14 / 15
3.3 Fault indications via R100 fault log
The table shows the fault log possibilities in prioritized order.
If two faults occurs at the same time, the fault with the highest priority will be shown!
* Depending on the expansion module.
Prior-
ity
Code
(faul
t log)
Fault indication
Pump
reaction
Cause Remedy Start after fault
R100 PMU 2000
151
Pump
blocked
Blocked Stopped • Motor, rotor, impeller or
pump blocked
• Fault in terminal box
• Disassemble pump and
remove blockage.
• Replace the terminal
box.
The fault must be reset manually before the pump can
run.
373
Internal
fault
Fault Stopped The terminal box current
limit has been exceeded
which may be caused by:
• Fault in the terminal
box
• Fault in the stator
• Replace the terminal
box.
• Replace the stator.
Pump will start automatically when the fault has disappeared and the red indicator light is no longer on.
The pump tries to restart
once every minute.
467
Overtemperature
Fault Stopped A too high temperature has
been measured in the
pump, which may be caused
by:
• Too high motor temperature due to stator fault
• Extremely high liquid
temperature
•Extremely high ambient temperature
• Fault in the terminal
box
• Replace the stator.
• Reduce the liquid temperature.
• Reduce the ambient
temperature.
• Replace the terminal
box.
Pump will start automatically when the fault has disappeared and the red indicator light is no longer on.
540
Undervoltage
Undervoltage
Stopped The supply voltage from
mains is too low.
Check that the supply voltage is in accordance with
the data on the nameplate.
Pump will start automatically when the fault has disappeared and the red indicator light is no longer on.
632
Overvoltage Overvoltage Stopped The supply voltage from
mains is too high.
Check that the supply voltage is in accordance with
the data on the nameplate.
Pump will start automatically when the fault has disappeared and the red indicator light is no longer on.
790
Internal
fault
No fault
indication
Pump is
running.
The terminal box registers
no signal from the HALL sensor in the stator.
• Replace the stator
• Replace the terminal
box.
When the fault has disappeared, the red indicator
light goes out automatically.
875
Internal
fault
No fault
indication
Pump is
running.
Too low DC voltage measured in the terminal box.
• Reset the fault indication.
• If the fault re-occurs, replace the terminal box.
When the fault has disappeared, the red indicator
light goes out automatically.
983
Internal
fault
No fault
indication
Pump is
running.
Fault in the storing of set
values (pressure) or measured values (hour counter)
in the internal memory of
the terminal box.
• Cut off the supply voltage, wait for approx. 1
minute, then cut in the
supply voltage again. A
new setpoint has now
been stored, and if no
fault is indicated, the
fault was temporary.
• If the fault re-occurs, replace the terminal box.
Once it has occurred, the
fault will be indicated periodically.
See "Remedy".
10 152
Fault in
module
communication
No fault
indication
Pump is
running.
The terminal box cannot
communicate with the
module fitted (GENI or LON).
(The fault also occurs if the
module is removed while
the pump is operating.)
• Check that the connection between module
and terminal box is OK.
See point 3 in section
B1.
When the fault has disappeared, the red indicator
light goes out automatically.
11 *
Fault in
module
No fault
indication
Pump is
running.
The terminal box has
received a feedback from
the expansion module fitted. There is a fault in the
expansion module.
• Replace the expansion
module.
When the fault has disappeared, the red indicator
light goes out automatically.