Grundfos TPE Series, TPED Series, NBE Series, NKGE Series, NBGE Series Installation And Operating Instructions Manual

...
GRUNDFOS INSTRUCTIONS
TPE, TPED, NBE, NBGE, NKE, NKGE, TPE, TPED, NBE, NKE Series 2000
Installation and operating instructions
Installation and operating instructions
TPE, TPED, NBE, NBGE, NKE, NKGE TPE, TPED, NBE, NKE Series 2000
http://net.grundfos.com/qr/i/98476024
English (GB) Installation and operating instructions
Original installation and operating instructions
CONTENTS
Page
1. Symbols used in this document
2. Abbreviations and definitions
3. General information
4. General description
4.1 Radio communication
4.2 Battery
5. Receiving the product
5.1 Transporting the product
5.2 Inspecting the product
6. Mechanical installation
6.1 Handling the product
6.2 Mounting the product
6.3 Cable entries
6.4 Ensuring motor cooling
6.5 Outdoor installation
6.6 Drain holes
7. Electrical installation
7.1 Protection against electric shock, indirect contact
7.2 Cable requirements
7.3 Mains supply
7.4 Additional protection
7.5 Connection terminals
7.6 Signal cables
7.7 Bus connection cable
8. Operating conditions
8.1 Maximum number of starts and stops
8.2 Alternating operation of twin-head pumps
8.3 Ambient temperature
8.4 Installation altitude
8.5 Humidity
8.6 Motor cooling
9. User interfaces
10. Standard control panel
10.1 Setpoint setting
11. Advanced control panel
11.1 Home display
11.2 Startup guide
11.3 Menu overview for advanced control panel
12. Grundfos GO
12.1 Communication
12.2 Menu overview for Grundfos GO
13. Description of functions
13.1 Setpoint
13.2 Operating mode
13.3 Set manual speed
13.4 "Set user-defined speed"
13.5 "Control mode"
13.6 "Proportional-pressure setup"
13.7 Analog inputs
13.8 Built-in Grundfos sensor
13.9 Pt100/1000 inputs
3
13.10 Digital inputs
4
13.11 Digital inputs/outputs
4
13.12 "Signal relays 1 and 2" (Relay outputs)
13.13 Analog output
4
13.14 "Controller" ("Controller settings")
4
13.15 Operating range
4
13.16 External setpoint function
5
13.17 Limit-exceeded function
5
13.18 "Pulse flowmeter setup"
5
13.19 "Ramps"
5
13.20 "Standstill heating"
5
13.21 Motor bearing monitoring
5
13.22 "Service"
5
13.23 "Number" (Pump number)
5
13.24 "Radio communication" (Enable/disable
6 6
13.25 Language
13.26 "Date and time" (Set date and time)
6
13.27 "Unit configuration" (Units)
7
13.28 "Buttons on product" (Enable/disable
7
13.29 Delete history
7
13.30 Define Home display
9
13.31 Display settings
9
13.32 "Store settings" (Store actual settings)
11
13.33 "Recall settings" (Recall stored settings)
12
13.34 "Undo"
12
13.35 "Pump name"
12
13.36 "Connection code"
12
13.37 Run start-up guide
12
13.38 Alarm log
13
13.39 Warning log
13
13.40 Assist
13
13.41 Assisted pump setup
13.42 Setup, analog input
13
13.43 "Multipump setup" (Setup of multi-pump
14
14
13.44 Description of control mode
16
13.45 Assisted fault advice
17
14. Selection of control mode
17
15. Bus signal
18
16. Priority of settings
22
17. Grundfos Eye
22
18. Signal relays
23
19. Installing a communication interface
26
26
20. Identification of functional module
26
21. Identification of control panel
26
22. Changing the position of the control
26
radio comm.)
settings)
system)
module
panel
27 32 32 33 33 34 35 37 37 38 40 40 43 44 44 44 44 45 45
45 45 45 46
46 46 46 46 46 47 47 47 47 48 48 48 48 48 49
49 53 53
54
55
56
57
58
59
61
61
62
2
23. Servicing the product
23.1 Motor
23.2 Pump
24. Cleaning the product
25. Megging
26. Technical data, single-phase motors
26.1 Supply voltage
26.2 Leakage current
27. Technical data, three-phase motors
27.1 Supply voltage
27.2 Leakage current, AC
28. Inputs and outputs
29. Other technical data
29.1 Torques
29.2 Sound pressure level
30. Factory settings
31. Disposing of the product
63
63 63
63
63

1. Symbols used in this document

63
63 63
64
64 64
65
66
67 68
69
70
Read this document before installing the product. Installation and operation must comply with local regulations and accepted codes of good practice.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
Tips and advice that make the work easier.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
A blue or grey circle with a white graphical symbol indicates that an action must be taken.
English (GB)
A red or grey circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
3

2. Abbreviations and definitions 3. General information

AI Analog input. AL Alarm, out of range at lower limit. AO Analog output. AU Alarm, out of range at upper limit. CIM Communication interface module.
Current sinking
Current sourcing
DI Digital input. DO Digital output. ELCB Earth leakage circuit breaker. FM Functional module.
GDS
GENIbus
GFCI
GND Earth. Grundfos
Eye
LIVE
OC
PE Protective earth.
PELV
RCD Residual-current device
SELV
TPE, NBE, NBGE, NKE, NKGE
TPED
TPE, TPED, NBE, NKE Series 2000
The ability to draw current into the terminal and guide it towards earth in the internal circuitry.
The ability to push current out of the terminal and into an external load which must return it to earth.
Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps.
Proprietary Grundfos fieldbus standard.
Ground fault circuit interrupter. USA and Canada.
Status indicator light.
Low voltage with the risk of electric shock if the terminals are touched.
Open collector: Configurable open-collector output.
Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except earth faults in other circuits.
Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including earth faults in other circuits.
Single-head pump without factory-fitted differential-pressure sensor.
Twin-head pump without factory-fitted differential-pressure sensor.
Single-head pump (TPE, NBE, NKE) and twin-head pump (TPED) with factory-fitted differential-pressure sensor.
These installation and operating instructions are a supplement to the installation and operating instructions for the corresponding standard pumps TP, TPD, NB, NBG, NK and NKG. For instructions not mentioned specifically in this manual, see the installation and operating instructions for the standard pump.

4. General description

The pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase mains connection.

4.1 Radio communication

This product incorporates a radio module for remote control which is a class 1 device and can be used anywhere in the EU member states without restrictions.
For use in USA and Canada, see page 71. Some variants of the product and products sold in
China and Korea have no radio module. This product can communicate with Grundfos GO
and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only Grundfos-approved external antennas may be connected to this product, and only by a Grundfos-approved installer.

4.2 Battery

Pumps fitted with the advanced functional module, FM 300, incorporate a Li-ion battery. The Li-ion battery complies with the Battery Directive (2006/66/EC). The battery does not contain mercury, lead and cadmium.
4

5. Receiving the product

D

5.1 Transporting the product

WARNING
Falling objects
Death or serious personal injury
- Secure the product during transportation to prevent it from tilting or falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.

5.2 Inspecting the product

Before you install the product, do the following:
• Check that the product is as ordered.
• Check that no visible parts have been damaged. If parts are damaged or missing, contact your local
Grundfos sales company.

6. Mechanical installation

6.1 Handling the product

Observe local regulations setting limits for manual lifting or handling. The motor weight is stated on the nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting equipment to the motor eyebolts when handling the product.

6.2 Mounting the product

CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation by bolts through the holes in the flange or the base plate.
In order to maintain the UL mark, additional requirements apply to the equipment. See page 71.
Secure the pump to a solid foundation by bolts through the holes in the flange or the base plate.

6.3 Cable entries

See the size of the cable entries in section 29. Other
technical data.

6.4 Ensuring motor cooling

Leave at least 50 mm between the end of the fan cover and a wall or other fixed objects. See fig. 1.
Fig. 1 Minimum distance, D, from the motor to
a wall or other fixed objects
English (GB)
TM05 5236 3512
Do not lift the product by the terminal box.
5

6.5 Outdoor installation

B3 B14 B5
If you install the motor outdoors, provide the motor with a cover and open the drain holes to avoid condensation on the electronic components. See figures 2 and 3.
When fitting a cover to the motor, observe the guidelines in section 6.4 Ensuring
motor cooling.
The cover must be sufficiently large to ensure that the motor is not exposed to direct sunlight, rain or snow. Grundfos does not supply covers. We therefore recommend that you have a cover built for the specific application. In areas with high humidity, we recommend that you connect the motor permanently to the mains supply and activate the built-in standstill heating function. See section
13.20 "Standstill heating", page 44.
Fig. 2 Examples of covers, not supplied by
Grundfos
In order to maintain the UL mark, additional requirements apply to the equipment. See page 71.

6.6 Drain holes

When the motor is installed in moist surroundings or areas with high humidity, the bottom drain hole must be open. The enclosure class of the motor will then be lower. This helps prevent condensation in the motor as the motor becomes self-venting, and it allows water and humid air to escape.
The motor has a plugged drain hole on the drive side. You can turn the flange 90 ° to both sides or 180 °.

7. Electrical installation

DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before you make any connections in the terminal box. Make sure that the power supply cannot be accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
- Check that the supply voltage and frequency correspond to the values stated on the nameplate.
If the power supply cable is damaged, it must be replaced by the manufacturer, the manufacturer's service partner or a similarly qualified person.
The user or the installer is responsible for the installation of correct earthing and protection
TM05 3496 3512
according to local regulations. All operations must be carried out by a qualified electrician.
Carry out the electrical connection according to local regulations.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Fig. 3 Drain holes
6
TM02 9037 1604

7.1 Protection against electric shock, indirect contact

WARNING
Electric shock
Death or serious personal injury
- Connect the motor to protective earth and provide protection against indirect contact in accordance with local regulations.
Protective-earth conductors must always have a yellow and green, PE, or yellow,green and blue, PEN, colour marking.
7.1.1 Protection against mains voltage transients
The motor is protected against mains voltage transients in accordance with EN 61800-3.
7.1.2 Motor protection
The motor requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.

7.2 Cable requirements

7.2.1 Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as to cable cross-sections.
1 x 200-230 V
Power [kW]
0.25 - 1.5
3 x 380-500 V
Power [kW]
0.25 - 2.2
3.0 - 11
Conductor type
Solid 1.5 - 2.5 16-12 Stranded 1.5 - 2.5 16-12
Conductor type
Solid 1.5 - 10 16-8 Stranded 1.5 - 10 16-8 Solid 2.5 - 10 14-8 Stranded 2.5 - 10 14-8
Cross section
2
[mm
][AWG]
Cross section
2
][AWG]
[mm
3 x 200-240 V
Power [kW]
1.1 - 1.5
2.2 - 5.5
7.2.2 Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 60 °C (140 °F).
Temperature rating for outer cable sheath: 75 °C (167 °F).
Conductor type
Solid 1.5 - 10 16-8 Stranded 1.5 - 10 16-8 Solid 2.5 - 10 14-8 Stranded 2.5 - 10 14-8
Cross section
2
][AWG]
[mm

7.3 Mains supply

DANGER
Electric shock
Death or serious personal injury
- Use the recommended fuse size. See sections 26.1 Supply voltage and
27.1 Supply voltage.
7.3.1 Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE. Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If you want to supply the motor through an IT network, make sure that you have a suitable motor variant. If you are in doubt, contact Grundfos.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
English (GB)
7
For maximum backup fuse, see section 26.1 Supply
RCD, type B
L1
L2
L3
L2
L1
L3
PE
RCD, type B
voltage.
Fig. 4 Example of a mains-connected motor
with mains switch, backup fuse and additional protection
Fig. 5 Mains connection, single-phase motors
7.3.2 Three-phase supply voltage
Three-phase motors are available for the voltages below:
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE. Check that the supply voltage and frequency
correspond to the values stated on the nameplate. The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in its socket when the supply cable has been connected.
For maximum backup fuse, see section 27.1 Supply
voltage.
If you want to supply the motor through an IT network, make sure that you have a suitable motor variant. If you are in doubt, contact Grundfos.
Only the following motors can be supplied through an IT network:
• Motors with speed of 1450-2000/2200 rpm and up to 1.5 kW
• Motors with speed of 2900-4000 rpm or 4000-5900 rpm and up to 2.2 kW.
TM05 4034 1912TM05 3494 1512
Corner earthing is not allowed for supply voltages above 3 x 240 V and 3 x 480 V, 50/60 Hz.
Fig. 6 Example of a mains-connected motor
with mains switch, backup fuses and additional protection
Fig. 7 Mains connection, three-phase motors
TM05 3942 1812TM05 3495 1512
8

7.4 Additional protection

DANGER
Electric shock
Death or serious personal injury
- Only use residual-current circuit breakers (ELCB, GFCI, RCD) of type B.
The residual-current circuit breaker must be marked with the following symbol:
The total leakage current of all the electrical equipment in the installation must be taken into account. You find the leakage current of the motor in sections 26.2 Leakage current and 27.2 Leakage
current, AC.
This product can cause a direct current in the protective earth conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of unstable power supply or a faulty installation. The motor is stopped if the voltage falls outside the permissible voltage range. The motor restarts automatically when the voltage is again within the permissible voltage range. Therefore, no additional protection relay is required.
The motor is protected against transients from the power supply according to EN 61800-3. In areas with high lightning intensity, we recommend external lightning protection.
Overload protection
If the upper load limit is exceeded, the motor automatically compensates for this by reducing the speed and stops if the overload condition persists.
The motor remains stopped for a set period. After this period, the motor automatically attempts to restart. The overload protection prevents damage to the motor. Consequently, no additional motor protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor as an additional protection. When the temperature rises above a certain level, the motor automatically compensates for this by reducing the speed and stops if the temperature keeps rising. The motor remains stopped for a set period. After this period, the motor automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power supply with a quality corresponding to IEC 60146-1-1, class C, to ensure correct motor operation at phase unbalance. This also ensures long life of the components.

7.5 Connection terminals

The descriptions and terminal overviews in this section apply to both single-phase and three-phase motors.
For maximum torques, see section 29.1 Torques.
7.5.1 Connection terminals, advanced functional module, FM 300
The advanced module has these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector
outputs
• Input and output for Grundfos Digital Sensor
Not applicable for TPE, TPED, NBE, NBGE, NKE and NKGE pumps. The factory-fitted differential-pressure sensor for TPE, TPED, NBE, NKE Series 2000 is connected to this input.
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop input where open circuit results in stop. A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation in their entire lengths.
English (GB)
9
Inputs and outputs
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
All inputs and outputs are internally separated from the mains-conducting parts by reinforced insulation and galvanically separated from other circuits. All control terminals are supplied by protective extra-low voltage, PELV, thus ensuring protection against electric shock.
Signal relay outputs – Signal relay 1:
LIVE: You can connect supply voltages up to 250 VAC . PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
– Signal relay 2:
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to the output as desired.
• Mains supply, terminals N, PE, L or L1, L2, L3,
PE.
10
* If you use an external supply source, make sure
that there is a connection to GND.
Fig. 8 Connection terminals, FM 300 (option)
TM05 3509 3512
Terminal Type Function
Normally
NC
closed contact
Normally
NO
open contact
Normally
NC
closed contact
Normally
NO
open contact
18 GND Earth
11 DI4/OC2
Pt100/1000
19
input 2 Pt100/1000
17
input 1
12 AO
9GND Earth
14 AI3
1DI2
LiqTec sensor
21
input 1
20 GND
LiqTec sensor
22
input 2
10 DI3/OC1
4AI1
2DI1
5+5 V
Signal relay 1 LIVE or PELVC1 Common
Signal relay 2 PELV onlyC2 Common
Digital input and output, configurable. Open collector: Maximum 24 V resistive or inductive.
Pt100/1000 sensor input
Pt100/1000 sensor input
Analog output: 0-20 mA / 4-20 mA 0-10 V
Analog input: 0-20 mA / 4-20 mA 0-10 V
Digital input, configurable
LiqTec sensor input white conductor
Earth brown and black conductors
LiqTec sensor input blue conductor
Digital input and output, configurable. Open collector: Maximum 24 V resistive or inductive.
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
Digital input, configurable
Supply to potentiometer and sensor
Terminal Type Function
6GND Earth A GENIbus, A GENIbus, A (+) Y GENIbus, Y GENIbus, GND B GENIbus, B GENIbus, B (-)
3GND Earth
15 +24 V Supply
8 +24 V Supply
26 +5 V
23 GND Earth
25 GDS TX
24 GDS RX
7AI2
Supply to potentiometer and sensor
Grundfos Digital Sensor output
Grundfos Digital Sensor input
Analog input: 0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V

7.6 Signal cables

• Use screened cables with a cross-sectional area of minimum 0.5 mm external on/off switch, digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to frame at both ends with good connection. The screens must be as close as possible to the terminals. See fig. 9.
Fig. 9 Stripped cable with screen and wire
• Always tighten screws for frame connections
• The wires in the motor terminal box must be as
connections
whether a cable is fitted or not.
short as possible.
2
and maximum 1.5 mm2 for
English (GB)
TM02 1325 4402
11

7.7 Bus connection cable

A
Y
B
A
Y
B
1
2 3
1 2 3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
7.7.1 New installations
For the bus connection, use a screened 3-core cable with a cross-sectional area of minimum 0.5 mm maximum 1.5 mm
If the motor is connected to a unit with a cable clamp which is identical to the one on the motor, connect
2
.
the screen to this cable clamp. If the unit has no cable clamp, leave the screen
unconnected at this end. See fig. 10.
Fig. 10 Connection with screened 3-core cable
7.7.2 Replacing a motor
• If you have used a screened 2-core cable in the existing installation, connect the cable as shown in fig. 11.
Fig. 11 Connection with screened 2-core cable
• If you have used a screened 3-core cable in the existing installation, follow the instructions in section 7.7.1 New installations.
2
and

8. Operating conditions

8.1 Maximum number of starts and stops

The number of starts and stops via the power supply must not exceed four times per hour.
When switched on via the power supply, the pump starts after approximately 5 seconds.
If a higher number of starts and stops is desired, use the input for external start-stop when starting or stopping the pump.
When started via an external on/off switch, the pump starts immediately.

8.2 Alternating operation of twin-head pumps

On twin-head pumps, the duty and backup pumps must be alternated on a regular basis, i.e. once a week, to ensure an even distribution of the operating
TM05 3973 1812TM02 8842 0904
hours on both pumps. The pumps alternate automatically. See section 13.43 "Multipump setup"
(Setup of multi-pump system).
If twin-head pumps are used for pumping domestic hot water, the duty and backup pumps must be alternated on a regular basis, i.e. once a day, to avoid blocking of the backup pump due to deposits such as calcareous deposits. As default, the pumps alternate automatically. See section
13.43 "Multipump setup" (Setup of multi-pump
system).

8.3 Ambient temperature

8.3.1 Ambient temperature during storage and
transportation
Minimum: -30 °C Maximum: 60 °C.
8.3.2 Ambient temperature during operation
3 x 200-240 V 3 x 380-500 V
Minimum -20 °C -20 °C Maximum 40 °C 50 °C
The motor can operate with the rated power output, P2, at 50 °C, but continuous operation at higher temperatures reduces the expected product life. If the motor is to operate at ambient temperatures between 50 and 60 °C, select an oversized motor. Contact Grundfos for further information.
12

8.4 Installation altitude

0
60
80
90
70
100
500 1000 1500 2000 2500 3000 3500
Altitude [m]
P2 [%]
500 480 460 440 420
380
400
0 500 1000 2000 2500 3000 3500
4000
1500
Supply voltage [V]
Altitude [m]
Supply voltage [V]
Altitude [m]
Installation altitude is the height above sea level of the installation site.
Motors installed up to 1000 m above sea level can be loaded 100 %.
The motors can be installed up to 3500 m above sea level.
Motors installed more than 1000 m above sea level must not be fully loaded due to the low density and consequent low cooling effect of the air.
Fig. 12 Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure correct clearance according to EN 60664-1:2007, you must adapt the supply voltage to the altitude:
Fig. 13 Supply voltage for three-phase motor in
250
240
230
220
210
200
relation to altitude
0 500 1000 1500 2000 2500 3000 3500 4000

8.5 Humidity

Maximum humidity: 95 %. If the humidity is constantly high and above 85 %,
one of the drain holes in the drive-end flange must be open. See section 6.6 Drain holes.

8.6 Motor cooling

To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate
cooling is ensured. See section 6.4 Ensuring
motor cooling.
• The temperature of the cooling air must not
exceed 50 °C.
• Keep cooling fins and fan blades clean.

9. User interfaces

WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as the product may be very hot.
TM05 5243 3717TM06 9866 3617TM06 9867 3617
You can make the pump settings by means of the following user interfaces:
Control panels
• Standard control panel.
• Advanced control panel.
Remote controls
• Grundfos GO.
If the power supply to the pump is switched off, the settings are stored.
WARNING
Electric shock
Death or serious personal injury
- If the control panel is cracked or perforated, replace it immediately. Contact the nearest Grundfos sales company.
See section 10. Standard control panel.
See section 11. Advanced control panel.
See section 12. Grundfos GO.
English (GB)
Fig. 14 Supply voltage for single-phase motor in
relation to altitude
13

10. Standard control panel

1
2
3
4
5
Stop
0
6
3
bar
[bar]
Pump variant
Fitted as standard
TPE, TPED - NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
Fig. 15 Standard control panel
Pos. Symbol Description
Grundfos Eye
1
2-
3
4
Shows the operating status of the pump. See section 17. Grundfos Eye for further information.
Light fields for indication of setpoint.
Up and down. Changes the setpoint.
Allows radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the pump and Grundfos GO or another pump, the green indicator light in Grundfos Eye on the pump flashes continuously. Press on the pump control panel to allow radio communication with Grundfos GO and other products of the same type.
Option
--

10.1 Setpoint setting

Set the desired setpoint of the pump by pressing or . The light fields on the control panel indicates the setpoint set.
10.1.1 Pump in differential-pressure control
The following example applies to a pump in an
TM05 4848 3512
application where a pressure sensor gives a feedback to the pump. If you retrofit the sensor to the pump, set it manually as the pump does not automatically register a connected sensor.
Figure 16 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 3 m with a sensor measuring range from 0 to 6 m. The setting range is equal to the sensor measuring range.
Pos. Symbol Description
Makes the pump ready for operation as well as starts and stops the pump.
Start
If you press the button when the pump is stopped, the
5
pump only starts if no other functions with higher priority have been enabled. See section 16. Priority of settings.
Stop
If you press the button when the pump is running, the pump always stops. The "Stop" text next to the button is on.
mode
Fig. 16 Setpoint set to 3 m, differential-pressure
control
TM05 4894 3512
14
10.1.2 Pump in constant-curve control mode
H
Q
Maximum
Minimum
H
Q
H
Q
In constant-curve control mode, the pump performance lies between the maximum and minimum curve of the pump. See fig. 17.
Fig. 17 Pump in constant-curve control mode
Setting to maximum curve:
•Press
• To change back, press
Example
Pump set to maximum curve. Figure 18 shows that the top light field is flashing,
indicating maximum curve.
Fig. 18 Maximum-curve duty
Setting to minimum curve:
•Press
• To change back, press continuously until the
continuously to change over to the
maximum curve of the pump. The top light field flashes. When the top light field is on, press for 3 seconds until the light field starts flashing.
continuously until the
desired setpoint is indicated.
continuously to change over to the
minimum curve of the pump. The bottom light field flashes. When the bottom light field is on,
for 3 seconds until the light field starts
press flashing.
desired setpoint is indicated.
Example
Pump set to minimum curve. Figure 19 shows that the bottom light field is
flashing, indicating minimum curve.
Fig. 19 Minimum-curve duty
10.1.3 Start-stop of pump
TM05 4895 2812TM05 4896 2812
Start the pump by pressing pressing until the desired setpoint is indicated.
Stop the pump by pressing . When the pump is stopped, the "Stop" text next to the button is on. You can also stop the pump by continuously pressing until none of the light fields are on.
You can also stop the pump with the Grundfos GO or via a digital input set to External stop. See section
16. Priority of settings.
10.1.4 Resetting of fault indications
Reset a fault indication in one of the following ways:
• Via the digital input if it has been set to Alarm
• Briefly press or
• Switch off the power supply until the indicator
• Switch the external start-stop input off and on.
• With Grundfos GO.
If you have stopped the pump by pressing
and the "Stop" text on the control panel
is on, you can only give it free to operation by pressing again.
If you have stopped the pump by pressing
, you can restart it by pressing or by
using Grundfos GO.
or by continuously
resetting.
on the pump. This does not
change the setting of the pump. You cannot reset a fault indication by pressing
if the buttons have been locked.
or
lights are off.
English (GB)
TM05 4897 2812
15

11. Advanced control panel

1
2
3
4
5
6
Pump variant
Fitted as standard
TPE, TPED - NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
Fig. 20 Advanced control panel
Pos. Symbol Description
Grundfos Eye
1
Shows the operating status of the pump. For further information, see section 17. Grundfos Eye.
2 - Graphical colour display.
3 Goes one step back.
Navigates between main menus, displays and digits. When you change the menu, the display always shows the top display of the new menu.
Navigates between submenus. Changes value settings.
4
Note: If you have disabled the possibility to make settings with the Enable/disable settings function, then you can enable it again temporarily by pressing these buttons simultaneously for at least 5 seconds. See section
13.28 "Buttons on product" (Enable/disable settings).
Option
-
Pos. Symbol Description
Saves changed values, resets alarms and expands the value field. Enables radio communication with Grundfos GO and other products of the same type. When you try to establish radio communication between the
4
pump and Grundfos GO or another pump, the green indicator light in Grundfos Eye flashes. A note also appears in the pump display stating that a wireless device wants to connect to the pump. Press on the pump control panel to allow radio communication with Grundfos GO and other products of the same type.
Makes the pump ready for operation and starts, and stops
TM05 4849 1013
5
the pump. Start:
If you press the button when the pump is stopped, the pump only starts if no other functions with higher priority have been enabled. See section 16. Priority
of settings.
Stop: If you press the button when the
pump is running, the pump is always stopped. When you stop the pump via this button, the icon appears in the bottom of the display.
6 Goes to the Home menu.
16

11.1 Home display

Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1 2 3 4
56789
Home
Fig. 21 Example of Home display
Pos. Symbol Description
Home This menu shows up to four user-defined parameters. You
1
2-
3-
4-
5
6
7
8
can select parameters shown as shortcut icon , and when pressing you go directly to the "Settings" display for the selected parameter.
Status This menu shows the status of the pump and system as well as warnings and alarms.
Settings This menu gives access to all setting parameters. You can make detailed settings of the pump in this menu. See section 13. Description of
functions.
Assist This menu enables assisted pump setup, provides a short description of the control modes and offers fault advice. See section 14. Selection of
control mode.
Indicates that the pump has been stopped via the button.
Indicates that the pump is functioning as master pump in a multipump system.
Indicates that the pump is functioning as a slave pump in a multipump system.
Indicates that the pump is operating in a multipump system. See section
13.43 "Multipump setup" (Setup of multi-pump system).
Pos. Symbol Description
Indicates that the possibility to make settings has been
9
disabled for protective reasons. See section 13.28 "Buttons on
product" (Enable/disable settings).
English (GB)

11.2 Startup guide

The pump incorporates a startup guide which is started at the first startup. See section 13.37 Run
start-up guide. After the startup guide, the main
menus appear in the display.
TM06 4516 2415
17

11.3 Menu overview for advanced control panel

11.3.1 Main menus
TPE,
TPED,
Home
Status
Operating status ●● ●
Operating mode, from ●● ● Control mode ●● ●
Pump performance ●● ●
Actual controlled value ●● ● Resulting setpoint ●● ● Speed ●● ●
Acc. flow and specific energy ●● ● Power and energy consumption ●● ● Measured values ●● ●
Set date and time ●● ●
Analog input 1 ●● ●
Analog input 2 ●● ●
Analog input 3 ●● ●
Pt100/1000 input 1 ●● ●
Pt100/1000 input 2 ●● ● Analog output ●● ● Warning and alarm ●● ●
Actual warning or alarm ●● ●
Warning log ●● ●
Alarm log ●● ● Operating log ●● ●
Operating hours ●● ●
Trend data ●● ● Fitted modules ●● ● Date and time ●● ● Product identification ●● ● Motor bearing monitoring ●● ● Multi-pump system - -
System operating status - -
System performance - -
18
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
Multipump
NKE
Series
2000
●● ●
TPE,
TPED,
NBE, NKE
Series
2000
system
Multipump
system
TPE,
NBE,
NKE,
TPE,
TPED,
NBE, NKE
Series
2000
TPED,
Status
System input power and energy - -
Pump 1, multi-pump system - -
Pump 2, multi-pump system - -
Pump 3, multi-pump system - -
Pump 4, multi-pump system - -
NBGE,
NKGE
Multipump
system
English (GB)
TPE,
TPED,
Settings
Setpoint ●● ●13.1 Setpoint 26 Operating mode ●● ●13.2 Operating mode 26 Set manual speed ●● ●13.3 Set manual speed 26
"Set user-defined speed" ●● ●
Control mode ●● ●13.5 "Control mode" 27 Analog inputs ●● ●
Analog input 1, setup ●● ● Analog input 2, setup ●● ● Analog input 3, setup ●● ●
Built-in Grundfos sensor - ●●
Pt100/1000 inputs ●● ●
Pt100/1000 input 2, setup ●● ●
Digital inputs ●● ●
Digital input 2, setup ●● ●
Digital inputs/outputs ●● ●
Digital input/output 4, setup ●● ●
Relay outputs ●● ●
Relay output 2 ●● ●
Analog output ●● ●
Function of analog output ●● ●
"Controller settings" ●● ●
Operating range ●● ●13.15 Operating range 40 Setpoint influence ●● ●
External setpoint function ●● ● 40
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
*
Section Page
13.4 "Set user-defined speed"
13.7 Analog inputs 32
13.8 Built-in Grundfos sensor
13.9 Pt100/1000 inputs 33Pt100/1000 input 1, setup ●● ●
13.10 Digital inputs 34Digital input 1, setup ●● ●
13.11 Digital inputs/outputs 35Digital input/output 3, setup ●● ●
13.12 "Signal relays 1 and 2" (Relay outputs)
13.13 Analog output 37Output signal ●● ●
13.14 "Controller" ("Controller settings")
26
33
37Relay output 1 ●● ●
38
19
Settings
"Predefined setpoints" ●● ●
Monitoring functions ●● ●
Motor bearing monitoring ●● ●
Motor bearing maintenance ●● ●
Limit-exceeded function ●● ●
"Special functions" ●●
"Pulse flowmeter setup" ●● ●
"Ramps" ●● ●13.19 "Ramps" 44 "Standstill heating" ●● ●13.20 "Standstill heating" 44
Communication ●● ●
Pump number ●● ●
Enable/disable radio comm. ●● ●
General settings ●● ●
Language ●● ●13.25 Language 45
Set date and time ●● ●
Units ●● ●
Enable/disable settings ●● ●
Delete history ●● ●13.29 Delete history 46 Define Home display ●● ●13.30 Define Home display 46 Display settings ●● ●13.31 Display settings 46
Store actual settings ●● ●
Recall stored settings ●● ●
Run start-up guide ●● ●13.37 Run start-up guide 48
* Applies only to a multipump system with TPE, TPED, NBE, NKE Series 2000 pumps.
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
13.16.2 "Predefined setpoints"
13.21 Motor bearing monitoring
Bearings replaced (Motor bearing maintenance)
13.17 Limit-exceeded function
13.18 "Pulse flowmeter setup"
13.23 "Number" (Pump number)
13.24 "Radio communication" (Enable/disable radio comm.)
13.26 "Date and time" (Set date and time)
13.27 "Unit configuration" (Units)
13.28 "Buttons on product" (Enable/disable settings)
13.32 "Store settings" (Store actual settings)
13.33 "Recall settings" (Recall stored settings)
42
44
45
43
44
45
45
45
46
46
46
47
20
TPE,
TPED,
Assist
Assisted pump setup ●● ●13.41 Assisted pump setup 48 Setup, analog input ●● ●13.42 Setup, analog input 49
Setting of date and time ●● ●
Setup of multi-pump system ●● ●
Description of control mode ●● ●
Assisted fault advice ●● ●13.45 Assisted fault advice 53
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
13.43 "Multipump setup" (Setup of multi-pump system)
13.43 "Multipump setup" (Setup of multi-pump system)
13.44 Description of control mode
English (GB)
49
49
53
21

12. Grundfos GO

+
+
1
2
The pump is designed for wireless radio or infrared communication with Grundfos GO.
Grundfos GO enables setting of functions and gives access to status overviews, technical product information and actual operating parameters.
Grundfos GO offers the following mobile interfaces (MI).
Fig. 22 Grundfos GO communicating with the
Pos. Description
pump via radio or infrared connection, IR
Grundfos MI 204: Add-on module enabling radio or infrared communication. You can use MI 204 in conjunction with an Apple iPhone or iPod
1
with Lightning connector, for example fifth generation or later iPhone or iPod. MI 204 is also available together with an Apple iPod touch and a cover.
Grundfos MI 301: Separate module enabling radio or infrared communication. You can use the module in
2
conjunction with an Android or iOS-based smart device with Bluetooth connection.

12.1 Communication

When Grundfos GO initiates communication with the pump, the indicator light in the middle of Grundfos Eye flashes green. See section 17. Grundfos Eye.
Furthermore, on pumps fitted with an advanced control panel a text appears in the display saying that a wireless device is trying to establish connection. Press on the pump in order to establish connection with Grundfos GO or press to reject connection.
Establish communication using one of these communication types:
• radio communication
• infrared communication.
12.1.1 Radio communication
Radio communication can take place at distances up to 30 m. The first time Grundfos GO communicates with the pump, you must enable communication by pressing or on the pump control panel. Later when communication takes place, the pump is
TM06 6256 0916
recognized by Grundfos GO and you can select the pump from the "List" menu.
12.1.2 Infrared communication
When communicating via infrared light, Grundfos GO must be pointed at the pump control panel.
22

12.2 Menu overview for Grundfos GO

Dashboard
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
●● ●
TPE,
TPED,
"Status"
NBE,
NBGE,
NKE,
NKGE
"System mode" - -
TPE,
TPED,
NBE, NKE
Series
2000
Multipump
system
*
"Resulting setpoint" ●●
"Resulting system
setpoint"
--
"Actual controlled value" ●●●
*
*
"Motor speed (rpm, %)" ●● -
"Power consumption" ●● -
"Power cons., sys." - -
*
"Energy consumption" ●●
"Energy cons., sys." - -
"Acc. flow, specific energy" ●●●
*
*
"Operating hours" ●●
"Operating hours, system" - -
*
"Analog input 1" ●● -
"Analog input 2" ●● -
"Analog input 3" ●● -
"Pt100/1000 input 1" ●● -
"Pt100/1000 input 2" ●● -
"Analog output" ●● -
"Digital input 1" ●● -
"Digital input 2" ●● -
"Digital in/output 3" ●● -
"Digital in/output 4" ●● -
"Fitted modules" ●● -
"Pump 1" - -
"Pump 2" - -
"Pump 3" - -
"Pump 4" - -
*
*
*
*
* Only available if Grundfos GO is connected to a multipump system.
English (GB)
23
"Settings"
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
"Setpoint" ●● ●13.1 Setpoint 26
"Operating mode" ●● ●13.2 Operating mode 26
"Set user-defined
speed"
●● ●13.4 "Set user-defined speed" 26
"Control mode" ●● ●13.5 "Control mode" 27
"Proportional-pressure
setup"
"Buttons on product" ●● ●
"Controller" ●● ●
- - 13.6 "Proportional-pressure setup" 32
13.28 "Buttons on product" (Enable/disable settings)
13.14 "Controller" ("Controller settings")
"Operating range" ●● ●13.15 Operating range 40
"Ramps" ●● 13.19 "Ramps" 44
"Pump number" ●● - 13.23 "Number" (Pump number) 45
"Radio communication" ●● -
13.24 "Radio communication" (Enable/disable radio comm.)
"Analog input 1" ●● -
13.7 Analog inputs 32"Analog input 2" ●● -
"Analog input 3" ●● - "Built-in Grundfos
sensor"
- ●●
"Pt100/1000 input 1" ●● - "Pt100/1000 input 2" ●● - "Digital input 1" ●● - "Digital input 2" ●● - "Digital in/output 3" ●● - "Digital in/output 4" ●● -
2)
13.8 Built-in Grundfos sensor 33
13.9 Pt100/1000 inputs 33
13.10 Digital inputs 34
13.11 Digital inputs/outputs 35
"Predefined setpoint" ●● ●13.16.2 "Predefined setpoints" 42 "Analog output" ●● - 13.13 Analog output 37 "External setpoint funct." ●● - 13.16.2 "Predefined setpoints" 40 "Signal relay 1" ●● - "Signal relay 2" ●● - "Limit 1 exceeded" ●● ● "Limit 2 exceeded" ●● ● "Alternating operation,
time" "Time for pump
changeover"
--
--
13.12 "Signal relays 1 and 2"
(Relay outputs)
13.17 Limit-exceeded function 43
1)
13.43 "Multipump setup" (Setup of
multi-pump system)
1)
"Standstill heating" ●● - 13.20 "Standstill heating" 44 "Motor-bearing
monitoring"
●● - 13.21 Motor bearing monitoring 44
"Service" ●● - 13.22 "Service" 45
46
38
45
37
49
24
TPE,
TPED,
"Settings"
NBE,
NBGE,
NKE,
NKGE
"Date and time" ●● ●
"Store settings" ●● -
"Recall settings" ●● -
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
13.26 "Date and time" (Set date
and time)
13.32 "Store settings" (Store actual
settings)
13.33 "Recall settings" (Recall
stored settings)
"Undo" ●● ●13.34 "Undo" 47 "Pump name" ●● ●13.35 "Pump name" 47 "Connection code" ●● ●13.36 "Connection code" 47 "Unit configuration" ●● ●13.27 "Unit configuration" (Units) 46
1)
Only available if Grundfos GO is connected to a multipump system.
2)
Applies only to a multipump system with TPE, TPED, NBE, NKE Series 2000 pumps.
45
46
47
English (GB)
"Alarms and warnings"
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
"Alarm log" ●● ●13.38 Alarm log 48 "Warning log" ●● ●13.39 Warning log 48 "Reset alarm" button ●● ●
"Assist"
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Multipump
system
Section Page
"Assisted pump setup" ●● 13.41 Assisted pump setup 48 "Assisted fault advice" ●● ●13.45 Assisted fault advice 53
"Multipump setup" ●● ●
13.43 "Multipump setup" (Setup of
multi-pump system)
49
25

13. Description of functions

Q
H
Q
H
Max.
Min.
Normal
Normal
Manual
Stop

13.1 Setpoint

Pump variant Setpoint
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can set the setpoint for all control modes in this submenu when you have selected the desired control mode. See section 13.5 "Control mode".
Factory setting
See section 30. Factory settings.

13.2 Operating mode

Pump variant Operating mode
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Possible operating modes:
• Normal The pump runs according to the selected control mode.
•Stop The pump stops.
•Min. Use the minimum-curve mode in periods in which a minimum flow is required.
•Max. Use the maximum-curve mode in periods in which a maximum flow is required. This operating mode is for instance suitable for systems with hot-water priority.
• Manual The pump is operating at a manually set speed. In Manual the setpoint via bus is overruled. See section 13.3 Set manual speed.
• "User-defined speed" The motor is operating at a speed set by the user. See section 13.4 "Set user-defined speed".
All operating modes are illustrated in the figure below.
TM06 4024 1515
Fig. 23 Operating modes

13.3 Set manual speed

Pump variant Set manual speed
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel. With Grundfos GO, you set the speed via the Setpoint menu.
You can set the pump speed in % of the maximum speed. When you have set the operating mode to Manual, the pump starts running at the set speed. The speed can then be changed manually via Grundfos GO or via the advanced control panel.
Factory setting
See section 30. Factory settings.

13.4 "Set user-defined speed"

You can set the motor speed in % of the maximum speed. When you have set the operating mode to "User-defined speed", the motor runs at the set speed.
26

13.5 "Control mode"

H
Q
Hset
Hset
2
p
Pump variant "Control mode"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Possible control modes:
• Prop. pressure (proportional pressure)
• Const. pressure (constant pressure)
• Const. temp. (constant temperature)
• Con. diff. press. (constant differential pressure)
• Con. diff. temp. (constant differential temperature)
• Const. flow rate (constant flow rate)
• Const. level (constant level)
• Const. other val. (constant other value)
• Const. curve (constant curve).
The operating mode must be set to Normal before a control mode can be enabled.
Factory setting
See section 30. Factory settings.
13.5.1 "Proportional pressure"
Fig. 24 "Proportional pressure"
Example
• Factory-fitted differential-pressure sensor.
Fig. 25 "Proportional pressure"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings")
English (GB)
TM05 7909 1613
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The head of the pump is reduced at decreasing water demand and increased at rising water demand. See fig. 24.
This control mode is especially suitable in systems with relatively large pressure losses in the distribution pipes. The head of the pump increases proportionally to the flow in the system to compensate for the large pressure losses in the distribution pipes.
The setpoint can be set with an accuracy of 0.1 metre. The head against a closed valve is half the setpoint.
For more information about settings, see section
13.6 "Proportional-pressure setup".
"Proportional
pressure"
-
27
13.5.2 "Constant pressure"
H
Q
p
p
H
Q
t
t
t
Pump variant "Constant pressure"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
We recommend this control mode if the pump is to deliver a constant pressure, independently of the flow in the system. The pump maintains a constant pressure independently of the flow rate. See fig. 26.
Fig. 26 "Constant pressure"
This control mode requires an external pressure sensor as shown in the examples below. You can set the pressure sensor in the Assist menu. See section
13.41 Assisted pump setup.
Examples
• One external pressure sensor.
13.5.3 "Constant temperature"
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
"Constant
temperature"
This control mode ensures a constant temperature. Constant temperature is a comfort control mode that you can use in domestic hot-water systems to control the flow to maintain a constant temperature in the system. See fig. 28.
TM05 7901 1613
TM05 7900 1613
Fig. 28 "Constant temperature"
This control mode requires an external temperature sensor. See the examples below.
Examples
• One external temperature sensor.
Fig. 27 "Constant pressure"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
28
Fig. 29 "Constant temperature"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
13.5.4 "Constant differential pressure"
H
Q
p
p
p
p
p
p
p
p
p
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
"Constant differential
pressure"
The pump maintains a constant differential pressure, independently of the flow in the system. See fig. 30. This control mode is primarily suitable for systems with relatively small pressure losses.
Fig. 30 "Constant differential pressure"
This control mode requires either an internal or
external differential-pressure sensor or two external pressure sensors. See the examples below.
Examples
• Factory-fitted differential-pressure sensor, only TPE, TPED, NBE, NKE Series 2000.
• One external differential-pressure sensor. The pump uses the input from the sensor to control the differential pressure. You can set the sensor manually or by using the Assist menu. See section 13.41 Assisted pump setup.
• Two external pressure sensors. Constant differential-pressure control is achievable with two pressure sensors. The pump uses the inputs from the two sensors and calculates the differential pressure. The sensors
TM05 7901 1613
must have the same unit and must be set as feedback sensors. You can set the sensors manually, sensor by sensor, or by using the Assist menu. See section 13.41 Assisted pump
setup.
English (GB)
Fig. 31 "Constant differential pressure"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
29
13.5.5 "Constant differential temperature"
H
Q
t
t
t
t
t
H
Q
Q
set
Qset
Q
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
"Constant differential
temperature"
The pump maintains a constant differential temperature in the system and the pump performance is controlled according to this. See fig.
32.
Fig. 32 "Constant differential temperature"
This control mode requires either two external temperature sensors or one external differential-temperature sensor. See the examples below.
Examples
• Two external temperature sensors.
• One external differential-temperature sensor.
13.5.6 "Constant flow rate"
Pump variant "Constant flow rate"
TPE, TPED, NBE,
NBGE, NKE, NKGE TPE, TPED, NBE, NKE
Series 2000
The pump maintains a constant flow in the system, independently of the head. See fig. 34.
TM05 7955 1713
Fig. 34 "Constant flow rate"
TM05 7954 1713
This control mode requires an external flow sensor. See the example below.
Example
• One external flow sensor.
Fig. 35 "Constant flow rate"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
Fig. 33 "Constant differential temperature"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
30
13.5.7 "Constant level"
H
Q
L
L
H
Q
Pump variant "Constant level"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The pump maintains a constant level, independently of the flow rate. See fig. 36.
Fig. 36 "Constant level"
This control mode requires an external level sensor. The pump can control the level in a tank in two ways:
• as an emptying function where the pump draws the liquid from the tank.
• as a filling function where the pump pumps the liquid into the tank.
See fig. 37. The type of level control function depends on the
setting of the built-in controller. See section
13.14 "Controller" ("Controller settings").
Examples
• One external level sensor. – emptying function.
• One external level sensor. – filling function.
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
13.5.8 "Constant other value"
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
"Constant other
value"
Any other value is kept constant.
13.5.9 "Constant curve"
Pump variant "Constant curve"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can set the pump to operate according to a
TM05 7941 1613
constant curve, like an uncontrolled pump. See fig.
38.
You can set the desired speed in % of the maximum speed in the range from 25 to 100 % (110 %).
Fig. 38 "Constant curve"
Controller settings
For recommended controller settings, see section
13.14 "Controller" ("Controller settings").
English (GB)
TM05 7957 1713
Fig. 37 "Constant level"
31

13.6 "Proportional-pressure setup"

PT PT PTPTTT
TT
TT
Q
Q
DPT
DPT DPT
LT LT
DPT DTT
1
5
24
910
7
12
816 15
313 6 14
11
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
"Proportional-pressure
setup"
TPE, TPED, NBE, NKE Series 2000
"Control-curve function"
You can set the curve either to quadratic or linear.
"Zero-flow head"
You can set this value in % of the setpoint. With a setting of 100 %, the control mode is equal to constant differential pressure.

13.7 Analog inputs

Pump variant Analog inputs
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Function Terminal*
Analog input 1, setup 4 Analog input 2, setup 7 Analog input 3, setup 14
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
Set the analog input for a feedback sensor via the Assisted pump setup menu. See section
13.41 Assisted pump setup.
If you want to set an analog input for other purposes, you can do this manually.
You can set the analog inputs via the Setup, analog input menu. See section 13.42 Setup, analog input.
If you perform the manual setting via Grundfos GO, you need to enter the menu for the analog input under the Settings menu.
Function
You can set the analog inputs to these functions:
•Not active.
• Feedback sensor.
• Ext. setpoint infl.. See section 13.16.1 Setpoint influence.
• Other function.
Measured parameter
Select one of the parameters, such as the parameter to be measured in the system by the sensor connected to the actual analog input. See fig. 39.
-
TM06 2328 3914
Fig. 39 Overview of sensor locations
Sensor function, measured parameter
Inlet pressure 1
Pos.
Diff. press., inlet 2 Liquid temp. 3 Diff. press.,outlet 4 Diff. press.,pump 5 Operating mode 6 Press. 2, external 7 Diff. press., ext. 8 Storage tank level 9 Feed tank level 10 Pump flow 11 Flow, external 12 Liquid temp. 13 Temperature 1 14 Temperature 2 15 Diff. temp., ext. 16 Ambient temp. Not shown Other parameter Not shown
Unit
Available measuring units:
Parameter Possible measuring units
Pressure bar, m, kPa, psi, ft Level m, ft, in
3
Flow rate m
/h, l/s, yd3/h, gpm Liquid temp. °C, °F Other parameter %
32
"Electrical signal"
Select signal type:
• 0.5-3.5 V
•0-5 V
• 0-10 V
• 0-20 mA
• 4-20 mA.
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
See section 30. Factory settings.
13.7.1 Setting two sensors for differential measurement
In order to measure the difference of a parameter between two points, set the corresponding sensors as follows:
Parameter
Pressure, option 1
Pressure, option 2
Flow Pump flow Flow, external Temperature Temperature 1 Temperature 2
Analog input
for sensor 1
Differential
pressure, inlet
Pressure 1,
external
If you want to use the control mode "constant differential pressure", you must choose the function Feedback sensor for the analog input of both sensors.
Analog input
for sensor 2
Differential
pressure, outlet
Pressure 2,
external

13.8 Built-in Grundfos sensor

Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can select the function of the built-in sensor in the Built-in Grundfos sensor menu.
Set the Built-in Grundfos sensor via the Assisted pump setup menu. See section 13.41 Assisted pump
setup.
Built-in Grundfos
sensor
-
If you perform the setting manually in the advanced control panel, you must enter the Analog inputs menu under the Settings menu in order to access the Built-in Grundfos sensor menu.
If you perform the setting manually via Grundfos GO, you need to enter the menu for the Built-in Grundfos sensor under the Settings menu.
Function
You can set the built-in sensor to these functions:
• Grundfos diff.-pressure sensor
- Not active
- Feedback sensor
- Setpoint influence
- Other function.
Factory setting
See section 30. Factory settings.

13.9 Pt100/1000 inputs

Pump variant Pt100/1000 inputs
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Function Terminal
Pt100/1000 input 1, setup 17 and 18 Pt100/1000 input 2, setup 18 and 19
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
Set the Pt100/1000 input for a feedback sensor via the Assisted pump setup menu. See section
13.41 Assisted pump setup.
If you want to set a Pt100/1000 input for other purposes, you can do this manually.
You can set the analog inputs via the Setup, analog input menu. See section 13.42 Setup, analog input.
If you perform the manual setting via Grundfos GO, you need to enter the menu for the Pt100/1000 input under the Settings menu.
Function
You can set the Pt100/1000 inputs to these functions:
•Not active
• Feedback sensor
• Ext. setpoint infl. See section 13.16.1 Setpoint influence.
• Other function.
English (GB)
33
Measured parameter
TT
TT
TT
DTT
43
12
Select one of the parameters, such as the parameter to be measured in the system by the Pt100/1000 sensor connected to the actual Pt100/1000 input. See fig. 40.
Fig. 40 Overview of Pt100/1000 sensor
locations
Parameter Pos.
Liquid temp. 1 Temperature 1 2 Temperature 2 3 Ambient temp. Not shown
Measuring range
-50 to 204 °C.
Factory setting
See section 30. Factory settings.

13.10 Digital inputs

Pump variant Digital inputs
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Function Terminal*
Digital input 1, setup 2 and 6 Digital input 2, setup 1 and 9
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
To set a digital input, make the settings below.
Function
Select one of these functions:
•Not active When set to Not active, the input has no function.
• External stop When the input is deactivated, open circuit, the pump stops.
• Min. (minimum speed) When the input is activated, the pump runs at the set minimum speed.
• Max. (maximum speed) When the input is activated, the pump runs at the set maximum speed.
34
• "User-defined speed" When the input is activated, the motor runs at a speed set by the user.
• External fault When the input is activated, a timer is started. If the input is activated for more than 5 seconds, the pump stops and a fault is indicated. This function depends on input from external equipment.
• Alarm resetting When the input is activated, a possible fault
TM06 4012 1515
indication is reset.
• Dry running When this function has been selected, lack of inlet pressure or water shortage can be detected. When lack of inlet pressure or water shortage, dry running, is detected, the pump stops. The pump cannot restart as long as the input is activated. This requires the use of an accessory, such as:
– a pressure switch installed on the inlet side of
the pump
– a float switch installed on the inlet side of the
pump.
• Accumulated flow When this function has been selected, the accumulated flow can be registered. This requires the use of a flowmeter which gives a feedback signal as a pulse per defined flow of water. See section 13.18 "Pulse flowmeter
setup".
• Predefined setpoint digit 1, applies only to digital input 2.
When digital inputs are set to predefined setpoint, the pump operates according to a setpoint based on the combination of the activated digital inputs. See section
13.16.2 "Predefined setpoints".
The priority of the selected functions in relation to each other appears from section 16. Priority of
settings. A stop command always has the highest
priority.
Activation delay
T input
T input > T1 + T2 T input < T1 + T2
T1 T2
T1 T2
T1 T1 T2T2
T1
T1
T input
T2
Mode C
Mode B
Mode A
Digital
input
T input > T1 + T2 T input < T1 + T2
T input
T input
+ 24V
DO 3/4
External
controller
Select the activation delay, T1. It is the time between the digital signal and the
activation of the selected function. Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 41.
•Not active
• active with interrupt, mode A
• active without interrupt, mode B
• active with after-run, mode C. Select the duration time, T2. It is the time which, together with the mode,
determines how long the selected function is active. Range: 0 to 15,000 seconds.

13.11 Digital inputs/outputs

Pump variant Digital inputs/outputs
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Function Terminal*
Digital input/output 3, setup 10 and 16 Digital input/output 4, setup 11 and 18
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
You can select if the interface must be used as input or output. The output is an open collector and you can connect it to for example an external relay or controller such as a PLC.
English (GB)
Fig. 41 Duration timer function of digital inputs
Factory setting
See section 30. Factory settings.
TM06 4949 3415
Fig. 42 Example of configurable digital inputs or
To set a digital input or output, make the settings below.
outputs
TM06 4463 2315
Mode
You can set the digital input or output 3 and 4 to act as digital input or digital output:
• Digital input
• Digital output.
Function
You can set the digital input or output 3 and 4 to these functions:
35
Possible functions, digital input or output 3
T input
T input > T1 + T2 T input < T1 + T2
T1 T2
T1 T2
T1 T1 T2T2
T1
T1
T input
T2
Mode C
Mode B
Mode A
Digital
input
T input > T1 + T2 T input < T1 + T2
T input
T input
Function if input See details in section
13.10 Digital inputs
• Not active
• External stop
•Min.
•Max.
• "User-defined speed"
• External fault
• Alarm resetting
• Dry running
Function if output See details in section
13.12 "Signal relays 1 and 2" (Relay outputs)
• Not active
• Ready
•Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
• Accumulated flow
• "Predefined setpoint digit 2"
Possible functions, digital input or output 4
Function if output Function if input See details in section
13.10 Digital inputs
See details in section
13.12 "Signal relays 1
and 2" (Relay
outputs)
• Not active
• External stop
•Min.
•Max.
• "User-defined
speed"
• External fault
• Alarm resetting
• Dry running
• Not active
• Ready
•Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
• Accumulated flow
• "Predefined setpoint
digit" 3"
Activation delay
Select the activation delay, T1. It is the time between the digital signal and the
activation of the selected function. Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 41.
•Not active
• active with interrupt, mode A
• active without interrupt, mode B
• active with after-run, mode C. Select the duration time, T2. It is the time which, together with the mode,
determines how long the selected function is active. Range: 0 to 15,000 seconds.
Fig. 43 Duration timer function of digital inputs
Factory setting
See section 30. Factory settings.
TM06 4949 3415
36

13.12 "Signal relays 1 and 2" (Relay outputs)

Pump variant "Signal relays 1 and 2"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Function Terminal*
Relay output 1 NC, C1, NO Relay output 2 NC, C2, NO
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
The pump incorporates two signal relays for potential-free signalling. For further information, see section 18. Signal relays.
Function
You can configure the signal relays to be activated by one of the following incidents:
•Not active.
• Ready
The pump can be running or is ready to run and no alarms are present.
•Alarm
There is an active alarm and the pump is stopped.
• "Operating" (Operation)
"Operating" equals "Running" but the pump is still in operation when it has been stopped due to a warning.
• "Running" (Pump running)
• Warning
There is an active warning.
• Limit 1 exceeded
When the Limit 1 exceeded function is activated, the signal relay is activated. See section
13.17 Limit-exceeded function.
• Limit 2 exceeded
When the Limit 2 exceeded function is activated, the signal relay is activated. See section
13.17 Limit-exceeded function.
• Relubricate
• "External fan control" (Control of external fan)
When you select "External fan control", the relay is activated if the internal temperature of the motor electronics reach a preset limit value.
Factory setting
See section 30. Factory settings.

13.13 Analog output

Pump variant Analog output
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Function Terminal*
Analog output 12
* See section 7.5.1 Connection terminals,
advanced functional module, FM 300.
The analog output enables the transfer of certain operating data to external control systems.
To set the analog output, make the settings below.
Output signal
• 0-10 V
• 0-20 mA
• 4-20 mA.
Function of analog output
• Actual speed.
Signal range [V, mA]
Actual speed
0 100 200
0-10 V 0 V 5 V 10 V 0-20 mA 0 mA 10 mA 20 mA 4-20 mA 4 mA 12 mA 20 mA
The reading is a percentage of nominal speed.
• Actual value
Signal range [V, mA]
Sensor
Actual value
min
0-10 V 0 V 10 V 0-20 mA 0 mA 20 mA 4-20 mA 4 mA 20 mA
The reading is a percentage of the range between sensor
and sensor
min
max
.
[%]
Sensor
max
English (GB)
37
• Resulting setpoint
Signal range [V, mA]
0-10 V 0 V 10 V 0-20 mA 0 mA 20 mA 4-20 mA 4 mA 20 mA
The reading is a percentage of the external setpoint range.
• Motor load
Signal range [V, mA]
0-10 V 0 V 10 V 0-20 mA 0 mA 20 mA 4-20 mA 4 mA 20 mA
The reading is a percentage of the range between 0 and 200 % of the maximum permissible load at the actual speed.
• Motor current
Signal range [V, mA]
0-10 V 0 V 5 V 10 V 0-20 mA 0 mA 10 mA 20 mA 4-20 mA 4 mA 12 mA 20 mA
The reading is a percentage of the range between 0 and 200 % of the rated current.
• Limit 1 exceeded and Limit 2 exceeded
Resulting setpoint
[%]
0 100
Motor load
[%]
0100
Motor current
[%]
0 100 200
• Flow rate
Signal range [V, mA]
0-10 V 0 V 5 V 10 V 0-20 mA 0 mA 10 mA 20 mA 4-20 mA 4 mA 12 mA 20 mA
The reading is a percentage of the range between 0 and 200 % of the nominal flow.
Factory setting
See section 30. Factory settings.
Flow rate
[%]
0 100 200

13.14 "Controller" ("Controller settings")

Pump variant "Controller"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The pumps have a factory setting of gain, Kp, and integral time, T
However, if the factory setting is not the optimum setting, you can change the gain and the integral time.
• Set the gain within the range from 0.1 to 20.
• Set the integral time within the range from 0.1 to 3600 seconds. If you select 3600 seconds, the controller functions as a P controller.
Furthermore, you can set the controller to inverse control. This means that if the setpoint is increased, the speed is reduced. In the case of inverse control, the gain must be set within the range from -0.1 to
-20.
.
i
Signal range [V, mA]
0-10 V 0 V 10 V 0-20 mA 0 mA 20 mA 4-20 mA 4 mA 20 mA
The Limit-exceeded function is typically used for monitoring of secondary parameters in the system. If the limit is exceeded, an output, warning or alarm is activated.
38
Limit-exceeded function
Output not
active
Output active
Guidelines for setting of PI controller
p
p
p
p
ǻS
L1
L1
ǻS
L2
t
L2
t
t
L2
t
t
t
L2
Q
p
p
L
L
The tables below show the recommended controller settings:
"Differential-temperature
control"
K
p
T
i
"Differential-pressure
control"
K
p
T
i
0.5 0.5
L1 < 5 m: 0.5
0.5
L1 > 5 m: 3
L1 > 10 m: 5
L1: distance in metres between pump and sensor.
K
1)
p
Cooling
system
T
2)
"Temperature
control"
Heating
system
0.5 -0.5 10 + 5L2
-0.5 10 + 5L2
L2: distance in metres between heat exchanger and sensor.
"Flow control" K
"Constant pressure
control"
i
p
T
0.5 0.5
K
p
T
0.5 0.5
0.1 0.5
English (GB)
i
i
0.5 -0.5 30 + 5L2
1)
In heating systems, an increase in pump performance results in a rise in temperature at the sensor.
2)
In cooling systems, an increase in pump performance results in a drop in temperature at the sensor.
L2: distance in metres between heat exchanger and sensor.
"Level control" K
p
T
-2.5 100
2.5 100
i
39
Rules of thumb
Fixed maximum speed
User-set maximum speed
"Operating range"
User-set minimum speed
Fixed minimum speed
24 %
13 %
0 %
67 %
100 %
100
0
100 %
0
1.2
2
0
3.5 V0.5 5 V0 10 V0 20 mA0 20 mA4
Actual input signal, 60 %
External setpoint signal
Setpoint
Sensor max.
Sensor min.
Actual
setpoint
If the controller is too slow-reacting, increase the gain.
If the controller is hunting or unstable, dampen the system by reducing the gain or increasing the integral time.
Factory setting
See section 30. Factory settings.

13.15 Operating range

Pump variant Operating range
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Set the operating range as follows:
• Set the minimum speed within the range from fixed minimum speed to user-set maximum speed.
• Set the maximum speed within the range from user-set minimum speed to fixed maximum speed.
The range between the user-set minimum and maximum speeds is the operating range. See fig. 44.
Speeds below 25 % may result in noise from the shaft seal.

13.16 External setpoint function

Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can influence the setpoint by an external signal, either via one of the analog inputs or, if an advanced functional module is fitted, via one of the Pt100/1000 inputs.
Before you can enable the External setpoint function, you must set one of the analog inputs or Pt100/1000 inputs to Setpoint influence.
See sections 13.7 Analog inputs and
13.9 Pt100/1000 inputs.
If more than one input has been set to Setpoint influence, the function selects the analog input with the lowest number, for example Setting of pump, and ignores the other inputs, for example Analog input 3 or "Pt100/1000 input 1".
Example with constant pressure with linear influence
Actual setpoint: actual input signal x (setpoint ­sensor min.) + sensor min.
At a lower sensor value of 0 bar, a setpoint of 2 bar and an external setpoint of 60 %, the actual setpoint is 0.60 x (2 - 0) + 0 = 1.2 bar.
[bar]
External setpoint
function
Fig. 44 Example of minimum and maximum
Factory setting
See section 30. Factory settings.
40
settings
TM00 6785 5095
Fig. 45 Example of setpoint influence with
-50 204 C
sensor feedback
TM06 4165 1615
Example with constant curve with linear
100
0
100 %
0
3.5 V0.5 5 V0 10 V0 20 mA0 20 mA4
-50 204 C
25
61
85
External setpoint signal
Speed [%]
Fixed maximum speed
Actual input signal, 60 %
User-set
minimum.
speed
Setpoint
Actual setpoint
100
0
100 %0
3.5 V0.5 5 V0 10 V0 20 mA0 20 mA4
Setpoint influence [%]
External input
100
0
20 100 %0
3.5 V0.5 5 V0 10 V0 20 mA0 20 mA4
-50 204 C
Setpoint influence [%]
External input
Normal
Stop
influence
Actual setpoint: actual input signal x (setpoint ­user-set minimum speed) + user-set minimum speed.
At a user-set minimum speed of 25 %, a setpoint of 85 % and an external setpoint of 60 %, the actual setpoint is 0.60 x (85 - 25) + 25 = 61 %. See fig. 46.
You can select these functions:
•Not active When set to Not active, the setpoint is not influenced from any external function.
• Linear function The setpoint is influenced linearly from 0 to 100 %. See fig. 47.
English (GB)
Fig. 46 Example of setpoint influence with
constant curve
Factory setting
See section 30. Factory settings.
13.16.1 Setpoint influence
Pump variant Setpoint influence
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The table below gives an overview of the types of setpoint influence and the availability depending on pump type.
Setpoint influence
Not active ●● Linear function ●● Linear with Stop ●● Influence table ●●
TM06 4525 2515
-50 204 C
TM06 4166 1615TM06 4167 1615
Fig. 47 Linear function
• Linear with Stop
– In the input signal range from 20 to 100 %, the
setpoint is influenced linearly. If the input signal is below 10 %, the pump changes to operating mode Stop. If the input signal is above 15 %, the operating mode is changed back to Normal. See fig. 48.
Pump type
TPE,
TPED,
NBE,
NBGE,
NKE,
NKGE
TPE,
TPED,
NBE,
NKE
Series
2000
Fig. 48 Linear with Stop
41
• Influence table
100
0
100 %0
3.5 V0.5 5 V0 10 V0 20 mA0 20 mA4
-50 204 C
Setpoint influence [%]
External input
0
1
2
3
4
5
6
7
Digital input 4
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
Setpoint 6
Setpoint 7 Digital input 3 Digital input 2
Actual setpoint
Stop
Normal setpoint
The setpoint is influenced by a curve made out of two to eight points. There will be a straight line between the points and a horizontal line before the first point and after the last point.
Fig. 49 Influence table, example with five points
Before the Digital inputs can be enabled, set one of the analog inputs or Pt100/1000 inputs to External setpoint function.
See sections 13.7 Analog inputs and
13.9 Pt100/1000 inputs.
13.16.2 "Predefined setpoints"
Pump variant "Predefined setpoints"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can set and activate seven predefined setpoints by combining the input signals to digital inputs 2, 3 and 4. See the table below.
Set the digital inputs 2, 3 and 4 to "
setpoints" if all seven predefined setpoints are to be
used. You can also set one or two of the digital inputs to "Predefined setpoints" but this limits the number of predefined setpoints available.
Predefined
Digital inputs
234
Setpoint
0 0 0 Normal setpoint or stop 1 0 0 Predefined setpoint 1 0 1 0 Predefined setpoint 2 1 1 0 Predefined setpoint 3 0 0 1 Predefined setpoint 4 1 0 1 Predefined setpoint 5 0 1 1 Predefined setpoint 6 1 1 1 Predefined setpoint 7
0: Open contact 1: Closed contact
Example
Figure 50 shows how you can use the digital inputs
TM06 4170 1615
to set seven predefined setpoints. Digital input 2 is open and digital inputs 3 and 4 are closed. If you compare with the table above, you can see that "Predefined setpoint 6" is activated.
Fig. 50 Principle sketch showing how
predefined setpoints function
TM06 4269 1815
If all digital inputs are open, the pump either stops or runs at the normal setpoint. Set the desired action with Grundfos GO or with the advanced control panel.
Factory setting
See section 30. Factory settings.
42

13.17 Limit-exceeded function

1
2
4 4
5 6
3
A
Time [s]
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This function can monitor a measured parameter or one of the internal values such as speed, motor load or motor current. If a set limit is reached, a selected action can take place. You can set two limit-exceeded functions meaning that you can monitor two parameters or two limits of the same parameter simultaneously.
Limit-exceeded
function
"Detection delay"
You can set a detection delay which ensures that the monitored parameter stays above or below a set limit in a set time before the function is activated.
"Resetting delay"
The resetting delay is the time from which the measured parameter differs from the set limit including the set hysteresis band and until the function is reset.
Example
The function is to monitor the outlet pressure of a pump. If the pressure is below 5 bar for more than 5 seconds, a warning must be given. If the outlet pressure is above 7 bar for more than 8 seconds, you must reset the warning.
English (GB)
The function requires setting of the following:
Measured
Here you set the measured parameter to be monitored.
"Limit"
Here you set the limit which activates the function.
"Hysteresis band"
Here you set the hysteresis band.
"Limit exceeded when"
Here you can set the function to be activated when the selected parameter exceeds or drops below the set limit.
• "Above limit" The function is activated if the measured parameter exceeds the set limit.
• "Below limit" The function is activated if the measured parameter drops below the set limit.
Action
If the value exceeds a limit, you can define an action. You can select the following actions:
• "No action" The pump remains in its current state. Use this setting if you only want to have a relay output when the limit is reached. See section
13.12 "Signal relays 1 and 2" (Relay outputs).
• "Warning/alarm" There is a warning.
•Stop The pump stops.
•Min. The pump reduces speed to minimum.
•Max. The pump increases speed to maximum.
• "User-defined speed" The pumps runs at a speed set by the user.
Fig. 51 "Limit exceeded" (example)
Pos. Setting parameter Setting
1Measured
"Outlet
pressure" 2 "Limit" 5 bar 3 "Hysteresis band" 2 bar 4 "Limit exceeded when" "Below limit" 5 "Detection delay" 5 seconds 6 "Resetting delay" 8 seconds
Limit-exceeded function
A
active
-
- "Action" "Warning"
Factory setting
See section 30. Factory settings.
TM06 4603 2515
43

13.18 "Pulse flowmeter setup"

User set ramp-up User set ramp-down
Speed
Time
User set
minimum
Fixed initial ramp Fixed final ramp
User set
maximum
Fixed
maximum
0
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
"Pulse flowmeter
setup"
TPE, TPED, NBE, NKE Series 2000
You can connect an external pulse flowmeter to one of the digital inputs in order to register the actual and accumulated flows. Based on this, you can also calculate the specific energy.
To enable a pulse flowmeter, set one of the digital-input functions to Accumulated flow and set the pumped volume per pulse. See section
13.10 Digital inputs.
Factory setting
See section 30. Factory settings.

13.19 "Ramps"

13.20 "Standstill heating"

Pump variant "Standstill heating"
TPE, TPED, NBE,
NBGE, NKE, NKGE TPE, TPED, NBE, NKE
Series 2000
You can use this function to avoid condensation in humid environments. When you set the function to "Active" and the pump is in operating mode Stop, a low AC voltage is applied to the motor windings. The voltage is not high enough to make the motor rotate but ensures that sufficient heat is generated to avoid condensation in the motor including the electronic parts in the drive.
Remember to remove the drain plugs and fit a cover over the motor.

13.21 Motor bearing monitoring

Pump variant "Ramps"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The ramps determine how quickly the motor can accelerate and decelerate, respectively, during start-stop or setpoint changes.
You can set the following:
• acceleration time, 0.1 to 300 seconds
• deceleration time, 0.1 to 300 seconds. The times apply to the acceleration from 0 rpm to
fixed maximum speed and the deceleration from fixed maximum speed to 0 rpm.
At short deceleration times, the deceleration of the motor may depend on load and inertia as there is no possibility of actively braking the motor.
If the power supply is switched off, the deceleration of the motor only depends on load and inertia.
Fig. 52 Ramp-up and ramp-down
Factory setting
See section 30. Factory settings.
44
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can set the motor bearing monitoring function to these values:
Motor bearing
monitoring
•"Active"
•Not active When the function is set to "Active", a counter in the
controller starts counting the mileage of the bearings.
The counter continues counting even if the function is changed to Not active, but a warning is not given when it is time for replacement.
When the function is changed to "Active" again, the accumulated mileage is again used to calculate the replacement time.
Factory setting
See section 30. Factory settings.
TM03 9439 0908

13.22 "Service"

Pump variant "Service"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
"Time until next service" (Motor bearing service)
This display shows when to replace the motor bearings. The controller monitors the operating pattern of the motor and calculates the period between bearing replacements.
Displayable values:
• "in 2 years"
• "in 1 year"
• "in 6 months"
• "in 3 months"
• "in 1 month"
• "in 1 week"
•"Now"
"Bearing replacements"
Indicates the number of bearing replacements that have been done during the lifetime of the motor.
Bearings replaced (Motor bearing maintenance)
When the bearing monitoring function is active, the controller gives a warning when the motor bearings are to be replaced.
When you have replaced the motor bearings, confirm this action by pressing [Bearings replaced].

13.23 "Number" (Pump number)

Pump variant "Number"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can allocate a unique number to the pump. This makes it possible to distinguish between pumps in connection with bus communication.
Factory setting
See section 30. Factory settings.

13.24 "Radio communication" (Enable/disable radio comm.)

Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can set the radio communication to either enabled or disabled. You can use this function in areas where radio communication is not allowed.
IR communication remains active.
Factory setting
See section 30. Factory settings.
"Radio
communication"

13.25 Language

Pump variant Language
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel.
In this menu you can select the desired language. A number of languages is available.

13.26 "Date and time" (Set date and time)

Pump variant "Date and time"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
You can set date and time as well as how they are to be shown in the display:
• Select date format:
YYYY-MM-DD DD-MM-YYYY MM-DD-YYYY.
• Select time format:
HH:MM 24-hour clock HH:MM am/pm 12-hour clock.
• Set date
•Set time.
Factory setting
See section 30. Factory settings.
English (GB)
45

13.27 "Unit configuration" (Units)

Pump variant "Unit configuration"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
In this menu you can select between SI and US units. The setting can be made generally for all parameters or customised for each parameter.
Factory setting
See section 30. Factory settings.

13.28 "Buttons on product" (Enable/disable settings)

Pump variant "Buttons on product"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
In this display, you can disable the possibility of making settings.
Grundfos GO
If you set the buttons to "Not active", the buttons on the standard control panel are disabled. If you set the buttons to "Not active" on pumps with an advanced control panel, see below.
Advanced control panel
If you have disabled the settings, you can still use the buttons to navigate through the menus but you cannot make changes in the Settings menu.
When you have disabled the possibility to make settings, the symbol appears in the display.
To unlock the pump and allow settings, press and
simultaneously for at least 5 seconds. Standard control panel The button always remains active but you can
only unlock all other buttons on the pump with Grundfos GO.
Factory setting
See section 30. Factory settings.

13.29 Delete history

• "Delete energy consumption".

13.30 Define Home display

Pump variant Define Home display
TPE, TPED ­NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel.
In this menu, you can set the Home display to show up to four user-set parameters.

13.31 Display settings

Pump variant Display settings
TPE, TPED -
NBE, NBGE, NKE, NKGE & TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel.
In this menu you can adjust the display brightness and set whether or not the display is to turn off if no buttons have been activated for a period of time.

13.32 "Store settings" (Store actual settings)

Pump variant "Store settings"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Grundfos GO
In this menu, you can store the actual settings for later use in the same pump or in other pumps of the same type.
Advanced control panel
In this menu, you can store the actual settings for later use in the same pump.
Pump variant Delete history
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
In this menu, you can delete the following historic data:
• "Delete operating log".
• "Delete heat energy data".
46
-
-

13.33 "Recall settings" (Recall stored settings)

Pump variant "Recall settings"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
Grundfos GO
In this menu, you can recall stored settings from a number of previously stored settings that the pump then uses.
Advanced control panel
In this menu, you can recall the last stored settings that the pump then uses.

13.34 "Undo"

Pump variant "Undo"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu is only available in Grundfos GO. In this display, you can undo all settings that have
been made with Grundfos GO in the current communication session. You cannot undo a Recall stored settings action.

13.35 "Pump name"

Pump variant "Pump name"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu is only available in Grundfos GO. In this display, you can give the pump a name. In this
way, you can easily identify the pump when connecting with Grundfos GO.
Factory setting
See section 30. Factory settings.

13.36 "Connection code"

Pump variant "Connection code"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu is only available in Grundfos GO. You can set a connection code to avoid having to
press the connection button each time and to restrict remote access to the product.
Setting the code in the product using Grundfos GO
1. Connect Grundfos GO to the product.
2. In the product dashboard, select "Settings".
3. Choose "Connection code".
4. Enter the wanted code and press [OK]. The code must be a character string, ASCII. You can always modify the code. The old code is not needed.
Setting the code in Grundfos GO
You can set a default connection code in Grundfos GO so that it automatically attempts to connect to the selected product via this code.
When you select a product with the same connection code in Grundfos GO, Grundfos GO automatically connects to the product and you do not have to press the connection button on the module.
Set the default code in Grundfos GO in this way:
1. In the main menu, under "General", select "Settings".
2. Choose "Remote".
3. Enter the connection code in the field "Preset connection code". The field now says "Connection code set".
You can always modify the default connection code by pressing [Delete] and entering a new one.
If Grundfos GO fails to connect and ask you to press the connection button on the product, it means that the product has no connection code or has a different connection code. In this case, you can only establish connection via the connection button.
After setting a connection code, you must switch off the product until the light in Grundfos Eye turns off before you can use the new connection code.
Factory setting
See section 30. Factory settings.
English (GB)
47

13.37 Run start-up guide

Pump variant Run start-up guide
TPE, TPED NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel.
The startup guide automatically starts when you start the pump for the first time.
You can always run the startup guide later via this menu.
The startup guide guides you through the general settings of the pump.
• Language. See section 13.25 Language.
• Select date format. See section 13.26 "Date and time" (Set date and
time).
• Set date. See section 13.26 "Date and time" (Set date and
time).
• Select time format. See section 13.26 "Date and time" (Set date and
time).
•Set time. See section 13.26 "Date and time" (Set date and
time).
• Setting of pump
– Go to Home – Run with Constant curve/Run with Constant
pressure. See section 13.5 "Control mode"
– Go to "Assisted pump setup".
See section 13.41 Assisted pump setup.
– Return to factory settings.
* Applies only for pumps with advanced functional
module, FM 300. For further information, see section 20. Identification of functional module.

13.38 Alarm log

13.39 Warning log

Pump variant Warning log
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu contains a list of logged warnings from the product. The log shows the name of the warning, when the warning occurred and when it was reset.

13.40 Assist

Pump variant Assist
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The menu consist of functions which take you through the steps needed to set the pump.

13.41 Assisted pump setup

Pump variant Assisted pump setup
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The menu guides you through the following:
Setting of pump
• Selection of control mode. See page 27.
• Configuration of feedback sensors.
• Adjusting the setpoint. See page 26.
• Controller settings. See page 38.
• Summary of settings.
Pump variant Alarm log
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu contains a list of logged alarms from the product. The log shows the name of the alarm, when the alarm occurred and when it was reset.
48
Example of how to use the Assisted pump setup for setting up the pump to constant pressure:
Grundfos GO
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode "Constant pressure".
4. Read the description of this control mode.
5. Select which analog input to use as sensor input.
6. Select sensor function according to where the sensor is installed in the system. See fig. 39.
7. Select electrical input signal according to the sensor specifications.
8. Select measuring unit according to the sensor specifications.
9. Set the minimum and maximum sensor values according to the sensor specifications.
10. Set the desired setpoint.
11. Set the controller settings K recommendations in section 13.14 "Controller"
("Controller settings").
12. Type the pump name.
13. Check the summary of settings and confirm them.
Advanced control panel
1. Open the Assist menu.
2. Select Assisted pump setup.
3. Select the control mode Const. pressure.
4. Select which analog input to be used as sensor input.
5. Select the measured parameter to be controlled. See fig. 39.
6. Select measuring unit according to the sensor specifications.
7. Set the minimum and maximum sensor values according to the sensor specifications.
8. Select electrical input signal according to the sensor specifications.
9. Set the setpoint.
10. Set the controller settings K recommendations in section 13.14 "Controller"
("Controller settings").
11. Check the summary of settings and confirm them by pressing [OK].
and Ti. See the
p
and Ti. See
p

13.42 Setup, analog input

Pump variant Setup, analog input
TPE, TPED ­NBE, NBGE, NKE,
NKGE & TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel.
The menu guides you through the following:
Setup, analog input
• Analog inputs 1 to 3. See page 32.
• Pt100/1000 input 1 and 2. See page 33.
• Adjusting the setpoint. See page 26.
• Summary.

13.43 "Multipump setup" (Setup of multi-pump system)

Pump variant "Multipump setup"
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
The multipump function enables the control of two pumps connected in parallel without the use of external controllers. The pumps in a multipump system communicate with each other via the wireless GENIair connection or the wired GENI connection.
A multipump system is set via a selected pump, i.e. the master pump, which is the first selected pump.
If two pumps in the system are configured with an outlet-pressure sensor, both pumps can function as master pumps and take over the master pump function if the other fails. This provides additional redundancy in the multipump system.
The multipump functions are described in the following sections.
English (GB)
49
13.43.1 Alternating operation
Alternating operation functions as a duty/standby operating mode and is possible with two pumps of same size and type connected in parallel. The main purpose of the function is to ensure an even amount of running hours and to ensure that the standby pump takes over if the running pump stops due to an alarm.
Each pump requires a non-return valve in series with the pump.
You can choose between two alternating operation modes:
• "Alternating operation, time" Pump changeover to the other is based on time.
• "Alternating operation, energy" Pump changeover to the other is based on energy consumption.
If the duty pump fails, the other pump takes over automatically.
13.43.2 Backup operation
Backup operation is possible with two pumps of same size and type connected in parallel. Each pump requires a non-return valve in series with the pump.
One pump is operating continuously. The backup pump is operated for a short time each day to prevent seizing up. If the duty pump stops due to a fault, the backup pump starts automatically.
13.43.3 Cascade operation
Cascade operation ensures that the pump performance is automatically adapted to the consumption by switching pumps on or off. The system thus runs as energy-efficiently as possible with a constant pressure and a limited number of pumps.
All pumps in operation run at equal speed. Pump changeover is automatic and depends on energy, operating hours and fault.
If the pump system consists of two to four single-head pumps connected in parallel, the pumps must be of the same type and size. Each pump requires a non-return valve in series with the pump.
Set the control mode to "Constant pressure" or "Constant curve".
This function is available with up to 4 motors installed in parallel. The motors must be of the same size and the pumps must be of the same model.
• The performance is adjusted to the demand through cutting pumps in or out and through parallel control of the pumps in operation.
• The controller maintains a constant pressure through continuous adjustment of the speed of the pumps.
• Pump changeover is automatic and depends on load, operating hours and fault detection.
• All pumps in operation run at the same speed.
• The number of pumps in operation also depends on the energy consumption of the pumps. If only one pump is required, two pumps will run at a lower speed if this results in a lower energy consumption.
• If several motors in the system have a sensor, they can all function as master and take over the master function if the other motors fail.
13.43.4 Setting a multipump system
You can set a multipump system in the following ways:
Grundfos GO and wireless pump connection
Grundfos GO and wired pump connection
Advanced control panel and wireless pump
connection
Advanced control panel and wired pump
connection
See step-by-step descriptions below.
50
Grundfos GO and wireless pump connection
1. Power on both pumps.
2. Establish contact to one of the pumps with Grundfos GO.
3. Set the needed analog and digital inputs via Grundfos GO according to the connected equipment and the required functionality. See section 13.41 Assisted pump setup.
4. Assign a pump name to the pump using Grundfos GO. See section 13.35 "Pump name".
5. Disconnect Grundfos GO from the pump.
6. Establish contact to the other pump.
7. Set the needed analog and digital inputs via Grundfos GO according to the connected equipment and the required functionality. See section 13.41 Assisted pump setup.
8. Assign a pump name to the pump using Grundfos GO. See section 13.35 "Pump name".
9. Select the "Assist" menu and "Multipump setup".
10. Select the desired multipump function. See sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade operation.
11. Press [>] to continue.
12. Set the time for pump changeover such as the time at which the alternation between the two pumps is to take place. This step applies only if you have selected "Alternating operation, time" and if the pumps are fitted with FM 300.
13. Press [>] to continue.
14. Select "Radio" as the communication method to be used between the two pumps.
15. Press [>] to continue.
16. Press "Select pump 2".
17. Select the pump from the list. Use the [OK] or button to identify the pump.
18. Press [>] to continue.
19. Confirm the multipump setup by pressing [Send].
20. Press [Finish] in the "Setup complete" dialog box.
21. Wait for the green indicator light in the middle of Grundfos Eye to light up.
The multipump system has now been set.
Grundfos GO and wired pump connection
1. Connect the two pumps with each other with a 3-core screened cable between the GENIbus terminals A, Y, B.
2. Power on both pumps.
3. Establish contact to one of the pumps with Grundfos GO.
4. Set the needed analog and digital inputs via Grundfos GO according to the connected equipment and the required functionality. See section 13.41 Assisted pump setup.
5. Assign a pump name to the pump using Grundfos GO. See section 13.35 "Pump name".
6. Assign pump number 1 to the pump. See section
13.23 "Number" (Pump number).
7. Disconnect Grundfos GO from the pump.
8. Establish contact to the other pump.
9. Set the needed analog and digital inputs via Grundfos GO according to the connected equipment and the required functionality. See section 13.41 Assisted pump setup.
10. Assign a pump name to the pump using Grundfos GO. See section 13.35 "Pump name".
11. Assign pump number 2 to the pump. See section
13.23 "Number" (Pump number).
12. Select the "Assist" menu and choose "Multipump setup".
13. Select the desired multipump function. See sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade operation.
14. Press [>] to continue.
15. Set the time for pump changeover such as the time at which the alternation between the two pumps is to take place. This step applies only if you have selected "Alternating operation, time" and if the pumps are fitted with FM 300.
16. Press [>] to continue.
17. Select "BUS cable" as the communication method to be used between the two pumps.
18. Press [>] to continue.
19. Press "Select pump 2".
20. Select the additional pump from the list. Use the [OK] or button to identify the additional pump.
21. Press [>] to continue.
22. Press [Send].
23. Press [Finish] in the "Setup complete" dialog box.
24. Wait for the green indicator light in the middle of Grundfos Eye to light up.
The multipump system has now been set.
English (GB)
51
Advanced control panel and wireless pump
connection
1. Power on both pumps.
2. On both pumps, set the needed analog and digital inputs according to the connected equipment and the required functionality. See section 13.41 Assisted pump setup.
3. Select the Assist menu on one of the pumps and choose Setup of multi-pump system.
4. Press [>] to continue.
5. Select Wireless as the communication method to be used between the two pumps.
6. Press [>] to continue.
7. Select the desired multipump function. See sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade operation.
8. Press [>] three times to continue.
9. Press [OK] to search for other pumps. The green indicator light in the middle of Grundfos Eye flashes on the other pumps.
10. Press the connect button on the pump which is to be added to the multipump system.
11. Press [>] to continue.
12. Set the time for pump changeover i.e. the time at which the alternation between the two pumps is to take place. This step applies only if you have selected "Alternating operation, time" and if the pumps are fitted with FM 300.
13. Press [>] to continue.
14. Press [OK]. The multipump function icons appear in the bottom of the control panels.
The multipump system has now been set.
Advanced control panel and wired pump connection
1. Connect the two pumps with each other with a 3-core screened cable between the GENIbus terminals A, Y, B.
2. Set the needed analog and digital inputs according to the connected equipment and the required functionality. See section 13.41 Assisted
pump setup.
3. Assign pump number 1 to the first pump. See section 13.23 "Number" (Pump number).
4. Assign pump number 2 to the other pump. See section 13.23 "Number" (Pump number).
5. Select the Assist menu on one of the pumps and choose Setup of multi-pump system.
6. Press [>] to continue.
7. Select Wired GENIbus as the communication method to be used between the two pumps.
8. Press [>] twice to continue.
9. Select the desired multipump function. See sections 13.43.1 Alternating operation,
13.43.2 Backup operation and 13.43.3 Cascade operation.
10. Press [>] to continue.
11. Press [OK] to search for other pumps.
12. Select the additional pump from the list.
13. Press [>] to continue.
14. Set the time for pump changeover i.e. the time at which the alternation between the two pumps is to take place. This step applies only if you have selected "Alternating operation, time" and if the pumps are fitted with FM 300.
15. Press [>] to continue.
16. Press [OK]. The multipump function icons appear in the bottom of the control panels.
The multipump system has now been set.
52
Disabling the multipump function via Grundfos GO
1. Select the "Assist" menu.
2. Select "Multipump setup".
3. Select "Disable".
4. Press [>] to continue.
5. Confirm the multipump setup by pressing [Send].
6. Press [Finish]. The multipump function has now been disabled.
Disabling a multipump via advanced control panel
1. Select the Assist menu.
2. Select Setup of multi-pump system.
3. Press [>] to continue.
4. Confirm No multi-pump function by pressing [OK].
5. Press [>] to continue.
6. Press [OK].
The multipump system has now been disabled.

13.44 Description of control mode

English (GB)
Pump variant
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu is only available in the advanced control panel.
This menu describes each of the possible control modes. See also section 13.5 "Control mode".
Description of control
mode
-

13.45 Assisted fault advice

Pump variant Assisted fault advice
TPE, TPED, NBE, NBGE, NKE, NKGE
TPE, TPED, NBE, NKE Series 2000
This menu gives guidance and corrective actions in case of pump failures.
53

14. Selection of control mode

H
Hset
Hset
2
H
Q
H
Q
H
Q
System application Select this control mode
In systems with relatively large pressure losses in the distribution pipes and in air-conditioning and cooling systems.
• Two-pipe heating systems with thermostatic valves and the following: – very long distribution pipes – strongly throttled balancing valves
Proportional pressure
– differential-pressure regulators – large pressure losses in those parts of the system through which the
total quantity of water flows, for example boiler, heat exchanger and distribution pipe up to the first branching.
• Primary circuit pumps in systems with large pressure losses in the
primary circuit.
• Air-conditioning systems with the following: – heat exchangers, fan coils – cooling ceilings – cooling surfaces.
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and the following: – sized for natural circulation – small pressure losses in those parts of the system through which the
total quantity of water flows, for example boiler, heat exchanger and distribution pipe up to the first branching, or modified to a high differential temperature between flow pipe and return pipe, for example district heating.
Constant differential pressure
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing
valves.
• Primary circuit pumps in systems with small pressure losses in the
primary circuit.
In systems with a fixed system characteristic. Examples:
• one-pipe heating systems
Constant temperature and
constant differential
temperature
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
If an external controller is installed, the pump is able to change from one constant curve to another, depending on the value of the external signal.
You can also set the pump to operate according to the maximum or minimum curve, like an uncontrolled pump:
• Use the maximum-curve mode in periods in which a maximum flow is
required. This operating mode is for instance suitable for systems with hot-water priority.
• Use the minimum-curve mode in periods in which a minimum flow is
required.
54
Constant curve
System application Select this control mode
Q
set
H
Q
H
Q
In systems requiring a constant flow, independently of pressure drop.
Constant flow rate
Examples:
• chillers for air-conditioning
• heating surfaces
• cooling surfaces.
English (GB)
In systems requiring a constant tank level, independently of the flow rate. Examples:
• process-water tanks
• boiler-condensate tanks.
In systems with pumps operating in parallel. The multipump function enables the control of two to four single-head
pumps connected in parallel and twin-head pumps without the use of external controllers. The pumps in a multipump system communicate with each other via the wireless GENIair connection or the wired GENI connection.

15. Bus signal

The pump supports serial communication via an RS-485 input. The communication is carried out according to the Grundfos GENIbus protocol and enables connection to other pumps as well as a building management system or another external control system.
Via a bus signal, you can remote-set pump operating parameters, such as setpoint and operating mode. At the same time, the pump can, via the bus, provide status information about important parameters, such as actual value of control parameter, input power and fault indications.
Contact Grundfos for further information.
If you use a bus signal, the number of settings available via Grundfos GO are reduced.
Constant level
Assist menu
Setup of multi-pump system
55

16. Priority of settings

You can always set the pump to stop by pressing on the pump control panel. When the pump is not in Stop mode, you can always set the pump to stop by continuously pressing . Furthermore, you can set the pump to maximum speed by continuously pressing . You can always set the pump to operation at maximum speed or to stop with Grundfos GO.
If two or more functions are enabled at the same time, the pump operates according to the function with the highest priority.
Example
If you have set the pump to maximum speed via the digital input, the pump control panel or Grundfos GO can only set the pump to Manual or Stop.
The priority of the settings appears from the table below.
Priority
1 Stop
2 Stop *
3 Manual
4
5 Stop
6
7 Stop
8 "Max. speed"
9 "Min. speed"
10 "Start"
11 "Max. speed"
12 "Min. speed"
13 "Min. speed"
14 "Start"
15 "Start"
* "Stop" and "Max. speed" settings made with
Grundfos GO or on the motor control panel can be overruled by another operating-mode command sent from a bus, for example "Start". If the bus communication is interrupted, the motor resumes its previous operating mode, for example "Stop", selected with Grundfos GO or on the motor control panel.
Start-stop
button
Grundfos GO or control
panel on pump
"Max. speed"*/
"User-defined speed"
Digital input Bus communication
"User-defined
speed"
56

17. Grundfos Eye

A
The operating condition of the pump is indicated by the Grundfos Eye on the control panel. See fig. 53, A.
TM05 5993 4312
Fig. 53 Grundfos Eye
Grundfos Eye Indication Description
No lights are on.
The two opposite green indicator lights are rotating in the direction of rotation of the pump when seen from the non-drive end.
The two opposite green indicator lights are permanently on.
The power is off. The pump is not running.
The power is on. The pump is running.
The power is on. The pump is not running.
English (GB)
One yellow indicator light is rotating in the direction of rotation of the pump when seen from the non-drive end.
One yellow indicator light is permanently on.
The two opposite red indicator lights flash simultaneously.
The green indicator light in the middle flashes quickly four times.
The green indicator light in the middle flashes continuously.
The green indicator light in the middle is permanently on.
The green indicator light in the middle flashes quickly while Grundfos Go is exchanging data with the pump. It takes a few seconds.
Warning. The pump is running.
Warning. The pump has stopped.
Alarm. The pump has stopped.
This is a feedback signal which the pump gives in order to ensure identification of itself.
Grundfos GO or another pump is trying to communicate with the pump. Press on the pump control panel to allow communication.
Remote control with Grundfos GO via radio. The pump is communicating with Grundfos GO via radio connection.
Remote control with Grundfos GO via infrared light. The pump is receiving data from Grundfos GO via infrared communication.
57

18. Signal relays

NCNO
C
NCNO
C
NCNO
C
NCNO
C
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
NCNO
C
C
NO NC
C
NO NC
NCNO
C
NCNO
C
NCNO
C
NCNOCNCNO
C
C
NO NC
NCNO
C
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
NCNO
C
C
NO NC
NCNO
C
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
NCNO
C
NCNO
C
NCNO
C
C
NO NC
NCNO
C
The pump has two outputs for potential-free signals via two internal relays.
You can set the signal outputs to Operation, Pump running, Ready, Alarm and Warning.
The functions of the two signal relays appear from the table below.
Description Grundfos Eye
Contact position of signal relays when activated
Operation Running Ready Alarm Warning
Operating mode
The power is off.
The pump runs in "Normal" mode.
The pump runs in "Manual" mode.
The pump is in operating mode "Stop".
Warning, but the pump is running.
Warning, but the pump runs in "Manual" mode.
Warning, but the pump was stopped via a "Stop" command.
Alarm, but the pump is running.
Off
Green, rotating
Green, rotating
Green, steady
Yellow, rotating
Yellow, rotating
Yellow, steady
Red, rotating
-
"Normal", "Min." or "Max."
"Manual"
"Stop"
"Normal", "Min." or "Max."
"Manual"
"Stop"
"Normal", "Min." or "Max."
Alarm, but the pump runs in "Manual" mode.
The pump has stopped due to an alarm.
Red, rotating
Red, flashing
"Manual"
"Stop"
58
19. Installing a communication
A
B
B
C
D
A
A
A
B
interface module
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before starting any work on the motor. Make sure that the power supply cannot be accidentally switched on.
Always use an antistatic service kit when handling electronic components. This prevents static electricity from damaging the components.
When unprotected, place the component on the antistatic cloth.
Fig. 54 Antistatic service kit
1. Loosen the four screws (fig. 55, A) and remove the terminal box cover (fig. 55, B).
2. Remove the CIM cover (fig. 56, A) by pressing the locking tab (fig. 56, B) and lifting the end of the cover (fig. 56, C). Then lift the cover off the hooks (fig. 56, D).
Fig. 56 Removing the CIM cover
3. Remove the securing screw (fig. 57, A).
Fig. 57 Removing the securing screw
4. Fit the CIM module by aligning it with the three
TM06 4462 2315TM06 4081 1515
plastic holders (fig. 58, A) and the connecting plug (fig. 58, B). Press home the module using your fingers.
English (GB)
TM06 4084 1515TM06 4082 1515TM06 4083 1515
Fig. 55 Removing the terminal box cover
Fig. 58 Fitting the CIM module
59
5. Fit and tighten the securing screw (fig. 57, A) to
A
FCC
1.3 Nm.
6. Make the electrical connections to the CIM module as described in the instructions delivered with the module.
7. Connect the cable screens of the bus cables to earth via one of the earth clamps (fig. 59, A).
Fig. 59 Connecting the cable screens to earth
8. Route the wires for the CIM module. See the example in fig. 60.
9. Fit the CIM cover.
10. If the CIM module is supplied with an FCC label, then place this on the terminal box. See fig. 61.
Fig. 61 FCC label
11. Fit the terminal box cover (fig. 55, B) and cross-tighten the four mounting screws (fig. 55, A) to 6 Nm.
TM06 4195 1615TM06 4085 1515
Make sure that the terminal box cover is aligned with the control panel. See section
22. Changing the position of the control panel.
TM05 7028 0413
Fig. 60 Example of wire routing
60

20. Identification of functional module

Env.Type :
Serial no :
SF CL:
PF:
PB FM HMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
: :
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
P
:
n
W
g
g
t
:
DE
:
k
g
g
D
:
T
amb
:
:
V
P
.C.
:
PU
T
C
T
yp
yp
e
:
P.N.
:
Ui:
I
:
f
HzP
S
p
p
:
:
PB FM
HMI CIM
VARIANT
Hp
rpm
: :
: :
PB
:
:
C
:
H
p
pm
Env.Type :
Serial no :
SF CL:
PF:
PB FM HMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
: :
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
PF
:
n
W
g
g
t
:
DE
:
k
g
g
D
:
T
amb
:
:
V
P
.C.
:
PU
T
C
T
yp
yp
e
:
P.N.
:
Ui:
I
:
f
HzP
S
p
p
:
:
PB FM
HMI CIM
VARIANT
Hp
rpm
: :
: :
PB
:
C
:
H
p
pm
:
You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the functional module in the "Fitted modules" menu under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify the functional module in the Fitted modules menu under Status.
Motor nameplate
You can identify the fitted module on the motor nameplate. See fig. 62.

21. Identification of control panel

You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the control panel in the "Fitted modules" menu under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify the control panel in the Fitted modules menu under Status.
Motor nameplate
You can identify the fitted control panel on the motor nameplate. See fig. 63.
English (GB)
IN
eri
e
F
i
L
F Am
F
r
/
IM
TM06 1889 3314
Fig. 62 Identification of functional module
Variant Description
FM 200 Standard functional module FM 300 Advanced functional module
Fig. 63 Identification of control panel
Variant Description
HMI 200 Standard control panel HMI 300 Advanced control panel
IN
eri
e
F
i
L
F Am
r
/
IM
TM06 4013 1415
61
22. Changing the position of the
control panel
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before starting any work on the motor. Make sure that the power supply cannot be accidentally switched on.
You can turn the control panel 180 °. Follow the instructions below.
1. Loosen the four screws, TX25, of the terminal box cover.
3. Press and hold in the two locking tabs, A, while gently lifting the plastic cover, B.
Fig. 66 Lifting the plastic cover
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
TM05 5353 3612
Fig. 64 Loosening the screws
2. Remove the terminal box cover.
Fig. 65 Removing the terminal box cover
TM05 5351 3612TM05 5352 3612
Fig. 67 Turning the plastic cover
5. Position the plastic cover correctly on the four rubber pins, C. Make sure that the locking tabs, A are placed correctly.
Fig. 68 Positioning the plastic cover
TM05 5354 3612TM05 5355 3612
62
6. Fit the terminal box cover, and make sure that it is also turned 180 ° so that the buttons on the control panel are aligned with the buttons on the plastic cover.
7. Tighten the four screws, TX25, with 5 Nm.
Fig. 69 Fitting the terminal box cover

23. Servicing the product

DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Wait at least 5 minutes before starting any work on the motor. Make sure that the power supply cannot be accidentally switched on.
DANGER
Magnetic field
Death or serious personal injury
- Do not handle the motor or rotor if you have a pacemaker.

23.1 Motor

If service is needed on the product, please contact Grundfos Service.

23.2 Pump

Service documentation is available in Grundfos Product Center (http://product-selection.grundfos.com/).
If you have any questions, please contact the nearest Grundfos company or service workshop.

24. Cleaning the product

WARNING
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the signal relays. Check that the terminal box cover is intact before spraying water on the product.
In order to avoid condensation in the motor, let the motor cool down before spraying it with cold water.

25. Megging

Megging of an installation incorporating MGE motors is not allowed, as the built-in
TM05 5356 3612
electronics may be damaged.

26. Technical data, single-phase motors

26.1 Supply voltage

• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Recommended fuse size
Motor size
[kW]
0.12 - 0.75 6 10
1.1 - 1.5 10 16
You can use standard as well as quick-blow or slow-blow fuses.

26.2 Leakage current

Earth leakage current less than 3.5 mA, AC. Earth leakage current less than 10 mA, DC. The leakage currents are measured in accordance
with EN 61800-5-1:2007.
Min.
[A]
English (GB)
Max.
[A]
63
27. Technical data, three-phase
motors

27.1 Supply voltage

Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Recommended fuse size
• 3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE.
Motor size
[kW]
0.25 - 1.1 6 6
1.5 6 10
2.2 6 16 31016 41316
5.5 16 32
7.5 20 32
11 32 32
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Motor size
[kW]
1.1 10 20
1.5 10 20
2.2 13 35 31635 42535
5.5 32 35
You can use standard as well as quick-blow or slow-blow fuses.
Minimum
[A]
Minimum
[A]
Maximum
[A]
Maximum
[A]

27.2 Leakage current, AC

Speed
[min
1400-2000 1450-2200
2900-4000
4000-5900
The leakage currents are measured without any load on the shaft and in accordance with EN 61800-5-1:2007.
-1
]
Power
[kW]
0.25 - 1.5
2.2 - 4
5.5 - 7.5
0.25 - 2.2
3 - 5.5
7.5 - 11
0.25 - 2.2
3 - 5.5
7.5 - 11
Mains
voltage
[V]
400 < 3.5 > 400 < 5 400 < 3.5 > 400 < 3.5 400 < 3.5 > 400 < 5 400 < 3.5 > 400 < 5 400 < 3.5 > 400 < 3.5 400 < 3.5 > 400 < 5 400 < 3.5 > 400 < 5 400 < 3.5 > 400 < 3.5 400 < 3.5 > 400 < 5
Leakage
current
[mA]
64

28. Inputs and outputs

Ground reference, GND
All voltages refer to GND. All currents return to GND.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in severely reduced operating reliability and motor life:
Relay 1: Maximum contact load: 250 VAC, 2 A or 30 VDC, 2
A. Relay 2: Maximum contact load: 30 VDC, 2 A. GENI terminals: -5.5 to 9.0 VDC or less than 25
mADC. Other input and output terminals: -0.5 to 26 VDC or
less than 15 mADC.
Digital inputs, DI
Internal pull-up current greater than 10 mA at V equal to 0 VDC.
Internal pull-up to 5 VDC; currentless for V than 5 VDC).
Low logic level: V High logic level: V Hysteresis: No. Screened cable: 0.5 - 1.5 mm
less than 1.5 VDC.
i
greater than 3.0 VDC.
i
2
, 28-16 AWG.
Maximum cable length: 500 m.
Open-collector digital outputs, OC
Current sinking capability: 75 mADC, no current sourcing.
Load types: Resistive or/and inductive. Low-state output voltage at 75 mADC: Maximum 1.2
VDC. Low-state output voltage at 10 mADC: Maximum 0.6
VDC. Overcurrent protection: Yes. Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.
i
greater
i
Analog inputs, AI
Voltage signal ranges:
• 0.5 - 3.5 VDC, AL AU.
• 0-5 VDC, AU.
• 0-10 VDC, AU. Voltage signal: Ri greater than 100 kΩ at 25 °C. Leak currents may occur at high operating
temperatures. Keep the source impedance low. Current signal ranges:
• 0-20 mADC, AU.
• 4-20 mADC, AL AU. Current signal: Ri equal to 292 Ω. Current overload protection: Yes. Change to voltage
signal. Measurement tolerance: - 0/+ 3 % of full scale
(maximum-point coverage). Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG. Maximum cable length: 500 m, excl. potentiometer. Potentiometer connected to +5 V, GND, any AI: Use maximum 10 kΩ. Maximum cable length: 100 m.
Analog output, AO
Current sourcing capability only. Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes. Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes. Tolerance: - 0/+ 4 % of full scale (maximum-point
coverage). Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG. Maximum cable length: 500 m.
English (GB)
65
Pt100/1000 inputs, PT
Temperature range:
• Minimum -30 °C. 88 Ω/882 Ω.
• Maximum 180 °C. 168 Ω/1685 Ω. Measurement tolerance: ± 1.5 °C. Measurement resolution: < 0.3 °C. Automatic range detection, Pt100 or Pt1000: Yes. Sensor fault alarm: Yes. Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG. Use Pt100 for short wires. Use Pt1000 for long wires.
LiqTec sensor inputs*
Use Grundfos LiqTec sensor only. Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Grundfos Digital Sensor input and output, GDS*
Use Grundfos Digital Sensor only. * Not applicable for TPE, TPED, NBE, NBGE, NKE
and NKGE pumps. The factory-fitted differential-pressure sensor for TPE, TPED, NBE, NKE Series 2000 is connected to this input.
Power supplies
+5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC, sourcing only.
• Overload protection: Yes.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC, sourcing only.
• Overload protection: Yes.
Digital outputs, relays
Potential-free changeover contacts. Minimum contact load when in use: 5 VDC, 10 mA. Screened cable: 0.5 - 2.5 mm
2
, 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos GENIbus protocol, RS-485. Screened 3-core cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.

29. Other technical data

EMC (electromagnetic compatibility)
Standard used: EN 61800-3. The table below shows the emission category of the
motor. C1 fulfils the requirements for residential areas.
Note: When connected to a public network, 11 kW motors do not comply with the partial weighted harmonic distortion (PWHD) requirements of EN 61000-3-12. If required by the distribution network operator, compliance can be obtained in the following way:
The impedance of the mains cables between the motor and the point of common coupling (PCC) must be equivalent to the impedance of a 50 m cable with a cross-section of 0.5 mm.
C3 fulfils the requirements for industrial areas. Note: When the motors are installed in residential areas, supplementary measures may be required as the motors may cause radio interference.
Motor
[kW]
0.25 C1 C1
0.37 C1 C1
0.55 C1 C1
0.75 C1 C1
1.1 C1 C1
1.5 C1 C1
2.2 C1 C1 3C1 C1 4C1 C1
5.5 C3/C1* C1
7.5 C3/C1* C3/C1*
11 - C 3/C1 *
*
C1, if equipped with an external Grundfos EMC filter.
Immunity: The motor fulfils the requirements for industrial areas.
Contact Grundfos for further information.
Emission category
1450-2000 min
2900-4000 min
-1
4000-5900 min
-1
-1
66
Enclosure class
Standard: IP55 (IEC 34-5). Optional: IP66 (IEC 34-5).
Insulation class
F (IEC 85).
Standby power consumption
5-10 W.
Cable entries
Number and size of cable entries
Motor
0.25 -
1400-2000
[kW]
1450-2200
-1
[min
1.5
2.2
3.0 -
4.0
5.5
7.5 - 111xM32 +
4xM20 4xM20 4xM20
1xM25 +
4xM20
1xM25 +
4xM20
1xM32 +
5xM20
5xM20
2900-4000
[min
]
4xM20 4xM20
1xM25 +
4xM20
1xM25 +
4xM20
1xM32 +
5xM20

29.1 Torques

-1
]
4000-5900
[min-1]
1xM25 +
4xM20
1xM25 +
4xM20
1xM32 +
5xM20
English (GB)
Terminal Thread size
L1, L2, L3, L, N M4 2.35 NC, C1, C2, NO M2.5 0.5 1 to 26 and A, Y, B M2 0.5
Maximum
torque
[Nm]
67

29.2 Sound pressure level

Maximum
Motor
[kW]
speed
stated on
nameplate
-1
[min
2000
0.25 -
0.75
4000
5900
2000
1.1
4000
5900
2000
1.5
4000
5900
2000
2.2
4000
5900
2000
4000
3
5900
2000
4000
4
5900
Sound pressure
Speed
-1
[min
]
]
1-phase
motors
1500 37 37 2000 43 43 3000 50 50 4000 60 60 4000 58 58 5900 68 68 1500 2000 3000 50 50 4000 60 60 4000 58 58 5900 68 68 1500 2000 3000 57 57 4000 64 64 4000 58 58 5900 68 68 1500 2000 3000 4000 4000 5900 1500 2000 3000 4000 4000 5900 1500 2000 3000 4000 4000 5900
level
ISO 3743
[dB(A)]
3-phase
motors
37 43
42 47
48 55 57 64 58 68 48 55 60 69 64 74 48 55 61 69 64 74
Sound pressure
Maximum
Motor
[kW]
speed
stated on
nameplate
[min
2000
5.5
4000
5900
2000
7.5
4000
5900
4000
11
5900
The grey fields indicate that the motor is not available in this MGE motor range.
Speed
-1
]
[min
-1
]
1500 2000 3000 4000 4000 5900 1500 2000 3000 4000 4000 5900 3000 4000 4000 5900
ISO 3743
[dB(A)]
1-phase
motors
level
3-phase
motors
58 61 61 69 64 74 58 61 66 73 69 79 66 73 69 79
68

30. Factory settings

Function is enabled. Function is disabled.
- Function is not available.
Settings
Setpoint 67 % 58 % 26 Operating mode Normal Normal 26 Control mode Const. curve Prop. pressure 27 Date and time ●● "Buttons on product" ●●46 "Controller" ("Controller settings") 38
"0.50.5
"T
i
"0.50.5
"K
p
Operating range 40
"Min." 25 % 25 % "Max." 100 % 110 %
"Ramps"
"Ramp-up" 1 second 1 second
"Ramp-down" 3 seconds 3 seconds "Number" (Pump number) 1 1 45 "Radio communication" ●●45 Analog input 1
Analog input 3 Built-in Grundfos sensor - 33 Pt100/1000 input 1 Pt100/1000 input 2 "Digital input 1" "Digital input 2" "Digital in/output 3" "Digital in/output 4" "Pulse flowmeter" "Predefined setpoints" Analog output External setpoint function Relay output 1 Relay output 2 Limit 1 exceeded Limit 2 exceeded "Standstill heating" Motor bearing monitoring "Pump name" Grundfos Grundfos 47 "Connection code" - - 47 "Unit configuration" SI SI 46
TPE, TPED, NBE,
NBGE, NKE, NKGE
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
❍❍
TPE, TPED, NBE, NKE
Series 2000
Function
description
on page
44
32Analog input 2
33
34
35
44 42 37 42
37
43
44 44
English (GB)
69

31. Disposing of the product

This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
70
Appendix 1

Installation in the USA and Canada

In order to maintain the cURus approval, follow these additional installation instructions. The UL approval is according to UL 1004-1.
Outdoor installation
According to UL 778/C22.2 No 108-14, pumps intended for outdoor use must be marked enclosure type 3 and the product must be tested at a surface temperature down to -35 °C. The MLE enclosure is approved for type 3 or 4 and is rated at a surface temperature down to 0 °C, thus it is only for indoor use in UL 778/C22.2 No 108-14 pump applications.
For more information about ambient temperature during operation, see section 8.3.2 Ambient
temperature during operation.
Canadian Interference-Causing Equipment Standard
This product complies with the Canadian ICES-003 Class B specifications. This Class B device meets all the requirements of the Canadian interference­causing equipment regulations.
Cet appareil numérique de la Classe B est conforme à la norme NMB-003 du Canada. Cet appareil numérique de la Classe B respecte toutes les exigences du Réglement sur le matériel brouilleur du Canada.

Electrical codes

For USA
This product complies with the Canadian Electrical Code and the US National Electrical Code.
This product has been tested according to the national standards for Electronically Protected Motors:
CSA 22.2 100-14:2014 (applies to Canada only). UL 1004-1:2015 (applies to USA only).
Pour le Canada
Codes de l'électricité
Ce produit est conforme au Code canadien de l'électricité et au Code national de l'électricité américain.
Ce produit a été testé selon les normes nationales s'appliquant aux moteurs protégés électroniquement:
CSA 22.2 100.04: 2009 (s'applique au Canada uniquement).
UL 1004-1: Juin 2011 (s'applique aux États-Unis uniquement).

Radio communication

For USA
This device complies with part 15 of the FCC rules and RSS210 of IC rules.
Operation is subject to the following two conditions:
• This device may not cause interference.
• This device must accept any interference, including interference that may cause undesired operation of the device.
Users are cautioned that changes or modifications not expressly approved by Grundfos could void the user's authority to operate the equipment.
Pour le Canada
Communication radio
Ce dispositif est conforme à la partie 15 des règles de la FCC et aux normes RSS210 de l'IC.
Son fonctionnement est soumis aux deux conditions suivantes:
• Ce dispositif ne doit pas provoquer de brouillage préjudiciable.
• Il doit accepter tout brouillage reçu, y compris le brouillage pouvant entraîner un mauvais fonctionnement.

Identification numbers

For USA
Grundfos Holding A/S Contains FCC ID: OG3-RADIOM01-2G4.
For Canada
Grundfos Holding A/S Model: RADIOMODULE 2G4 Contains IC: 10447A-RA2G4M01.
Pour le Canada
Numéros d'identification
Grundfos Holding A/S Modèle: RADIOMODULE 2G4 Contient IC: 10447A-RA2G4M01.

Appendix

71
Location of identification numbers
Stop
Identification numbers
Identification numbers
Appendix
Fig. 1 Identification numbers
Fig. 2 Identification numbers

Electrical connection

Conductors
See section 7.2 Cable requirements, page 7.
Tor que s
Maximum tightening torques for the terminals can be found in section29.1 Torques, page 67.
Line reactors
Maximum line reactor size must not exceed 1.5 mH. Maximum line reactor size in front of the drive must
not exceed the following values:
Short circuit current
If a short circuit occurs, the pump can be used on a mains supply delivering not more than 5000 RMS symmetrical amperes, 600 V maximum.
Fuses
Fuses used for motor protection must be rated for minimum 500 V.
Motors up to and including 10 hp require class K5 UL-listed fuses. Any UL-listed fuse can be used for
TM05 7572 1213TM05 7573 1213
motors of 15 hp.
Branch circuit protection
When the pump is protected by a circuit breaker, this must be rated for a maximum voltage of 480 V. The circuit breaker must be of the "inverse time" type.
Overload protection
Degree of overload protection provided internally by the drive, in percent of full-load current: 102 %.
Maximum line reactor
P2
[kW]
1450-2000 rpm 1450-2200 rpm
[mH]
2900-4000 rpm 4000-5900 rpm
0.25 - 3 1.5 1.5
40.7 0.7
5.5 0.9 0.3
7.5 0.6 0.6 11 0. 3 0 .3
Exceeding these values will create resonance between the reactor and the drive, which will reduce the lifetime of the product.
72
73
Grundfos companies
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 Garín Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belarus
Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56, БЦ «Порт» Тел.: +7 (375 17) 286 39 72/73 Факс: +7 (375 17) 286 39 71
E-mail: minsk@grundfos.com
Bosnia and Herzegovina
GRUNDFOS Sarajevo Zmaja od Bosne 7-7A, BH-71000 Sarajevo Phone: +387 33 592 480 Telefax: +387 33 590 465 www.ba.grundfos.com e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 10F The Hub, No. 33 Suhong Road Minhang District Shanghai 201106 PRC Phone: +86 21 612 252 22 Telefax: +86 21 612 253 33
COLOMBIA
GRUNDFOS Colombia S.A.S. Km 1.5 vía Siberia-Cota Conj. Potrero Chico, Parque Empresarial Arcos de Cota Bod. 1A. Cota, Cundinamarca Phone: +57(1)-2913444 Telefax: +57(1)-8764586
Croatia
GRUNDFOS CROATIA d.o.o. Buzinski prilaz 38, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.hr.grundfos.com
GRUNDFOS Sales Czechia and Slovakia s.r.o.
Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Trukkikuja 1 FI-01360 Vantaa Phone: +358-(0) 207 889 500
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Tópark u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800
Indonesia
PT. GRUNDFOS POMPA Graha Intirub Lt. 2 & 3 Jln. Cililitan Besar No.454. Makasar, Jakarta Timur ID-Jakarta 13650 Phone: +62 21-469-51900 Telefax: +62 21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. 1-2-3, Shin-Miyakoda, Kita-ku, Hamamatsu 431-2103 Japan Phone: +81 53 428 4760 Telefax: +81 53 428 5005
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Veluwezoom 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
Romania
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундф ос Россия ул. Школьная, 39-41 Москва, RU-109544, Russia Тел. (+7) 495 564-88-00 (495) 737-30-
00 Факс (+7) 495 564 8811 E-mail grundfos.moscow@grundfos.com
Serbia
Grundfos Srbija d.o.o. Omladinskih brigada 90b 11070 Novi Beograd Phone: +381 11 2258 740 Telefax: +381 11 2281 769 www.rs.grundfos.com
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689
Slovakia
GRUNDFOS s.r.o. Prievozská 4D 821 09 BRATISLAVA Phona: +421 2 5020 1426 sk.grundfos.com
Slovenia
GRUNDFOS LJUBLJANA, d.o.o. Leskoškova 9e, 1122 Ljubljana Phone: +386 (0) 1 568 06 10 Telefax: +386 (0)1 568 06 19 E-mail: tehnika-si@grundfos.com
South Africa
GRUNDFOS (PTY) LTD Corner Mountjoy and George Allen Roads Wilbart Ext. 2 Bedfordview 2008 Phone: (+27) 11 579 4800 Fax: (+27) 11 455 6066 E-mail: lsmart@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31 331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-44-806 8111 Telefax: +41-44-806 8115
Tai wan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
Бізнес Центр Європа Столичне шосе, 103 м. Київ, 03131, Україна Телефон : (+38 044) 237 04 00 Факс.: (+38 044) 237 04 01
E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971 4 8815 166 Telefax: +971 4 8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 4TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 9300 Loiret Blvd. Lenexa, Kansas 66219 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Uzbekistan
Grundfos Tashkent, Uzbekistan The Representative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292
Addresses Revised 14.03.2018
Grundfos companies
98476024 1018
ECM: 1246569
© 2018 Grundfos Holding A/S, all rights reserved.
Trademarks displayed in this material, including but not limited to Grundfos, the Grundfos logo and “be
think innovate” are registered trademarks owned by The Grundfos Group. All rights reserved.
www.grundfos.com
Loading...