Grundfos LFE, LCSE Installation And Operating Instructions Manual

GRUNDFOS INSTRUCTIONS
LFE, LCSE
End-suction, frame-mounted pumps with integrated VFD End-suction, close-coupled, split-coupling pumps with integrated VFD
Installation and operating instructions
)UDQ©DLV&$
(VSD³RO0;
Table of contents
English (US)
Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Notice d'installation et de fonctionnement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Instrucciones de instalación y operación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
2
English (US) Installation and operating instructions
Original installation and operating instructions
These installation and operating instructions describe LFE, LCSE.
Sections 1-5 give the information necessary to be able to unpack, install and start up the product in a safe way.
Sections 6-30 give important information about the product, as well as information on service, fault finding and disposal of the product.
CONTENTS
Page
1. Limited warranty
2. General information
2.1 Symbols used in this document
2.2 Other important notes
3. Receiving the product
3.1 Unpacking the product
3.2 Inspecting the product
3.3 Temporary storage after delivery
4. Installing the product
4.1 Location
4.2 Horizontal pump foundation
4.3 Securing the base plate
4.4 Mechanical installation
4.5 Electrical connections
4.6 Motors
5. Starting up the product
5.1 Priming
5.2 Pre-start checklist
5.3 Motor direction of rotation
5.4 Starting the pump
5.5 Voltage and frequency variation
6. Storing and handling the product
7. Product introduction
7.1 Applications
7.2 Pumped liquids
7.3 Pump identification
8. Servicing the product
8.1 Maintaining the product
8.2 Lubricating the product
8.3 Disassembling the pump
8.4 Replacing the shaft seal (LCSE pumps)
8.5 Replacing the wear ring
8.6 Reassembling the pump
8.7 LFE, exploded view and parts list
8.8 LCSE, exploded view and parts list
9. Taking the product out of operation
9.1 General procedure
9.2 Short-term shutdown
9.3 Long-term shutdown
10. Fault finding
11. PACO MLE motors
11.1 Pumps without factory-fitted sensor
11.2 Pumps with pressure sensor
11.3 Settings
12. Installing the motor
12.1 Motor cooling
12.2 Outdoor installation
13. Electrical connection
13.1 Three-phase pumps, 3-10 hp
13.2 Three-phase pumps, 15-30 hp
13.3 Signal cables
10
10 10 10 10 10
10 11
11 11 11
11
11 11 13 14 14 14 15 16
17
17 17 17
18 20
20 20 20
20
20 20
21
21 23 26
13.4 E-pump electrical connections
13.5 Bus connection cable
14. Modes
14.1 Overview of modes
14.2 Operating mode
14.3 Control mode
15. Setting up the pump
15.1 Factory setting
16. Setting by means of control panel
16.1 Setting of operating mode
16.2 Setpoint setting
4 5
5 5
5
5 5 5
6
6 6 6 7 9 9
17. Setting by means of R100
17.1 Menu OPERATION
17.2 Menu STATUS
17.3 Menu INSTALLATION
17.4 Typical display settings for constant-pressure E-pumps
17.5 Typical display settings for analog-input E-pumps
17.6 Grundfos GO Remote
18. Setting by means of PC Tool E-products
19. Priority of settings
20. External forced-control signals
20.1 Start/stop input
20.2 Digital input
21. External setpoint signal
22. Bus signal
23. Other bus standards
24. Indicator lights and signal relay
25. Emergency operation (only 15-30 hp)
26. Insulation resistance
27. Maintaining and servicing the motor
27.1 Cleaning of the motor
27.2 Relubrication of motor bearings
27.3 Replacement of motor bearings
27.4 Replacement of varistor (only 15-30 hp)
27.5 Service parts and service kits
28. Technical data
28.1 Technical data - three-phase pumps, 3-10 hp
28.2 Technical data - three-phase pumps, 15-30 hp
28.3 Other technical data
29. Installing the product in the USA and Canada
29.1 Electrical connection
29.2 General considerations
30. Disposing of the product
26 28
28
28 28 29
29
29
29
29 30
30
32 33 35 42 43 44
45 45 45
45 46
46 47 47 47 49 50 50
50 50 50 51 51
51
51 52 53
54
54 54
54
English (US)
3
English (US)
Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
The use of this product requires experience with and knowledge of the product. Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety. Children must not use or play with this product.
CAUTION
Successful operation depends on careful attention to the procedures described in this manual. Keep this manual for future use.
1. Limited warranty
New equipment manufactured by seller or service supplied by seller is warranted to be free from defects in material and workmanship under normal use and service for a minimum of twelve (12) months from date of installation, eighteen (18) months from date of shipment, unless otherwise stated in product warranty guide (available upon request). In the case of spare or replacement parts manufactured by seller, the warranty period shall be for a period of twelve months from shipment. Seller's obligation under this warranty is limited to repairing or replacing, at its option, any part found to its satisfaction to be so defective, provided that such part is, upon request, returned to seller's factory from which it was shipped, transportation prepaid. Parts replaced under warranty shall be warranted for twelve months from the date of the repair, not to exceed the original warranty period. This warranty does not cover parts damaged by decomposition from chemical action or wear caused by abrasive materials, nor does it cover damage resulting from misuse, accident, neglect, or from improper operation, maintenance, installation, modification or adjustment. This warranty does not cover parts repaired outside seller's factory without prior written approval. Seller makes no warranty as to starting equipment, electrical apparatus or other material not of its manufacture. If purchaser or others repair, replace, or adjust equipment or parts without seller's prior written approval, seller is relieved of any further obligation to purchaser under this paragraph with respect to such equipment or parts, unless such repair, replacement, or adjustment was made after seller failed to satisfy within a reasonable time seller's obligations under this paragraph. Seller's liability for breach of these warranties (or for breach of any other warranties found by a court of competent jurisdiction to have been given by seller) shall be limited to: (a) accepting return of such equipment exw plant of manufacture, and (b) refunding any amount paid thereon by purchaser (less depreciation at the rate of 15 % per year if purchaser has used equipment for more than thirty [30] days), and canceling any balance still owing on the equipment, or (c) in the case of service, at seller's option, redoing the service, or refunding the purchase order amount of the service or portion thereof upon which such liability is based.
These warranties are expressly in lieu of any other warranties, express or implied, and seller specifically disclaims any implied warranty of merchantability or fitness for a particular purpose, and in lieu of any other obligation or liability on the part of the seller whether a claim is based upon negligence, breach of warranty, or any other theory or cause of action. In no event shall seller be liable for any consequential, incidental, indirect, special or punitive damages of any kind. For purposes of this paragraph, the equipment warranted shall not include equipment, parts, and work not manufactured or performed by seller. With respect to such equipment, parts, or work, seller's only obligation shall be to assign to purchaser the warranties provided to seller by the manufacturer or supplier providing such equipment, parts or work. No equipment furnished by seller shall be deemed to be defective by reason of normal wear and tear, failure to resist erosive or corrosive action of any fluid or gas, purchaser's failure to properly store, install, operate, or maintain the equipment in accordance with good industry practices or specific recommendations of seller, including, but not limited to seller's installation and operation manuals, or purchaser's failure to provide complete and accurate information to seller concerning the operational application of the equipment.
4
2. General information
3. Receiving the product
2.1 Symbols used in this document
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
The text accompanying the three hazard symbols DANGER, WARNING and CAUTION will be structured in the following way:
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
Example
DANGER
Electric shock
Death or serious personal injury.
- Before starting any work on the product, make sure that the power supply has been switched off and that it cannot be accidentally switched on.
2.2 Other important notes
3.1 Unpacking the product
WARNING
Overhead load
Death or serious personal injury
- Do not lift the unit by the eye bolts on the motor. Unload and handle the unit with a sling.
3.2 Inspecting the product
• Check that the product received is in accordance with the order.
• Check that the voltage, phase and frequency of the product match the voltage, phase and frequency of the installation site. See section 7.3 Pump identification.
• Check the product for defects and damage immediately upon arrival. Any accessories ordered will be packed in a separate container and shipped with the product.
• If any equipment is damaged in transit, promptly report this to the carrier's agent. Make complete notations on the freight bill.
3.3 Temporary storage after delivery
• If the product is not to be installed and operated immediately after receiving it, store it in a clean, dry area at a moderate ambient temperature.
• Rotate the shaft by hand periodically, at least weekly, to coat the bearing with lubricant to retard oxidation and corrosion.
• Follow the motor manufacturer's storage recommendations where applicable.
• During storage and transport maintain an ambient temperature from -13 to +158 °F (-25 to +70 °C) for the E-motor. At temperatures below the prescribed temperature, the E-motor must be equipped with a anti-condensation heater. This could be an external heating element or an incorporated functionality of the E-motor.
English (US)
A blue or grey circle with a white graphical symbol indicates that an action must be taken to avoid a hazard.
A red or grey circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
Notes or instructions that make the work easier and ensure safe operation.
5
English (US)
GroutBase plate
Finished grouting
0.75 - 1.25 in. allowance
(20-32 mm)
for grout
Formwork
Pipe sleeve
Washer
Lug
Top foundation
Wedges or shims left in place
0.25 in.
4. Installing the product
4.3 Securing the base plate
4.1 Location
• Locate the pump as close as possible to the liquid supply. Use the shortest and most direct inlet pipe practical. Refer to section 4.4.2 Inlet pi pe.
• Locate the pump below system level wherever possible. This will facilitate priming, assure a steady liquid flow, and provide a positive inlet pressure.
• The net positive suction head (NPSH) available must always be equal to or exceed the required NPSH specified on the pump performance curve. Make sure the required NPSH is provided at the inlet.
• Always allow sufficient accessibility space for maintenance and inspection. Provide a clearance of 24 in. (610 mm) with ample head room for use of a hoist strong enough to lift the product.
• Electrical characteristics must match those specified on the motor nameplate, within the limits covered in section
5. Starting up the product.
• Do not expose the product to sub-zero temperatures to prevent the pumped liquid from freezing and to prevent damage to the e-motor. If there is frost during shutdown periods, see sections 5. Starting up the product and 9.2 Short-
term shutdown.
4.2 Horizontal pump foundation
Install horizontal pumps permanently on a firm, raised concrete foundation of sufficient size to dampen any vibration and prevent any deflection or shaft misalignment. The foundation may float on springs or be a raised part of the equipment room floor.
Proceed like this:
1. Pour the foundation without interruption to 0.75 - 1.5 in. (20-
35 mm) below the final pump level. Leave the top of the foundation rough. Then clean and wet it down.
2. Score and groove the top surface of the foundation before the
concrete sets to provide a suitable bonding surface for the grout.
3. Place anchor bolts in pipe sleeves for positioning allowance.
See fig. 1.
4. Allow enough bolt length for grout, lower base plate flange,
nuts, and washers.
5. Allow the foundation to cure several days before proceeding
to install the pump.
LFE pumps require grouting in order to ensure a stable pump and motor shaft alignment.
LCSE pumps do not require alignment or grouting.
When the raised concrete foundation has been poured and allowed to set, proceed as follows:
1. Lower the pump base plate over the anchor bolts and rest it on loose adjustment wedges or shims placed near each anchor bolt and at intervals not exceeding 24 in. (610 mm) along each side.
2. Place the shims or wedges so that they raise the bottom of the base 0.75 - 1.25 in. (20-32 mm) above the foundation, allowing clearance for grout.
3. Level the pump shaft, flanges, and base plate using a spirit level, adjusting the wedges or shims, as required.
4. Make sure that the pipes can be aligned to the pump flanges without placing any strain on either flange.
5. For LFE, after pump alignment has been established, put nuts on foundation bolts and tighten them just enough to keep the base plate from moving.
6. Construct a formwork around the concrete foundation and pour grout inside the base plate, as shown in fig. 1. The grout will compensate for uneven foundation, distribute the weight of the pump, and prevent shifting.
TM 05 4775 4713
Fig. 1 Anchor bolt installation
Use an approved, non-shrinking grout.
6
7. Allow at least 24 hours for this grout to set before proceeding with pipe connections.
8. After the grout has thoroughly hardened, check the foundation bolts and tighten them if necessary. Recheck the pump alignment after tightening the foundation bolts.
4.4 Mechanical installation
Eccentric
reducer
Concentric
reducer
Tapered side is down
Air pocket
Correct
Wrong
4.4.1 Piping
Do not let the pump support the pipes. Use pipe hangers or other supports at proper intervals to provide pipe support near the pump.
• Make sure that both the inlet and outlet pipes are independently supported and properly aligned so that no strain is transmitted to the pump when flange bolts are tightened.
• Make sure the pipes are as straight as possible, so as to avoid unnecessary bends and fittings. Where necessary, use 45 ° or long-sweep 90 ° pipe bends to decrease friction loss.
• Where flanged joints are used, make sure that inside diameters match properly and that mounting holes are aligned.
• Do not apply force to pipes when making any connections!
4.4.2 Inlet pipe
The inlet pipe must be selected and installed in a manner that minimizes pressure loss and permits sufficient liquid flow into the pump during starting and operation.
Observe the following precautions when installing the inlet pipe:
At no point must the diameter of the inlet pipe be smaller than that of the pump inlet port.
• If possible, run a horizontal inlet line along an even gradient. We recommend a gradual upward slope to the pump under suction lift conditions, and a gradual downward slope for positive inlet pressure conditions.
• Avoid any high points, such as pipe loops (see fig. 3), as this may create air pockets and throttle the system or cause erratic pumping.
• Install a gate valve in the inlet line to be able to isolate the pump during shutdown and maintenance, and to facilitate pump removal. Where two or more pumps are connected to the same inlet line, install two gate valves to be able to isolate each pump from the line.
• Always install gate or butterfly valves in positions that prevent air pockets.
Do not use globe valves, particularly when NPSH is critical.
• During pumping operation, the valves on the inlet line must always be fully open.
• Install properly sized pressure gauges in the tapped holes on the pump inlet and outlet flanges. Pressure gauges will enable the operator to monitor the pump performance and determine whether the pump conforms to the parameters of the performance curve. If cavitation, vapor binding, or other unstable operating situations occur, pressure gauges will indicate wide fluctuation in the inlet and outlet pressures.
English (US)
Fig. 2 Inlet pipe
• Run the inlet pipe as direct as possible, and ideally, make sure the length is at least ten times the pipe diameter. A short inlet pipe can be the same diameter as the inlet port. A long inlet pipe must be one or two sizes larger (depending on length) than the inlet port, and with a reducer between the pipe and the inlet port.
• Use an eccentric reducer, with the tapered side down. See fig.
2.
Correct
TM06 1087 1614
Air pockets
Wrong
TM06 1088 1614
Fig. 3 Air pocket prevention
7
English (US)
4.4.3 Outlet pipe
• A short outlet pipe can be the same diameter as the pump outlet port. A long outlet pipe must be one or two sizes larger than the outlet port, depending on the length.
• An even gradient is best for long horizontal outlet pipes.
• Install a gate valve near the outlet port to be able to isolate the pump during shutdown and maintenance, and to facilitate pump removal.
• Any high points in the outlet pipe may entrap air or gas and thus retard pump operation.
• If water hammer occurs (i.e. if check valves are used), close the outlet gate valve before pump shutdown.
Shaft seals
The pumps are available with stuffing boxes with packing rings or mechanical shaft seals.
Stuffing boxes
The stuffing boxes are normally packed before shipment. If the pump is installed within 60 days after shipment, the packing
material will be in good condition for operation with a sufficient supply of lubricating liquid.
If the pump is stored for more than 60 days, it may be necessary to repack the stuffing boxes.
The stuffing box must be supplied at all times with a source of clean, clear liquid to flush and lubricate the packing rings.
Packing gland adjustment
With the pump running, adjust the packing gland to permit 40 to 60 drops per minute for shaft lubrication. After initial start up, additional packing and adjustment may be required.
Mechanical shaft seals
Mechanical shaft seals require no maintenance or adjustment. End suction pumps equipped with mechanical shaft seals are
matched to the operating conditions for which the pump was sold. Observe the following precautions to avoid shaft seal damage and obtain maximum shaft seal life.
4.4.4 Coupling alignment of LCSE pumps
No alignment of the pump and motor is required.
4.4.5 Coupling alignment of LFE pumps
The pump and motor were accurately aligned from factory, but handling during shipment could alter this pre-alignment.
1. If the pump and motor were shipped mounted on a common base frame as an assembly, remove the coupling guard.
2. Checking parallel alignment Place a straight edge across both coupling rims at the top, the bottom, and both sides. See fig. 4. After each adjustment, recheck all features of alignment. Parallel alignment is correct when the measurements show that all points of the coupling faces are within ± 0.005 in. (0.127 mm) of each other. If misalignment is detected, loosen the motor and shift or shim as necessary to re-align. Then re-tighten the bolts. Always align the motor to the pump as pipe strain will occur if the pump is shifted. Never reposition the pump on the base frame.
TM05 4794 2613
Fig. 4 Checking parallel alignment
Do not run the pump dry or against a closed valve! Dry running will cause seal failure within minutes.
Do not exceed the temperature or pressure limitations for the mechanical shaft seal used.
Clean and purge the inlet pipe in new installations before installing and operating pump. Pipe scale, welding slag and other abrasives can cause rapid shaft seal failure.
8
3. Checking angular alignment
Insert a pair of inside callipers or a taper gauge at four points at 90 ° intervals around the coupling. See fig. 5. Angular alignment is correct when the measurements show that all points of the coupling faces are within ± 0.005 in. (0.127 mm) of each other.
– If misalignment is detected, loosen the motor and shift or
shim as necessary to re-align. Then re-tighten the bolts. Always align the motor to the pump as pipe strain will occur if the pump is shifted. Never reposition the pump on the base frame.
Fig. 5 Checking angular alignment
• Check shaft seal alignment once again after final pipe connections to the pump have been made, motor wiring has been checked, correct direction of rotation has been established, and pipes have been filled with liquid.
• Leave the coupling guards off until the pump priming procedure has been completed.
• Install the coupling guards after installation has been completed to protect personnel from rotating machinery.
4.5 Electrical connections
DANGER
Electric shock
Death or serious personal injury
- The electrical installation must be carried out by a qualified electrician in accordance with local regulations and the manuals provided with the electrical accessories.
4.6 Motors
See also section 11. PACO MLE m otors. The motor control circuit must include the following components
in order to comply with the National Electrical Code:
Motor disconnecting device
• Install a motor disconnecting device that is capable of disconnecting both the controller (motor starter) and the motor from their source of power.
• Locate the disconnecting device in such a way that the controller (motor starter) can be seen from the disconnecting device. In all cases, the distance from the disconnecting device to the controller must be less than 50 ft (15.24 m).
• In most installations the disconnecting device will be a circuit breaker or fusible disconnect switch.
Motor short circuit and ground fault circuit interrupter
• A short circuit and ground fault circuit interrupter is usually a circuit breaker or fusible disconnect switch.
• Select the circuit breaker or fuse in accordance with applicable local and state electrical codes in addition to the National Electrical Code.
Motor controller with current protection (magnetic starter)
• Install these components in accordance with applicable local and state electrical codes in addition to the National Electrical Code.
DANGER
TM05 4795 2613
4.6.1 Wiring
• Mount the control panel or the motor starter(s) close to the pump to provide convenient control and easy installation.
• Wire panel or starter(s) to motor(s) and pilot device(s). Wires to the motor(s) must be sized for at least 125 % of the motor nameplate full load amps. We recommend AWG #16 Type THW stranded wire for wiring of pilot devices, such as float switches.
• Check that the voltage, phase and frequency of the incoming power source correspond to the voltage, phase and frequency of the motor(s).
• Make sure that the starters are suitable for operating the pump motors on the voltage, phase and frequency available.
Explosive environment
Death or serious personal injury
- Observe the rules and regulations generally or specifically imposed by the relevant responsible authorities or trade organizations in relation to running powered equipment in an explosive environment.
English (US)
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, be sure the power supply has been switched off and that it cannot be accidentally switched on.
9
English (US)
5. Starting up the product
5.3 Motor direction of rotation
5.1 Priming
• End suction pumps are non-self-priming, and must be completely primed, i.e. filled with liquid, before starting.
• If the pump will be operated with a positive inlet pressure, prime it by opening the inlet valve and allowing liquid to enter the pump housing. Open the air vents at this time, and make sure all air is forced out of pump by the liquid before closing the air vents.
• Rotate the shaft by hand to free entrapped air from the impeller passageways.
• If the pump will be operating with a suction lift, priming must be accomplished by other methods. Use foot valves or ejectors, or fill the pump housing and the inlet line manually with liquid.
Never run the pump dry in the hope that it will prime itself. The result will be serious damage to the shaft seals, pump wear rings and shaft sleeves.
5.2 Pre-start checklist
WARNING
Product failure
Death or serious personal injury
- Do not operate the product above the nameplate conditions.
Make the following inspections before starting your end suction pump:
1. Make sure the inlet and outlet pipes have been cleaned and flushed to remove dirt and debris.
2. Double check the direction of rotation is clockwise. Operating in reverse will destroy the impeller and shaft.
3. Make sure all wiring connections to the motor and starting device are in accordance with the wiring diagram.
4. If the motor has been in storage for a long time, either before or after installation, refer to the motor instructions before starting.
5. Check the voltage, phases, and frequency with the motor nameplate. Turn the impeller by hand to make sure it rotates freely.
6. Tighten the plugs in the gauge and drain holes. If the pump is fitted with pressure gauges, keep the gauge cocks closed when they are not in use.
7. Check the inlet and outlet pipes for leaks, and make sure all flange bolts are securely tightened.
Never check the motor direction of rotation unless the pump and motor couplings have been disconnected and physically separated. Failure to follow this instruction can result in serious damage to the pump and the motor if the direction of rotation is wrong.
5.4 Starting the pump
DANGER
Moving machine parts
Death or serious personal injury
- Mount an approved coupling guard before operating the product.
1. Install the factory-provided coupling guard on coupled products.
2. Fully open the gate valve (if any) in the inlet line, and close the gate valve in the outlet line.
3. Fill the inlet line with liquid and completely prime the pump.
4. Start the pump.
5. Immediately make a visual check of the pump and inlet pipe for pressure leaks.
6. Immediately after the pump has reached full operating speed, slowly open the outlet gate valve until complete system flow is achieved.
7. Check the outlet pipe for pressure leaks.
8. If the pump is fitted with pressure gauges, open gauge cocks and record pressure readings for future reference. Verify that the pump is performing in accordance with the parameters specified in the performance curves.
9. Check and record voltage, amperage per phase, and kilowatts, if a wattmeter is available.
5.5 Voltage a nd frequency variation
The motor will operate satisfactorily under the following voltage and frequency variations, but not necessarily in accordance with the standards established for operation under rated conditions:
• The voltage variation may not exceed 10 % above or below
the rating specified on the motor nameplate.
• The frequency variation may not exceed 5 % above or below
the motor rating.
• The sum of the voltage and frequency variations may not
exceed 10 % above or below the motor rating, provided the frequency variation does not exceed 5 %.
6. Storing and handling the product
See sections 3.3 T emporary storage af ter delivery, 9.2 Short-term
shutdown and 9.3 Long-term shutdown.
10
7. Product introduction
CAT#: 21-20709-133L01-25E1MS1
STOCK#: 91893522
SER#: 1971001000
GPM: 234
TDH: 88
MFD BY GRUNDFOS CBS INC 34014412
IMP DIA
5.11
:
This data booklet describes:
• LFE end-suction, frame-mounted pumps with integrated VFD
• LCSE end-suction, close-coupled, split-coupling pumps with integrated VFD.
7.1 Applications
We recommend the integrated VFD end suction pumps for these applications:
• commercial and industrial cooling systems
– pumping both primary and secondary cooling water
• condenser water systems
• district cooling systems
• water distribution systems
• irrigation systems.
7.2 Pumped liquids
Clean, thin, non-aggressive liquids, not containing solid particles or fibers. Do not pump liquids that will attack the pump materials chemically.
7.3 Pump identification
Pumps are identified by catalog and serial numbers (LFE nameplate shown in fig. 6). These numbers are stamped on the pump nameplate as shown in fig. 6, affixed to each pump volute casing, and should be referred to in all correspondence with Grundfos.
Fig. 6 Nameplate
8. Servicing the product
8.1 Maintaining the product
WARNING
Moving machine parts
Death or serious personal injury
- Before any inspection, maintenance, service or repair of the product, make sure the motor controls are in the "OFF" position, locked and tagged.
8.2 Lubricating the product
8.2.1 Lubricating the motor
Always follow the motor manufacturer's lubricating instructions, if they are available, and periodically check grease fittings and drain plugs for leaks. Use the standard lubrication interval. See the installation and operating instructions or the lubrication plate on the E-motor. If the lubricating instructions are not available, refer to the table below for recommended lubricating intervals.
Recommended lubricating intervals
Motor rpm Motor hp Operating conditions
Standard Severe Extreme
1750
and below
above 1750 all hp 6 mo 3 mo 3 mo
Standard conditi ons:
Operating 8 hours per day operation, normal or light load, clean air, 100 °F (37 °C), maximum ambient temperature.
Severe conditions:
Operating continuously 24 hours, shock loads or vibrations, poor ventilation, 100-150 °F (37-65 °C), ambient temperature.
Extreme conditions:
Continuous operation, heavy shocks or vibrations, dirt or dust in the air, extremely high ambient temperature.
TM 06 1036 1414
3.00-7.50 3 yrs 1 yr 6 mo 10-30 1-3 yrs 6 mo-1 yr 3 mo
English (US)
11
English (US)
8.2.2 Lubricating the pump Grease lubrication
In the standard configuration, LFE pumps with horizontal bearing frames have sealed-for-life bearings (requiring no lubrication). For customized pumps with regreasable bearings, use an approved grease and proceed as described below.
Approved grease lubricants
Manufacturer Lubricant
Shell Dolium
Exxon Polyrex
Chevron
SRI GreaseNLGI 2
Black Pearl - NLGI 2
p
R
p
Philips Polytac
Texaco Polystar RB
• Remove the drain plug, if any, and the filler plug. Add clean lubricant until grease appears at the drain hole or along the pump shaft. On pumps with drain hole, all old grease can be purged. In such cases, the drain hole must be left unplugged for several minutes during pump operation to allow excess grease to be forced out.
• Lubricate the pump bearings at 1-3 month intervals, depending on the severity of the environment. Pumps in a clean, dry, moderate temperature (100 °F (37 °C) maximum) environment must be regreased at 3-month intervals.
Do not over-grease! Too much grease can cause overheating and premature bearing failure.
Oil lubrication
LFE pumps with oil lubricated bearings are fitted with a transparent reservoir, a constant-level oiler, that maintains the oil level about the centerline of the bearing. See fig. 7.
• Follow a regular maintenance program. When necessary, renew the oil supply in the reservoir of the constant-level oiler.
• Change the oil after the first 200 hours of operation. To change the oil, remove the drain plug at the bottom of the bearing cover and the filler plug, that also acts as a vent plug, at the top of the bearing frame. After draining the oil, replace the fittings and refill the reservoir with an acceptable oil from the table List of acceptable oil lubricants on page 12. After the first oil change, the oil must be changed again at 2000 hours and then at intervals of 8000 hours or once a year, thereafter.
Oil level
Fig. 7 Oil lubrication
List of acceptable oil lubricants
Lubricant manufacturer Bearing oil brand name
Aral Refining Co.
British Petroleum Co.
Calypsol Oil Co.
Aral Oil CMU
Aral Oil TU 518
BP Energol TH 100-HB
Calypsol Bison Oil
SR 25 or SR 36
Chevron
Standard Oil Co.
Hydraulic Oil 11
Circulating oil 45
Esso-Mar 25
Esso Corp
Teresso 47
Esstic 50
Fina Oil Co.
Gulf Refining Co.
Socony Mobil Oil Co.
Fina hydran 34 Fina Cirkan 32
Gulf Harmony 47
Gulf Paramount 45
Vac hlp 25
Mobulix D.T.E. 25
Shell Oil Co. Shell Tellus oil 29
Sundco Oil Co. Sunvis 821
The Texas Co.
Texaco ursa oil P 20
Dea viscobil sera 4
TM06 1089 1614
12
8.3 Disassembling the pump
8.3.1 Preparations before disassembling the pump
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, be sure the power supply has been switched off and that it cannot be accidentally switched on.
CAUTION
Toxic material
Minor or moderate personal injury.
- Wash down the pump before doing any work on it.
DANGER
Hot, caustic, flammable or toxic materials, including vapors
Death or serious personal injury
- Be extremely cautious when venting and/or draining hazardous liquids.
- Wear protective clothing when there are caustic, corrosive, volatile, flammable, or hot liquids.
- DO NOT breathe toxic vapors.
- DO NOT allow sparks, open fire, or hot surfaces near the equipment.
Complete disassembly instructions are outlined below. Proceed only as far as required to perform the maintenance work needed.
1. Switch off the power supply.
2. Drain the system.
3. Flush the system, if necessary.
4. For closed coupled units: Remove the motor fixation bolts.
8.3.2 Disassembling the liquid end
1. Remove the pump housing screws (8B).
2. Remove the back pull-out bearing frame (20Y) from the pump housing (1A).
3. Remove the impeller screw (8A).If necessary, use a strap wrench around the impeller or shaft to prevent rotation.
8.3.3 Disassembling the bearing frame (LFE)
1. Remove the slinger (13G).
2. Remove the lip seal(s) (14S), if any.
3. Remove the bearing housing locking ring (61K).
4. Press or tap on the pump end of the bearing-shaft assembly until one bearing is out.
5. When one bearing is out, remove the second locking ring (61F), then remove the complete bearing-shaft assembly from the bearing housing.
6. Remove the shaft locking ring (61C) and press off the bearings.
7. Press new bearings onto the shaft; remember to press only on the inner race of the bearings while pressing them on.
8. Assemble the bearing frame in the reverse procedure used for disassembling.
9. Observe the following when reassembling the bearing frame. – Replace the lip seals (14S) if they are worn or damaged. – Replace the bearings (18A) and (18B) if they are loose,
rough or noisy when rotated.
– Check the shaft (6A) for shaft runout at the sleeve (5A) area.
Maximum permissible runout is 0.002 in. (0.0508 mm) total indicator runout.
English (US)
WARNING
Moving machine parts
Death or serious personal injury
- Do not insert a screwdriver between the impeller vanes to prevent rotation.
4. Use an appropriately sized puller aligned behind the impeller vanes to remove the impeller (3A) from the shaft (6A).
5. Remove the impeller key (12A).
6. Remove the back plate screws (8D). Remove the back plate (2K) and the seal housing (26P).
7. Place the seal housing on a flat surface and press out the shaft seal (14A).
8. If the shaft sleeve (5A) requires replacement, heat it evenly to approximately 350 °F (176 °C) to loosen the thread-locking fluid. Twist the sleeve off the shaft (6A).
13
English (US)
8.4 Replacing the shaft seal (LCSE pumps)
1. Complete preparations listed in section 8.3 Disassembling the
pump.
2. Remove the coupling guard screws (8E).
3. Remove the coupling guard (34F).
4. Remove the nut (35E) and the bolt (8E) that hold the coupling halves together.
5. Pry apart the coupling halves (23D), remove the coupling key (12B).
Mark or measure the original position of the pump coupling on the motor side.
6. For pumps with lubrication lines, unscrew the tubing connector from the pipe tee of the air vent assembly. Thread sealing compound was applied to the threads during factory assembly, and the resulting bond may retard but will not prevent manual disassembling.
7. Remove the seal housing cap screws and slide the seal housing (2N) up the shaft to remove it.
8. Remove the shaft seal (14A) manually from the shaft (6A). Apply water-soluble lubricant to the shaft, if necessary, to ease the removal of the shaft seal. Pull the seal head assembly manually from the shaft, using a slight twisting motion (as necessary) to loosen bellows from shaft.
9. Remove and discard the shaft seal spring and the shaft seal retainer.
10. Remove and discard the shaft seal seat from the seal housing (2N) and thoroughly clean the inside cavity of the seal housing.
11. The interior surface of the bellows on a new shaft seal is coated with a bonding agent that adheres to the motor shaft. When the old shaft seal is removed, the bonding agent no longer exists and the bellows may crack or split during removal. We always recommend that you install a new mechanical shaft seal if it becomes necessary to remove the existing shaft seal from the shaft.
12. Clean and lubricate the shaft (6A) with a water-soluble lubricant and make sure no sharp edges can cut or scratch the bellows of the new shaft seal.
13. Press the new shaft seal seat firmly into the seal housing. Avoid direct contact between the seal face and metallic or abrasive objects, and wipe the seal face clean after installation to ensure an abrasive-free sealing surface.
14. Slide the new shaft seal (14A) onto the shaft by applying even pressure to the shaft seal.
15. Install the shaft seal housing (2N) on the shaft.
16. See the reassembly instructions in section 8.6 Reassembling
the pump.
8.5 Replacing the wear ring
1. Complete preparations in sections 8.3.1 Preparations before
disassembling the pump and 8.3.2 Disassembling the liquid end.
2. Remove the rotating assembly.
3. Remove the pump housing (1A) from the pipes, if necessary, to facilitate easy access to the interior of the pump housing. If necessary, remove the flange bolts at the pipes.
4. Remove a worn wear ring (4A) by drilling two holes slightly smaller than the width of the wear ring into the exposed edge of the wear ring. Insert a chisel into the holes to completely sever the wear ring at the holes and break the wear ring into two halves for easy removal.
5. Clean the wear ring cavity in the pump housing prior to installing a new wear ring to ensure a properly aligned fit.
6. To reassemble, press fit the new wear ring squarely into the pump housing cavity. Tap the wear ring into place to make sure it is pressed home into the cavity.
Do not use metal tools on the wear ring surfaces. Use only rubber, rawhide, wood or other soft material to prevent damage to the wear ring.
8.6 Reassembling the pump
WARNING
Moving machine parts
Death or serious personal injury
- Reinstall approved coupling guards and make sure they are in place prior to operation.
1. Clean all parts before reassembly.
2. Refer to the parts list to identify required replacement items.
3. Specify the pump serial or catalog number when ordering parts.
4. Reassemble the pump in the reverse procedure used for disassembling.
5. Observe the following when reassembling the pump: – All mechanical seal components must be in good condition
or leakage may result. We recommend that you replace the complete shaft seal.
– Install new shaft sleeves by bonding them to the shaft with a
thread-locking fluid.
6. Re-install the coupling guards on coupled pumps.
14
8.7 LFE, exploded view and parts list
English (US)
TM06 6570 1816
Pos. Description Pos. Description Pos. Description
1A Pump housing 11F Gasket 20A Base plate 2K Backplate 12A Key 20Y Bearing frame 3A Impeller 12B Key 23A Coupling hub 4A Wear ring 13G Slinger 26P Seal housing 4F* Balance wear ring 14A Shaft seal 34A Coupling guard 5A Shaft sleeve 14S Lip seal 61C Locking ring 6A Shaft 16A Drain plug 61F Locking ring 8D Cap screw 18A Bearing, inboard 61K Locking ring 10A Washer 18B Bearing, outboard 65A Motor 11A Ga ske t
* If applicable
15
English (US)
8.8 LCSE, exploded view and parts list
Pos. Description Pos. Description
1A Pump housing 15A Locating ring 2N Shaft seal housing 16A Drain plug 3A Impeller 17E O-ring 4A Wear ring 20A+20B Base plate rails 4F Balance wear ring 20C Base plate 6A Pump shaft 20D Pump support 8B Cap screw 21A Motor stool 8C Screw 22A Stud 8D Screw 23D Coupling halves 8E Bolt 24H Bushing 8F Screw 34A Washer 8G Screw 34B Washer 8H Cap screw 34C Washer 8I Cap screw 34D Washer 8J Screw 34E Washer 8N Screw 34F Coupling guard 11A Ga ske t 35 E Nu t 12A Key 35F Nut 12B Key 65A Motor 14A Shaft seal
TM06 4401 2215
16
9. Taking the product out of operation
The following shutdown procedures will apply for the L pumps in most normal shutdown situations. If the pump will be inoperative for a long time, follow the storage procedures in section 9.3 Long-
term shutdown.
9.1 General procedure
• Always close the outlet gate valve before stopping the pump. Close the valve slowly to prevent hydraulic shock.
• Disconnect and lock off the power to the motor.
9.2 Short-term shutdown
• For overnight or temporary shutdown periods under non­freezing conditions, the pump may remain filled with liquid. Make sure the pump is fully primed before restarting.
• For short or frequent shutdown periods under freezing conditions, keep the liquid moving within the pump housing and insulate or heat the pump exterior to prevent freezing.
9.3 Long-term shutdown
• For long shutdown periods, or to isolate the pump for maintenance, close the inlet gate valve. If no inlet valve is used and the pump has positive inlet pressure, drain all liquid from the inlet line to stop the liquid flow into the pump inlet. Remove the plugs in the pump drain and vent holes, as required, and drain all liquid from the pump housing.
• If there will be freezing conditions during long shutdown periods, completely drain the pump and blow out all liquid passages and pockets with compressed air. Freezing of the pumped liquid can also be prevented by filling the pump with antifreeze solution.
English (US)
17
English (US)
10. Fault finding
DANGER
Electric shock
Death or serious personal injury
- Before starting any work on the product, be sure the power supply has been switched off and that it cannot be accidentally switched on.
CAUTION
Toxic material
Minor or moderate personal injury.
- Wash down the pump before doing any work on it.
Fault Cause Remedy
1. Outlet pressure is too low. a) The speed of rotation is too low. Reestablish correct speed and direction of
b) The system pressure is lower than
anticipated. c) There is air or gas in the pumped liquid. Remove the air from the pumped liquid. d) The wear rings are worn. Replace the wear rings. e) The impeller is damaged. Repair or replace the impeller. f) The impeller diameter is too small. Replace the impeller with one of the correct
g) Wrong direction of rotation. Interchange two wires in the power supply. h) The pump has lost its prime. Re-prime the pump. i) There is insufficient NPSH. Restore required NPSH. j) Passages are restricted. Clean the impeller and pump housing
k) Joints or the stuffing box are leaking. • Tighten the joints or the stuffing box gland.
2. Insufficient inlet pressure. a) The inlet line is drawing air. Tighten the connections. b) The suction lift is too high or there is
insufficient NPSH. c) Air or gas is trapped in the pumped liquid. Remove the trapped air/gas from liquid. d) The strainer is clogged. Clean the strainer.
3. Noise level has increased. a) Poor alignment of the pump. Inlet and outlet pipe clamps are loose.
b) Cracked foundation. Repair the foundation. c) Worn ball bearings. • Replace the worn bearings.
d) The motor is unbalanced. • Disconnect the motor and operate it alone.
e) Hydraulic resonance. • Alter the resonant pipes.
DANGER
Hot, caustic, flammable or toxic materials, including vapors
Death or serious personal injury
- Be extremely cautious when venting and/or draining hazardous liquids.
- Wear protective clothing when there are caustic, corrosive, volatile, flammable, or hot liquids.
- DO NOT breathe toxic vapors.
- DO NOT allow sparks, open fire, or hot surfaces near the equipment.
rotation. Check the system curve.
diameter.
passages.
• Replace the shaft sleeve.
• Replace the gaskets.
Reduce the suction lift or restore required NPSH.
• Ensure proper alignment of the pump and the motor.
• Support the inlet and outlet pipes.
• Make sure the vibration dampers, flexible pipes, and conduit connectors are installed correctly.
• Renew the lubrication.
• Remove large pieces of debris, such as
wood or rags from the pump.
• Clean out the pump, if necessary.
• Change the pump speed.
• Insert a pulsation damper on the pump or the pipes.
• Insert a flow straightener.
18
Fault Cause Remedy
4. Insufficient flow. a) The pump is not primed. Prime the pump. b) The system pressure exceeds the shut off
pressure. c) The rotation speed is too low. Reestablish the correct speed of rotation. d) The suction lift is too high or there is
insufficient NPSH. e) The strainer or impeller is clogged. Clean the strainer and impeller passages. f) Wrong direction of rotation. Reestablish the correct direction of rotation. g) Leaking joints. Tighten the joints. h) Broken shafting or coupling. Repair or replace damaged parts. i) Closed inlet valve. If the inlet valve is closed, open it slowly. j) There is not enough inlet pressure for hot
or volatile liquids. k) Foot valve is too small. Replace the foot valve. l) Worn or damaged hydraulic parts. Repair or replace the worn parts. m) Excessive clearance between the wear
surfaces.
5. Pump loses its prime after starting.
6. Excessive power required. a) The speed of rotation is too high. Reduce the speed of rotation.
a) Joints or the stuffing box are leaking. • Tighten the joints or the stuffing box gland.
b) The suction lift is too high or there is
insufficient NPSH.
b) The pump is operating beyond its
recommended performance range.
c) The specific gravity or the viscosity of the
pumped liquid is too high.
d) The shaft is bent. Replace the shaft. e) Stuffing-boxes too tight. Retighten the stuffing box if possible.
f) Impeller clearances are too small causing
rubbing or worn wear surfaces.
g) There is an electrical or mechanical defect
in the motor.
h) The pump is restricted in its rotation. Remove any obstacles or replace any worn
i) Incorrect lubrication of the motor. Reestablish correct lubrication of the motor.
• Increase the liquid level on the inlet side.
• Open the isolating valve in the inlet pipe.
Reduce the suction lift or restore required NPSH.
Reestablish required inlet pressure.
See section 8.5 Replacing the wear ring.
• Replace the shaft sleeve.
• Replace the gaskets. Reduce the suction lift or restore required
NPSH.
Set the duty point in accordance with the recommended performance range.
If less flow is sufficient, reduce the flow on the outlet side, or fit the pump with a more powerful motor.
Alternatively, repair or replace the stuffing box. Adjust the impeller clearance, if possible, or
replace the wear ring. Contact your local service center for
diagnostics.
parts.
English (US)
19
English (US)
11. PACO MLE motors
Grundfos E-pumps have standard motors with integrated variable frequency drive. The pumps are for a single-phase or three-phase power supply connection.
12. Installing the motor
The pump must be secured to a firm, raised concrete foundation by means of bolts through the holes in the flange or baseplate.
11.1 Pumps without factory-fitted sensor
The pumps have a built-in PI controller and can be set up for an external sensor enabling control of the following parameters:
• pressure
• differential pressure
• temperature
• differential temperature
•flow rate
• liquid level in a tank. From the factory, the pumps have been set to control mode
uncontrolled. The PI controller can be activated by means of the Grundfos GO Remote or R100.
11.2 Pumps with pressure sensor
The pumps have a built-in PI controller and are set up with a pressure sensor enabling control of the pump outlet pressure.
The pumps are set to control mode controlled. The pumps are typically used to hold a constant pressure in variable-demand systems or differential pressure in closed-loop applications.
11.3 Settings
The description of settings apply both to pumps without factory­fitted sensor and to pumps with a factory-fitted pressure sensor.
Setpoint
The desired setpoint can be set in three different ways:
• directly on the pump control panel
• via an input for external setpoint signal
• by means of the Grundfos GO remote or wireless remote control.
Other settings
All other settings can only be made by means of the Grundfos GO Remote or R100.
Important parameters such as actual value of control parameter, power consumption, etc. can be read via the Grundfos GO remote or R100.
If special or customized settings are required, use Grundfos PC Tool E-products. Contact Grundfos for more information.
In order to retain the UL/cUL approval, follow the additional installation procedures on page 54.
12.1 Motor cooling
To ensure sufficient cooling of motor and electronics, observe the following requirements:
• Make sure that sufficient cooling air is available.
• Keep the temperature of the cooling air below 104 °F (40 °C).
• Keep cooling fins and fan blades clean.
12.2 Outdoor installation
When installed outdoors, the pump must be provided with a suitable cover to avoid condensation on the electronic components. See fig. 8.
TM00 8622 0101 - TM02 8514 0304
Fig. 8 Examples of covers
Remove the drain plug pointing downwards in order to avoid moisture and water build-up inside the motor.
Vertically mounted pumps are IP55 after removal of the drain plug. Horizontally mounted pumps change enclosure class to IP54.
20
13. Electrical connection
L1 L2 L3
L2
L1
L3 PE
For description of how to connect E-pumps electrically, see the following sections:
13.1 Three-phase pumps, 3-10 hp.
13.2 Three-phase pumps, 15-30 hp.
13.1 Three-phase pumps, 3-10 hp
DANGER
Electric shock
Death or serious personal injury
- The user or the installer is responsible for the installation of correct grounding and protection according to current national and local standards.
- All operations must be carried out by qualified personnel.
DANGER
Electric shock
Death or serious personal injury
- Disconnect all electric supply circuits and ensure these have been switched off for at least 5 minutes before making any connections in the pump terminal box. For instance, the signal relay may be connected to an external supply which is still connected when the power supply is disconnected.
The above warning is indicated on the motor terminal box by this yellow label:
13.1.1 Preparation
Before connecting the E-pump to the power supply, take the issues illustrated in the figure below into consideration.
ELCB
Fig. 9 Power supply-connected pump with power switch,
backup fuses, additional protection and protective grounding
13.1.2 Protection against electric shock - indirect contact
DANGER
Electric shock
Death or serious personal injury
- Ensure the pump is grounded in accordance with national regulations. As the leakage current of 5­10 hp (4-7.5 kW) motors is > 3.5 mA, take extra precautions when grounding these motors.
EN 50178 and BS 7671 specify the following precautions when leakage current > 3.5 mA:
• Install the pump in a stationary, permanent position.
• Connect the pump permanently to the power supply.
• Carry out the grounding connection as duplicate leads. Mark the protective ground leads with a yellow/green (PE) or
yellow/green/blue (PEN) color marking.
13.1.3 Backup fuses
For recommended fuse sizes, see section 28.1.1 Supply voltage.
13.1.4 Additional protection
If the pump is connected to an electric installation where an ground leakage circuit breaker (ELCB) is used as additional protection, use a circuit breaker of a type marked with the following symbols:
ELCB
This circuit breaker is type B. Take into account the total leakage current of all the electrical
equipment in the installation. Check the leakage current of the motor in normal operation; see
section 28.1.3 Leakage current. During start and at asymmetrical supply systems, the leakage
current can be higher than normal and may cause the ELCB to trip.
13.1.5 Motor protection
The pump requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking (IEC 34-11, TP 211).
13.1.6 Protection against voltage transients
TM00 9270 4696
The pump is protected against voltage transients by built-in varistors between the phases and between phases and ground.
English (US)
21
English (US)
L1 L2 L3
L1 L2 L3
13.1.7 Supply voltage and power supply
3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE. 3 x 208-230 V - 10 %/+ 10 %, 60 Hz, PE. The supply voltage and frequency are marked on the pump
nameplate. Make sure that the pump is suitable for the power supply of the installation site.
The wires in the terminal box must be as short as possible. Excepted from this is the protective ground lead which must be long enough that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
Fig. 10 Power connection
Cable glands
Cable glands comply with EN 50626.
• 2 x M16 cable gland
• 1 x M20 cable gland
• 2 x M16 knock-out cable entries.
DANGER
Electric shock, malfunction or damage
Death or serious personal injury; product damage or failure
- Replace power supply cable immediately if damaged. Only qualified personnel must replace it.
Grid types
Three-phase E-pumps can be connected to all grid types.
DANGER
Electric shock
Death or serious personal injury; product damage or failure
- Do not connect three-phase E-pumps to a power supply with a voltage between phase and ground of more than 440 V.
13.1.8 Start/stop of pump
The number of starts and stops via the power supply must not exceed 4 times per hour.
When the pump is switched on via the power supply, it will start after approximately 5 seconds.
If a higher number of starts and stops is desired, use the input for external start/stop when starting/stopping the pump.
When the pump is switched on via an external On/Off switch, it will start immediately.
Automatic restart
If a pump set up for automatic restart is stopped due to a fault, it will restart automatically when the fault has disappeared.
However, automatic restart only applies to fault types set up to automatic restart. These faults could typically be one of these faults:
• temporary overload
• fault in the power supply.
13.1.9 Connections
If no external On/Off switch is connected, connect terminals 2 and 3 using a short wire.
TM03 8600 2007
As a precaution, the wires to be connected to the following connection groups must be separated from each other by reinforced insulation in their entire lengths:
Group 1: Inputs
• start/stop terminals 2 and 3
• digital input terminals 1 and 9
• setpoint input terminals 4, 5 and 6
• sensor input terminals 7 and 8
• GENIbus terminals B, Y and A All inputs (group 1) are internally separated from the power-
conducting parts by reinforced insulation and galvanically separated from other circuits.
All control terminals are supplied with protective extra-low voltage (PELV), thus ensuring protection against electric shock.
Group 2: Output (relay signal, terminals NC, C, NO)
The output (group 2) is galvanically separated from other circuits. Therefore, the supply voltage or protective extra-low voltage can be connected to the output as desired.
22
13.1.10 Three-phase pumps, 3-10 hp
L1 L2 L3
L2
L1
L3 PE
Group 3: Power supply (terminals L1, L2, L3)
Group 2
13: GND (frame) 12: Analog output 11: Digital input 4 10: Digital input 3 1: Digital input 2 9: GND (frame) 8: +24 V 7: Sensor input B: RS-485B Y: Screen A: RS-485A
6: GND (frame) 5: +10 V 4: Setpoint input 3: GND (frame) 2: Start/stop
13.2 Three-phase pumps, 15-30 hp
DANGER
Group 3
Electric shock
Death or serious personal injury
- The user or the installer is responsible for the installation of correct grounding and protection according to current national and local standards.
- All operations must be carried out by qualified personnel.
English (US)
DANGER
Electric shock
Death or serious personal injury
- Disconnect all electric supply circuits and ensure these have been switched off for at least 5 minutes before making any connections in the pump terminal box. For instance, the signal relay may be connected to an external supply which is still connected when the power supply is disconnected.
CAUTION
Hot surface
Group 1
13.2.1 Preparation
Before connecting the E-pump to the power supply, take the issues illustrated in the figure below into consideration.
Minor or moderate personal injury
- Wear hand protection and use care when handling terminal box when product is operating. The surface of the terminal box may be above 158 °F (70 °C) when the pump is operating.
Fig. 11 Connection terminals
A galvanic separation must fulfill the requirements for reinforced insulation including creepage distances and clearances specified in EN 60335.
TM05 2985 0812
ELCB
TM00 9270 4696
Fig. 12 Power supply-connected pump with power switch,
backup fuses, additional protection and protective grounding
23
English (US)
13.2.2 Protection against electric shock - indirect contact
DANGER
Electric shock
Death or serious personal injury
- Ensure the pump is grounded in accordance with national regulations. As the leakage current of 5­10 hp (4-7.5 kW) motors is > 3.5 mA, take extra precautions when grounding these motors.
EN 61800-5-1 specifies that the pump must be stationary and installed permanently when the leakage current is > 10 mA.
One of the following requirements must be fulfilled:
• A single protective ground lead (7 AWG minimum copper)
Fig. 13 Connection of a single protective ground lead using
one of the leads of a 4-core power cable (7 AWG minimum)
• Two protective ground leads of the same cross-sectional area as the power supply leads, with one lead connected to an additional ground terminal in the terminal box.
13.2.3 Backup fuses
For recommended fuse sizes, see section 28.2.1 Supply voltage.
13.2.4 Additional protection
If the pump is connected to an electric installation where an ground leakage circuit breaker (ELCB) is used as additional protection, use a circuit breaker of a type marked with the following symbols:
ELCB
This circuit breaker is type B. Take into account the total leakage current of all the electrical
equipment in the installation. Check the leakage current of the motor in normal operation. See
section 28.2.3 Leakage current. During start and at asymmetrical supply systems, the leakage
current can be higher than normal and may cause the ELCB to trip.
13.2.5 Motor protection
The pump requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking (IEC 34-11, TP 211).
13.2.6 Protection against voltage transients
The pump is protected against voltage transients in accordance with EN 61800-3 and is capable of withstanding a VDE 0160 pulse.
TM04 3021 3508TM03 8606 2007
The pump has a replaceable varistor which is part of the transient protection.
Over time this varistor will become worn and will need to be replaced. When the time comes for replacement, Grundfos GO, R100 and PC Tool E-products will indicate this as a warning. See section 27. Maintaining and servicing the motor.
Fig. 14 Connection of two protective ground leads using two of
the leads of a 5-core power supply cable
Protective ground leads must always have a yellow/green (PE) or yellow/green/blue (PEN) color marking.
24
13.2.7 Supply voltage
3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE. The supply voltage and frequency are marked on the pump
nameplate. Make sure that the motor is suitable for the power supply of the installation site.
The wires in the terminal box must be as short as possible. Excepted from this is the protective ground lead which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
Torques, terminals L1-L3: Min. torque: 1.6 ft-lbs (2.2 Nm) Max. torque: 1.8 ft-lbs (2.4 Nm)
Fig. 15 Power connection
Cable glands
Cable glands comply with EN 50626.
• 1 x M40 cable gland
• 1 x M20 cable gland
• 2 x M16 cable gland
• 2 x M16 knock-out cable entries.
DANGER
Electric shock, malfunction or damage
Death or serious personal injury; product damage or failure
- Replace power supply cable immediately if damaged.
- Only qualified personnel must replace it.
Grid types
Three-phase E-pumps can be connected to all grid types.
13.2.8 Start/stop of pump
The number of starts and stops via the power supply must not exceed 4 times per hour.
When the pump is switched on via the power supply, it will start after approx. 5 seconds.
If a higher number of starts and stops is desired, use the input for external start/stop when starting/stopping the pump.
When the pump is switched on via an external On/Off switch, it will start immediately.
13.2.9 Connections
If no external On/Off switch is connected, connect terminals 2 and 3 using a short wire.
As a precaution, the wires to be connected to the following connection groups must be separated from each other by reinforced insulation in their entire lengths:
Group 1: Inputs
• start/stop terminals 2 and 3
• digital input terminals 1 and 9
• setpoint input terminals 4, 5 and 6
TM03 8605 2007 - TM04 3048 3508
• sensor input terminals 7 and 8
• GENIbus terminals B, Y and A All inputs (group 1) are internally separated from the power-
conducting parts by reinforced insulation and galvanically separated from other circuits.
All control terminals are supplied with protective extra-low voltage (PELV), thus ensuring protection against electric shock.
Group 2: Output (relay signal, terminals NC, C, NO)
The output (group 2) is galvanically separated from other circuits. Therefore, the supply voltage or protective extra-low voltage can be connected to the output as desired.
English (US)
DANGER
Electric shock
Death or serious personal injury; product damage or failure
- Do not connect three-phase E-pumps to a power supply with a voltage between phase and ground of more than 440 V.
25
English (US)
6: GND (frame) 5: +10 V 4: Setpoint input 3: GND (frame) 2: Start/stop
Group 2
Group 3
20: PT 100 B 19: PT 100 B 18: PT 100 A 17: PT 100 A 16: GND (frame) 15: +24 V 14: Sensor input 2 13: GND 12: Analog output 11: Digital input 4 10: Digital input 3 1: Digital input 2 9: GND (frame) 8: +24 V 7: Sensor input B: RS-485B Y: Screen A: RS-485A
Group 1
Group 3: Power supply (terminals L1, L2, L3)
13.3 Signal cables
• Use screened cables with a conductor cross-section of min. 28 AWG and maximum 16 AWG for external On/Off switch, digital input, setpoint and sensor signals.
• Connect the screens of the cables to frame at both ends with good frame connection. The screens must be as close as possible to the terminals. See fig. 17.
Fig. 17 Stripped cable with screen and wire connection
• Always tighten screws for frame connections whether a cable is fitted or not.
• Make the wires in the pump terminal box as short as possible.
13.4 E-pump electrical connections
13.4.1 Type key
DPI +T 0-6 G 1/2" 020 E, Set
Type Temperature sensor:
+T = with temperature Sensor Flow range [m Thread size Output signal:
020 = 4-20 mA O-ring material:
E = EPDM F = FKM
Set = Complete pressure transmitter
3
/h]
TM02 1325 0901
Fig. 16 Connection terminals
A galvanic separation must fulfill the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
26
TM05 2986 0812
13.4.2 Electrical connections
p
Dry-running sensor
Set to automatic resetting
Connection terminals on E-pump: 2 (Start/Stop) and 3 (GND)
3
2
1 x 200-240 VAC or
1 x 80-130 VAC
Jumper cable
Brown
Black
Blue
White
PIN 123 4
Fig. 18 Electrical connections
13.4.3 Connection of E-pump to LiqTec
2
1
4
Wire color Brown Grey Blue Black
Output
4-20 mA
Output
2 x 0-10 V
+ Not used - Not used
Pressure
+
signal
-*
Temperature
signal
English (US)
* Common ground for both pressure and temperature signal.
3
* Power supply (screened cable): SELV or PELV. * Grundfos will not be liable for damage or wear to products
TM04 7156 1610
caused by abnormal operating conditions, accident abuse, misuse unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions. Splicing of the supplied cable would void any warranty.
Fig. 19 Connection of E-pump to LiqTec
TM03 0437 5104
27
English (US)
Pump
Pump
Q
H
13.5 Bus connection cable
13.5.1 New installations
For the bus connection, use a screened 3-core cable with a conductor cross-section of 28-16 AWG.
• If the pump is connected to a unit with a cable clamp which is identical to the one on the pump, connect the screen to this cable clamp.
• If the unit has no cable clamp as shown in fig. 20, leave the screen unconnected at this end.
14. Modes
Grundfos E-pumps are set and controlled according to operating and control modes.
14.1 Overview of modes
Operating modes Normal Stop Min. Max.
Control modes Uncontrolled Controlled
A
1
2
Y
3
B
A
1
2
Y
3
B
Fig. 20 Connection with screened 3-core cable
13.5.2 Replacing an existing pump
• If a screened 2-core cable is used in the existing installation, connect it as shown in fig. 21.
A
1
Y
2
B
A
1
Y
2
B
Fig. 21 Connection with screened 2-core cable
• If a screened 3-core cable is used in the existing installation, follow the instructions in section 13.5.1 New installations.
Constant
curve
1)
For this control mode the pump is equipped with a pressure
TM02 8841 0904TM02 8842 0904
sensor. The pump may also be equipped with a temperature sensor in which case the description would be constant
Constant
pressure
1)
temperature in control mode controlled.
14.2 Operating mode
When the operating mode is set to Normal, the control mode can be set to controlled or uncontrolled. See section 14.3 Control
mode.
The other operating modes that can be selected are Stop, Min. or Max.
• Stop: the pump has been stopped
• Min.: the pump is operating at its minimum speed
• Max.: the pump is operating at its maximum speed. Figure 22 is a schematic illustration of minimum and maximum
curves.
Max.
Min.
TM00 5547 0995
Fig. 22 Minimum and maximum curves
The maximum curve can for instance be used in connection with the venting procedure during installation.
The minimum curve can be used in periods in which a minimum flow is required.
If the power supply to the pump is disconnected, the mode setting will be stored.
The Grundfos GO and R100 offer additional possibilities of setting and status displays. See section 17. Setting by means of
R100 for setting by means of R100. See section 17.6 Grundfos GO Remote for setting by means of Grundfos GO.
28
14.3 Control mode
H
Q
Q
H
set
H
Q
H
UncontrolledControlled
H
Q
Hset
Hset
2
p
14.3.1 Pumps without factory-fitted sensor
The pumps are factory-set to control mode uncontrolled. In control mode uncontrolled, the pump will operate according to
the constant curve set, fig. 23.
Fig. 23 Pump in control mode uncontrolled (constant curve)
16. Setting by means of control panel
Proportional pressure
The pump head is reduced at decreasing water demand and increased at rising water demand. See fig. 25.
This control mode is especially suitable in systems with relatively large pressure losses in the distribution pipes. The head of the pump will increase proportionally to the flow in the system to compensate for the large pressure losses in the distribution pipes.
The setpoint can be set with an accuracy of 0.33 ft (0.1 m). The head against a closed valve is half the setpoint, H
TM00 7746 1304TM00 7668 0404
set
English (US)
.
14.3.2 Pumps with pressure sensor
The pump can be set to one of two control modes, i.e. controlled and uncontrolled, fig. 24.
In control mode controlled, the pump will adjust its performance, i.e. pump discharge pressure, to the desired setpoint for the control parameter.
In control mode uncontrolled, the pump will operate according to the constant curve set.
Fig. 24 Pump in control mode controlled (constant pressure)
or uncontrolled (constant curve)
15. Setting up the pump
15.1 Factory setting
Pumps without factory-fitted sensor
The pumps have been factory-set to control mode uncontrolled. The setpoint value corresponds to 100 % of the maximum pump performance (see data sheet for the pump).
Pumps with pressure sensor
The pumps have been factory-set to control mode controlled. The setpoint value corresponds to 50 % of the sensor measuring range (see sensor nameplate).
TM05 7909 1613
Fig. 25 Proportional pressure
This control mode requires a factory-fitted differential-pressure sensors as shown in the example below:
Example
• Factory-fitted differential-pressure sensor.
Fig. 26 Proportional pressure
16.1 Setting of operating mode
Settings available:
•Normal
•Stop
•Min.
•Max.
Start/stop of pump
Start the pump by continuously pressing until the desired setpoint is indicated. This is operating mode Normal.
Stop the pump by continuously pressing until none of the light fields are activated and the green indicator light flashes.
29
English (US)
H
Q
H
Q
0
6
3
[bar]
H
Q
Setting to Minimum
Press pump (bottom light field flashes). When the bottom light field is on, press for 3 seconds until the light field starts flashing.
To return to uncontrolled or controlled operation, press continuously until the desired setpoint is indicated.
Setting to Maximum
Press continuously to change to the maximum curve of the pump (top light field flashes). When the top light field is on, press
To return to uncontrolled or controlled operation, press continuously until the desired setpoint is indicated.
continuously to change to the minimum curve of the
Fig. 27 Minimum curve duty
for 3 seconds until the light field starts flashing.
16.2.2 Pump in control mode uncontrolled Example
In control mode uncontrolled, the pump performance is set within the range from minimum to maximum curve. See fig. 30.
TM00 7346 1304TM00 7345 1304TM00 7743 0904
TM00 7746 1304TM02 0936 0501
Fig. 30 Pump performance setting, control mode uncontrolled
17. Setting by means of R100
The pump is designed for wireless communication with Grundfos remote control R100.
Fig. 31 R100 communicating with the pump via infra-red light
Fig. 28 Maximum curve duty
16.2 Setpoint setting
Set the desired setpoint by pressing the button or . The light fields on the control panel will indicate the setpoint set.
See examples in sections 16.2.1 Pump in control mode controlled
(pressure control) and 16.2.2 Pump in control mode uncontrolled.
16.2.1 Pump in control mode controlled (pressure control)
Example
Figure 29 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 43 psi (3 bar). The setting range is equal to the sensor measuring range (see sensor nameplate).
Fig. 29 Setpoint set to 3 bar, pressure control
During communication, the R100 must be pointed at the control panel. When the R100 communicates with the pump, the red indicator light will flash rapidly. Keep pointing the R100 at the control panel until the red LED diode stops flashing.
The R100 offers setting and status displays for the pump. The displays are divided into four parallel menus (see fig. 39):
0. GENERAL (see operating instructions for the R100)
1. OPERATION
2. STATUS
3. INSTALLATION The figure above each individual display in fig. 39 refers to the
section in which the display is described.
30
Loading...
+ 130 hidden pages