The ability to draw current into the
terminal and guide it towards GND in
the internal circuitry.
The ability to push current out of the
terminal and into an external load
which must return it to GND.
Grundfos Digital Sensor.
Factory-fitted sensor in some
Grundfos pumps.
Proprietary Grundfos fieldbus
standard.
Ground fault circuit interrupter.
(USA and Canada).
Status indicator light.
Low voltage with the risk of electric
shock if the terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV
under normal conditions and under
single-fault conditions, except earth
faults in other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV
under normal conditions and under
single-fault conditions, including
earth faults in other circuits.
These installation and operating instructions are a
supplement to the installation and operating
instructions for the corresponding standard pumps
CR, CRI, CRN, SPK, MTR and CM. For instructions
not mentioned specifically in this manual, see the
installation and operating instructions for the
standard pump.
4. General description
Grundfos E-pumps are fitted with
frequency-controlled permanent-magnet motors for
single-phase or three-phase mains connection.
4.1 Pumps without factory-fitted sensor
The pumps have a built-in PI controller and can be
set for an external sensor enabling the control of the
following parameters:
• constant pressure
• constant differential pressure
• constant temperature
• constant differential temperature
• constant flow rate
• constant level
• constant curve
• constant other value.
The pumps have been factory-set to constant-curve
control mode. You can change the control mode with
R100 or Grundfos GO.
4.2 Pumps with factory-fitted pressure
sensor
The pumps have a built-in PI controller and are set
for a pressure sensor enabling the control of the
outlet pressure.
The pumps have been factory-set to
constant-pressure control mode. The pumps are
typically used to keep a constant pressure in
variable-demand systems.
4
4.3 Settings
The description of settings applies both to pumps
without factory-fitted sensor and to pumps with a
factory-fitted pressure sensor.
Setpoint
You can set the desired setpoint in three ways:
• on the pump control panel
• via an input for external setpoint signal
• with the Grundfos wireless R100 remote control
or Grundfos GO.
Other settings
Make all other settings with R100 or Grundfos GO.
You can read important parameters, such as the
actual value of the control parameter and power
consumption, via R100 or Grundfos GO.
If special or customised settings are required, use
Grundfos PC Tool. Contact your local Grundfos
company for more information.
4.4 Radio communication
This product incorporates a radio module for remote
control which is a class 1 device and which you can
use anywhere in the EU without restrictions.
For use in USA and Canada, see page 73.
Some variants of the product and products sold in
China and Korea have no radio module.
This product can communicate with the Grundfos
GO and other products of the same type via the
built-in radio module.
In some cases, an external antenna may be
required. Only Grundfos-approved external antennas
may be connected to this product, and only by a
Grundfos-approved installer.
4.5 Battery
A Li-ion battery is fitted in CRE, CRIE, CRNE, SPKE
and MTRE pumps. The Li-ion battery complies with
the Battery Directive (2006/66/EC). The battery does
not contain mercury, lead and cadmium.
5. Receiving the product
5.1 Transporting the product
WARNING
Falling objects
Death or serious personal injury
- Secure the product during
transportation to prevent it from tilting or
falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the
product.
• Motors from 2.2 to 5.5 kW: Do not stack more
than two motors in their original packaging.
• Motors from 5.5 to 11 kW: Do not stack the
motors.
5.2 Inspecting the product
Before you install the product, do the following.
1. Check that the product is as ordered.
2. Check that no visible parts have been damaged.
3. If parts are damaged or missing, contact your
local Grundfos sales company.
6. Mechanical installation
6.1 Handling the product
Observe local regulations setting limits for manual
lifting or handling. The motor weight is stated on the
nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
English (GB)
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting
equipment to the motor eyebolts when
handling the product.
Do not lift the product by the terminal box.
5
6.2 Mounting
D
B3B14B5
English (GB)
CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation
by bolts through the holes in the flange
or the base plate.
In order to maintain the UL mark,
additional requirements apply to the
equipment. See page 73.
6.3 Cable entries
See the size of the cable entries in section 29. Other
technical data.
6.4 Cable glands
The number and size of cable glands delivered with
the pump depends on the motor size. See section
29. Other technical data.
6.5 Ensuring motor cooling
Leave at least 50 mm between the end of the fan
cover and a wall or other fixed objects. See fig. 1.
Fig. 1Minimum distance (D) from the motor to
a wall or other fixed objects
6.6 Outdoor installation
If you install the motor outdoors, provide the motor
with a suitable cover and open the drain holes to
avoid condensation on the electronic components.
See figures 2 and 3.
When fitting a cover to the motor, observe
the guideline in section 6.5 Ensuring motor
cooling.
The cover must be sufficiently large to ensure that
the motor is not exposed to direct sunlight, rain or
snow. Grundfos does not supply covers. We
therefore recommend that you have a cover built for
the specific application. In areas with high humidity,
we recommend that you connect the motor
permanently to the mains supply and activate the
built-in standstill heating function. See section
13.22 Standstill heating, page 48.
Fig. 2Examples of covers (not supplied by
Grundfos)
In order to maintain the UL mark,
additional requirements apply to the
equipment. See page 73.
6.7 Drain holes
When the motor is installed in moist surroundings or
areas with high humidity, the bottom drain hole must
be open. The enclosure class of the motor will then
be lower. This helps prevent condensation in the
TM05 5236 3512
motor as the motor becomes self-venting, and it
allows water and humid air to escape.
The motor has a plugged drain hole on the drive
side. You can turn the flange 90 ° to both sides or
180 °.
TM05 3496 3512
6
TM02 9037 1604
Fig. 3Drain holes
7. Electrical installation
DANGER
Electric shock
- Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
minutes before you make any
connections in the terminal box. Make
sure that the power supply cannot be
accidentally switched on.
DANGER
Electric shock
- Death or serious personal injury
- Check that the supply voltage and
frequency correspond to the values
stated on the nameplate.
If the power supply cable is damaged, it must be
replaced by the manufacturer, the manufacturer's
service partner or a similarly qualified person.
The user or the installer is responsible for the
installation of correct earthing and protection
according to local regulations. All operations must be
carried out by a qualified electrician.
7.1 Protection against electric shock,
indirect contact
WARNING
Electric shock
- Death or serious personal injury
- Connect the motor to a protective earth
and provide protection against indirect
contact in accordance with local
regulations.
Protective-earth conductors must always have a
yellow/green (PE) or yellow/green/blue (PEN) colour
marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage
transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The
motor incorporates thermal protection against slow
overloading and blocking.
7.2 Cable requirements
7.2.1 Cable cross-section
DANGER
Electric shock
- Death or serious personal injury
- Always comply with local regulations as
to cable cross-sections.
1 x 200-230 V
Power
[kW]
0.25 - 1.5
3 x 380-500 V
Power
[kW]
0.25 - 2.2
3.0 - 11
3 x 200-240 V
Power
[kW]
1.1 - 1.5
2.2 - 5.5
7.2.2 Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 60 °C
(140 °F).
Temperature rating for outer cable sheath: 75 °C
(167 °F).
- Use the recommended fuse size. See
section 26.1 Supply voltage.
7.3.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If you want to supply the motor through an
IT network, make sure that you have a
suitable motor variant. If you are in doubt,
contact Grundfos.
The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
earth conductor which must be so long that it is the
last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 26.1 Supply
voltage.
Fig. 4Example of a mains-connected motor
with mains switch, backup fuse and
additional protection
The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
earth conductor which must be so long that it is the
last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
In order to avoid loose connections, make sure that
you have pressed home the terminal block for L1, L2
and L3 in its socket when you connect the supply
cable.
For maximum backup fuse, see section 27.1 Supply
voltage.
Only the following motors can be supplied through
an IT network:
• Motors with speed of 1450-2000/2200 rpm and
• Motors with speed of 2900-4000 rpm or
If you want to supply the motor through an
IT network, make sure that you have a
suitable motor variant. If you are in doubt,
contact Grundfos.
up to 1.5 kW
4000-5900 rpm and up to 2.2 kW.
Corner earthing is not allowed for supply
voltages above 3 x 240 V and 3 x 480 V,
50/60 Hz.
TM05 4034 1912TM05 3494 1512
Fig. 6Example of a mains-connected motor
with mains switch, backup fuses and
additional protection
TM05 3942 1812TM05 3495 1512
Fig. 5Mains connection, single-phase motors
7.3.2 Three-phase supply voltage
Three-phase motors are available for the voltages
below:
Fig. 7Mains connection, three-phase motors
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
8
7.4 Additional protection
DANGER
Electric shock
- Death or serious personal injury
- Only use residual-current circuit
breakers (ELCB, GFCI, RCD) of type B.
The residual-current circuit breaker must be marked
with the following symbol:
The total leakage current of all the electrical
equipment in the installation must be taken into
account. You find the leakage current of the motor in
sections 26.2 Leakage current and 27.2 Leakage
current (AC).
This product can cause a direct current in the
protective earth conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of
unstable power supply or a faulty installation. The
motor is stopped if the voltage falls outside the
permissible voltage range. The motor restarts
automatically when the voltage is again within the
permissible voltage range. Therefore, no additional
protection relay is required.
The motor is protected against transients
from the power supply according to EN
61800-3. In areas with high lightning
intensity, we recommend external lightning
protection.
Overload protection
If the upper load limit is exceeded, the motor
automatically compensates for this by reducing the
speed and stops if the overload condition persists.
The motor remains stopped for a set period. After
this period, the motor automatically attempts to
restart. The overload protection prevents damage to
the motor. Consequently, no additional motor
protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor
as an additional protection. When the temperature
rises above a certain level, the motor automatically
compensates for this by reducing the speed and
stops if the temperature keeps rising. The motor
remains stopped for a set period. After this period,
the motor automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power
supply with a quality corresponding to IEC
60146-1-1, class C, to ensure correct motor
operation at phase unbalance. This also ensures
long life of the components.
7.5 Connection terminals
The descriptions and terminal overviews in this
section apply to both single- and three-phase
motors.
For maximum torques, see section Torques, page
71.
7.5.1 Connection terminals, CRE, CRIE, CRNE,
SPKE and MTRE pumps
CRE, CRIE, CRNE, SPKE and MTRE pumps have a
number of inputs and outputs enabling the pumps to
be used in advanced applications where many inputs
and outputs are required.
The pumps have these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector
outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
English (GB)
9
English (GB)
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
Digital input 1 is factory-set to be start-stop
input where open circuit results in stop. A
jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if
digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by
reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from
the mains-conducting parts by reinforced insulation
and galvanically separated from other circuits. All
control terminals are supplied by protective extra-low
voltage (PELV), thus ensuring protection against
electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250
VAC .
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
• Mains supply (terminals N, PE, L or L1, L2, L3,
PE).
10
* If you use an external supply source, there must
be a connection to GND.
Fig. 8Connection terminals, CRE, CRIE,
CRNE, SPKE and MTRE pumps
TM05 3509 3512
Terminal TypeFunction
Normally closed
NC
contact
C1Common
Normally open
NO
contact
Normally closed
NC
contact
C2Common
Normally open
NO
contact
18GNDGround
11DI4/OC2
Pt100/1000
19
input 2
Pt100/1000
17
input 1
12AO
9GNDGround
14AI3
1DI2
Signal relay 1
(LIVE or PELV)
Signal relay 2
(PELV only)
Digital input/output,
configurable.
Open collector: Max.
24 V resistive or
inductive.
Pt100/1000 sensor
input
Pt100/1000 sensor
input
Analog output:
0-20 mA / 4-20 mA
0-10 V
Analog input:
0-20 mA / 4-20 mA
0-10 V
Digital input,
configurable
Terminal TypeFunction
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
8+24 VSupply
26+5 V
23GNDGround
25GDS TX
24GDS RX
7AI2
Supply to
potentiometer and
sensor
Grundfos Digital
Sensor output
Grundfos Digital
Sensor input
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
English (GB)
LiqTec sensor
21
input 1
20GND
LiqTec sensor
22
input 2
10DI3/OC1
4AI1
2DI1
5+5 V
6GNDGround
LiqTec sensor input
(white conductor)
Ground (brown and
black conductors)
LiqTec sensor input
(blue conductor)
Digital input/output,
configurable.
Open collector: Max.
24 V resistive or
inductive.
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
Digital input,
configurable
Supply to
potentiometer and
sensor
11
7.5.2 Connection terminals, CME pumps
English (GB)
The CME pump has these connections:
• two analog inputs
• two digital inputs or one digital input and one
open-collector output
• Grundfos Digital Sensor input and output
• two signal relay outputs
• GENIbus connection.
See fig. 9.
Digital input 1 is factory-set to be start-stop
input where open circuit results in stop. A
jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if
digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by
reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from
the mains-conducting parts by reinforced insulation
and galvanically separated from other circuits. All
control terminals are supplied by protective extra-low
voltage (PELV), thus ensuring protection against
electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250
VAC to the output.
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
• Mains supply (terminals N, PE, L or L1, L2, L3,
PE).
12
* If you use an external supply source, there must
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
be a connection to GND.
Fig. 9Connection terminals, CME pump
(optional for CRE, CRIE, CRNE, SPKE
and MTRE pumps)
Terminal TypeFunction
Normally
NC
closed contact
C1Common
Normally open
NO
contact
Normally
NC
closed contact
C2Common
Normally open
NO
contact
10DI3/OC1
4AI1
2DI1
5+5 V
6GNDGround
TM05 3510 3512
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
8+24 VSupply
26+5 V
23GNDGround
25GDS TX
24GDS RX
7AI2
Signal relay 1
(LIVE or PELV)
Signal relay 2
(PELV only)
Digital input/output,
configurable.
Open collector: Max.
24 V resistive or
inductive.
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
Digital input,
configurable
Supply to
potentiometer and
sensor
Supply to
potentiometer and
sensor
Grundfos Digital
Sensor output
Grundfos Digital
Sensor input
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
English (GB)
13
7.6 Signal cables
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
English (GB)
• Use screened cables with a cross-sectional area
of minimum 0.5 mm
the external on/off switch, digital inputs, setpoint
and sensor signals.
• Connect the screens of the cables to the frame at
both ends with good connection. The screens
must be as close as possible to the terminals.
2
and maximum 1.5 mm2 for
See fig. 10.
7.7 Bus connection cable
7.7.1 New installations
For the bus connection, use a screened 3-core cable
with a cross-sectional area of minimum 0.5 mm
maximum 1.5 mm
If the motor is connected to a unit with a cable clamp
which is identical to the one on the motor, connect
2
.
the screen to this cable clamp.
If the unit has no cable clamp leave the screen
unconnected at this end. See fig. 11.
2
and
Fig. 10 Stripped cable with screen and wire
• Always tighten screws for frame connections
• The wires in the motor terminal box must be as
connections
whether a cable is fitted or not.
short as possible.
TM02 1325 4402
Fig. 11 Connection with screened 3-core cable
7.7.2 Replacing a motor
• If a 2-core cable is used in the installation,
connect it as shown in fig. 12.
Fig. 12 Connection with screened 2-core cable
• If a screened 3-core cable is used in the
installation, follow the instructions in section
7.7.1 New installations.
TM05 3973 1812TM02 8842 0904
14
8. Operating conditions
60
80
90
70
100
Altitude [m]
P2 [%]
60
80
90
70
100
Altitude [m]
P2 [%]
8.1 Maximum number of starts and stops
The number of starts and stops via the power supply
must not exceed four times per hour.
When switched on via the power supply, the pump
starts after approximately 5 seconds.
If a higher number of starts and stops is desired, use
the input for external start-stop when
starting/stopping the pump.
When started via an external on/off switch, the pump
starts immediately.
8.2 Ambient temperature
8.2.1 Ambient temperature during storage and
transportation
Minimum: -30 °C
Maximum: 60 °C.
8.2.2 Ambient temperature during operation
3 x 200-240 V3 x 380-500 V
Minimum-20 °C-20 °C
Maximum40 °C50 °C
The motor can operate with the rated power output
(P2) at 50 °C, but continuous operation at higher
temperatures reduces the expected product life. If
the motor is to operate at ambient temperatures
between 50 and 60 °C, select an oversized motor.
Contact Grundfos for further information.
8.3 Installation altitude
Installation altitude is the height above sea level of
the installation site.
Motors installed up to 1000 m above sea level can
be loaded 100 %.
The motors can be installed up to 3500 m above sea
level.
Motors installed more than 1000 m above
sea level must not be fully loaded due to
the low density and consequent low
cooling effect of the air.
0
500 1000 1500 2000 2500 3000 3500
Fig. 13 Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure
correct clearance according to EN 60664-1:2007,
you must adapt the supply voltage to the altitude:
English (GB)
TM05 5243 3717TM05 5243 3717
0
500 1000 1500 2000 2500 3000 3500
Fig. 14 Motor output power in relation to altitude
15
In order to maintain the galvanic isolation and ensure
500
480
460
440
420
380
400
0 500 10002000 2500 3000 3500
4000
1500
Supply voltage [V]
Altitude [m]
Supply voltage [V]
Altitude [m]
English (GB)
correct clearance according to EN 60664-1:2007,
you must adapt the supply voltage to the altitude:
Fig. 15 Supply voltage for three-phase motor in
250
240
230
220
210
200
relation to altitude
0 500 1000 1500 2000 2500 3000 3500 4000
9. User interfaces
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as
the product may be very hot.
You can make the pump settings by means of the
following user interfaces:
Control panels
• Standard control panel.
See section 10. Standard control panel.
TM06 9866 3617TM06 9867 3617
• Advanced control panel.
See section 11. Advanced control panel.
Remote controls
• Grundfos GO.
See section 12. Grundfos GO.
• Grundfos R100 remote control.
See section 13. Description of functions.
If the power supply to the pump is switched off, the
settings are stored.
Fig. 16 Supply voltage for single-phase motor in
relation to altitude
8.4 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %,
open the drain holes in the drive-end flange. See
section 6.7 Drain holes.
8.5 Motor cooling
To ensure cooling of motor and electronics, observe
the following:
• Position the motor in such a way that adequate
cooling is ensured. See section 6.5 Ensuring
motor cooling.
• The temperature of the cooling air must not
exceed 50 °C.
• Keep cooling fins and fan blades clean.
16
10. Standard control panel
1
2
3
4
5
Stop
0
6
3
bar
The pumps are fitted with this control panel as
standard.
Fig. 17 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
2-
3
4
5
Shows the operating status of the
pump.
For further information, see
section 16. Grundfos Eye.
Light fields for indication of
setpoint.
Up and down. Changes the
setpoint.
Allows radio communication with
Grundfos GO and other products
of the same type.
When you try to establish radio
communication between the
pump and Grundfos GO or
another pump, the green indicator
light in Grundfos Eye on the pump
flashes continuously. Press on
the pump control panel to allow
radio communication with
Grundfos GO and other products
of the same type.
Makes the pump ready for
operation or starts and stops the
pump.
Start
If you press the button when the
pump is stopped, the pump only
starts if no other functions with
higher priority have been
enabled. See section 15. Priority
of settings.
Stop
If you press the button when the
pump is running, the pump always
stops. The "Stop" text next to the
button is on.
10.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or . The green light fields on the control panel
indicate the setpoint set.
10.1.1 Pump in constant pressure control mode
The following example applies to a pump in an
application where a pressure sensor gives a
feedback to the pump. If the sensor is retrofitted to
the pump, you must set it up manually as the pump
does not automatically register a connected sensor.
See section 13.6 Analog inputs.
Figure 18 shows that the light fields 5 and 6 are
activated, indicating a desired setpoint of 3 bar with
a sensor measuring range from 0 to 6 bar. The
setting range is equal to the sensor measuring
range.
TM05 4848 3512
Fig. 18 Setpoint set to 3 bar, constant pressure
control
English (GB)
TM05 4894 3512
17
10.1.2 Pump in constant-curve control mode
H
Q
Max.
Min.
H
Q
H
Q
English (GB)
In constant-curve control mode, the pump
performance lies between the maximum and
minimum curve of the pump. See fig. 19.
Fig. 19 Pump in constant-curve control mode
Setting to maximum curve:
•Press
maximum curve of the pump (top light field
flashes). When the top light field is on, press
for 3 seconds until the light field starts flashing.
• To go back, press
desired setpoint is indicated.
Example: Pump set to maximum curve.
Figure 20 shows that the top light field is flashing,
indicating maximum curve.
Fig. 20 Maximum curve duty
Setting to minimum curve:
•Press
minimum curve of the pump (bottom light field
flashes). When the bottom light field is on, press
flashing.
• To go back, press continuously until the
desired setpoint is indicated.
continuously to change over to the
continuously until the
continuously to change over to the
for 3 seconds until the light field starts
Example: Pump set to minimum curve.
Figure 21 shows that the bottom light field is
flashing, indicating minimum curve.
Fig. 21 Minimum curve duty
10.1.3 Start-stop of pump
Stop the pump by pressing . When the pump is
stopped, the "Stop" text next to the button is on. You
TM05 4895 2812TM05 4896 2812
can also stop the pump by continuously pressing
until none of the light fields are on.
Start the pump by pressing
pressing until the desired setpoint is indicated.
If you have stopped the pump by pressing , it can
only be given free to operation by pressing again.
If you have stopped the pump by pressing , it can
only be restarted by pressing .
You can also stop the pump with Grundfos GO or via
a digital input set to External stop. See section
15. Priority of settings.
10.1.4 Resetting of fault indications
You can reset a fault indication in one of the
following ways:
• Via the digital input if you have set it to Alarm
resetting.
• Briefly press or
not change the setting of the pump.
You cannot reset a fault indication by pressing
• Switch off the power supply until the indicator
lights are off.
• Switch the external start-stop input off and then
on again.
• With Grundfos GO.
if the buttons have been locked.
or
or by continuously
on the pump. This does
TM05 4897 2812
18
11. Advanced control panel
1
2
3
4
5
6
The pumps can be fitted with the advanced control
panel as an option.
Fig. 22 Advanced control panel
Pos. Symbol Description
Grundfos Eye
Shows the operating status of the
1
2-Graphical colour display.
3Goes one step back.
4
pump.
For further information, see section
16. Grundfos Eye.
Navigates between main menus,
displays and digits.
When you change the menu, the
display always shows the top
display of the new menu.
Navigates between submenus.
Changes value settings.
Note: If you have disabled the
possibility to make settings with the
Enable/disable settings function,
then you can enable it again
temporarily by pressing these
buttons simultaneously for at least
5 seconds. See section
13.30 "Buttons on product"
(Enable/disable settings).
Pos. Symbol Description
Saves changed values, resets
alarms and expands the value field.
Enables radio communication with
Grundfos GO and other products of
the same type.
When you try to establish radio
communication between the pump
4
TM05 4849 1013
and Grundfos GO or another pump,
the green indicator light in Grundfos
Eye flashes. A note also appears in
the pump display stating that a
wireless device wants to connect to
the pump. Press on the pump
control panel to allow radio
communication with Grundfos GO
and other products of the same
type.
Makes the pump ready for
operation/starts and stops the
pump.
Start:
If you press the button when the
pump is stopped, the pump only
starts if no other functions with
5
higher priority have been enabled.
See section 15. Priority of settings.
Stop:
If you press the button when the
pump is running, the pump is
always stopped. When you stop the
pump via this button, the
appears in the bottom of the
display.
6Goes to the Home menu.
English (GB)
icon
19
11.1 Home display
Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1234
56789
Home
English (GB)
Fig. 23 Example of Home display
Pos. Symbol Description
Home
This menu shows up to four
user-defined parameters. You can
1
select parameters shown as
shortcut icon , and when
pressing you go directly to the
"Settings" display for the selected
parameter.
Status
2-
This menu shows the status of the
pump and system as well as
warnings and alarms.
Settings
This menu gives access to all
3-
setting parameters. You can make
detailed settings of the pump in
this menu.
See section 13. Description of
functions.
Assist
This menu enables assisted pump
4-
5
6
setup, provides a short
description of the control modes
and offers fault advice.
See section 13.41 Assist.
Indicates that the pump has been
stopped via the
Indicates that the pump is
functioning as master pump in a
multipump system.
Indicates that the pump is
7
8
functioning as a slave pump in a
multipump system.
Indicates that the pump is
operating in a multipump system.
See section 13.45 "Multi-pump
setup" (Setup of multi-pump
system).
button.
Pos. Symbol Description
Indicates that the possibility to
make settings has been disabled
9
for protective reasons. See
section 13.30 "Buttons on
product" (Enable/disable
settings).
11.2 Startup guide
The pump incorporates a startup guide which is
started at the first startup. See section 13.38 Run
start-up guide. After the startup guide, the main
menus appear in the display.
TM06 4516 2415
20
11.3 Menu overview for advanced control panel
11.3.1 Home
Home
CRE, CRIE,
CRNE, SPKE,
MTRE
CME
Multipump
system
●●●
11.3.2 Status
Status
CRE, CRIE,
CRNE, SPKE,
MTRE
CME
Multipump
system
Operating status●●●
Operating mode, from●●●
Control mode●●●
Pump performance●●●
Actual controlled value●●●
Resulting setpoint●●●
Speed●●●
Acc. flow and specific energy●●●
Power and energy consumption●●●
Measured values●●●
Analog input 1●●●
Analog input 2●●●
Analog input 3●●
1)
Pt100/1000 input 1●●1)●
Pt100/1000 input 2●●1)●
Analog output●●1)●
1)
●
1)
1)
1)
Warning and alarm●●●
Actual warning or alarm●●●
Warning log●●●
Alarm log●●●
Operating log●●●
Operating hours●●●
Fitted modules●●●
Date and time●●●
Product identification●●●
Motor bearing monitoring●●●
Multi-pump system●
System operating status●
System performance●
System input power and energy●
Pump 1, multi-pump system●
Pump 2, multi-pump system●
Pump 3, multi-pump system●
Pump 4, multi-pump system●
1)
Only available if an advanced functional module, type FM 300, is fitted.
English (GB)
21
11.3.3 "Settings"
English (GB)
Settings
CRE, CRIE,
CRNE,
SPKE, MTRE
CME
Multipump
system
SectionPage
Setpoint●●●13.1 Setpoint28
Operating mode●●●13.2 Operating mode28
Set manual speed●●●13.3 Set manual speed28
"Set user-defined speed"●●●13.4 "Set user-defined speed"28
Control mode●●●13.5 "Control mode"28
Analog inputs●●●
Only available if an advanced functional module, type FM 300, is fitted.
11.3.4 Assist
CRE, CRIE,
CRNE,
SPKE, MTRE
CME
Multipump
system
SectionPage
13.18 "Stop function"
(Low-flow stop function)
13.20 "Pulse flowmeter"
(Pulse flowmeter setup)
13.25 "Number" (Pump
number)
13.26 "Radio communication"
(Enable/disable radio comm.)
13.28 "Date and time" (Set
date and time)
13.29 "Unit configuration"
(Units)
13.30 "Buttons on product"
(Enable/disable settings)
13.34 "Store settings" (Store
actual settings)
13.35 "Recall settings" (Recall
stored settings)
45
48
49
49
50
50
50
51
51
English (GB)
Assist
Assisted pump setup●●●13.42 Assisted pump setup53
Setup, analog input●●●13.43 Setup, analog input53
Setting of date and time●●●13.44 Setting of date and time54
13.45 "Multi-pump setup"
(Setup of multi-pump system)
13.46 Description of control
mode
54
57
23
12. Grundfos GO
+
+
1
2
English (GB)
The pump is designed for wireless radio or infrared
communication with Grundfos GO.
Grundfos GO enables setting of functions and gives
access to status overviews, technical product
information and actual operating parameters.
Grundfos GO offers the following mobile interfaces
(MI).
Fig. 24 Grundfos GO communicating with the
Pos. Description
1
2
pump via radio or infrared connection
(IR)
Grundfos MI 204:
Add-on module enabling radio or infrared
communication. You can use MI 204 in
conjunction with an Apple iPhone or iPod
with Lightning connector, e.g. fifth
generation or later iPhone or iPod.
MI 204 is also available together with an
Apple iPod touch and a cover.
Grundfos MI 301:
Separate module enabling radio or infrared
communication. You can use the module in
conjunction with an Android or iOS-based
smart device with Bluetooth connection.
12.1 Communication
When Grundfos GO initiates communication with the
pump, the indicator light in the middle of Grundfos
Eye flashes green. See section 16. Grundfos Eye.
Furthermore, on pumps fitted with an advanced
control panel a text appears in the display saying
that a wireless device is trying to establish
connection. Press on the pump in order to
establish connection with Grundfos GO or press
to reject connection.
Establish communication using one of these
communication types:
• radio communication
• infrared communication.
12.1.1 Radio communication
Radio communication can take place at distances up
to 30 m. The first time Grundfos GO communicates
with the pump, you must enable communication by
pressing or on the pump control panel. Later
when communication takes place, the pump is
TM06 6256 0916
recognized by Grundfos GO and you can select the
pump from the "List" menu.
12.1.2 Infrared communication
When communicating via infrared light, Grundfos GO
must be pointed at the pump control panel.
24
Loading...
+ 54 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.