Grundfos JP Booster PT Installation And Operating Instructions Manual

English (GB) Installation and operating instructions
Caution
Note
Note
Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
2. Applications
3. System sizing
4. Electrical connection
5. Ejector valve
5.1 Ejector valve setting
6. Start-up
6.1 Shaft seal run-in
7. Adjustment
7.1 Calculating the cut-in and cut-out pressures
7.2 Adjusting the precharge pressure
7.3 Setting the pressure switch
8. Operation and maintenance
9. Frost protection
10. Technical data
11. Fault finding
12. Disposal
Warning Prior to installation, read this document
and the quick guide. Installation and operation must comply with local regulations and accepted codes of good practice.
Warning The use of this product requires
experience with and knowledge of the product. Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety. Children must not use or play with this product.

1. Symbols used in this document

Warning If these safety instructions are not
observed, it may result in personal injury.
Warning If these instructions are not observed,
it may lead to electric shock with consequent risk of serious personal injury or death.
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
9 9 9

2. Applications

9
10
10

3. System sizing

10
10
11
11 11 11
12 12

4. Electrical connection

12 13 13
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Single-phase motors incorporate a thermal switch and require no additional motor protection.
Three-phase motors must be connected to an external mains switch and a motor-protective circuit breaker.
Notes or instructions that make the job easier and ensure safe operation.
Warning The system in which the product is
incorporated must be designed for the maximum pump pressure.
The default setting can be found in the quick guide.
Warning The electrical installation should be
carried out by an authorised person in accordance with local regulations.
Warning During electrical installation, make sure
that the power supply cannot be accidentally switched on.
Warning The unit must be connected to an
external mains switch with a minimum contact gap of 3 mm in all poles.
As a precaution, the pump must be connected to a socket with earth connection.
We recommend to fit the permanent installation with an earth leakage circuit breaker (ELCB) with a tripping current
30 mA.
English (GB)
9

5. Ejector valve

Note
V
S
P
T
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 Q [m³/h]
0
5
10
15
20
25
30
35
40
45
H
[m]
0.00 0. 25 0.50 0.75 1.00 Q [l/s]
JP 5
IS O 9906 Annex A
P
o
s
.
1
P
o
s
.
2
Caution
Note
English (GB)
The ejector valve is supplied separate with the pump.
Remove the plug (V), see fig. 1, and fit the ejector valve into the hole.
The O-ring must be fitted to the ejector valve.
Tighten the valve using fingers only.
Pos. 2
Turn the valve to the right (in). Select pos. 2 when the pump has been primed, and
a large quantity of water and a low pressure are required.
Pos. Ejector valve Direction
1
Left
(out)
TM04 2299 2308
Fig. 1 Ejector valve

5.1 Ejector valve setting

The ejector valve in the plug hole (V) can be turned to two positions. See fig. 3.
Figure 2 shows an example of how the ejector valve position may affect the QH curve.
Fig. 2 QH curve and ejector valve positions
Pos. 1
Turn the valve to the left (out). Select pos. 1 when the suction pipe is empty and the
pump is to be primed. Select also pos. 1 when a small quantity of water and
a high pressure are required.
10
2
TM00 5495 4995TM00 7474 1396
Right
(in)
Fig. 3 Ejector valve positions

6. Start-up

Do not start the pump until it has been filled with liquid. See the quick guide.
We recommend to fit a non-return valve on the suction side of the pump.

6.1 Shaft seal run-in

The seal faces are lubricated by the pumped liquid, meaning that there may be a certain amount of leakage from the shaft seal.
When the pump is started up for the first time, or when a new shaft seal is installed, a certain run-in period is required before the leakage is reduced to an acceptable level. The time required for this depends on the operating conditions, i.e. every time the operating conditions change, a new run-in period will be started.
Under normal conditions, the leaking liquid will evaporate. As a result, no leakage will be detected.
TM04 2300 2308

7. Adjustment

Note
Caution
Note
The JP Booster PT comes with the following factory settings in bar:
Pump
JP 5 & 6 1.9 2.2 3.3
Tank
precharge
pressure

7.1 Calculating the cut-in and cut-out pressures

The cut-in pressure is the sum of these variables:
• required minimum pressure at the highest
tapping point
from the pump to the highest tapping point
• head
• pressure loss in pipes.
Recommended cut-out pressure: cut-in pressure + 1.0 - 1.5 bar.
The cut-out pressure must not exceed the maximum discharge pressure of the pump.

7.2 Adjusting the precharge pressure

When the pump cut-in pressure has been determined, the required precharge pressure of the diaphragm tank can be calculated. The precharge pressure must be adjusted to 90 % of the cut-in pressure.
When adjusting/reading the precharge pressure, make that there is no water pressure on the diaphragm tank from the pipework.
If the pressure switch setting is changed, the precharge pressure must be adjusted too.
See the installation and operating instructions for the diaphragm tank.
Cut-in
pressure
Cut-out
pressure

7.3 Setting the pressure switch

Warning Switch off the power supply before
adjusting the pressure switch. Fit the cover on the pressure switch
before you switch on the power supply to check the cut-in and cut-out pressure.
The cut-out pressure must be lower than the maximum operating pressure of the pump and tank.
Remove the cover from the pressure switch to access the adjusting screws. See fig. 4.
Fig. 4 Pressure switch
Setting the cut-out pressure
1. Turn screw (pos. A) clockwise to increase the cut-out pressure. Turn it counter-clockwise to reduce the cut-out pressure. The differential pressure range remains unchanged.
2. Start the pump and check by reading the pressure gauge whether the desired cut-out and cut-in pressures have been obtained.
Setting the cut-in pressure
1. Turn screw (pos. B) clockwise to reduce the cut-in pressure. Turn it counter-clockwise to increase the cut-in pressure. The differential pressure range is widened and narrowed respectively.
2. Start the pump and check by reading the pressure gauge whether the desired cut-out and cut-in pressures have been obtained.
Repeat the procedure until the right cut-in and cut-out pressures have been obtained.
English (GB)
TM01 6914 3799
11

8. Operation and maintenance

Caution
English (GB)
Warning Prior to start-up, the system should be
flushed through with clean water and drained to remove possible impurities.
Do not cover the motor of the booster system as an adequate supply of cool air must reach the motor cooling fan.

9. Frost protection

If there is a risk of frost, the tank and pump must be drained.

10. Technical data

Ambient temperature
Maximum +40 °C.
Storage temperature
Minimum -20 °C. Maximum +70 °C.
Liquid temperature
+40 °C.
System pressure
Maximum 6 bar.
Inlet pressure
At inlet pressures above 1.5 bar the discharge pressure must be at least 2.5 bar.
Supply voltage
1 x 220-240 V, 50 Hz. 3 x 220-240/380-415 V, 50 Hz.
Insulation class
F.
Enclosure class
IP44.
Relative air humidity
Maximum 95 %.
Sound power level
The sound power level of the pump is lower than 72 dB(A).
Start/stop frequency
Maximum 100 per hour.
12

11. Fault finding

Warning Before starting fault finding, switch off
the power supply. Make sure that the power supply cannot be accidentally switched on.
Fault Cause Remedy
1. The pump does not start.
2. There is power on the pressure switch but not the pump.
3. The pump does not start when water is consumed.
4. Frequent starts/stops.
5. The pump does not stop.
6. The motor cuts out during operation.
* Or contact the nearest Grundfos company or
service workshop.
a) The fuses in the electric
installation have burnt.
b) The earth leakage circuit
breaker or the voltage-operated circuit breaker has tripped.
a) The power supply to the pump
is disconnected after the pressure switch unit.
b) The pressure switch unit is
defective.
a) Too big difference in height
between the pressure switch unit and the tapping point.
b) The pressure switch unit is
defective. a) Leakage in the pipework. Check and repair the pipework. b) The pressure tank has no
precharge pressure, or the
tank size is insufficient. a) The pressure switch unit is
defective. a) The thermal switch in the
motor has tripped due to
overheating.
Replace the fuses. If the new fuses also burn, check the electric installation.
Cut in the circuit breaker and check the electric installation.
Check the cable connections.
Repair or replace the pressure switch unit. *
Adjust the cut-in pressure.
Repair or replace the pressure switch unit. *
Check the tank precharge pressure, and recharge the tank, if necessary. See section 7.
Repair or replace the pressure switch unit. *
The thermal switch will cut in automatically when the motor has cooled sufficiently. If the problem still persists, check these two possible causes:
• Impeller stuck. Clean the pump.
• Motor defective. Repair or replace the motor. *
English (GB)

12. Disposal

This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Subject to alterations.
13
Loading...