The ability to draw current into the
terminal and guide it towards earth in
the internal circuitry.
The ability to push current out of the
terminal and into an external load
which must return it to earth.
Grundfos Digital Sensor.
Factory-fitted sensor in some
Grundfos pumps.
Proprietary Grundfos fieldbus
standard.
Ground fault circuit interrupter.
USA and Canada.
Status indicator light.
Low voltage with the risk of electric
shock if the terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV
under normal conditions and under
single-fault conditions, except earth
faults in other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV
under normal conditions and under
single-fault conditions, including earth
faults in other circuits.
Single-head pump without
factory-fitted differential-pressure
sensor.
Twin-head pump without factory-fitted
differential-pressure sensor.
Single-head pump (TPE, NBE, NKE)
and twin-head pump (TPED) with
factory-fitted differential-pressure
sensor.
These installation and operating instructions are a
supplement to the installation and operating
instructions for the corresponding standard pumps
TP, TPD, NB, NBG, NK and NKG. For instructions not
mentioned specifically in this manual, see the
installation and operating instructions for the
standard pump.
4. General description
The pumps are fitted with frequency-controlled
permanent-magnet motors for single-phase or
three-phase mains connection.
4.1 Radio communication
This product incorporates a radio module for remote
control which is a class 1 device and can be used
anywhere in the EU member states without
restrictions.
For use in USA and Canada, see page 71.
Some variants of the product and products sold in
China and Korea have no radio module.
This product can communicate with Grundfos GO
and other products of the same type via the built-in
radio module.
In some cases, an external antenna may be
required. Only Grundfos-approved external antennas
may be connected to this product, and only by a
Grundfos-approved installer.
4.2 Battery
Pumps fitted with the advanced functional module,
FM 300, incorporate a Li-ion battery. The Li-ion
battery complies with the Battery Directive
(2006/66/EC). The battery does not contain mercury,
lead and cadmium.
4
5. Receiving the product
D
5.1 Transporting the product
WARNING
Falling objects
Death or serious personal injury
- Secure the product during
transportation to prevent it from tilting or
falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the
product.
5.2 Inspecting the product
Before you install the product, do the following:
• Check that the product is as ordered.
• Check that no visible parts have been damaged.
If parts are damaged or missing, contact your local
Grundfos sales company.
6. Mechanical installation
6.1 Handling the product
Observe local regulations setting limits for manual
lifting or handling. The motor weight is stated on the
nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting
equipment to the motor eyebolts when
handling the product.
6.2 Mounting the product
CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation
by bolts through the holes in the flange
or the base plate.
In order to maintain the UL mark,
additional requirements apply to the
equipment. See page 71.
Secure the pump to a solid foundation by bolts
through the holes in the flange or the base plate.
6.3 Cable entries
See the size of the cable entries in section 29. Other
technical data.
6.4 Ensuring motor cooling
Leave at least 50 mm between the end of the fan
cover and a wall or other fixed objects. See fig. 1.
Fig. 1Minimum distance, D, from the motor to
a wall or other fixed objects
English (GB)
TM05 5236 3512
Do not lift the product by the terminal box.
5
6.5 Outdoor installation
B3B14B5
English (GB)
If you install the motor outdoors, provide the motor
with a cover and open the drain holes to avoid
condensation on the electronic components. See
figures 2 and 3.
When fitting a cover to the motor, observe
the guidelines in section 6.4 Ensuring
motor cooling.
The cover must be sufficiently large to ensure that
the motor is not exposed to direct sunlight, rain or
snow. Grundfos does not supply covers. We
therefore recommend that you have a cover built for
the specific application. In areas with high humidity,
we recommend that you connect the motor
permanently to the mains supply and activate the
built-in standstill heating function. See section
13.20 "Standstill heating", page 44.
Fig. 2Examples of covers, not supplied by
Grundfos
In order to maintain the UL mark,
additional requirements apply to the
equipment. See page 71.
6.6 Drain holes
When the motor is installed in moist surroundings or
areas with high humidity, the bottom drain hole must
be open. The enclosure class of the motor will then
be lower. This helps prevent condensation in the
motor as the motor becomes self-venting, and it
allows water and humid air to escape.
The motor has a plugged drain hole on the drive
side. You can turn the flange 90 ° to both sides or
180 °.
7. Electrical installation
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
minutes before you make any
connections in the terminal box. Make
sure that the power supply cannot be
accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
- Check that the supply voltage and
frequency correspond to the values
stated on the nameplate.
If the power supply cable is damaged, it must be
replaced by the manufacturer, the manufacturer's
service partner or a similarly qualified person.
The user or the installer is responsible for the
installation of correct earthing and protection
TM05 3496 3512
according to local regulations. All operations must be
carried out by a qualified electrician.
Carry out the electrical connection according to local
regulations.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Fig. 3Drain holes
6
TM02 9037 1604
7.1 Protection against electric shock,
indirect contact
WARNING
Electric shock
Death or serious personal injury
- Connect the motor to protective earth
and provide protection against indirect
contact in accordance with local
regulations.
Protective-earth conductors must always have a
yellow and green, PE, or yellow,green and blue,
PEN, colour marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage
transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The
motor incorporates thermal protection against slow
overloading and blocking.
7.2 Cable requirements
7.2.1 Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as
to cable cross-sections.
- Use the recommended fuse size. See
sections 26.1 Supply voltage and
27.1 Supply voltage.
7.3.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If you want to supply the motor through an
IT network, make sure that you have a
suitable motor variant. If you are in doubt,
contact Grundfos.
The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
earth conductor which must be so long that it is the
last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
English (GB)
7
For maximum backup fuse, see section 26.1 Supply
RCD, type B
L1
L2
L3
L2
L1
L3
PE
RCD, type B
English (GB)
voltage.
Fig. 4Example of a mains-connected motor
with mains switch, backup fuse and
additional protection
Fig. 5Mains connection, single-phase motors
7.3.2 Three-phase supply voltage
Three-phase motors are available for the voltages
below:
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
earth conductor which must be so long that it is the
last one to be disconnected in case the cable is
inadvertently pulled out of the cable entry.
In order to avoid loose connections, ensure that the
terminal block for L1, L2 and L3 is pressed home in
its socket when the supply cable has been
connected.
For maximum backup fuse, see section 27.1 Supply
voltage.
If you want to supply the motor through an
IT network, make sure that you have a
suitable motor variant. If you are in doubt,
contact Grundfos.
Only the following motors can be supplied through
an IT network:
• Motors with speed of 1450-2000/2200 rpm and
up to 1.5 kW
• Motors with speed of 2900-4000 rpm or
4000-5900 rpm and up to 2.2 kW.
TM05 4034 1912TM05 3494 1512
Corner earthing is not allowed for supply
voltages above 3 x 240 V and 3 x 480 V,
50/60 Hz.
Fig. 6Example of a mains-connected motor
with mains switch, backup fuses and
additional protection
Fig. 7Mains connection, three-phase motors
TM05 3942 1812TM05 3495 1512
8
7.4 Additional protection
DANGER
Electric shock
Death or serious personal injury
- Only use residual-current circuit
breakers (ELCB, GFCI, RCD) of type B.
The residual-current circuit breaker must be marked
with the following symbol:
The total leakage current of all the electrical
equipment in the installation must be taken into
account. You find the leakage current of the motor in
sections 26.2 Leakage current and 27.2 Leakage
current, AC.
This product can cause a direct current in the
protective earth conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of
unstable power supply or a faulty installation. The
motor is stopped if the voltage falls outside the
permissible voltage range. The motor restarts
automatically when the voltage is again within the
permissible voltage range. Therefore, no additional
protection relay is required.
The motor is protected against transients
from the power supply according to EN
61800-3. In areas with high lightning
intensity, we recommend external lightning
protection.
Overload protection
If the upper load limit is exceeded, the motor
automatically compensates for this by reducing the
speed and stops if the overload condition persists.
The motor remains stopped for a set period. After
this period, the motor automatically attempts to
restart. The overload protection prevents damage to
the motor. Consequently, no additional motor
protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor
as an additional protection. When the temperature
rises above a certain level, the motor automatically
compensates for this by reducing the speed and
stops if the temperature keeps rising. The motor
remains stopped for a set period. After this period,
the motor automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power
supply with a quality corresponding to IEC
60146-1-1, class C, to ensure correct motor
operation at phase unbalance. This also ensures
long life of the components.
7.5 Connection terminals
The descriptions and terminal overviews in this
section apply to both single-phase and three-phase
motors.
For maximum torques, see section 29.1 Torques.
7.5.1 Connection terminals, advanced functional
module, FM 300
The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector
outputs
• Input and output for Grundfos Digital Sensor
Not applicable for TPE, TPED, NBE, NBGE, NKE
and NKGE pumps. The factory-fitted
differential-pressure sensor for TPE, TPED, NBE,
NKE Series 2000 is connected to this input.
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop
input where open circuit results in stop. A
jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if
digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by
reinforced insulation in their entire
lengths.
English (GB)
9
• Inputs and outputs
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
English (GB)
All inputs and outputs are internally separated
from the mains-conducting parts by reinforced
insulation and galvanically separated from other
circuits.
All control terminals are supplied by protective
extra-low voltage, PELV, thus ensuring protection
against electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250
VAC .
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
• Mains supply, terminals N, PE, L or L1, L2, L3,
PE.
10
* If you use an external supply source, make sure
that there is a connection to GND.
Fig. 8Connection terminals, FM 300 (option)
TM05 3509 3512
Terminal TypeFunction
Normally
NC
closed
contact
Normally
NO
open contact
Normally
NC
closed
contact
Normally
NO
open contact
18GNDEarth
11DI4/OC2
Pt100/1000
19
input 2
Pt100/1000
17
input 1
12AO
9GNDEarth
14AI3
1DI2
LiqTec sensor
21
input 1
20GND
LiqTec sensor
22
input 2
10DI3/OC1
4AI1
2DI1
5+5 V
Signal relay 1
LIVE or PELVC1Common
Signal relay 2
PELV onlyC2Common
Digital input and
output, configurable.
Open collector:
Maximum 24 V
resistive or inductive.
Pt100/1000 sensor
input
Pt100/1000 sensor
input
Analog output:
0-20 mA / 4-20 mA
0-10 V
Analog input:
0-20 mA / 4-20 mA
0-10 V
Digital input,
configurable
LiqTec sensor input
white conductor
Earth
brown and black
conductors
LiqTec sensor input
blue conductor
Digital input and
output, configurable.
Open collector:
Maximum 24 V
resistive or inductive.
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
Digital input,
configurable
Supply to
potentiometer and
sensor
Terminal TypeFunction
6GNDEarth
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDEarth
15+24 VSupply
8+24 VSupply
26+5 V
23GNDEarth
25GDS TX
24GDS RX
7AI2
Supply to
potentiometer and
sensor
Grundfos Digital
Sensor output
Grundfos Digital
Sensor input
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V /
0-10 V
7.6 Signal cables
• Use screened cables with a cross-sectional area
of minimum 0.5 mm
external on/off switch, digital inputs, setpoint and
sensor signals.
• Connect the screens of the cables to frame at
both ends with good connection. The screens
must be as close as possible to the terminals.
See fig. 9.
Fig. 9Stripped cable with screen and wire
• Always tighten screws for frame connections
• The wires in the motor terminal box must be as
connections
whether a cable is fitted or not.
short as possible.
2
and maximum 1.5 mm2 for
English (GB)
TM02 1325 4402
11
7.7 Bus connection cable
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
English (GB)
7.7.1 New installations
For the bus connection, use a screened 3-core cable
with a cross-sectional area of minimum 0.5 mm
maximum 1.5 mm
If the motor is connected to a unit with a cable clamp
which is identical to the one on the motor, connect
2
.
the screen to this cable clamp.
If the unit has no cable clamp, leave the screen
unconnected at this end. See fig. 10.
Fig. 10 Connection with screened 3-core cable
7.7.2 Replacing a motor
• If you have used a screened 2-core cable in the
existing installation, connect the cable as shown
in fig. 11.
Fig. 11 Connection with screened 2-core cable
• If you have used a screened 3-core cable in the
existing installation, follow the instructions in
section 7.7.1 New installations.
2
and
8. Operating conditions
8.1 Maximum number of starts and stops
The number of starts and stops via the power supply
must not exceed four times per hour.
When switched on via the power supply, the pump
starts after approximately 5 seconds.
If a higher number of starts and stops is desired, use
the input for external start-stop when starting or
stopping the pump.
When started via an external on/off switch, the pump
starts immediately.
8.2 Alternating operation of twin-head
pumps
On twin-head pumps, the duty and backup pumps
must be alternated on a regular basis, i.e. once a
week, to ensure an even distribution of the operating
TM05 3973 1812TM02 8842 0904
hours on both pumps. The pumps alternate
automatically. See section 13.43 "Multipump setup"
(Setup of multi-pump system).
If twin-head pumps are used for pumping domestic
hot water, the duty and backup pumps must be
alternated on a regular basis, i.e. once a day, to
avoid blocking of the backup pump due to deposits
such as calcareous deposits. As default, the pumps
alternate automatically. See section
13.43 "Multipump setup" (Setup of multi-pump
system).
8.3 Ambient temperature
8.3.1 Ambient temperature during storage and
transportation
Minimum: -30 °C
Maximum: 60 °C.
8.3.2 Ambient temperature during operation
3 x 200-240 V3 x 380-500 V
Minimum-20 °C-20 °C
Maximum40 °C50 °C
The motor can operate with the rated power output,
P2, at 50 °C, but continuous operation at higher
temperatures reduces the expected product life. If
the motor is to operate at ambient temperatures
between 50 and 60 °C, select an oversized motor.
Contact Grundfos for further information.
12
8.4 Installation altitude
0
60
80
90
70
100
500 1000 1500 2000 2500 3000 3500
Altitude [m]
P2 [%]
500
480
460
440
420
380
400
0 500 10002000 2500 3000 3500
4000
1500
Supply voltage [V]
Altitude [m]
Supply voltage [V]
Altitude [m]
Installation altitude is the height above sea level of
the installation site.
Motors installed up to 1000 m above sea level can
be loaded 100 %.
The motors can be installed up to 3500 m above sea
level.
Motors installed more than 1000 m above
sea level must not be fully loaded due to
the low density and consequent low
cooling effect of the air.
Fig. 12 Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure
correct clearance according to EN 60664-1:2007,
you must adapt the supply voltage to the altitude:
Fig. 13 Supply voltage for three-phase motor in
250
240
230
220
210
200
relation to altitude
0 500 1000 1500 2000 2500 3000 3500 4000
8.5 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %,
one of the drain holes in the drive-end flange must
be open. See section 6.6 Drain holes.
8.6 Motor cooling
To ensure cooling of motor and electronics, observe
the following:
• Position the motor in such a way that adequate
cooling is ensured. See section 6.4 Ensuring
motor cooling.
• The temperature of the cooling air must not
exceed 50 °C.
• Keep cooling fins and fan blades clean.
9. User interfaces
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as
the product may be very hot.
TM05 5243 3717TM06 9866 3617TM06 9867 3617
You can make the pump settings by means of the
following user interfaces:
Control panels
• Standard control panel.
• Advanced control panel.
Remote controls
• Grundfos GO.
If the power supply to the pump is switched off, the
settings are stored.
WARNING
Electric shock
Death or serious personal injury
- If the control panel is cracked or
perforated, replace it immediately.
Contact the nearest Grundfos sales
company.
See section 10. Standard control panel.
See section 11. Advanced control panel.
See section 12. Grundfos GO.
English (GB)
Fig. 14 Supply voltage for single-phase motor in
relation to altitude
13
10. Standard control panel
1
2
3
4
5
Stop
0
6
3
bar
[bar]
English (GB)
Pump variant
Fitted as
standard
TPE, TPED●-
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
Fig. 15 Standard control panel
Pos.Symbol Description
Grundfos Eye
1
2-
3
4
Shows the operating status of
the pump.
See section 17. Grundfos Eye
for further information.
Light fields for indication of
setpoint.
Up and down. Changes the
setpoint.
Allows radio communication
with Grundfos GO and other
products of the same type.
When you try to establish
radio communication between
the pump and Grundfos GO or
another pump, the green
indicator light in Grundfos Eye
on the pump flashes
continuously. Press on the
pump control panel to allow
radio communication with
Grundfos GO and other
products of the same type.
Option
--
10.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or . The light fields on the control panel indicates
the setpoint set.
10.1.1 Pump in differential-pressure control
The following example applies to a pump in an
TM05 4848 3512
application where a pressure sensor gives a
feedback to the pump. If you retrofit the sensor to the
pump, set it manually as the pump does not
automatically register a connected sensor.
Figure 16 shows that the light fields 5 and 6 are
activated, indicating a desired setpoint of 3 m with a
sensor measuring range from 0 to 6 m. The setting
range is equal to the sensor measuring range.
Pos.Symbol Description
Makes the pump ready for
operation as well as starts and
stops the pump.
Start
If you press the button when
the pump is stopped, the
5
pump only starts if no other
functions with higher priority
have been enabled. See
section 16. Priority of settings.
Stop
If you press the button when
the pump is running, the pump
always stops. The "Stop" text
next to the button is on.
mode
Fig. 16 Setpoint set to 3 m, differential-pressure
control
TM05 4894 3512
14
10.1.2 Pump in constant-curve control mode
H
Q
Maximum
Minimum
H
Q
H
Q
In constant-curve control mode, the pump
performance lies between the maximum and
minimum curve of the pump. See fig. 17.
Fig. 17 Pump in constant-curve control mode
Setting to maximum curve:
•Press
• To change back, press
Example
Pump set to maximum curve.
Figure 18 shows that the top light field is flashing,
indicating maximum curve.
Fig. 18 Maximum-curve duty
Setting to minimum curve:
•Press
• To change back, press continuously until the
continuously to change over to the
maximum curve of the pump. The top light field
flashes. When the top light field is on, press
for 3 seconds until the light field starts flashing.
continuously until the
desired setpoint is indicated.
continuously to change over to the
minimum curve of the pump. The bottom light
field flashes. When the bottom light field is on,
for 3 seconds until the light field starts
press
flashing.
desired setpoint is indicated.
Example
Pump set to minimum curve.
Figure 19 shows that the bottom light field is
flashing, indicating minimum curve.
Fig. 19 Minimum-curve duty
10.1.3 Start-stop of pump
TM05 4895 2812TM05 4896 2812
Start the pump by pressing
pressing until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is
stopped, the "Stop" text next to the button is on. You
can also stop the pump by continuously pressing
until none of the light fields are on.
You can also stop the pump with the Grundfos GO or
via a digital input set to External stop. See section
16. Priority of settings.
10.1.4 Resetting of fault indications
Reset a fault indication in one of the following ways:
• Via the digital input if it has been set to Alarm
• Briefly press or
• Switch off the power supply until the indicator
• Switch the external start-stop input off and on.
• With Grundfos GO.
If you have stopped the pump by pressing
and the "Stop" text on the control panel
is on, you can only give it free to operation
by pressing again.
If you have stopped the pump by pressing
, you can restart it by pressing or by
using Grundfos GO.
or by continuously
resetting.
on the pump. This does not
change the setting of the pump.
You cannot reset a fault indication by pressing
if the buttons have been locked.
or
lights are off.
English (GB)
TM05 4897 2812
15
11. Advanced control panel
1
2
3
4
5
6
English (GB)
Pump variant
Fitted as
standard
TPE, TPED-●
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
Fig. 20 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
Shows the operating status of
the pump.
For further information, see
section 17. Grundfos Eye.
2-Graphical colour display.
3Goes one step back.
Navigates between main
menus, displays and digits.
When you change the menu, the
display always shows the top
display of the new menu.
Navigates between submenus.
Changes value settings.
4
Note: If you have disabled the
possibility to make settings with
the Enable/disable settings
function, then you can enable it
again temporarily by pressing
these buttons simultaneously for
at least 5 seconds. See section
13.28 "Buttons on product"
(Enable/disable settings).
Option
●-
Pos. Symbol Description
Saves changed values, resets
alarms and expands the value
field.
Enables radio communication
with Grundfos GO and other
products of the same type.
When you try to establish radio
communication between the
4
pump and Grundfos GO or
another pump, the green
indicator light in Grundfos Eye
flashes. A note also appears in
the pump display stating that a
wireless device wants to
connect to the pump. Press
on the pump control panel to
allow radio communication with
Grundfos GO and other
products of the same type.
Makes the pump ready for
operation and starts, and stops
TM05 4849 1013
5
the pump.
Start:
If you press the button when the
pump is stopped, the pump only
starts if no other functions with
higher priority have been
enabled. See section 16. Priority
of settings.
Stop:
If you press the button when the
pump is running, the pump is
always stopped. When you stop
the pump via this button, the
icon appears in the bottom of
the display.
6Goes to the Home menu.
16
11.1 Home display
Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1234
56789
Home
Fig. 21 Example of Home display
Pos. Symbol Description
Home
This menu shows up to four
user-defined parameters. You
1
2-
3-
4-
5
6
7
8
can select parameters shown
as shortcut icon , and when
pressing you go directly to
the "Settings" display for the
selected parameter.
Status
This menu shows the status of
the pump and system as well
as warnings and alarms.
Settings
This menu gives access to all
setting parameters. You can
make detailed settings of the
pump in this menu.
See section 13. Description of
functions.
Assist
This menu enables assisted
pump setup, provides a short
description of the control
modes and offers fault advice.
See section 14. Selection of
control mode.
Indicates that the pump has
been stopped via the
button.
Indicates that the pump is
functioning as master pump in
a multipump system.
Indicates that the pump is
functioning as a slave pump in
a multipump system.
Indicates that the pump is
operating in a multipump
system. See section
13.43 "Multipump setup"
(Setup of multi-pump system).
Pos. Symbol Description
Indicates that the possibility to
make settings has been
9
disabled for protective reasons.
See section 13.28 "Buttons on
product" (Enable/disable
settings).
English (GB)
11.2 Startup guide
The pump incorporates a startup guide which is
started at the first startup. See section 13.37 Run
start-up guide. After the startup guide, the main
menus appear in the display.
TM06 4516 2415
17
11.3 Menu overview for advanced control panel
English (GB)
11.3.1 Main menus
TPE,
TPED,
Home
Status
Operating status●● ●
Operating mode, from●● ●
Control mode●● ●
Pump performance●● ●
Actual controlled value●● ●
Resulting setpoint●● ●
Speed●● ●
Acc. flow and specific energy●● ●
Power and energy consumption●● ●
Measured values●● ●
Set date and time●● ●
Analog input 1●● ●
Analog input 2●● ●
Analog input 3●● ●
Pt100/1000 input 1●● ●
Pt100/1000 input 2●● ●
Analog output●● ●
Warning and alarm●● ●
Actual warning or alarm●● ●
Warning log●● ●
Alarm log●● ●
Operating log●● ●
Operating hours●● ●
Trend data●● ●
Fitted modules●● ●
Date and time●● ●
Product identification●● ●
Motor bearing monitoring●● ●
Multi-pump system--●
System operating status--●
System performance--●
18
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
Multipump
NKE
Series
2000
●● ●
TPE,
TPED,
NBE,
NKE
Series
2000
system
Multipump
system
TPE,
NBE,
NKE,
TPE,
TPED,
NBE,
NKE
Series
2000
TPED,
Status
System input power and energy--●
Pump 1, multi-pump system--●
Pump 2, multi-pump system--●
Pump 3, multi-pump system--●
Pump 4, multi-pump system--●
NBGE,
NKGE
Multipump
system
English (GB)
TPE,
TPED,
Settings
Setpoint●● ●13.1 Setpoint26
Operating mode●● ●13.2 Operating mode26
Set manual speed●● ●13.3 Set manual speed26
"Set user-defined speed"●● ●
Control mode●● ●13.5 "Control mode"27
Analog inputs●● ●
Analog input 1, setup●● ●
Analog input 2, setup●● ●
Analog input 3, setup●● ●
13.43 "Multipump setup"
(Setup of multi-pump system)
13.43 "Multipump setup"
(Setup of multi-pump system)
13.44 Description of control
mode
English (GB)
49
49
53
21
12. Grundfos GO
+
+
1
2
English (GB)
The pump is designed for wireless radio or infrared
communication with Grundfos GO.
Grundfos GO enables setting of functions and gives
access to status overviews, technical product
information and actual operating parameters.
Grundfos GO offers the following mobile interfaces
(MI).
Fig. 22 Grundfos GO communicating with the
Pos. Description
pump via radio or infrared connection,
IR
Grundfos MI 204:
Add-on module enabling radio or infrared
communication. You can use MI 204 in
conjunction with an Apple iPhone or iPod
1
with Lightning connector, for example fifth
generation or later iPhone or iPod.
MI 204 is also available together with an
Apple iPod touch and a cover.
Grundfos MI 301:
Separate module enabling radio or infrared
communication. You can use the module in
2
conjunction with an Android or iOS-based
smart device with Bluetooth connection.
12.1 Communication
When Grundfos GO initiates communication with the
pump, the indicator light in the middle of Grundfos
Eye flashes green. See section 17. Grundfos Eye.
Furthermore, on pumps fitted with an advanced
control panel a text appears in the display saying
that a wireless device is trying to establish
connection. Press on the pump in order to
establish connection with Grundfos GO or press
to reject connection.
Establish communication using one of these
communication types:
• radio communication
• infrared communication.
12.1.1 Radio communication
Radio communication can take place at distances up
to 30 m. The first time Grundfos GO communicates
with the pump, you must enable communication by
pressing or on the pump control panel. Later
when communication takes place, the pump is
TM06 6256 0916
recognized by Grundfos GO and you can select the
pump from the "List" menu.
12.1.2 Infrared communication
When communicating via infrared light, Grundfos GO
must be pointed at the pump control panel.
22
12.2 Menu overview for Grundfos GO
Dashboard
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
●● ●
TPE,
TPED,
"Status"
NBE,
NBGE,
NKE,
NKGE
"System mode"--●
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
*
"Resulting setpoint"●●
"Resulting system
setpoint"
--●
"Actual controlled value"●●●
*
*
"Motor speed (rpm, %)"●● -
"Power consumption"●● -
"Power cons., sys."--●
*
"Energy consumption"●●
"Energy cons., sys."--●
"Acc. flow, specific energy"●●●
*
*
"Operating hours"●●
"Operating hours, system"--●
*
"Analog input 1"●● -
"Analog input 2"●● -
"Analog input 3"●● -
"Pt100/1000 input 1"●● -
"Pt100/1000 input 2"●● -
"Analog output"●● -
"Digital input 1"●● -
"Digital input 2"●● -
"Digital in/output 3"●● -
"Digital in/output 4"●● -
"Fitted modules"●● -
"Pump 1"--●
"Pump 2"--●
"Pump 3"--●
"Pump 4"--●
*
*
*
*
* Only available if Grundfos GO is connected to a multipump system.
English (GB)
23
English (GB)
"Settings"
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
SectionPage
"Setpoint"●● ●13.1 Setpoint26
"Operating mode"●● ●13.2 Operating mode26
"Set user-defined
speed"
●● ●13.4 "Set user-defined speed"26
"Control mode"●● ●13.5 "Control mode"27
"Proportional-pressure
setup"
"Buttons on product"●● ●
"Controller"●● ●
-●-13.6 "Proportional-pressure setup"32
13.28 "Buttons on product"
(Enable/disable settings)
13.14 "Controller" ("Controller
settings")
"Operating range"●● ●13.15 Operating range40
"Ramps"●●13.19 "Ramps"44
"Pump number"●● -13.23 "Number" (Pump number)45
"Radio communication"●● -
13.24 "Radio communication"
(Enable/disable radio comm.)
You can set the setpoint for all control modes in this
submenu when you have selected the desired
control mode. See section 13.5 "Control mode".
Factory setting
See section 30. Factory settings.
13.2 Operating mode
Pump variantOperating mode
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Possible operating modes:
• Normal
The pump runs according to the selected control
mode.
•Stop
The pump stops.
•Min.
Use the minimum-curve mode in periods in which
a minimum flow is required.
•Max.
Use the maximum-curve mode in periods in
which a maximum flow is required.
This operating mode is for instance suitable for
systems with hot-water priority.
• Manual
The pump is operating at a manually set speed.
In Manual the setpoint via bus is overruled.
See section 13.3 Set manual speed.
• "User-defined speed"
The motor is operating at a speed set by the
user. See section 13.4 "Set user-defined speed".
All operating modes are illustrated in the figure
below.
●
●
TM06 4024 1515
Fig. 23 Operating modes
13.3 Set manual speed
Pump variantSet manual speed
●
●
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu is only available in the advanced control
panel. With Grundfos GO, you set the speed via the
Setpoint menu.
You can set the pump speed in % of the maximum
speed. When you have set the operating mode to
Manual, the pump starts running at the set speed.
The speed can then be changed manually via
Grundfos GO or via the advanced control panel.
Factory setting
See section 30. Factory settings.
●
●
13.4 "Set user-defined speed"
You can set the motor speed in % of the maximum
speed. When you have set the operating mode to
"User-defined speed", the motor runs at the set
speed.
The operating mode must be set to Normal
before a control mode can be enabled.
Factory setting
See section 30. Factory settings.
13.5.1 "Proportional pressure"
●
●
Fig. 24 "Proportional pressure"
Example
• Factory-fitted differential-pressure sensor.
Fig. 25 "Proportional pressure"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings")
English (GB)
TM05 7909 1613
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The head of the pump is reduced at decreasing
water demand and increased at rising water
demand. See fig. 24.
This control mode is especially suitable in systems
with relatively large pressure losses in the
distribution pipes. The head of the pump increases
proportionally to the flow in the system to
compensate for the large pressure losses in the
distribution pipes.
The setpoint can be set with an accuracy of 0.1
metre. The head against a closed valve is half the
setpoint.
For more information about settings, see section
13.6 "Proportional-pressure setup".
"Proportional
pressure"
-
●
27
13.5.2 "Constant pressure"
H
Q
p
p
H
Q
t
t
t
English (GB)
Pump variant"Constant pressure"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
We recommend this control mode if the pump is to
deliver a constant pressure, independently of the
flow in the system. The pump maintains a constant
pressure independently of the flow rate. See fig. 26.
Fig. 26 "Constant pressure"
This control mode requires an external pressure
sensor as shown in the examples below. You can set
the pressure sensor in the Assist menu. See section
13.41 Assisted pump setup.
Examples
• One external pressure sensor.
13.5.3 "Constant temperature"
Pump variant
●
●
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
"Constant
temperature"
●
●
This control mode ensures a constant temperature.
Constant temperature is a comfort control mode that
you can use in domestic hot-water systems to control
the flow to maintain a constant temperature in the
system. See fig. 28.
TM05 7901 1613
TM05 7900 1613
Fig. 28 "Constant temperature"
This control mode requires an external temperature
sensor. See the examples below.
Examples
• One external temperature sensor.
Fig. 27 "Constant pressure"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
28
Fig. 29 "Constant temperature"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
13.5.4 "Constant differential pressure"
H
Q
p
p
p
p
p
p
p
p
p
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
"Constant differential
pressure"
●
●
The pump maintains a constant differential pressure,
independently of the flow in the system. See fig. 30.
This control mode is primarily suitable for systems
with relatively small pressure losses.
Fig. 30 "Constant differential pressure"
This control mode requires either an internal or
external differential-pressure sensor or two external
pressure sensors. See the examples below.
Examples
• Factory-fitted differential-pressure sensor, only
TPE, TPED, NBE, NKE Series 2000.
• One external differential-pressure sensor.
The pump uses the input from the sensor to
control the differential pressure. You can set the
sensor manually or by using the Assist menu.
See section 13.41 Assisted pump setup.
• Two external pressure sensors.
Constant differential-pressure control is
achievable with two pressure sensors. The
pump uses the inputs from the two sensors and
calculates the differential pressure. The sensors
TM05 7901 1613
must have the same unit and must be set as
feedback sensors. You can set the sensors
manually, sensor by sensor, or by using the
Assist menu. See section 13.41 Assisted pump
setup.
English (GB)
Fig. 31 "Constant differential pressure"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
29
13.5.5 "Constant differential temperature"
H
Q
△t
t
t
t
t
H
Q
Q
set
Qset
Q
English (GB)
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
"Constant differential
temperature"
The pump maintains a constant differential
temperature in the system and the pump
performance is controlled according to this. See fig.
32.
Fig. 32 "Constant differential temperature"
This control mode requires either two external
temperature sensors or one external
differential-temperature sensor. See the examples
below.
Examples
• Two external temperature sensors.
• One external differential-temperature sensor.
13.5.6 "Constant flow rate"
Pump variant"Constant flow rate"
TPE, TPED, NBE,
●
●
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The pump maintains a constant flow in the system,
independently of the head. See fig. 34.
●
●
TM05 7955 1713
Fig. 34 "Constant flow rate"
TM05 7954 1713
This control mode requires an external flow sensor.
See the example below.
Example
• One external flow sensor.
Fig. 35 "Constant flow rate"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
Fig. 33 "Constant differential temperature"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
30
13.5.7 "Constant level"
H
Q
L
L
H
Q
Pump variant"Constant level"
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The pump maintains a constant level, independently
of the flow rate. See fig. 36.
●
●
Fig. 36 "Constant level"
This control mode requires an external level sensor.
The pump can control the level in a tank in two ways:
• as an emptying function where the pump draws
the liquid from the tank.
• as a filling function where the pump pumps the
liquid into the tank.
See fig. 37.
The type of level control function depends on the
setting of the built-in controller. See section
13.14 "Controller" ("Controller settings").
Examples
• One external level sensor.
– emptying function.
• One external level sensor.
– filling function.
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
13.5.8 "Constant other value"
Pump variant
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
"Constant other
value"
●
●
Any other value is kept constant.
13.5.9 "Constant curve"
Pump variant"Constant curve"
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can set the pump to operate according to a
TM05 7941 1613
constant curve, like an uncontrolled pump. See fig.
38.
You can set the desired speed in % of the maximum
speed in the range from 25 to 100 % (110 %).
●
●
Fig. 38 "Constant curve"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
English (GB)
TM05 7957 1713
Fig. 37 "Constant level"
31
13.6 "Proportional-pressure setup"
PTPTPTPTTT
TT
TT
Q
Q
DPT
DPTDPT
LTLT
DPT DTT
1
5
24
910
7
12
816 15
313614
11
English (GB)
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
"Proportional-pressure
setup"
TPE, TPED, NBE,
NKE Series 2000
"Control-curve function"
You can set the curve either to quadratic or linear.
"Zero-flow head"
You can set this value in % of the setpoint. With a
setting of 100 %, the control mode is equal to
constant differential pressure.
13.7 Analog inputs
Pump variantAnalog inputs
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
FunctionTerminal*
Analog input 1, setup 4
Analog input 2, setup 7
Analog input 3, setup 14
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
Set the analog input for a feedback sensor via the
Assisted pump setup menu. See section
13.41 Assisted pump setup.
If you want to set an analog input for other purposes,
you can do this manually.
You can set the analog inputs via the Setup, analog
input menu. See section 13.42 Setup, analog input.
If you perform the manual setting via Grundfos GO,
you need to enter the menu for the analog input
under the Settings menu.
Function
You can set the analog inputs to these functions:
•Not active.
• Feedback sensor.
• Ext. setpoint infl..
See section 13.16.1 Setpoint influence.
• Other function.
Measured parameter
Select one of the parameters, such as the parameter
to be measured in the system by the sensor
connected to the actual analog input. See fig. 39.
-
●
TM06 2328 3914
Fig. 39 Overview of sensor locations
●
●
Sensor function, measured
parameter
Inlet pressure1
Pos.
Diff. press., inlet2
Liquid temp.3
Diff. press.,outlet4
Diff. press.,pump5
Operating mode6
Press. 2, external7
Diff. press., ext.8
Storage tank level9
Feed tank level10
Pump flow11
Flow, external12
Liquid temp.13
Temperature 114
Temperature 215
Diff. temp., ext.16
Ambient temp.Not shown
Other parameterNot shown
Unit
Available measuring units:
ParameterPossible measuring units
Pressurebar, m, kPa, psi, ft
Levelm, ft, in
3
Flow ratem
/h, l/s, yd3/h, gpm
Liquid temp.°C, °F
Other parameter%
32
"Electrical signal"
Select signal type:
• 0.5-3.5 V
•0-5 V
• 0-10 V
• 0-20 mA
• 4-20 mA.
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
See section 30. Factory settings.
13.7.1 Setting two sensors for differential
measurement
In order to measure the difference of a parameter
between two points, set the corresponding sensors
as follows:
If you want to use the control mode
"constant differential pressure", you must
choose the function Feedback sensor for
the analog input of both sensors.
Analog input
for sensor 2
Differential
pressure, outlet
Pressure 2,
external
13.8 Built-in Grundfos sensor
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can select the function of the built-in sensor in
the Built-in Grundfos sensor menu.
Set the Built-in Grundfos sensor via the Assisted
pump setup menu. See section 13.41 Assisted pump
setup.
Built-in Grundfos
sensor
-
●
If you perform the setting manually in the advanced
control panel, you must enter the Analog inputs
menu under the Settings menu in order to access the
Built-in Grundfos sensor menu.
If you perform the setting manually via Grundfos GO,
you need to enter the menu for the Built-in Grundfos
sensor under the Settings menu.
Function
You can set the built-in sensor to these functions:
• Grundfos diff.-pressure sensor
- Not active
- Feedback sensor
- Setpoint influence
- Other function.
Factory setting
See section 30. Factory settings.
13.9 Pt100/1000 inputs
Pump variantPt100/1000 inputs
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
FunctionTerminal
Pt100/1000 input 1, setup17 and 18
Pt100/1000 input 2, setup18 and 19
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
Set the Pt100/1000 input for a feedback sensor via
the Assisted pump setup menu. See section
13.41 Assisted pump setup.
If you want to set a Pt100/1000 input for other
purposes, you can do this manually.
You can set the analog inputs via the Setup, analog
input menu. See section 13.42 Setup, analog input.
If you perform the manual setting via Grundfos GO,
you need to enter the menu for the Pt100/1000 input
under the Settings menu.
Function
You can set the Pt100/1000 inputs to these
functions:
•Not active
• Feedback sensor
• Ext. setpoint infl.
See section 13.16.1 Setpoint influence.
• Other function.
●
●
English (GB)
33
Measured parameter
TT
TT
TT
DTT
43
12
English (GB)
Select one of the parameters, such as the parameter
to be measured in the system by the Pt100/1000
sensor connected to the actual Pt100/1000 input.
See fig. 40.
Fig. 40 Overview of Pt100/1000 sensor
locations
ParameterPos.
Liquid temp.1
Temperature 12
Temperature 23
Ambient temp.Not shown
Measuring range
-50 to 204 °C.
Factory setting
See section 30. Factory settings.
13.10 Digital inputs
Pump variantDigital inputs
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
FunctionTerminal*
Digital input 1, setup2 and 6
Digital input 2, setup1 and 9
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
To set a digital input, make the settings below.
Function
Select one of these functions:
•Not active
When set to Not active, the input has no function.
• External stop
When the input is deactivated, open circuit, the
pump stops.
• Min. (minimum speed)
When the input is activated, the pump runs at the
set minimum speed.
• Max. (maximum speed)
When the input is activated, the pump runs at the
set maximum speed.
34
• "User-defined speed"
When the input is activated, the motor runs at a
speed set by the user.
• External fault
When the input is activated, a timer is started. If
the input is activated for more than 5 seconds,
the pump stops and a fault is indicated. This
function depends on input from external
equipment.
• Alarm resetting
When the input is activated, a possible fault
TM06 4012 1515
indication is reset.
• Dry running
When this function has been selected, lack of
inlet pressure or water shortage can be detected.
When lack of inlet pressure or water shortage,
dry running, is detected, the pump stops. The
pump cannot restart as long as the input is
activated. This requires the use of an accessory,
such as:
– a pressure switch installed on the inlet side of
the pump
– a float switch installed on the inlet side of the
pump.
• Accumulated flow
When this function has been selected, the
accumulated flow can be registered. This
requires the use of a flowmeter which gives a
feedback signal as a pulse per defined flow of
water. See section 13.18 "Pulse flowmeter
setup".
• Predefined setpoint digit 1, applies only to digital
input 2.
●
●
When digital inputs are set to predefined
setpoint, the pump operates according to a
setpoint based on the combination of the
activated digital inputs. See section
13.16.2 "Predefined setpoints".
The priority of the selected functions in relation to
each other appears from section 16. Priority of
settings. A stop command always has the highest
priority.
Activation delay
T input
T input > T1 + T2T input < T1 + T2
T1 T2
T1 T2
T1T1T2T2
T1
T1
T input
T2
Mode C
Mode B
Mode A
Digital
input
T input > T1 + T2T input < T1 + T2
T input
T input
+ 24V
DO 3/4
External
controller
Select the activation delay, T1.
It is the time between the digital signal and the
activation of the selected function.
Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 41.
•Not active
• active with interrupt, mode A
• active without interrupt, mode B
• active with after-run, mode C.
Select the duration time, T2.
It is the time which, together with the mode,
determines how long the selected function is active.
Range: 0 to 15,000 seconds.
13.11 Digital inputs/outputs
Pump variantDigital inputs/outputs
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
FunctionTerminal*
Digital input/output 3, setup10 and 16
Digital input/output 4, setup11 and 18
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
You can select if the interface must be used as input
or output. The output is an open collector and you
can connect it to for example an external relay or
controller such as a PLC.
●
●
English (GB)
Fig. 41 Duration timer function of digital inputs
Factory setting
See section 30. Factory settings.
TM06 4949 3415
Fig. 42 Example of configurable digital inputs or
To set a digital input or output, make the settings
below.
outputs
TM06 4463 2315
Mode
You can set the digital input or output 3 and 4 to act
as digital input or digital output:
• Digital input
• Digital output.
Function
You can set the digital input or output 3 and 4 to
these functions:
35
Possible functions, digital input or output 3
T input
T input > T1 + T2T input < T1 + T2
T1 T2
T1 T2
T1T1T2T2
T1
T1
T input
T2
Mode C
Mode B
Mode A
Digital
input
T input > T1 + T2T input < T1 + T2
T input
T input
English (GB)
Function if input
See details in section
13.10 Digital inputs
• Not active
• External stop
•Min.
•Max.
• "User-defined
speed"
• External fault
• Alarm resetting
• Dry running
Function if output
See details in section
13.12 "Signal relays 1
and 2" (Relay
outputs)
• Not active
• Ready
•Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
• Accumulated flow
• "Predefined setpoint
digit 2"
Possible functions, digital input or output 4
Function if output
Function if input
See details in section
13.10 Digital inputs
See details in section
13.12 "Signal relays 1
and 2" (Relay
outputs)
• Not active
• External stop
•Min.
•Max.
• "User-defined
speed"
• External fault
• Alarm resetting
• Dry running
• Not active
• Ready
•Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
• Accumulated flow
• "Predefined setpoint
digit" 3"
Activation delay
Select the activation delay, T1.
It is the time between the digital signal and the
activation of the selected function.
Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 41.
•Not active
• active with interrupt, mode A
• active without interrupt, mode B
• active with after-run, mode C.
Select the duration time, T2.
It is the time which, together with the mode,
determines how long the selected function is active.
Range: 0 to 15,000 seconds.
Fig. 43 Duration timer function of digital inputs
Factory setting
See section 30. Factory settings.
TM06 4949 3415
36
13.12 "Signal relays 1 and 2" (Relay
outputs)
Pump variant"Signal relays 1 and 2"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
FunctionTerminal*
Relay output 1NC, C1, NO
Relay output 2NC, C2, NO
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
The pump incorporates two signal relays for
potential-free signalling. For further information, see
section 18. Signal relays.
Function
You can configure the signal relays to be activated
by one of the following incidents:
•Not active.
• Ready
The pump can be running or is ready to run and
no alarms are present.
•Alarm
There is an active alarm and the pump is
stopped.
• "Operating" (Operation)
"Operating" equals "Running" but the pump is still
in operation when it has been stopped due to a
warning.
• "Running" (Pump running)
• Warning
There is an active warning.
• Limit 1 exceeded
When the Limit 1 exceeded function is activated,
the signal relay is activated. See section
13.17 Limit-exceeded function.
• Limit 2 exceeded
When the Limit 2 exceeded function is activated,
the signal relay is activated. See section
13.17 Limit-exceeded function.
• Relubricate
• "External fan control" (Control of external fan)
When you select "External fan control", the relay
is activated if the internal temperature of the
motor electronics reach a preset limit value.
Factory setting
See section 30. Factory settings.
●
●
13.13 Analog output
Pump variantAnalog output
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
FunctionTerminal*
Analog output12
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
The analog output enables the transfer of certain
operating data to external control systems.
To set the analog output, make the settings below.
Output signal
• 0-10 V
• 0-20 mA
• 4-20 mA.
Function of analog output
• Actual speed.
Signal
range
[V, mA]
Actual speed
0100200
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
The reading is a percentage of nominal speed.
• Actual value
Signal
range
[V, mA]
Sensor
Actual value
min
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
The reading is a percentage of the range between
sensor
and sensor
min
max
.
[%]
●
●
Sensor
max
English (GB)
37
• Resulting setpoint
English (GB)
Signal
range
[V, mA]
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
The reading is a percentage of the external setpoint
range.
• Motor load
Signal
range
[V, mA]
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
The reading is a percentage of the range between 0
and 200 % of the maximum permissible load at the
actual speed.
• Motor current
Signal
range
[V, mA]
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
The reading is a percentage of the range between 0
and 200 % of the rated current.
• Limit 1 exceeded and Limit 2 exceeded
Resulting setpoint
[%]
0100
Motor load
[%]
0100
Motor current
[%]
0100200
• Flow rate
Signal
range
[V, mA]
0-10 V0 V5 V10 V
0-20 mA0 mA10 mA20 mA
4-20 mA4 mA12 mA20 mA
The reading is a percentage of the range between 0
and 200 % of the nominal flow.
Factory setting
See section 30. Factory settings.
Flow rate
[%]
0100200
13.14 "Controller" ("Controller settings")
Pump variant"Controller"
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The pumps have a factory setting of gain, Kp, and
integral time, T
However, if the factory setting is not the optimum
setting, you can change the gain and the integral
time.
• Set the gain within the range from 0.1 to 20.
• Set the integral time within the range from 0.1 to
3600 seconds. If you select 3600 seconds, the
controller functions as a P controller.
Furthermore, you can set the controller to inverse
control. This means that if the setpoint is increased,
the speed is reduced. In the case of inverse control,
the gain must be set within the range from -0.1 to
-20.
.
i
●
●
Signal
range
[V, mA]
0-10 V0 V10 V
0-20 mA0 mA20 mA
4-20 mA4 mA20 mA
The Limit-exceeded function is typically used for
monitoring of secondary parameters in the system. If
the limit is exceeded, an output, warning or alarm is
activated.
38
Limit-exceeded function
Output not
active
Output active
Guidelines for setting of PI controller
p
p
p
p
ǻS
L1
L1
ǻS
L2
t
L2
t
t
L2
t
t
t
L2
Q
p
p
L
L
The tables below show the recommended controller
settings:
"Differential-temperature
control"
K
p
T
i
"Differential-pressure
control"
K
p
T
i
0.50.5
L1 < 5 m: 0.5
0.5
L1 > 5 m: 3
L1 > 10 m: 5
L1: distance in metres between pump and sensor.
K
1)
p
Cooling
system
T
2)
"Temperature
control"
Heating
system
0.5-0.510 + 5L2
-0.510 + 5L2
L2: distance in metres between heat exchanger and
sensor.
"Flow control"K
"Constant pressure
control"
i
p
T
0.50.5
K
p
T
0.50.5
0.10.5
English (GB)
i
i
0.5-0.530 + 5L2
1)
In heating systems, an increase in pump
performance results in a rise in temperature at
the sensor.
2)
In cooling systems, an increase in pump
performance results in a drop in temperature at
the sensor.
L2: distance in metres between heat exchanger and
sensor.
"Level control"K
p
T
-2.5100
2.5100
i
39
Rules of thumb
Fixed maximum speed
User-set maximum speed
"Operating range"
User-set minimum speed
Fixed minimum speed
24 %
13 %
0 %
67 %
100 %
100
0
100 %
0
1.2
2
0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
Actual input
signal, 60 %
External
setpoint
signal
Setpoint
Sensor max.
Sensor min.
Actual
setpoint
English (GB)
If the controller is too slow-reacting, increase the
gain.
If the controller is hunting or unstable, dampen the
system by reducing the gain or increasing the
integral time.
Factory setting
See section 30. Factory settings.
13.15 Operating range
Pump variantOperating range
TPE, TPED, NBE, NBGE,
NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Set the operating range as follows:
• Set the minimum speed within the range from
fixed minimum speed to user-set maximum
speed.
• Set the maximum speed within the range from
user-set minimum speed to fixed maximum
speed.
The range between the user-set minimum and
maximum speeds is the operating range. See fig. 44.
Speeds below 25 % may result in noise from the
shaft seal.
13.16 External setpoint function
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can influence the setpoint by an external signal,
either via one of the analog inputs or, if an advanced
functional module is fitted, via one of the Pt100/1000
inputs.
●
●
Before you can enable the External
setpoint function, you must set one of the
analog inputs or Pt100/1000 inputs to
Setpoint influence.
See sections 13.7 Analog inputs and
13.9 Pt100/1000 inputs.
If more than one input has been set to Setpoint
influence, the function selects the analog input with
the lowest number, for example Setting of pump, and
ignores the other inputs, for example Analog input 3
or "Pt100/1000 input 1".
Example with constant pressure with linear
influence
Actual setpoint: actual input signal x (setpoint sensor min.) + sensor min.
At a lower sensor value of 0 bar, a setpoint of 2 bar
and an external setpoint of 60 %, the actual setpoint
is 0.60 x (2 - 0) + 0 = 1.2 bar.
[bar]
External setpoint
function
●
●
Fig. 44 Example of minimum and maximum
Factory setting
See section 30. Factory settings.
40
settings
TM00 6785 5095
Fig. 45 Example of setpoint influence with
-50204 C
sensor feedback
TM06 4165 1615
Example with constant curve with linear
100
0
100 %
0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
25
61
85
External
setpoint
signal
Speed [%]
Fixed
maximum
speed
Actual input
signal, 60 %
User-set
minimum.
speed
Setpoint
Actual setpoint
100
0
100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
Setpoint influence[%]
External
input
100
0
20100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Setpoint influence [%]
External
input
Normal
Stop
influence
Actual setpoint: actual input signal x (setpoint user-set minimum speed) + user-set minimum
speed.
At a user-set minimum speed of 25 %, a setpoint of
85 % and an external setpoint of 60 %, the actual
setpoint is 0.60 x (85 - 25) + 25 = 61 %. See fig. 46.
You can select these functions:
•Not active
When set to Not active, the setpoint is not
influenced from any external function.
• Linear function
The setpoint is influenced linearly from 0 to 100
%. See fig. 47.
English (GB)
Fig. 46 Example of setpoint influence with
constant curve
Factory setting
See section 30. Factory settings.
13.16.1 Setpoint influence
Pump variantSetpoint influence
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The table below gives an overview of the types of
setpoint influence and the availability depending on
pump type.
Setpoint influence
Not active●●
Linear function●●
Linear with Stop●●
Influence table●●
TM06 4525 2515
-50204 C
TM06 4166 1615TM06 4167 1615
Fig. 47 Linear function
• Linear with Stop
– In the input signal range from 20 to 100 %, the
setpoint is influenced linearly.
If the input signal is below 10 %, the pump
changes to operating mode Stop. If the input
signal is above 15 %, the operating mode is
changed back to Normal. See fig. 48.
●
●
Pump type
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Fig. 48 Linear with Stop
41
• Influence table
100
0
100 %0
3.5 V0.5
5 V0
10 V0
20 mA0
20 mA4
-50204 C
Setpoint influence [%]
External
input
0
1
2
3
4
5
6
7
Digital input 4
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
Setpoint 6
Setpoint 7
Digital input 3
Digital input 2
Actual setpoint
Stop
Normal
setpoint
English (GB)
The setpoint is influenced by a curve made out of
two to eight points. There will be a straight line
between the points and a horizontal line before
the first point and after the last point.
Fig. 49 Influence table, example with five points
Before the Digital inputs can be enabled,
set one of the analog inputs or Pt100/1000
inputs to External setpoint function.
See sections 13.7 Analog inputs and
13.9 Pt100/1000 inputs.
13.16.2 "Predefined setpoints"
Pump variant"Predefined setpoints"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can set and activate seven predefined setpoints
by combining the input signals to digital inputs 2, 3
and 4. See the table below.
Set the digital inputs 2, 3 and 4 to "
setpoints" if all seven predefined setpoints are to be
used. You can also set one or two of the digital inputs
to "Predefined setpoints" but this limits the number of
predefined setpoints available.
Figure 50 shows how you can use the digital inputs
TM06 4170 1615
to set seven predefined setpoints. Digital input 2 is
open and digital inputs 3 and 4 are closed. If you
compare with the table above, you can see that
"Predefined setpoint 6" is activated.
●
●
Fig. 50 Principle sketch showing how
predefined setpoints function
TM06 4269 1815
If all digital inputs are open, the pump either stops or
runs at the normal setpoint. Set the desired action
with Grundfos GO or with the advanced control
panel.
Factory setting
See section 30. Factory settings.
42
13.17 Limit-exceeded function
1
2
44
56
3
A
Time [s]
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This function can monitor a measured parameter or
one of the internal values such as speed, motor load
or motor current. If a set limit is reached, a selected
action can take place. You can set two
limit-exceeded functions meaning that you can
monitor two parameters or two limits of the same
parameter simultaneously.
Limit-exceeded
function
●
●
"Detection delay"
You can set a detection delay which ensures that the
monitored parameter stays above or below a set limit
in a set time before the function is activated.
"Resetting delay"
The resetting delay is the time from which the
measured parameter differs from the set limit
including the set hysteresis band and until the
function is reset.
Example
The function is to monitor the outlet pressure of a
pump. If the pressure is below 5 bar for more than 5
seconds, a warning must be given. If the outlet
pressure is above 7 bar for more than 8 seconds,
you must reset the warning.
English (GB)
The function requires setting of the following:
Measured
Here you set the measured parameter to be
monitored.
"Limit"
Here you set the limit which activates the function.
"Hysteresis band"
Here you set the hysteresis band.
"Limit exceeded when"
Here you can set the function to be activated when
the selected parameter exceeds or drops below the
set limit.
• "Above limit"
The function is activated if the measured
parameter exceeds the set limit.
• "Below limit"
The function is activated if the measured
parameter drops below the set limit.
Action
If the value exceeds a limit, you can define an action.
You can select the following actions:
• "No action"
The pump remains in its current state. Use this
setting if you only want to have a relay output
when the limit is reached. See section
13.12 "Signal relays 1 and 2" (Relay outputs).
• "Warning/alarm"
There is a warning.
•Stop
The pump stops.
•Min.
The pump reduces speed to minimum.
•Max.
The pump increases speed to maximum.
• "User-defined speed"
The pumps runs at a speed set by the user.
Fig. 51 "Limit exceeded" (example)
Pos. Setting parameterSetting
1Measured
"Outlet
pressure"
2"Limit"5 bar
3"Hysteresis band"2 bar
4"Limit exceeded when""Below limit"
5"Detection delay"5 seconds
6"Resetting delay"8 seconds
Limit-exceeded function
A
active
-
-"Action""Warning"
Factory setting
See section 30. Factory settings.
TM06 4603 2515
43
13.18 "Pulse flowmeter setup"
User set ramp-upUser set ramp-down
Speed
Time
User set
minimum
Fixed initial rampFixed final ramp
User set
maximum
Fixed
maximum
0
English (GB)
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
"Pulse flowmeter
setup"
TPE, TPED, NBE, NKE
Series 2000
You can connect an external pulse flowmeter to one
of the digital inputs in order to register the actual and
accumulated flows. Based on this, you can also
calculate the specific energy.
To enable a pulse flowmeter, set one of the
digital-input functions to Accumulated flow and set
the pumped volume per pulse. See section
13.10 Digital inputs.
Factory setting
See section 30. Factory settings.
13.19 "Ramps"
13.20 "Standstill heating"
Pump variant"Standstill heating"
TPE, TPED, NBE,
●
●
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
●
●
You can use this function to avoid condensation in
humid environments. When you set the function to
"Active" and the pump is in operating mode Stop, a
low AC voltage is applied to the motor windings. The
voltage is not high enough to make the motor rotate
but ensures that sufficient heat is generated to avoid
condensation in the motor including the electronic
parts in the drive.
Remember to remove the drain plugs and
fit a cover over the motor.
13.21 Motor bearing monitoring
Pump variant"Ramps"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The ramps determine how quickly the motor can
accelerate and decelerate, respectively, during
start-stop or setpoint changes.
You can set the following:
• acceleration time, 0.1 to 300 seconds
• deceleration time, 0.1 to 300 seconds.
The times apply to the acceleration from 0 rpm to
fixed maximum speed and the deceleration from
fixed maximum speed to 0 rpm.
At short deceleration times, the deceleration of the
motor may depend on load and inertia as there is no
possibility of actively braking the motor.
If the power supply is switched off, the deceleration
of the motor only depends on load and inertia.
Fig. 52 Ramp-up and ramp-down
Factory setting
See section 30. Factory settings.
44
Pump variant
●
●
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can set the motor bearing monitoring function to
these values:
Motor bearing
monitoring
●
●
•"Active"
•Not active
When the function is set to "Active", a counter in the
controller starts counting the mileage of the
bearings.
The counter continues counting even if the function
is changed to Not active, but a warning is not given
when it is time for replacement.
When the function is changed to "Active" again, the
accumulated mileage is again used to calculate the
replacement time.
Factory setting
See section 30. Factory settings.
TM03 9439 0908
13.22 "Service"
Pump variant"Service"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
"Time until next service" (Motor bearing service)
This display shows when to replace the motor
bearings. The controller monitors the operating
pattern of the motor and calculates the period
between bearing replacements.
Displayable values:
• "in 2 years"
• "in 1 year"
• "in 6 months"
• "in 3 months"
• "in 1 month"
• "in 1 week"
•"Now"
"Bearing replacements"
Indicates the number of bearing replacements that
have been done during the lifetime of the motor.
Bearings replaced (Motor bearing maintenance)
When the bearing monitoring function is active, the
controller gives a warning when the motor bearings
are to be replaced.
When you have replaced the motor bearings, confirm
this action by pressing [Bearings replaced].
●
●
13.23 "Number" (Pump number)
Pump variant"Number"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can allocate a unique number to the pump. This
makes it possible to distinguish between pumps in
connection with bus communication.
Factory setting
See section 30. Factory settings.
●
●
13.24 "Radio communication"
(Enable/disable radio comm.)
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can set the radio communication to either
enabled or disabled. You can use this function in
areas where radio communication is not allowed.
IR communication remains active.
Factory setting
See section 30. Factory settings.
"Radio
communication"
●
●
13.25 Language
Pump variantLanguage
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu is only available in the advanced control
panel.
In this menu you can select the desired language. A
number of languages is available.
●
●
13.26 "Date and time" (Set date and time)
Pump variant"Date and time"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
You can set date and time as well as how they are to
be shown in the display:
• Select date format:
YYYY-MM-DD
DD-MM-YYYY
MM-DD-YYYY.
• Select time format:
HH:MM 24-hour clock
HH:MM am/pm 12-hour clock.
• Set date
•Set time.
Factory setting
See section 30. Factory settings.
●
●
English (GB)
45
13.27 "Unit configuration" (Units)
English (GB)
Pump variant"Unit configuration"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
In this menu you can select between SI and US
units. The setting can be made generally for all
parameters or customised for each parameter.
Factory setting
See section 30. Factory settings.
13.28 "Buttons on product"
(Enable/disable settings)
Pump variant"Buttons on product"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
In this display, you can disable the possibility of
making settings.
Grundfos GO
If you set the buttons to "Not active", the buttons on
the standard control panel are disabled. If you set
the buttons to "Not active" on pumps with an
advanced control panel, see below.
Advanced control panel
If you have disabled the settings, you can still use
the buttons to navigate through the menus but you
cannot make changes in the Settings menu.
When you have disabled the possibility to make
settings, the symbol appears in the display.
To unlock the pump and allow settings, press and
simultaneously for at least 5 seconds.
Standard control panel
The button always remains active but you can
only unlock all other buttons on the pump with
Grundfos GO.
Factory setting
See section 30. Factory settings.
13.29 Delete history
• "Delete energy consumption".
13.30 Define Home display
●
●
Pump variantDefine Home display
TPE, TPEDNBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
This menu is only available in the advanced control
panel.
In this menu, you can set the Home display to show
up to four user-set parameters.
●
13.31 Display settings
Pump variantDisplay settings
TPE, TPED-
●
●
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
This menu is only available in the advanced control
panel.
In this menu you can adjust the display brightness
and set whether or not the display is to turn off if no
buttons have been activated for a period of time.
●
13.32 "Store settings" (Store actual
settings)
Pump variant"Store settings"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Grundfos GO
In this menu, you can store the actual settings for
later use in the same pump or in other pumps of the
same type.
Advanced control panel
In this menu, you can store the actual settings for
later use in the same pump.
●
●
Pump variantDelete history
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
In this menu, you can delete the following historic
data:
• "Delete operating log".
• "Delete heat energy data".
46
-
-
13.33 "Recall settings" (Recall stored
settings)
Pump variant"Recall settings"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
Grundfos GO
In this menu, you can recall stored settings from a
number of previously stored settings that the pump
then uses.
Advanced control panel
In this menu, you can recall the last stored settings
that the pump then uses.
●
●
13.34 "Undo"
Pump variant"Undo"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu is only available in Grundfos GO.
In this display, you can undo all settings that have
been made with Grundfos GO in the current
communication session. You cannot undo a Recall
stored settings action.
●
●
13.35 "Pump name"
Pump variant"Pump name"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu is only available in Grundfos GO.
In this display, you can give the pump a name. In this
way, you can easily identify the pump when
connecting with Grundfos GO.
Factory setting
See section 30. Factory settings.
●
●
13.36 "Connection code"
Pump variant"Connection code"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu is only available in Grundfos GO.
You can set a connection code to avoid having to
press the connection button each time and to restrict
remote access to the product.
Setting the code in the product using Grundfos
GO
1. Connect Grundfos GO to the product.
2. In the product dashboard, select "Settings".
3. Choose "Connection code".
4. Enter the wanted code and press [OK].
The code must be a character string, ASCII. You
can always modify the code. The old code is not
needed.
Setting the code in Grundfos GO
You can set a default connection code in Grundfos
GO so that it automatically attempts to connect to the
selected product via this code.
When you select a product with the same connection
code in Grundfos GO, Grundfos GO automatically
connects to the product and you do not have to press
the connection button on the module.
Set the default code in Grundfos GO in this way:
1. In the main menu, under "General", select
"Settings".
2. Choose "Remote".
3. Enter the connection code in the field "Preset
connection code". The field now says
"Connection code set".
You can always modify the default connection code
by pressing [Delete] and entering a new one.
If Grundfos GO fails to connect and ask you to press
the connection button on the product, it means that
the product has no connection code or has a
different connection code. In this case, you can only
establish connection via the connection button.
After setting a connection code, you must switch off
the product until the light in Grundfos Eye turns off
before you can use the new connection code.
Factory setting
See section 30. Factory settings.
●
●
English (GB)
47
13.37 Run start-up guide
English (GB)
Pump variantRun start-up guide
TPE, TPED●
NBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
This menu is only available in the advanced control
panel.
The startup guide automatically starts when you start
the pump for the first time.
You can always run the startup guide later via this
menu.
The startup guide guides you through the general
settings of the pump.
• Language. See section 13.25 Language.
• Select date format.
See section 13.26 "Date and time" (Set date and
time).
• Set date.
See section 13.26 "Date and time" (Set date and
time).
• Select time format.
See section 13.26 "Date and time" (Set date and
time).
•Set time.
See section 13.26 "Date and time" (Set date and
time).
• Setting of pump
– Go to Home
– Run with Constant curve/Run with Constant
pressure.
See section 13.5 "Control mode"
– Go to "Assisted pump setup".
See section 13.41 Assisted pump setup.
– Return to factory settings.
* Applies only for pumps with advanced functional
module, FM 300. For further information, see
section 20. Identification of functional module.
13.38 Alarm log
13.39 Warning log
Pump variantWarning log
TPE, TPED, NBE,
NBGE, NKE, NKGE
●
TPE, TPED, NBE, NKE
Series 2000
This menu contains a list of logged warnings from
the product. The log shows the name of the warning,
when the warning occurred and when it was reset.
●
●
13.40 Assist
Pump variantAssist
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The menu consist of functions which take you
through the steps needed to set the pump.
●
●
13.41 Assisted pump setup
Pump variantAssisted pump setup
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The menu guides you through the following:
Setting of pump
• Selection of control mode. See page 27.
• Configuration of feedback sensors.
• Adjusting the setpoint. See page 26.
• Controller settings. See page 38.
• Summary of settings.
●
●
Pump variantAlarm log
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu contains a list of logged alarms from the
product. The log shows the name of the alarm, when
the alarm occurred and when it was reset.
48
●
●
Example of how to use the Assisted pump setup
for setting up the pump to constant pressure:
Grundfos GO
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode "Constant pressure".
4. Read the description of this control mode.
5. Select which analog input to use as sensor input.
6. Select sensor function according to where the
sensor is installed in the system. See fig. 39.
7. Select electrical input signal according to the
sensor specifications.
8. Select measuring unit according to the sensor
specifications.
9. Set the minimum and maximum sensor values
according to the sensor specifications.
10. Set the desired setpoint.
11. Set the controller settings K
recommendations in section 13.14 "Controller"
("Controller settings").
12. Type the pump name.
13. Check the summary of settings and confirm
them.
Advanced control panel
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode Const. pressure.
4. Select which analog input to be used as sensor
input.
5. Select the measured parameter to be controlled.
See fig. 39.
6. Select measuring unit according to the sensor
specifications.
7. Set the minimum and maximum sensor values
according to the sensor specifications.
8. Select electrical input signal according to the
sensor specifications.
9. Set the setpoint.
10. Set the controller settings K
recommendations in section 13.14 "Controller"
("Controller settings").
11. Check the summary of settings and confirm them
by pressing [OK].
and Ti. See the
p
and Ti. See
p
13.42 Setup, analog input
Pump variantSetup, analog input
TPE, TPEDNBE, NBGE, NKE,
NKGE & TPE, TPED,
NBE, NKE Series 2000
This menu is only available in the advanced control
panel.
The menu guides you through the following:
Setup, analog input
• Analog inputs 1 to 3. See page 32.
• Pt100/1000 input 1 and 2. See page 33.
• Adjusting the setpoint. See page 26.
• Summary.
●
13.43 "Multipump setup" (Setup of
multi-pump system)
Pump variant"Multipump setup"
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
The multipump function enables the control of two
pumps connected in parallel without the use of
external controllers. The pumps in a multipump
system communicate with each other via the
wireless GENIair connection or the wired GENI
connection.
A multipump system is set via a selected pump, i.e.
the master pump, which is the first selected pump.
If two pumps in the system are configured with an
outlet-pressure sensor, both pumps can function as
master pumps and take over the master pump
function if the other fails. This provides additional
redundancy in the multipump system.
The multipump functions are described in the
following sections.
●
●
English (GB)
49
13.43.1 Alternating operation
English (GB)
Alternating operation functions as a duty/standby
operating mode and is possible with two pumps of
same size and type connected in parallel. The main
purpose of the function is to ensure an even amount
of running hours and to ensure that the standby
pump takes over if the running pump stops due to an
alarm.
Each pump requires a non-return valve in series with
the pump.
You can choose between two alternating operation
modes:
• "Alternating operation, time"
Pump changeover to the other is based on time.
• "Alternating operation, energy"
Pump changeover to the other is based on
energy consumption.
If the duty pump fails, the other pump takes over
automatically.
13.43.2 Backup operation
Backup operation is possible with two pumps of
same size and type connected in parallel. Each
pump requires a non-return valve in series with the
pump.
One pump is operating continuously. The backup
pump is operated for a short time each day to
prevent seizing up. If the duty pump stops due to a
fault, the backup pump starts automatically.
13.43.3 Cascade operation
Cascade operation ensures that the pump
performance is automatically adapted to the
consumption by switching pumps on or off. The
system thus runs as energy-efficiently as possible
with a constant pressure and a limited number of
pumps.
All pumps in operation run at equal speed. Pump
changeover is automatic and depends on energy,
operating hours and fault.
If the pump system consists of two to four
single-head pumps connected in parallel, the pumps
must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
Set the control mode to "Constant pressure" or
"Constant curve".
This function is available with up to 4 motors
installed in parallel. The motors must be of the same
size and the pumps must be of the same model.
• The performance is adjusted to the demand
through cutting pumps in or out and through
parallel control of the pumps in operation.
• The controller maintains a constant pressure
through continuous adjustment of the speed of
the pumps.
• Pump changeover is automatic and depends on
load, operating hours and fault detection.
• All pumps in operation run at the same speed.
• The number of pumps in operation also depends
on the energy consumption of the pumps. If only
one pump is required, two pumps will run at a
lower speed if this results in a lower energy
consumption.
• If several motors in the system have a sensor,
they can all function as master and take over the
master function if the other motors fail.
13.43.4 Setting a multipump system
You can set a multipump system in the following
ways:
• Grundfos GO and wireless pump connection
• Grundfos GO and wired pump connection
• Advanced control panel and wireless pump
connection
• Advanced control panel and wired pump
connection
See step-by-step descriptions below.
50
Grundfos GO and wireless pump connection
1. Power on both pumps.
2. Establish contact to one of the pumps with
Grundfos GO.
3. Set the needed analog and digital inputs via
Grundfos GO according to the connected
equipment and the required functionality. See
section 13.41 Assisted pump setup.
4. Assign a pump name to the pump using Grundfos
GO. See section 13.35 "Pump name".
5. Disconnect Grundfos GO from the pump.
6. Establish contact to the other pump.
7. Set the needed analog and digital inputs via
Grundfos GO according to the connected
equipment and the required functionality. See
section 13.41 Assisted pump setup.
8. Assign a pump name to the pump using Grundfos
GO. See section 13.35 "Pump name".
9. Select the "Assist" menu and "Multipump setup".
10. Select the desired multipump function. See
sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade
operation.
11. Press [>] to continue.
12. Set the time for pump changeover such as the
time at which the alternation between the two
pumps is to take place. This step applies only if
you have selected "Alternating operation, time"
and if the pumps are fitted with FM 300.
13. Press [>] to continue.
14. Select "Radio" as the communication method to
be used between the two pumps.
15. Press [>] to continue.
16. Press "Select pump 2".
17. Select the pump from the list.
Use the [OK] or button to identify the pump.
18. Press [>] to continue.
19. Confirm the multipump setup by pressing [Send].
20. Press [Finish] in the "Setup complete" dialog box.
21. Wait for the green indicator light in the middle of
Grundfos Eye to light up.
The multipump system has now been set.
Grundfos GO and wired pump connection
1. Connect the two pumps with each other with a
3-core screened cable between the GENIbus
terminals A, Y, B.
2. Power on both pumps.
3. Establish contact to one of the pumps with
Grundfos GO.
4. Set the needed analog and digital inputs via
Grundfos GO according to the connected
equipment and the required functionality. See
section 13.41 Assisted pump setup.
5. Assign a pump name to the pump using Grundfos
GO. See section 13.35 "Pump name".
6. Assign pump number 1 to the pump. See section
13.23 "Number" (Pump number).
7. Disconnect Grundfos GO from the pump.
8. Establish contact to the other pump.
9. Set the needed analog and digital inputs via
Grundfos GO according to the connected
equipment and the required functionality. See
section 13.41 Assisted pump setup.
10. Assign a pump name to the pump using Grundfos
GO. See section 13.35 "Pump name".
11. Assign pump number 2 to the pump. See section
13.23 "Number" (Pump number).
12. Select the "Assist" menu and choose "Multipump
setup".
13. Select the desired multipump function. See
sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade
operation.
14. Press [>] to continue.
15. Set the time for pump changeover such as the
time at which the alternation between the two
pumps is to take place. This step applies only if
you have selected "Alternating operation, time"
and if the pumps are fitted with FM 300.
16. Press [>] to continue.
17. Select "BUS cable" as the communication
method to be used between the two pumps.
18. Press [>] to continue.
19. Press "Select pump 2".
20. Select the additional pump from the list.
Use the [OK] or button to identify the
additional pump.
21. Press [>] to continue.
22. Press [Send].
23. Press [Finish] in the "Setup complete" dialog box.
24. Wait for the green indicator light in the middle of
Grundfos Eye to light up.
The multipump system has now been set.
English (GB)
51
Advanced control panel and wireless pump
English (GB)
connection
1. Power on both pumps.
2. On both pumps, set the needed analog and
digital inputs according to the connected
equipment and the required functionality. See
section 13.41 Assisted pump setup.
3. Select the Assist menu on one of the pumps and
choose Setup of multi-pump system.
4. Press [>] to continue.
5. Select Wireless as the communication method to
be used between the two pumps.
6. Press [>] to continue.
7. Select the desired multipump function. See
sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade
operation.
8. Press [>] three times to continue.
9. Press [OK] to search for other pumps.
The green indicator light in the middle of
Grundfos Eye flashes on the other pumps.
10. Press the connect button on the pump which is to
be added to the multipump system.
11. Press [>] to continue.
12. Set the time for pump changeover i.e. the time at
which the alternation between the two pumps is
to take place. This step applies only if you have
selected "Alternating operation, time" and if the
pumps are fitted with FM 300.
13. Press [>] to continue.
14. Press [OK].
The multipump function icons appear in the
bottom of the control panels.
The multipump system has now been set.
Advanced control panel and wired pump
connection
1. Connect the two pumps with each other with a
3-core screened cable between the GENIbus
terminals A, Y, B.
2. Set the needed analog and digital inputs
according to the connected equipment and the
required functionality. See section 13.41 Assisted
pump setup.
3. Assign pump number 1 to the first pump. See
section 13.23 "Number" (Pump number).
4. Assign pump number 2 to the other pump. See
section 13.23 "Number" (Pump number).
5. Select the Assist menu on one of the pumps and
choose Setup of multi-pump system.
6. Press [>] to continue.
7. Select Wired GENIbus as the communication
method to be used between the two pumps.
8. Press [>] twice to continue.
9. Select the desired multipump function. See
sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade
operation.
10. Press [>] to continue.
11. Press [OK] to search for other pumps.
12. Select the additional pump from the list.
13. Press [>] to continue.
14. Set the time for pump changeover i.e. the time at
which the alternation between the two pumps is
to take place.
This step applies only if you have selected
"Alternating operation, time" and if the pumps are
fitted with FM 300.
15. Press [>] to continue.
16. Press [OK].
The multipump function icons appear in the
bottom of the control panels.
The multipump system has now been set.
52
Disabling the multipump function via Grundfos
GO
1. Select the "Assist" menu.
2. Select "Multipump setup".
3. Select "Disable".
4. Press [>] to continue.
5. Confirm the multipump setup by pressing [Send].
6. Press [Finish].
The multipump function has now been disabled.
Disabling a multipump via advanced control
panel
1. Select the Assist menu.
2. Select Setup of multi-pump system.
3. Press [>] to continue.
4. Confirm No multi-pump function by pressing
[OK].
5. Press [>] to continue.
6. Press [OK].
The multipump system has now been disabled.
13.44 Description of control mode
English (GB)
Pump variant
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu is only available in the advanced control
panel.
This menu describes each of the possible control
modes. See also section 13.5 "Control mode".
Description of control
mode
-
●
13.45 Assisted fault advice
Pump variantAssisted fault advice
TPE, TPED, NBE,
NBGE, NKE, NKGE
TPE, TPED, NBE, NKE
Series 2000
This menu gives guidance and corrective actions in
case of pump failures.
●
●
53
14. Selection of control mode
H
Hset
Hset
2
H
Q
H
Q
H
Q
English (GB)
System applicationSelect this control mode
In systems with relatively large pressure losses in the distribution pipes and
in air-conditioning and cooling systems.
• Two-pipe heating systems with thermostatic valves and the following:
– very long distribution pipes
– strongly throttled balancing valves
Proportional pressure
– differential-pressure regulators
– large pressure losses in those parts of the system through which the
total quantity of water flows, for example boiler, heat exchanger and
distribution pipe up to the first branching.
• Primary circuit pumps in systems with large pressure losses in the
primary circuit.
• Air-conditioning systems with the following:
– heat exchangers, fan coils
– cooling ceilings
– cooling surfaces.
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and the following:
– sized for natural circulation
– small pressure losses in those parts of the system through which the
total quantity of water flows, for example boiler, heat exchanger and
distribution pipe up to the first branching, or modified to a high
differential temperature between flow pipe and return pipe, for
example district heating.
Constant differential pressure
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing
valves.
• Primary circuit pumps in systems with small pressure losses in the
primary circuit.
In systems with a fixed system characteristic.
Examples:
• one-pipe heating systems
Constant temperature and
constant differential
temperature
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
If an external controller is installed, the pump is able to change from one
constant curve to another, depending on the value of the external signal.
You can also set the pump to operate according to the maximum or
minimum curve, like an uncontrolled pump:
• Use the maximum-curve mode in periods in which a maximum flow is
required. This operating mode is for instance suitable for systems with
hot-water priority.
• Use the minimum-curve mode in periods in which a minimum flow is
required.
54
Constant curve
System applicationSelect this control mode
Q
set
H
Q
H
Q
In systems requiring a constant flow, independently of pressure drop.
Constant flow rate
Examples:
• chillers for air-conditioning
• heating surfaces
• cooling surfaces.
English (GB)
In systems requiring a constant tank level, independently of the flow rate.
Examples:
• process-water tanks
• boiler-condensate tanks.
In systems with pumps operating in parallel.
The multipump function enables the control of two to four single-head
pumps connected in parallel and twin-head pumps without the use of
external controllers. The pumps in a multipump system communicate with
each other via the wireless GENIair connection or the wired GENI
connection.
15. Bus signal
The pump supports serial communication via an
RS-485 input. The communication is carried out
according to the Grundfos GENIbus protocol and
enables connection to other pumps as well as a
building management system or another external
control system.
Via a bus signal, you can remote-set pump operating
parameters, such as setpoint and operating mode. At
the same time, the pump can, via the bus, provide
status information about important parameters, such
as actual value of control parameter, input power and
fault indications.
Contact Grundfos for further information.
If you use a bus signal, the number of
settings available via Grundfos GO are
reduced.
Constant level
Assist menu
Setup of multi-pump system
55
16. Priority of settings
English (GB)
You can always set the pump to stop by pressing
on the pump control panel. When the pump is not in
Stop mode, you can always set the pump to stop by
continuously pressing . Furthermore, you can set
the pump to maximum speed by continuously
pressing . You can always set the pump to
operation at maximum speed or to stop with
Grundfos GO.
If two or more functions are enabled at the same
time, the pump operates according to the function
with the highest priority.
Example
If you have set the pump to maximum speed via the
digital input, the pump control panel or Grundfos GO
can only set the pump to Manual or Stop.
The priority of the settings appears from the table
below.
Priority
1Stop
2Stop *
3Manual
4
5Stop
6
7Stop
8"Max. speed"
9"Min. speed"
10"Start"
11"Max. speed"
12"Min. speed"
13"Min. speed"
14"Start"
15"Start"
* "Stop" and "Max. speed" settings made with
Grundfos GO or on the motor control panel can
be overruled by another operating-mode
command sent from a bus, for example "Start". If
the bus communication is interrupted, the motor
resumes its previous operating mode, for
example "Stop", selected with Grundfos GO or on
the motor control panel.
Start-stop
button
Grundfos GO or control
panel on pump
"Max. speed"*/
"User-defined speed"
Digital inputBus communication
"User-defined
speed"
56
17. Grundfos Eye
A
The operating condition of the pump is indicated by
the Grundfos Eye on the control panel. See fig. 53,
A.
TM05 5993 4312
Fig. 53 Grundfos Eye
Grundfos EyeIndicationDescription
No lights are on.
The two opposite green indicator lights
are rotating in the direction of rotation
of the pump when seen from the
non-drive end.
The two opposite green indicator lights
are permanently on.
The power is off.
The pump is not running.
The power is on.
The pump is running.
The power is on.
The pump is not running.
English (GB)
One yellow indicator light is rotating in
the direction of rotation of the pump
when seen from the non-drive end.
One yellow indicator light is
permanently on.
The two opposite red indicator lights
flash simultaneously.
The green indicator light in the middle
flashes quickly four times.
The green indicator light in the middle
flashes continuously.
The green indicator light in the middle
is permanently on.
The green indicator light in the middle
flashes quickly while Grundfos Go is
exchanging data with the pump. It
takes a few seconds.
Warning.
The pump is running.
Warning.
The pump has stopped.
Alarm.
The pump has stopped.
This is a feedback signal which the
pump gives in order to ensure
identification of itself.
Grundfos GO or another pump is
trying to communicate with the
pump. Press on the pump control
panel to allow communication.
Remote control with Grundfos GO
via radio.
The pump is communicating with
Grundfos GO via radio connection.
Remote control with Grundfos GO
via infrared light.
The pump is receiving data from
Grundfos GO via infrared
communication.
57
18. Signal relays
NCNO
C
NCNO
C
NCNO
C
NCNO
C
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
NCNO
C
C
NO NC
C
NO NC
NCNO
C
NCNO
C
NCNO
C
NCNOCNCNO
C
C
NO NC
NCNO
C
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
NCNO
C
C
NO NC
NCNO
C
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
NCNO
C
NCNO
C
NCNO
C
C
NO NC
NCNO
C
English (GB)
The pump has two outputs for potential-free signals
via two internal relays.
You can set the signal outputs to Operation, Pump
running, Ready, Alarm and Warning.
The functions of the two signal relays appear from
the table below.
DescriptionGrundfos Eye
Contact position of signal relays when activated
Operation Running ReadyAlarm Warning
Operating
mode
The power is
off.
The pump runs
in "Normal"
mode.
The pump runs
in "Manual"
mode.
The pump is in
operating mode
"Stop".
Warning, but
the pump is
running.
Warning, but
the pump runs
in "Manual"
mode.
Warning, but
the pump was
stopped via a
"Stop"
command.
Alarm, but the
pump is
running.
Off
Green, rotating
Green, rotating
Green, steady
Yellow, rotating
Yellow, rotating
Yellow, steady
Red, rotating
-
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
"Normal",
"Min." or
"Max."
Alarm, but the
pump runs in
"Manual" mode.
The pump has
stopped due to
an alarm.
Red, rotating
Red, flashing
"Manual"
"Stop"
58
19. Installing a communication
A
B
B
C
D
A
A
A
B
interface module
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
minutes before starting any work on the
motor. Make sure that the power supply
cannot be accidentally switched on.
Always use an antistatic service kit when
handling electronic components. This
prevents static electricity from damaging
the components.
When unprotected, place the component
on the antistatic cloth.
Fig. 54 Antistatic service kit
1. Loosen the four screws (fig. 55, A) and remove
the terminal box cover (fig. 55, B).
2. Remove the CIM cover (fig. 56, A) by pressing
the locking tab (fig. 56, B) and lifting the end of
the cover (fig. 56, C). Then lift the cover off the
hooks (fig. 56, D).
Fig. 56 Removing the CIM cover
3. Remove the securing screw (fig. 57, A).
Fig. 57 Removing the securing screw
4. Fit the CIM module by aligning it with the three
TM06 4462 2315TM06 4081 1515
plastic holders (fig. 58, A) and the connecting
plug (fig. 58, B). Press home the module using
your fingers.
English (GB)
TM06 4084 1515TM06 4082 1515TM06 4083 1515
Fig. 55 Removing the terminal box cover
Fig. 58 Fitting the CIM module
59
5. Fit and tighten the securing screw (fig. 57, A) to
A
FCC
English (GB)
1.3 Nm.
6. Make the electrical connections to the CIM
module as described in the instructions delivered
with the module.
7. Connect the cable screens of the bus cables to
earth via one of the earth clamps (fig. 59, A).
Fig. 59 Connecting the cable screens to earth
8. Route the wires for the CIM module. See the
example in fig. 60.
9. Fit the CIM cover.
10. If the CIM module is supplied with an FCC label,
then place this on the terminal box. See fig. 61.
Fig. 61 FCC label
11. Fit the terminal box cover (fig. 55, B) and
cross-tighten the four mounting screws (fig. 55,
A) to 6 Nm.
TM06 4195 1615TM06 4085 1515
Make sure that the terminal box cover is
aligned with the control panel. See section
22. Changing the position of the control
panel.
TM05 7028 0413
Fig. 60 Example of wire routing
60
20. Identification of functional module
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
P
:
n
W
g
g
t
:
DE
:
k
g
g
D
:
T
amb
:
:
V
P
.C.
:
PU
T
C
T
yp
yp
e
:
P.N.
:
Ui:
I
:
f
HzP
S
p
p
:
:
PB
FM
HMICIM
VARIANT
Hp
rpm
::
:
:
PB
:
:
C
:
H
p
pm
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
PF
:
n
W
g
g
t
:
DE
:
k
g
g
D
:
T
amb
:
:
V
P
.C.
:
PU
T
C
T
yp
yp
e
:
P.N.
:
Ui:
I
:
f
HzP
S
p
p
:
:
PBFM
HMI
CIM
VARIANT
Hp
rpm
:
:
::
PB
:
C
:
H
p
pm
:
You can identify the fitted module in one of the
following ways:
Grundfos GO
You can identify the functional module in the "Fitted
modules" menu under "Status".
Pump display
For pumps fitted with the advanced control panel,
you can identify the functional module in the Fitted
modules menu under Status.
Motor nameplate
You can identify the fitted module on the motor
nameplate. See fig. 62.
21. Identification of control panel
You can identify the fitted module in one of the
following ways:
Grundfos GO
You can identify the control panel in the "Fitted
modules" menu under "Status".
Pump display
For pumps fitted with the advanced control panel,
you can identify the control panel in the Fitted
modules menu under Status.
Motor nameplate
You can identify the fitted control panel on the motor
nameplate. See fig. 63.
English (GB)
IN
eri
e
F
i
L
F Am
F
r
/
IM
TM06 1889 3314
Fig. 62 Identification of functional module
VariantDescription
FM 200Standard functional module
FM 300Advanced functional module
Fig. 63 Identification of control panel
VariantDescription
HMI 200Standard control panel
HMI 300Advanced control panel
IN
eri
e
F
i
L
F Am
r
/
IM
TM06 4013 1415
61
22. Changing the position of the
English (GB)
control panel
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
minutes before starting any work on the
motor. Make sure that the power supply
cannot be accidentally switched on.
You can turn the control panel 180 °. Follow the
instructions below.
1. Loosen the four screws, TX25, of the terminal
box cover.
3. Press and hold in the two locking tabs, A, while
gently lifting the plastic cover, B.
Fig. 66 Lifting the plastic cover
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
TM05 5353 3612
Fig. 64 Loosening the screws
2. Remove the terminal box cover.
Fig. 65 Removing the terminal box cover
TM05 5351 3612TM05 5352 3612
Fig. 67 Turning the plastic cover
5. Position the plastic cover correctly on the four
rubber pins, C. Make sure that the locking tabs, A
are placed correctly.
Fig. 68 Positioning the plastic cover
TM05 5354 3612TM05 5355 3612
62
6. Fit the terminal box cover, and make sure that it
is also turned 180 ° so that the buttons on the
control panel are aligned with the buttons on the
plastic cover.
7. Tighten the four screws, TX25, with 5 Nm.
Fig. 69 Fitting the terminal box cover
23. Servicing the product
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
minutes before starting any work on the
motor. Make sure that the power supply
cannot be accidentally switched on.
DANGER
Magnetic field
Death or serious personal injury
- Do not handle the motor or rotor if you
have a pacemaker.
23.1 Motor
If service is needed on the product, please contact
Grundfos Service.
23.2 Pump
Service documentation is available in Grundfos
Product Center
(http://product-selection.grundfos.com/).
If you have any questions, please contact the
nearest Grundfos company or service workshop.
24. Cleaning the product
WARNING
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Check that the
terminal box cover is intact before
spraying water on the product.
In order to avoid condensation in the motor, let the
motor cool down before spraying it with cold water.
25. Megging
Megging of an installation incorporating
MGE motors is not allowed, as the built-in
TM05 5356 3612
electronics may be damaged.
26. Technical data, single-phase
motors
26.1 Supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Recommended fuse size
Motor size
[kW]
0.12 - 0.75610
1.1 - 1.51016
You can use standard as well as quick-blow or
slow-blow fuses.
26.2 Leakage current
Earth leakage current less than 3.5 mA, AC.
Earth leakage current less than 10 mA, DC.
The leakage currents are measured in accordance
with EN 61800-5-1:2007.
Min.
[A]
English (GB)
Max.
[A]
63
27. Technical data, three-phase
English (GB)
motors
27.1 Supply voltage
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Recommended fuse size
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE.
Motor size
[kW]
0.25 - 1.166
1.5610
2.2616
31016
41316
5.51632
7.52032
113232
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Motor size
[kW]
1.11020
1.51020
2.21335
31635
42535
5.53235
You can use standard as well as quick-blow or
slow-blow fuses.
Minimum
[A]
Minimum
[A]
Maximum
[A]
Maximum
[A]
27.2 Leakage current, AC
Speed
[min
1400-2000
1450-2200
2900-4000
4000-5900
The leakage currents are measured without any load
on the shaft and in accordance with EN
61800-5-1:2007.
All voltages refer to GND.
All currents return to GND.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in
severely reduced operating reliability and motor life:
Relay 1:
Maximum contact load: 250 VAC, 2 A or 30 VDC, 2
A.
Relay 2:
Maximum contact load: 30 VDC, 2 A.
GENI terminals: -5.5 to 9.0 VDC or less than 25
mADC.
Other input and output terminals: -0.5 to 26 VDC or
less than 15 mADC.
Digital inputs, DI
Internal pull-up current greater than 10 mA at V
equal to 0 VDC.
Internal pull-up to 5 VDC; currentless for V
than 5 VDC).
Low logic level: V
High logic level: V
Hysteresis: No.
Screened cable: 0.5 - 1.5 mm
less than 1.5 VDC.
i
greater than 3.0 VDC.
i
2
, 28-16 AWG.
Maximum cable length: 500 m.
Open-collector digital outputs, OC
Current sinking capability: 75 mADC, no current
sourcing.
Load types: Resistive or/and inductive.
Low-state output voltage at 75 mADC: Maximum 1.2
VDC.
Low-state output voltage at 10 mADC: Maximum 0.6
VDC.
Overcurrent protection: Yes.
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.
i
greater
i
Analog inputs, AI
Voltage signal ranges:
• 0.5 - 3.5 VDC, AL AU.
• 0-5 VDC, AU.
• 0-10 VDC, AU.
Voltage signal: Ri greater than 100 kΩ at 25 °C.
Leak currents may occur at high operating
temperatures. Keep the source impedance low.
Current signal ranges:
• 0-20 mADC, AU.
• 4-20 mADC, AL AU.
Current signal: Ri equal to 292 Ω.
Current overload protection: Yes. Change to voltage
signal.
Measurement tolerance: - 0/+ 3 % of full scale
(maximum-point coverage).
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m, excl. potentiometer.
Potentiometer connected to +5 V, GND, any AI:
Use maximum 10 kΩ.
Maximum cable length: 100 m.
Analog output, AO
Current sourcing capability only.
Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes.
Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (maximum-point
coverage).
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.
English (GB)
65
Pt100/1000 inputs, PT
English (GB)
Temperature range:
• Minimum -30 °C. 88 Ω/882 Ω.
• Maximum 180 °C. 168 Ω/1685 Ω.
Measurement tolerance: ± 1.5 °C.
Measurement resolution: < 0.3 °C.
Automatic range detection, Pt100 or Pt1000: Yes.
Sensor fault alarm: Yes.
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs*
Use Grundfos LiqTec sensor only.
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Grundfos Digital Sensor input and output, GDS*
Use Grundfos Digital Sensor only.
* Not applicable for TPE, TPED, NBE, NBGE, NKE
and NKGE pumps. The factory-fitted
differential-pressure sensor for TPE, TPED, NBE,
NKE Series 2000 is connected to this input.
Power supplies
+5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC, sourcing only.
• Overload protection: Yes.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC, sourcing only.
• Overload protection: Yes.
Digital outputs, relays
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
Standard used: EN 61800-3.
The table below shows the emission category of the
motor.
C1 fulfils the requirements for residential areas.
Note: When connected to a public network, 11 kW
motors do not comply with the partial weighted
harmonic distortion (PWHD) requirements of EN
61000-3-12. If required by the distribution network
operator, compliance can be obtained in the
following way:
The impedance of the mains cables between the
motor and the point of common coupling (PCC) must
be equivalent to the impedance of a 50 m cable with
a cross-section of 0.5 mm.
C3 fulfils the requirements for industrial areas.
Note: When the motors are installed in residential
areas, supplementary measures may be required as
the motors may cause radio interference.
Motor
[kW]
0.25C1C1
0.37C1C1
0.55C1C1
0.75C1C1
1.1C1C1
1.5C1C1
2.2C1C1
3C1C1
4C1C1
5.5C3/C1*C1
7.5C3/C1*C3/C1*
11- C 3/C1 *
*
C1, if equipped with an external Grundfos EMC
filter.
Immunity: The motor fulfils the requirements for
industrial areas.
Setpoint67 %58 %26
Operating modeNormalNormal26
Control modeConst. curveProp. pressure27
Date and time●●
"Buttons on product"●●46
"Controller" ("Controller settings")38
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
70
Appendix1
Installation in the USA and Canada
In order to maintain the cURus approval,
follow these additional installation
instructions. The UL approval is according
to UL 1004-1.
Outdoor installation
According to UL 778/C22.2 No 108-14, pumps
intended for outdoor use must be marked enclosure
type 3 and the product must be tested at a surface
temperature down to -35 °C. The MLE enclosure is
approved for type 3 or 4 and is rated at a surface
temperature down to 0 °C, thus it is only for indoor
use in UL 778/C22.2 No 108-14 pump applications.
For more information about ambient temperature
during operation, see section 8.3.2 Ambient
temperature during operation.
Canadian Interference-Causing Equipment
Standard
This product complies with the Canadian ICES-003
Class B specifications. This Class B device meets all
the requirements of the Canadian interferencecausing equipment regulations.
Cet appareil numérique de la Classe B est conforme
à la norme NMB-003 du Canada. Cet appareil
numérique de la Classe B respecte toutes les
exigences du Réglement sur le matériel brouilleur du
Canada.
Electrical codes
For USA
This product complies with the Canadian Electrical
Code and the US National Electrical Code.
This product has been tested according to the
national standards for Electronically Protected
Motors:
CSA 22.2 100-14:2014 (applies to Canada only).
UL 1004-1:2015 (applies to USA only).
Pour le Canada
Codes de l'électricité
Ce produit est conforme au Code canadien de
l'électricité et au Code national de l'électricité
américain.
Ce produit a été testé selon les normes nationales
s'appliquant aux moteurs protégés
électroniquement:
CSA 22.2 100.04: 2009 (s'applique au Canada
uniquement).
UL 1004-1: Juin 2011 (s'applique aux États-Unis
uniquement).
Radio communication
For USA
This device complies with part 15 of the FCC rules
and RSS210 of IC rules.
Operation is subject to the following two conditions:
• This device may not cause interference.
• This device must accept any interference,
including interference that may cause undesired
operation of the device.
Users are cautioned that changes or modifications
not expressly approved by Grundfos could void the
user's authority to operate the equipment.
Pour le Canada
Communication radio
Ce dispositif est conforme à la partie 15 des règles
de la FCC et aux normes RSS210 de l'IC.
Son fonctionnement est soumis aux deux conditions
suivantes:
• Ce dispositif ne doit pas provoquer de brouillage
préjudiciable.
• Il doit accepter tout brouillage reçu, y compris le
brouillage pouvant entraîner un mauvais
fonctionnement.
Maximum tightening torques for the terminals can be
found in section29.1 Torques, page 67.
Line reactors
Maximum line reactor size must not exceed 1.5 mH.
Maximum line reactor size in front of the drive must
not exceed the following values:
Short circuit current
If a short circuit occurs, the pump can be used on a
mains supply delivering not more than 5000 RMS
symmetrical amperes, 600 V maximum.
Fuses
Fuses used for motor protection must be rated for
minimum 500 V.
Motors up to and including 10 hp require class K5
UL-listed fuses. Any UL-listed fuse can be used for
TM05 7572 1213TM05 7573 1213
motors of 15 hp.
Branch circuit protection
When the pump is protected by a circuit breaker, this
must be rated for a maximum voltage of 480 V. The
circuit breaker must be of the "inverse time" type.
Overload protection
Degree of overload protection provided internally by
the drive, in percent of full-load current: 102 %.
Maximum line reactor
P2
[kW]
1450-2000 rpm
1450-2200 rpm
[mH]
2900-4000 rpm
4000-5900 rpm
0.25 - 31.51.5
40.70.7
5.50.90.3
7.50.60.6
110. 30 .3
Exceeding these values will create resonance
between the reactor and the drive, which will reduce
the lifetime of the product.
72
73
Grundfos companies
Argentina
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Centro
Industrial Garin
1619 Garín Pcia. de B.A.
Phone: +54-3327 414 444
Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Zmaja od Bosne 7-7A,
BH-71000 Sarajevo
Phone: +387 33 592 480
Telefax: +387 33 590 465
www.ba.grundfos.com
e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo
Branco, 630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: bulgaria@grundfos.bg