Grundfos CRIE, CRE, CRNE, CME, SPKE Installation And Operating Instructions Manual

...
GRUNDFOS INSTRUCTIONS
CRE, CRIE, CRNE, SPKE, MTRE, CME
Installation and operating instructions
Other languages
http://net.grundfos.com/qr/i/98358864
English (GB) Installation and operating instructions

English (GB)

CONTENTS
Page
1. Symbols used in this document
2. Abbreviations and definitions
3. General information
4. General description
4.1 Pumps without factory-fitted sensor
4.2 Pumps with factory-fitted pressure sensor
4.3 Settings
4.4 Radio communication
4.5 Battery
5. Receiving the product
5.1 Transporting the product
5.2 Inspecting the product
6. Mechanical installation
6.1 Handling the product
6.2 Mounting
6.3 Cable entries
6.4 Cable glands
6.5 Ensuring motor cooling
6.6 Outdoor installation
6.7 Drain holes
7. Electrical installation
7.1 Protection against electric shock, indirect contact
7.2 Cable requirements
7.3 Mains supply
7.4 Additional protection
7.5 Connection terminals
7.6 Signal cables
7.7 Bus connection cable
8. Operating conditions
8.1 Maximum number of starts and stops
8.2 Ambient temperature
8.3 Installation altitude
8.4 Humidity
8.5 Motor cooling
9. User interfaces
10. Standard control panel
10.1 Setpoint setting
11. Advanced control panel
11.1 Home display
11.2 Startup guide
11.3 Menu overview for advanced control panel
12. Grundfos GO
12.1 Communication
12.2 Menu overview for Grundfos GO
2
13. Description of functions
13.1 Setpoint
13.2 Operating mode
13.3 Set manual speed
13.4 "Set user-defined speed"
3
13.5 "Control mode"
4
13.6 Analog inputs
4
13.7 Pt100/1000 inputs
4
13.8 Digital inputs
4
13.9 Digital inputs/outputs
13.10 "Signal relays" 1 and 2 (Relay outputs)
4
13.11 Analog output
5
13.12 "Controller" (Controller settings)
5
13.13 Operating range
5
13.14 External setpoint function
5
13.15 Predefined setpoints
5
13.16 Limit-exceeded function
5
13.17 "LiqTec" (LiqTec function)
13.18 "Stop function" (Low-flow stop function)
5
13.19 Pipe filling function
5
13.20 "Pulse flowmeter" (Pulse flowmeter
6 6
13.21 Ramps
6
13.22 Standstill heating
6
13.23 Motor bearing monitoring
6
13.24 "Service"
6
13.25 "Number" (Pump number)
7
13.26 "Radio communication" (Enable/disable
7
13.27 Language
7
13.28 "Date and time" (Set date and time)
8
13.29 "Unit configuration" (Units)
9
13.30 "Buttons on product" (Enable/disable
9
14
13.31 Delete history
14
13.32 Define Home display
13.33 Display settings
15
13.34 "Store settings" (Store actual settings)
15
13.35 "Recall settings" (Recall stored settings)
15
13.36 "Pump name"
15
13.37 "Connection code"
16
13.38 Run start-up guide
16
13.39 Alarm log
16
13.40 Warning log
17
13.41 Assist
17
13.42 Assisted pump setup
19
13.43 Setup, analog input
20
13.44 Setting of date and time
20
13.45 "Multi-pump setup" (Setup of multi-pump
21
13.46 Description of control mode
24
13.47 Assisted fault advice
24
14. Bus signal
25
15. Priority of settings
16. Grundfos Eye
17. Signal relays
setup)
radio comm.)
settings)
system)
28
28 28 28 28 28 33 35 35 37 38 38 40 41 41 43 44 45 45 47
48 48 48 48 49 49
49 49 50 50
50 50 51 51 51 51 51 52 52 52 53 53 53 53 54
54 57 57
57
58
59
60
18. Installing a communication interface module
19. Identification of functional module
20. Identification of control panel
21. Changing the position of the control panel
22. Servicing the product
22.1 Motor
22.2 Pump
23. Cleaning the product
24. Factory settings
25. Megging
26. Technical data, single-phase motors
26.1 Supply voltage
26.2 Leakage current
27. Technical data, three-phase motors
27.1 Supply voltage
27.2 Leakage current (AC)
28. Inputs/outputs
29. Other technical data
29.1 Sound pressure level
30. Disposing of the product
Read this document before installing the product. Installation and operation must comply with local regulations and accepted codes of good practice.

1. Symbols used in this document

61
63
63
64
65
65 65
65
66
68
68
68 68
68
68 69
69
71
72
72
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
Tips and advice that make the work easier.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
A blue or grey circle with a white graphical symbol indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
English (GB)
3

2. Abbreviations and definitions 3. General information

English (GB)
AI Analog input. AL Alarm, out of range at lower limit. AO Analog output. AU Alarm, out of range at upper limit. CIM Communication interface module.
Current sinking
Current sourcing
DI Digital input. DO Digital output. ELCB Earth leakage circuit breaker. FM Functional module.
GDS
GENIbus
GFCI
GND Ground. Grundfos
Eye
LIVE
OC
PE Protective earth.
PELV
RCD Residual-current device
SELV
The ability to draw current into the terminal and guide it towards GND in the internal circuitry.
The ability to push current out of the terminal and into an external load which must return it to GND.
Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps.
Proprietary Grundfos fieldbus standard.
Ground fault circuit interrupter. (USA and Canada).
Status indicator light.
Low voltage with the risk of electric shock if the terminals are touched.
Open collector: Configurable open-collector output.
Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except earth faults in other circuits.
Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including earth faults in other circuits.
These installation and operating instructions are a supplement to the installation and operating instructions for the corresponding standard pumps CR, CRI, CRN, SPK, MTR and CM. For instructions not mentioned specifically in this manual, see the installation and operating instructions for the standard pump.

4. General description

Grundfos E-pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase mains connection.

4.1 Pumps without factory-fitted sensor

The pumps have a built-in PI controller and can be set for an external sensor enabling the control of the following parameters:
• constant pressure
• constant differential pressure
• constant temperature
• constant differential temperature
• constant flow rate
• constant level
• constant curve
• constant other value. The pumps have been factory-set to constant-curve
control mode. You can change the control mode with R100 or Grundfos GO.

4.2 Pumps with factory-fitted pressure sensor

The pumps have a built-in PI controller and are set for a pressure sensor enabling the control of the outlet pressure.
The pumps have been factory-set to constant-pressure control mode. The pumps are typically used to keep a constant pressure in variable-demand systems.
4

4.3 Settings

The description of settings applies both to pumps without factory-fitted sensor and to pumps with a factory-fitted pressure sensor.
Setpoint
You can set the desired setpoint in three ways:
• on the pump control panel
• via an input for external setpoint signal
• with the Grundfos wireless R100 remote control or Grundfos GO.
Other settings
Make all other settings with R100 or Grundfos GO. You can read important parameters, such as the
actual value of the control parameter and power consumption, via R100 or Grundfos GO.
If special or customised settings are required, use Grundfos PC Tool. Contact your local Grundfos company for more information.

4.4 Radio communication

This product incorporates a radio module for remote control which is a class 1 device and which you can use anywhere in the EU without restrictions.
For use in USA and Canada, see page 73. Some variants of the product and products sold in
China and Korea have no radio module. This product can communicate with the Grundfos
GO and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only Grundfos-approved external antennas may be connected to this product, and only by a Grundfos-approved installer.

4.5 Battery

A Li-ion battery is fitted in CRE, CRIE, CRNE, SPKE and MTRE pumps. The Li-ion battery complies with the Battery Directive (2006/66/EC). The battery does not contain mercury, lead and cadmium.

5. Receiving the product

5.1 Transporting the product

WARNING
Falling objects
Death or serious personal injury
- Secure the product during transportation to prevent it from tilting or falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.
• Motors from 2.2 to 5.5 kW: Do not stack more than two motors in their original packaging.
• Motors from 5.5 to 11 kW: Do not stack the motors.

5.2 Inspecting the product

Before you install the product, do the following.
1. Check that the product is as ordered.
2. Check that no visible parts have been damaged.
3. If parts are damaged or missing, contact your local Grundfos sales company.

6. Mechanical installation

6.1 Handling the product

Observe local regulations setting limits for manual lifting or handling. The motor weight is stated on the nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
English (GB)
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting equipment to the motor eyebolts when handling the product.
Do not lift the product by the terminal box.
5

6.2 Mounting

D
B3 B14 B5
English (GB)
CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation by bolts through the holes in the flange or the base plate.
In order to maintain the UL mark, additional requirements apply to the equipment. See page 73.

6.3 Cable entries

See the size of the cable entries in section 29. Other
technical data.

6.4 Cable glands

The number and size of cable glands delivered with the pump depends on the motor size. See section
29. Other technical data.

6.5 Ensuring motor cooling

Leave at least 50 mm between the end of the fan cover and a wall or other fixed objects. See fig. 1.
Fig. 1 Minimum distance (D) from the motor to
a wall or other fixed objects

6.6 Outdoor installation

If you install the motor outdoors, provide the motor with a suitable cover and open the drain holes to avoid condensation on the electronic components. See figures 2 and 3.
When fitting a cover to the motor, observe the guideline in section 6.5 Ensuring motor
cooling.
The cover must be sufficiently large to ensure that the motor is not exposed to direct sunlight, rain or snow. Grundfos does not supply covers. We therefore recommend that you have a cover built for the specific application. In areas with high humidity, we recommend that you connect the motor permanently to the mains supply and activate the built-in standstill heating function. See section
13.22 Standstill heating, page 48.
Fig. 2 Examples of covers (not supplied by
Grundfos)
In order to maintain the UL mark, additional requirements apply to the equipment. See page 73.

6.7 Drain holes

When the motor is installed in moist surroundings or areas with high humidity, the bottom drain hole must be open. The enclosure class of the motor will then be lower. This helps prevent condensation in the
TM05 5236 3512
motor as the motor becomes self-venting, and it allows water and humid air to escape.
The motor has a plugged drain hole on the drive side. You can turn the flange 90 ° to both sides or 180 °.
TM05 3496 3512
6
TM02 9037 1604
Fig. 3 Drain holes

7. Electrical installation

DANGER
Electric shock
- Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before you make any connections in the terminal box. Make sure that the power supply cannot be accidentally switched on.
DANGER
Electric shock
- Death or serious personal injury
- Check that the supply voltage and frequency correspond to the values stated on the nameplate.
If the power supply cable is damaged, it must be replaced by the manufacturer, the manufacturer's service partner or a similarly qualified person.
The user or the installer is responsible for the installation of correct earthing and protection according to local regulations. All operations must be carried out by a qualified electrician.

7.1 Protection against electric shock, indirect contact

WARNING
Electric shock
- Death or serious personal injury
- Connect the motor to a protective earth and provide protection against indirect contact in accordance with local regulations.
Protective-earth conductors must always have a yellow/green (PE) or yellow/green/blue (PEN) colour marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.

7.2 Cable requirements

7.2.1 Cable cross-section
DANGER
Electric shock
- Death or serious personal injury
- Always comply with local regulations as to cable cross-sections.
1 x 200-230 V
Power [kW]
0.25 - 1.5
3 x 380-500 V
Power [kW]
0.25 - 2.2
3.0 - 11
3 x 200-240 V
Power [kW]
1.1 - 1.5
2.2 - 5.5
7.2.2 Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 60 °C (140 °F).
Temperature rating for outer cable sheath: 75 °C (167 °F).
Conductor type
Solid 1.5 - 2.5 16-12 Stranded 1.5 - 2.5 16-12
Conductor type
Solid 1.5 - 10 16-8 Stranded 1.5 - 10 16-8 Solid 2.5 - 10 14-8 Stranded 2.5 - 10 14-8
Conductor type
Solid 1.5 - 10 16-8 Stranded 1.5 - 10 16-8 Solid 2.5 - 10 14-8 Stranded 2.5 - 10 14-8
Cross section
2
[mm
][AWG]
Cross section
2
[mm
][AWG]
Cross section
2
[mm
][AWG]
English (GB)
7

7.3 Mains supply

RCD,
type B
L1
L2
L3
L2
L1
L3
PE
RCD,
type B
English (GB)
DANGER
Electric shock
- Death or serious personal injury
- Use the recommended fuse size. See section 26.1 Supply voltage.
7.3.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE. Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If you want to supply the motor through an IT network, make sure that you have a suitable motor variant. If you are in doubt, contact Grundfos.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 26.1 Supply
voltage.
Fig. 4 Example of a mains-connected motor
with mains switch, backup fuse and additional protection
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
In order to avoid loose connections, make sure that you have pressed home the terminal block for L1, L2 and L3 in its socket when you connect the supply cable.
For maximum backup fuse, see section 27.1 Supply
voltage.
Only the following motors can be supplied through an IT network:
• Motors with speed of 1450-2000/2200 rpm and
• Motors with speed of 2900-4000 rpm or
If you want to supply the motor through an IT network, make sure that you have a suitable motor variant. If you are in doubt, contact Grundfos.
up to 1.5 kW
4000-5900 rpm and up to 2.2 kW.
Corner earthing is not allowed for supply voltages above 3 x 240 V and 3 x 480 V, 50/60 Hz.
TM05 4034 1912TM05 3494 1512
Fig. 6 Example of a mains-connected motor
with mains switch, backup fuses and additional protection
TM05 3942 1812TM05 3495 1512
Fig. 5 Mains connection, single-phase motors
7.3.2 Three-phase supply voltage
Three-phase motors are available for the voltages below:
Fig. 7 Mains connection, three-phase motors
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE. Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
8

7.4 Additional protection

DANGER
Electric shock
- Death or serious personal injury
- Only use residual-current circuit breakers (ELCB, GFCI, RCD) of type B.
The residual-current circuit breaker must be marked with the following symbol:
The total leakage current of all the electrical equipment in the installation must be taken into account. You find the leakage current of the motor in sections 26.2 Leakage current and 27.2 Leakage
current (AC).
This product can cause a direct current in the protective earth conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of unstable power supply or a faulty installation. The motor is stopped if the voltage falls outside the permissible voltage range. The motor restarts automatically when the voltage is again within the permissible voltage range. Therefore, no additional protection relay is required.
The motor is protected against transients from the power supply according to EN 61800-3. In areas with high lightning intensity, we recommend external lightning protection.
Overload protection
If the upper load limit is exceeded, the motor automatically compensates for this by reducing the speed and stops if the overload condition persists.
The motor remains stopped for a set period. After this period, the motor automatically attempts to restart. The overload protection prevents damage to the motor. Consequently, no additional motor protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor as an additional protection. When the temperature rises above a certain level, the motor automatically compensates for this by reducing the speed and stops if the temperature keeps rising. The motor remains stopped for a set period. After this period, the motor automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power supply with a quality corresponding to IEC 60146-1-1, class C, to ensure correct motor operation at phase unbalance. This also ensures long life of the components.

7.5 Connection terminals

The descriptions and terminal overviews in this section apply to both single- and three-phase motors.
For maximum torques, see section Torques, page
71.
7.5.1 Connection terminals, CRE, CRIE, CRNE, SPKE and MTRE pumps
CRE, CRIE, CRNE, SPKE and MTRE pumps have a number of inputs and outputs enabling the pumps to be used in advanced applications where many inputs and outputs are required.
The pumps have these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector
outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
English (GB)
9
English (GB)
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
Digital input 1 is factory-set to be start-stop input where open circuit results in stop. A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation in their entire lengths.
• Inputs and outputs All inputs and outputs are internally separated from
the mains-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by protective extra-low voltage (PELV), thus ensuring protection against electric shock.
• Signal relay outputs – Signal relay 1:
LIVE: You can connect supply voltages up to 250 VAC . PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
– Signal relay 2:
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
• Mains supply (terminals N, PE, L or L1, L2, L3,
PE).
10
* If you use an external supply source, there must
be a connection to GND.
Fig. 8 Connection terminals, CRE, CRIE,
CRNE, SPKE and MTRE pumps
TM05 3509 3512
Terminal Type Function
Normally closed
NC
contact
C1 Common
Normally open
NO
contact
Normally closed
NC
contact
C2 Common
Normally open
NO
contact
18 GND Ground
11 DI4/OC2
Pt100/1000
19
input 2 Pt100/1000
17
input 1
12 AO
9 GND Ground
14 AI3
1DI2
Signal relay 1 (LIVE or PELV)
Signal relay 2 (PELV only)
Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive.
Pt100/1000 sensor input
Pt100/1000 sensor input
Analog output: 0-20 mA / 4-20 mA 0-10 V
Analog input: 0-20 mA / 4-20 mA 0-10 V
Digital input, configurable
Terminal Type Function
A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
23 GND Ground
25 GDS TX
24 GDS RX
7AI2
Supply to potentiometer and sensor
Grundfos Digital Sensor output
Grundfos Digital Sensor input
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
English (GB)
LiqTec sensor
21
input 1
20 GND
LiqTec sensor
22
input 2
10 DI3/OC1
4AI1
2DI1
5+5 V
6 GND Ground
LiqTec sensor input (white conductor)
Ground (brown and black conductors)
LiqTec sensor input (blue conductor)
Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive.
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
Digital input, configurable
Supply to potentiometer and sensor
11
7.5.2 Connection terminals, CME pumps
English (GB)
The CME pump has these connections:
• two analog inputs
• two digital inputs or one digital input and one
open-collector output
• Grundfos Digital Sensor input and output
• two signal relay outputs
• GENIbus connection.
See fig. 9.
Digital input 1 is factory-set to be start-stop input where open circuit results in stop. A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation in their entire lengths.
• Inputs and outputs All inputs and outputs are internally separated from
the mains-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by protective extra-low voltage (PELV), thus ensuring protection against electric shock.
• Signal relay outputs – Signal relay 1:
LIVE: You can connect supply voltages up to 250 VAC to the output. PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
– Signal relay 2:
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
• Mains supply (terminals N, PE, L or L1, L2, L3,
PE).
12
* If you use an external supply source, there must
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
be a connection to GND.
Fig. 9 Connection terminals, CME pump
(optional for CRE, CRIE, CRNE, SPKE and MTRE pumps)
Terminal Type Function
Normally
NC
closed contact
C1 Common
Normally open
NO
contact
Normally
NC
closed contact
C2 Common
Normally open
NO
contact
10 DI3/OC1
4AI1
2DI1
5+5 V
6 GND Ground
TM05 3510 3512
A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
23 GND Ground
25 GDS TX
24 GDS RX
7AI2
Signal relay 1 (LIVE or PELV)
Signal relay 2 (PELV only)
Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive.
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
Digital input, configurable
Supply to potentiometer and sensor
Supply to potentiometer and sensor
Grundfos Digital Sensor output
Grundfos Digital Sensor input
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
English (GB)
13

7.6 Signal cables

A
Y
B
A
Y
B
1
2 3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
English (GB)
• Use screened cables with a cross-sectional area
of minimum 0.5 mm the external on/off switch, digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to the frame at
both ends with good connection. The screens must be as close as possible to the terminals.
2
and maximum 1.5 mm2 for
See fig. 10.

7.7 Bus connection cable

7.7.1 New installations
For the bus connection, use a screened 3-core cable with a cross-sectional area of minimum 0.5 mm maximum 1.5 mm
If the motor is connected to a unit with a cable clamp which is identical to the one on the motor, connect
2
.
the screen to this cable clamp. If the unit has no cable clamp leave the screen
unconnected at this end. See fig. 11.
2
and
Fig. 10 Stripped cable with screen and wire
• Always tighten screws for frame connections
• The wires in the motor terminal box must be as
connections
whether a cable is fitted or not.
short as possible.
TM02 1325 4402
Fig. 11 Connection with screened 3-core cable
7.7.2 Replacing a motor
• If a 2-core cable is used in the installation, connect it as shown in fig. 12.
Fig. 12 Connection with screened 2-core cable
• If a screened 3-core cable is used in the installation, follow the instructions in section
7.7.1 New installations.
TM05 3973 1812TM02 8842 0904
14

8. Operating conditions

60
80
90
70
100
Altitude [m]
P2 [%]
60
80
90
70
100
Altitude [m]
P2 [%]

8.1 Maximum number of starts and stops

The number of starts and stops via the power supply must not exceed four times per hour.
When switched on via the power supply, the pump starts after approximately 5 seconds.
If a higher number of starts and stops is desired, use the input for external start-stop when starting/stopping the pump.
When started via an external on/off switch, the pump starts immediately.

8.2 Ambient temperature

8.2.1 Ambient temperature during storage and transportation
Minimum: -30 °C Maximum: 60 °C.
8.2.2 Ambient temperature during operation
3 x 200-240 V 3 x 380-500 V
Minimum -20 °C -20 °C Maximum 40 °C 50 °C
The motor can operate with the rated power output (P2) at 50 °C, but continuous operation at higher temperatures reduces the expected product life. If the motor is to operate at ambient temperatures between 50 and 60 °C, select an oversized motor. Contact Grundfos for further information.

8.3 Installation altitude

Installation altitude is the height above sea level of the installation site.
Motors installed up to 1000 m above sea level can be loaded 100 %.
The motors can be installed up to 3500 m above sea level.
Motors installed more than 1000 m above sea level must not be fully loaded due to the low density and consequent low cooling effect of the air.
0
500 1000 1500 2000 2500 3000 3500
Fig. 13 Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure correct clearance according to EN 60664-1:2007, you must adapt the supply voltage to the altitude:
English (GB)
TM05 5243 3717TM05 5243 3717
0
500 1000 1500 2000 2500 3000 3500
Fig. 14 Motor output power in relation to altitude
15
In order to maintain the galvanic isolation and ensure
500 480 460 440 420
380
400
0 500 1000 2000 2500 3000 3500
4000
1500
Supply voltage [V]
Altitude [m]
Supply voltage [V]
Altitude [m]
English (GB)
correct clearance according to EN 60664-1:2007, you must adapt the supply voltage to the altitude:
Fig. 15 Supply voltage for three-phase motor in
250
240
230
220
210
200
relation to altitude
0 500 1000 1500 2000 2500 3000 3500 4000

9. User interfaces

WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as the product may be very hot.
You can make the pump settings by means of the following user interfaces:
Control panels
• Standard control panel. See section 10. Standard control panel.
TM06 9866 3617TM06 9867 3617
• Advanced control panel. See section 11. Advanced control panel.
Remote controls
• Grundfos GO. See section 12. Grundfos GO.
• Grundfos R100 remote control. See section 13. Description of functions.
If the power supply to the pump is switched off, the settings are stored.
Fig. 16 Supply voltage for single-phase motor in
relation to altitude

8.4 Humidity

Maximum humidity: 95 %. If the humidity is constantly high and above 85 %,
open the drain holes in the drive-end flange. See section 6.7 Drain holes.

8.5 Motor cooling

To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate cooling is ensured. See section 6.5 Ensuring
motor cooling.
• The temperature of the cooling air must not exceed 50 °C.
• Keep cooling fins and fan blades clean.
16

10. Standard control panel

1
2
3
4
5
Stop
0
6
3
bar
The pumps are fitted with this control panel as standard.
Fig. 17 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
2-
3
4
5
Shows the operating status of the pump. For further information, see section 16. Grundfos Eye.
Light fields for indication of setpoint.
Up and down. Changes the setpoint.
Allows radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the pump and Grundfos GO or another pump, the green indicator light in Grundfos Eye on the pump flashes continuously. Press on the pump control panel to allow radio communication with Grundfos GO and other products of the same type.
Makes the pump ready for operation or starts and stops the pump.
Start
If you press the button when the pump is stopped, the pump only starts if no other functions with higher priority have been enabled. See section 15. Priority
of settings.
Stop
If you press the button when the pump is running, the pump always stops. The "Stop" text next to the button is on.

10.1 Setpoint setting

Set the desired setpoint of the pump by pressing or . The green light fields on the control panel indicate the setpoint set.
10.1.1 Pump in constant pressure control mode
The following example applies to a pump in an application where a pressure sensor gives a feedback to the pump. If the sensor is retrofitted to the pump, you must set it up manually as the pump does not automatically register a connected sensor. See section 13.6 Analog inputs.
Figure 18 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 3 bar with a sensor measuring range from 0 to 6 bar. The setting range is equal to the sensor measuring range.
TM05 4848 3512
Fig. 18 Setpoint set to 3 bar, constant pressure
control
English (GB)
TM05 4894 3512
17
10.1.2 Pump in constant-curve control mode
H
Q
Max.
Min.
H
Q
H
Q
English (GB)
In constant-curve control mode, the pump performance lies between the maximum and minimum curve of the pump. See fig. 19.
Fig. 19 Pump in constant-curve control mode
Setting to maximum curve:
•Press maximum curve of the pump (top light field flashes). When the top light field is on, press for 3 seconds until the light field starts flashing.
• To go back, press desired setpoint is indicated.
Example: Pump set to maximum curve. Figure 20 shows that the top light field is flashing,
indicating maximum curve.
Fig. 20 Maximum curve duty
Setting to minimum curve:
•Press minimum curve of the pump (bottom light field flashes). When the bottom light field is on, press
flashing.
• To go back, press continuously until the desired setpoint is indicated.
continuously to change over to the
continuously until the
continuously to change over to the
for 3 seconds until the light field starts
Example: Pump set to minimum curve. Figure 21 shows that the bottom light field is
flashing, indicating minimum curve.
Fig. 21 Minimum curve duty
10.1.3 Start-stop of pump
Stop the pump by pressing . When the pump is stopped, the "Stop" text next to the button is on. You
TM05 4895 2812TM05 4896 2812
can also stop the pump by continuously pressing until none of the light fields are on.
Start the pump by pressing pressing until the desired setpoint is indicated.
If you have stopped the pump by pressing , it can only be given free to operation by pressing again.
If you have stopped the pump by pressing , it can only be restarted by pressing .
You can also stop the pump with Grundfos GO or via a digital input set to External stop. See section
15. Priority of settings.
10.1.4 Resetting of fault indications
You can reset a fault indication in one of the following ways:
• Via the digital input if you have set it to Alarm resetting.
• Briefly press or not change the setting of the pump. You cannot reset a fault indication by pressing
• Switch off the power supply until the indicator lights are off.
• Switch the external start-stop input off and then on again.
• With Grundfos GO.
if the buttons have been locked.
or
or by continuously
on the pump. This does
TM05 4897 2812
18

11. Advanced control panel

1
2
3
4
5
6
The pumps can be fitted with the advanced control panel as an option.
Fig. 22 Advanced control panel
Pos. Symbol Description
Grundfos Eye Shows the operating status of the
1
2 - Graphical colour display.
3 Goes one step back.
4
pump. For further information, see section
16. Grundfos Eye.
Navigates between main menus, displays and digits. When you change the menu, the display always shows the top display of the new menu.
Navigates between submenus. Changes value settings. Note: If you have disabled the possibility to make settings with the Enable/disable settings function, then you can enable it again temporarily by pressing these buttons simultaneously for at least 5 seconds. See section
13.30 "Buttons on product" (Enable/disable settings).
Pos. Symbol Description
Saves changed values, resets alarms and expands the value field. Enables radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the pump
4
TM05 4849 1013
and Grundfos GO or another pump, the green indicator light in Grundfos Eye flashes. A note also appears in the pump display stating that a wireless device wants to connect to the pump. Press on the pump control panel to allow radio communication with Grundfos GO and other products of the same type.
Makes the pump ready for operation/starts and stops the pump. Start:
If you press the button when the pump is stopped, the pump only starts if no other functions with
5
higher priority have been enabled. See section 15. Priority of settings.
Stop: If you press the button when the
pump is running, the pump is always stopped. When you stop the pump via this button, the appears in the bottom of the display.
6 Goes to the Home menu.
English (GB)
icon
19

11.1 Home display

Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1 2 3 4
56789
Home
English (GB)
Fig. 23 Example of Home display
Pos. Symbol Description
Home This menu shows up to four user-defined parameters. You can
1
select parameters shown as shortcut icon , and when pressing you go directly to the "Settings" display for the selected parameter.
Status
2-
This menu shows the status of the pump and system as well as warnings and alarms.
Settings This menu gives access to all
3-
setting parameters. You can make detailed settings of the pump in this menu. See section 13. Description of
functions.
Assist This menu enables assisted pump
4-
5
6
setup, provides a short description of the control modes and offers fault advice. See section 13.41 Assist.
Indicates that the pump has been stopped via the
Indicates that the pump is functioning as master pump in a multipump system.
Indicates that the pump is
7
8
functioning as a slave pump in a multipump system.
Indicates that the pump is operating in a multipump system. See section 13.45 "Multi-pump
setup" (Setup of multi-pump system).
button.
Pos. Symbol Description
Indicates that the possibility to make settings has been disabled
9
for protective reasons. See section 13.30 "Buttons on
product" (Enable/disable settings).

11.2 Startup guide

The pump incorporates a startup guide which is started at the first startup. See section 13.38 Run
start-up guide. After the startup guide, the main
menus appear in the display.
TM06 4516 2415
20

11.3 Menu overview for advanced control panel

11.3.1 Home
Home
CRE, CRIE,
CRNE, SPKE,
MTRE
CME
Multipump
system
●●●
11.3.2 Status
Status
CRE, CRIE,
CRNE, SPKE,
MTRE
CME
Multipump
system
Operating status ●●●
Operating mode, from ●●● Control mode ●●●
Pump performance ●●●
Actual controlled value ●●● Resulting setpoint ●●● Speed ●●●
Acc. flow and specific energy ●●● Power and energy consumption ●●● Measured values ●●●
Analog input 1 ●●●
Analog input 2 ●●●
Analog input 3 ●●
1)
Pt100/1000 input 1 ●●1)●
Pt100/1000 input 2 ●●1)● Analog output ●●1)●
1)
1)
1)
1)
Warning and alarm ●●●
Actual warning or alarm ●●●
Warning log ●●●
Alarm log ●●● Operating log ●●●
Operating hours ●●● Fitted modules ●●● Date and time ●●● Product identification ●●● Motor bearing monitoring ●●● Multi-pump system
System operating status
System performance
System input power and energy
Pump 1, multi-pump system
Pump 2, multi-pump system
Pump 3, multi-pump system
Pump 4, multi-pump system
1)
Only available if an advanced functional module, type FM 300, is fitted.
English (GB)
21
11.3.3 "Settings"
English (GB)
Settings
CRE, CRIE,
CRNE,
SPKE, MTRE
CME
Multipump
system
Section Page
Setpoint ●●●13.1 Setpoint 28 Operating mode ●●●13.2 Operating mode 28 Set manual speed ●●●13.3 Set manual speed 28 "Set user-defined speed" ●●●13.4 "Set user-defined speed" 28 Control mode ●●●13.5 "Control mode" 28 Analog inputs ●●●
Analog input 1, setup ●●●
Analog input 2, setup ●●●
Analog input 3, setup ●●
1)
Pt100/1000 inputs ●●1)●
Pt100/1000 input 2, setup ●●1)●
13.6 Analog inputs 33
1)
1)
1)
13.7 Pt100/1000 inputs 35Pt100/1000 input 1, setup ●●1)●
1)
Digital inputs ●●●
13.8 Digital inputs 35Digital input 1, setup ●●●
Digital input 2, setup ●●
1)
1)
Digital inputs/outputs ●●●
13.9 Digital inputs/outputs 37Digital input/output 3, setup ●●●
Digital input/output 4, setup ●●
1)
Relay outputs ●●●
Relay output 2 ●●● Analog output ●●
1)
Function of analog output ●●1)●
Controller settings ●●●
1)
13.10 "Signal relays" 1 and 2 (Relay outputs)
1)
1)
13.11 Analog output 38Output signal ●●1)●
1)
13.12 "Controller" (Controller settings)
Operating range ●●●13.13 Operating range 41
Setpoint influence ●●●
Ext. setpoint infl. ●●●
Predefined setpoints ●●
1)
13.14 External setpoint function
13.14 External setpoint function
1)
13.15 Predefined setpoints 43
Monitoring functions ●●●
Motor bearing monitoring ●●●
Motor bearing maintenance ●●●
13.23 Motor bearing monitoring
"Bearings replaced" (Motor bearing maintenance)
Limit-exceeded function ●●●13.16 Limit-exceeded function 44
LiqTec function ●●●
1)
Only available if an advanced functional module, type FM 300, is fitted.
13 . 1 7 " L i qTec" ( L i q Te c function)
Continued on page 23.
38Relay output 1 ●●●
40
41
41
48
49
45
22
Continued from page 22.
Settings
Special functions ●●●
Low-flow stop function ●●●
Pipe filling function ●●●13.19 Pipe filling function 47
Pulse flowmeter setup ●●●
Ramps ●●●13.21 Ramps 48
Standstill heating ●●●13.22 Standstill heating 48 Communication ●●●
Pump number ●●●
Enable/disable radio comm. ●●●
General settings ●●●
Language ●●●13.27 Language 49
Set date and time ●●●
Units ●●●
Enable/disable settings ●●●
Delete history ●●●13.31 Delete history 50
Define Home display ●●●13.32 Define Home display 51
Display settings ●●●13.33 Display settings 51
Store actual settings ●●●
Recall stored settings ●●●
Run start-up guide ●●●13.38 Run start-up guide 52
1)
Only available if an advanced functional module, type FM 300, is fitted.
11.3.4 Assist
CRE, CRIE,
CRNE,
SPKE, MTRE
CME
Multipump
system
Section Page
13.18 "Stop function" (Low-flow stop function)
13.20 "Pulse flowmeter" (Pulse flowmeter setup)
13.25 "Number" (Pump number)
13.26 "Radio communication" (Enable/disable radio comm.)
13.28 "Date and time" (Set date and time)
13.29 "Unit configuration" (Units)
13.30 "Buttons on product" (Enable/disable settings)
13.34 "Store settings" (Store actual settings)
13.35 "Recall settings" (Recall stored settings)
45
48
49
49
50
50
50
51
51
English (GB)
Assist
Assisted pump setup ●●●13.42 Assisted pump setup 53 Setup, analog input ●●●13.43 Setup, analog input 53 Setting of date and time ●●●13.44 Setting of date and time 54
Setup of multi-pump system ●●●
Description of control mode ●●●
Assisted fault advice ●●●13.47 Assisted fault advice 57
CRE, CRIE,
CRNE,
SPKE, MTRE
CME
Multipump
system
Section Page
13.45 "Multi-pump setup" (Setup of multi-pump system)
13.46 Description of control mode
54
57
23

12. Grundfos GO

+
+
1
2
English (GB)
The pump is designed for wireless radio or infrared communication with Grundfos GO.
Grundfos GO enables setting of functions and gives access to status overviews, technical product information and actual operating parameters.
Grundfos GO offers the following mobile interfaces (MI).
Fig. 24 Grundfos GO communicating with the
Pos. Description
1
2
pump via radio or infrared connection (IR)
Grundfos MI 204: Add-on module enabling radio or infrared communication. You can use MI 204 in conjunction with an Apple iPhone or iPod with Lightning connector, e.g. fifth generation or later iPhone or iPod. MI 204 is also available together with an Apple iPod touch and a cover.
Grundfos MI 301: Separate module enabling radio or infrared communication. You can use the module in conjunction with an Android or iOS-based smart device with Bluetooth connection.

12.1 Communication

When Grundfos GO initiates communication with the pump, the indicator light in the middle of Grundfos Eye flashes green. See section 16. Grundfos Eye.
Furthermore, on pumps fitted with an advanced control panel a text appears in the display saying that a wireless device is trying to establish connection. Press on the pump in order to establish connection with Grundfos GO or press to reject connection.
Establish communication using one of these communication types:
• radio communication
• infrared communication.
12.1.1 Radio communication
Radio communication can take place at distances up to 30 m. The first time Grundfos GO communicates with the pump, you must enable communication by pressing or on the pump control panel. Later when communication takes place, the pump is
TM06 6256 0916
recognized by Grundfos GO and you can select the pump from the "List" menu.
12.1.2 Infrared communication
When communicating via infrared light, Grundfos GO must be pointed at the pump control panel.
24
Loading...
+ 54 hidden pages