Grundfos S2, S3, S4, ST Installation And Operating Instructions Manual

S pumps, ranges 72-74-78
S2, S3, S4, ST 55-520 kW
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
English (GB)
English (GB) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
2. General description
This booklet includes instructions for installation, operation and maintenance of Grundfos submersible sewage and wastewater S-range pumps with motors of 55 to 520 kW.
Fig. 1 S pump, range 72
1. Symbols used in this document
2
2. General description
2
2.1 Applications
3
2.2 Potentially explosive environments
3
2.3 Operating conditions
4
2.4 Sound pressure level
4
3. Identification
5
3.1 Type key
5
3.2 Nameplates
6
3.3 Approval plates, range 72
6
3.4 Ex certification and classification
6
4. Safety
7
5. Transportation and storage
7
5.1 Lifting the pump
7
5.2 Raising pump to upright position
9
5.3 Storage
10
6. Installation
10
6.1 Installation types
10
6.2 Start and stop levels
12
6.3 Submerged installation on auto-coupling
12
6.4 Column pipe installation
12
6.5 Dry installation
13
7. Motor protection
14
7.1 IO 113
14
7.2 SM 113
14
7.3 Switches and sensors
14
8. Electrical connection
16
8.1 Cross-sections for power cables
16
8.2 Wiring diagram for sensors
17
8.3 Frequency converter operation
17
9. Startup
18
9.1 Checking the direction of rotation
18
10. Maintenance and service
19
10.1 Oil check and oil change
19
10.2 Inspection and adjustment of impeller clearance
20
10.3 Contaminated pumps
22
11. Fault finding chart
23
12. Disposal
23
Warning Prior to installation, read these installation and
operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
Warning If these safety instructions are not observed,
it may result in personal injury.
Warning These instructions must be observed for
explosion-proof pumps. We recommend that you also follow these instructions for standard pumps.
Warning If these instructions are not observed, it may lead
to electric shock with consequent risk of serious personal injury or death.
Warning The surface of the product may be so hot that
it may cause burns or personal injury.
Warning The sound pressure level is so high that hearing
protection must be used.
Caution
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Note
Notes or instructions that make the job easier and ensure safe operation.
TM03 1507 1110
Pos. Description
1 Inlet 2Outlet 3 Power supply cables 4 Control cable 5 Lifting bracket 6 Terminal box 7 Submersible motor 8Pump
17 Air vent valve
English (GB)
2.1 Applications
S pumps, range 72, 74 and 78, are designed for the pumping of sewage and wastewater in a wide range of municipal and industrial applications.
Depending on the installation type, the pumps can be used for submerged or dry, horizontal or vertical, installation.
Maximum solids size: 90-145 mm, depending on impeller type.
2.2 Potentially explosive environments
In potentially explosive environments, use only Ex-approved apparatus. All range-72 pumps are available as Ex versions. Range 72 Ex pumps can be used in hazardous areas classified as Zone 1 or Zone 2.
Warning Special conditions for safe use of S pumps,
range 72 Ex, 74 and 78:
1. Make sure the moisture switches and thermal switches are connected in two separate circuits and have separate alarm outputs (motor stop) in case of high humidity or high temperature in the motor.
2. Bolts used for replacement must be class A4-80 or A2-80 according EN/ISO 3506-1.
3. The flame path gaps of the motor are specified by the manufacturer and are narrower than standard. Please see the manufacturer's installation, operation and maintenance document for guidance.
4. During operation, the cooling jacket, when fitted, must be filled with pumped liquid.
5. The level of pumped liquid must be controlled by level switches connected to the motor control circuit. The minimum level depends on the installation type and is specified in these installation and operating instructions.
6. Dry-running is not allowed.
7. Make sure the permanently attached cables are suitably mechanically protected and terminated in a suitable terminal board.
8. The sewage pumps have an ambient temperature range of 0-40 °C and a maximum process temperature 40 °C.
9. The control unit must protect the WIO against the short circuit current of the supply to which it is connected. The maximum current from the control unit must be limited to 350 mA.
10.The maximum submersion depth is 20 m.
Warning Special conditions for safe use of WIO sensor
1. The control unit must protect the sensor against the short-circuit current of the current supply to which it is connected.
2. The sensor must be installed in such a way that danger of mechanical impact is avoided.
3. The WIO sensor must not be used in oil with a flash point below 250 °C.
4. The WIO sensor is approved according to EN/IEC 60079-18:2004. In Ex and IEC Ex applications, the maximum current supplied to the sensor must be limited to 350 mA according to EN/IEC 60079-18:2004.
Installation
type
Description Accessories
S
Sewage pump without cooling jacket for submerged installation on auto coupling.
Auto coupling
C
Sewage pump with cooling jacket for submerged installation on auto coupling.
Auto coupling
D
Sewage pump with cooling jacket for dry vertical installation.
Base plate for vertical installation
H
Sewage pump with cooling jacket for dry horizontal installation.
Base plate for horizontal installation
ST
Sewage pump without cooling jacket for installation in vertical column pipe.
Seat ring
Note
Ranges 74 and 78 are not available with Ex approval.
English (GB)
2.3 Operating conditions
pH value
All pumps can be used for pumping liquids with a pH value between 4 and 10.
Liquid temperature
The allowed temperature is 0-40 °C.
Ambient temperature
The allowed temperature is 0-40 °C.
Density and viscosity of pumped liquid
Density: 1000 kg/m
3
.
Kinematic viscosity: 1 mm
2
/s (1 cSt).
2.3.1 Installation depth
The maximum submersion depth is 20 m.
2.3.2 Level of pumped liquid
To avoid air being sucked into the pump and to ensure adequate cooling of the motor during operation, the following minimum requirements must be met:
Installation type S: For S1 operation (continuous operation), the pump must always be covered by the pumped liquid to the top of the motor. See fig. 2. See also section 9.1 Checking the direction
of rotation.
Installation type C: The pump housing must always be covered by the pumped liquid.
Fig. 2 Stop levels
Installation types D and H: See section 6.5 Dry installation.
Installation type ST: The liquid level must be at least 900-1100 mm above the pump inlet. See fig. 21.
2.3.3 Pressure version
See section 4. Safety.
2.3.4 Operating mode
The pumps are designed for continuous operation with the maximum number of starts per hour stated in the table below:
2.3.5 Enclosure class
IEC IP68.
2.4 Sound pressure level
Note
In special situations the temperature of the pumped liquid may be higher, if the motor is not fully loaded.
If necessary, contact the nearest Grundfos company or service workshop.
Warning Explosion-proof pumps must never pump liquids
with a temperature higher than 40 °C.
Note
In special situations the ambient temperature may be higher, if the motor is not fully loaded.
If necessary, contact the nearest Grundfos company or service workshop.
Warning For explosion-proof pumps, the ambient
temperature on the installation site must be in the range between 0 and 40 °C.
Note
When pumping liquids with a density and/or a kinematic viscosity higher than the values stated above, use motors with correspondingly higher outputs.
Warning An Ex motor must always be fully submerged
during operation.
Warning Install an additional level switch to ensure that
the pump is stopped in case the stop level switch is not operating.
Warning Installation type S and C pumps must always be
fully submerged in the pumped liquid to be Ex protected.
Note
For installation type C pumps, the air vent valve must always be open, also during operation. See fig. 1.
Installation types C and S
TM03 1626 0208
Warning During operation, the cooling jacket must be
filled with pumped liquid to ensure sufficient cooling. Before the first startup and after long standstill periods, the air must be evacuated from the cooling jacket through an air-vent valve.
S pump, range Starts per hour
72 15
74 and 78 10
Warning Depending of the installation type the sound
pressure level of the pump can be higher than 70 dB (A). Use hearing protection when working nearby such an installation in operation.
Ex pumps, installation type S
Installation type C
English (GB)
3. Identification
3.1 Type key
All S pumps, ranges 72, 74 and 78, described in this booklet are identified by the type designation stated in the confirmation of order and other documentation supplied with the pump.
Please note that the pump type described in this booklet is not necessarily available in all variants.
Code Example S 2 .90 .250 .2250 .4 .72 S .C .496 .G .N .D .5 13 .Z
S
ST
Pump type:
Grundfos sewage and wastewater pump Multi-channel impeller pump installed in a column pipe
2 3 4
Impeller type:
Two-channel Three-channel Four-channel
Pump passage:
Maximum solids size [mm]
250
[ ]
Pump discharge, S-type:
Nominal diameter of pump discharge port [mm]
Pump discharge, ST-type:
Nominal diameter of column pipe [mm]
Output power, P2:
P2 = Code number from type designation / 10 [kW]
4 6
8 10 12 14
Number of poles:
4-pole motor 6-pole motor 8-pole motor 10-pole motor 12-pole motor 14-pole motor
72 74 78
Pump range:
Range 72 Range 74 Range 78
S
H M
L
E
F
Pressure version:
Super high High Medium Low Extra low Super low
S
C D H
Installation type:
Submerged installation without cooling jacket Submerged installation with cooling jacket Dry installation with cooling jacket Dry horizontal installation with cooling jacket
Impeller diameter (mean):
[mm]
G Q
Material code for impeller, pump housing and stator housing:
Cast iron impeller, pump housing and stator housing Stainless steel impeller, DIN W.-Nr. 1.4408
N
Ex
Pump version:
Non-explosion-proof pump Pump with explosion-proof motor
B
D
Sensor version:
S pump with built-in SM 113 module. PTC sensors are connected directly to IO 113 or other PTC relay. S pump without built-in SM 113 module
5
6
Frequency:
50 Hz 60 Hz
11 13 18 1G 1B 1D
11 1G 1H
Voltage and connection:
50 Hz
3 x 400 / 690 V Y/D 3 x 415 / 719 V Y/D 3 x 380-400 / 660-690 V Y/D 3 x 380 / 660 V Y/D 3 x 400-415 / 690-719 V Y/D 3 x 380-415 / 660-719 V Y/D
60 Hz:
3 x 575 / (996) V Y/D 3 x 380 / 660 V Y/D 3 x 460 / (797) V Y/D
Z Custom-built products
English (GB)
3.2 Nameplates
Fig. 3 Pump nameplate
3.3 Approval plates, range 72
Fig. 4 Approval plates of explosion-proof S-pumps, range 72
The approval plate gives the following details:
3.4 Ex certification and classification
The range 72 Ex-pumps have an EC-type Examination Certificate issued by Baseefa Ltd.
The certified pumps (Ex-pumps) are supplied with an approval plate fixed in a visible place close to the nameplate.
Figure 4 shows the approval plates for range 72 pumps equipped optionally with the motors classified to T3 or T4 temperature class.
TM06 1781 2514 - TM06 0370 5313
Pos. Description
1 Type designation 2 Product number 3 Serial number 4 Maximum head [m] 5 Maximum installation depth [m] 6 Number of phases 7 Voltage, delta connection 8 Voltage, star connection
9 Rated power input [kW] 10 Power factor 11 Production code [YYWW] 12 Production number 13 Maximum liquid temperature [°C] 14 Maximum flow rate [l/s] 15 Enclosure class 16 Frequency [Hz] 17 Rated speed 18 Current, delta connection 19 Current, star connection 20 Rated power output P2 21 Insulation class 22 Weight 23 Place of production
1
2
3
4
5
6
7
8
9
10
11
12
23
13
14
15
16
17 18
19
20
21 22
12
22
23
TM06 0916 1214 - TM06 0917 1214
CE CE mark Baseefa 1180 ATEX-notified body identification number
EU ex symbol II Equipment group (II = non-mining) 2 Equipment category (high protection) G Type of explosive atmosphere (G = Gas)
Ex
Explosion-proof motor according to European
standard b Control of ignition sources c Constructional safety d Flameproof IIB Gas group (Ethylene)
T3
Maximum surface temperature of the motor is
200 °C
T4
Maximum surface temperature of the motor is
135 °C Baseefa Certificate number Type 72X2254 (example) No. Serial number PC Production code (year/week)
72
Direct drive, 50 or 60 Hz CE 1180 II 2 G Ex bcd IIB T4 Frequency converter
drive
CE 1180 II 2 G Ex bcd IIB T3
English (GB)
4. Safety
For safety reasons, all work in pits must be supervised by a person outside the pump pit.
Pits for submersible sewage and wastewater pumps contain sewage and wastewater with toxic and/or disease-causing substances. Therefore, all persons involved must wear appropriate personal protective equipment and clothing, and all work on and near the pump must be carried out under strict observance of the hygiene regulations in force.
5. Transportation and storage
The pump is supplied from factory on a steel transportation stand in horizontal position. Pump and stand is protected by a special cover.
Fig. 5 Covered pump in transportation stand
The pump is equipped with a label indicating the centre of gravity of the pump including installation/transportation accessories. See fig. 5. The position of the label varies depending on pump type and accessories.
Fig. 6 Symbol of centre of gravity
Fig. 7 Transportation stand with cable holders
5.1 Lifting the pump
S pumps, range 78 weigh up to 8100 kg without accessories. It is therefore very important to use the right lifting equipment.
The pump weight is stated on the pump nameplate. See section 3.2 Nameplates.
Warning Pump installation in pits must be carried out by
specially trained persons. Work in or near pits must be carried out
according to local regulations. Warning
It must be possible to lock the main power switch in position 0. Type and requirements as specified in EN 60204-1, 5.3.2.
Warning Persons must not enter the installation area
when the atmosphere is explosive.
Warning Never work under a pump when it is hanging
from crane!
Warning Before attempting to lift the pump, make sure the
rated capacity of the lifting equipment (lifting chain etc.) is adequate for the lifting work.
The rated capacity of the lifting equipment is stated on the equipment nameplate. The weight of the pump is stated on the pump nameplate.
Warning For some installation types, the surface
temperature may be up to 90 °C.
Warning The surface temperature of the cables may
exceed 70 °C.
TM03 3069 4809
Note
We recommend that you keep the transportation stand in storage for later use.
TM04 6728 0810TM03 3365 4809
Note
The weight is stated with 10 m cables.
Note
The weights of installation type S and C pumps include the weight of the guide claw.
The weight of installation type H pumps includes the weight of the horizontal base stand.
English (GB)
Pump type
Net weight [kg]
SCDH
Range 72
S2.90.250.2250.4.72S 1770 1950 1955 2250 S2.100.250.2250.4.72H 1760 1945 1955 2240 S2.100.250.1750.4.72H 1760 1945 1955 2240 S2.100.300.2250.4.72M 1840 2020 2010 2300 S2.100.300.1750.4.72M 1840 2020 2010 2300 S3.110.300.1800.6.72H 1965 2160 2150 2440 S3.110.300.1600.8.72H 1965 2165 2155 2445 S3.120.500.1800.6.72M 2335 2520 2360 2700 S3.120.500.1600.8.72M 2330 2530 2370 2700 S3.120.500.1250.8.72M 2330 2530 2370 2700 S3.135.500.1800.6.72L 2340 2525 2360 2700 S3.135.500.1600.8.72L 2335 2535 2375 2705 S3.135.500.1250.8.72L 2335 2535 2375 2705 S3.135.600.1600.8.72E 2710 2910 2690 3020 S3.135.600.1300.10.72E 2730 2930 2710 3040 S3.135.600.1100.10.72E 2720 2920 2700 3030 S3.135.600.900.10.72E 2710 2910 2690 3020
Range 74 CDH
S2.90.300.2500.4.74S 2800 2800 3000 S2.90.300.3150.4.74S 3500 3500 3700 S2.100.300.2500.4.74H 2800 2800 3000 S2.100.300.3150.4.74H 3500 3500 3700 S3.110.300.2000.6.74H 3000 3000 3200 S3.110.300.2500.6.74H 3100 3100 3400 S3.110.300.3150.6.74H 3900 3900 4100 S3.120.300.2000.6.74M 3300 3200 3400 S3.120.300.2500.6.74M 3500 3300 3500 S3.120.300.3150.6.74M 4300 4100 4300 S3.135.500.2000.6.74L 3300 3300 3500 S3.135.500.2500.6.74L 3500 3400 3700 S3.135.500.3150.6.74L 4200 4200 4400 S3.135.600.2000.8.74E 3900 3700 4000 S3.135.600.2500.8.74E 4600 4400 4700
Range 78 CDH
S3.115.500.3150.8.78H 5600 5500 6000 S3.115.500.3500.8.78H 6000 5800 6300 S3.115.500.4000.8.78H 6100 5900 6400 S3.115.500.4500.8.78H 6200 6000 6500 S3.115.500.5000.8.78H 6200 6100 6600 S3.115.500.5200.8.78H 6400 6200 6700 S3.130.500.2500.10.78M 5200 5100 5600 S3.130.500.3150.8.78M 5500 5400 5900 S3.130.500.3150.10.78M 5800 5600 6100 S3.130.500.3500.8.78M 5900 5800 6300 S3.130.500.3500.10.78M 6100 5900 6400 S3.130.500.4000.8.78M 6000 5900 6400 S3.130.500.4000.10.78M 6100 6000 6500 S3.130.500.4500.8.78M 6100 6000 6500 S3.130.500.5000.8.78M 6200 6100 6600 S3.130.500.5200.8.78M 6300 6200 6700 S3.145.500.1600.10.78L 5000 4900 5300 S3.145.500.2000.10.78L 5100 5000 5500 S3.145.500.2500.10.78L 5400 5300 5800 S3.145.500.3150.8.78L 5700 5600 6100
S3.145.500.3150.10.78L 5900 5800 6300 S3.145.500.3500.8.78L 6000 5900 6400 S3.145.500.3500.10.78L 6200 6100 6600 S3.145.500.4000.8.78L 6100 6000 6500 S3.145.500.5000.8.78L 6300 6200 6700 S3.145.500.5200.8.78L 6400 6300 6800 S4.135.600.1300.12.78E 5700 5700 6300 S4.135.600.1600.12.78E 5900 5900 6500 S4.135.600.2000.10.78E 5800 5800 6400 S4.135.600.2500.10.78E 6000 6000 6600 S4.135.600.3150.8.78E 6300 6300 6900 S4.135.600.3150.10.78E 6600 6600 7100 S4.135.600.3500.8.78E 6700 6700 7300 S4.135.600.4000.8.78E 6800 6800 7300 S4.135.600.4500.8.78E 6900 6900 7500 S4.135.600.5000.8.78E 7000 7000 7500 S4.135.600.5200.8.78E 7100 7100 7700 S4.155.800.2500.10.78F 6600 6500 7200 S4.155.800.3150.10.78F 7100 7000 7700 S4.155.800.3500.10.78F 7400 7300 8000 S4.155.800.4000.10.78F 7500 7400 8100 S4.155.800.1600.12.78F 6500 6400 7100 S4.155.800.2000.12.78F 7100 7000 7700 S4.155.800.2500.12.78F 7300 7200 8000 S4.155.800.1100.14.78F 6300 6200 6900 S4.155.800.1300.14.78F 6500 6400 7100 S4.155.800.1600.14.78F 7000 6900 7600
ST pumps Weight [kg]
Range 74
ST3.135.1200.2000.8.74E 2800 ST3.135.1200.2500.8.74E 3400
Range 78
ST4.135.1400.3150.8.78E 4700 ST4.135.1400.3500.8.78E 5000 ST4.135.1400.4000.8.78E 5100 ST4.135.1400.4500.8.78E 5200 ST4.135.1400.5000.8.78E 5300 ST4.135.1400.5200.8.78E 5400 ST4.135.1400.5200.8.78E 5400 ST4.135.1400.2000.10.78E 4200 ST4.135.1400.2500.10.78E 4400 ST4.135.1400.3150.10.78E 4900 ST4.135.1400.1300.12.78E 4100 ST4.135.1400.1600.12.78E 4300 ST4.155.1600.2500.10.78F 4700 ST4.155.1600.3150.10.78F 5200 ST4.155.1600.3500.10.78F 5500 ST4.155.1600.4000.10.78F 5500 ST4.155.1600.1600.12.78F 4600 ST4.155.1600.2000.12.78F 5200 ST4.155.1600.2500.12.78F 5400 ST4.155.1600.1100.14.78F 4400 ST4.155.1600.1300.14.78F 4600 ST4.155.1600.1600.14.78F 5100
Pump type
Net weight [kg]
SCDH
English (GB)
All lifting equipment must be rated for the purpose and checked for damage before any attempt to lift the pump. The lifting equipment rating must under no circumstances be exceeded. The pump weight is stated on the pump nameplate.
Fig. 8 Lifting points on pump, range 72
Fig. 9 Lifting points on pump, range 74 and 78
5.2 Raising pump to upright position
Fig. 10 Raising the pump to upright position, step 1
Fig. 11 Raising the pump to upright position, step 2
Fig. 12 Raising the pump to upright position, step 3
Note
The weights are net weights including the accessories mounted from factory.
Warning Always lift the pump by the marked lifting points
or by means of a fork-lift truck. To make the use of a fork-lift truck when moving
a pump safer, the approximate centre of gravity is marked with a label attached to the transportation stand. Make sure the centre of gravity is between the fork-lift arms when lifting the pump.
Never lift the pump by the power supply cables. It may result in electric short-circuit and risk of electric shock when the pump is connected to the mains. The cables and cable entry may be damaged, leading to loss of watertightness and consequent severe damage to the motor.
TM03 4459 0208TM04 6068 4809
Warning If during transportation, assembly or dismantling
the pump is tilted more than 10 ° in any direction from its normal position (EN 809, 5.2.1.4), the pump may lose its stability. Secure the pump by means of chains or place it in horizontal position.
Warning Make sure that the lifting brackets are tightened
before attempting to lift the pump. Tighten if necessary. Carelessness during lifting or transportation may cause injury to personnel or damage to the pump.
TM03 3034 0208TM03 3035 0208TM03 3036 0208