English (GB) Installation and operating instructions
Caution
Note
English (GB)
Original installation and operating instructions
TABLE OF CONTENTS
1.Symbols used in this document
2.Scope of delivery
2.1MD
2.2MLD
3.General description
3.1Applications
4.Transportation and storage
5.Product description
5.1Lifting station
5.2LC 221 controller
6.Operating LC 221 controller
6.1Description of display
6.2Setup menu
6.3Information menu
6.4Description of fault indications
7.Installation of lifting station
7.1General description
7.2Guidelines for installation of lifting station
7.3Procedure for installation of lifting station
8.Installation of LC 221 controller
8.1Location
8.2Mechanical installation
8.3Electrical connection
8.4Setting of LC 221
8.5Wiring diagrams
9.Startup
10.Maintenance and service
10.1 Mechanical maintenance
10.2 Motor
10.3 Electrical maintenance
10.4 Cleaning the level sensor
10.5 Contaminated lifting station or components
11.Fault finding
12.Technical data
12.1 Lifting station
12.2 Collecting tank
12.3 Pump
12.4 LC 221 controller
13.Disposal
Warning
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
Warning
The use of this product requires experience with and
knowledge of the product.
Persons with reduced physical, sensory or mental
capabilities must not use this product, unless they
are under supervision or have been instructed in the
use of the product by a person responsible for their
safety.
Children must not use or play with this product.
Page
10
10
12
13
14
16
16
17
17
19
19
19
20
20
21
22
22
23
23
23
24
24
25
26
26
26
26
26
26
1. Symbols used in this document
Warning
If these safety instructions are not observed, it may
2
2
2
2
3
4
4
4
4
6
result in personal injury.
Warning
These instructions must be observed for
explosion-proof pumps.
If these safety instructions are not observed, it may
result in malfunction or damage to the equipment.
Notes or instructions that make the job easier and
ensure safe operation.
2. Scope of delivery
2.1 MD
Grundfos Multilift MD lifting stations are supplied complete with
collecting tank, butterfly-non-return valves, a sensor unit with
cable and two pumps with cable, both connected to the LC 221
controller. The controller includes a power supply cable with plug.
An accessories bag containing the following items is also
included:
• 1 x installation and operating instructions
• 1 x Quick guide for controller menu
• 1 x discharge adapter flange, DN 80, with connection piece,
DN 100 (outer diameter, 110 mm)
• 1 x flexible hose, DN 100, and two clamps to connect the
discharge pipe
• 1 x flexible hose, DN 70, and two clamps to connect the
venting pipe
• 2 x screw and expansion anchor for tank fixation
• 3 x screw and washer for fastening a pipe plug in the inlet disk,
if required
• 1 x socket seal, DN 100
• 1 x socket seal, DN 50, for diaphragm pump connection or
inlet, DN 50
• 1 x gasket kit, DN 80, 4 bolts M16, nuts and washers
(galvanised).
2.2 MLD
Grundfos Multilift MLD lifting stations are supplied complete with
collecting tank, butterfly-non-return valves, a sensor unit with
cable and two pumps with cable, both connected to the LC 221
controller. The controller includes a power supply cable with plug.
An accessories bag containing the following items is also
included:
• 1 x installation and operating instructions
• 1 x Quick guide for controller menu
• 1 x discharge adapter flange, DN 80, with connection piece,
DN 100 (outer diameter, 110 mm)
• 1 x flexible hose, DN 100, and two clamps to connect
discharge pipe
• 1 x flexible hose, DN 70, and two clamps to connect venting
pipe
• 4 x screw and expansion anchor for tank fixation
• 1 x socket seal, DN 150
• 1 x flexible hose connection with two clamps, DN 50, for
diaphragm pump connection or inlet, DN 50
• 1 x gasket kit, DN 80, 4 bolts M16, nuts and washers
(galvanized).
2
3. General description
Grundfos Multilift MD and MLD lifting stations are supplied
complete with collecting tank, pumps, level sensor, LC 221
controller and connection accessories.
The following gives a description of the components.
English (GB)
Fig. 1 Multilift MD front and rear view
Pos. Description
1Pump
2Lifting eye for pumps
3Nameplate
4Venting port, DN 70 (outer diameter, 75 mm), open
5Screw cap for pressure tube and tank inspection opening
6Vertical inlet, DN 150 (seal is accessory)
7Fixing point
Non-return butterfly valve, DN 80, with inspection cover
8
and drain screw to lift up the valve flap
Discharge adapter flange, DN 80, to pipe ∅110 w i th
9
flexible connection piece and 2 clamps
Side or top inlet, DN 50 (seals are accessory).
10
Socket for MD; connecting piece for MLD
Collecting tank with carrying handle moulded into tank
11
body
Port for manually operated diaphragm pump, 1 1/2".
12
Socket with seal for MD; connecting piece with flexible
connection hose and clamps for MLD
13Horizontal inlet, DN 100 (seal is accessory)
Adjustable inlet disk, DN 100
14
(DN 150 optional as accessory)
15Separate inspection cover
TM05 1521 2911
Fig. 2 Multilift MLD front and rear view
TM05 1522 2911
3
3.1 Applications
Note
Typ
Prod.-Nr.
P. c.
fHz
Serial no.
Phases
UV
A
kW
Gkg
m
m
98127055
0197
I
1/1
P1
Qmax
Hmin
Hmax
T
Med
max
T
Amb
max
m /h
3
C
C
Made in Germany
96075419
DK - 8850 Bjerringbro, Denmark
1
2
3
4
5
6
10
11
12
13
14
15
16
17
18
20
19
7
8
9
English (GB)
Grundfos Multilift MD and MLD lifting stations are designed for
the collection and pumping of domestic wastewater with no free
flow to sewer level. Grundfos Multilift MD and MLD lifting stations
are designed for the collection and pumping of the following
liquids:
• domestic wastewater, including grey wastewater without
faeces, black wastewater with faeces (discharge from water
closets)
• sludge-containing water.
The lifting stations are capable of pumping liquids containing
fibres, textiles, faeces, etc., below sewer level from multi-family
houses, offices, schools, hotels, restaurants, public areas and
other commercial buildings and similar industrial applications.
Do not pump rainwater with the Multilift MD and MLD lifting
stations for these two reasons:
• The motors of the lifting stations are not designed for
continuous operation which may be necessary in case of
heavy rainfall.
• Rainwater must not be discharged into a lifting station inside a
building according to EN 12056-4.
If in doubt, please contact Grundfos for advice.
Do not discharge the following substances/types of wastewater
via a lifting station:
• solid matter, tar, high content of sand, cement, ash, cardboard,
debris, garbage etc.
• wastewater from sanitary installations situated above the flood
level (this must be drained away via a free-flow drainage
system according to EN 12056-1).
• wastewater containing hazardous substances such as greasy
wastewater from large-scale catering establishments.
For drainage of greasy wastewater, use a grease separator
according to EN 1825-2 between a canteen or commercial
kitchen and the Multilift MD or MLD.
5.1 Lifting station
The Grundfos Multilift MD and MLD lifting stations are supplied
complete with two single- or three-phase submersible pumps
connected to the LC 221 controller incorporating a level sensor.
Type key, lifting station
ExampleMLD.22.3.4
Multilift lifting station
L = large tank
D = 2 pumps
Output power, P
1 = single-phase motor
3 = three-phase motor
2 = 2-pole motor
4 = 4-pole motor
Nameplate, lifting station
/ 100 (W)
2
4. Transportation and storage
Warning
Fig. 3 Nameplate, lifting station
TM04 7639 2210
The motor lifting eye is only intended for lifting the
pump. Never lift or lower the lifting station by means
of the lifting eye.
Lift the lifting station by the collecting tank.
For long periods of storage, the LC 221 controller must be
protected against moisture and heat.
After a long period of storage, the pumps must be inspected
before they are started up again. Make sure that the impellers
can rotate freely.
5. Product description
The MD and MLD Multilift lifting stations are described in the
following sections:
• section 5.1 Lifting station describing the lifting station with
collecting tank, pumps, non-return valve and level sensor
• section 5.2 LC 221 controller describing the controller as well
as the functions and operation of the controller.
In section 7. Installation of lifting station and the following
sections, the above components are described as one unit.
Pos. Description
1Type designation
2Product number
3Production code (year/week)
4Frequency [Hz]
5Number of phases + voltage [V]
6Voltage [V]
7Full-load current [A]
8Motor input power P
[kW]
1
9EAC and CE mark
10Duty type
11Serial number
3
12Maximum flow rate [m
/h]
13Minimum head [m]
14Maximum head [m]
15Maximum liquid temperature [°C]
16Maximum ambient temperature [°C]
4
17Weight [kg]
18European norm identification code
19Notified Body
20Reference number for the Declaration of Performance
5.1.1 Collecting tank
Note
The gas-, odour- and pressure-tight collecting tank is made of
wastewater resistant polyethylene (PE) and has all necessary
ports for the connection of inlet pipes, discharge pipe, venting
pipe and a manually operated diaphragm pump, which is
available as an accessory.
The MD collecting tank has a turnable, eccentric disk in the
back allowing adjustment of the inlet to any height between 180
and 315 mm above the floor. The most common heights are
marked beside the inlet. See section 7.3 Procedure for
installation of lifting station.
Furthermore, the MD collecting tank offers four horizontal inlets in
the sides (2 x DN 100 and 2 x DN 50) and three vertical inlets at
the top of the tank (2 x DN 150 and 1 x DN 50). The centres of the
horizontal inlets are 120 mm (DN 50) and 250 mm (DN 150)
above the floor.
The side and back inlets 180 and 250 mm above the floor are for
direct connection to wall-hung or floor-standing toilet according to
EN 33 and EN 37. Further sanitary appliances can be connected
to the other ports.
The MLD collecting tank offers one vertical inlet, DN 50, at the
top of the tank and one vertical inlet, DN 150, in the stepped part
of the tank.
The tank volume and effective volume (volume between start and
stop) for Multilift MD and MLD lifting stations appear from the
following table:
MD
Inlet level [mm]180250315
Total tank volume [l]130
Effective tank volume [l]496986
MLD
Inlet level [mm]560
Total tank volume [l]270
Effective tank volume [l]190
Setting to the relevant start inlet level must be made during the
start-up phase via the setup menu. See section 6.2 Setup menu.
The first step after power supply connection is a start-up phase
with level setting.
To minimise sedimentation, the tank bottom is chamfered to lead
the wastewater to the pump.
5.1.2 Pumps
The pump impellers are designed as free-flow vortex impellers,
ensuring almost unchanged performance throughout the entire
life of the pump. The stator housing of the motor is made of cast
iron. The pump has a mechanical shaft seal.
See more technical data in section 12. Technical data.
Single-phase motors are protected by a thermal switch in the
windings and run via a capacitor inside the controller cabinet.
Three-phase motors are protected by a thermal switch in the
windings and an additional thermal circuit breaker in the cabinet
of Multilift MD/MLD22, 24, 32 and 38 to cut out the motor in case
of overload.
If the phase sequence for three-phase pumps is wrong, the
controller will indicate fault and prevent the pump(s) from starting.
For correction of phase sequence, see fig. 14. For direction of
rotation, see section 10.2 Motor.
If the motor is overloaded, it will stop automatically.
When it has cooled to normal temperature, it will
restart automatically.
Performance curves are available in the databooklet, which you
can download via the QR code or link below:
http://net.grundfos.com/qr/i/98288126
5.1.3 Shaft seal
The pumps have three shaft seals, the oil chambers in between are
filled for life and therefore require no maintenance.
For replacement in case of service, please see service
instructions.
5.1.4 Motor cable
The motor cable is fitted to the motor via a cable entry.
The enclosure class is IP68. The length of the cable is either 4 m
or 10 m.
Nameplate, motor
1
2
3
4
5
6
7
8
Prod.-Nr.
Phases
DK - 8850 Bjerringbro, Denmark
98189706 - A
P. c .
1217001
f
50
Serial no.
Hz
3
400
U
1/1
I
P1
P2
5.3
2.8
2.2
V
A
kW
S3-40%-1min
0.77
1405
n
F
24
G
IP68
Made in Germany
min
kg
-1
98189706
9
10
11
12
13
14
15
Fig. 4 Nameplate, motor
Pos. Description
1Product number and model
2Production code (year/week)
3Frequency
4Number of phases
5Rated voltage
6Rated current
7Input power
8Shaft power
9Serial number
10Operating mode
11Powe r factor
12Rated speed
13Insulation class
14Weight
15Production country
English (GB)
TM03 3618 0506
5
5.1.5 Non-return valve
Note
English (GB)
The DN 80 non-return valve includes a drain screw to lift up the
internal flap in order to drain the discharge pipe in case of
maintenance or service. The valve is designed and tested
according to EN12050-4. See fig. 5.
Loosen the lock nut a little before turning the drain
screw.
Fig. 5 Butterfly (double) non-return valve, DN 80
5.2 LC 221 controller
The LC 221 is a level controller specially designed for controlling
and monitoring the Grundfos lifting stations, Multilift MD and
MLD. The basis for the control is the signal received continuously
from the piezoresistive, analogue level sensor.
The level controller switches the MD and MLD Multilift pumps on
and off according to the liquid level measured by the level sensor.
When the first start level is reached, the first pump will start, and
when the liquid level has been lowered to the stop level, the pump
will be stopped by the controller. If the liquid level rises up to the
second start level, the second pump will also start, and when the
liquid level has been lowered to the stop level, the pumps will be
stopped by the controller.
Starts alternate between the two pumps.
In case of pump failure in one pump, the other pump will take
over (automatic pump changeover).
An alarm will be indicated in case of high water-level in the tank,
pump failure, etc.
Furthermore, the level controller has many more functions as
described below.
TM051530 2911
5.1.6 Level sensor
The piezoresistive pressure sensor placed in the controller is
connected via a hose to a pressure tube in the tank. The screw
cap where the hose is connected includes a connection for a DN
100 tube. This tube, the pressure tube, extends down into the
tank. The rising liquid level compresses the air inside the
pressure tube and hose, and the piezoresistive sensor transforms
the changing pressure into an analogue signal. The control box
uses the analogue signal to start and stop the pump and to
indicate high water-level alarm. The pressure tube is fixed
underneath the screw cap and can be taken out for maintenance,
service and for cleaning the inside of the tube. An O-ring ensures
tightness.
The hose is supplied in lengths of 4 or 10 m. The hose must be
connected to the controller.
Fig. 6 Screw cap with hose, DN 100 tube
Fig. 7 LC 221 level controller for Multilift MD and MLD
The LC 221 controller has the following functions:
• on/off control of two wastewater pumps based on a continuous
signal from a piezoresistive level sensor with alternating
operation and automatic changeover in case of pump failure
• motor protection with motor-protective circuit breaker and/or
current measurement as well as connection of thermal
switches
• motor protection via operating-time limitation with subsequent
emergency operation. Normal operating times are max.
25 seconds (MD) and 55 seconds (MLD), and the operating
TM05 0332 1011
time is limited to three minutes (see section 6.4 Description of
fault indications, fault code F011).
• automatic test runs (2 seconds) during long periods of
inactivity (24 hours after last operation)
• re-starting delay up to 45 seconds after returning from power
cut-off to mains operation (in order to even out the mains load
when several appliances are started up at the same time)
TM05 1859 3811
6
• setting of delay times:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Type
Prod.-No.
P.c.
f
PhasesU
G
Serial no.
P
max
TAmbmax
IPump max
V
A
Hz
C
O
kg
98189707
LC 221.1.230.1.10.30/150 MPU
98189707
1221
1
10
250
16
0
V01
0012
220-240
3
2
5.2
40
50
Ucontact max
IFuse max
TAmb min
A
C
O
Icontact max
V
W
A
I
c < 10 kA
IP55
Made in Germany
• automatic current measurement for alarm indications
• setting of current values:
• operating indication of:
• alarm indication of:
• selection of automatic alarm resetting
• fault log of up to 20 alarms
• selection between different start levels
• selection of maintenance interval (0, 3, 6 or 12 months).
As standard, the LC 221 has four potential-free outputs for:
Furthermore, LC 221 has six digital inputs for the following
functions:
For updates and further adjustments, a PC Tool can be
connected. See service instructions.
To allow for the situation that the normal power supply should fail,
a battery (accessory) can be installed which activates an acoustic
alarm (buzzer). The buzzer is activated as long as the fault exists.
It cannot be reset.
In case of sectional power failure, the common alarm output
which is a potential-free changeover contact can be used to
forward the alarm signal to a control room by means of an
external power source.
– stopping delay (time from the stop level is reached till the
pump is stopped) - reduces water hammer if pipes are long
– starting delay (time from the start level is reached till the
pump is started)
– alarm delay (time from a fault appears till an alarm is
indicated). This prevents short-time high-level alarm in case
of temporary high inflow to the tank.
– overcurrent (preset)
– rated current (preset)
– dry running current (preset).
– operating mode (auto, manual)
– operating hours
– impulses (number of starts)
– highest measured motor current.
– pump status (running, fault)
– phase sequence failure and missing phase
– thermal-switch failure
– high-water alarm (5 seconds delay)
– time for service/maintenance (selectable).
– pump running
– pump failure
– high water-level alarm
– common fault.
– connecting an analogue sensor (4-20 mA or 0-5 V)
– connecting up to four level switches and pressure sensors
instead of analogue sensor. An additional float switch can
be connected to the alarm input as backup for the analogue
sensor.
– connecting a separate level switch to be used for flood
detection outside Multilift MD or MLD. Lifting stations are
often installed in a sump inside the basement - the lowest
point in the building. In case of e.g. groundwater inflow or
water pipe burst, an alarm will be indicated by the controller.
– connecting a piezoresistive pressure sensor PCB
(pre-assembled)
– connecting an external alarm reset
– connecting the thermal switch of the motor.
Type key, LC 221 controller
ExampleLC 221 .2 .230 .1 .10 .30
LC 221 = controller type
1 = one-pump controller
2 = two-pump controller
Voltage [V]
1 = single-phase
The controller type, voltage variant, etc. are stated in the type
designation on the nameplate situated on the side of the
controller cabinet.
Fig. 8 Example of an LC 221 nameplate
Pos.Description
1Type designation
2Product number
3Production code (year, week)
4Number of phases
5Maximum pump input current
6Maximum voltage at potential-free contact
7Maximum backup fuse
8Minimum ambient temperature
9Version
10Serial number
11Rated voltage
12Power consumption
13Maximum current at potential-free contact
14Weight
15Maximum ambient temperature
16Frequency
English (GB)
TM054782 3311
7
5.2.1 Design
1
2
3
4
English (GB)
The LC 221 level controller incorporates the necessary
components to control and protect the pumps, such as relays and
capacitors for single-phase motors, contactors for three-phase
motors and additional motor-protective circuit breaker
(> Multilift MD22 or MLD22).
The control panel offers a user interface with operating buttons
and a display for indication of operating conditions and fault
indications.
Furthermore, it has an integrated piezoresistive pressure sensor
which is activated by compressed air directly via the pressure
tube inside the collecting tank. Finally, it has terminals for power
supply, connection to the pump and the inputs and outputs
mentioned in section 5.2 LC 221 controller.
The front cover is closed by four bayonet fastenings with quarter
turn locks. On the left side, the locks are extended and connected
to the cabinet bottom with hinge strings. The cabinet offers the
possibility of being mounted on a wall without opening it first.
A drilling template and six screws with rubber guides are
enclosed.
5.2.2 Control panel
Display (pos. 1)
The display shows all relevant operating data and fault indications.
The operation and fault indications are described in section
6.1 Description of display.
Operating buttons (pos. 2)
The level controller is operated by the operating buttons placed
under the display. The functions of the operating buttons are
described in the table below:
Operating
button
Status LEDs (pos. 3)
The upper LED (green) is on when the power supply is on.
The lower LED flashes (red) in case of fault to make the fault
visible from a long distance and is thus an addition to the display
symbols and fault codes.
The operating mode is selected by the
ON-OFF-AUTO selector switch which has three
different positions:
POS I:
Starts the pump manually. The operating time
protection is active and indicates alarm after three
minutes. Normal operating times are up to max.
25 seconds (MD) and 55 seconds (MLD).
TM05 1860 3811
POS O:
• Stops the pump when running and cuts off the
power supply to the pump. The three symbols
"Settings locked", "Information" and "Setup" will
be visible.
• Resets fault indications.
POS AUTO:
Automatic operation. The pump will start and stop
according to the signal from the level sensor.
8
5.2.3 Internal layout of LC 221
Note: Cable connections for pos. 8-15:
Use a cable tie if leads protrude more than
20 mm from the cable sheath.
X5
Figure 10 shows the internal layout of LC 221.
English (GB)
7
207
>20
Fig. 10 Internal layout LC 221 (three-phase PCB as example)
Pos. DescriptionCommentsTerminal designation
1Terminals for power supplyPE, N, L3, L2, L1
2Terminals for connecting pump 1PE, N, W1, V1, U1
3Terminals for connecting pump 2PE, N, W2, V2, U2
4Terminals for thermal switch, pump 1T1, T2
5Terminals for thermal switch, pump 2T1, T2
6Terminals for external reset230 V11, 12
7Terminals for external alarm (outside the tank)230 V13, 14
8Terminals for common fault
9Terminals for high water-level alarmX10
10Terminals for failure, pump 2X9
11Terminals for failure, pump 1X8
12Terminals for operation, pump 2X7
Potential-free changeover NO/NC
contacts with max. 250 V / 2 A.
Attention: Connect these terminals
to supply network potential or low
voltage but do not mix the two.
X11
13Terminals for operation, pump 1X6
Terminals for level switchesDigital81-88
14
Terminals for additional high water-level alarm
(inside the tank)
Digital81, 82
15Terminals for analogue sensor0-5 V or 4-20 mA91 (GND), 92 (Signal), 93 (12 V)
16Service connector to PC Tool17Connector for GENIbus interface moduleNot in use for this application-
18Control circuit fuse
Fine-wire fuse:
100 mAT / 20 mm x ∅5
-
19Piezoresistive pressure sensor module0-5 V20DIP switchesNot in use for this application-
Non-rechargeable batteries only.
21Connector for battery, 9 V
The controller is not equipped with a
-
charging device.
TM05 3597 1612 - TM05 3719 1712
9
6. Operating LC 221 controller
English (GB)
6.1 Description of display
The display of the LC 221 level controller is shown in fig. 11.
TM05 1861 3811
Fig. 11 LC 221 display
The table below describes the symbols shown in the display as well as the corresponding functions and indications.
Symbol FunctionDescription
Settings locked
Automatic operating
mode
Information
Setup
Alarm
Impulse counterThe symbol is visible when the number of starts in the information menu is shown in the display.
The symbol is visible when the setup menu is locked. This prevents unauthorised persons from
making changes to the settings. To unlock the buttons, enter the code 1234.
The symbol is visible when the level controller is in automatic mode, i.e. when the selector switch
is in position AUTO.
The symbol is visible when there is information about faults, operating hours, number of starts,
max. current of pump. The symbol will be visible if the level controller detects a fault and the fault
will be written into the fault log. After you have entered the fault log, the symbol will switch off.
See section 6.3 Information menu.
The setup menu holds information about setup for start level, rated current, the stop-, start- and alarm
delay, selection of maintenance interval, reset (automatic or manual) and reset back to factory
settings. For the procedure and a description of the settings, see section 6.2 Setup menu.
The symbol is visible if an alarm situation occurs. The type of alarm will appear from the
information menu. The symbol disappears when the fault has disappeared.
10
Settable times and fault
indication
The symbol is visible when the operating hours in the information menu and the delays set in the
setup menu are shown in the display. The symbol flashes when max. operating time has been
exceeded.
Symbol FunctionDescription
In automatic mode, faults are indicated by means of a code, and in normal operation these two
values are shown:
• the liquid level in the tank, if the pump is not running
• the current consumption, if the pump is running. If both pumps are running, the current
consumption shown is the value for both pumps.
In the information menu, the following information is indicated:
• fault codes
Values in the form of
digits
• operating hours
•impulses
• max. measured motor current.
In the setup menu, the following information is indicated:
•set start level
• set delays
•set currents
• sensor calibration (presettings for piezoresistive level sensor)
• service intervals
• total reset to factory settings.
English (GB)
Pump operation and
pump fault in pump 1
Pump operation and
pump fault in pump 2
Phase-sequence fault
Thermal-switch failure
High-water alarmThe symbol is visible if the liquid level in the tank reaches max. level.
Liquid levelThe symbol is visible when the current liquid level is indicated in the middle of the display.
The symbol is visible when pump 1 is running and flashes when pump 1 has a fault. In case of
fault, it can be combined with other symbols or fault codes in the display.
The symbol is visible when pump 2 is running and flashes when pump 2 has a fault. In case of
fault, it can be combined with other symbols or fault codes in the display.
(Only three-phase pumps)
The symbol flashes in case of a phase-sequence fault and missing phase.
See section 6.4 Description of fault indications.
The symbol is visible if the motor temperature exceeds the permissible value and the thermal
switch cuts out the pump.
11
6.2 Setup menu
L_01 Start level [mm]
Setup menu
3.8
I_02 Rated current [A]
T_01 Stop delay [sec.]
T_02 Start delay [sec.]
2
0
T_03 Alarm delay [sec.]
5
Manual/
Automatic
0, 3, 6, 12
EXIT
EXIT Back to main menu
G_01 Reset to factory settings
A_01 Reset alarm
M_01 Maintenance interval [month]
180
250
315
English (GB)
All settings are preset except for the start level. The start level
depends on the inlet height and must be set during the start-up
phase. See section 8.4 Setting of LC 221. However, in case
adjustments are required, settings can be made via the setup
menu. To open the setup menu, mark the symbol using the
button and press the button . Navigate through the menu by
means of the buttons and . Select the desired menu item by
pressing the button . Enter values or select settings from a list
by means of the buttons and . Save the settings by pressing
the button . See also fig. 12.
The following settings can be made:
•start level
• rated current
• stop delay
•start delay
• alarm delay
• time for maintenance
• alarm reset (manually or automatically)
• reset to factory settings.
Fig. 12 Menu structure for setup menu
TM06 6676 2016
12
6.3 Information menu
EXIT
EXIT Back to main menu
R_03 Measured max. motor current [A]
3.9
007200
000020
20 faults from 01 to 20
20 F006 …
01 F002
R_02 Impulse counter
R_01 Hour counter
F_01 Fault LOG
Information menu
All status data and fault indications can be seen in the information
menu. The information menu can be seen in all operating modes
(ON-OFF-AUTO). To open the information menu, mark the
symbol using the button and press the button .
Navigate through the menu by means of the buttons and .
Select the desired menu item by pressing the button .
See also fig. 13.
In the information menu the following data can be read:
• fault indications
• operating hours
• number of starts
• max. measured motor current.
English (GB)
Fig. 13 Menu structure for information menu
TM05 1809 3811
13
6.4 Description of fault indications
English (GB)
If a fault occurs, the symbol will be visible, an audible alarm will be given by the buzzer and the fault code will be written by means of
the 14-segment characters in the display. To see the kind of fault, if it is automatically reset and the code is not longer visible, open the
fault log (see fig. 13). When you leave the fault log, the symbol will disappear.
The last 20 faults are stored in the fault log as fault codes. The meaning of the fault codes are described in the table below:
Reset of
Fault
code
F001
Meaning
Phase sequence
failure
Displayed
text
F001●
Flashing
symbols
fault
indications
Auto Man
Description
(Only three-phase pumps)
The phase sequence between control board and power supply is
wrong. See fig. 14.
F002
F003High liquid levelF003●●The liquid level is high in relation to preset value.
F004Sensor failureSENSOR-●●Sensor signal out of range or lost.
F005
F006
F007
F008
F011
F012
F013External faultEXT-●
F014Battery failureBAT-●●The battery is empty and must be replaced.
F015
F016
F017
F018
F019
F117F117●
F020
One phase
missing
Overtemperature,
pump 1
Overtemperature,
pump 2
Overcurrent,
pump 1
Overcurrent,
pump 2
Operating time
exceeded, pump 1F011●●
Operating time
exceeded, pump 2F012●●
Relay or
contactor does
not open, pump 1
Relay or
contactor does
not close, pump 1
Relay or
contactor does
not open, pump 2
Relay or
contactor does
not close, pump 2
Display
communication
failure
High level alarm
in tank
F002●●
TEMP●●
TEMP●●
F007●
F008●
RELAY●
RELAY
RELAY●
RELAY
Display is
off.
F020●
(Only three-phase pumps)
One phase is missing.
Motor thermal switches connected to the controller will stop pump 1
in case of overheating.
Motor thermal switches connected to the controller will stop pump 2
in case of overheating.
Pump 1 is stopped if an overcurrent is measured for a certain period
of time (blockage protection).
Pump 2 is stopped if an overcurrent is measured for a certain period
of time (blockage protection).
The pump has run for more than the allowed operating time and the
controller has stopped the pump for a defined cool-down period in
order to prevent overheating. The operating time and cool down
period depends on the pump. See duty type on nameplate.
Check that the outlet isolating valve is open.
Check that the non-return valve is functioning. A leaky non-return
valve can allow liquid in the outlet pipe to flow back in to the
collecting tank.
Remove any blockage from the venting system, see fig. 33.
An external level switch can be connected to the controller to give
an alarm when basement outside the lifting station is flooded by
groundwater or water from burst water pipe.
Pump 1 receives a signal to stop, but does not react. This situation
is detected by current measurement.
Pump 1 receives a signal to start, but does not react. This situation
is detected by current measurement.
Pump 2 receives a signal to stop, but does not react. This situation
is detected by current measurement.
Pump 2 receives a signal to start, but does not react. This situation
is detected by current measurement.
Communication failure between the main board and the display. As
the display is off, the fault code can be found via PC tool only.
●
Check the patch cable RJ45 between the main board and the
display.
Communication failure between the main board and the display.
The display is still on and is displaying the fault code F117. Check
the patch cable RJ45 between the main board and the display.
Alarm triggered by the additional float switch inside the tank. The
piezoresistive sensor has failed to detect the start level. The float
switch is triggered and starts a pump for 20 seconds (preset value,
changeable via PC tool).
Check the tank, the level sensor hose and the hose connections for
any air leakage.
The level sensor hose is connected correctly to the pneumatic
coupling underneath the controller when you cannot pull it out
without pressing the locking mechanism.
14
If a fault occurs, the red LED will flash, the symbol will be
visible and the fault will be added to the fault log.
Furthermore,Hthe buzzer will be activated, the symbol will be
visible, the corresponding symbols will flash and the fault code
will be displayed. When the fault has disappeared or has been
removed, the controller will automatically switch to normal
operation again. However, the controller enables resetting of the
fault indication (visible and acoustic alarms) either manually
(Man) or automatically (Auto).
If manual resetting was selected in setup menu, the acoustic
alarm and red LED can be reset by pressing the button .
The fault indication will be reset when the fault has disappeared,
has been removed or the ON-OFF-AUTO switch has been set to
OFF position.
You can get an overview of faults in the fault log in information
menu.
The symbol will be visible as long as the fault log is open.
If automatic resetting was selected in menu setup, the red LED
and the symbol will disappear, and the buzzer will be
deactivated again after the fault has disappeared, has been
removed or the ON-OFF-AUTO switch has been set to OFF
position. However, even if automatic resetting was selected,
some of the fault indications have to be reset manually.
See the table above.
Every 30 minutes the fault indication will be written from the
short-term memory into the long-term memory.
English (GB)
Fig. 14 Changing phases of a three-phase controller with
phase inverter
TM05 3455 0616
15
7. Installation of lifting station
472165
3
3
4
65
English (GB)
7.1 General description
When installing the Multilift MD or MLD lifting station, make sure
that all local regulations covering venting, access to the stations,
etc. are observed.
7.1.1 Installation sketches
Fig. 15 Installation sketch, Multilift MD
Fig. 16 Installation sketch, Multilift MLD
TM05 1864 3811
TM05 1865 3811
Pos.AccessoriesProduct number
1Socket seal, DN 10097726942
2Socket seal, DN 5098079669
3Diaphragm pump, 1 1/2"96003721
4PVC isolating valve, DN 10096615831
5Cast iron isolating valve, DN 8096002011
6Gasket kit, DN 80, with bolts, nuts and washers96001999
7Inlet disk with socket seal, DN 150, for replacement98079681
16
7.2 Guidelines for installation of lifting station
Note
Caution
Note
The guidelines for correct mechanical installation of lifting station
are according to EN 12056-4.
See section 7.1.1 Installation sketches.
• Install the lifting station in a properly lit and vented room with
60 cm free space around all parts to be serviced and operated.
• Provide a pump sump below the floor level. If a lifting station is
installed in a basement with the risk of penetrating
groundwater, it is advisable (in certain countries required) to
install a drainage pump in a separate pump sump below floor
level in order to drain the room. See figures 15 and 16.
The collecting tank, pump and cables may be flooded
(max. 2 m for 7 days).
The controller must be installed in a dry and well
ventilated place.
• All pipe connections must be flexible to reduce resonance.
• Lifting stations must be secured against uplift and twist.
• All discharge pipes from lifting station, diaphragm pump and
drainage pump must have a bend above the local backwater
level. The highest point of the bend/reversed water seal must
be above street level. See figures 15 and 16.
• For discharge pipes, DN 80 and upwards, install an isolating
valve in the discharge pipe. Also provide an isolating valve in
the inlet line.
• Surface water must not be discharged into the lifting station
inside the building. It must have its own pumping station
outside the building.
• Lifting stations must be provided with an approved non-return
valve according to EN 12050-4.
• The volume of the discharge pipe above the non-return-valve
up to the backwater level must be smaller than the effective
tank volume.
• In general, a lifting station for black wastewater must be
vented above roof level. However, it is permitted to lead the
ventilation, as a secondary ventilation, into the main building
ventilation system. Special venting valves (accessory) must be
placed outside the building.
• If the wastewater is discharged into a collecting line, this
collecting line must have a filling ratio of at least h/d = 0.7.
The collecting line must be at least one nominal diameter
bigger after the discharge pipe connection.
• The controller must be placed in a flood safe place and be
equipped with an alarm.
• Use a diaphragm pump for simple, manual draining of the
collecting tank in case of pump failure (not obligatory).
7.3 Procedure for installation of lifting station
7.3.1 Inlet pipe connections, Multilift MD
1. Check the scope of delivery.
For scope of delivery see section 2. Scope of delivery.
2. Prepare the adjustable inlet on the back of Multilift MD.
The turnable inlet disk has a DN 100 inlet and allows the inlet
height to be adjusted to any height between 180 and 315 mm
above floor level. The most common heights, 180, 250 and
315 mm, are marked beside the inlet. See fig. 17. An inlet disk
with a DN 150 inlet is available as an accessory. See fig. 18.
The screws around the outer ring of the inlet disk are not fully
tightened allowing the inlet disk to be turned. This will allow
the inlet to be adjusted to the desired inlet height. When the
desired inlet height has been set, tighten all screws.
All screws must be tightened to max. 9 Nm.
Before connecting Multilift MD, consider that when
turning the inlet disk to fit to the height of the inlet
pipe, the lifting station and the discharge will move
sideways accordingly (max. 72.5 mm). See fig. 17.
Fig. 17 DN 100 inlet disk, adjustable from 180 to 315 mm
above the floor to the middle of the inlet pipe
English (GB)
TM05 0351 1011
TM051669 3411
Fig. 18 Optional DN 150 inlet disk, adjustable from 207 to
279 mm above the floor to the middle of the inlet pipe
17
English (GB)
Caution
Note
Caution
DN 50 - ∅43
DN 100 - ∅100
DN 150 - ∅150
Fig. 19 Untightened screw in outer ring
Multilift MD lifting stations are supplied with loose
screws in the outer ring of the turnable inlet disk. See
fig. 19. Check and tighten all screws to max.
tightening torque of 9 Nm before connecting the inlet
pipe.
If the main inlet is not to be used it can easily be
plugged using a standard DN 100 pipe plug fastened
with three screws and washers.
See fig. 20.
4. Prepare the connection for diaphragm pump (optional).
Use cup drill, ∅43, for DN 50 connection socket. To avoid
sharp cutting edges, the hole must be deburred.
TM05 0336 1011
TM05 1242 2511
Fig. 21 Cutting or drilling of optional connection holes
5. Connect the inlet pipe to the tank.
Install an isolating valve between inlet pipe and lifting station
to avoid inflow during maintenance and service.
We recommend an easy-to-handle PVC isolating valve.
Fig. 20 Plugging the main inlet
3. Prepare optional inlets by cutting out the desired one.
Use cup drills ∅150 for DN 150, ∅100 for DN 100 and ∅43 for
DN 50 inlets. The cutting line is recessed. To avoid sharp
cutting edges, the holes must be deburred. The socket seals
are provided with collars.
18
TM05 0329 1011 - TM05 0352 1011
TM05 1503 2811
Fig. 22 Installation of isolating valve
Make sure that weight from inlet, discharge and vent
pipes does not rest on the tank. Long pipe sections,
valves, etc. must be supported.
Warning
Never step on the lifting station.
7.3.2 Inlet pipe connections, Multilift MLD
Note
1. Check the scope of delivery.
For scope of delivery, see section 2. Scope of delivery.
2. Prepare the ∅150 inlet.
Use a cup drill ∅150 to drill out the hole along the recessed
line. See fig. 21. The tank minimum inlet level for MLD is
approximately 560 mm. See fig. 23.
3. Prepare the additional ∅50 inlet.
Cut along the stepped line of the ∅50 inlet port on top of the
tank.
Fig. 23 Minimum inlet level for MLD
7.3.3 Further connections for Multilift MD and MLD
1. Connect the discharge pipe.
Install an isolating valve between the non-return valve and the
supplied flexible connection hose, DN 100 (internal diameter
110 mm). A flexible connection can be ensured if a distance of
approx. 3 cm is left between the pipe ends of the connection
piece and the discharge pipes.
4. Fix the tank to the floor.
Fig. 25 Fixing point for fixation of tank to the floor
8. Installation of LC 221 controller
Warning
Before making any connections in LC 221 or working
on pump, pit, etc., make sure that the power supply
has been switched off and that it cannot be
accidentally switched on.
The installation must be carried out by authorised personnel in
accordance with local regulations.
8.1 Location
TM03 3613 0406TM05 1866 3811
Warning
Do not install the LC 221 controller in explosion
hazard areas.
LC 221 can be installed at ambient temperatures ranging from
0 °C to +40 °C.
Enclosure class: IP55.
Install the controller as close as possible to the lifting station.
When installed outdoors, LC 221 must be placed in a protective
shed or enclosure. LC 221 must not be exposed to direct sunlight.
English (GB)
TM05 0334 1011
Fig. 24 Isolating valve on top of non-return valve
2. Connect the venting pipe.
The DN 70 venting port on top of the tank is open.
Connect the venting pipe to the venting port via a flexible
connection piece. The venting pipe must be led out above the
roof into the open air in accordance with local regulations.
Check the use of venting valves (accessory) according to
local regulations if venting above the roof is impossible.
A flexible connection can be ensured if a distance of
approx. 3 cm is left between the venting pipe end and the
venting port.
3. Connect the diaphragm pump (optional).
Fit the diaphragm pump on the discharge side. To facilitate
servicing of the diaphragm pump, we recommend fitting a
1 1/2" isolating valve to the tank port.
8.2 Mechanical installation
Warning
When drilling the holes, take care not to damage any
cables or water and gas pipes. Ensure a safe
installation.
LC 221 can be mounted without removing the front
cover.
Proceed as follows:
• Mount LC 221 on a plane wall surface.
• Mount LC 221 with the cable entries pointing downwards
(additional cable entries, if required, must be fitted in the
bottom plate of the cabinet).
• Mount LC 221 with four screws through the mounting holes in
the back plate of the cabinet. Drill the mounting holes with a
6 mm drill using the drilling template supplied with the
controller. Fit the screws into the mounting holes and tighten
securely. Fit the plastic caps.
19
English (GB)
Fig. 26 Mounting of controller to the wall
8.3 Electrical connection
Warning
The protective earth (PE) of the power outlet must be
connected to the protective earth of the product. The
plug must have the same PE connection system as
the power outlet.
Warning
The installation must be fitted with a residual current
device (RCD) with a tripping current less than 30 mA.
Warning
The product must be connected to an external main
switch with a minimum contact gap of 3 mm (0.12
inch) in all poles.
Warning
LC 221 must be connected in accordance with the
rules and standards in force for the application in
question.
Warning
Before opening the cabinet, switch off the power
supply.
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the power
supply on which it will be used.
All cables/wires must be fitted through the cable entries and
gaskets.
The power outlet must be placed near the cabinet as the
controller is supplied with a 1.5 m cable.
Maximum back-up fuse is stated on the controller nameplate.
8.4 Setting of LC 221
Only the start level corresponding to the inlet level to the
collecting tank needs to be set. All other values are preset but
can be adjusted if required.
Select the height of the inlet pipe, 180, 250 or 315 mm above
floor level, using the buttons and , and press the button
to save the desired value. If the height of the inlet pipe is between
two values, e.g. 220 mm above the floor, choose the nearest
lower value (180 mm). Now the controller is ready for automatic
mode.
The following values can be changed, if necessary:
Start level
The start level must be set according to the inlet pipe height
above floor level (180, 250 and 315 mm). Stop and alarm levels
are preset.
Rated current
Preset value from factory according to the rated current of the
motor. The protection against pump blockage is a preset value for
overcurrent.
Stop delay
The stop delay increases the effective volume and reduces the
quantity of residual water in the tank. It also prevents water
hammer. The non-return valve closes more softly. The preset
value is 0.
Start delay
TM05 1940 4011
Normally there is no need to make adjustments for lifting stations
except on a houseboat or pontoon boat. The preset value is 0.
Alarm delay
High temporary inflow can cause short-time high-level alarm.
This situation may arise when a backwash filter of a swimming
pool is connected to Multilift MD. Preset value is 5 seconds.
Maintenance interval
The maintenance/service interval can be set to 0, 3, 6 or
12 months and is indicated in the "SERVICE" display (no acoustic
signal).
Reset alarm
It is possible to set the controller to reset some alarms
automatically when the fault disappears; however, most alarms
must be reset manually. See section 6.4 Description of fault
indications. Preset value is AUTO.
Reset to factory settings
The controller will reboot, and start-up settings will have to be
made again. See section 6.2 Setup menu.
8.4.1 External alarm
Lifting stations are often installed in sumps below the basement
of buildings. That is the deepest point in the building, and an
additional alarm level switch can be placed outside the lifting
station to detect flooding caused by leakages, pipe bursts or
groundwater inflow.
The external alarm can be connected to a level switch (230 V /
2 A) at terminals 13, 14.
MD/MLD.32.3.2 and MD/MLD.38.3.2 with
motor-protective circuit breaker
21
9. Startup
Note
English (GB)
Warning
Before starting any work on a pump used for
pumping liquids which could be hazardous to health,
clean and vent the pump, pit, etc., thoroughly
according to local regulations.
Warning
Before making any connections in LC 221 or working
on pump, pit, etc., make sure that the power supply
has been switched off and that it cannot be
accidentally switched on.
Prior to start-up, the connection and settings must have been
carried out according to sections 8.3 Electrical connection and
8.4 Setting of LC 221.
Start-up must be carried out by authorised personnel.
Proceed as follows:
1. Check all connections.
2. Connect the plug to the power supply and follow the controller
start-up sequence.
Note: It will take up to 45 seconds to boot the controller.
This time can be reduced to 5 seconds by pressing the OK
button. When the power supply is connected for the first time,
three values for the start level can be chosen (180, 250 or
315 mm above floor level) according to the inlet height to the
collecting tank. If the inlet height is between two levels,
choose the lower level for start in the display. All other
settings are preset. Some settings can be changed.
See section 8.4 Setting of LC 221. Now the controller is ready
for automatic mode (selector switch in pos. AUTO).
3. Open the isolating valves in discharge and inlet lines.
4. Activate a sanitary appliance connected to the inflow of the
Multilift MD or MLD and monitor the increasing liquid level in
the tank up to the start level. Check the starts and stops at
least twice.
If the pump cable was disconnected from the
controller, for instance to lead the cable through an
empty cable conduit, check the direction of rotation
of the pump.See section 10.2 Motor.
10. Maintenance and service
The Multilift MD and MLD require a minimum of maintenance.
Warning
Before carrying out maintenance and service on
lifting stations used for pumping liquids which might
be hazardous to health, make sure that the lifting
station has been thoroughly flushed with clean water
and that the discharge pipe has been drained. Rinse
the parts in water after dismantling. Make sure that
the isolating valves have been closed. The work
must be carried out in accordance with local
regulations.
Warning
Before making any connections in LC 221 or working
on lifting stations, make sure that the power supply
has been switched off and that it cannot be
accidentally switched on.
According to EN 12056-4 lifting stations must be checked at the
following regular intervals:
• every 12 months in single-family houses
• every 6 months in multi-family dwellings
• every 3 months in commercial and industrial applications.
During the check, local regulations must be observed.
The periodic checks of the lifting station must be carried out by
authorised personnel and must comprise electrical and
mechanical maintenance.
Check the following points:
• Discharge and inlet connections
Check all connections to the lifting station for tightness and
leakages. Make sure that weight from the inlet, discharge and
venting pipes does not rest on the tank. Long pipe sections,
valves, etc. must be supported.
• Power consumption
See nameplate.
• Cable entry
Make sure that the cable entry is watertight and that the
cables are not bent sharply and/or pinched.
• Pump parts
Remove eight screws and dismantle the pump from the tank
and check that the vent hole of the pump housing is clear.
When the pumps is mounted again, we recommend to replace
the O-ring between pump and tank. Make a test run with clean
water. In case of noise, vibration or abnormal running, contact
Grundfos.
• Ball bearings
Check the shaft for noisy or heavy operation. Replace defective
ball bearings. A general overhaul of the pump is usually
required in case of defective ball bearings or poor motor
function. This work must be carried out by the manufacturer or
an authorised service workshop.
Cleaning the non-return valve (if required)
Proceed as follows:
1. Close the isolating valves in the discharge pipe and in the
inlet pipe (if fitted) or drain the discharge pipe by tightening
the drain screw on the side of the non-return valve. See fig. 5.
2. Clean the non-return valve via its inspection cover.
Replace the gasket of the inspection cover when
reassembling the non-return valve.
22
10.1 Mechanical maintenance
Caution
Note
• Remove possible deposits and/or sludge build-up in the
collecting tank.
• Remove any blockages on the inlet side of the lifting station.
A blockage will typically be a large solid object.
• Check and replace the gaskets of connections at valves, etc.,
if necessary.
• Check the tank for cracks and deformations. These may occur
in case of faulty assembly and therefore excessive stress on
the tank.
Note: The above list is not complete. The lifting station may be
installed in environments which require thorough and frequent
maintenance.
10.2 Motor
Check the direction of rotation of the pump in the following way:
• Turn off the power.
• Unscrew the lifting eye on top of motor. See fig. 31.
• The top of the motor shaft is now visible. See fig. 32.
Check that rotor and impeller can be turned freely by turning
the shaft with a large slotted screwdriver.
English (GB)
TM05 0344 1011TM05 0330 1011
Fig. 33 Vent holes in pump housing and collecting tank
Fig. 31 Lifting eye
Fig. 32 Top of slotted motor shaft
If the pump has been disassembled, remember to
align the vent hole in the pump with the vent hole in
the tank when remounting the pump to the tank.See
figures 33 and 34.
TM05 0338 1011TM05 0339 1011
Fig. 34 Alignment marks on tank and pump flange
10.3 Electrical maintenance
• Check the gasket of the LC 221 cabinet front cover and of the
cable entries.
• Check the cable connections.
• Check the controller functions.
• Check and clean the level sensor. See section 10.4 Cleaning
the level sensor.
• If LC 221 is installed in a particularly moist environment in a
basement, we recommend checking the terminals on the PCB
in order to identify possible corrosion. In typical installations,
the contacts will work for several years and do not require any
inspection.
• Replace the 9 V battery, if fitted, in connection with annual
service.
The above list is not complete. LC 221 may be
installed in environments which require thorough and
frequent maintenance.
23
10.4 Cleaning the level sensor
English (GB)
1. Push the ON-OFF-AUTO selector switch to position OFF ( ).
See section 5.2.2 Control panel.
2. Loosen the screw cap by turning it counterclockwise.
See fig. 35.
3. Lift the pressure tube carefully out of the collecting tank.
Do not lift it by means of the hose.
4. Check for possible deposits on or in the pressure tube. See
section 5.1.6 Level sensor.
5. Scrape off any deposits. If necessary, remove the hose from
the controller, and rinse the tube and hose with clean water at
low pressure. Make sure no water remains in the hose.
6. Refit the pressure tube by screwing the screw cap on to the
tank. Reconnect the hose to the controller.
7. Check the sensor by test running Multilift MD, MLD.
Fig. 35 Removing the level sensor
10.5 Contaminated lifting station or components
Warning
If a Multilift lifting station has been used for a liquid
which is injurious to health or toxic, it will be
classified as contaminated.
If Grundfos is requested to service the lifting station, Grundfos
must be contacted with details about the pumped liquid, etc. before
the lifting station is returned for service. Otherwise Grundfos can
refuse to accept the lifting station for service.
Lifting stations which have been in contact with the pumped liquid
must be thoroughly cleaned before they are returned to Grundfos.
Any costs of returning the lifting station are to be paid by the
customer.
However, any application for service (no matter to whom it may
be made) must include details about the pumped liquid if the
lifting station has been used for liquids which are injurious to
health or toxic.
TM05 0545 1011
24
11. Fault finding
Warning
Before carrying out any work on lifting stations used for pumping liquids which might be hazardous to health, make sure that
the lifting station has been thoroughly flushed with clean water and that the discharge pipe has been drained. Rinse the parts
in water after dismantling. Make sure that the isolating valves have been closed. The work must be carried out in accordance
with local regulations.
Before making any connections in the LC 221 or work on lifting stations, etc., it must be ensured that the power supply has
been switched off and that it cannot be accidentally switched on.
FaultCauseRemedy
1. The pump(s)
does/do not run.
2. The sensor signal is
out of range.
All pumps are
started and high
level alarm is on.
3. The pump(s) is/are
starting/stopping
too frequently and
even if there is no
inflow.
4. One pump starts
sometimes without
visible reason.
a) No power supply.
None of the indicator lights are on.
With battery back-up:
See section 5.2 LC 221 controller.
b) The ON-OFF-AUTO selector switch is in position
OFF ( ), see section 6. Operating LC 221
controller.
c) Control circuit fuses are blown.Check and eliminate the cause. Replace the control
d) The motor-protective circuit breaker has cut out
the pump (only relevant if a motor-protective
circuit breaker has been installed). The pump
symbol in the display is flashing and the red
indicator light for fault is flashing. The fault
indication in the display is RELAY and the fault
code is F018.
e) Motor/supply cable is defective or the connections
have become loose.
f) The fault indication in the display is SENSOR and
in the fault code is F005 and/or F006.
g) The module power circuit board or the LCD board
is defective.
a) Discharge valves are not all opened.Open all discharge isolating valves.
b) There is a blockage in the tank or pump.Remove blockage.
c) The pump venting is not working, which means
that the pump cannot built pressure.
d) The lifting station is undersized.Recalculate the inflow parameters and compare with
a) The level sensor fails. The sensor gives wrong
signal.
b) The operating time protection is activated, the
pump and time symbols are flashing, the red LED
is flashing and the display indicates fault code
F011 and/or F012. If the pump runs longer than 3
minutes, a protection program of the controller will
stop the pump for 3 minutes and the other pump
will take over. At the next start impulse, the first
pump will be activated again. If the venting
problem persists, the pump will be stopped after 3
minutes and so on.
Note: Normal operating times are up to
60 seconds depending on duty point and effective
tank volume.
c) The thermal switch has cut out the pump. The
pump and thermal switch symbols on the display
are flashing, and the red indicator light for fault is
permanently on. The fault indication in the display
is TEMP and in the fault code is F005 and/or
F006.
a) Test run 24 hours after last operation.No action necessary. It is a safety function that
Switch on the power supply or wait until the power cut
is over. During the power cut, drain the collecting tank
with diaphragm pump.
Push the ON-OFF-AUTO selector switch into position
ON ( ) or AUTO ( ).
circuit fuses.
Check the pump and tank as well as the setting of the
motor-protective circuit breaker. If the pump is
blocked, remove the blockage. If the setting of the
motor-protective circuit breaker is wrong, readjust it
(compare the setting with the nameplate).
Check motor and supply cable. Replace cable or
retighten connections if necessary.
Clean the level sensor (see section 10.4 Cleaning the
level sensor), and start up again. Check the cable and
the connection on the controller board. If the signal is
still wrong, please call Grundfos service.
Replace the PCB or LCD board.
Remove blockage from the pump venting hole,
located above the impeller.
the size and pumping volume of the lifting station.
Contact the nearest Grundfos sales company for
ordering a new product if needed.
Clean the level sensor
(see section 10.4 Cleaning the level sensor).
Check that the discharge valve is open. Check the
venting of the pump housing. If blocked clean the vent
hole. See fig. 33.
Allow the pump to cool. After cooling, the pump will
restart automatically unless the LC 221 has been set
to manual restarting. See section 8.4 Setting of LC
221. If so, the ON-OFF-AUTO selector switch must be
pushed into position OFF ( ) for a short period.
Check the inflow parameters and the non-return valve.
The risk is low, but if the non-return valve flap is leaky,
liquid in the discharge pipe can flow back.
A high number of starts without cooling time in
between over a longer period can cause thermal
cut-out. Consider S3 duty. See section 12. Technical
data.
See also section 10.4 Cleaning the level sensor.
prevents the shaft sealing from seizing up.
English (GB)
25
12. Technical data
English (GB)
12.4 LC 221 controller
12.1 Lifting station
Weight:
Temperature range:
Flood conditions:Max. 2 m for 7 days
Sound pressure level:
Depending on variant.
See nameplates
0-40 °C
For short periods up to 60 °C
(max. 5 minutes per hour)
< 70 dB(A) according to
EN 12050-1 and the Machinery
Directive
12.2 Collecting tank
Material:PE (polyethylene)
12.3 Pump
Motor
Mains frequency:50 Hz
Isolation class:F (155 °C)
Impeller type:Vortex
Enclosure class:IP68
pH-range:4-10
Starts per hour:Max. 60
Max density of liquid:1100 kg/m
3
Controller
Voltage variants,
rated voltages:
Voltage tolerances for LC 221: - 10 %/+ 6 % of rated voltage
Mains frequency for LC 221:50/60 Hz
Supply system earthing:For TN systems
Controller power consumption: 6 W
Control circuit fuse:
Ambient temperature:
During operation:
In stock:
Enclosure class:IP55
Potential-free contacts:NO/NC, max. 250 VAC / 2 A
Input external reset:230 V
Cabinet of LC 221
External dimensions:
Material:
Weight:
1 x 230 V, 3 x 230 V,
3 x 400 V
Fine-wire fuse:
100 mAT / 250 V / 20 mm x ∅5
0 to +40 °C (must not be
exposed to direct sunlight)
-30 to +60 °C
Height = 390 mm
Width = 262 mm
Depth = 142 mm
ABS
(acrylonitrile butadiene styrene)
Depending on variant.
See nameplate
ComponentMaterial
Pump housingCast iron
ImpellerPPE+PS
Pump shaft
Motor cablePolychloroprene
O-ringsNBR rubber
Multilift MD
Multilift MLD
MD/MLD.12.1.4
MD/MLD.12.3.43 x 400 V1.8 / 1.53.7 / 19CEE 3P+N+E, 16 A
MD/MLD.15.1.41 x 230 V2.3 / 1.710.1 / 39
MD/MLD.15.3.43 x 400 V2.3 / 1.84 / 19CEE 3P+N+E, 16 A
MD/MLD.22.3.4
MD/MLD.22.3.43 x 400 V5.5 / 29.7CEE 3P+N+E, 16 A
MD/MLD.24.3.23 x 230 V
MD/MLD.24.3.23 x 400 V5.5 / 39CEE 3P+N+E, 16 A
MD/MLD.32.3.23 x 230 V
MD/MLD.32.3.23 x 400 V6.7 / 39CEE 3P+N+E, 16 A
MD/MLD.38.3.2
MD/MLD.38.3.23 x 400 V7.5 / 39CEE 3P+N+E, 16 A
S3 -50 %, 1 min.
S3 -50 %, 1 min.
S3 -40 %, 1 min.
Stainless steel,
DIN W.-Nr. 1.4301
DutyVoltage [V]
1 x 230 V1.9 / 1.49 / 39
3 x 230 V
3 x 230 V
Power P1 / P2
[kW]
2.8 / 2.3
3.1 / 2.6
4.0 / 3.4
4.6 / 3.9
I
/ I
1/1
start
10.2 / 51.5
9.7 / 88.7
88.7
13 / 88.7
[A]RPM [min-1]
14304
14104
14304
29202
29202
28802
Number of
poles
Plug type
E/F, I
-
E/F, I
-
CEE 3P+E 16 A
CEE 3P+E 16 A
CEE 3P+E 16 A
CEE 3P+E 16 A
13. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
26
The crossed-out wheelie bin symbol on a product
means that it must be disposed of separately from
household waste. When a product marked with this
symbol reaches its end of life, take it to a collection
point designated by the local waste disposal
authorities. The separate collection and recycling of such
products will help protect the environment and human health.
Appendix1
Fig. A - Dimensional sketches - MD
Appendix
27
TM05 0441 1011
Appendix
Fig. B - Dimensional sketches - MLD
TM05 0442 1011
28
Argentina
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Centro
Industrial Garin
1619 Garín Pcia. de B.A.
Phone: +54-3327 414 444
Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Zmaja od Bosne 7-7A,
BH-71000 Sarajevo
Phone: +387 33 592 480
Telefax: +387 33 590 465
www.ba.grundfos.com
e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo Branco,
630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: bulgaria@grundfos.bg