Grundfos.bk Page 1 Wednesday, September 3, 2008 1:36 PM
Shower pump
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Page 2
Grundfos.bk Page 2 Wednesday, September 3, 2008 1:36 PM
Declaration of Conformity
We Grundfos declare under our sole responsibility that the products SSL,
STL, STC, SSR, STR, SSP, STP, SSN and STN, to which this declaration
relates, are in conformity with the Council Directives on the approximation
of the laws of the EC Member States relating to
— Machinery (98/37/EC).
— Electrical equipment designed for use within certain voltage limits
(2006/95/EC).
Standards used: EN 60335-1: 2002 and EN 60335-2-41: 2003.
— Electromagnetic compatibility (2004/108/EC).
Bjerringbro, 20th December 2007
Svend Aage Kaae
Technical Director
2
Page 3
Grundfos.bk Page 3 Wednesday, September 3, 2008 1:36 PM
CONTENTS
Page
1.Symbols used in this document3
2.General3
2.1Type key3
3.Important instructions3
4.Positioning the pump4
4.1Negative head4
5.Hot-water cylinder connections4
6.Cold-water supply4
7.Connecting the pump4
7.1STC, STR, SSR, STL and SSL pumps 4
8.Electrical connections5
8.1Electrical connection, 1 x 230 V, 50 Hz5
8.2Electrical connection, low-voltage pumps (STL, SSL and
STL 2.0 CN)5
9.Before using the pump5
10.Negative-head pumps 6
10.1 General6
10.2 Dry-running protection6
10.3 Connecting the pump6
10.4 Installation instructions6
10.5 Pressure and flow control6
10.6 Operating instructions6
10.7 Maintenance6
11.Fault finding chart7
11.1 Fault finding, negative-head pumps (STN, SSN and STL
2.0 CN)8
12.Technical data9
13.Service11
14.Disposal11
Warning
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
1. Symbols used in this document
Warning
If these safety instructions are not observed,
it may result in personal injury!
If these safety instructions are not observed,
Caution
Note
it may result in malfunction or damage to the
equipment!
Notes or instructions that make the job easier
and ensure safe operation.
2. General
These installation and operating instructions apply to the
Grundfos Shower Pumps, types STL, SSL, STC, STR, SSR, STP, SSP, STN and SSN.
For supplementary instructions regarding negative-head pumps,
see section 10. Negative-head pumps.
Your shower pump has been designed, manufactured and
carefully tested in England.
If correctly installed and not misused, it will give many years of
reliable service.
A shower pump installation requires a cold-water storage tank
and a hot-water cylinder. See fig. 2, page 12.
Low-voltage shower pumps
All transformers are fitted with auto-resetting thermal cut-outs.
If the transformer overheats for any reason, the thermal cut-out
will switch the pump off. The cut-out will automatically switch the
pump on again when the transformer has cooled down.
For the STL 2.0 CN pumps, also read the instructions in section
10. Negative-head pumps.
Please dispose of any packaging supplied with
Note
this pump in an environmentally friendly and
legal manner.
2.1 Type key
ExampleSTP2.0B
S: Shower pump range
T: Twin impeller
S: Single impeller
P: Positive head
N: Negative head
L: Low voltage
C: Centrifugal
R: Regenerative
Maximum head [bar]
Material:
B: Brass
C: Composite
CN: Composite, negative head
3. Important instructions
Do not connect the pump directly to the water
mains supply.
Caution
Note
• A supply head of at least 2 metres is recommended.
• Non-return valves
Do not fit non-return valves in the suction line to the pump.
Make sure that the pump can vent back to the supply tank.
• STC, STR, SSR, STL and SSL pumps
The strainers supplied with the pump must be used on suction
connections. See fig. 1, page 4.
• Push-fit connections (SSN, SSP, STN and STP pumps)
The pump suction and discharge ports are fitted with push-fit
connections. The flexible hoses supplied with the pump must
be used.
Make sure that each hose connection is fully inserted to a
minimum depth of 33 mm.
The hot-water supply to the pump suction port should be
connected from the first outlet from the hot-water cylinder
expansion pipe, i.e use a Surrey flange.
• Disconnecting hose
To disconnect the "push-fit" hose, firmly push down the white
or grey retaining ring, while pulling out the hose.
• No solder flux
Do not allow any solder flux to come into contact with any of
the plastic parts of the pump.
• Do not let the pump run dry
Purge with water thoroughly for 5 minutes before running the
pump.
• Test the system
After completing installation, the whole system must be
thoroughly tested – operating both hot and cold water at
maximum flow.
Maximum hot-water temperature setting must not exceed
60 °C (140 °F) in accordance with BS 6700: 2006.
Finally check that each connection is watertight and not
leaking.
The pump cannot normally be used with
combination boilers.
Make sure that no foreign particles (such as
solder, dust, etc.) are allowed to enter the pump.
The pump cannot operate if the level of the water
in the cold-water storage tank is below the level
of the pump.
3
Page 4
Grundfos.bk Page 4 Wednesday, September 3, 2008 1:36 PM
4. Positioning the pump
Select a position for installing the pump which
Note
Minimum inlet pressure: 2 metres (recommended).
Keep the pump as close as possible to the source of hot and cold
water.
For optimum performance, ensure
• a good water flow to the pump
• sufficient head
• unrestrictive pipework
• provision to prevent air locks.
Place the pump in a well-ventilated location, e.g. on the floor of
the airing cupboard.
Caution
Caution
The pump must be mounted horizontally with discharge ports
vertically upwards to ensure correct operation of the flow
switches.
To reduce noise, we recommend the pump be mounted on a
small concrete foundation of approximately 225 x 225 mm and
40-50 mm thick.
Connect the pump and shower system as shown in fig. 2,
page 12.
To achieve 0.5 l/min. to turn the flow switches on, there must be a
minimum height between the water level in the cold-water storage
tank and the shower outlet of approximately 250 mm. See fig. 2,
page 12.
The pump must be installed in accordance with the Water Supply
(Water Fittings) Regulations 1999.
For installation within a bathroom, locate the pump in accordance
with the IEE Wiring Regulations seventeenth edition (BS 7671:
2008) Part 6 Section 601 for a shower pump with an IPX2
enclosure. The pump must be positioned at least 0.6 metres
horizontally or 3 metres vertically away from any bath, shower
tray or basin.
affords easy access for subsequent servicing
and maintenance.
Do not cover the pump, otherwise the motor will
overheat.
The pump must be placed in a frost-free location.
Warning
The pump may be fitted under a bath, providing
this space is only accessible through the use of
a tool. If in doubt, consult the Wiring Regulations.
6. Cold-water supply
Do not connect the pump directly to the water
Caution
The cold-water supply to the pump must be connected using
22 mm pipe to the cold-water storage tank. See fig. 2, page 12.
The tank connector should be positioned at least 25 mm (1”)
lower than the cold-water supply to the hot-water cylinder to
prevent the supply of hot water only.
mains supply.
Do not use any jointing compounds or tape.
7. Connecting the pump
Caution
For ease of installation, subsequent servicing and cleaning of
strainers, full-bore isolating gate valves should be fitted in the
pump suction and discharge ports.
Note
The flexible hoses supplied with the pump must be used for
connecting the pump to the pipework. Use of these hoses will
ensure strain- and vibration-free watertight connections. The
maximum bend angle should not exceed 45 °.
After initial installation, run the pump for a few minutes, switch off,
drain down and clean the suction strainers.
For SSN, SSP, STN and STP pumps, remove the suction hose
from the pump, and the strainer basket can be removed by hand
or with long-nosed pliers.
Line up pipework, and fit hoses to the pump before connecting to
pipes. Position pipework accurately so that the pump is not
subject to mechanical strain.
Plastic nuts should be finger-tight plus 1/4 turn. The nuts should
be retightened after hot water has been pumped for the first time.
Note
7.1 STC, STR, SSR, STL and SSL pumps
The strainers supplied with the pump must be fitted to the pump
suction connections only with the wire dome towards the pump.
See fig. 1.
Do not use any jointing compounds or tape.
Isolating valves greatly assist draining down,
strainer cleaning and refilling, which will result in
much lower service costs.
Do not bend hoses as this will cause restriction
of flow.
4.1 Negative head
If the water level in the cold-water storage tank is below the level
of the shower outlet, this is called a negative-head system. To
enable the pump to operate, a negative-head pump must be
used. See section 2.1 Type key.
If the pump is positioned above the outlet of
Note
the hot-water storage cylinder, ensure that the
pipework to the pump from the cylinder has a
downward loop. This will help prevent air locks.
5. Hot-water cylinder connections
Caution
The use of a Surrey flange (see fig. 2, page 12) is recommended
to ensure a free-flowing supply of air-free hot water.
The hot-water supply may be taken directly from the top of the
hot-water cylinder, but entrapped air may cause problems.
22 mm copper pipe should be used to ensure an adequate flow to
the pump. Where high flows are expected, 28 mm is
recommended.
Do not use any jointing compounds.
Discharge
Suction
Fig. 1 Fitting the strainer
Suction
strainer
Discharge
connection
TM04 02 0203 5107
4
Page 5
Grundfos.bk Page 5 Wednesday, September 3, 2008 1:36 PM
8. Electrical connections
Warning
The pump must be earthed.
The pump must be connected to an external
mains switch with a contact separation gap
of at least 3 mm in each pole.
The pump must be connected to a 230 V, 50 Hz,
supply with a switched spur fused at 5 A
(10 A on models STP 4.0 B and STN 4.0 B).
Metal pipes must be earthed by the use of
earthing clamps to BS 951 and 4 mm earthing
wire.
Complete all pipework before making electrical
Caution
If in doubt, consult a qualified electrician or call your local
electricity board engineer.
8.1 Electrical connection, 1 x 230 V, 50 Hz
Observe colour coding as follows:
• Brown to terminal L.
• Yellow/green to terminal E (PE).
Ensure that the earth lead is at least as long as the other two
leads.
• Blue to terminal N (neutral).
Insert the lead fully into the terminal connector and tighten the
screw firmly. Ensure that the connection is secure. Be sure to
tighten the cable restraint.
Ensure compliance with IEE Regulations. In the interests of
safety, it is recommended that a residual current device (RCD)
be installed in the supply circuit.
The pump switch should be left "on" at all times for normal
operation of the system.
connections.
Do not allow any water to enter into the electric
terminal box.
Warning
Do not operate the pump without terminal box
cover in place.
Ensure compliance with IEE Regulations.
Observe colour coding as follows:
• Brown to terminal L.
• Blue to terminal N.
For normal operation of the shower, the transformer can be left
permanently switched on – very little power is used when the
pump is not running.
Copper pipes should have supplementary earth bonding. Where
the earth continuity has been broken, the pump suction and
discharge pipework should be connected with earthing clamps to
BS 951 and 4 mm earthing wire.
9. Before using the pump
Warning
Do not let the pump run dry.
Purge water thoroughly through the system
before switching on the electricity supply to
the pump.
Do not switch on the electricity supply.
1. Turn on the water supply. Allow the system to fill.
2. Immediately inspect for any leaks.
3. With pump not running, allow maximum water flow, for
example remove handset from shower hose, letting the
shower hose hang into the shower tray or bath. Operate
maximum hot and cold flow for at least 2 minutes, to flush out
all debris and ensure air is thoroughly purged from the system.
4. Switch on the electricity supply to the pump. Again operate the
pump in both full hot and cold modes for about 2 minutes.
5. With the pump operating, carefully inspect again for any leaks
from all connections on both hot- and cold-feed pipes to the
pump and to the system.
After hot water has been run for several minutes, check all
hot-water connections and make sure that there are no leaks.
6. The first few times the pump is used, the insulating varnish
used on the pump motor may give off an odour. This is
perfectly normal and will diminish with use.
The low-voltage pump has added electrical protection via a safety
isolating transformer. See fig. 3, page 13, or fig. 4, page 14.
For installations where the pump has to be placed in the
bathroom (for example under the bath), we recommend that
the safety isolating transformer is placed outside the bathroom or
shower area.
The low-voltage leads from the transformer must be connected to
the two terminals marked "T" in the terminal box. As the supply is
AC, the leads can be connected to either terminal on the pump.
The low-voltage pump installation kits are supplied with 3 metres
of connecting lead. The connecting leads between the pump and
the isolating transformer can be extended up to about 15 metres.
Use 1.0 mm cable.
The safety isolating transformer must be connected to a
230-240 V, 50 Hz, supply voltage with a switched spur fused
at 5 A. The switch must have a double-pole disconnection with
a separation gap of at least 3 mm. See fig. 3, switched spur.
Do not connect the pump directly to 240 V.
Electrical hazard will result and the motor will be
irreparably damaged.
Warning
Do not locate 230-240 V connections, plugs or
switches within the "wet" area in accordance
with IEE Regulations.
5
Page 6
Grundfos.bk Page 6 Wednesday, September 3, 2008 1:36 PM
10. Negative-head pumps
Pump types: STN, SSN and STL 2.0 CN.
10.1 General
Automatic negative-head shower pumps are designed to operate
automatically in installations where the pumped system outlets
are above the stored water level.
Shower pumps, types STN and SSN, feature independent
pressure and flow controls, with built-in non-return valves and
stainless-steel expansion tanks in each pump end. This system
ensures complete hot- and cold-water system isolation with
stable control over a very wide flow range.
The pump is fitted with dry-running protection. Should the water
supply fail, the pump will stop to prevent damage to the shaft
seals.
10.2 Dry-running protection
STN, SSN and STL 2.0 CN negative-head pumps feature dryrunning protection to avoid damage to seals caused by water
starvation. This condition is possible if there is insufficient stored
water or the pump strainers are blocked.
If the pump runs for 60 seconds with an insufficient water supply,
the pump will stop and "lock out".
Resetting the "lock out"
To reset the pump, switch the electricity supply off for
10 seconds.
When the electricity supply is switched on again, the pump will
run for a few seconds to recharge the tanks. If it continues to run
and there is no demand, this would indicate that one of the
following is still present:
• No water in the system.
• Blocked strainer.
• Air which has not yet cleared.
Caution
10.3 Connecting the pump
Caution
For the pump to work correctly, it must have:
• Air-free supply of hot water – the use of Surrey flanges is
recommended.
• 22 mm (minimum) feed pipes, gate valves and flexible hoses.
• Minimum head of water to supply the pump 2 metres (6'6").
However, the STN and SSN pumps will function with a supply
head as low as 600 mm (2 ft), providing the water make-up
system has unrestrictive pipework, and provision is made to
avoid air locks.
• Maximum hot-water temperature of 60 °C conforming to
BS 6700: 2006.
• Maximum static head of 8 m, i.e. the highest point of the
system must be less than 8 m above the pump. See fig. 4,
page 14.
10.4 Installation instructions
• The hot-water cylinder must have an expansion pipe or be
fitted with a vent pipe connected to the pump hot-water supply,
to allow air from the hot-water cylinder to escape.
Excessive air entering the pump will cause faulty operation
and damage to the pump seals which will cause serious water
leaks.
• Feed pipes, hot and cold, must be minimum 22 mm with
22 mm service isolating gate valves. The flexible hoses
supplied must be used. The hoses must be connected without
kinks which will restrict water flow. The maximum bend angle
is 45 °.
Continued dry running will lead to overheating of
the shaft seals and eventually to a water leak.
Do not connect the pump directly to the water
mains supply.
• Ensure an adequate head of water and non-restrictive makeup pipework.
Inadequate feed head will cause pump cavitation, unstable
water temperature, noise and ultimately pump and seal
damage.
• All air must be thoroughly purged from the system. If air is
present in the pump, it will be unable to generate sufficient
pressure to operate the pressure switch. This will cause the
pump to run or pulse continuously.
• Lavatory cisterns
If the pump is to supply a lavatory cistern, certain precautions
should be taken to avoid frequent starting and stopping of the
pump due to low flow rates.
If possible, best practice is to supply the cistern from the
mains water supply. Failing this, a "Torbeck" or equilibrium
valve is recommended. If either of these are not possible, the
following instructions should be followed:
– A: The pump is supplied with two expansion or pressure
tanks. They have capacities of 500 ml and 160 ml.
The larger tank must be used on the cold side of the
pump.
– B: The cistern filling pipework must be as free-flowing as
possible with all flow restrictors removed.
It is possible to change the tanks from one side of the pump
to the other. When doing so, take care to ensure that none
of the fibre washers are lost.
• Washer dryers
Only brass pumps must be used for these applications.
10.5 Pressure and flow control
Shower pumps for negative-head applications are controlled by
both water pressure and water flow.
Twin-impeller pumps incorporate two separate pressure and flow
control systems, one on each pump end, ensuring complete
isolation of hot- and cold-water systems and consistent operation
over a wide range of unbalanced flow rates.
The control system manifold includes an integral non-return valve
to maintain system pressure when water is not flowing.
Operation
The pressure switches start the pump on falling pressure.
The switch point is factory-set.
It is important that the total head on the pump
Note
Once the pump has been started by the pressure switches, the
flow switches maintain the pump running, providing the flow rate
is above 0.4 l/min. When the flow rate drops below 0.4 l/min. or
the demand is turned off, the pump will stop after first running on
for 3 seconds to recharge the pressure tanks.
is less than 8 metres. Otherwise the pressure
switch can never operate and hence the pump
will fail to start.
10.6 Operating instructions
Taps and valves used on the "pressure system" must be fully
turned off when not in use.
10.7 Maintenance
Washers and seals must be replaced when necessary to prevent
leaks or drips.
Any leak or drip will cause the pump to operate periodically, the
frequency dependent on the rate of the leak.
Tank air-pressure setting
The pressures are factory-set. In the event of a leak, they should
be set as follows:
The smaller tank (160 ml) should be set at a pressure between
0.9 and 1.0 bar. The larger tank (500 ml) should be set at a
pressure between 0.5 and 0.6 bar.
In certain applications, e.g. steam cabinets, it
Note
For further information regarding general maintenance and
service, see section 13. Service.
may be necessary to increase the pressure.
Consult the appliance manufacturer.
6
Page 7
Grundfos.bk Page 7 Wednesday, September 3, 2008 1:36 PM
11. Fault finding chart
Before starting work on the pump, make sure that the electricity supply has been switched off and that it cannot be
accidentally switched on.
FaultPossible causeRemedy
1. The pump fails to start. a) The electricity supply is switched off.Switch on the electricity supply.
b) The fuses are blown.Replace the blown fuses. If the new ones blow too,
the electric installation should be checked.
c) The built-in thermal protection has switched
off the motor.
d) Isolating valves are closed.Open the isolating valves.
e) Strainers are blocked.Close the service isolating gate valves, clean the
f) Pump installed with non-vertical discharge
ports (flow switches).
g) Insufficient water flow, below 0.5 l/min. Increase the water flow to at least 0.5 l/min.
2. The flow from the
shower drops.
3. The pump runs
continuously.
4. The pump pulses.a) The use of other taps in the house may
5. Unstable water
temperature/noisy
pump.
a) Blocked strainers.Clean the pump strainers.
a) A tap or outlet is turned on.Ensure there are no leaks and that all taps and
b) Flow switch or reed switch faulty or
incorrectly set.
c) Air in the system.Vent the system.
d) The float in the flow switch is stuck in the
up (on) position.
cause the pump to start momentarily.
a) Air entering the pump, most commonly from
the hot-water cylinder.
b) Too high water temperature.Reduce hot-water temperature. The maximum
c) Debris caught in the impeller casing. Remove debris.
The thermal protection resets automatically within
1 to 2 hours.
strainers and re-open the service isolating gate valves.
The pump must be installed with vertical discharge ports
(flow switches).
appliances are off.
Adjust or replace as appropriate.
Make sure that the flow switch can operate correctly and
there is no debris in the flow switch.
Contact your installer.
Fit a Surrey flange and study the pipework layout.
There should be no high points where air can collect.
recommended hot-water temperature setting is 60 ºC
(140 ºF).
7
Page 8
Grundfos.bk Page 8 Wednesday, September 3, 2008 1:36 PM
Before starting work on the pump, make sure that the electricity supply has been switched off and that it cannot be
accidentally switched on.
FaultPossible causeRemedy
1. The pump fails to start. a) The electricity supply is switched off.Switch on the electricity supply.
b) The fuses are blown.Replace the blown fuses. If the new ones blow too, the
electric installation should be checked.
c) The built-in thermal protection has switched
off the motor.
d) Isolating valves are closed.Open the isolating valves.
e) Strainers are blocked.Close the service isolating gate valves, clean the
f) Pump installed with non-vertical discharge
ports (flow switches).
g) Dry-running protection operated. Switch off the electricity supply for 10 seconds to reset.
2. The flow from the
shower drops.
3. The pump runs
continuously.
4. The pump pulses.a) The use of other taps in the house may
5. Pump stops when there
is a demand.
6. Pump hunts when
shutting down.
7. Pump hunts when
starting up.
a) Blocked strainers.Clean the pump strainers.
a) A flow demand still exists.Check the installation for leaks.
b) Flow switch or reed switch faulty or
incorrectly set.
c) Faulty pressure switch.Check the pressure switch.
d) The float in the flow switch is stuck in the
up (on) position.
cause the pump to start momentarily.
b) Leaks in the system.Check the system for leaks.
c) Faulty non-return valve.Check the non-return valves and replace, if necessary.
a) Flow demand below 0.4 l/min.Increase the flow demand.
b) Flow switch or reed switch faulty.Replace the flow switch or reed switch.
a) Incorrect tank air-pressure setting.Adjust the tank air-pressure setting.
b) Insufficient run-on time.Replace the printed-circuit board (PCB).
a) Flow rate below 0.4 l/min.Increase the flow rate.
b) Flow switch or reed switch faulty or
incorrectly set.
The thermal protection resets automatically within
1to2hours.
strainers and re-open the service isolating gate valves.
The pump must be installed with vertical discharge ports
(flow switches).
Adjust or replace as appropriate.
Make sure that the flow switch can operate correctly and
there is no debris in the flow switch.
Contact your installer.
Adjust or replace as appropriate.
8
Page 9
Grundfos.bk Page 9 Wednesday, September 3, 2008 1:36 PM
12. Technical data
Data
Supply voltage1 x 230 V, 50 Hz
Power consumption400 W435 W370 W525 W640 W850 W920 W
Rated current1.7 A1.9 A1.6 A2.3 A2.8 A4.0 A4.3 A
Rating*Continuous operation
Enclosure class **IPX2
Motor2-pole induction
Inlet head (min. - max.)1 to 20 m
Maximum developed pump
head
Maximum operating pressure6 bar
Minimum starting flow rate0.5 l/min.
Length178 mm178 mm230 mm245 mm243 mm266 mm296 mm
Width135 mm135 mm135 mm135 mm135 mm135 mm135 mm
Height225 mm225 mm225 mm225 mm225 mm225 mm225 mm
Weight7.1 kg7.1 kg7.4 kg8.4kg9.9 kg12.0 kg14.5 kg
Sound pressure level (1 m)< 70 dB(A)
* Recommended minimum flow rate: 5 l/min.
** When mounted on a flat horizontal surface.
Data
Supply voltage1 x 230 V, 50 Hz
Power consumption270 W350 W
Rated current1.5 A1.8 A
Rating*20 min. on / 40 min. off
Enclosure class**IPX2
MotorUniversal
Inlet head (min. - max.)2 to 10 m
Maximum developed pump
head
Maximum operating pressure3.0 bar
Minimum starting flow rate0.5 l/min.
Length300 mm305 mm
Width120 mm120 mm
Height185 mm185 mm
Weight2.9 kg3.3 kg
Sound pressure level (1 m)< 70 dB(A)
* At flow rates between 5 and 20 l/min.
** When mounted on a flat horizontal surface.
Grundfos.bk Page 10 Wednesday, September 3, 2008 1:36 PM
Data
Supply voltage (transformer)1 x 230 V, 50 Hz
Transformer output29 VDC37 VDC38 VDC39 VDC39 VDC
Power consumption170 W270 W160 W380 W380 W
Rated current5.4 A7.0 A4.0 A10 A10 A
Rating*
Enclosure class**IPX2IPX2
MotorPermanent magnet, low voltage, DC
Inlet head (min. - max.)2 to 10 m2 to 8 m
Maximum developed pump
head
Maximum operating pressure3 bar
Minimum starting flow rate0.5 l/min.
Length [mm]275 mm275 mm225 mm285 mm285 mm
Width [mm]120 mm120 mm120 mm120 mm215 mm
Height [mm]185 mm185 mm185 mm185 mm256 mm
Weight [kg]4.6 kg5.8 kg4.0 kg6.9 kg8.3 kg
Sound pressure level (1 m)< 70 dB(A)
* At flow rates between 5 and 20 l/min.
** When mounted on a flat horizontal surface.
STL 1.0 CSTL 1.5 CSSL 1.4 CSTL 2.0 CSTL 2.0 CN
20 min. on /
40 min. off
9.5 m15 m14 m19.5 m19.5 m
Pump type
30 min. on / 30 min. off
Data
Supply voltage1 x 230 V, 50 Hz
Power consumption350 W390 W270 W
Rated current1.5 A1.7 A1.2 A
Rating*20 min. on / 40 min. off20 min. on / 40 min. off20 min. on / 40 min. off
Enclosure class**IPX2
Motor4 pole, induction
Inlet head (min. - max.)1 to 10 m
Maximum developed pump
head
Maximum working pressure3 bar
Minimum starting flow rate0.5 l/min.
Length 250 mm250 mm230 mm
Width 140 mm140 mm140 mm
Height 190 mm190 mm190 mm
Weight 5.8 kg5.8 kg5.4 kg
Sound pressure level (1 m)< 70 dB(A)
* Recommended minimum flow rate: 5 l/min.
** When mounted on a flat horizontal surface
STR 1.2 CSTR 1.5 CSSR 1.5 C
12 m15 m16 m
Pump type
10
Page 11
Grundfos.bk Page 11 Wednesday, September 3, 2008 1:36 PM
Data
Supply voltage (transformer)1 x 230 V, 50 Hz
Power consumption400 W435 W525 W640 W850 W920
Rated current1.7 A1.9 A2.3 A2.8 A4.0 A4.3
Rating*Continuous operation
Enclosure class**IPX2
Motor2-pole induction
Inlet head (min. - max.)1 to 8 m
Maximum developed pump
head
Maximum operating pressure6 bar
Minimum starting flow rate0.5 l/min.
Length [mm]178 mm178 mm245 mm243 mm266 mm296 mm
Width [mm]225 mm225 mm225 mm225 mm225 mm225 mm
Height [mm]283 mm283 mm283 mm283 mm283 mm283 mm
Weight [kg]7.6 kg7.6 kg9.7 kg11.3 kg13.3 kg15.8 kg
Sound pressure level (1 m)< 70 dB(A)
• The flexible pump hoses, dependent on water temperature
and mechanical stress, can deteriorate with age. We
recommend that all flexible hoses and connections are
inspected at least every 6 months. Replace as necessary to
prevent leaks.
• If the flow from the shower drops below its normal
performance, it may be necessary to clean the pump strainers.
Blocked strainers are common on initial installation of pumps,
or in new buildings where the use of jointing compounds,
tapes, flux and other debris can be flushed through the
system.
In this event, close the service valves, remove and clean the
strainers. See section 7. Connecting the pump.
• A common cause of poor shower performance is a clogged
shower head/handset, so regular cleaning and descaling is
important – this applies particularly to hard-water areas.
Pump type
14. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
Subject to alterations.
11
Page 12
r
Grundfos.bk Page 12 Wednesday, September 3, 2008 1:36 PM
System vent
Cold-water storage tank
of at least 50 gallon
capacity
Shower outlet
250 mm (10 inches)
below water level
Shower
valve
Cold-wate
supply
min.
22 mm
Expansion pipe
22 mm
Hot-water supply
Surrey
flange
min.
22 mm
service
gate
valves
Hot
Supply to
Full-bore gate valve
Water mains
Cold-water supply to cylinder, min. 22 mm, 28 mm recommended
Hot-water
cylinder
Cold
another shower,
if required
Fig. 2 Installation of STP, SSP, STC and STR pumps
Pump
230 V
switched spur
TM04 0201 5107
12
Page 13
Grundfos.bk Page 13 Wednesday, September 3, 2008 1:36 PM
System vent
Cold-water supply to cylinder, min. 22 mm, 28 mm recommended
Cold-water storage tank
of at least 50 gallon
capacity
Expansion pipe
Hot-water supply
Surrey
flange
Hot-water
min.
22 mm
cylinder
Cold-water
supply
min.
22 mm
Anti-scald valve
(optional)
Shower
valve
Low-voltage
transformer
Shower outlet
250 mm (10 inches)
below water level
(Except STL 2.0 CN)
22 mm
service
gate
valves
Hot
Supply to
another shower,
Cold
if required
Min. 2 metres (6 ft. 6 in.)
max. 10 metres (33 ft)
supply head from water
level to pump suction port
Water mains
Full-bore gate valve
Fig. 3 Installation of STL and SSL pumps
230 V
switched spur
Pump
TM04 0202 5107
13
Page 14
Grundfos.bk Page 14 Wednesday, September 3, 2008 1:36 PM
Shower
valve
Max.
8 m
Cistern
Basin
Bath
System vent
Negative
Cold-water storage tank
of at least 50 gallon
capacity
Hot-water supply
min.
Surrey
22 mm
flange
Cold-water
supply
min.
22 mm
22 mm
service
gate
valves
Hot
Cold
Supply to another shower,
bath or basin, if required
Positive
Hot-water
cylinder
Min. 22 mm
Water mains
230 V switched spur
Low-voltage pumps must be
connected via transformer only
Fig. 4 Installation of STN, SSN and STL 2.0 CN pumps
Pump
TM04 0200 5107
14
Page 15
Grundfos.bk Page 15 Wednesday, September 3, 2008 1:36 PM
Argentina
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Lote
34A
1619 - Garin
Pcia. de Buenos Aires
Phone: +54-3327 414 444
Telefax: +54-3327 411 111
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Paromlinska br. 16,
BiH-71000 Sarajevo
Phone: +387 33 713290
Telefax: +387 33 231795
Brazil
Mark GRUNDFOS Ltda.
Av. Humberto de Alencar Castelo
Branco, 630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015