Grundfos TPE Series, TPED Series, NBE Series, NKGE Series, NBGE Series Installation And Operating Instructions Manual

...
GRUNDFOS INSTRUCTIONS
TPE, TPED, NBE, NBGE, NKE, NKGE, TPE, TPED, NBE, NKE Series 2000
Installation and operating instructions
Installation and operating instructions
TPE, TPED, NBE, NBGE, NKE, NKGE TPE, TPED, NBE, NKE Series 2000
http://net.grundfos.com/qr/i/98476024
English (GB) Installation and operating instructions
Original installation and operating instructions
CONTENTS
Page
1. Symbols used in this document
2. Abbreviations and definitions
3. General information
4. General description
4.1 Radio communication
4.2 Battery
5. Receiving the product
5.1 Transporting the product
5.2 Inspecting the product
6. Mechanical installation
6.1 Handling the product
6.2 Mounting the product
6.3 Cable entries
6.4 Ensuring motor cooling
6.5 Outdoor installation
6.6 Drain holes
7. Electrical installation
7.1 Protection against electric shock, indirect contact
7.2 Cable requirements
7.3 Mains supply
7.4 Additional protection
7.5 Connection terminals
7.6 Signal cables
7.7 Bus connection cable
8. Operating conditions
8.1 Maximum number of starts and stops
8.2 Alternating operation of twin-head pumps
8.3 Ambient temperature
8.4 Installation altitude
8.5 Humidity
8.6 Motor cooling
9. User interfaces
10. Standard control panel
10.1 Setpoint setting
11. Advanced control panel
11.1 Home display
11.2 Startup guide
11.3 Menu overview for advanced control panel
12. Grundfos GO
12.1 Communication
12.2 Menu overview for Grundfos GO
13. Description of functions
13.1 Setpoint
13.2 Operating mode
13.3 Set manual speed
13.4 "Set user-defined speed"
13.5 "Control mode"
13.6 "Proportional-pressure setup"
13.7 Analog inputs
13.8 Built-in Grundfos sensor
13.9 Pt100/1000 inputs
3
13.10 Digital inputs
4
13.11 Digital inputs/outputs
4
13.12 "Signal relays 1 and 2" (Relay outputs)
13.13 Analog output
4
13.14 "Controller" ("Controller settings")
4
13.15 Operating range
4
13.16 External setpoint function
5
13.17 Limit-exceeded function
5
13.18 "Pulse flowmeter setup"
5
13.19 "Ramps"
5
13.20 "Standstill heating"
5
13.21 Motor bearing monitoring
5
13.22 "Service"
5
13.23 "Number" (Pump number)
5
13.24 "Radio communication" (Enable/disable
6 6
13.25 Language
13.26 "Date and time" (Set date and time)
6
13.27 "Unit configuration" (Units)
7
13.28 "Buttons on product" (Enable/disable
7
13.29 Delete history
7
13.30 Define Home display
9
13.31 Display settings
9
13.32 "Store settings" (Store actual settings)
11
13.33 "Recall settings" (Recall stored settings)
12
13.34 "Undo"
12
13.35 "Pump name"
12
13.36 "Connection code"
12
13.37 Run start-up guide
12
13.38 Alarm log
13
13.39 Warning log
13
13.40 Assist
13
13.41 Assisted pump setup
13.42 Setup, analog input
13
13.43 "Multipump setup" (Setup of multi-pump
14
14
13.44 Description of control mode
16
13.45 Assisted fault advice
17
14. Selection of control mode
17
15. Bus signal
18
16. Priority of settings
22
17. Grundfos Eye
22
18. Signal relays
23
19. Installing a communication interface
26
26
20. Identification of functional module
26
21. Identification of control panel
26
22. Changing the position of the control
26
radio comm.)
settings)
system)
module
panel
27 32 32 33 33 34 35 37 37 38 40 40 43 44 44 44 44 45 45
45 45 45 46
46 46 46 46 46 47 47 47 47 48 48 48 48 48 49
49 53 53
54
55
56
57
58
59
61
61
62
2
23. Servicing the product
23.1 Motor
23.2 Pump
24. Cleaning the product
25. Megging
26. Technical data, single-phase motors
26.1 Supply voltage
26.2 Leakage current
27. Technical data, three-phase motors
27.1 Supply voltage
27.2 Leakage current, AC
28. Inputs and outputs
29. Other technical data
29.1 Torques
29.2 Sound pressure level
30. Factory settings
31. Disposing of the product
63
63 63
63
63

1. Symbols used in this document

63
63 63
64
64 64
65
66
67 68
69
70
Read this document before installing the product. Installation and operation must comply with local regulations and accepted codes of good practice.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
Tips and advice that make the work easier.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
A blue or grey circle with a white graphical symbol indicates that an action must be taken.
English (GB)
A red or grey circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
3

2. Abbreviations and definitions 3. General information

AI Analog input. AL Alarm, out of range at lower limit. AO Analog output. AU Alarm, out of range at upper limit. CIM Communication interface module.
Current sinking
Current sourcing
DI Digital input. DO Digital output. ELCB Earth leakage circuit breaker. FM Functional module.
GDS
GENIbus
GFCI
GND Earth. Grundfos
Eye
LIVE
OC
PE Protective earth.
PELV
RCD Residual-current device
SELV
TPE, NBE, NBGE, NKE, NKGE
TPED
TPE, TPED, NBE, NKE Series 2000
The ability to draw current into the terminal and guide it towards earth in the internal circuitry.
The ability to push current out of the terminal and into an external load which must return it to earth.
Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps.
Proprietary Grundfos fieldbus standard.
Ground fault circuit interrupter. USA and Canada.
Status indicator light.
Low voltage with the risk of electric shock if the terminals are touched.
Open collector: Configurable open-collector output.
Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except earth faults in other circuits.
Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including earth faults in other circuits.
Single-head pump without factory-fitted differential-pressure sensor.
Twin-head pump without factory-fitted differential-pressure sensor.
Single-head pump (TPE, NBE, NKE) and twin-head pump (TPED) with factory-fitted differential-pressure sensor.
These installation and operating instructions are a supplement to the installation and operating instructions for the corresponding standard pumps TP, TPD, NB, NBG, NK and NKG. For instructions not mentioned specifically in this manual, see the installation and operating instructions for the standard pump.

4. General description

The pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase mains connection.

4.1 Radio communication

This product incorporates a radio module for remote control which is a class 1 device and can be used anywhere in the EU member states without restrictions.
For use in USA and Canada, see page 71. Some variants of the product and products sold in
China and Korea have no radio module. This product can communicate with Grundfos GO
and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only Grundfos-approved external antennas may be connected to this product, and only by a Grundfos-approved installer.

4.2 Battery

Pumps fitted with the advanced functional module, FM 300, incorporate a Li-ion battery. The Li-ion battery complies with the Battery Directive (2006/66/EC). The battery does not contain mercury, lead and cadmium.
4

5. Receiving the product

D

5.1 Transporting the product

WARNING
Falling objects
Death or serious personal injury
- Secure the product during transportation to prevent it from tilting or falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.

5.2 Inspecting the product

Before you install the product, do the following:
• Check that the product is as ordered.
• Check that no visible parts have been damaged. If parts are damaged or missing, contact your local
Grundfos sales company.

6. Mechanical installation

6.1 Handling the product

Observe local regulations setting limits for manual lifting or handling. The motor weight is stated on the nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting equipment to the motor eyebolts when handling the product.

6.2 Mounting the product

CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation by bolts through the holes in the flange or the base plate.
In order to maintain the UL mark, additional requirements apply to the equipment. See page 71.
Secure the pump to a solid foundation by bolts through the holes in the flange or the base plate.

6.3 Cable entries

See the size of the cable entries in section 29. Other
technical data.

6.4 Ensuring motor cooling

Leave at least 50 mm between the end of the fan cover and a wall or other fixed objects. See fig. 1.
Fig. 1 Minimum distance, D, from the motor to
a wall or other fixed objects
English (GB)
TM05 5236 3512
Do not lift the product by the terminal box.
5

6.5 Outdoor installation

B3 B14 B5
If you install the motor outdoors, provide the motor with a cover and open the drain holes to avoid condensation on the electronic components. See figures 2 and 3.
When fitting a cover to the motor, observe the guidelines in section 6.4 Ensuring
motor cooling.
The cover must be sufficiently large to ensure that the motor is not exposed to direct sunlight, rain or snow. Grundfos does not supply covers. We therefore recommend that you have a cover built for the specific application. In areas with high humidity, we recommend that you connect the motor permanently to the mains supply and activate the built-in standstill heating function. See section
13.20 "Standstill heating", page 44.
Fig. 2 Examples of covers, not supplied by
Grundfos
In order to maintain the UL mark, additional requirements apply to the equipment. See page 71.

6.6 Drain holes

When the motor is installed in moist surroundings or areas with high humidity, the bottom drain hole must be open. The enclosure class of the motor will then be lower. This helps prevent condensation in the motor as the motor becomes self-venting, and it allows water and humid air to escape.
The motor has a plugged drain hole on the drive side. You can turn the flange 90 ° to both sides or 180 °.

7. Electrical installation

DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before you make any connections in the terminal box. Make sure that the power supply cannot be accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
- Check that the supply voltage and frequency correspond to the values stated on the nameplate.
If the power supply cable is damaged, it must be replaced by the manufacturer, the manufacturer's service partner or a similarly qualified person.
The user or the installer is responsible for the installation of correct earthing and protection
TM05 3496 3512
according to local regulations. All operations must be carried out by a qualified electrician.
Carry out the electrical connection according to local regulations.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Fig. 3 Drain holes
6
TM02 9037 1604

7.1 Protection against electric shock, indirect contact

WARNING
Electric shock
Death or serious personal injury
- Connect the motor to protective earth and provide protection against indirect contact in accordance with local regulations.
Protective-earth conductors must always have a yellow and green, PE, or yellow,green and blue, PEN, colour marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.

7.2 Cable requirements

7.2.1 Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as to cable cross-sections.
1 x 200-230 V
Power [kW]
0.25 - 1.5
3 x 380-500 V
Power [kW]
0.25 - 2.2
3.0 - 11
Conductor type
Solid 1.5 - 2.5 16-12 Stranded 1.5 - 2.5 16-12
Conductor type
Solid 1.5 - 10 16-8 Stranded 1.5 - 10 16-8 Solid 2.5 - 10 14-8 Stranded 2.5 - 10 14-8
Cross section
2
[mm
][AWG]
Cross section
2
][AWG]
[mm
3 x 200-240 V
Power [kW]
1.1 - 1.5
2.2 - 5.5
7.2.2 Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 60 °C (140 °F).
Temperature rating for outer cable sheath: 75 °C (167 °F).
Conductor type
Solid 1.5 - 10 16-8 Stranded 1.5 - 10 16-8 Solid 2.5 - 10 14-8 Stranded 2.5 - 10 14-8
Cross section
2
][AWG]
[mm

7.3 Mains supply

DANGER
Electric shock
Death or serious personal injury
- Use the recommended fuse size. See sections 26.1 Supply voltage and
27.1 Supply voltage.
7.3.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE. Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If you want to supply the motor through an IT network, make sure that you have a suitable motor variant. If you are in doubt, contact Grundfos.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
English (GB)
7
For maximum backup fuse, see section 26.1 Supply
RCD, type B
L1
L2
L3
L2
L1
L3
PE
RCD, type B
voltage.
Fig. 4 Example of a mains-connected motor
with mains switch, backup fuse and additional protection
Fig. 5 Mains connection, single-phase motors
7.3.2 Three-phase supply voltage
Three-phase motors are available for the voltages below:
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE. Check that the supply voltage and frequency
correspond to the values stated on the nameplate. The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in its socket when the supply cable has been connected.
For maximum backup fuse, see section 27.1 Supply
voltage.
If you want to supply the motor through an IT network, make sure that you have a suitable motor variant. If you are in doubt, contact Grundfos.
Only the following motors can be supplied through an IT network:
• Motors with speed of 1450-2000/2200 rpm and up to 1.5 kW
• Motors with speed of 2900-4000 rpm or 4000-5900 rpm and up to 2.2 kW.
TM05 4034 1912TM05 3494 1512
Corner earthing is not allowed for supply voltages above 3 x 240 V and 3 x 480 V, 50/60 Hz.
Fig. 6 Example of a mains-connected motor
with mains switch, backup fuses and additional protection
Fig. 7 Mains connection, three-phase motors
TM05 3942 1812TM05 3495 1512
8

7.4 Additional protection

DANGER
Electric shock
Death or serious personal injury
- Only use residual-current circuit breakers (ELCB, GFCI, RCD) of type B.
The residual-current circuit breaker must be marked with the following symbol:
The total leakage current of all the electrical equipment in the installation must be taken into account. You find the leakage current of the motor in sections 26.2 Leakage current and 27.2 Leakage
current, AC.
This product can cause a direct current in the protective earth conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of unstable power supply or a faulty installation. The motor is stopped if the voltage falls outside the permissible voltage range. The motor restarts automatically when the voltage is again within the permissible voltage range. Therefore, no additional protection relay is required.
The motor is protected against transients from the power supply according to EN 61800-3. In areas with high lightning intensity, we recommend external lightning protection.
Overload protection
If the upper load limit is exceeded, the motor automatically compensates for this by reducing the speed and stops if the overload condition persists.
The motor remains stopped for a set period. After this period, the motor automatically attempts to restart. The overload protection prevents damage to the motor. Consequently, no additional motor protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor as an additional protection. When the temperature rises above a certain level, the motor automatically compensates for this by reducing the speed and stops if the temperature keeps rising. The motor remains stopped for a set period. After this period, the motor automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power supply with a quality corresponding to IEC 60146-1-1, class C, to ensure correct motor operation at phase unbalance. This also ensures long life of the components.

7.5 Connection terminals

The descriptions and terminal overviews in this section apply to both single-phase and three-phase motors.
For maximum torques, see section 29.1 Torques.
7.5.1 Connection terminals, advanced functional module, FM 300
The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector
outputs
• Input and output for Grundfos Digital Sensor
Not applicable for TPE, TPED, NBE, NBGE, NKE and NKGE pumps. The factory-fitted differential-pressure sensor for TPE, TPED, NBE, NKE Series 2000 is connected to this input.
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop input where open circuit results in stop. A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation in their entire lengths.
English (GB)
9
Inputs and outputs
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
All inputs and outputs are internally separated from the mains-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by protective extra-low voltage, PELV, thus ensuring protection against electric shock.
Signal relay outputs – Signal relay 1:
LIVE: You can connect supply voltages up to 250 VAC . PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
– Signal relay 2:
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
• Mains supply, terminals N, PE, L or L1, L2, L3,
PE.
10
* If you use an external supply source, make sure
that there is a connection to GND.
Fig. 8 Connection terminals, FM 300 (option)
TM05 3509 3512
Terminal Type Function
Normally
NC
closed contact
Normally
NO
open contact
Normally
NC
closed contact
Normally
NO
open contact
18 GND Earth
11 DI4/OC2
Pt100/1000
19
input 2 Pt100/1000
17
input 1
12 AO
9GND Earth
14 AI3
1DI2
LiqTec sensor
21
input 1
20 GND
LiqTec sensor
22
input 2
10 DI3/OC1
4AI1
2DI1
5+5 V
Signal relay 1 LIVE or PELVC1 Common
Signal relay 2 PELV onlyC2 Common
Digital input and output, configurable. Open collector: Maximum 24 V resistive or inductive.
Pt100/1000 sensor input
Pt100/1000 sensor input
Analog output: 0-20 mA / 4-20 mA 0-10 V
Analog input: 0-20 mA / 4-20 mA 0-10 V
Digital input, configurable
LiqTec sensor input white conductor
Earth brown and black conductors
LiqTec sensor input blue conductor
Digital input and output, configurable. Open collector: Maximum 24 V resistive or inductive.
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
Digital input, configurable
Supply to potentiometer and sensor
Terminal Type Function
6GND Earth A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3GND Earth
15 +24 V Supply
8 +24 V Supply
26 +5 V
23 GND Earth
25 GDS TX
24 GDS RX
7AI2
Supply to potentiometer and sensor
Grundfos Digital Sensor output
Grundfos Digital Sensor input
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V

7.6 Signal cables

• Use screened cables with a cross-sectional area of minimum 0.5 mm external on/off switch, digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to frame at both ends with good connection. The screens must be as close as possible to the terminals. See fig. 9.
Fig. 9 Stripped cable with screen and wire
• Always tighten screws for frame connections
• The wires in the motor terminal box must be as
connections
whether a cable is fitted or not.
short as possible.
2
and maximum 1.5 mm2 for
English (GB)
TM02 1325 4402
11

7.7 Bus connection cable

A
Y
B
A
Y
B
1
2 3
1 2 3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
7.7.1 New installations
For the bus connection, use a screened 3-core cable with a cross-sectional area of minimum 0.5 mm maximum 1.5 mm
If the motor is connected to a unit with a cable clamp which is identical to the one on the motor, connect
2
.
the screen to this cable clamp. If the unit has no cable clamp, leave the screen
unconnected at this end. See fig. 10.
Fig. 10 Connection with screened 3-core cable
7.7.2 Replacing a motor
• If you have used a screened 2-core cable in the existing installation, connect the cable as shown in fig. 11.
Fig. 11 Connection with screened 2-core cable
• If you have used a screened 3-core cable in the existing installation, follow the instructions in section 7.7.1 New installations.
2
and

8. Operating conditions

8.1 Maximum number of starts and stops

The number of starts and stops via the power supply must not exceed four times per hour.
When switched on via the power supply, the pump starts after approximately 5 seconds.
If a higher number of starts and stops is desired, use the input for external start-stop when starting or stopping the pump.
When started via an external on/off switch, the pump starts immediately.

8.2 Alternating operation of twin-head pumps

On twin-head pumps, the duty and backup pumps must be alternated on a regular basis, i.e. once a week, to ensure an even distribution of the operating
TM05 3973 1812TM02 8842 0904
hours on both pumps. The pumps alternate automatically. See section 13.43 "Multipump setup"
(Setup of multi-pump system).
If twin-head pumps are used for pumping domestic hot water, the duty and backup pumps must be alternated on a regular basis, i.e. once a day, to avoid blocking of the backup pump due to deposits such as calcareous deposits. As default, the pumps alternate automatically. See section
13.43 "Multipump setup" (Setup of multi-pump
system).

8.3 Ambient temperature

8.3.1 Ambient temperature during storage and
transportation
Minimum: -30 °C Maximum: 60 °C.
8.3.2 Ambient temperature during operation
3 x 200-240 V 3 x 380-500 V
Minimum -20 °C -20 °C Maximum 40 °C 50 °C
The motor can operate with the rated power output, P2, at 50 °C, but continuous operation at higher temperatures reduces the expected product life. If the motor is to operate at ambient temperatures between 50 and 60 °C, select an oversized motor. Contact Grundfos for further information.
12

8.4 Installation altitude

0
60
80
90
70
100
500 1000 1500 2000 2500 3000 3500
Altitude [m]
P2 [%]
500 480 460 440 420
380
400
0 500 1000 2000 2500 3000 3500
4000
1500
Supply voltage [V]
Altitude [m]
Supply voltage [V]
Altitude [m]
Installation altitude is the height above sea level of the installation site.
Motors installed up to 1000 m above sea level can be loaded 100 %.
The motors can be installed up to 3500 m above sea level.
Motors installed more than 1000 m above sea level must not be fully loaded due to the low density and consequent low cooling effect of the air.
Fig. 12 Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure correct clearance according to EN 60664-1:2007, you must adapt the supply voltage to the altitude:
Fig. 13 Supply voltage for three-phase motor in
250
240
230
220
210
200
relation to altitude
0 500 1000 1500 2000 2500 3000 3500 4000

8.5 Humidity

Maximum humidity: 95 %. If the humidity is constantly high and above 85 %,
one of the drain holes in the drive-end flange must be open. See section 6.6 Drain holes.

8.6 Motor cooling

To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate
cooling is ensured. See section 6.4 Ensuring
motor cooling.
• The temperature of the cooling air must not
exceed 50 °C.
• Keep cooling fins and fan blades clean.

9. User interfaces

WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as the product may be very hot.
TM05 5243 3717TM06 9866 3617TM06 9867 3617
You can make the pump settings by means of the following user interfaces:
Control panels
• Standard control panel.
• Advanced control panel.
Remote controls
• Grundfos GO.
If the power supply to the pump is switched off, the settings are stored.
WARNING
Electric shock
Death or serious personal injury
- If the control panel is cracked or perforated, replace it immediately. Contact the nearest Grundfos sales company.
See section 10. Standard control panel.
See section 11. Advanced control panel.
See section 12. Grundfos GO.
English (GB)
Fig. 14 Supply voltage for single-phase motor in
relation to altitude
13

10. Standard control panel

1
2
3
4
5
Stop
0
6
3
bar
[bar]
Pump variant
Fitted as standard
TPE, TPED - NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
Fig. 15 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
2-
3
4
Shows the operating status of the pump. See section 17. Grundfos Eye for further information.
Light fields for indication of setpoint.
Up and down. Changes the setpoint.
Allows radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the pump and Grundfos GO or another pump, the green indicator light in Grundfos Eye on the pump flashes continuously. Press on the pump control panel to allow radio communication with Grundfos GO and other products of the same type.
Option
--

10.1 Setpoint setting

Set the desired setpoint of the pump by pressing or . The light fields on the control panel indicates the setpoint set.
10.1.1 Pump in differential-pressure control
The following example applies to a pump in an
TM05 4848 3512
application where a pressure sensor gives a feedback to the pump. If you retrofit the sensor to the pump, set it manually as the pump does not automatically register a connected sensor.
Figure 16 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 3 m with a sensor measuring range from 0 to 6 m. The setting range is equal to the sensor measuring range.
Pos. Symbol Description
Makes the pump ready for operation as well as starts and stops the pump.
Start
If you press the button when the pump is stopped, the
5
pump only starts if no other functions with higher priority have been enabled. See section 16. Priority of settings.
Stop
If you press the button when the pump is running, the pump always stops. The "Stop" text next to the button is on.
mode
Fig. 16 Setpoint set to 3 m, differential-pressure
control
TM05 4894 3512
14
10.1.2 Pump in constant-curve control mode
H
Q
Maximum
Minimum
H
Q
H
Q
In constant-curve control mode, the pump performance lies between the maximum and minimum curve of the pump. See fig. 17.
Fig. 17 Pump in constant-curve control mode
Setting to maximum curve:
•Press
• To change back, press
Example
Pump set to maximum curve. Figure 18 shows that the top light field is flashing,
indicating maximum curve.
Fig. 18 Maximum-curve duty
Setting to minimum curve:
•Press
• To change back, press continuously until the
continuously to change over to the
maximum curve of the pump. The top light field flashes. When the top light field is on, press for 3 seconds until the light field starts flashing.
continuously until the
desired setpoint is indicated.
continuously to change over to the
minimum curve of the pump. The bottom light field flashes. When the bottom light field is on,
for 3 seconds until the light field starts
press flashing.
desired setpoint is indicated.
Example
Pump set to minimum curve. Figure 19 shows that the bottom light field is
flashing, indicating minimum curve.
Fig. 19 Minimum-curve duty
10.1.3 Start-stop of pump
TM05 4895 2812TM05 4896 2812
Start the pump by pressing pressing until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is stopped, the "Stop" text next to the button is on. You can also stop the pump by continuously pressing until none of the light fields are on.
You can also stop the pump with the Grundfos GO or via a digital input set to External stop. See section
16. Priority of settings.
10.1.4 Resetting of fault indications
Reset a fault indication in one of the following ways:
• Via the digital input if it has been set to Alarm
• Briefly press or
• Switch off the power supply until the indicator
• Switch the external start-stop input off and on.
• With Grundfos GO.
If you have stopped the pump by pressing
and the "Stop" text on the control panel
is on, you can only give it free to operation by pressing again.
If you have stopped the pump by pressing
, you can restart it by pressing or by
using Grundfos GO.
or by continuously
resetting.
on the pump. This does not
change the setting of the pump. You cannot reset a fault indication by pressing
if the buttons have been locked.
or
lights are off.
English (GB)
TM05 4897 2812
15

11. Advanced control panel

1
2
3
4
5
6
Pump variant
Fitted as standard
TPE, TPED - NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
Fig. 20 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
Shows the operating status of the pump. For further information, see section 17. Grundfos Eye.
2 - Graphical colour display.
3 Goes one step back.
Navigates between main menus, displays and digits. When you change the menu, the display always shows the top display of the new menu.
Navigates between submenus. Changes value settings.
4
Note: If you have disabled the possibility to make settings with the Enable/disable settings function, then you can enable it again temporarily by pressing these buttons simultaneously for at least 5 seconds. See section
13.28 "Buttons on product" (Enable/disable settings).
Option
-
Pos. Symbol Description
Saves changed values, resets alarms and expands the value field. Enables radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the
4
pump and Grundfos GO or another pump, the green indicator light in Grundfos Eye flashes. A note also appears in the pump display stating that a wireless device wants to connect to the pump. Press on the pump control panel to allow radio communication with Grundfos GO and other products of the same type.
Makes the pump ready for operation and starts, and stops
TM05 4849 1013
5
the pump. Start:
If you press the button when the pump is stopped, the pump only starts if no other functions with higher priority have been enabled. See section 16. Priority
of settings.
Stop: If you press the button when the
pump is running, the pump is always stopped. When you stop the pump via this button, the icon appears in the bottom of the display.
6 Goes to the Home menu.
16

11.1 Home display

Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1 2 3 4
56789
Home
Fig. 21 Example of Home display
Pos. Symbol Description
Home This menu shows up to four user-defined parameters. You
1
2-
3-
4-
5
6
7
8
can select parameters shown as shortcut icon , and when pressing you go directly to the "Settings" display for the selected parameter.
Status This menu shows the status of the pump and system as well as warnings and alarms.
Settings This menu gives access to all setting parameters. You can make detailed settings of the pump in this menu. See section 13. Description of
functions.
Assist This menu enables assisted pump setup, provides a short description of the control modes and offers fault advice. See section 14. Selection of
control mode.
Indicates that the pump has been stopped via the button.
Indicates that the pump is functioning as master pump in a multipump system.
Indicates that the pump is functioning as a slave pump in a multipump system.
Indicates that the pump is operating in a multipump system. See section
13.43 "Multipump setup" (Setup of multi-pump system).
Pos. Symbol Description
Indicates that the possibility to make settings has been
9
disabled for protective reasons. See section 13.28 "Buttons on
product" (Enable/disable settings).
English (GB)

11.2 Startup guide

The pump incorporates a startup guide which is started at the first startup. See section 13.37 Run
start-up guide. After the startup guide, the main
menus appear in the display.
TM06 4516 2415
17

11.3 Menu overview for advanced control panel

11.3.1 Main menus
TPE,
TPED,
Home
Status
Operating status ●● ●
Operating mode, from ●● ● Control mode ●● ●
Pump performance ●● ●
Actual controlled value ●● ● Resulting setpoint ●● ● Speed ●● ●
Acc. flow and specific energy ●● ● Power and energy consumption ●● ● Measured values ●● ●
Set date and time ●● ●
Analog input 1 ●● ●
Analog input 2 ●● ●
Analog input 3 ●● ●
Pt100/1000 input 1 ●● ●
Pt100/1000 input 2 ●● ● Analog output ●● ● Warning and alarm ●● ●
Actual warning or alarm ●● ●
Warning log ●● ●
Alarm log ●● ● Operating log ●● ●
Operating hours ●● ●
Trend data ●● ● Fitted modules ●● ● Date and time ●● ● Product identification ●● ● Motor bearing monitoring ●● ● Multi-pump system - -
System operating status - -
System performance - -
18
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
Multipump
NKE
Series
2000
●● ●
TPE,
TPED,
NBE, NKE
Series
2000
system
Multipump
system
TPE,
NBE,
NKE,
TPE,
TPED,
NBE, NKE
Series
2000
TPED,
Status
System input power and energy - -
Pump 1, multi-pump system - -
Pump 2, multi-pump system - -
Pump 3, multi-pump system - -
Pump 4, multi-pump system - -
NBGE,
NKGE
Multipump
system
English (GB)
TPE,
TPED,
Settings
Setpoint ●● ●13.1 Setpoint 26 Operating mode ●● ●13.2 Operating mode 26 Set manual speed ●● ●13.3 Set manual speed 26
"Set user-defined speed" ●● ●
Control mode ●● ●13.5 "Control mode" 27 Analog inputs ●● ●
Analog input 1, setup ●● ● Analog input 2, setup ●● ● Analog input 3, setup ●● ●
Built-in Grundfos sensor - ●●
Pt100/1000 inputs ●● ●
Pt100/1000 input 2, setup ●● ●
Digital inputs ●● ●
Digital input 2, setup ●● ●
Digital inputs/outputs ●● ●
Digital input/output 4, setup ●● ●
Relay outputs ●● ●
Relay output 2 ●● ●
Analog output ●● ●
Function of analog output ●● ●
"Controller settings" ●● ●
Operating range ●● ●13.15 Operating range 40 Setpoint influence ●● ●
External setpoint function ●● ● 40
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
*
Section Page
13.4 "Set user-defined speed"
13.7 Analog inputs 32
13.8 Built-in Grundfos sensor
13.9 Pt100/1000 inputs 33Pt100/1000 input 1, setup ●● ●
13.10 Digital inputs 34Digital input 1, setup ●● ●
13.11 Digital inputs/outputs 35Digital input/output 3, setup ●● ●
13.12 "Signal relays 1 and 2" (Relay outputs)
13.13 Analog output 37Output signal ●● ●
13.14 "Controller" ("Controller settings")
26
33
37Relay output 1 ●● ●
38
19
Settings
"Predefined setpoints" ●● ●
Monitoring functions ●● ●
Motor bearing monitoring ●● ●
Motor bearing maintenance ●● ●
Limit-exceeded function ●● ●
"Special functions" ●●
"Pulse flowmeter setup" ●● ●
"Ramps" ●● ●13.19 "Ramps" 44 "Standstill heating" ●● ●13.20 "Standstill heating" 44
Communication ●● ●
Pump number ●● ●
Enable/disable radio comm. ●● ●
General settings ●● ●
Language ●● ●13.25 Language 45
Set date and time ●● ●
Units ●● ●
Enable/disable settings ●● ●
Delete history ●● ●13.29 Delete history 46 Define Home display ●● ●13.30 Define Home display 46 Display settings ●● ●13.31 Display settings 46
Store actual settings ●● ●
Recall stored settings ●● ●
Run start-up guide ●● ●13.37 Run start-up guide 48
* Applies only to a multipump system with TPE, TPED, NBE, NKE Series 2000 pumps.
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
13.16.2 "Predefined setpoints"
13.21 Motor bearing monitoring
Bearings replaced (Motor bearing maintenance)
13.17 Limit-exceeded function
13.18 "Pulse flowmeter setup"
13.23 "Number" (Pump number)
13.24 "Radio communication" (Enable/disable radio comm.)
13.26 "Date and time" (Set date and time)
13.27 "Unit configuration" (Units)
13.28 "Buttons on product" (Enable/disable settings)
13.32 "Store settings" (Store actual settings)
13.33 "Recall settings" (Recall stored settings)
42
44
45
43
44
45
45
45
46
46
46
47
20
TPE,
TPED,
Assist
Assisted pump setup ●● ●13.41 Assisted pump setup 48 Setup, analog input ●● ●13.42 Setup, analog input 49
Setting of date and time ●● ●
Setup of multi-pump system ●● ●
Description of control mode ●● ●
Assisted fault advice ●● ●13.45 Assisted fault advice 53
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
13.43 "Multipump setup" (Setup of multi-pump system)
13.43 "Multipump setup" (Setup of multi-pump system)
13.44 Description of control mode
English (GB)
49
49
53
21

12. Grundfos GO

+
+
1
2
The pump is designed for wireless radio or infrared communication with Grundfos GO.
Grundfos GO enables setting of functions and gives access to status overviews, technical product information and actual operating parameters.
Grundfos GO offers the following mobile interfaces (MI).
Fig. 22 Grundfos GO communicating with the
Pos. Description
pump via radio or infrared connection, IR
Grundfos MI 204: Add-on module enabling radio or infrared communication. You can use MI 204 in conjunction with an Apple iPhone or iPod
1
with Lightning connector, for example fifth generation or later iPhone or iPod. MI 204 is also available together with an Apple iPod touch and a cover.
Grundfos MI 301: Separate module enabling radio or infrared communication. You can use the module in
2
conjunction with an Android or iOS-based smart device with Bluetooth connection.

12.1 Communication

When Grundfos GO initiates communication with the pump, the indicator light in the middle of Grundfos Eye flashes green. See section 17. Grundfos Eye.
Furthermore, on pumps fitted with an advanced control panel a text appears in the display saying that a wireless device is trying to establish connection. Press on the pump in order to establish connection with Grundfos GO or press to reject connection.
Establish communication using one of these communication types:
• radio communication
• infrared communication.
12.1.1 Radio communication
Radio communication can take place at distances up to 30 m. The first time Grundfos GO communicates with the pump, you must enable communication by pressing or on the pump control panel. Later when communication takes place, the pump is
TM06 6256 0916
recognized by Grundfos GO and you can select the pump from the "List" menu.
12.1.2 Infrared communication
When communicating via infrared light, Grundfos GO must be pointed at the pump control panel.
22

12.2 Menu overview for Grundfos GO

Dashboard
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
●● ●
TPE,
TPED,
"Status"
NBE,
NBGE,
NKE,
NKGE
"System mode" - -
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
*
"Resulting setpoint" ●●
"Resulting system
setpoint"
--
"Actual controlled value" ●●●
*
*
"Motor speed (rpm, %)" ●● -
"Power consumption" ●● -
"Power cons., sys." - -
*
"Energy consumption" ●●
"Energy cons., sys." - -
"Acc. flow, specific energy" ●●●
*
*
"Operating hours" ●●
"Operating hours, system" - -
*
"Analog input 1" ●● -
"Analog input 2" ●● -
"Analog input 3" ●● -
"Pt100/1000 input 1" ●● -
"Pt100/1000 input 2" ●● -
"Analog output" ●● -
"Digital input 1" ●● -
"Digital input 2" ●● -
"Digital in/output 3" ●● -
"Digital in/output 4" ●● -
"Fitted modules" ●● -
"Pump 1" - -
"Pump 2" - -
"Pump 3" - -
"Pump 4" - -
*
*
*
*
* Only available if Grundfos GO is connected to a multipump system.
English (GB)
23
Loading...
+ 53 hidden pages