Grundfos MAGNA 32-60, MAGNA 32-100 Instructions Manual

Page 1
GRUNDFOS INSTRUCTIONS
MAGNA
Series 2000 MAGNA 32-60, 32-100
Installation and operating instructions
3191277
Conforms to ANSI/UL Std. 778 Certified to CAN/CSA Std. E60335-2-51
Page 2
2
(QJOLVK86
English (US) Installation and operating instructions
CONTENTS
Page
1. Limited warranty
Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating nstructions.
To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.
1. Limited warranty
2
2. Symbols used in this document
3
3. General description
3
4. Applications
3
4.1 Pumped liquids
3
5. Installation
4
5.1 Positioning
4
5.2 Changing the control box position
5
5.3 Insulation shells
5
5.4 Non-return valve
5
5.5 Frost protection
5
6. Electrical connection
6
6.1 Supply voltage
6
6.2 Connection to the supply
6
7. Start-up
6
8. Functions
6
8.1 Functions selected via the pump control panel
6
8.2 Functions selected via the R100 remote control
6
8.3 Functions selected via expansion modules
7
8.4 Control modes
7
8.5 Selection of control mode
8
8.6 Automatic nighttime duty
8
8.7 Constant-curve duty
9
8.8 Max. or min. curve d uty
9
8.9 Temperature influence
9
8.10 Expansion modules
10
8.11 Connection to LON network
10
9. Pump setup
10
9.1 Factory setting
10
9.2 Control panel
11
9.3 R100 remote control
12
9.4 R100 display overview
13
9.5 Menu OPERATION
14
9.6 Menu STATUS
14
9.7 Menu INSTALLATION
15
9.8 Priority of settings
16
10. Troubleshooting
17
10.1 Checking the module
18
11. Megging
19
12. Technical data
20
13. Disposal
20
Warning
Prior to installation, read these installa­tion and operating instructions. Instal­lation and operation must comply with local regulations and accepted codes of good practice.
This booklet should be left with the owner of the pump for future reference and information regarding its opera­tion.
Page 3
3
(QJOLVK86
2. Symbols used in th is d ocument
3. General description
The GRUNDFOS MAGNA Series 2000 is a circulator pump with integrated differential pressure control enabling adjustment of pump performance to the actual system requirements. In many systems, this will reduce the power consumption considerably, reduce noise from thermostatic valves and similar fittings, and improve the control of the system.
The desired head can be set on the pump control panel.
Fig. 1 Grundfos MAGNA Series 2000 circulator
pump
4. Applications
The GRUNDFOS MAGNA is designed for circulating liquids in heating and air-conditioning systems.
The pump range is primarily used in
• systems with a variable flow. The pump range can also be used in
• systems with a constant flow where it is desirable to optimize the setting of the pump duty point
• systems with variable flow-pipe temperature.
4.1 Pumped liquids
Grundfos MAGNA is intended for pumping clean water not containing solid particles or fibers.
Warning
If these safety instructions are not observed, it may result in personal injury!
&DXWLRQ
If these safety instructions are not observed, it may result in malfunc­tion or damage to the equipment!
1RWH
Notes or instructions that make the job easier and ensure safe operation.
Warning
The use of this product requires experience with and knowledge of the product.
Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety.
Children must not use or play with this product.
TM04 9389 4010
Warning
The pump must not be used for the transfer of flammable liquids such as diesel oil, petrol or similar liquids.
Page 4
4
(QJOLVK86
5. Installation
Arrows on the pump housing indicate the liquid flow direction through the pump.
5.1 Positioning
GRUNDFOS MAGNA must be installed with the pump head in horizontal position; see fig. 2.
Fig. 2 Installation positions
Page 5
5
(QJOLVK86
5.2 Changing the control box position
Procedure:
5.2.1 Control box position
For permissible control box positions, see the Quick Guide.
5.3 Insulation shells
Insulation shells for pumps in heating systems are supplied with the pump.
For cold water applications, a silicone RTV sealant must be liberally applied to the area shown in fig. 3 to prevent condensation between the shell and pump housing. Follow the sealant manufacturers instructions for safety and proper usage.
The fitting of insulation shells will increase the pump dimensions.
Fig. 3 Shaded area indicates silicone RTV
sealant
5.4 Non-return valve
If a non-return valve is fitted in the pipe system, see fig. 4; ensure that the set minimum discharge pressure of the pump is always higher than the closing pressure of the valve. This is especially important in proportional-pressure control mode (reduced head at low flow).
Fig. 4 Non-return valve
5.5 Frost protection
If the pump is not used during periods of frost, necessary steps must be taken to prevent bursting pipes.
Warning
Before any dismantling of the pump, the system must be drained or the isolating valves on both sides of the pump must be closed as the pumped liquid may be scalding hot and under high pressure.
Step Action Illustration
1
Remove the two screws.
TM03 0474 5204
2
Pull the stator and the pump head approx.
0.22 inches (5 mm) out.
TM03 0475 5204
3
Turn the stator and the pump head to the desired position.
TM03 0476 5204
4
Push the stator and the pump head into place.
TM03 0475 5204
5
Refit the two screws
(16 + 5 Nm).
TM03 0580 0305
11RWH
It is recommended to fit insulation shells to the pump.
TM04 9313 3910TM02 0640 0301
11RWH
Additives with a density and/or kin­ematic viscosity higher than those/that of water will reduce the hydraulic performance.
Page 6
6
(QJOLVK86
6. Electrical connection
The electrical connection and protection must be carried out in accordance with local regulations.
• The pump requires no external motor protection.
• Check that the supply voltage and frequency cor­respond to the values stated on the pump name­plate.
6.1 Supply voltage
1 x 208 - 230 V +/- 10 %, 50/60 Hz.
6.2 Connection to the supply
7. Start-up
Do not start the pump until the system has been filled with liquid and vented. Furthermore, the required minimum inlet pressure must be available at the pump inlet, see section 12. Technical data.
The system cannot be vented through the pump.
8. Functions
Most functions can be selected via the pump control panel. However, some functions can only be selected with the R100 or via expansion modules.
8.1 Functions selected via the pump control panel
The following functions are selected via the pump control panel; see fig. 11.
AUTO
ADAPT (factory setting)
Recommended for most heating installations. During operation, the pump automatically makes the necessary adjustment to the actual system characteristic. This setting ensures minimum energy consumption and noise level which reduces operating costs and increases comfort.
Proportional-pressure control
The pump head is changed continuously in accordance with the water demand in the system. The desired setpoint can be set on the pump control panel.
Constant-pressure control
A constant head is maintained, regardless of water demand. The desired setpoint can be set on the pump control panel.
Automatic night-time duty
The pump changes automatically between normal duty and night-time duty depending on the flow-pipe temperature. Automatic nighttime duty can be combined with the above-mentioned control modes.
8.2 Functions selected via the R100 remote control
Additional functions can be selected via the R100 remote control:
Constant-curve duty
The pump runs at a constant speed, on or between the max. and min. curves.
Temperature influence
The pump head varies depending on the liquid temperature.
Warning
Risk of electric shock — This pump is supplied with a grounding conductor and grounding-type attachmen t plug. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, ground­ing-type receptacle.
Warning
The pump must be connected to an external disconnect switch.
Grounding can be used for protection against indirect contact.
Megging must be carried out as described in section 11. Megging.
Warning
If the pump is connected to an elec­tric installation where a Ground Fault Circuit Interrupt (GFCI) is used as additional protection, this circuit breaker must trip out when ground fault currents with DC con­tent (pulsating DC) occur.
TM03 0520 0105
Page 7
7
(QJOLVK86
8.3 Functions selected via expansion modules
Further functions are available via the GENI module or the relay module:
8.3.1 GENI module
External analog control of head or speed via a
signal from an external 0-10 V signal transmitter.
External forced control via inputs for:
- Max. curve
- Min. curve.
Bus communication via GENIbus
The pump can be controlled and monitored by a Grundfos Control MPC Series 2000, a building management system or another type of external control system.
External start/stop
The pump can be started and stopped via the = digital input.
Fault, ready and operating indication via signal
relay
The pump controls an external fault, ready and operating signal relay via a potential-free output. The function of the signal relay is set with the R100.
8.3.2 Relay module
External start/stop
The pump can be started and stopped via the digital input.
Fault, ready and operating indication via
signal relay
The pump controls an external fault, ready and operating signal relay via a potential-free output. The function of the signal relay is set with the R100.
8.4 Control modes
A GRUNDFOS MAGNA pump can be set to the control mode which is most suitable for the individual system.
Possible control modes:
•AUTO
ADAPT
(factory setting)
• Proportional pressure
• Constant pressure.
Each of the control modes can be combined with automatic night-time duty, see section 8.6 Automatic nighttime duty.
AUTO
ADAPT
To be set on the control panel or with the R100, see section 9. Pump setup.
The control mode AUTO
ADAPT continuously adapts
the pump performance. The setpoint of the pump has been factory-set as
follows and cannot be changed manually:
MAGNA 32-60 to 12 ft (3.6 m)
• MAGNA 32-100 to 18 ft (5.5 m).
When the pump registers a lower pressure on the max. curve, A
2
, the AUTOADAPT function automati­cally selects a correspondingly lower control curve, H
set2
, thus reducing the energy consumption.
Fig. 5 AUTO
ADAPT
A1: Original duty point. A
2
: Lower registered pressure on the max.
curve.
A
3
: New duty point after AUTOADAPT control.
H
set1
: Original setpoint.
H
set2
: New setpoint after AUTOADAPT control.
H
fac.
: Factory-set setpoint.
The AUTO
ADAPT function can be reset by pressing
the button for approx. 10 seconds until the control mode is back to the starting point (AUTO
ADAPT or
AUTO
ADAPT with automatic
nighttime duty).
Proportional-pressure control
To be set on the control panel or with the R100, see section 9. Pump setup.
The pump head is reduced at decreasing water demand and increased at rising water demand; see fig. 6.
Constant-pressure control
To be set on the control panel or with the R100, see section 9. Pump setup.
The pump maintains a constant pressure, regardless of water demand; see fig. 6.
Fig. 6 Pressure control
TM02 0251 4800
TM00 5546 4596
H
max.
H
fac.
A
1
A
3
A
2
H
set2
H
set1
H
set
H
set
H
set
Proportional pressure
Constant pressure
Page 8
8
(QJOLVK86
8.5 Selection of control mode
8.5.1 Setpoint setting
The setpoint can be set by pressing or when the pump is in control mode:
• proportional pressure,
• constant pressure or
• constant-curve duty. Set the setpoint so that it matches the system. A too high setting may result in noise in the system
whereas a too low setting may result in insufficient heating or cooling in the system.
If AUTO
ADAPT is selected, the setpoint cannot be set.
8.6 Automatic nighttime duty
To be set on the control panel or with the R100, see section 9. Pump setup.
Once automatic nighttime duty has been activated, the pump automatically changes between normal duty and night-time duty (duty at low performance).
Changeover between normal duty and nighttime duty is dependent on the flow-pipe temperature.
The pump automatically changes over to nighttime duty when the built-in sensor registers a flow-pipe temperature drop of more than 18 °F - 27 °F (10 °C - 15 °C) within approx. 2 hours. The temperature drop must be at least 0.18 °F/min (0.1 °C/min).
Changeover to normal duty takes place without a time lag when the temperature has increased by approx. 18 °F (10 °C).
System type Description
Select this control mode
Typical heating systems
Grundfos recommends to let the pump remain in AUTO
ADAPT mode.
This ensures optimum performance at the lowest possible energy consumption.
AUTO
ADAPT
Relatively great head losses in the distribution pipes and air-condition­ing systems
1. Two-pipe heating systems with thermostatic valves and:
• with a pump head higher than 10 ft (3 m),
Proportional
pressure
• very long distribution pipes,
• strongly throttled pipe balancing valves,
• differential pressure regulators,
• great head losses in those parts of the system through which the total quantity of water flows (e.g. boiler, heat exchanger and distribution pipe up to the first branching).
2. Primary circuit pumps in systems with great head losses in the pri­mary circuit.
3. Air-condition­ing systems with
• heat exchangers (fan coils),
• cooling ceil ings,
• cooling surfaces.
Relatively small head losses in the distribution pipes
1. Two-pipe heating sys­tems with thermostatic valves and:
• with a pump head lower than
6.5 ft (2 m),
Constant pressure
• with small head losses in those parts of the sys­tem through which the total quantit y of wat er flow s (e.g. boiler, heat exchanger and distribution pipe up to the first branching) or
• modified to a high differential temperature between flow pipe and return pipe (e.g. district heating).
2. Underfloor heating systems with thermostatic valves.
3. One-pipe heating systems with thermostatic valves or pipe balanc­ing valves.
4. Primary circuit pumps in systems with small head losses in the pri­mary circuit.
1RWH
Automatic nighttime duty cannot be used in air-conditioning systems.
Page 9
9
(QJOLVK86
8.7 Constant-curve duty
To be set with the R100, see section 9. Pump setup. The pump can be set to operate according to a
constant curve, like an uncontrolled pump, see fig. 8. When the pump has been set to constant-curve
mode with the R100, the setting can be changed on the control panel or with the R100.
MAGNA 32-60, 32-100
Select one of 9 curves (81 curves with the R100) between the max. and min. curves, see fig. 7.
Fig. 7 Operating curves
8.8 Max. or min. curve duty
To be set on the control panel, with the R100 or via GENI module, see section 9. Pump setup.
The pump can be set to operate according to the max. or min. curve, like an uncontrolled pump, see fig. 8.
This operating mode is available, regardless of the control mode.
Fig. 8 Max. and min. curves
The max. curve mode can be selected if an uncon­trolled pump is required.
The min. curve mode can be used in periods in which a minimum flow is required. This operating mode is for instance suitable for manual nighttime duty if automatic night-time duty is not desired.
8.9 Temperature influence
To be set with the R100, see section 9. Pump setup. When this function is activated in proportional- or
constant-pressure control mode, the setpoint for head will be reduced according to the liquid temperature.
It is possible to set temperature influence to function at liquid temperatures below 176 °F (80 °C) or below 122 °F (50 °C). These temperature limits are called T
max.
. The setpoint is reduced in relation to the head
set (= 100 %) according to the characteristics below.
Fig. 9 Temperature influence
In the above example, T
max.
= 176 °F (80 °C) has
been selected. The actual liquid temperature T
actual
causes the setpoint for head to be reduced from 100 % to H
actual
.
The temperature influence function requires:
• Proportional- or constant-pressure control mode.
• The pump must be installed in the flow pipe.
• System with flow-pipe temperature control. Temperature influence is suitable in:
• systems with variable flows (e.g. two-pipe heating systems), in which the activation of the temperature influence function will ensure a further reduction of the pump performance in periods with small heating demands and consequently a reduced flow-pipe temperature.
• systems with almost constant flows (e.g. one-pipe heating systems and underfloor heating systems), in which variable heating demands cannot be registered as changes in the head as is the case with two-pipe heating systems. In such systems, the pump performance can only be adjusted by activating the temperature influence function.
Selection of T
max.
In systems with a flow-pipe temperature of:
• up to and including 131 °F (55 °C), select T
max.
= 122 °F (50 °C),
• above 131 °F (55 °C), select T
max.
= 176 °F (80 °C).
TM03 0551 0205TM00 5547 4596
Max.
Min.
Max.
Min.
TM01 0626
11RWH
The temperature influence function cannot be used in air-conditioning systems.
H
actual
T
actual
Page 10
10
(QJOLVK86
8.10 Expansion modules
The pump can be fitted with an expansion module enabling communication with external signals (signal transmitters).
Two types of expansion modules are available:
• Relay module
• GENI module.
8.10.1 Relay module
For mounting and operation, see relay module installation and operating instructions.
Functions
• External start/stop
• Fault, ready and operating indication via signal relay.
8.10.2 GENI module
For mounting and operation, see GENI module installation and operating instructions.
Functions
• External start/stop
• External forced control
• External analog 0-10 V control
• Bus communication via GENIbus
• Duty standby alternating mode
• Fault, ready and operating indication via signal relay.
8.11 Connection to LON network
The pump can be connected to a LON network via a GENI module and an external Grundfos G10 LON interface. Product number: 605726.
Fig. 10 Connection to LON network
9. Pump setup
For the setting of the pump, use:
• control panel.
• R100 remote control.
• bus communication (not described in detail in these instructions, contact Grundfos).
The table shows the application of the individual operating units and in which section the function has been described.
"–" = not available with this operating unit.
9.1 Factory setting
The pump is factory-set to AUTOADAPT without automatic nighttime duty.
TM03 0378 5004
LON network
24 VAC/VDC
GENI module
Possible settings
Control
panel
R100
AUTOADAPT 9.2.1 9.7.1 Automatic nighttime duty 9.2.1 9.7.2 Proportional-pressure
control
9.2.1 9.7.1
Constant-pressure con­trol
9.2.1 9.7.1
Setpoint setting 9.2.2 9.5.1 Max. curve duty 9.2.3 9.5.2 Min. curve duty 9.2.4 9.5.2 Constant-curve duty 9.5.2 Temperature influence 9.7.3 Activation/deactivation of
pump buttons
9.7.4
Allocation of pump num­ber
9.7.6
Start/stop 9.2.5 9.5.2
Resetting of fault indi­cations
9.2.6 9.5.3
Reading of various data
9.6.1 -
9.6.7
Page 11
11
(QJOLVK86
9.2 Control panel
The control panel, fig. 11, incorporates:
For further information, see section
10. Troubleshooting.
Fig. 11 Control panel
9.2.1 Control mode setting
Description of function, see section 8.4 Control modes.
To change the control mode, press , pos. 3, according to this cycle:
Fig. 12 Cycle of control modes
Automatic nighttime duty can be activated together with each of the control modes.
The light symbols in pos. 4 of fig. 11, indicate the pump settings:
"–" = no light.
Warning
At high liquid temperatures, the pump may be so hot that only the buttons should be touched to avoid burns.
Pos. Description
1 Buttons for setting
2
• Indicator lights for operating and fault indication and
• sym bol for indication of external con­trol
3 Button for change of control mode 4
Light symbols for indication of control mode and night-time duty
5
Light fields for indication of head, flow and operating mode
TM03 8752 2407
TM03 1288 1505
Light in Control mode
Automatic
nighttime
duty
AUTO
ADAPT AUTOADAPT NO
Proportional
pressure
NO
Constant pressure
NO
Constant curve NO
AUTO
ADAPT
AUTOADAPT YES
Proportional
pressure
YES
Constant pressure
YES
Constant curve YES
Page 12
12
(QJOLVK86
9.2.2 Setpoint setting
Set the setpoint of the pump by pressing or when the pump has been set to proportional­pressure control, constant-pressure control or constant-curve duty.
The light fields, pos. 5, on the control panel indicate the setpoint set.
MAGNA 32-60, 32-100
The light fields can indicate a maximum setpoint of
29.5 ft (9 m).
Fig. 13 Light fields MAGNA xx-100
9.2.3 Setting to max. curve duty
Description of function, see section 8.8 Max. or min. curve duty.
To change over to the max. curve, press continuously until "MAX" illuminates, see fig. 14. To change back, press continuously until the desired setpoint is indicated.
Fig. 14 Max. curve
9.2.4 Setting to min. curve duty
Description of function, see section 8.8 Max. or min. curve duty.
To change over to the min. curve, press continuously until "MIN" illuminates, see fig. 15. To change back, press continuously until the desired setpoint is indicated.
Fig. 15 Min. cu rve
9.2.5 Start/stop of pump
To stop the pump, press continuously until "STOP" illuminates. When the pump is stopped, the green indicator light will be flashing.
To start the pump, press continuously.
9.2.6 Resetting of fault indications
The fault indications are reset by briefly pressing any button. The settings remain unchanged. If the fault has not disappeared, the fault indication will reappear within 4.5 minutes.
9.3 R100 remote control
The pump is designed for wireless communication with the Grundfos R100 remote control. The R100 communicates with the pump via infrared light.
During communication, the R100 must be pointed at the pump control panel. When the R100 is communicating with the pump, the red indicator light will flash rapidly.
The R100 offers additional possibilities of setting and status displays for the pump.
TM03 0380 2507
TM03 0381 2507
TM03 0382 2507
11RWH
If the pump is to be stopped, it is recommended to use the start/stop input, the R100 or to switch off the electricity supply. In this way, the setpoint will remain unchanged when the pump is started again.
Page 13
13
(QJOLVK86
9.4 R100 display overview
The R100 displays are divided into four parallel menus, see fig. 16:
0. GENERAL, see operating instructions for R100
1. OPERATION
2. STATUS
3. INSTALLATION
The number stated at each individual display in fig. 16 refers to the section in which the display is described.
Fig. 16 Menu overview
9.5.3
9.6.2
9.6.3
9.6.4
9.6.5
9.7.5
9.7.4
9.7.3
9.6.6
9.6.7
9.5.2
9.7.1
9.6.1
9.5.1
9.5.4
9.7.2
9.7.6
This display appears only once, i.e. when the R100 gets contact with the pump.
3. INSTALLATION
2. STATUS
0. GENERAL 1. OPERATION
Page 14
14
(QJOLVK86
9.5 Menu OPERATION
When the communication between the R100 and the pump has been established, "Contact with" appears in the display. When the "arrow down" on the R100 is pressed, menu OPERATION appears.
9.5.1 Setpoint
This display depends on the control mode selected in the display "Control mode" in menu INSTALLATION.
If the pump is forced-controlled via external signals, the number of possible settings will be reduced, see section 9.8 Priori ty of settings. Attempts to change the settings will result in an indication in the display saying that the pump is forced-controlled and changes therefore cannot be made.
This display will appear when the pump is in AUTO
ADAPT mode.
Set the desired setpoint by pressing the buttons "+" and "–" on the R100 (not possible when the pump is in AUTO
ADAPT mode).
Furthermore, it is possible to select one of these operating modes:
• Stop
Min. (min. curve)
Max. (max. curve). The display is different if proportional pressure, con-
stant pressure or constant curve has been selected. The actual duty point of the pump is indicated by a
square in the Q/H field. No indication at low flow.
9.5.2 Operating mode
Select an operating mode:
• Stop
Min. (min. curve)
Normal (AUTO
ADAPT , proportional pressure,
constant pressure or constant curve)
Max. (max. curve).
9.5.3 Fault indications
If the pump is in alarm status, the cause will appear in this display.
Possible causes:
• Pump blocked
• Internal fault
•Overvoltage
• Undervoltage
• Overtemperature
• Module fault
• Fault in module communication.
The fault indication can be reset in this display. If the fault has not disappeared when resetting is attempted, the fault indication will reappear in the display when communicating with the pump.
9.5.4 Alarm log
The alarm code with text appears in this display. The display also shows the number of minutes the pump has been connected to the electricity supply after the fault occurred.
The last five fault indications will appear in the alarm log.
9.6 Menu STATUS
The displays appearing in this menu are status displays only. It is not possible to change or set values.
The actual values in the display are indicative and based on estimation.
9.6.1 Actual setpoint
Field "Actual setpoint":
Actual setpoint of pump.
Field "corresponding to":
Actual setpoint in % of the setpoint set if the pump is connected to an external analog 0-10 V signal transmitter or if temperature influence or proportional-pressure control is activated.
1RWH
The display "Contact with" appears only once, i.e. when the R100 gets contact with the pump.
Page 15
15
(QJOLVK86
9.6.2 Operating mode
This display shows the actual operating mode (Stop, Min., Normal or Max.) and where it was selected (Pump, R100, BUS or External).
9.6.3 Head and flow
The actual head and flow of the pump. If "<" is indicated in front of the flow, the flow is less
than the displayed value. If the pump is unable to determine head and flow,
this is indicated by "–".
9.6.4 Speed
The actual pump speed.
9.6.5 Liquid temperature
The actual temperature of the pumped liquid.
9.6.6 Power input and power consumption
Actual power input and power consumption of the pump.
The value of power consumption is an accumulated value and cannot be set to zero.
9.6.7 Operating hours
Operating hours of the pump. The value of operating hours is an accumulated
value and cannot be set to zero.
9.7 Menu INSTALLATION
This menu shows the settings that should be considered when installing the pump.
9.7.1 Control mode
Description of function, see section 8.4 Control modes or 8.7 Constant-curve duty.
Select one of the control modes:
•AUTO
ADAPT
Prop. pressure (proportional pressure)
Const. pressure (constant pressure)
Const. curve (constant curve). Setting of setpoint and curve is carried out in display
9.5.1 Setpoint in menu OPERATION (not possible when the pump is in AUTO
ADAPT mode).
9.7.2 Automatic night-time duty
In this display, automatic night-time duty can be acti­vated or deactivated.
Automatic night-time duty can be set to:
•Active
• Not active,
irrespective of the control mode selected.
9.7.3 Temperature influence
Description of function, see section 8.9 Temperature influence.
Page 16
16
(QJOLVK86
The temperature influence function can be activated in this display when the control mode is proportional pressure or constant pressure; see section
9.7.1 Control mode. In the case of temperature influence, the pump must
be installed in the flow pipe. It is possible to choose between maximum temperatures of 122 °F (50 °C) and 176 °F (80 °C).
When the temperature influence is active, a small thermometer is shown in the display "Setpoint" in menu OPERATION, see section 9.5.1 Setpoint.
9.7.4 Buttons on pump
To prevent unauthorized persons from operating the pump, the function of the buttons , and ca n be deactivated in this display. The buttons can be reactivated only with the R100.
The buttons can be set to:
Active
• Not active.
9.7.5 Signal relay
If an expansion module has been fitted, the signal relay function can be set in this display.
Fault (functions as a fault signal relay)
Ready (functions as a ready signal relay)
Operation (functions as an operating signal relay).
9.7.6 Pump number
A number from 1 up to and including 64 can be allocated to a pump or can be changed so that the R100, Grundfos Control MPC Series 2000 or other systems can distinguish between two or more pumps.
9.8 Priority of settings
The external forced-control signals will influence the settings available on the pump control panel and with the R100. However, the pump can always be set to max. curve duty or to stop on the pump control panel or with the R100.
If two or more functions are activated at the same time, the pump will operate according to the setting with the highest priority.
The priority of the settings is as shown in the table. Example: If the pump has been forced to stop via an
external signal, the pump control panel or the R100 can only set the pump to max. curve.
With expansion module
As illustrated in the table, the pump does not react to external signals (max. curve and min. curve) when the pump is controlled via bus.
If the pump is to react to external signals (max. curve and min. curve), the system must be configured for that function.
For further details, please contact Grundfos.
1RWH
If the pump is in cont ro l m ode AUTO
ADAPT
or constant curve, the temperature influence cannot be set with the R100.
Priority
Possible settings
Pump
control
panel
or R100
External
signals
Bus
signal
1Stop 2 Max. curve 3Stop
Stop
4
Max.curve Max.curve
5
Min. curve Min. curve Min. curve
6
Setpoint
setting
Setpoint
setting
Not active when the pump is con­trolled via bus.
Only active when the pump is con­trolled via bus.
Page 17
17
(QJOLVK86
10. Troubleshooting
Warning
The pumped liquid may be scalding hot and under high pressure. Before any removal or dismantling of the pump, the system must therefore be drained or the isolating valves on either side of the pump must be closed.
Indicator light is off.
Indicator light is on.
Indicator light is flashing.
Indicator
lights
Fault Cause Remedy
Green Red
The pump is not running.
One fuse in the installation is blown/tripped out.
Replace the fuse. Check that the electricity supply falls within the specified range.
The current-operated or volt­age-operated circuit breaker has tripped out.
Reset circuit breaker to ON position. Check that the electricity supply falls within the specified range.
The pump may be defective.
Replace the pump or call Grund­fos Service for assistance.
The pump is not running.
The pump has been stopped in one of the following ways:
1. With the button .
2. With the R100.
3. External on/off switch in posi­tion off.
4. Via bus signal.
1. Start the pump by pressing .
2. Start the pump with the R100 or by pressing .
3. Switch on the on/off switch.
4. Start the pump via bus signal.
The pump has stopped due to a fault.
Electricity supply failure.
Check that the electricity supply falls within the specified range.
Pump blocked and/or impurities in the pump.
Dismantle and clean the pump.
The pump may be defective.
Use the R100 for fault finding, see section 9.5.3 Fault indica- tions. Replace the pump or call Grund­fos Service for assistance.
The pump is running but has a fault.
The pump has a fault, but is able to operate.
Try to reset the fault indication by briefly switching off the electricity supply or by pressing the button
, or . Use the R100 for fault finding, see section 9.5.3 Fault indica- tions. In case of repeated faults, contact Grundfos Service.
The pump has been set to stop and has a fault.
The pump has a fault, but is able to operate (has been set to STOP).
Page 18
18
(QJOLVK86
10.1 Checking the module
Noise in the system.
Air in the system. Vent the system.
The flow is too high.
Reduce the setpoint and possibly change over to AUTO
ADAPT or
constant pressure.
The pressure is too high.
Reduce the setpoint and possibly change over to AUTO
ADAPT or
proportional pressure.
Noise in the pump.
The inlet pressure is too low.
Increase the inlet pressure and/or check air volume in the expan­sion tank (if installed).
Air in the pump.
Set the pump to "MAX" by contin­uously pressing the button or with the R100. After venting, set the pump back to normal duty by pressing the buttons , or with the R100. Note: The pump must not run dry.
Indicator
lights
Fault Cause Remedy
Green Red
11RWH
The R100 can also be used for fault finding.
Illustration Action
TM03 0892 0705
1. Remove the module cover.
2. Check the LEDs. When the pump is switched on and the module is correctly mounted, the left LED must be flashing and the right LED must be permanently on.
3. Refit the module cover.
Flashing
Permanently on
Page 19
19
(QJOLVK86
11. Megging
Megging of an installation incorporating a GRUNDFOS MAGNA pump is not allowed, as the built-in electronics may be damaged. If megging of the pump is necessary, the pump should be electrically separated from the installation.
Procedure:
Warning
Before removing the cables, the electricity must be switched off.
Megging of the pump
Step Illustration Action
1
TM03 0908 0705
• Switch off the electricity supply.
• Open the conn ection box.
2
TM03 0909 0705
• Remove the supply wires L an d N a nd the earth ground wire (GND).
3
TM03 0910 0705
• Short-circuit the wires L and N using a wire.
• Test between the wires L/N and earth ground (GND).
Test voltage: Max. 1000 VAC/1500 VDC. Maximum permissible leakage current < 35
mA. Note: Never test between the supply wires
(L and N).
4
TM03 0911 0705
Test the cable to the pump.
• Pull the plug out of the pump and test again.
• Refit the suppl y wires L and N and the earth ground wire (GND).
• Switch on the electricity supply.
LN
GND
GND
L/N
GND
L/N
Page 20
20
(QJOLVK86
12. Technical data
Supply voltage
1 x 208 - 230 V +/- 10 %, 50/60 Hz.
Motor protection
The pump requires no external motor protection.
Enclosure class
IP44.
Insulation class
F.
Relative air humidity
Maximum 95 %.
Ambient temperature
+32 °F (+0 °C) to +95 °F (+35 °C).
Temperature class
TF110 to EN 60335-2-51.
Liquid temperature
+35 °F (+2 °C) to +200 °F (+93 °C).
Maximum flow
Max. 50 gpm.
Maximum system pressure
Max. 145 psi.
Inlet pressure
Recommended inlet pressures:
• Min. 0.145 psi (0.10 bar ) at 167 °F (+ 75 °C).
• Min. 5.08 psi (0.35 bar) at 200 °F (+93 °C).
Sound pressure level
The sound pressure level of the pump is lower than 32 dB(A).
Inputs and outputs of a pump with relay module
Inputs and outputs of a pump with GENI module
13. Disposal
This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Signal output
Internal potential-free change-over contact. Maximum load: 250 V, 2 A, AC1. Minimum load: 5 V, 100 mA. Screened cable depending on signal level.
Input for exter­nal start/stop
External potential-free contact. Contact load: 5 V, 10 mA. Screened cable. Loop resistance: Maximum 130 :.
Inputs for max. and min. curves
External potential-free contact. Contact load: 5 V, 1 mA. Screened cable. Loop resistance: Maximum 130 :.
Input for analog 0-10 V signal
External signal: 0-10 VDC. Maximum load: 1 mA. Screened cable.
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485. Screened cable. Wire cross section:
0.25 - 1 mm
2
. Cable length: Maximum 3937 ft (1200 m).
Signal output
Internal potential-free change-over contact. Maximum load: 250 V, 2 A AC1. Minimum load: 5 V, 100 mA. Screened cable depending on signal level.
Input for exter­nal start/stop
External potential-free contact. Contact load: 5 V, 10 mA. Screened cable. Loop resistance: Maximum 130 :.
Page 21
21
(QJOLVK86
Master pump
TM03 0857 0605
Master definition
Page 22
22
(QJOLVK86
Slave pump
TM03 0856 0605
Page 23
*UXQGIRVFRPSDQLHV
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913 -227-3 500
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905-829-9 533 Telefax: +1-905-829-9512
México
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L.C.P. 66600 Phone: +52-81-8144-4000 Telefax: +52-81-8144-4010
Page 24
www.grundfos.com
Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence
The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.
L-MAG-TL-03 11.11
97758317 11.11
US
Repl. 10.11
© 2010 - 2011 Grundfos Pumps Corp.
ECM: 1083640
Loading...