We, Grundfos, declare under our sole responsibility that the product
LC/LCD 108, to which this declaration relates, is in conformity with these
Council directives on the approximation of the laws of the EC member
states:
— Machinery Directive (98/37/EC).
Standard used: EN 809: 2000.
— Low Voltage Directive (2006/95/EC).
Standards used: EN 60335-1: 2002 and EN 60335-2-51: 2003.
— EMC Directive (2004/108/EC).
Standards used: EN 61000-6-2 and EN 61000-6-3.
Bjerringbro, 15th December 2008
Niels Vinther
Technical Manager
2
CONTENTS
Page
1.General3
1.1Applications3
1.2Variants3
2.Location and mounting3
2.1Location4
2.2Mounting of LCD 108 for direct-on-line starting4
3.Systems for parallel operation with 3 float switches 4
3.1Electrical connection4
3.2Setting5
3.3Control panel7
3.4Battery back-up functions7
3.5Reset button and ON-OFF-AUTO selector switch8
4.Systems for parallel operation with 4 float switches 8
4.1Electrical connection8
4.2Setting9
4.3Control panel10
4.4Battery back-up functions11
4.5Reset button and ON-OFF-AUTO selector switch12
5.Systems for 100 % standby operation13
5.1Electrical connection13
5.2Setting13
5.3Control panel15
5.4Battery back-up functions15
5.5Reset button and ON-OFF-AUTO selector switch16
6.System for full-control operation17
6.1Electrical connection17
6.2Setting17
6.3Control panel19
6.4Battery back-up functions19
6.5Reset button and ON-OFF-AUTO selector switch20
7.Start-up21
8.Maintenance21
9.Technical data21
10.Fault finding chart22
11.Disposal22
Before beginning installation procedures, these
installation and operating instructions should be
studied carefully. The installation and operation
should also be in accordance with local regulations
and accepted codes of good practice.
1. General
The LCD 108 controller is designed for the control of pumps in
wastewater systems.
Type key:
1.1 Applications
The LCD 108 enables:
• control of two pumps based on signals from float switches,
• automatic pump changeover (even distribution of operating
hours on both pumps),
• selection of automatic test run during long periods of inactivity
(every 24 hours),
• battery back-up in case of mains supply failure (accessory for
certain variants),
• starting delay within the range from 0 to 255 sec. (random)
after returning from battery operation to mains operation
(resulting in an even mains load when several pumping
stations are started up at the same time),
• selection of automatic alarm resetting,
• selection of automatic restarting,
• setting of stop delays matching the actual operating
conditions,
• indication of liquid level,
• alarm indication of:
- inadmissibly high liquid level,
- overload (via motor protection relay),
- overtemperature (via PTC resistance or thermal switch in
motor),
- wrong phase sequence (only certain variants),
- mains supply failure (only certain variants),
- defective float switch.
As standard, the LCD 108 has one alarm output for common
alarm. Certain variants have an additional alarm output for
separate high-level alarm.
Furthermore, the controller incorporates a buzzer (only certain
variants).
1.2 Variants
The actual controller type, voltage variant, etc. are stated in the
type key on the nameplate situated on the side of the controller
cabinet.
The LCD 108 is available for direct-on-line starting.
The LCD 108 can be connected and set to operation/control in 4
different ways, see sections 3. to 6.:
• Section 3. Systems for parallel operation with 3 float switches.
(Electrodes can also be used.)
• Section 4. Systems for parallel operation with 4 float switches.
(Electrodes can also be used.)
• Section 5. Systems for 100 % standby operation.
• Section 6. System for full-control operation.
2. Location and mounting
ExampleLCD108400323 SMS
LCD = two-pump controller
108 = type designation
Phase voltage [V]
1 = single-phase
3 = three-phase
Maximum operating current per pump [A]
SMS = with SMS unit
Before starting any work on pumps used to pump
liquids which could be constituted as being
hazardous to health, thorough cleaning/venting of
pumps, pits, etc. must be carried out according to
local regulations.
Before making any connections in the LCD 108 or
work on pumps, pits, etc., it must be ensured that the
electricity supply has been switched off and that it
cannot be accidentally switched on.
The installation must be carried out by authorized personnel in
accordance with local regulations.
3
2.1 Location
22
12
T21
T11
T22
T12
H-NOH-COM
H-NC
G-NO
G-COM
G-NC
21
11
32
42
31
41
The LCD 108 controller and an EEx barrier, if
required, must not be installed in explosion hazard
areas.
Only float switches approved for use in explosion
hazard areas may be used. The float switches must
be connected via an EEx barrier, e.g. Grundfos
number 96440300.
The LCD 108 can be mounted at ambient temperatures ranging
from –30 °C to +50 °C.
Enclosure class: IP 65.
When installed outdoors, the LCD 108 must be placed in a
protective shed or cupboard.
The LCD 108 must not be exposed to direct sunlight.
2.2 Mounting of LCD 108 for direct-on-line starting
Before mounting, remove the transport protectors, if any, from
inside the cabinet.
Mount the LCD 108:
• on a plane wall surface,
• with the Pg cable entries pointing downwards
(additional Pg cable entries, if required, must be fitted in the
bottom plate of the cabinet),
• with four screws through the mounting holes in the back plate
of the cabinet. The mounting holes must be bored with a 4 mm
bore. Fit the screws into the mounting holes and tighten
securely. Fit the plastic caps supplied with the controller on the
screws (IP 65).
Figure 1 shows the terminals listed under positions 2 and 3.
3. Systems for parallel operation with 3 float
switches
Description (see also page 23 or 24):
The pumps are controlled by the liquid level in the pit.
• When the float switch, pos. 1, registers liquid, the first pump is
started.
• When the float switch, pos. 2, registers liquid, the next pump is
started.
• When the float switch, pos. 1, does not register any liquid, the
"stop delay" is initiated (can be set). After expiration of the
stop delay, both pumps are stopped.
• The pumps operate alternately.
The top float switch, pos. 3, activates the high-level alarm.
Before starting any work on pumps used to pump
liquids which could be constituted as being
hazardous to health, thorough cleaning/venting of
pumps, pits, etc. must be carried out according to
local regulations.
Before making any connections in the LCD 108 or
work on pumps, pits, etc., it must be ensured that the
electricity supply has been switched off and that it
cannot be accidentally switched on.
3.1 Electrical connection
Parallel operation with 3 float switches, pages 23 or 24.
Before starting work on the system, switch off the
supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. A1 on page 23.
The figures show all electrical connections required to connect
the LCD 108 for direct-on-line starting, parallel operation with 3 float switches.
Fig. A2 on page 24.
The figure shows all electrical connections required to connect
the LCD 108 for star-delta starting, parallel operation with 3 float switches.
• input for the PTC resistance/thermal switch of the
motor (T11-T21, T12-T22),
2
• output for external alarm device for high-level alarm
(H-NC, H-COM, H-NO) (only certain variants),
• output for external alarm device for common alarm
(G-NC, G-COM, G-NO).
Note: If the distance between the controller and pit exceeds
20 metres, it is not advisable to use electrodes as problems with
the signal values sent back to the controller may arise.
In such cases, it is recommended to use float switches.
Note: Cables of up to 100 metres can be connected between the
controller and the float switches.
4
TM01 4833 2308
The LCD 108 must be connected in accordance with
the rules and standards in force for the application in
question.
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the
electricity supply on which it will be used.
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65).
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, an external mains
switch must be installed.
Note: If the PTC resistance/thermal switch of the motor is
connected, the factory-fitted short-circuit jumper must be
removed (terminals T11-T21, T12-T22). For correct installation of
PTC resistor/thermal switch, see the installation and operating
instructions of the pump.
Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further
details can be found in the installation and operating instructions
for the pump in question.
Float switches placed in an explosion hazard area
must be connected via an EEx barrier, e.g. Grundfos
number 96440300.
The EEx barrier must not be installed in the explosion
hazard area.
Equipment used in explosion hazard areas must in
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in accordance
with local regulations.
Note: Float switches of the same type as Grundfos product
number 96003332 or 96003695, i.e. float switches with
gold-plated contacts suitable for low voltages and currents (40 V/
100 mA), must be used. All EEx-approved float switches are also
suitable.
The float switches must be connected as NO contacts, i.e. brown
and black leads, when float switches, Grundfos product number
96003332 or 96003695, are used.
Key to the symbols in fig. A1 on page 23 and fig. A2 on
page 24:
Pos. Description
Float switch for start of the first pump/
1
common stop.
2Float switch for start of the next pump.21-22
3Float switch for high-level alarm.31-32
Terminal
number
11- 12
3.2 Setting
Parallel operation with 3 float switches, pages 23 and 24.
The module CU 212 has a 10-pole DIP switch in the bottom right
corner, see fig. 2.
Note: During the setting of the DIP switch, the controller must
always be dead for at least 1 minute to achieve the correct
configuration during start-up after change of the DIP switch
setting.
The DIP switch setting offers the following possibilities:
• selection of starting delay and automatic test run (switch 4),
• setting of stop delay (switches 5, 6 and 7),
• selection of automatic alarm resetting (switch 9),
• selection of automatic restarting (switch 10).
At this setting, the start-up is delayed within the range
from 0 to 255 sec. (random) after the electricity supply
has been switched on when the liquid level is
sufficiently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently
high.
No automatic test run.
• Switches 5, 6 and 7, stop delay:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
The stop delay is the time from the stop signal is given until the
pump is stopped.
It must be ensured that the pump is not running dry.
0 sec.60 sec.
15 sec.90 sec.
30 sec.120 sec.
45 sec.180 sec.
•Switch 8:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Switch 8 has no function in connection with the actual
application (parallel operation with 3 float switches, pages 23 and 24), but this setting must be maintained!
•Switch 9, automatic alarm resetting:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Fig. 2
Set the DIP switch as shown in fig. 2.
Each individual switch (1 to 10) of the DIP switch can be set to
position OFF or ON.
During the setting of the DIP switch, the controller must always
be dead for at least 1 minute to achieve the correct configuration
during start-up after change of the DIP switch setting.
Set the switches 1 to 10 as follows:
•Switches 1, 2 and 3, application type:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
This setting determines the actual application type
(parallel operation with 3 float switches, pages 23 and 24).
•Switch 4, starting delay and automatic test run
(only in the case of battery back-up):
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
This setting ensures automatic resetting of alarm
signals to external alarm devices and the built-in
buzzer. However, an alarm signal will only be reset if
the cause of the fault no longer exists.
At this setting, the alarm signal must be reset manually
by means of the reset button (the reset button is
described in section 3.5).
•Switch 10, automatic restarting:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
TM01 6870 2308
This setting enables automatic restarting after the PTC
resistance/thermal switch of the motor has cut out the
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
When the pumps connected are used in explosion
hazard areas, switch 10 must not be in this
position!
At this setting, the pump must be restarted manually after
the PTC resistance/thermal switch of the motor has cut
out the pump. To restart the pump, push the ON-OFFAUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in
section 3.5).
When the pumps connected are used in explosion
hazard areas, switch 10 must be in this position!
5
AC/DC selector:
AC 1 2
13-18 VAC
0 V
AC
DC
G3 4
AC 1 2
13-18 VAC
0 V
AC
DC
G3 4
AC 1 2
12 VDC
0 V
AC
DC
G3 4
The AC/DC selector switch for electrodes and/or float switches is
placed as shown in fig. 3.
Fig. 3
Operation with electrodes and
float switches:
Selector switch in position AC:
It is possible to connect 3
electrodes (1 as reference
electrode) and 2 float switches.
The controller transmits a 13 to
18 VAC signal.
Operation with float switches:
Selector switch in position AC:
It is possible to connect 4 float
switches.
The controller transmits a 13 to
18 VAC signal.
TM02 5747 3902
Operation with float switches:
Selector switch in position DC:
It is possible to connect 4 float
switches.
Cables of up to 100 metres can be
connected between the controller
and the float switches.
The controller transmits a 12 VDC
signal.
If the distance between the controller and pit exceeds 20 metres,
it is not advisable to use electrodes as problems with the signal
values sent back to the controller may arise. In such cases, it is
recommended to use float switches.
6
3.3 Control panel
CU 212
21
1
2
1234756
12
11
9
8
10
1
CU 212
2
CU 212
2
1
Parallel operation with 3 float switches, pages 23 and 24.
Figure 4 shows the control panel of the CU 212 module.
Fig. 4
Key to the symbols in fig. 4:
Pos. Description
Green indicator light for pump 1 and 2, indicating
1
starting delay (flashing) and pump operation
(permanently on).
Red indicator light for pump 1 and 2.
2
Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch for pump 1, three
5
positions, see section 3.5.
ON-OFF-AUTO selector switch for pump 2, three
6
positions, see section 3.5.
Reset button, push-button for manual resetting of alarm
7
signals to external alarm devices and the built-in buzzer
(only certain variants), see section 3.5.
Orange indicator light, which is activated by the float
8
switch for start of the first pump/common stop.
Orange indicator light, which is activated by the float
9
switch for start of the next pump.
Two orange indicator lights, which are activated by the
10
float switch for high-level alarm. In case of high-level
and
alarm, the top indicator light is flashing and the other is
11
permanently on.
Green indicator light, indicating that the electricity
12
supply has been switched on.
The table below shows the situations which may occur if the
normal electricity supply to the LCD 108 fails and a back-up
battery is connected:
= the indicator light is off.
= the indicator light is on.
= the indicator light is flashing.
Mains supply failure:
• The common alarm is active.
The red indicator light is on.
• The green indicator light (electricity
supply switched on) is off.
Mains supply failure and high-level alarm:
TM01 6397 3902
• The common alarm is active.
The red indicator light is on.
• The top orange indicator light is flashing.
• The second orange indicator light from
the top is on.
• The green indicator light (electricity
supply switched on) is off.
3.4 Battery back-up functions
Parallel operation with 3 float switches, pages 23 and 24.
If a back-up battery for CU 212 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
electricity supply to the LCD 108 fails (see also the illustrations
below):
• The common alarm is active, the red indicator light is on –
cannot be reset!
• If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot
be reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
• If the liquid level in the pit rises above the level for high-level
alarm, the top orange indicator light will be flashing and the
second orange indicator light from the top will be permanently
on.
• If the starting delay function and automatic test run were
selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
the liquid level is sufficiently high, see section 3.2.
7
3.5 Reset button and ON-OFF-AUTO selector switch
21
Parallel operation with 3 float switches, pages 23 and 24.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch for each pump has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long
period, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 3.2. Consequently,
the pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
OFF (), middle position:
• The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light
indication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.
AUTO ( ), bottom position:
• The pump is controlled by the input signals from the float switches and the pump according to the selected
DIP switch setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 3.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 3.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ().
4. Systems for parallel operation with 4 float
switches
Description (see also page 25 or 26):
The pumps are controlled by the liquid level in the pit.
• The float switch, pos. 2, starts the first pump.
• The float switch, pos. 3, starts the next pump.
• The float switch, pos. 1, stops both pumps after expiration of
the "stop delay" (can be set).
• The pumps operate alternately.
• The top float switch, pos. 4, activates the high-level alarm.
Before starting any work on pumps used to pump
liquids which could be constituted as being
hazardous to health, thorough cleaning/venting of
pumps, pits, etc. must be carried out according to
local regulations.
Before making any connections in the LCD 108 or
work on pumps, pits, etc., it must be ensured that the
electricity supply has been switched off and that it
cannot be accidentally switched on.
4.1 Electrical connection
Parallel operation with 4 float switches, pages 25 and 26.
Before starting work on the system, switch off the
supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. B1 on page 25.
The figures show all electrical connections required to connect
the LCD 108 for direct-on-line starting, parallel operation with 4 float switches.
Fig. B2 on page 26.
The figure shows all electrical connections required to connect
the LCD 108 for star-delta starting, parallel operation with 4 float switches.
The LCD 108 must be connected in accordance with
the rules and standards in force for the application in
question.
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the
electricity supply on which it will be used.
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65).
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, an external mains
switch must be installed.
Note: If the PTC resistance/thermal switch of the motor is
connected, the factory-fitted short-circuit jumper must be
removed (terminals T11-T21, T12-T22). For correct installation of
PTC resistor/thermal switch, see the installation and operating
instructions of the pump.
Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further
details can be found in the installation and operating instructions
for the pump in question.
Float switches placed in an explosion hazard area
must be connected via an EEx barrier, e.g. Grundfos
number 96440300.
The EEx barrier must not be installed in the explosion
hazard area.
Equipment used in explosion hazard areas must in
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in accordance
with local regulations.
8
Note: Float switches of the same type as Grundfos product
number 96003332 or 96003695, i.e. float switches with
gold-plated contacts suitable for low voltages and currents (40 V/
100 mA), must be used. All EEx-approved float switches are also
suitable.
The float switches must be connected as NO contacts, i.e. brown
and black leads, when float switches, Grundfos product number
96003332 or 96003695, are used.
Key to the symbols in fig. B1 on page 25 and fig. B2 on
page 26:
Pos. Description
1Float switch for common stop.11-12
2Float switch for start of the first pump.21-22
3Float switch for start of the next pump.31-32
4Float switch for high-level alarm.41-42
Terminal
number
4.2 Setting
Parallel operation with 4 float switches, pages 25 and 26.
The module CU 212 has a 10-pole DIP switch in the bottom right
corner, see fig. 5.
Note: The controller must be off circuit to ensure the correct
configuration during start-up after change of the DIP switch
setting.
The DIP switch setting offers the following possibilities:
• selection of starting delay and automatic test run (switch 4),
• setting of stop delay (switches 5, 6 and 7),
• selection of automatic alarm resetting (switch 9),
• selection of automatic restarting (switch 10).
•Switch 4, starting delay and automatic test run
(only in the case of battery back-up):
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
At this setting, the start-up is delayed within the range
from 0 to 255 sec. (random) after the electricity supply
has been switched on when the liquid level is
sufficiently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently
high.
No automatic test run.
• Switches 5, 6 and 7, stop delay:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
The stop delay is the time from the stop signal is given until the
pump is stopped.
It must be ensured that the pump is not running dry.
0 sec.60 sec.
15 sec.90 sec.
30 sec.120 sec.
45 sec.180 sec.
Fig. 5
Set the DIP switch as shown in fig. 5. Each individual switch (1 to
10) of the DIP switch can be set to position OFF or ON.
Note: The DIP switch must not be set to other switch
combinations than those described in this section.
Set the switches 1 to 10 as follows:
•Switches 1, 2 and 3, application type:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
This setting determines the actual application type
(parallel operation with 4 float switches, pages 25 and
26).
•Switch 8:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Switch 8 has no function in connection with the actual
application (parallel operation with 4 float switches, pages 25 and 26), but this setting must be maintained!
•Switch 9, automatic alarm resetting:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
This setting ensures automatic resetting of alarm
signals to external alarm devices and the built-in
buzzer. However, an alarm signal will only be reset if
the cause of the fault no longer exists.
At this setting, the alarm signal must be reset manually
by means of the reset button (the reset button is
TM04 2341 2308
•Switch 10, automatic restarting:
described in section 4.5).
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
This setting enables automatic restarting after the PTC
resistance/thermal switch of the motor has cut out the
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
When the pumps connected are used in explosion
hazard areas, switch 10 must not be in this
position!
At this setting, the pump must be restarted manually after
the PTC resistance/thermal switch of the motor has cut
out the pump. To restart the pump, push the ON-OFFAUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in
section 4.5).
When the pumps connected are used in explosion
hazard areas, switch 10 must be in this position!
9
AC/DC selector:
AC 1 2
13-18 VAC
0 V
AC
DC
G3 4
AC 1 2
13-18 VAC
0 V
AC
DC
G3 4
AC 1 2
12 VDC
0 V
AC
DC
G3 4
CU 212
21
1
2
1234756
12
11
9
8
10
The AC/DC selector switch for electrodes and/or float switches is
placed as shown in fig. 6.
Fig. 6
Operation with electrodes and
float switches:
Selector switch in position AC:
It is possible to connect 3
electrodes (1 as reference
electrode) and 2 float switches.
The controller transmits a 13 to
18 VAC signal.
Operation with float switches:
Selector switch in position AC:
It is possible to connect 4 float
switches.
The controller transmits a 13 to
18 VAC signal.
Operation with float switches:
Selector switch in position DC:
It is possible to connect 4 float
switches.
Cables of up to 100 metres can be
connected between the controller
and the float switches.
The controller transmits a 12 VDC
signal.
If the distance between the controller and pit exceeds 20 metres,
it is not advisable to use electrodes as problems with the signal
values sent back to the controller may arise. In such cases, it is
recommended to use float switches.
4.3 Control panel
Parallel operation with 4 float switches, pages 25 and 26.
Figure 7 shows the control panel of the CU 212 module.
Fig. 7
TM02 5747 3902
Key to the symbols in fig. 7:
Pos. Description
Green indicator light for pump 1 and 2, indicating
1
starting delay (flashing) and pump operation
(permanently on).
Red indicator light for pump 1 and 2.
2
Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch for pump 1, three
5
positions, see section 4.5.
ON-OFF-AUTO selector switch for pump 2, three
6
positions, see section 4.5.
Reset button, push-button for manual resetting of alarm
7
signals to external alarm devices and the built-in buzzer
(only certain variants), see section 4.5.
Orange indicator light, which is activated by the float
8
switch for common stop.
Orange indicator light, which is activated by the float
9
switch for start of the first pump.
Orange indicator light, which is activated by the float
10
switch for start of the next pump.
Orange indicator light, which is activated by the float
11
switch for high-level alarm. In case of high-level alarm,
the indicator light is flashing.
Green indicator light, indicating that the electricity
12
supply has been switched on.
TM01 6397 3902
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.