor clean in order to ensure adequate ventilation. If installed in
a dusty environment, clean and check the pump regularly.
24.2 Service
If Grundfos is requested to service the pump, you must clean it
must before returning it. If you cannot clean the pump properly,
then provide Grundfos with all relevant information about the
pumped liquid.
If the above is not fulfilled, Grundfos can refuse to accept the
pump for service.
Possible costs of returning the pump are to be paid by the
customer.
24.2.1 Integral shaft/coupling
TPE2 and TPE3 pumps have integral shaft/coupling. We
recommend that you do not remove the motor.
If the motor has been removed, you must remove the motor stool
in order to refit the motor correctly. Otherwise the shaft seal may
be damaged.
24.2.2 Blanking flanges
For twin-head pumps, a blanking flange with a pump housing
gasket is available. See fig. 89.
Fig. 89 Fitting the blanking flange
If one pump requires service, fit the blanking flange to allow the
other pump to continue operating.
TM05 7921 1613
60
Page 61
25. Fault finding
Warning
Before removing the terminal box cover or removing
or dismantling the pump, make sure that the power
supply has been switched off for at least 5 minutes.
Make sure that the power supply cannot be
accidentally switched on.
Warning
Make sure that the escaping water does not cause
injury to persons or damage to the equipment.
FaultCause/remedy
1. The motor does not run when started.a) Supply failure.
b) The fuses are blown.
c) The motor is defective.
2. Motor alarm when the power supply is switched on.a) Supply failure.
b) The cable connection is loose or faulty.
c) The motor winding is defective.
d) The pump is mechanically blocked.
3. Occasional motor alarm.a) The supply voltage is periodically too low or too high.
b) The differential pressure across pump is too low.
4. No motor alarm, but the pump does not run.a) Check the power supply.
b) Check the fuses.
5. The pump performance is not constant.a) The pump inlet pressure is too low.
b) The inlet pipe or pump is partly is blocked by impurities.
c) The pump draws in air.
6. The pump runs but delivers no water.a) The inlet pipe or pump is blocked by impurities.
b) The foot or non-return valve is blocked in closed position.
c) There is a leakage in the inlet pipe.
d) There is air in the inlet pipe or pump.
7. The pump runs backwards when switched off.*a) There is a leakage in inlet pipe.
b) The foot or non-return valve is defective.
c) The foot or non-return valve is blocked in open or partly open
position.
8. Leakage in shaft seal.a) The shaft seal is defective.
9. Noise.a) The pump is cavitating.
b) The pump does not rotate freely (frictional resistance) because of
incorrect pump shaft position.
c) There is resonance in the installation.
d) There are foreign bodies in the pump.
English (GB)
* In twin-head pump installations, the backup pump will often
rotate slowly.
61
Page 62
26. Megging
Caution
English (GB)
Megging of an installation incorporating MGE motors
is not allowed, as the built-in electronics may be
damaged.
27. Technical data, single-phase motors
27.1 Supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Recommended fuse size
Motor size
[kW]
Min.
[A]
0.25 - 0.75610
1.1 - 1.51016
Standard as well as quick-blow or slow-blow fuses may be used.
27.2 Leakage current
Earth leakage current less than 3.5 mA (AC supply).
Earth leakage current less than 10 mA (DC supply).
The leakage currents are measured in accordance with EN
61800-5-1:2007.
28. Technical data, three-phase motors
28.1 Supply voltage
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Recommended fuse size
Motor size
[kW]
0.25 - 1.166
1.5 - 2.2610
Standard as well as quick-blow or slow-blow fuses may be used.
28.2 Leakage current
Motor size
[kW]
0.75 - 2.2
supply voltage less than 400 V
0.75 - 2.2
supply voltage greater than 400 V
The leakage currents are measured in accordance with EN
61800-5-1:2007.
Min.
[A]
Leakage current
[mA]
< 3.5
< 5
Max.
[A]
Max.
[A]
29. Inputs or outputs
Earth reference (GND)
All voltages refer to GND.
All currents return to GND.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in severely
reduced operating reliability and motor life:
Relay 1:
Maximum contact load: 250 VAC, 2 A or 30 VDC, 2 A.
Relay 2:
Maximum contact load: 30 VDC, 2 A.
GENI terminals: -5.5 to 9.0 VDC or < 25 mADC.
Other input or output terminals: -0.5 to 26 VDC or < 15 mADC.
Digital inputs (DI)
Internal pull-up current > 10 mA at V
Internal pull-up to 5 VDC (currentless for V
Certain low logic level: V
Certain high logic level: V
< 1.5 VDC.
i
> 3.0 VDC.
i
Hysteresis: No.
Screened cable: 0.5 - 1.5 mm
Maximum cable length: 500 m.
Open-collector digital outputs (OC)
Current sinking capability: 75 mADC, no current sourcing.
Load types: Resistive or/and inductive.
Low-state output voltage at 75 mADC: Max. 1.2 VDC.
Low-state output voltage at 10 mADC: Max. 0.6 VDC.
Overcurrent protection: Yes.
Screened cable: 0.5 - 1.5 mm
Maximum cable length: 500 m.
Analog inputs (AI)
Voltage signals:
• 0.5 - 3.5 VDC, AL AU.
• 0-5 VDC, AU.
• 0-10 VDC, AU.
Voltage signal: R
> 100 kΩ at 25 °C.
i
Leak currents may occur at high operating temperatures. Keep
the source impedance low.
Current signal ranges:
• 0-20 mADC, AU.
• 4-20 mADC, AL AU.
Current signal: R
= 292 Ω.
i
Current overload protection: Yes. Change to voltage signal.
Measurement tolerance: - 0/+ 3 % of full scale (max.-point
coverage).
Screened cable: 0.5 - 1.5 mm
Maximum cable length: 500 m (excl. potentiometer).
Potentiometer connected to +5 V, GND, any AI:
Use maximum 10 kΩ.
Maximum cable length: 100 m.
= 0 VDC.
i
2
/ 28-16 AWG.
2
/ 28-16 AWG.
2
/ 28-16 AWG.
> 5 VDC).
i
62
Page 63
Analog output (AO)
Current sourcing capability only.
Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes.
Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (max-point coverage).
2
Screened cable: 0.5 - 1.5 mm
/ 28-16 AWG.
Maximum cable length: 500 m.
Pt100/1000 inputs (PT)
Temperature range:
• Minimum -50 °C (80 Ω/803 Ω).
• Maximum 204 °C (177 Ω/1773 Ω).
Measurement tolerance: ± 1.5 °C.
Measurement resolution: < 0.3 °C.
Automatic range detection (Pt100 or Pt1000): Yes.
Sensor fault alarm: Yes.
2
Screened cable: 0.5 - 1.5 mm
/ 28-16 AWG.
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs
Use Grundfos LiqTec sensor only.
2
Screened cable: 0.5 - 1.5 mm
/ 28-16 AWG.
Grundfos Digital Sensor input and output (GDS)
Use Grundfos Digital Sensor only.
Power supplies (+5 V, +24 V)
+5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC (sourcing only).
• Overload protection: Yes.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC (sourcing only).
• Overload protection: Yes.
Digital outputs (relays)
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
2
Screened cable: 0.5 - 2.5 mm
/ 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos GENIbus protocol, RS-485.
2
Screened 3-core cable: 0.5 - 1.5 mm
/ 28-16 AWG.
Maximum cable length: 500 m.
30. Other technical data
EMC (electromagnetic compatibility)
EN 61800-3.
Residential areas, unlimited distribution, corresponding to CISPR
11, class B, group 1.
Industrial areas, unlimited distribution, corresponding to CISPR
11, class A, group 1.
Contact Grundfos for further information.
Maximum tightening torques for the terminals can be found in
section Torques, page 63.
1.4.3 Line reactors
Maximum line reactor size must not exceed 1.5 mH.
1.4.4 Fuse size/circuit breaker
If a short-circuit occurs, the pump can be used on a mains supply
delivering not more than 5000 RMS symmetrical amperes, 600 V
maximum.
Motor sizeFuse sizeCircuit breaker type/model
0.25 to 2.2 kW25 A25 A / inverse time
Fuses
When the motor is protected by fuses, they must be rated for
480 V. Maximum sizes are stated in the table above.
Motors up to and including 2.2 kW require class K5 UR fuses.
Circuit breaker
When the pump is protected by a circuit breaker, this must be
rated for a maximum voltage of 480 V. The circuit breaker must
be of the "inverse time" type.
The interrupting rating (RMS symmetrical amperes) must not be
less than the values stated in the table above.
1.4.5 Overload protection
Degree of overload protection provided internally by the drive,
in percent of full-load current: 102 %.
66
Subject to alterations.
Page 67
Appendix1
GB: Inlet pressure stated in bar relative pressure (pressure gauge value measured on the suction side of the pump)
BG: bar ( )
CZ: Tlak na sání vyjádený v barech je relativní tlak (hodnota na manometru mená na sací stran erpadla)
DE: Zulaufdruck in bar Relativdruck (Manometerdruck auf der Saugseite der Pumpe gemessen)
DK: Tilløbstrykket angivet i bar relativt tryk (manometerværdi målt på pumpens sugeside)
EE: Rõhk sisendis, antud baarides, on suhteline rõhk (manomeetri näit, mõõdetuna pumba imipoolel)
ES: Presión de aspiración indicada en bar como presión relativa (valor del manómetro medido en la aspiración de la bomba)
FI:Tulopaine ilmoitettuna baareina on suhteellinen paine (painemittarin lukema mitattu pumpun imupuolella)
FR: Pression d'entrée indiquée en bar (valeur mesurée à l'aide d'un manomètre placé sur le côté aspiration de la pompe)
GR: bar ( )
HR: Ulazni tlak u barima relativnog tlaka (manometarski tlak izmjeren na usisnoj strani crpke)
HU: Hozzáfolyási nyomás bar-ban, túlnyomás (nyomásmér mért értéke a szivattyú szívóoldalán)
IT:Pressione di aspirazione indicata in bar (valore misurato con un manometro posto sul lato aspirazione della pompa)
LT:Manometrinis slgis vade bar (manometru matuojama sl
LV:Iepldes spiediens tiek noradts nosactas spiediena mrvienbas, baros (manometra radjumi tiek mrti ska scpus)
NL: Inlaatdruk weergegeven in bar relatieve druk (drukopnemer waarde, gemeten aan de zuigkant van de pomp)
PL: Cinienie na krócu ssawnym pompy wyraone w barach (mierzone manometrem na stronie ssawnej pompy)
PT:Pressão de entrada com a pressão relativa apresentada em bar (ponto de medida na parte de aspiração da bomba)
RO: Presiunea de intrare exprimat în bar ca presiune relativ (valoarea masurat de manometru pe partea de aspiraie a pompei)
RS: Ulazni pritisak je dat u barima relativnog pritiska (manometarska vrednost merena na usisnoj strani pumpe)
SE: Tilloppstrycket angivet i bar relativt tryck (manometervärde mätt på pumpens sugsida)
SI:Vhodni tlak v barih relativni tlak (izmerjena vrednost na sesalni strani rpalke)
SK: Vstupný tlak uvedený v baroch relatívneho tlaku (hodnota na manometru meraná na sacej strane erpadla)
AR: )
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Centro
Industrial Garin
1619 Garín Pcia. de B.A.
Phone: +54-3327 414 444
Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Zmaja od Bosne 7-7A,
BH-71000 Sarajevo
Phone: +387 33 592 480
Telefax: +387 33 590 465
www.ba.grundfos.com
e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo Branco,
630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: bulgaria@grundfos.bg