English (GB) Installation and operating instructions
Original installation and operating instructions
These installation and operating instructions
describe Grundfos NS and PF.
Sections 1-3 give the information necessary to be
able to unpack, install and start up the product in a
safe way.
Sections 4-9 give important information about the
product, as well as information on service, fault
finding and disposal of the product.
CONTENTS
Page
1.General information
1.1 Target group
2.Installing the product
2.Installing the product
2.1 Pump location
2.2 Mechanical installation
2.3 Electrical connection
3.Starting up the product
3.1 Priming
4.Handling and storing the product
4.1 Handling the product
4.2 Storing the product
5.Product introduction
5.1 Product description
5.3 Applications
6.Maintaining the product
7.Fault finding
8.Technical data
8.1 Operating conditions
8.2 Mechanical data
8.3 Electrical data
9.Disposing of the product
Read this document before installing the
product. Installation and operation must
comply with local regulations and accepted
codes of good practice.
This appliance can be used by children
aged from 8 years and above and persons
with reduced physical, sensory or mental
capabilities or lack of experience and
knowledge if they have been given
supervision or instruction concerning use
of the appliance in a safe way and
understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not
be made by children without supervision.
Make sure that the system in which the
pump is incorporated is designed for the
maximum pump pressure.
This pump has been evaluated for use with
water only.
1. General information
1.1 Target group
These installation and operating instructions are
3
intended for professional installers.
3
4
1.2 Hazard statements
4
The symbols and hazard statements below may
4
appear in Grundfos installation and operating
4
instructions, safety instructions and service
4
instructions.
6
7
7
7
7
7
7
8
8
9
10
10
11
12
The hazard statements are structured in the
12
following way:
DANGER
Indicates a hazardous situation which, if
not avoided, will result in death or serious
personal injury.
WARNING
Indicates a hazardous situation which, if
not avoided, could result in death or
serious personal injury.
CAUTION
Indicates a hazardous situation which, if
not avoided, could result in minor or
moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
English (GB)
3
1.3 Notes
English (GB)
The symbols and notes below may appear in
Grundfos installation and operating instructions,
safety instructions and service instructions.
Observe these instructions for explosionproof products.
A blue or grey circle with a white graphical
symbol indicates that an action must be
taken.
A red or grey circle with a diagonal bar,
possibly with a black graphical symbol,
indicates that an action must not be taken
or must be stopped.
If these instructions are not observed, it
may result in malfunction or damage to the
equipment.
Tips and advice that make the work easier.
2. Installing the product
Observe local regulations concerning
limits for manual lifting or handling.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Use safety shoes when handling the
pump.
2.1 Pump location
Install the pump in a dry well-ventilated location.
Protect the pump from rain, frost and direct sunlight.
We recommend that you place the pump as close as
possible to the liquid to be pumped.
2.2 Mechanical installation
2.2.1 Foundation
Fasten the pump to a solid horizontal foundation by
means of screws through the holes in the base plate.
NS pumps can be installed in horizontal or vertical
position. If the pump is installed in vertical position,
the motor must be above the pump.
PF pumps must only be installed in horizontal
position.
2.2.2 Pipework
Make sure that the pump is not stressed by the
pipework.
Fit rigid pipes with pipe hangers.
Use sealing tape on the inlet and outlet ports of the
pump.
4
2.3 Electrical connection
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product,
make sure that the power supply has
been switched off and that it cannot be
accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
- The protective earth of the socket outlet
must be connected to the protective
earth of the pump. The plug must
therefore have the same PE connection
system as that of the socket outlet. If
not, use a suitable adapter.
We recommend that you fit the permanent
installation with a residual-current circuit
breaker, RCCB, with a tripping current less
than 30 mA.
DANGER
Electric shock
Death or serious personal injury
- If the pump is used for cleaning or other
maintenance of swimming pools,
garden ponds or similar places, make
sure that the pump is supplied through a
residual-current circuit breaker, RCCB,
with a tripping current of 30 mA.
DANGER
Electric shock
Death or serious personal injury
- Power supply cables without a plug
must be connected to a supply
disconnecting device incorporated in
the fixed wiring according to the local
wiring rules.
DANGER
Electric shock
Death or serious personal injury
- The pump must be earthed.
2.3.1 Wiring diagram
Red
Blue
Black
NL
Capacitor
Red
Blue
Black
Capacitor
White
Red
W2
W1
V2
U1
Blue
Blue
Capacitor
Brown
Ground
Motor protection
Motor
Line
White
Red
Motor
Blue
Blue
Power supply
Earth
Motor protection
Capacitor
Brown
Wiring diagram A
Fig. 1Wiring diagram A for single-phase pumps
Wiring diagram B
English (GB)
TM06 4453 2315
Fig. 2Wiring diagram B for single-phase pumps
TM06 4451 2315
5
Wiring diagram C
LINE 230 V - 220-277 V
W2
U2
V2
U1
V1
W1
White
Red
Blue
RedBlueWhite
3 230/400
3 ~ 220-277/380-480
MOTOR
LINE 400 V - 380-480 V
W2
U2
V2
U1
V1
W1
White
Red
Blue
RedBlueWhite
3 230/400
3 ~ 220-277/380-480
MOTOR
Blue
Red
White
Blue
Red
White
Blue
Red
White
Blue
Red
White
Three-phase
230/400
Three-phase
220-277 / 380-480
Motor
Three-phase
230/400
Three-phase
220-277 / 380-480
Motor
Voltage
230 V - 220-277 V
Voltage
400 V - 380-480 V
English (GB)
Fig. 3Wiring diagram C for three-phase
Pump
PF 1-30
PF 2-50
NS 4-23
NS 5-33
NS 13-18
NS 3-40
NS 5-50
NS 5-60
NS 6-30
NS 6-40
NS 30-18
NS 30-18
NS 30-36
6
pumps
Voltage
[V]
220-240A
220-240B
3 x 400CNS 30-30
Wiring
diagram
3. Starting up the product
WARNING
Flammable material
Death or serious personal injury
- Do not use the pump for flammable
liquids, such as diesel oil, petrol or
similar liquids.
DANGER
Electric shock
Death or serious personal injury
- Do not use the pump in swimming
pools, garden ponds or similar places if
there are people in the water.
CAUTION
Hot surface
Minor or moderate personal injury
- Do not run pump continuously with a
closed inlet or outlet valve.
CAUTION
Hot or cold liquid
Minor or moderate personal injury
- Make sure that the escaping hot or cold
liquid does not cause injury to persons
or damage to the equipment.
WARNING
Corrosive substance
Death or serious personal injury
TM06 7750 3916
- Do not use the pump for aggressive
liquids.
CAUTION
Hot surface
Minor or moderate personal injury
- Use protective gloves if the liquid or
ambient temperature is higher than
40 °C.
CAUTION
Impurities in water
Minor or moderate personal injury
- Flush the system with clean water to
remove all impurities before you start
the pump.
3.1 Priming
1. Remove the priming plug. Use a flat-blade
screwdriver if the priming plug is tight.
2. Fill the pump housing with water.
3. Fit the priming plug and screw it tight by hand
only.
Always tighten plastic plugs by hand to
avoid damage to the threads.
Fig. 4Priming the NS pump
Fig. 5Priming the PF pump
4. Handling and storing the product
4.1 Handling the product
Use lifting equipment when handling the
product.
Do not drop or shake the product.
4.2 Storing the product
Store the product indoors in a dry and dust-free
environment. Protect the product from vibrations.
Storage temperature: -10 to +40 °C.
5. Product introduction
5.1 Product description
Grundfos NS pumps are centrifugal pumps designed
TM06 7290 3716TM06 7291 3716
for lifting water in domestic, industrial and
agricultural installations.
The pumps come in two versions:
• single-impeller pumps
• twin-impeller pumps.
Grundfos PF pumps are compact peripheral
Light industrial
applications, such as
feeding pressurised boilers
(anticondensation)
Light gardening
applications
TM06 8363 0816
Water supply●
Draining and filling of
cisterns
Grundfos NSGrundfos
6. Maintaining the product
In normal operation, the pump does not require any
specific maintenance.
DANGER
Electric shock
Death or serious personal injury
- If the power supply cable is damaged, it
must be replaced by the manufacturer,
his service agent or similarly qualified
persons in order to avoid hazard.