The ability to draw current into the
terminal and guide it towards earth in
the internal circuitry.
The ability to push current out of the
terminal and into an external load
which must return it to earth.
Grundfos Digital Sensor.
Factory-fitted sensor in some
Grundfos pumps.
Proprietary Grundfos fieldbus
standard.
Ground fault circuit interrupter.
USA and Canada.
Status indicator light.
Low voltage with the risk of electric
shock if the terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV
under normal conditions and under
single-fault conditions, except earth
faults in other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV
under normal conditions and under
single-fault conditions, including earth
faults in other circuits.
Single-head pump without
factory-fitted differential-pressure
sensor.
Twin-head pump without factory-fitted
differential-pressure sensor.
Single-head pump (TPE, NBE, NKE)
and twin-head pump (TPED) with
factory-fitted differential-pressure
sensor.
These installation and operating instructions are a
supplement to the installation and operating
instructions for the corresponding standard pumps
TP, TPD, NB, NBG, NK and NKG. For instructions not
mentioned specifically in this manual, see the
installation and operating instructions for the
standard pump.
4. General description
The pumps are fitted with frequency-controlled
permanent-magnet motors for single-phase or
three-phase mains connection.
4.1 Radio communication
This product incorporates a radio module for remote
control which is a class 1 device and can be used
anywhere in the EU member states without
restrictions.
For use in USA and Canada, see page 71.
Some variants of the product and products sold in
China and Korea have no radio module.
This product can communicate with Grundfos GO
and other products of the same type via the built-in
radio module.
In some cases, an external antenna may be
required. Only Grundfos-approved external antennas
may be connected to this product, and only by a
Grundfos-approved installer.
4.2 Battery
Pumps fitted with the advanced functional module,
FM 300, incorporate a Li-ion battery. The Li-ion
battery complies with the Battery Directive
(2006/66/EC). The battery does not contain mercury,
lead and cadmium.
4
5. Receiving the product
D
5.1 Transporting the product
WARNING
Falling objects
Death or serious personal injury
- Secure the product during
transportation to prevent it from tilting or
falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the
product.
5.2 Inspecting the product
Before you install the product, do the following:
• Check that the product is as ordered.
• Check that no visible parts have been damaged.
If parts are damaged or missing, contact your local
Grundfos sales company.
6. Mechanical installation
6.1 Handling the product
Observe local regulations setting limits for manual
lifting or handling. The motor weight is stated on the
nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting
equipment to the motor eyebolts when
handling the product.
6.2 Mounting the product
CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation
by bolts through the holes in the flange
or the base plate.
In order to maintain the UL mark,
additional requirements apply to the
equipment. See page 71.
Secure the pump to a solid foundation by bolts
through the holes in the flange or the base plate.
6.3 Cable entries
See the size of the cable entries in section 29. Other
technical data.
6.4 Ensuring motor cooling
Leave at least 50 mm between the end of the fan
cover and a wall or other fixed objects. See fig. 1.
Fig. 1Minimum distance, D, from the motor to
a wall or other fixed objects
English (GB)
TM05 5236 3512
Do not lift the product by the terminal box.
5
6.5 Outdoor installation
B3B14B5
English (GB)
If you install the motor outdoors, provide the motor
with a cover and open the drain holes to avoid
condensation on the electronic components. See
figures 2 and 3.
When fitting a cover to the motor, observe
the guidelines in section 6.4 Ensuring
motor cooling.
The cover must be sufficiently large to ensure that
the motor is not exposed to direct sunlight, rain or
snow. Grundfos does not supply covers. We
therefore recommend that you have a cover built for
the specific application. In areas with high humidity,
we recommend that you connect the motor
permanently to the mains supply and activate the
built-in standstill heating function. See section
13.20 "Standstill heating", page 44.
Fig. 2Examples of covers, not supplied by
Grundfos
In order to maintain the UL mark,
additional requirements apply to the
equipment. See page 71.
6.6 Drain holes
When the motor is installed in moist surroundings or
areas with high humidity, the bottom drain hole must
be open. The enclosure class of the motor will then
be lower. This helps prevent condensation in the
motor as the motor becomes self-venting, and it
allows water and humid air to escape.
The motor has a plugged drain hole on the drive
side. You can turn the flange 90 ° to both sides or
180 °.
7. Electrical installation
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
minutes before you make any
connections in the terminal box. Make
sure that the power supply cannot be
accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
- Check that the supply voltage and
frequency correspond to the values
stated on the nameplate.
If the power supply cable is damaged, it must be
replaced by the manufacturer, the manufacturer's
service partner or a similarly qualified person.
The user or the installer is responsible for the
installation of correct earthing and protection
TM05 3496 3512
according to local regulations. All operations must be
carried out by a qualified electrician.
Carry out the electrical connection according to local
regulations.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Fig. 3Drain holes
6
TM02 9037 1604
7.1 Protection against electric shock,
indirect contact
WARNING
Electric shock
Death or serious personal injury
- Connect the motor to protective earth
and provide protection against indirect
contact in accordance with local
regulations.
Protective-earth conductors must always have a
yellow and green, PE, or yellow,green and blue,
PEN, colour marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage
transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The
motor incorporates thermal protection against slow
overloading and blocking.
7.2 Cable requirements
7.2.1 Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as
to cable cross-sections.
- Use the recommended fuse size. See
sections 26.1 Supply voltage and
27.1 Supply voltage.
7.3.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If you want to supply the motor through an
IT network, make sure that you have a
suitable motor variant. If you are in doubt,
contact Grundfos.
The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
earth conductor which must be so long that it is the
last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
English (GB)
7
For maximum backup fuse, see section 26.1 Supply
RCD, type B
L1
L2
L3
L2
L1
L3
PE
RCD, type B
English (GB)
voltage.
Fig. 4Example of a mains-connected motor
with mains switch, backup fuse and
additional protection
Fig. 5Mains connection, single-phase motors
7.3.2 Three-phase supply voltage
Three-phase motors are available for the voltages
below:
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
earth conductor which must be so long that it is the
last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
In order to avoid loose connections, ensure that the
terminal block for L1, L2 and L3 is pressed home in
its socket when the supply cable has been
connected.
For maximum backup fuse, see section 27.1 Supply
voltage.
If you want to supply the motor through an
IT network, make sure that you have a
suitable motor variant. If you are in doubt,
contact Grundfos.
Only the following motors can be supplied through
an IT network:
• Motors with speed of 1450-2000/2200 rpm and
up to 1.5 kW
• Motors with speed of 2900-4000 rpm or
4000-5900 rpm and up to 2.2 kW.
TM05 4034 1912TM05 3494 1512
Corner earthing is not allowed for supply
voltages above 3 x 240 V and 3 x 480 V,
50/60 Hz.
Fig. 6Example of a mains-connected motor
with mains switch, backup fuses and
additional protection
Fig. 7Mains connection, three-phase motors
TM05 3942 1812TM05 3495 1512
8
7.4 Additional protection
DANGER
Electric shock
Death or serious personal injury
- Only use residual-current circuit
breakers (ELCB, GFCI, RCD) of type B.
The residual-current circuit breaker must be marked
with the following symbol:
The total leakage current of all the electrical
equipment in the installation must be taken into
account. You find the leakage current of the motor in
sections 26.2 Leakage current and 27.2 Leakage
current, AC.
This product can cause a direct current in the
protective earth conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of
unstable power supply or a faulty installation. The
motor is stopped if the voltage falls outside the
permissible voltage range. The motor restarts
automatically when the voltage is again within the
permissible voltage range. Therefore, no additional
protection relay is required.
The motor is protected against transients
from the power supply according to EN
61800-3. In areas with high lightning
intensity, we recommend external lightning
protection.
Overload protection
If the upper load limit is exceeded, the motor
automatically compensates for this by reducing the
speed and stops if the overload condition persists.
The motor remains stopped for a set period. After
this period, the motor automatically attempts to
restart. The overload protection prevents damage to
the motor. Consequently, no additional motor
protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor
as an additional protection. When the temperature
rises above a certain level, the motor automatically
compensates for this by reducing the speed and
stops if the temperature keeps rising. The motor
remains stopped for a set period. After this period,
the motor automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power
supply with a quality corresponding to IEC
60146-1-1, class C, to ensure correct motor
operation at phase unbalance. This also ensures
long life of the components.
7.5 Connection terminals
The descriptions and terminal overviews in this
section apply to both single-phase and three-phase
motors.
For maximum torques, see section 29.1 Torques.
7.5.1 Connection terminals, advanced functional
module, FM 300
The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector
outputs
• Input and output for Grundfos Digital Sensor
Not applicable for TPE, TPED, NBE, NBGE, NKE
and NKGE pumps. The factory-fitted
differential-pressure sensor for TPE, TPED, NBE,
NKE Series 2000 is connected to this input.
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop
input where open circuit results in stop. A
jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if
digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by
reinforced insulation in their entire
lengths.
English (GB)
9
• Inputs and outputs
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
English (GB)
All inputs and outputs are internally separated
from the mains-conducting parts by reinforced
insulation and galvanically separated from other
circuits.
All control terminals are supplied by protective
extra-low voltage, PELV, thus ensuring protection
against electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250
VAC .
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
• Mains supply, terminals N, PE, L or L1, L2, L3,
PE.
10
* If you use an external supply source, make sure
that there is a connection to GND.
Fig. 8Connection terminals, FM 300 (option)
TM05 3509 3512
Terminal TypeFunction
Normally
NC
closed
contact
Normally
NO
open contact
Normally
NC
closed
contact
Normally
NO
open contact
18GNDEarth
11DI4/OC2
Pt100/1000
19
input 2
Pt100/1000
17
input 1
12AO
9GNDEarth
14AI3
1DI2
LiqTec sensor
21
input 1
20GND
LiqTec sensor
22
input 2
10DI3/OC1
4AI1
2DI1
5+5 V
Signal relay 1
LIVE or PELVC1Common
Signal relay 2
PELV onlyC2Common
Digital input and
output, configurable.
Open collector:
Maximum 24 V
resistive or inductive.
Pt100/1000 sensor
input
Pt100/1000 sensor
input
Analog output:
0-20 mA / 4-20 mA
0-10 V
Analog input:
0-20 mA / 4-20 mA
0-10 V
Digital input,
configurable
LiqTec sensor input
white conductor
Earth
brown and black
conductors
LiqTec sensor input
blue conductor
Digital input and
output, configurable.
Open collector:
Maximum 24 V
resistive or inductive.
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
Digital input,
configurable
Supply to
potentiometer and
sensor
Terminal TypeFunction
6GNDEarth
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDEarth
15+24 VSupply
8+24 VSupply
26+5 V
23GNDEarth
25GDS TX
24GDS RX
7AI2
Supply to
potentiometer and
sensor
Grundfos Digital
Sensor output
Grundfos Digital
Sensor input
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
7.6 Signal cables
• Use screened cables with a cross-sectional area
of minimum 0.5 mm
external on/off switch, digital inputs, setpoint and
sensor signals.
• Connect the screens of the cables to frame at
both ends with good connection. The screens
must be as close as possible to the terminals.
See fig. 9.
Fig. 9Stripped cable with screen and wire
• Always tighten screws for frame connections
• The wires in the motor terminal box must be as
connections
whether a cable is fitted or not.
short as possible.
2
and maximum 1.5 mm2 for
English (GB)
TM02 1325 4402
11
7.7 Bus connection cable
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
English (GB)
7.7.1 New installations
For the bus connection, use a screened 3-core cable
with a cross-sectional area of minimum 0.5 mm
maximum 1.5 mm
If the motor is connected to a unit with a cable clamp
which is identical to the one on the motor, connect
2
.
the screen to this cable clamp.
If the unit has no cable clamp, leave the screen
unconnected at this end. See fig. 10.
Fig. 10 Connection with screened 3-core cable
7.7.2 Replacing a motor
• If you have used a screened 2-core cable in the
existing installation, connect the cable as shown
in fig. 11.
Fig. 11 Connection with screened 2-core cable
• If you have used a screened 3-core cable in the
existing installation, follow the instructions in
section 7.7.1 New installations.
2
and
8. Operating conditions
8.1 Maximum number of starts and stops
The number of starts and stops via the power supply
must not exceed four times per hour.
When switched on via the power supply, the pump
starts after approximately 5 seconds.
If a higher number of starts and stops is desired, use
the input for external start-stop when starting or
stopping the pump.
When started via an external on/off switch, the pump
starts immediately.
8.2 Alternating operation of twin-head
pumps
On twin-head pumps, the duty and backup pumps
must be alternated on a regular basis, i.e. once a
week, to ensure an even distribution of the operating
TM05 3973 1812TM02 8842 0904
hours on both pumps. The pumps alternate
automatically. See section 13.43 "Multipump setup"
(Setup of multi-pump system).
If twin-head pumps are used for pumping domestic
hot water, the duty and backup pumps must be
alternated on a regular basis, i.e. once a day, to
avoid blocking of the backup pump due to deposits
such as calcareous deposits. As default, the pumps
alternate automatically. See section
13.43 "Multipump setup" (Setup of multi-pump
system).
8.3 Ambient temperature
8.3.1 Ambient temperature during storage and
transportation
Minimum: -30 °C
Maximum: 60 °C.
8.3.2 Ambient temperature during operation
3 x 200-240 V3 x 380-500 V
Minimum-20 °C-20 °C
Maximum40 °C50 °C
The motor can operate with the rated power output,
P2, at 50 °C, but continuous operation at higher
temperatures reduces the expected product life. If
the motor is to operate at ambient temperatures
between 50 and 60 °C, select an oversized motor.
Contact Grundfos for further information.
12
8.4 Installation altitude
0
60
80
90
70
100
500 1000 1500 2000 2500 3000 3500
Altitude [m]
P2 [%]
500
480
460
440
420
380
400
0 500 10002000 2500 3000 3500
4000
1500
Supply voltage [V]
Altitude [m]
Supply voltage [V]
Altitude [m]
Installation altitude is the height above sea level of
the installation site.
Motors installed up to 1000 m above sea level can
be loaded 100 %.
The motors can be installed up to 3500 m above sea
level.
Motors installed more than 1000 m above
sea level must not be fully loaded due to
the low density and consequent low
cooling effect of the air.
Fig. 12 Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure
correct clearance according to EN 60664-1:2007,
you must adapt the supply voltage to the altitude:
Fig. 13 Supply voltage for three-phase motor in
250
240
230
220
210
200
relation to altitude
0 500 1000 1500 2000 2500 3000 3500 4000
8.5 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %,
one of the drain holes in the drive-end flange must
be open. See section 6.6 Drain holes.
8.6 Motor cooling
To ensure cooling of motor and electronics, observe
the following:
• Position the motor in such a way that adequate
cooling is ensured. See section 6.4 Ensuring
motor cooling.
• The temperature of the cooling air must not
exceed 50 °C.
• Keep cooling fins and fan blades clean.
9. User interfaces
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as
the product may be very hot.
TM05 5243 3717TM06 9866 3617TM06 9867 3617
You can make the pump settings by means of the
following user interfaces:
Control panels
• Standard control panel.
• Advanced control panel.
Remote controls
• Grundfos GO.
If the power supply to the pump is switched off, the
settings are stored.
WARNING
Electric shock
Death or serious personal injury
- If the control panel is cracked or
perforated, replace it immediately.
Contact the nearest Grundfos sales
company.
See section 10. Standard control panel.
See section 11. Advanced control panel.
See section 12. Grundfos GO.
English (GB)
Fig. 14 Supply voltage for single-phase motor in
relation to altitude
13
10. Standard control panel
1
2
3
4
5
Stop
0
6
3
bar
[bar]
English (GB)
Pump variant
Fitted as
standard
TPE, TPED●-
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
Fig. 15 Standard control panel
Pos.Symbol Description
Grundfos Eye
1
2-
3
4
Shows the operating status of
the pump.
See section 17. Grundfos Eye
for further information.
Light fields for indication of
setpoint.
Up and down. Changes the
setpoint.
Allows radio communication
with Grundfos GO and other
products of the same type.
When you try to establish
radio communication between
the pump and Grundfos GO or
another pump, the green
indicator light in Grundfos Eye
on the pump flashes
continuously. Press on the
pump control panel to allow
radio communication with
Grundfos GO and other
products of the same type.
Option
--
10.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or . The light fields on the control panel indicates
the setpoint set.
10.1.1 Pump in differential-pressure control
The following example applies to a pump in an
TM05 4848 3512
application where a pressure sensor gives a
feedback to the pump. If you retrofit the sensor to the
pump, set it manually as the pump does not
automatically register a connected sensor.
Figure 16 shows that the light fields 5 and 6 are
activated, indicating a desired setpoint of 3 m with a
sensor measuring range from 0 to 6 m. The setting
range is equal to the sensor measuring range.
Pos.Symbol Description
Makes the pump ready for
operation as well as starts and
stops the pump.
Start
If you press the button when
the pump is stopped, the
5
pump only starts if no other
functions with higher priority
have been enabled. See
section 16. Priority of settings.
Stop
If you press the button when
the pump is running, the pump
always stops. The "Stop" text
next to the button is on.
mode
Fig. 16 Setpoint set to 3 m, differential-pressure
control
TM05 4894 3512
14
10.1.2 Pump in constant-curve control mode
H
Q
Maximum
Minimum
H
Q
H
Q
In constant-curve control mode, the pump
performance lies between the maximum and
minimum curve of the pump. See fig. 17.
Fig. 17 Pump in constant-curve control mode
Setting to maximum curve:
•Press
• To change back, press
Example
Pump set to maximum curve.
Figure 18 shows that the top light field is flashing,
indicating maximum curve.
Fig. 18 Maximum-curve duty
Setting to minimum curve:
•Press
• To change back, press continuously until the
continuously to change over to the
maximum curve of the pump. The top light field
flashes. When the top light field is on, press
for 3 seconds until the light field starts flashing.
continuously until the
desired setpoint is indicated.
continuously to change over to the
minimum curve of the pump. The bottom light
field flashes. When the bottom light field is on,
for 3 seconds until the light field starts
press
flashing.
desired setpoint is indicated.
Example
Pump set to minimum curve.
Figure 19 shows that the bottom light field is
flashing, indicating minimum curve.
Fig. 19 Minimum-curve duty
10.1.3 Start-stop of pump
TM05 4895 2812TM05 4896 2812
Start the pump by pressing
pressing until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is
stopped, the "Stop" text next to the button is on. You
can also stop the pump by continuously pressing
until none of the light fields are on.
You can also stop the pump with the Grundfos GO or
via a digital input set to External stop. See section
16. Priority of settings.
10.1.4 Resetting of fault indications
Reset a fault indication in one of the following ways:
• Via the digital input if it has been set to Alarm
• Briefly press or
• Switch off the power supply until the indicator
• Switch the external start-stop input off and on.
• With Grundfos GO.
If you have stopped the pump by pressing
and the "Stop" text on the control panel
is on, you can only give it free to operation
by pressing again.
If you have stopped the pump by pressing
, you can restart it by pressing or by
using Grundfos GO.
or by continuously
resetting.
on the pump. This does not
change the setting of the pump.
You cannot reset a fault indication by pressing
if the buttons have been locked.
or
lights are off.
English (GB)
TM05 4897 2812
15
11. Advanced control panel
1
2
3
4
5
6
English (GB)
Pump variant
Fitted as
standard
TPE, TPED-●
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
Fig. 20 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
Shows the operating status of
the pump.
For further information, see
section 17. Grundfos Eye.
2-Graphical colour display.
3Goes one step back.
Navigates between main
menus, displays and digits.
When you change the menu, the
display always shows the top
display of the new menu.
Navigates between submenus.
Changes value settings.
4
Note: If you have disabled the
possibility to make settings with
the Enable/disable settings
function, then you can enable it
again temporarily by pressing
these buttons simultaneously for
at least 5 seconds. See section
13.28 "Buttons on product"
(Enable/disable settings).
Option
●-
Pos. Symbol Description
Saves changed values, resets
alarms and expands the value
field.
Enables radio communication
with Grundfos GO and other
products of the same type.
When you try to establish radio
communication between the
4
pump and Grundfos GO or
another pump, the green
indicator light in Grundfos Eye
flashes. A note also appears in
the pump display stating that a
wireless device wants to
connect to the pump. Press
on the pump control panel to
allow radio communication with
Grundfos GO and other
products of the same type.
Makes the pump ready for
operation and starts, and stops
TM05 4849 1013
5
the pump.
Start:
If you press the button when the
pump is stopped, the pump only
starts if no other functions with
higher priority have been
enabled. See section 16. Priority
of settings.
Stop:
If you press the button when the
pump is running, the pump is
always stopped. When you stop
the pump via this button, the
icon appears in the bottom of
the display.
6Goes to the Home menu.
16
11.1 Home display
Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1234
56789
Home
Fig. 21 Example of Home display
Pos. Symbol Description
Home
This menu shows up to four
user-defined parameters. You
1
2-
3-
4-
5
6
7
8
can select parameters shown
as shortcut icon , and when
pressing you go directly to
the "Settings" display for the
selected parameter.
Status
This menu shows the status of
the pump and system as well
as warnings and alarms.
Settings
This menu gives access to all
setting parameters. You can
make detailed settings of the
pump in this menu.
See section 13. Description of
functions.
Assist
This menu enables assisted
pump setup, provides a short
description of the control
modes and offers fault advice.
See section 14. Selection of
control mode.
Indicates that the pump has
been stopped via the
button.
Indicates that the pump is
functioning as master pump in
a multipump system.
Indicates that the pump is
functioning as a slave pump in
a multipump system.
Indicates that the pump is
operating in a multipump
system. See section
13.43 "Multipump setup"
(Setup of multi-pump system).
Pos. Symbol Description
Indicates that the possibility to
make settings has been
9
disabled for protective reasons.
See section 13.28 "Buttons on
product" (Enable/disable
settings).
English (GB)
11.2 Startup guide
The pump incorporates a startup guide which is
started at the first startup. See section 13.37 Run
start-up guide. After the startup guide, the main
menus appear in the display.
TM06 4516 2415
17
11.3 Menu overview for advanced control panel
English (GB)
11.3.1 Main menus
TPE,
TPED,
Home
Status
Operating status●● ●
Operating mode, from●● ●
Control mode●● ●
Pump performance●● ●
Actual controlled value●● ●
Resulting setpoint●● ●
Speed●● ●
Acc. flow and specific energy●● ●
Power and energy consumption●● ●
Measured values●● ●
Set date and time●● ●
Analog input 1●● ●
Analog input 2●● ●
Analog input 3●● ●
Pt100/1000 input 1●● ●
Pt100/1000 input 2●● ●
Analog output●● ●
Warning and alarm●● ●
Actual warning or alarm●● ●
Warning log●● ●
Alarm log●● ●
Operating log●● ●
Operating hours●● ●
Trend data●● ●
Fitted modules●● ●
Date and time●● ●
Product identification●● ●
Motor bearing monitoring●● ●
Multi-pump system--●
System operating status--●
System performance--●
18
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
Multipump
NKE
Series
2000
●● ●
TPE,
TPED,
NBE,
NKE
Series
2000
system
Multipump
system
TPE,
NBE,
NKE,
TPE,
TPED,
NBE,
NKE
Series
2000
TPED,
Status
System input power and energy--●
Pump 1, multi-pump system--●
Pump 2, multi-pump system--●
Pump 3, multi-pump system--●
Pump 4, multi-pump system--●
NBGE,
NKGE
Multipump
system
English (GB)
TPE,
TPED,
Settings
Setpoint●● ●13.1 Setpoint26
Operating mode●● ●13.2 Operating mode26
Set manual speed●● ●13.3 Set manual speed26
"Set user-defined speed"●● ●
Control mode●● ●13.5 "Control mode"27
Analog inputs●● ●
Analog input 1, setup●● ●
Analog input 2, setup●● ●
Analog input 3, setup●● ●
13.43 "Multipump setup"
(Setup of multi-pump system)
13.43 "Multipump setup"
(Setup of multi-pump system)
13.44 Description of control
mode
English (GB)
49
49
53
21
12. Grundfos GO
+
+
1
2
English (GB)
The pump is designed for wireless radio or infrared
communication with Grundfos GO.
Grundfos GO enables setting of functions and gives
access to status overviews, technical product
information and actual operating parameters.
Grundfos GO offers the following mobile interfaces
(MI).
Fig. 22 Grundfos GO communicating with the
Pos. Description
pump via radio or infrared connection,
IR
Grundfos MI 204:
Add-on module enabling radio or infrared
communication. You can use MI 204 in
conjunction with an Apple iPhone or iPod
1
with Lightning connector, for example fifth
generation or later iPhone or iPod.
MI 204 is also available together with an
Apple iPod touch and a cover.
Grundfos MI 301:
Separate module enabling radio or infrared
communication. You can use the module in
2
conjunction with an Android or iOS-based
smart device with Bluetooth connection.
12.1 Communication
When Grundfos GO initiates communication with the
pump, the indicator light in the middle of Grundfos
Eye flashes green. See section 17. Grundfos Eye.
Furthermore, on pumps fitted with an advanced
control panel a text appears in the display saying
that a wireless device is trying to establish
connection. Press on the pump in order to
establish connection with Grundfos GO or press
to reject connection.
Establish communication using one of these
communication types:
• radio communication
• infrared communication.
12.1.1 Radio communication
Radio communication can take place at distances up
to 30 m. The first time Grundfos GO communicates
with the pump, you must enable communication by
pressing or on the pump control panel. Later
when communication takes place, the pump is
TM06 6256 0916
recognized by Grundfos GO and you can select the
pump from the "List" menu.
12.1.2 Infrared communication
When communicating via infrared light, Grundfos GO
must be pointed at the pump control panel.
22
12.2 Menu overview for Grundfos GO
Dashboard
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
●● ●
TPE,
TPED,
"Status"
NBE,
NBGE,
NKE,
NKGE
"System mode"--●
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
*
"Resulting setpoint"●●
"Resulting system
setpoint"
--●
"Actual controlled value"●●●
*
*
"Motor speed (rpm, %)"●● -
"Power consumption"●● -
"Power cons., sys."--●
*
"Energy consumption"●●
"Energy cons., sys."--●
"Acc. flow, specific energy"●●●
*
*
"Operating hours"●●
"Operating hours, system"--●
*
"Analog input 1"●● -
"Analog input 2"●● -
"Analog input 3"●● -
"Pt100/1000 input 1"●● -
"Pt100/1000 input 2"●● -
"Analog output"●● -
"Digital input 1"●● -
"Digital input 2"●● -
"Digital in/output 3"●● -
"Digital in/output 4"●● -
"Fitted modules"●● -
"Pump 1"--●
"Pump 2"--●
"Pump 3"--●
"Pump 4"--●
*
*
*
*
* Only available if Grundfos GO is connected to a multipump system.
English (GB)
23
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.