Introduction 4
Grundfos MS Motors Introduction 4
MS Motor Selection 4
Product Range 5
Model Designation 6
Nameplate 6
Features
MS 402 7
MS 4000 8
Special Construction Features 8
MS 6000 9
Special Construction Features 9
Operating Conditions
Operating Conditions 10
MS 402 11
MS 4000 12
MS 6000 13
Construction
Material specification for MS 402 14
Material specification for MS 4000 15
Material specification for MS 6000 16
Technical Data
Outline Drawing MS 402 26
Dimensions and Weights MS 402 26
Outline Drawing MS 4000 27
Dimensions and Weights MS 4000 27
Outline Drawing MS 6000 28
Dimensions and Weights MS 6000 28
Electrical Data
Grundfos Motors Specifications 29
Transformer Capacity 31
Engine-Driven Generators 32
Motor Protection Chart 33
Motor Cable Selection Chart
(Motor Service to Entrance) 35
Single Phase, 60 Hz 35
Three Phase, 60 Hz 35
Accessories
CU 3 37
Benefits of CU 3/R100 38
Control functions 39
Features and benefits 40
Motor protection via CU 3 41
Control unit CU 3 with R100
remote control and printer 41
R100 Menus 42
Menu Structure of the R100 Remote Control 43
Complete Borehole Monitoring
System with CU 3 and SM 100 44
Selection
Motor Operation 17
Motor Loading, Failure and Lifetime 17
Motor Efficiency 18
Application and Selection Issues 19
Mechanical Installation
Submersible Motor Cooling 20
Required Cooling Flow and Velocity 20
Water Temperature and Motor Derating 20
Shroud/Flow Inducer Sleeve/Cooling Sleeve 21
Special (Non Water Well) Applications 22
Electrical Installation
Submersible Power Cable 24
Cable Selection 25
Further product documentation
Sources of product documentation 45
WinCAPS® 45
WebCAPS® 46
2
Page 3
Mission
- to successfully develop, produce, and sell high quality
motors and pumping systems worldwide, contributing to a
better quality of life and healthier environment
• One of the 3 largest pump companies in the world
• The second largest manufacturer of submersible motors in the world
• World headquarters in Denmark
• North American headquarters in Kansas City - Manufacturing in Fresno, California
• 60 companies in 40 countries
• More than 10 million motors and pumps produced annually worldwide
• North American companies operating in USA, Canada and Mexico
• Continuous reinvestment in growth and development enables the company to
BE responsible, THINK ahead, and INNOVATE
3
Page 4
Product data
MS Motors
Introduction
Grundfos MS Motors Introduction
Grundfos Submersible motors are designed specifically
for operation in and under water.
The motor and power cable are designed and sealed to
prevent water from contacting any part of the electrical
circuit.
The motors are equipped with a high-capacity thrust
bearing to support the total thrust of the pumping unit.
The Grundfos submersible motor depends on
surrounding water to carry away heat; most require a
specified flow of water for adequate cooling.
MS Motor Selection
Selecting the best submersible motor for a particular
pump application requires careful consideration of
several factors. The motor must match the pump in
mounting dimensions, and must also have adequate Hp
load rating and thrust rating to support the pump over
its entire operating range. Grundfos 4” and 6” submersible motors are built to NEMA standards, which define
their physical dimensions, electrical ratings, and thrust
ratings. The motor must be capable of operation at the
water temperature and velocity presented by the installation.
Grundfos literature specifies the maximum water
temperature and minimum required velocity past the
motor. Motor operation in water that exceeds the rated
temperature may be allowable at reduced loading,
depending on the particular motor.
If the installation does not assure the specified velocity
past the motor- because of well diameter, well inflow
above the pump or other reasons - a sleeve over the
motor should be used to induce the required velocity.
MS 402 is generally recommended for operation in
water without any appreciable amount of chloride at
common groundwater temperatures.
• MS402 is made of 304 stainless steel AISI
Sand Content
Max. sand content in pumped liquid: 50 ppm.
Ambient Pressure
Max. 20 bar ~ 290 psi.
It is generally not recommended to install the motor for
operation in a vacuum.
MS Motors
Cooling
Cooling of the motor depends on temperature and
velocity of flow of the pumped liquid past the motor. In
order to ensure sufficient cooling, the values for max.
temperature of the pumped liquid and its velocity of flow
past the motor stated in the table to the right must be
kept.
Note: The temperature limits are based on the condition that the other operating conditions are as specified
in this Product Guide.
In case the actual temperature of the pumped liquid is
higher than the one stated in the table, or if the operating conditions are especially unfavourable, please
contact Grundfos.
Free Convection
Free convection is achieved when the diameter of the
borehole is at least 2" (~ 50 mm) bigger than the outer
diameter of the motor, or if the motor is installed in the
borehole screen.
Velocity of Flow Past
the Motor
0.0 f/s
(Free Convection)
Min. 0.25 f/s
Fig. 2 Free Convection
Max. Temperature of Pumped Liquid
Vertical
Installation
30°C
(86°F)
40°C
(104°F)
Horizontal
Installation
Flow sleeve
recommended
40°C
(105°F)
ø95
ø145
TM00 5122 5094TM00 5123 5094
Fig. 3 Flow of Pumped Liquid past the Motor
11
Page 12
Operating Conditions
MS 4000
Pumped Liquids
The MS 4000 motors are available in several versions
to enable use in various liquids.
• MS 4000 is generally recommended for use in water
without chloride.
MS 4000 is made of 304 stainless steel AISI
• MS 4000 R is recommended for use in aggressive
liquids.
MS 4000 R is made of 904L stainless steel AISI
• MS 4000 RE is recommended for use in aggressive
and slightly contaminated liquids.
MS 4000 RE is made of 904L stainless steel AISI,
and the original rubber parts have been
replaced with FKM.
In cases of doubt, please make an analysis of the liquid
and contact Grundfos.
MS Motors
Sand Content
Max. sand content in pumped liquid: 50 ppm.
Ambient Pressure
Max. 60 bar ~ 870 psi.
It is generally not recommended to install the motor for
operation in a vacuum.
Cooling
Cooling of the motor depends on temperature and
velocity of flow of the pumped liquid past the motor. In
order to ensure sufficient cooling, the values for max.
temperature of the pumped liquid and its velocity of flow
past the motor stated in the table to the right must be
kept.
It is recommended to always install the motor in the
borehole screen.
Note: The temperature limits are based on the condition that the other operating conditions are as specified
in this Product Guide.
In case the actual temperature of the pumped liquid is
higher than the one stated in the table, or if the operating conditions are especially unfavourable, please
contact Grundfos.
Free Convection
Free convection is achieved when the diameter of the
borehole is at least 2" (~ 50 mm) bigger than the outer
diameter of the motor, or if the motor is installed in the
borehole screen.
Velocity of Flow Past
the Motor
0.0 f/s
(Free Convection)
Min. 0.25 f/s
Fig. 4 Free Convection
Max. Temperature of Pumped Liquid
Vertical
Installation
30°C
(86°F)
40°C
(104°F)
motor
D
D
borehole
Horizontal
Installation
Flow sleeve
recommended
40°C
(105°F)
TM00 5688 1395
12
Page 13
Operating Conditions
MS 6000
Pumped Liquids
The MS 6000 motors are available in several versions
to enable use in various liquids.
• MS 6000 is generally recommended for use in
common groundwater.
MS 6000 is made of 304 stainless steel AISI.
• MS 6000 R is recommended for use in aggressive
liquids.
MS 6000 R is made of 904L stainless steel AISI.
• MS 6000 RE is recommended for use in aggressive
and slightly contaminated liquids.
MS 4000 RE is made of 904 stainless steel AISI,
and the rubber parts are made of FKM.
In cases of doubt, please make an analysis of the liquid
and contact Grundfos.
Sand Content
Max. sand content in pumped liquid: 50 ppm.
MS Motors
Ambient Pressure
Max. 60 bar ~ 870 psi.
It is generally not recommendable to install the motor
for operation in a vacuum.
If this cannot be avoided, please contact Grundfos for
guidance.
Cooling
Cooling of the motor depends on temperature and
velocity of flow of the pumped liquid past the motor. In
order to ensure sufficient cooling, the values for max.
temperature of the pumped liquid and its velocity of flow
past the motor stated in the table to the right must be
kept.
Free Convection
Free convection is achieved when the diameter of the
borehole is at least 2" (~ 50 mm) bigger than the outer
diameter of the motor.
Velocity of Flow Past
the Motor
0.0 f/s
(Free Convection)
Min. 0.25 f/s
Max. Temperature of Pumped Liquid
Vertical
Installation
30°C
(86°F)
40°C
(104°F)
motor
D
Horizontal
Installation
Flow sleeve
recommended
40°C
(105°F)
Fig. 5 Free Convection
D
borehole
TM00 5688 1395
13
Page 14
Construction
MS Motors
Material specification for MS 402
Standard Version
Pos. ComponentMaterialAISI
1aPlugPlastics, PELD
2ShaftStainless steel431
2aStop ring (upthrust)Polyethylene, PP
5cHousing for radial bearingSilumin
Radial bearing,
5b
stationary
6Bearing journalTungsten carbide
7Filling compoundPolyurethane
8Stator sleevePlastics, PET
9Stator windingCopper wire
10Stator housingStainless steel403
Radial bearing,
11
stationary
12Bearing journalTungsten carbide
13Intermediate ringSintered steel
Thrust bearing ring,
14
rotating
Thrust bearing shoes.
15
stationary
16Rotor laminationMagnetic sheet steel
17Stator laminationMagnetic sheet steel
21NutStainless steel304
22StayboltStainless steel304
25Cover plateStainless steel304
25a ScrewStainless steel304
27Sand shieldNBR rubber
32Bellows sealNBR rubber
32a Lock ringComposite PPS
50,
ScrewStainless steel304
74
Rotor rods
Motor liquidSML-2
Ceramic
Ceramic
Ceramic
Carbon
Cast aluminium or copper
Example: MS 402
25
32
25a
5b
6
•
•
•••
••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•••••
••••••••••••••
••••••
2b
9
8
•••••••••••••••
•••••
••••••••••••••
••••••
•••••••••••••••
•
•••••
••••••••••••
•
••••••
••••••••••••
•
•••••
••••••••••••
•
••••••
••••••••••••
•
•••••
••••••••••••
•
••••••
••••••••••••
•
•••••
••••••••••••
•
•
•
•••••
•
•
••
•
•
••
•
•
•
•
•
••
•
•
•
•
•
••
•
•
•
•
•
••
•
•
•
•
•
••
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•••
•
•
•
••••
•
•
•
•••••
•
•
••••••
•
•
•
•••••••
•
•
•••••••
•
•
•
••••••••
•
•
••••••••
•
•
•
•••••••••
•
•
••••••••
•
•
•
•••••••••
•
•
••••••••
•
••
•
••••••••
•
•
••••••••
•
••
•
••••••••
•
•
•••••••
•
••
•
•••••••
•
•
10
16
17
•••••••
•
•
•••••••
••
•
••••••••
•
•
••••••••
••
•
••••••••
•
•
••••••••
••
8
14
15
13
•
•••••••••
•
••••••••
•
••••••••
•
••••••••
•
••••••••
•
•••••••
•
•••••••
•
••••••
•
•••••
•
••••
•
•••
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•••••••••••••••••••••••
•••••••••••••••••••••••
•••••••••••••••••••••••
•••••••••••••••••••••••
•••••••••••••••••••••••
•••••••••••••••••••••••
•••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••
•••••••••••••••••
••••••••••••••••••
•••••••••••••••••
••••••••••••••••••
•••••••••••••••••
••••••••••••••••••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•••••
••
•
50
•••
•••
•••
•••••
••••
••••
••••
••••
•••
••••
•••
••••
•••
•••
•••
•••
•••
•••
••
••••
•••••
••••••
•••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
••••••••
•••••••
••••••
•••••
••••
••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••
••••••••••••••••••••••••••
••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
••••••••••••••••••••••••••
•••••••••••••••••••••••••••
2a
27
21
1a
22
32a
•
•
•
••
•••
••
5a
•
••
•••
•••
•••
•••
••
•••
••
••
••
••
••
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
•
••
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
•
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••
•
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••
••••
••••
•••
••
7
14
11
74
12
TM00 4736 4094
Page 15
Construction
MS Motors
Material specification for MS 4000
Standard Version
Pos. ComponentMaterialAISI
1StatorStainless steel304
2RotorStainless steel431
3Thrust bearing, (stationary)Carbon
4Radial bearing, completeCeramic
5Bearing pipe, completeCast iron GG20
6Thrust bearing, (rotating)Ceramic
7Clamping ring
10Bearing retainer
11Adjusting screw
12DiaphragmNBR rubber
13Motor end shieldStainless steel304
15Nut (special)
16Lock washer
18/
NutStainless steel316
21
20Motor cable
22StayboltStainless steel316
22a Staybolt completeStainless steel316
24O-ring
25Shaft seal housingStainless steel304
27Spline protectorNBR rubber
28Supporting ring for 27
29Sand shieldNBR rubber
30Spring
31Supporting ring
32Seal ring, upper (stationary)
33O-ring
34Seal ring, lower (rotating)Tungsten carbide
70Motor liquidSML-2
NBR rubber
Tungsten carbide
Example: MS 4000
22a
22
21
24
5
2
1
4
6
3
R-Version
Pos. ComponentMaterialAISI
1StatorStainless steel904L
13Motor end shieldStainless steel904L
18/
NutStainless steel904L
21
22StayboltStainless steel904L
22a Staybolt completeStainless steel
25Shaft seal housingStainless steel904L
RE-Version
Pos. ComponentMaterialAISI
12DiaphragmFKM
27Spline protectorFKM
29Sand shieldFKM
32Seal ring upper, (stationary) FKM ceramic
34Seal ring lower, (rotating)
FKM
ceramic
904L
316
11
10
7
15
12
13
16
18
TM00 5068 4994
15
Page 16
Construction
MS Motors
Material specification for MS 6000
Standard Version
Pos. ComponentMaterialAISI
1StatorStainless steel304
2Rotor
2aStop ringPTFE
3Thrust bearing, (stationary)Carbon
4Radial bearing, lower
5Radial bearing, upper
6Thrust bearing (rotating)
7Clamping flangeSteel
10Thrust coverSteel
11Adjusting screwSteel
12DiaphragmNBR rubber
13Motor end shieldStainless steel304
22BoltStainless steel904L
22a Priming screwStainless steel316
27Sand shieldNBR rubber
28Retaining boltsStainless steel
29Shaft seal housingStainless steel304
30SpringStainless steel
Seal ring complete
32
(stationary)
33O-ring
Seal ring complete
34
(rotating)
42Stop for bearing Steel
46Hex socket screwStainless steel304
46a WasherNyltite
47ScrewSteel
49Retaining springSteel
50Screw for motor cableStainless steel304
70Motor liquidSML-2
R-Version
Pos. ComponentMaterialAISI
1StatorStainless steel904L
13Motor end shieldStainless steel904L
22BoltStainless steel904L
22a Priming screwStainless steel904L
46Hex socket screwStainless steel904L
50Screw for motor cableStainless steel904L
RE-Version
Pos. ComponentMaterialAISI
12DiaphargmFKM
27Sand shieldFKM
Seal ring complete
32
(stationary)
Ceramic/tungsten
carbide
Ceramic/tungsten
carbide
NBR
Ceramic
Tungsten carbide
FKM
Ceramic
Example: MS 6000
30
32
34
50
33
5
2a
2
1
42
11
10
7
12
27
22
29
22a
28
4
6
3
49
46a
46
47
13
TM03 0536 0205
16
Page 17
Selection
MS Motors
Motor Operation
Most deep well submersible type pumps are powered
by electric motors. The optimum power unit used is
dependent on several physical and environmental
factors, which include the horsepower required for
pumping, the annual hours of operation and the availability and cost of energy.
How does a motor "know" what horsepower to deliver?
Electric motors draw power in proportion to the applied
load. Although a motor is rated for a certain output
power (this is the number stamped on the nameplate),
that motor can deliver a wide range of power depending
on the voltage and frequency provided and the torque
demanded by the shaft load.
Power is the rate of energy use. Input power to a electrical motor is measured in kW, the motor converts that
electric power into mechanical power.
Output power is the product of speed (rpm) and torque
(ft.-lb.). For a given voltage and frequency combination,
the motor will always operate at a point on a specific
torque vs. speed curve.
The units of both output power and torque are generally
specified as a percentage of the motors full load rated
value on the manufactures performance curve.
A small change in speed produce large changes in
available torque near the normal (close to rated) operating speed.
Thus as load torque increases, the rotational speed will
drop slightly (increased slip) as the motor load
increases.
As soon as voltage is supplied to the motor, the motor
“knows” the power to deliver by speeding up until it puts
out exactly the same torque as the load requires at that
speed.
At start-up, the motor produces torque higher than the
torque required by the driven load, accelerating the
pump shaft to full load speed.
A submersible pump is a centrifugal device which
exhibits variable torque load characteristics, it takes
very little torque to accelerate the load at low speed.
A centrifugal pump requires torque approximately
proportional to the square of its speed. The maximum
speed of a induction motor is a function of the number
of poles and line frequency.
Typical speeds associated with submersible motors,
based on the number of poles and a line frequency of
60 Hz are; 2p - 3600 rpm (sync.)/ 3450 rpm (@ full load)
and 4p - 1800 rpm (sync.)/ 1760 (@ full load).
The synchronous speed on any motor can be calculated when the number of poles and operating
frequency is known, using the formula below:
N = f x 120/P where; N = sync. speed (rpm), P = poles, f = frequency (Hz)
Note: Actual induction motor speed at full load will be
2-5% less than the synchronous speed calculated using
the formula above.
A pump driven by two different motors of the same
nominal speed (rpm), but different Hp ratings, will draw
approximately the same power.
Under steady-state conditions the speed of operation
does not change significantly, unless the motor is too
small and stalls.
Motor Loading, Failure
and Lifetime
Motor load is commonly expressed as the percentage
of output power to rated output. Because output power
(load) is difficult to measure in the field, motor load is
usually estimated by measuring input power (kWI) and
assuming an efficiency.
It can also be estimated by measuring kVA and
assuming both power factor and efficiency. Failure of a
motor occurs when insulation breaks down from heat
and mechanical stresses.
The temperature of the windings are primarily dependent on the current (amps) draw through them and the
ability of motor to dissipate the heat generated to the
ambient environment. The higher the temperature, the
shorter the life. A 10°C(50F) rise can halve motor life.
Motor current draw increases with load; as a result,
motors that operate outside established load and
temperature ratings, will operate fewer hours before
failure.
The voltage supplied to the motor terminals have a
significant impact on motor life.
Motors are designed to operate at a utilization voltage
level or range, which is generally lower than the electrical system distribution voltage provided to the utility
meter. Motors can operate within a range of voltages;
but above a certain voltage, destructive arcing and
insulation deterioration can occur.
Conversely, as voltage drops, more current is needed
to maintain torque and power; so the motor runs hotter
and its life is shortened.
In addition to the overall voltage provided to the motor,
voltage unbalance must be considered. If the voltages
on the three phases to the motor are not well balanced,
one winding will carry more current and may over heat
and fail.
17
Page 18
Selection
MS Motors
Most electrical utilities guarantees voltages to a +/-5
percent standard; for "480" service voltage will be
between 456 V and 504 V at the meter; for "240"
service, the voltages must be between 228 V and
252 V.
If a motor is damaged as a result of over or under
voltage outside the service limits, the utility may be
liable for damages.
Because motors will operate cooler with higher voltages, reasonable over voltage levels rarely causes
problems. There are only small variations in power
factor and efficiency near rated conditions, volt- amps
for a particular load can be assumed constant over the
range of voltage guarantee by the utility.
The maximum continuous load sustained by a motor is
indicated by the service factor. A motor with a service
factor of 1.15 can maintain a 115% overload; provided
voltages are at the rated level and well balanced and
the insulation system can be maintained at or below
rated temperature. The actual motor load percentage
can be calculated using the formula listed below:
EM IHp×
% Motor Load
where; Em = motor efficiency
IHp = Input Horsepower
Motor design and economic criteria have forced motor
manufactures to build less service factor (SF) into
motors.
The SF allows the motor to provide power under
optimal conditions at the nameplate rated power times
the SF. At rated conditions, (ie. 100 Hp motor with a SF
of 1.15 is designed to provide 115 HP under continuos
load).
A 1982 survey of motor manufacturers showed six of
seven respondents recommending loading at 100
percent of rated power or less while only one still
suggests loading up to SF rating.
For this reason, it is recommended that motor loading
not exceed 100% of the nameplate horsepower rating.
It is best to consider the SF as a contingency against
over loading as a result of low voltage, current imbalance and/or adverse ambient conditions.
------------------------- -
Rated HP
100×=
Motor Efficiency
An electric motor operates at a relatively constant efficiency and speed over a wide range of loadings.
Efficiency does not change significantly with age of the
motor or the load applied to it.
Motor efficiency is practically constant at motor loads
between 50 and 100%.
Reducing motor size for the sake of energy conservation, as a result of efficiency increases associated with
loading the motor closer to full magnetic saturation
(100% load) is not recommended.
As a general rule, a bigger motor that is underloaded
(down to 50 percent) is more efficient than a fully
loaded smaller motor driving the same load. Submersible pump motors will have slightly lower efficiencies
than surface motor as a result of the compact design
requirements and the need for internal cooling/lubricating fluid.
Most submersible motors have an efficiency stamped
on the nameplate. The average or nominal efficiency
values associated with "canned/ hermetically sealed"
type submersible motors are listed in the Electrical Data
Section.
18
Page 19
Selection
MS Motors
Application and Selection Issues
The term application not only refers to the end use of
the product but also the parameters which affect the
selection of the correct submersible motor and pump
products. The primary considerations involved with the
selection of submersible motors are discussed as
follows:
• The Insulation System. The insulation system is
the key to long motor life. The life of the insulation
system is affected by three major factors: Load,
Duty Cycle, and Temperature Rise. The load of a
motor is described in horsepower or kilowatts and is
defined as the work required to perform a function.
The load created by pumps is a result of the rotation
of impeller(s) to create a pressure forcing fluid
through a system. The duty cycle is the time period,
which the motor is operating. It is continuous or intermittent. Temperature rise is the difference between the operating temperature of the windings
and the temperature of the medium to cool the motor. The rise of the motor is directly affected by the
load and duty cycle. Extra load in the form of a service factor increases the temperature rise of the
winding.
The total temperature must never exceed the maximum
capacity of the insulation system. Submersible motors
used for water well service normally employ class “F”
insulation (150°F rise), but are designed for a class A
temperature rise (60°F).
• Cooling. Submersible motors are no different than
conventional motors, in that the heat generated
within the motor must be dissipated. The temperature rise within the motor is limited to a value which
when added to the temperature of the external cooling medium does not exceed the maximum temperature capacity of the insulation system. The ability
to dissipate the heat depends on two factors: (1)
The temperature of the cooling medium (ambient)
and (2) the rate of cooling medium flow past the motor external surfaces. Excess ambient temperature
and reduced flow rate both require derating of the
load capability of the unit. The derating of the load
reduces the temperature rise of the winding within
the limits set by the heat dissipation capacity of the
cooling medium.
• Materials of Construction. Submersible pumps
and motors are also selected based on the chemical
and physical make-up of the water in which they will
be submerged. Sea water applications require specialized construction due to the corrosive water encountered. A standard motor will not survive highly
corrosive water submergence, while a specially designed motor will.
• Design Factors. Other factors, which affect sub-
mersible motor selection, are voltage, depth of installation, thrust and controls. It is necessary that
the voltage and frequency variations be within the
limits set in NEMA MGI-18 (submersible motors for
deep well pumps). The maximum recommended
depth for most submersible motors relates to 290
psi on the unit (approx. 2000 feet). The thrust delivered by the pump must be less than the capacity of
the thrust bearing of the submersible motor. Controls must be quick trip, ambient compensated type
to quickly pull an improperly applied or defective
motor off the line so that no damage occurs.
Submersible construction and design for 4"and 6" sizes
are covered by NEMA standards.
19
Page 20
Mechanical Installation
MS Motors
Submersible Motor Cooling
The key to long submersible motor life is good cooling.
Most submersible pumps rely on moving heat away
from the motor by forced convection. The ambient/
produced fluid is typically drawn by the motor in the
course of pumping to accomplish this task. Grundfos
Submersible Motors are designed to operate at full load
in water up to 30°C (86°F) free convection, and 40C
(104F) provided the flow velocity can be maintained at
a minimum of 0.25 feet per second (fps).
Required Cooling Flow
and Velocity
AWWA specifications state the maximum motor diameter and the minimum inside diameter of the well shall
be in such relationship that under any operating condition the water velocity past the motor shall not exceed
12 fps (3.7 m/s) nor be less than 0.5 fps (0.15 m/s). The
AWWA specifications are principally applicable to
motors 6-inch and larger, as most 4-inch motor designs
are based on a minimum cooling flow velocity of 0.25
fps (0.08 m/s) at rated ambient temperature. Table 1
relates flow, casing and motor size requirements to
accomplish minimum cooling velocity.
Note: At the velocity specified in the table the temperature differential
between the motor surface and ambient water will range from 5° - 15°C
(10-30°F).
Grundfos Submersible Motors require no cooling fluid
flow past the motor, when the produced fluid temperature is 30°C (86°F) or less. Cooling by free convection
in such cases, is contingent on no adverse operating
conditions present such as; poor power, high stop/start
frequency, presence of incrustating deposits on the
motor surface, etc. Detramental operating conditions
are difficult to identify or predict, and for this reason, the
minimum cooling flow should be provided whenever
possible - regardless of the ambient fluid temperature.
4" Motor
(0.25 fps)
6" Motor
(0.5 fps)
Water Temperature and Motor
Derating
As previously stated, the full motor capacity is a function of ambient fluid temperature and flow past the
motor.
When the ambient temperature exceeds the temperature at which the motor performance is based, the
motor must be derated and/or cooling velocity
increased. Table 2 provides typical derating criteria for
hermetically sealed/canned type submersible motors.
Such motors should not be used in applications which
exceed 60°C (140°F) regardless of any special provisions incorporated into the system. AWWA specifications state that the motor temperature shall not exceed
the allowable operating temperature of the motor thrust
and radial bearings, and in no case shall it exceed the
temperature rating of the motor insulation system.
When the service duty exceeds 40°C (104°F) pumps
and motors fitted with NBR rubber components are
subject to reduced life if not replaced on a regular basis.
A minimum replacement interval of three years is
recommended.
FKM elastomers (rubber compounds) are recommended any time the normal ambient fluid temperature
exceeds 104°F. Allowable % Max. Namplate Amps
Derated for Ambient Water Temp. @ .5 fps
(Table 2) Allowable % Max Nameplate Amps
Derated. for Ambient Water Temp at .50fps.
Water Temp.0 - 3 Hp5 - 15 Hp20 - 40 Hp
30°C (86°F)100%100%100%
35°C (95°F)100%100%90%
40°C (104°F)100%90%80%
45°C (113°F)90%80%70%
50°C (122°F)80%70%60%
55°C (130°F)70%60%45%
60°C (140°F)50%--
Note: Derating % is based on an ambient fluid temperature of 30°C
(86°F) @ 0.5 fps, consult motor manufacture for specific maximum fullload cooling water temperature without derating. Typical base abient fluid
temperature rating for various manufactures of submersible motors used
in the water supply industry range from 25°C to 40°C, with 30°C being
the most prominent.
20
Page 21
Mechanical Installation
MS Motors
Shroud/Flow Inducer Sleeve/
Cooling Sleeve
On some installations it is necessary to use a shroud to
insure that all, or some portion of the produced fluid
pass by the motor in order to carry away the heat generated.
In some cases, the shroud is used to increase velocity
(create turbulent flow) in order to prevent the formation
of deposit and inhibit corrosion.
A shroudshould be used/ considered under the
following operating scenarios:
1. Top-feeding (cascading) wells can feed the water directly into the pump without its flowing past the motor if the well is not cased to below the motor, or
casing is perforated above the motor.
2. Flow may be inadequate when the motor is in a
large body of water or a casing much larger than the
motor, or if delivery is very low, or in sump/wet pit
tank applications.
3. If the groundwater is aggressive or contains
chloride, the corrosion rate will double for every
15°C (56F) increase in temperature between the
motor metallic housing and water. The motor housing is generally 5-15°C (41-56F)warmer than the
produced water. A cooling sleeve will therefore reduce the risk of motor corrosion by keeping the exterior motor surface temperature lower during
operation.
4. If the well water contains a significant amount of
iron (iron bacteria), manganese and calcium. These
substances will be oxidized and deposited on the
motor surface. In case of low flow past the motor,
incrustation build-up forms a heat insulating layer of
oxidized minerals, which may result in hot spots in
the motor winding insulation. This temperature increase may reach values, that impare the insulating
system, and consequently the motor life.
A cooling sleeve will insure turbulent flow past the
motor prohibiting incrustation build-up and optimize
cooling.
A cooling sleeve/shroud should be selected so as to
keep the maximum fluid velocity past the motor to 15
fps (12 fps by AWWA specs.).
At the higher velocities, erosion can be significantly
accelerated in the presence of abrasives and increase
intake losses can impare pump performance.
Head loss for various motor O.D. and casing/shroud
I.D. combinations are listed in Table 3, and should be
considered under marginal submergence and suction
conditions.
A fluid velocity of 3 fps is generally considered optimum
and 0.5 fps is the minimum cooling velocity value.
The actual fluid velocity past the motor can be calculated using the formula:
Velocity (past motor) = gpm/2.45 (ID casting)2 - (OD motor)2.
where; Casing or shroud ID and motor OD values are in
inches, and velocity(past the motor is in fps.
(Table 3) Annular Space Head Loss (Hf) from Flow
Past Motor (ft. of Water)
Motor
(nominal)
Casing I.D.4.25"5"6"6"7"8"
1004.70.31.7
15010.20.60.23.7
2001.10.46.30.5
gpm
2501.80.79.60.8
3002.51.013.61.20.2
40023.72.00.4
5003.10.7
6004.41.0
Note: The tabulated friction loss values assume maximum motor length
for the specified nominal motor size and a smooth casing/sleeve ID, and
include entry and exit losses.
4"4"4"6"6"6"
250.3
501.2
Typical cooling sleeve/shroud configurations. The
motor shroud is generally of the next nominal diameter
of standard pipe larger than the motor or the pump,
depending on the shroud configuration used. The
tubular/pipe material can be plastic or thin walled steel
(corrosion resistant materials preferred). The cap/top
must accommodate power cable without damage and
provide a snug fit, so that only a very small amount of
fluid can be pulled through the top of the shroud. The fit
should not be completely water tight as ventilation is
often required to allow escape of the air or gas that
might accumulate. The shroud body should be stabilized to prevent rotation and maintain the motor
centered within the shroud. The shroud length should
extend to a length of 1-2 times the shroud diameter
beyond the bottom of the motor when possible.
Shrouds are typically attached immediately above the
pump intake or at the pump/column correction.
A typical motor sleeve/shroud selection example is
sited below and illustrated in Figure 5:
21
Page 22
Mechanical Installation
Example 1:
A six-inch motor and pump that delivers 60 gpm will be
installed in a 10” well, 90 gpm past the motor is required
assuming 10” ID well (from Table 1). An 8” or smaller
sleeve must be added to the pump to provide a cooling
flow velocity of 0.5 fps or greater.
Typical Motor Jacket Installation Scenarios
Typical Flow Inducer Sleeve Cutaway View
MS Motors
If a well feeds water from above the pump, has a
casing/chamber too small to allow a motor jacket/
sleeve on the pump, and does not have adequate level
and flow to allow raising the pump above the inflow, it
is difficult to properly cool the motor. When possible,
the casing depth should be increased to allow flow to
come from below the motor. If this is not practical,
adequate flow past the motor can usually be attained by
employing a motor jacket with a stringer pipe or by
using a jet tube as shown in Figure 6.
Fig. 6 Motor Jacket Installation
The table shows the recommended number of starts of intermittent operation:
Special (Non Water Well) Applications
A cooling shroud should be used in all static horizontal
and vertical installations where water can directly enter
the pump intake, without crossing the motor surface. In
addition to focusing the pumped fluid to dissipate motor
heat, a motor shroud can be used to improve suction
conditions by reducing vortices. Such applications
include fountains and pump-out tanks, where the
ambient fluid temperature is often higher than groundwater temperatures.
22
In such installations; motor submergence-temperature
considerations, as well as pump intake requirement
must be carefully considered.
Intermittent Operation
Motor typeRecommended number of starts
MS 402 - 4"Min. 1 pr. year
MS 4000 - 4"Max. 100 pr. hour
MS 6000 - 6"Max. 300 pr. day
A typical horizontal pump out tank application is illustrated in Figure 7. Vertical application should be
handled as illustrated in Figure 8, which is analogues to
top feeding water well application.
Page 23
Mechanical Installation
Cooling Sleeve - Horizontally Installed Motor in a
Tank
Water level
Min. 1.5 ft
W/O Cooling Shroud
Baffle Plate
MS Motors
Cooling Sleeve - Vertically Insulated Motor in Tank
Seen from above
Water level
Baffle Plate
Min. 1.5 ft
W Cooling Shroud
Fig. 7 Horizontal Installation
Vortex
TM03 0561 0205
Fig. 8 Vert ical Flow
Cross section
Vortex
TM03 0559 0205 - TM03 0560 0205
23
Page 24
Electrical Installation
MS Motors
Submersible Power Cable
Power is transmitted from the starter/controller to the
submersible motor through a marine duty power cable,
typically consisting of three flexible stranded conductors of the proper size to carry the motor full load
amperes (FLA) at its rated voltage. AWWA standards
require a separate ground wire to be provided (ie. 3wire cable systems are equipped with three power
conductors and a ground wire of the same size).
Proper cable selection is a function of motor load,
voltage, available space, length (setting depth) and
environment.
(Table 4) Typical Submersible Power Cable Physical Data
600 Volt (115, 208, 230, 460 and 575 Volt Motors)5000 Volt (2300 Volt Motors)
Type IType IIType IIIType IV
3 Conductors and ground in a
Common Jacket (4 wire total)
Cable Size
3 Conductors and ground in Sep-
arate Jackets (4 wire total)
Typical conductor insulation materials are synthetic
rubber (RW, RUW, TW, etc.), plastic (PVC, XPLE, etc.)
or special polymer (FPE, hypalin, EPR - EPDM, etc.).
Special cable insulations are often recommended or
required for sever duty or special applications such as;
gas, hydro - carbon, heat, variable frequency, etc.
Cable can be provided as three or more separate individual or, twisted conductors, molded side by side in a
flat cable configuration or three conductors with a round
common jacket. Refer to Table 4 for general submersible power cable physical data (weight and diameter).
Armored cable is also available for special applications,
but is typically not employed in the water supply
industry. Cable is supported and attached to column/
drop pipe by means of cable clamps, tape or bands.
One extra foot of cable for each fifty feet of length
should be allowed plus an additional ten to fifty feet for
surface connections.
3 Conductors in a Common
Jacket (3 wire total)
3 Conductors in Separate
Jackets (3 wire total)
AWG
MCM
14.39.16.19.10
12.43.20.21.13
10.64.32.27.18
8.76.44.31.291.02.69.39.43
6.91.65.36.431.10.85.43.52
41.02.90.42.641.211.12.47.71
21.151.26.48.971.331.46.53.99
11.341.68.581.26----
01.432.0.621.541.512.09.621.49
001.532.41.671.911.612.56.661.87
0001.642.89.722.36----
00001.803.58.782.931.823.40--
2501.975.88.904.82----
3002.096.60.955.62----
3502.207.341.006.502.514.8--
4002.348.181.057.25----
5002.259.301.138.87----
1. Types I and II cables are typically insulated and jacketed with synthetic rubber, PVC or XLPE.
2. Types II and IV are often supplied paralleled in a flat cable configuration, or in a twisted configuration for smaller sizes.
Type I and II cable include 3 power conductors and a ground conductor.
3. AWWA minimum stranding and insulation requirements; No. 10 and smaller - 7 strand/ Class B, No. 9 through No. 2 - 19 strand/ Class C, No. 1
through 4/0 - 19 strand/ Class B. Minimum conductor area to meet minimum ICEA (Insulated Cable Engineers Association) code for operation in free air.
4. Verity actual cable weight per foot with manufacture for greater accuracy, as weight and diameter will very with insulation system and manufacture.
O.D. (in)Wt. (lbs./ft.)
O.D. (in)
per Cable
Wt. (lbs./ft.)
for 4 Cables
O.D. (in)Wt. (lbs./ft.)
O.D. (in)
per Cable
Wt. (lbs./ft.)
for 3 Cables
24
Page 25
Electrical Installation
MS Motors
Cable Selection
Maximum cable lengths are generally calculated to
maintain 95% of service entrance voltage at the motor
running at maximum nameplate amps, and to maintain
adequate starting torque. Calculations take into
account basic cable resistance, reactance, power
factor and temperature rise cable larger than specified
may always be used, and will reduce power consumption. The wire sizing chart in the Electrical Data section
tabulates copper cable sizes for various cable lengths
vs motor size. The use of power cables smaller than the
minimum sizes as permitted by code or recommended
by Grundfos will generally void the motor warranty.
Understized cable sizes will cause reduced starting
torque and poor motor operation.
Mixed Cable
In a submersible pump installation any combination of
cables sizes may be used provided they do not exceed
the individual maximum conductor ampacity limit and
the aggregate voltage drop does not exceed 5% of the
motor nameplate voltage while operating at full load.
Mixed cable sizes are most often encountered when a
pump is being replaced with a larger horsepower unit.
Cable Splice
When the downhole power cable (drop cable) must be
spliced or connected to the motor leads, it is necessary
that the splice be water tight. Under normal service
conditions, the splice can be made using commercially
available potting compounds, heat shrink or tape. Each
type of splicing methods is affective when made by
competent personnel, potted or head shrink splices are
recommended when submergence pressures exceeds
25 psi (60’). A cable splice should exhibit a minimum
insulation resistance of 10 megohms, measured in a
submerged state after 24 hours in water. A typical low
voltage (< 600V) tape splice is illustrated below in
Figure 9.
When three conductors are encased in a single outer
shealth, tape individual conductors as described, staggering joints. Total thickness of tape should be no less
than the thickness of the conductor insulation.
Motor Lead
Most manufactures will provide a factory motor lead
assembly, pre-potted and designed to provide a water
tight connection between it and the motor terminals.
Typical motor lead length range from 48" to 150" and
are generally spliced to the drop cable immediately
above the pump. Minimum wire sizes (AWG) for factory
provided motor lead assemblies, by nominal motor size
are; 4" - #14 to #12, 6" - #10 to #8, 8" - #4 and 10" - #2.
In general, a motor lead assembly should not be reused
as rubber compounds typically used in there construction will set with time, making a water tight connection
difficult. Grundfos installation instructions, which
includes pot head connecting torque values and lubrication requirements, should be strictly observed.
STAKED CONNECTOR
2"
2"
Fig. 9 Tape Splice
2"
RUBBER TAPE
PVC ELECTRICAL TAPE
2"
TM03 0564 0205
25
Page 26
Technical Data
Outline Drawing MS 402
3.74
MS Motors
3.0
1.48
.14
3.43
.90
A
1.50 +.005/-.003
Dimensions and Weights MS 402
Output
Standard motors
[HP]P2 [kW]
P
2
.33.2516010.214.917.4.0953
.50.3716011.014.917.4.1017
.75.55150/6011.618.019.8.1062
1.0.75150/6012.219.622.9.1112
1.51.1150/6013.723.126.4.1239
2.01.5150/6013.724.227.6.1239
.50.37350/609.012.114.3.0858
.75.55350/609.613.816.1.0904
1.0.75350/6011.018.019.4.1017
1.51.1350/6012.219.622.9.1112
2.01.5350/6013.723.126.4.1239
3.02.2350/6013.724.229.5.1239
Phases
Frequency
[Hz]
A-Dimension
[in]
Net Weight
[lbs]
Gross Weight
[lbs]
Shipping
Vol ume
3
]
[f
TM03 0645 0405
26
Page 27
Technical Data
Outline Drawing MS 4000
3.74
MS Motors
3.0
1.57
3.43
.866
A
1.50 +.005/-.003
Dimensions and Weights MS 4000
Output
Standard motors
[HP]P2 [kW]
P
2
21.5150/6019.537.239.5.4415
32.2150/6022.644.347.5.4415
53.7150/6026.656.258.5.4415
3.02.2350/6018.035.237.5.4415
5.03.7350/6022.746.248.5.4415
7.55.5350/6026.657.359.5.4415
107.5350/6030.668.370.5.4415
Phases
Frequency
[Hz]
A-Dimension
[in]
Net Weight
[lbs]
Gross Weight
[lbs]
Shipping
Vol ume
3
]
[f
TM03 0646 0405
27
Page 28
Technical Data
Outline Drawing MS 6000
5.43
MS Motors
4.37
A
2.87 +0.0/-.15
Dimensions and Weights MS 6000
Output
Standard motors
[HP]P2 kWp]
P
2
7.55.5350/6021.473.880.41.412
107.5350/6022.681.588.21.412
1511.0350/6025.0100.3109.11.871
2015.0350/6027.5115.7124.51.871
2518.5350/6029.7127.8136.61.871
3022.0350/6032.0141.0149.91.871
4030.0350/6037.2170.8179.61.871
Phases
Frequency
[Hz]
A-Dimension
[in]
Net Weight
[lbs]
Gross Weight
[klbs]
Shipping
Vol ume
3
]
[f
TM03 0644 0405
28
Page 29
Electrical Data
MS Motors
Grundfos Motors Specifications
1- Phase Motors
HPPhVolt
4-Inch, Single Phase, 2-Wire Motors (control box not required)
1/312304.625.759779006.8-8.2S79952101
1/2111512.05562769001.1-1.3R79922102
1/212306.034.562769005.2-6.3R79952102
3/412308.440.562759003.2-3.8N79952103
112309.848.463829002.5-3.1M79952104
1 1/2123013.16264859001.9-2.3L79952105
4-Inch, Single Phase, 3-Wire Motors
1/311159.02959779001.55-1.92.4-3M79423101
1/312304.61459779006.8-8.317.3-21.1L79453101
1/2111512.042.561769000.9-1.11.9-2.35L79423102
1/212306.021.562769004.7-5.715.8-19.6L79453102
3/412308.431.462759003.2-3.914-17.2L79453103
112309.83763829002.6-3.110.3-12.5K79453104
1.5123011.645.969899001.9-2.37.8-9.6H79453105
2123013.257728615001.5-1.83.4-4.1G79454506
3123017.077749315001.2-1.42.45-3F79454507
5123027.5110779215000.65-0.852.1-2.6F79454509
AmperageFull Load
MaxStartEff. (%)Pwr Fact.Blk-YelRed-Yel
Max.
Thrust
(lbs)
Line-to-Line
Resistance (Ω)
KVA Code
Nameplate
No.
3-Phase Motors
HPPhVolt
4-Inch, Three Phase, 3-Wire Motors
2307.340.375729003.9K79302005
1 1/23
23
33
53
7 1/23
103
4603.720.1757290015.9K79362005
5752.916.1757290025.2K79392005
2308.74876759003.0J79302006
4604.424767590012.1J79362006
5753.519.2767590018.8J79392006
23012.25677759002.2H79302006
4606.12877759009.0H79362007
5754.822777590013.0H79395507
23019.8108808215001.2H79304509
4609.954808215005.0H79354509
5757.954808215007.3H79394509
23025.0130818215000.84H79305511
46012.867818215003.24J79355511
57510.653818215005.2J79395511
46018.090818015001.16H79355512
57514.472818015001.84H79395512
AmperageFull Load
MaxStart.Eff. (%)Pwr fact.Blk-YelRed-Yel
Max.
Thrust
(lbs)
Line-to-Line
Resistance (Ω)
KVA Code
Nameplate
No.
29
Page 30
Electrical Data
MS Motors
HPPhVolt
6-Inch, Three Phase, 3-Wire Motors
23026.411980.57615000.63H78305511
7 1/23
103
153
203
253
303
40346064.032064.08270000.39H78355520
46013.25980.57615002.4G78355511
57510.64880.57615004.07H78395511
23034.015682.57915000.41G78305512
46017.078827915001.8G78355512
57513.663827915003.1G78395512
23049.023082.58270000.25G78305514
46024.511582.58270001.16F78355514
57519.69282.58270001.9G78395514
23066.0343848170000.20H78305516
46033.0172848270000.80H78355516
57526.4137848270001.32H78395516
46041.021784.58070000.62H78355517
57533.017584.58070001.04H78395517
46046.5237858370000.55G78355518
57537.018984.58370000.92G78395518
AmperageFull Load
MaxStartEff. (%)Pwr Fact.Blk-YelRed-Yel
Max.
Thrust
(lbs)
Line-to-Line
Resistance (Ω)
KVA Code
Nameplate
No.
30
Page 31
Electrical Data
Transformer Capacity
Required for Three-Phase Motors
SubmersibleSmallest KVA Rating - Each Transformer
Three-Phase
Motor HP Rating
1.5321
2421.5
3532
57.553
7.5107.55
1015105
1520157.5
20251510
25302010
30402515
40503020
50603520
60754025
75905030
1001206540
1251508550
15017510060
17520011570
20023013075
Pump Motor KVA requirements only - does not include allowances for other loads.
This is also the KVA required for single phase motors.
Total Effective
KVA Required
Open WYE or DELTA
2 Transformers
MS Motors
WYE or DELTA
3 Transformers
31
Page 32
Electrical Data
Engine-Driven Generators
Required for Submersible Motors
Sub Motor HP
Single or Three Phase
1/3 Hp1.51.01.21.5
1/2 Hp2.02.51.51.9
3/4 Hp3.03.82.02.5
1 Hp4.05.02.53.13
1 1/2 Hp5.06.253.03.8
2 Hp7.59.44.05.0
3 Hp10.012.55.06.25
5 Hp15.018.757.59.4
7 1/2 Hp20.025.010.012.5
10 Hp30.037.515.018.75
15 Hp40.050.020.025.0
20 Hp60.075.025.031.0
25 Hp75.094.030.037.5
30 Hp100.0125.040.050.0
40 Hp100.0125.050.062.5
50 Hp150.0188.060.075.0
60 Hp175.0220.075.094.0
75 Hp250.0313.0100.0125.0
100 Hp300.0375.0150.0188.0
125 Hp375.0469.0175.0219.0
150 Hp450.0563.0200.0250.0
175 Hp525.0656.0250.0313.0
200 Hp600.0750.0275.0344.0
1. Figures shown are based on typical 80°C rise continuous duty generators with 35% maximum voltage dip during start-up of single-phase
and three-phase motors.
2. Contact the manufacturer of the generator to assure the unit has adequate capacity to run the submersible motor.
Externally
kW
Minimum kW Rating of Generator
Regulated
KVA
Internally
kW
MS Motors
Regulated
KVA
32
Page 33
Electrical Data
Motor Protection Chart
1- Phase Motors
HPPhVolt
4-Inch, Single Phase, 2-Wire Motors (control box not required)
1/31230155--79952101
1/211153015--79922102
1/21230157--79952102
3/41230209--79952103
112302512--79952104
1 1/212303515--79952105
4-Inch, Single Phase, 3-Wire Motors
1/311152510--79423101
1/31230155--79453101
1/211153015--79423102
1/21230157--79453102
3/41230209--79453103
112302512--79453104
1.512303015--79453105
212303015--79454506
312304520--79454507
512307030--79454509
Circ. Brkr or FusesThree Phase Overload Protection
Std.DelayStarter size
Furnas Amb.
Comp
MS Motors
Nameplate
3-Phase Motors
HPPhVolt
4-Inch, Three Phase, 3-Wire Motors
1 1/23
23
33
53
7 1/23
103
Circ. Brkr or FusesThree Phase Overload Protection
Std.DelayStarter size
2301580K4179302005
4601040K3279362005
5751040K2879392005
23020100K5079302006
4601050K3479362006
5751040K3179392006
23030150K5479302006
4601570K3779362007
5751560K3679395507
23040251K6179304509
46020120K5079354509
5751590K4379394509
23060301K6779305511
46035151K5679355511
57530151K5379395511
46050251K6179355512
57540201K5879395512
Furnas Amb.
Comp
Nameplate
33
Page 34
Electrical Data
MS Motors
HPPhVolt
6-Inch, Three Phase, 3-Wire Motors
23060351K6778305511
7 1/23
103
153
203
253
303
403460150803K7878355520
46030151K5678355511
57525121K5378395511
23080451 3/4K7078305512
46040201K6078355512
57535151K5778395512
230125602 1/2k7678305514
46060301 3/4K6778355514
57550251 3/4k6278395514
230150803k7978305516
46080402k6878355516
57570302k6778395516
460100502K7378355517
57580402K7078395517
460110602 1/2K7678355518
575100402 1/2K7278395518
Circ. Brkr or FusesThree Phase Overload Protection
Std.DelayStarter size
Furnas Amb.
Comp
Nameplate
34
Page 35
Electrical Data
MS Motors
Motor Cable Selection Chart
(Motor Service to Entrance)
Single Phase, 60 Hz
Motor RatingCopper Wire Size
VoltsHP14121086420000000000250300
115
230
1/3130210340540840130019602910-----
1/210016025039062096014602160-----
1/355088013902190340052507960------
1/240065010201610251038805880------
3/430048076012001870289043706470-----
125040063099015402380361053606520----
1 1/219031048077012001870285042805240----
21502503906209701530236036204480---
31201903004707501190185028903610----
5--180280450710111017402170----
7 1/2---20031049075011401410----
10----2503906009301160----
Three Phase, 60 Hz
Motor RatingCopper Wire Size
VoltsHP14121086420000000000250300
1 1/23105007901260---------
22403906109701520--------
318029047074011601810-------
5-17028044069010801660------
208
230
7 1/2--20031049077011801770-----
10---23037057088013301640----
15----25039060091011101340---
20-----30046070086010501270--
25------37057070084010301170-
30------3104705807008509701110
1 1/23605809201450---------
228045070011101740--------
321034054086013402080-------
5-20032051080012401900------
7 1/2--23036057089013502030-----
10---270420660101015201870----
15----29045069010401801540---
20-----35053081099012001450--
25-----28043065080097011701340-
30------35054066080097011101270
35
Page 36
Electrical Data
Motor RatingCopper Wire Size
VoltsHP14121086420000000000250300
1 1/21700------------
213002070-----------
3100016002520----------
559095015002360---------
7 1/2420680107016902640--------
10310500790125019603050-------
15--540850134020903200------
20--4106501030161024703730-----
25---5308301300199030103700----
460
575
1. If aluminum conductor is used, multiply lengths by 0.5. Maximum allowable length of aluminum is considerably shorter than copper wire of same size.
2. The portion of the total cable which is between the service entrance and a 3ø motor starter should not exceed 25% of the total maximum length to assure
reliable starter operation. Single-Phase control boxes may be connected at any point of the total cable length.
3. Cables #14 to #0000 are AWG sizes, and 250 to 300 are MCM sizes.
30---43068010701640249030603700---
40-----79012101830225027103290--
50-----64098014801810219026503010-
60------830125015401850224025402890
75-------103012601520185021002400
100--------9401130138015601790
125----------108012201390
150-----------10501190
200-----------10801300
250------------1080
1 1/22620------------
22030------------
315802530-----------
592014802330----------
7 1/2660106016802650---------
1049078012401950---------
15-53085013402090--------
20--650103016102520-------
25--520830130020303110------
30---6801070167025603880-----
40----7901240190028603510----
50-----10001540231028403420---
60-----85013001960240028903500--
75------106016001970238028903290-
100-------119014601770215024402790
MS Motors
36
Page 37
Accessories
CU 3
The CU 3 control unit is an electronic motor starter for
monitoring and protecting installations with rated voltages of 200-575 V, 50 - 60 Hz, and a maximum power
consumption of 400 A.
The CU 3 monitors the following parameters:
• System insulation resistance to earth before start.
• Motor temperature.
• Motor current consumption and current unbalance.
• Voltage supply.
• Phase sequence.
The CU 3 protects against:
• Dry running (not for certain MS 402 motors).
• Incipient motor defect
• Too high motor temperature (not for certain MS 402
motors).
• Motor burnout.
As standard, the CU 3 incorporates:
• Time relay for star-delta starting and autotransformer starting.
• Relay output for external fault indication.
In addition CU 3 can be expanded to offer the following
functions:
• Remote control R100: Wireless infra-red remote
control by means of the R100. This function enables
the user to change factory settings and to monitor
the installation by calling up actual operating data,
e.g. current consumption, supply voltage and operating hours.
• External sensors SM 100: Reception of data from
external sensors by means of an SM 100 sensor
module and control according to the data received,
e.g. flow rate, pressure, water level and conductivity.
• Communication module: Monitoring and communication via a data BUS (GENIbus), a modem or radio, e.g. PC-based control/monitoring.
Fig. 10
Fig. 11
Fig. 12
R100
CU 3
200 mm
SM 100
200 mm
MS Motors
CU 3
54.5 mm
192.5 mm
54.5 mm
192.5 mm
Single-turn transformers, 100-400 A.
No monitoring of motor temperature.
Signal converter, 1-20 A/20-120 A, with
monitoring of motor temperature.
Fig. 13
330 mm
50 mm
37
Page 38
Accessories
Technical data
Enclosure class:IP 20.
Ambient temp.:–20°C to +60°C.
Relative humidity:99%.
Voltage variation:–25/+15% of nominal voltage.
Frequency:45 Hz to 65 Hz.
Max. back-up fuse: 10 A.
Relay output:Max. 415 V, 3 A, AC 1.
Approvals:The CU 3 complies with: VDE,
DEMKO, EN, UL and CSA.
Marking:CE.
Benefits of CU 3/R100
CU 3 is suitable for all 3-phase submersible motors.
MS Motors
Parameters monitored by
CU 3
Temperature
Motor currentThe motor is stopped when the rated motor current set is exceeded.Motor starter/protective relay
Overvoltage/undervoltageIf the actual value is higher/lower than the value set, the motor is stopped.Line monitor
Dry running
Phase asymmetry/direction of
rotation
Energy consumption in kW/h
Operating hours
Starting delayProgrammable.Time-delay relay
Restarting delayProgrammable limit of starts/stops.Time-delay relay
Star-delta startingCorresponding to a star-delta time-delay relay.Time-delay relay
Description
The actual motor temperature is measured by means of the Pt100.
The value measured is transferred via a separate cable to a relay.
The motor power input is measured on each of the three phases and registered as
an average of these three values.
If the average value is lower than the value set, the motor is stopped.
The motor power input is measured on each of the three phases.
If the input phase sequence is changed, a fault indication is given.
The power is read and accumulated every 10 seconds.
The energy consumption is calculated and accumulated every 2 hours.
Running when the motor relay is activated.
Stopped when the motor is not running.
These components need not be
installed
Level relay 3 electrodes,
electrode cable
Phase monitoring
Counter (not calibrated)
Operating-hours counter
38
Page 39
Accessories
Control functions
This table describes the protection provided by CU 3.
Control
parameters
Ground failure Insulation resistance is measured only
Temperature The actual motor temperature is measured
Overvoltage/
undervoltage
Overload The motor power input is measured on
Dry running The motor power input is measured on
Current unbalance The power input of the motor is measured
Phase sequence CU 3 and motor are installed so that the
FunctionProblemAdvantages
when motor is not operating.
A high-impedance voltage is applied to the
motor leads and leakage to ground is
measured. If the factory-set value is
higher than the one measured the motor
cannot be started.
by means of the Pt100. Via a relay, the
signal is sent to the CU 3 where the
measured temperature is compared with
the factory-set value. Temperature protection requires a submersible motor with a
Pt100.
If the factory-set values are exceeded, a
fault indication is given. If the CU 3
receives a temperature signal, the voltage
is no longer monitored, but the motor will
continue to run.
Therefore, the motor and consequently
the pump operation will be affected by
voltage variations critical to the life of the
motor.
If there is no temperature signal, the motor
will be stopped in case of overvoltage/
undervoltage.
each of the three phases. The registered
power input is average of these three
values. If the factory-set value is
exceeded, the motor will stop.
each of the three phases. The registered
power input is an average of these three
values.
If the average value is lower than the
factory-setting value, the motor will stop.
on each of the three phases.
phase sequence corresponds to correct
direction of rotation.
CU 3 monitors changes in the phase
sequences.
Damaged or decomposed insulation in
motor, cable or cable
joint.
Overload, frequen start
s/stops, operation
against blocked
discharge pipe, insufficient flow velocity past
the motor.
The installation is close
to a transformer, the
mains do not absorb
load variations.
Incorrect dimensioning
of pump/motor, voltage
supply failure, defective
cable, blocking, wear or
corrosion.
Pump exposed to dry
running or underload,
for example caused by
wear.
Mains load is uneven,
incipient motor defect,
phase voltages diverging.
Two phases are
wrongly connected.
MS Motors
Possibility of failure
indication on motor,
cable and cable joint,
service indication.
Longer motor life, safe
operating conditions,
service indication.
Important installation
parameter, possibility
of improving operating
conditions.
Longer pump lift,
safe operating
conditions, service indication.
Traditional dry-running
protection is no longer
necessary, no extra
cables.
Motor protection
against overload,
service indication.
Ensures correct pump
performance.
39
Page 40
Accessories
pg
Features and benefits
MS Motors
Selecting the right pump
The Grundfos CU 3 control unit and a flowmeter provide
for a constant monitoring of energy consumption and
performance of the pump thus making it possible to
ensure that the right pump is selected for the application in question.
The CU 3 control unit makes it possible to choose the
borehole(s) to be in operation which offer(s) the lowest
operating costs.
Choosing the right time for service
The constant monitoring by the CU 3 control unit makes
it possible to service the pump, i.e. clean it and replace
wear parts, at the best possible time.
Today service and maintenance work is often carried
out at regular intervals or when actual downtime
occurs. Both are unlikely to result in an optimum
energy-efficient operation.
Avoiding overpumping
Using the Grundfos CU 3 control unit and a water level
sensor it is possible to carry out test pumping of each
borehole. This is done by measuring the water table
level and the volume of water which is pumped. The
purpose is to ensure that only the water naturally
running to the borehole is pumped. As a result operations will provide for optimum efficiency. Consequently,
the lives of both borehole and pump will increase, since
both water aeration and the risk of ingress of aggressive water are reduced.
By minimizing the risk of overpumping and thus the
pumping of impure ground water the costs of water
treatment can be reduced to a minimum.
Using the Grundfos CU 3 control unit and a sensor it is
possible to measure water conductivity in each borehole. This provides for the possibility of selecting the
40
borehole (or boreholes) to be in operation which
supplies the best water quality at any time.
Fig. 16
Conductivity
Time
Fig. 17
Page 41
Accessories
MS Motors
Motor protection via CU 3
• Power on
• Motor on
• Motor temperature
• Ground failure
• Overload/dry running
• Overvoltage/undervoltage
• Current unbalance
• Direction of rotation
CU 3
Netz ein
Trockenlauf (blinkt) / !berlast (leuchtet)
Unterspannung (blinkt) / !berspannung (leuchtet)
Motor læuft
Massefehler
Stromasymmetrie
Reset
Motortemperatur Phasenfolge
Signal converter
1-12 [A], 10-120 [A]
or single transformers
100-400 A
3 x 230 V, 60 Hz
3 x 460 V, 60 Hz
Control unit CU 3 with R100
remote control and printer
• Power on
• Motor on
• Motor temperature
• Ground failure
• Overload/dry running
• Overvoltage/undervoltage
• Current unbalance
• Direction of rotation
CU 3
Wireless infra-red
communication
Trockenlauf (blinkt) / !berlast (leuchtet)
Netz ein
Unterspannung (blinkt) / !berspannung (leuchtet)
Motor læuft
Massefehler
Stromasymmetrie
Reset
Motortemperatur Phasenfolge
Signal Converter
1-12 [A], 10-120 [A]
or single Transformers
100-400 A, 3 x 230 V, 60 Hz
3 x 460 V, 60 Hz
R 100
Connection to Pump.
No extra Cable required.
High-frequency signals.
Fig. 18
Control Cabinet
Ground level
Water level
Riser Pipe
Submersible Pump
Submersible Motor with
Tempcon or Pt100
Control Cabinet
Connection to Pump.
No extra Cable requred.
High-frequency Signals.
Ground level
Inductive Flowmeter
Water level
Riser Pipe
Submersible Pump
Submersible Motor with
Tempcon or Pt100
TM00 7977 1702
TM00 7978 1702
Fig. 19
41
Page 42
Accessories
MS Motors
R100 Menus
0. General
1. Operation
1.1 Warning and stop indication.
1.2 Indication of automatically reset fault indications.
Possibility of start and stop.
2. Status
Indication of:
2.1 Motor temperature
2.2 Current and voltage values.
2.3 Average supply voltage.
2.4 Average input current of the three phases.
2.5 Actual current unbalance.
2.6 Actual insulation resistance to earth.
2.7 Phase sequence and frequency.
2.8 Actual power input and total power consumption.
2.9 Accumulated number of operating hours.
2.10 Value measured by an external sensor.
2.11 Energy consumption per m
2.12 Actual flow.
2.13 Accumulated flow.
3. Limits
Indication and setting of:
3.1 Motor temperature.
3.2 Current stop limits.
3.3 Current warning limits.
3.4 Voltage variations.
3.5 Insulation resistance.
3.6 Currrent unbalance.
3.7 Stop for external sensor.
3.8 Warning limits for external sensor.
4. Installation
Setting possibilities:
4.1 Automatic or manual resetting of fault indications.
4.2 Release time for fault indications.
4.3 Star connection time for star-delta or
auto-transformer starting.
4.4 Starting delay when first started, e.g. after supply
failure.
4.5 Minimum start cycle time.
4.6 On/off of groundwater lowering function.
4.7 Run/stop times for groundwater lowering.
4.8 Electronic numbering of CU 3 units.
4.9 On/off of power and temperature measuring
funciton.
4.10 External sensor type. On/off of external analog
sensor with or without zero offset.
4.11 Groundwater lowering by means of level sensors.
Filling and emptying function.
4.12 On/off of external digital sensor.
3
pumped liquid.
Status report
All settings and measured values can be transferred to
a portable printer via wireless infra-red communication
and be printed in a status report.
Wireless infra-red
communication
CU 3
CU 3
Fig. 20
IR-Printer
Fig. 21
R100
R100
R 100
TM00 7981 1702TM00 7982 1302
42
Page 43
Accessories
Menu Structure of the R100 Remote Control
MS Motors
Set
Light
0. General
1. Operation
1.1
1.2
Start
Contrast
2. Status3. Limits4. Installation
2.1
2.2
2.3
2.4
2.5
2.6
3.1
3.2
3.3
3.4
3.5
3.6
4.1
4.2
4.3
4.4
4.5
4.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
3.7
3.8
4.7
4.8
4.9
4.10
4.11
4.12
TM01 0226 0201
43
Page 44
Accessories
MS Motors
Complete Borehole Monitoring
System with CU 3 and SM 100
Monitoring parameters (Diodes)
• Power on
• Motor on
• Motor temperature
• Ground failure
• Overload/dry running
• Overvoltage/undervoltage
• Current unbalance
• Direction of rotation
(not supplied with the unit)
PC
Gateway
(not supplied with
the unit)
Digital inputs
For Analog Sensors
Communication
Module
Signal Converter
1-12 [A], 10-20 [A]
or single-turn transformers 100-400 A
3 x 230 V, 60 Hz
3 x 460 V, 60 Hz
Connection to Pump.
No extra Cable required.
High-frequency Signals.
CU 3
RS-485
Inductive flowmeter
Water level
Riser Pipe
SM 100
Control Cabinet
Ground level
SM 100
The SM 100 sensor module can be connected to eight
analog sensors and have eight digital inputs for
sensors, e.g. monitoring of
- pH value
- conductivity
- O
2
- pressure
- etc.
CU3CU3CU3SM100
Protokoll-
umsetzer
(bauseits)
GRUNDFOS-GENIbus
max. 1200 m
PC
Fig. 23
Maximum connection to the GENIbus:
• 28 CU 3 units, or
• 14 CU 3 units and 14 SM 100 units, or
• 27 CU 3 and 1 SM 100.
Product numbers
CU 3 - 3 x 460 V
Product number
62500293z
62500294z
62500295z
Product
Sensor module SM 1003 x 460 V00626191
Communication module RS 485-00626159
Remote control R100-00625333
HP printer for R100-00620480
Signal converter
Current range for signal converter [A]
1-1210-120100-400
CU 3 expansion possibilities
RangeProduct number
1-12 [A]00620497
10-120 [A]00620498
100-400 [A]00626148
TM00 7980 1702
Submersible Pump
Submersible Motor with
Tempcon or Pt100
Fig. 22
44
TM00 7979 1702
Page 45
Further product documentation
Sources of product documentation
In addition to the printed data booklet, Grundfos offers
the following sources of product documentation.
• WinCAPS
• WebCAPS.
WinCAPS®
WinCAPS is a Windows-based Computer-Aided
Product Selection program containing information on
more than 90,000 Grundfos products.
Available on CD-ROM in more than 15 languages,
WinCAPS offers
• detailed technical information
• selection of the optimum pump solution
• dimensional drawings of each pump
• detailed service documentation
• installation and operating instructions
• wiring diagrams of each pump.
Click on Catalog and
select a product from the
extensive product catalog.
Fig. 24 WinCAPS CD-ROM
Click on Sizing and select
the most suitable pump
for your application.
cd-wincaps.
Fig. 25 WinCAPS
WinCAPS_US.
45
Page 46
Further product documentation
WebCAPS®
WebCAPS is a Web-based Computer Aided-Product
Selection program and a web-version of WinCAPS.
Available on Grundfos’ homepage,
www.grundfos.com, WebCAPS offers
• detailed technical information
• dimensional drawings of each pump
• wiring diagrams of each pump.
Click Catalog and
select a product from
the extensive
product catalog.
Click Replacement
and select the right
replacement pump
based on the
current installation.
Click Literature to
select and download
Grundfos documentation
by browsing the product
ranges or performing
a specific search. The
literature includes:
- Data booklets
- Installation and
operating manuals
- Service etc.
Click Product
search and select
a product from the
extensive product
catalog.
Click Service to
to find information
on service kits and
spare parts.
Being a registered
user click Log in to:
- save your settings
- define and save your
own units
- save personalized
information.
Click Units and select your
preferred units of measurement:
- Default units
- SI units
- US units.
Click Language and
select your preferred
language.