Grundfos CRE Series, CRIE Series, CRNE Series, SPKE Series, MTRE Series Installation And Operating Instructions Manual

...
GRUNDFOS INSTRUCTIONS
CRE, CRIE, CRNE, SPKE, CRKE, MTRE, CME
Grundfos E-pumps with MLE frequency-controlled permanent-magnet motors
Installation and operating instructions
English (US)
English (US) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
1. Limited warranty
2. Symbols used in this document
3. Abbreviations and definitions
4. General information
5. General description
5.1 Pumps without factory-fitted sensor
5.2 Pumps with factory-fitted pressure sensor
5.3 Settings
5.4 Radio communication
5.5 Battery
6. Mechanical installation
6.1 Mounting
6.2 Cable entries
6.3 Ensuring motor cooling
6.4 Outdoor installation
6.5 Drain holes
7. Electrical installation
7.1 Protection against electric shock, indirect contact
7.2 Power supply
7.3 Additional protection
7.4 Connection terminals
7.5 Signal cables
7.6 E-pump electrical connections
7.7 Bus connection cable
8. Operating conditions
8.1 Maximum number of starts and stops
8.2 Ambient temperature
8.3 Installation altitude
8.4 Air humidity
8.5 Motor cooling
9. Operating and control modes
9.1 Overview
9.2 Operating mode
9.3 Control mode
10. User interfaces
10.1 Standard control panel
10.2 Changing the position of the control panel
10.3 R100 remote control
10.4 Grundfos GO Remote
11. External setpoint signal
11.1 Operation with sensor feedback
11.2 Constant-curve operation
12. Bus signal
13. Priority of settings
14. Grundfos Eye
15. Signal relays
16. Megging
17. Technical data, single-phase motors
17.1 Supply voltage
17.2 Leakage current
18. Technical data, three-phase motors
18.1 Supply voltage
18.2 Leakage current
Page
11 11 12
12
12 12 12 13 13
13
13 13 14
14
14 17 18 32
33
33 34
35 35 36 37 38 38
38 38
38
38 38
19. Inputs/outputs
20. Other technical data
20.1 Sound pressure level
21. Disposal
2
1. Limited warranty
3
Products manufactured by GRUNDFOS PUMPS CORPORATION
3
(Grundfos) are warranted to the original user only to be free of
4
defects in material and workmanship for a period of 24 months
4
from date of installation, but not more than 30 months from date
4
of manufacture. Grundfos' liability under this warranty shall be
4
limited to repairing or replacing at Grundfos' option, without
4
charge, F.O.B. Grundfos' factory or authorized service station,
4
any product of Grundfos' manufacture. Grundfos will not be liable
4
for any costs of removal, installation, transportation, or any other
4
charges which may arise in connection with a warranty claim.
4
Products which are sold but not manufactured by Grundfos are
4
subject to the warranty provided by the manufacturer of said
5
products and not by Grundfos' warranty. Grundfos will not be
5
liable for damage or wear to products caused by abnormal
5
operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in
5
accordance with Grundfos' printed installation and operating
5
instructions.
6
To obtain service under this warranty, the defective product must
7
be returned to the distributor or dealer of Grundfos' products from
7
which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.
Warnin g Prior to installation, read these installation and
operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
38 39
39
40
2. Symbols used in this document 3. Abbreviations and definitions
Caution
Note
Note
Warnin g If these safety instructions are not observed,
it may result in personal injury.
Warnin g If these instructions are not observed, it may lead
to electric shock with consequent risk of serious personal injury or death.
Warnin g The surface of the product may be so hot that
it may cause burns or personal injury.
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Notes or instructions that make the job easier and ensure safe operation.
AI Analog input. AL Alarm, out of range at lower limit. AO Analog output. AU Alarm, out of range at upper limit. CIM Communication interface module.
Current sinking
Current sourcing
DI Digital input. DO Digital output. ELCB Ground leakage circuit breaker.
GDS
GENIbus Proprietary Grundfos fieldbus standard.
GFCI
GND Ground. Grundfos Eye Status indicator light.
LIVE
OC
PE Protective ground.
PELV
SELV
The ability to draw current into the terminal and guide it towards GND in the internal circuitry.
The ability to push current out of the terminal and into an external load which must return it to GND.
Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps.
Ground fault circuit interrupter. (USA and Canada).
Low voltage with the risk of electric shock if the terminals are touched.
Open collector: Configurable open-collector output.
Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except ground faults in other circuits.
Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including ground faults in other circuits.
English (US)
English (US)
Note
Note
4. General information
These installation and operating instructions are a supplement to the installation and operating instructions for the corresponding standard pumps CR, CRI, CRN, CRK, SPK, MTR and CM.
For instructions not mentioned specifically in this manual, see the installation and operating instructions for the standard pump.
5. General description
Grundfos E-pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase power supply connection.
5.1 Pumps without factory-fitted sensor
The pumps have a built-in PI controller and can be set up for an external sensor enabling the control of the following parameters:
• constant pressure
• constant differential pressure
• constant temperature
• constant differential temperature
• constant flow rate
• constant level
• constant curve
• constant other value. The pumps have been factory-set to constant-curve control
mode. The control mode can be changed with the R100 or Grundfos GO Remote.
5.2 Pumps with factory-fitted pressure sensor
The pumps have a built-in PI controller and are set up with a pressure sensor enabling the control of the pump discharge pressure.
The pumps have been factory-set to constant-pressure control mode. The pumps are typically used to keep a constant pressure in variable-demand systems.
5.4 Radio communication
This product incorporates a radio module for remote control. For use in USA and Canada, see page 41.
This product can communicate with the Grundfos GO Remote and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only Grundfos-approved external antennas may be connected to
this product, and only by a Grundfos-approved installer.
5.5 Battery
A Li-ion battery is fitted in CRE, CRIE, CRNE, CRKE, SPKE and MTRE pumps. The Li-ion battery complies with the Battery Directive (2006/66/EC). The battery does not contain mercury, lead and cadmium.
6. Mechanical installation
Warnin g Installation and operation must comply with local
regulations and accepted codes of good practice.
6.1 Mounting
The pump must be secured to a solid foundation by means of bolts through the holes in the flange or baseplate.
In order to maintain the UR mark, follow the additional installation procedures on page 41.
6.2 Cable entries
The motor has four M20 screwed cable entries fitted with blind plugs from factory.
The following cable glands are included:
• 2 x M20 cable gland, sensor/signal cables
• 1 x M20 cable gland, power supply cable.
5.3 Settings
The description of settings applies both to pumps without factory-fitted sensor and to pumps with a factory-fitted pressure sensor.
Setpoint
The desired setpoint can be set in three ways:
• directly on the pump control panel
• via an input for external setpoint signal
• by means of Grundfos wireless remote control R100 or Grundfos GO Remote.
Other settings
All other settings can only be made by means of the R100 or Grundfos GO Remote.
Important parameters, such as actual value of control parameter, power consumption, etc. can be read via the R100 or Grundfos GO Remote.
If special or customized settings are required, use Grundfos PC Tool E-products. Contact your local Grundfos company for more information.
6.3 Ensuring motor cooling
Note
Note
Note
Note
D
B3 B14 B5
In order to ensure sufficient cooling of the motor, the distance (D) between the end of the fan cover and a wall or other fixed objects must always be at least 2", irrespective of motor size. See fig. 1.
7. Electrical installation
Carry out the electrical connection according to local regulations. Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Warnin g Do not make any connections in the terminal box
unless the power supply has been switched off for at least 5 minutes.
Make sure that the power supply cannot be accidentally switched on.
The motor must be ground and protected against indirect contact in accordance with local regulations.
If the power supply cable is damaged, it must be replaced by the manufacturer, the manufacturer's service partner or a similarly qualified person.
English (US)
Fig. 1 Minimum distance (D) from the motor to a wall or other
fixed objects
6.4 Outdoor installation
When installed outdoors, the motor must be provided with a suitable cover to avoid condensation on the electronic components. See fig. 2.
When fitting a cover to the motor, observe the guideline in section 6.3 Ensuring motor cooling.
The cover must be sufficiently large to ensure that the motor is not exposed to direct sunlight, rain or snow. Grundfos does not supply covers. We therefore recommend that you have a cover built for the specific application. In areas with high air humidity, we recommend that you enable the built-in standstill heating function. See section Standstill heating, page 31.
Fig. 2 Examples of covers (not supplied by Grundfos)
6.5 Drain holes
When the motor is installed in moist surroundings or areas with high air humidity, the bottom drain hole should be open.
The enclosure class of the motor will then be lower. The open drain hole helps prevent condensation in the motor as it will make the motor self-venting and allow water and humid air to escape.
The motor has a plugged drain hole on the drive side. The flange can be turned 90 ° to both sides or 180 °.
TM05 5236 3512
The user or the installer is responsible for the installation of correct grounding and protection according to local regulations. All operations must be carried out by a qualified electrician.
7.1 Protection against electric shock, indirect contact
Warnin g The motor must be grounded and protected
against indirect contact in accordance with local regulations.
Protective-ground conductors must always have a yellow/green (PE) or yellow/green/blue (PEN) color marking.
7.1.1 Protection against power supply voltage transients
The motor is protected against power supply voltage transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.
7.1.3 Backup fuses
For recommended fuse sizes, see page 41.
TM05 3496 3512TM02 9037 1604
Fig. 3 Drain holes
English (US)
ELCB
(GFCI)
Caution
Note
Note
L1
L2
L3
L2
L1
L3
PE
ELCB
(GFCI)
7.2 Power supply
7.2.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated ground conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 17.1 Supply voltage.
Fig. 4 Example of a power-connected motor.
7.2.2 Three-phase supply voltage
• 3 x 440-480 V - 10 %/+ 10 %, 50/60 Hz, PE.
In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in its socket when the supply cable has been connected.
Corner grounding is not allowed for supply voltages above 3 x 480 V, 50/60 Hz.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated ground conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 18.1 Supply voltage.
TM05 4034 1912TM05 3494 1512
TM05 3942 1812TM05 3495 1512
Fig. 6 Example of a power-connected motor
Fig. 5 Power connection, single-phase motors
Fig. 7 Power connection, three-phase motors
7.3 Additional protection
Note
Note
Note
Note
ELCB (GFCI)
ELCB (GFCI)
Note
Note
Note
Note
7.3.1 Single-phase motors
If the motor is connected to an electric installation where a ground leakage circuit breaker (ELCB) or ground fault circuit interrupter (GFCI) is used as additional protection, this circuit breaker or interrupter must be marked with the following symbol:
When a ground leakage circuit breaker or ground fault circuit interrupter is selected, the total leakage current of all the electrical equipment in the installation must be taken into account.
The leakage current of the motor can be found in section
17.2 Leakage current.
7.3.2 Three-phase motors
If the motor is connected to an electric installation where a ground leakage circuit breaker (ELCB) or ground fault circuit interrupter (GFCI) is used as additional protection, this circuit breaker or interrupter must be of the following type:
• It must be suitable for handling leakage currents and cutting-in with short pulse-shaped leakage.
• It must trips out when alternating fault currents and fault currents with DC content, i.e. pulsating DC and smooth DC fault currents, occur.
For these motors a ground leakage circuit breaker or ground fault circuit interrupter, type B, must be used.
This circuit breaker or interrupter must be marked with the following symbols:
When a ground leakage circuit breaker or ground fault circuit interrupter is selected, the total leakage current of all the electrical equipment in the installation must be taken into account.
The leakage current of the motor can be found in section
18.2 Leakage current.
Protection against phase unbalance
The motor must be connected to a power supply with a quality corresponding to IEC 60146-1-1, class C, to ensure correct motor operation at phase unbalance.
This also ensures long life of the components.
7.4 Connection terminals
The descriptions and terminal overviews in this section apply to both single- and three-phase motors.
For maximum tightening torques, see section Torques, page 39.
7.4.1 Connection terminals, CRE, CRIE, CRNE, CRKE, SPKE and MTRE pumps
CRE, CRIE, CRNE, CRKE, SPKE and MTRE pumps have a number of inputs and outputs enabling the pumps to be used in advanced applications where many inputs and outputs are required.
The pumps have these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start/stop input where open circuit will result in stop. A jumper has been factory-fitted between terminals 2 and
6. Remove the jumper if digital input 1 is to be used as external start/stop or any other external function.
As a precaution, the wires to be connected to the connection groups below must be separated from each other by reinforced insulation in their entire lengths.
Inputs and outputs
All inputs and outputs are internally separated from the power-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by safety extra-low voltage (SELV), thus ensuring protection against electric shock.
• Start/stop: (Digital input 1) Terminals 2 and 6
• Pressure sensor: (Analog input 1) Terminals 4 and 8
• Pressure switch: (Digital input 3) Terminals 10 and 6
• External analog signal input: (Analog input 2) Terminals 7 and
23
• GENIbus Terminals A, Y and B
Signal relay outputs
– Signal relay 1:
LIVE: Power supply voltages up to 250 VAC can be connected to this output. SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
– Signal relay 2:
SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE)
A galvanically safe separation must fulfill the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
English (US)
English (US)
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
Terminal Type Function
NC
C1 Common
NO
Normally closed contact
Normally open contact
Signal relay 1 (LIVE or SELV)
NC
C2 Common
NO
Normally closed contact
Normally open contact
Signal relay 2 (SELV only)
18 GND Ground
Digital input/output,
11 DI 4/O C2
configurable. Open collector: Max. 24 V
resistive or inductive. 19 Pt100/1000 input 2 Pt100/1000 sensor input 17 Pt100/1000 input 1 Pt100/1000 sensor input
Analog output: 12 AO
0-20 mA / 4-20 mA
0-10 V
9 GND Ground
Analog input: 14 AI3
0-20 mA / 4-20 mA
0-10 V
1 DI2 Digital input, configurable
21 LiqTec sensor input 1
LiqTec sensor input
(white conductor)
Ground 20 GND
(brown and black
conductors)
22 LiqTec sensor input 2
LiqTec sensor input
(blue conductor)
* If an external supply source is used, there must be a
connection to GND.
Fig. 8 Connection terminals, CRE, CRIE, CRNE, CRKE,
SPKE and MTRE pumps
Digital input/output,
10 DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
TM05 3509 3512
2 DI1 Digital input, configurable
5+5 V
Supply to potentiometer
and sensor
6 GND Ground A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
Supply to potentiometer and sensor
23 GND Ground
25 GDS TX
24 GDS RX
Grundfos Digital Sensor output
Grundfos Digital Sensor input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
7.4.2 Connection terminals, CME pumps
Note
Note
Note
Note
The CME pump has these connections:
• two analog inputs
• two digital inputs or one digital input and one open-collector output
• Grundfos Digital Sensor input and output
• two signal relay outputs
• GENIbus connection.
See fig. 9.
Digital input 1 is factory-set to be start/stop input where open circuit will result in stop. A jumper has been factory-fitted between terminals 2 and
6. Remove the jumper if digital input 1 is to be used as external start/stop or any other external function.
As a precaution, the wires to be connected to the connection groups below must be separated from each other by reinforced insulation in their entire lengths.
Inputs and outputs All inputs and outputs are internally separated from the power conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by safety extra-low voltage (SELV), thus ensuring protection against electric shock.
• Start/stop: (Digital input 1) Terminals 2 and 6
• Pressure sensor: (Analog input 1) Terminals 4 and 8
• Pressure switch: (Digital input 3) Terminals 10 and 6
• External analog signal input: (Analog input 2) Terminals 7 and 23
• GENIbus Terminals A, Y and B
Signal relay outputs
– Signal relay 1:
LIVE: Power supply voltages up to 250 VAC can be connected to this output. SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
– Signal relay 2:
SELV: The output is galvanically separated from other circuits. Therefore, the supply voltage or safety extra-low voltage can be connected to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE)
A galvanically safe separation must fulfill the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
English (US)
English (US)
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
Terminal Type Function
NC
C1 Common
NO
Normally closed contact
Normally open contact
Signal relay 1 (LIVE or SELV)
* If an external supply source is used, there must be a
connection to GND.
Fig. 9 Connection terminals, CME pump
NC
C2 Common
NO
Normally closed contact
Normally open contact
Signal relay 2 (SELV only)
Digital input/output,
10 DI3/OC1
configurable. Open collector: Max. 24 V resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5+5 V
Supply to potentiometer and sensor
6 GND Ground A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
TM05 3510 3512
8 +24 V Supply
26 +5 V
Supply to potentiometer and sensor
23 GND Ground
25 GDS TX
Grundfos Digital Sensor output
24 GDS RX Grundfos Digital Sensor input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
10
7.5 Signal cables
Dry-running sensor
Set to automatic resetting
Connection terminals on E-pump:
2 (Start/Stop) and 6 (GND)
2
1 x 200-240 VAC
or
1 X 80-130 VAC
Brown
Black
Blue
White
Jumper cable
6
• Use screened cables with a conductor cross-section of min. 28 AWG and max. 16 AWG for external on/off switch, digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to frame at both ends with good connection. The screens must be as close as possible to the terminals. See fig. 10.
Fig. 10 Stripped cable with screen and wire connections
7.6 E-pump electrical connections
7.6.1 Connection of E-pump to Danfoss pressure sensor MBS3000
The blue wire of the pressure sensor is connected to the #4 terminal of the E-pump. The brown wire of the pressure sensor is connected to the #8 terminal of the E-pump.
See section 7.5 Signal cables on or additional details.
TM02 1325 4402
English (US)
• Always tighten screws for frame connections whether a cable is fitted or not.
• Make the wires in the motor terminal box as short as possible.
7.6.2 Connection of E-pump to LiqTec
®
TM05 1533 2911
Fig. 11 Danfoss pressure sensor
Fig. 12 Connection of E-pump to LiqTec
TM03 0437 5104
11
English (US)
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
Caution
1
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.91
0.90
0.89
0.88
0
0
3281 3937 4593 5249 5906 6562 7218
[ft]
P2 [%]
7.7 Bus connection cable
7.7.1 New installations
For the bus connection, use a screened 3-core cable with a conductor cross-section 28-16 AWG.
• If the motor is connected to a unit with a cable clamp which is identical to the one on the motor, connect the screen to this cable clamp.
• If the unit has no cable clamp as shown in fig. 13, leave the screen unconnected at this end.
Fig. 13 Connection with screened 3-core cable
7.7.2 Replacing an existing motor
• If a screened 2-core cable is used in the existing installation, connect it as shown in fig. 14.
8. Operating conditions
8.1 Maximum number of starts and stops
The number of starts and stops via the power supply must not exceed four times per hour.
When switched on via the power supply, the pump will start after approx. 5 seconds.
If a higher number of starts and stops is desired, use the input for external start/stop when starting/stopping the pump.
When started via an external on/off switch, the pump will start immediately.
8.2 Ambient temperature
8.2.1 Ambient temperature during storage and transportation
Minimum -22 °F Maximum +140 °F.
8.2.2 Ambient temperature during operation
Minimum -4 °F
TM05 3973 1812TM02 8842 0904
Maximum -122 °F. The motor can operate with the rated power output (P2) at 122 °F,
but continuous operation at higher temperatures will reduce the expected product life. If the motor is to operate at ambient temperatures between 122 and 140 °F, an oversized motor must be selected. Contact Grundfos for further information.
8.3 Installation altitude
The motor must not be installed more than 6560 ft above sea level.
Installation altitude is the height above sea level of the installation site.
• Motors installed up to 3280 ft above sea level can be loaded 100 %.
• Motors installed more than 3280 ft above sea level must not
Fig. 14 Connection with screened 2-core cable
• If a screened 3-core cable is used in the existing installation,
be fully loaded due to the low density and consequent low cooling effect of the air. See fig. 15.
follow the instructions in section 7.7.1 New installations.
TM05 6400-U.S. 1013
Fig. 15 Derating of motor output power (P2) in relation to
altitude above sea level
12
8.4 Air humidity
Q
H
Max.
Min.
Maximum air humidity: 95 %. If the air humidity is constantly high and above 85 %, the drain
holes in the drive-end flange should be open. See section 6.5 Drain holes.
8.5 Motor cooling
To ensure cooling of motor and electronics, the following must be observed:
• Position the motor in such a way that adequate cooling is
ensured. See section 6.3 Ensuring motor cooling.
• The temperature of the cooling air must not exceed 122 °F.
• Keep cooling fins and fan blades clean.
9. Operating and control modes
Grundfos E-pumps are set and controlled according to operating and control modes.
9.1 Overview
Operating modes
Normal
Stop
Min.
Max.
Manual
Control modes
Constant pressure
Constant differential pressure
Constant temperature
9.2 Operating mode
When the operating mode is set to "Normal", the control mode can be set to constant curve or any other control mode.
See section 9.3 Control mode. Other operating modes:
•Stop The pump has been stopped.
•Min. The pump is operating at its minimum speed.
•Max. The pump is operating at its maximum speed.
• Manual The pump is operating at a manually set speed.
Figure 16 illustrates the min. and max. curves.
Fig. 16 Min. and max. curves
The max. curve can for instance be used in connection with the venting procedure during installation.
The min. curve can be used in periods in which a minimum flow is required.
If the power supply to the pump is disconnected, the setting of operating mode will be stored.
English (US)
TM00 5547 0995
Constant differential temperature
Constant flow rate
Constant level
Constant curve
Constant other value
Example
If the pump is fitted with a pressure sensor, the control mode must be set to constant pressure. If the pump is for instance fitted with a temperature sensor, the control mode should be constant temperature. See section 9.3 Control mode for further information.
13
English (US)
Q
H
Q
H
H
set
1
2
3
4
5
Stop
9.3 Control mode
9.3.1 Pumps without factory-fitted sensor
The pumps have been factory-set to constant-curve control mode.
In this control mode, the pump will operate according to the constant curve set. See fig. 17.
Fig. 17 Pump in constant-curve control mode
Factory setting
Pumps supplied without sensor have been factory-set to constant-curve control mode.
The setpoint value corresponds to 100 % of the maximum pump performance. See data booklet or WebCAPS.
9.3.2 Pumps with factory-fitted pressure sensor
The pressure sensor is fitted on the pump discharge side, and the pump is set to constant pressure.
In this control mode, the pump will adjust its performance, i.e. pump discharge pressure, to the desired setpoint (H
18.
). See fig.
set
10. User interfaces
Warnin g The product may be so hot that only the buttons
should be touched to avoid burns.
Pump settings can be made by means of the following user interfaces:
Control panel
• Standard control panel. See section 10.1 Standard control panel.
Remote controls
• Grundfos R100 remote control. See section 10.3 R100 remote control.
• Grundfos GO Remote. See section 10.4 Grundfos GO Remote.
If the power supply to the pump is switched off, the settings will be stored.
TM05 6403 4712TM05 6398 4712
10.1 Standard control panel
TM05 4848 3512
Fig. 19 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
Shows the operating status of the pump. See section 14. Grundfos Eye for further information.
2 - Light fields for indication of setpoint.
Fig. 18 Pump in constant-pressure control mode
Factory setting
Pumps supplied with pressure sensor have been factory-set to constant-pressure control mode.
The setpoint value corresponds to 50 % of the sensor measuring range. See sensor nameplate.
3 Changes the setpoint.
Enables radio communication with the
4
Grundfos GO Remote and other products of the same type.
Makes the pump ready for operation/starts and stops the pump.
Start:
If the button is pressed when the pump is stopped, the pump will only start if no other functions with higher priority have been
5
enabled. See section 13. Priority of
settings.
Stop:
If the button is pressed when the pump is running, the pump will always be stopped. When the pump is stopped via this button, the "Stop" text next to the button will illuminate.
14
Loading...
+ 30 hidden pages