Grundfos G100 Installation And Operating Instructions Manual

G100
GRUNDFOS INSTRUCTIONS
Installation and operating instructions
Declaration of Conformity
We Grundfos declare under our sole responsibility that the products Profibus-DP and Radio/Modem/PLC version, to which this declaration
relates, are in conformity with the Council Directives on the approxima­tion of the laws of the EC Member States relating to
– Electromagnetic compatibility (89/336/EEC).
Standards used: EN 61000-6-2 and EN 61000-6-3.
– Electrical equipment designed for use within certain voltage limits
(73/23/EEC) [95]. Standard used: EN 61010-1.
Konformitätserklärung
Wir Grundfos erklären in alleiniger Verantwortung, dass die Produkte Profibus-DP und Radio/Modem/PLC-Ausführung, auf die sich diese
Erklärung bezieht, mit den folgenden Richtlinien des Rates zur Anglei­chung der Rechtsvorschriften der EG-Mitgliedstaaten übereinstimmen
– Elektromagnetische Verträglichkeit (89/336/EWG).
Normen, die verwendet wurden: EN 61000-6-2 und EN 61000-6-3.
– Elektrische Betriebsmittel zur Verwendung innerhalb bestimmter
Spannungsgrenzen (73/23/EWG) [95]. Norm, die verwendet wurde: EN 61010-1.
Déclaration de Conformité
Nous Grundfos déclarons sous notre seule responsabilité que les pro­duits Profibus-DP et version Radio/Modem/PLC auxquels se réfère cette déclaration sont conformes aux Directives du Conseil concernant le rapprochement des législations des Etats membres CE relatives à
– Compatibilité électromagnétique (89/336/CEE).
Standards utilisés: EN 61000-6-2 et EN 61000-6-3.
– Matériel électrique destiné à employer dans certaines limites
de tension (73/23/CEE) [95]. Standard utilisé: EN 61010-1.
Försäkran om överensstämmelse
Vi Grundfos försäkrar under ansvar, att produkterna Profibus-DP och version Radio/Modem/PLC, som omfattas av denna försäkran, är i
överensstämmelse med Rådets Direktiv om inbördes närmande till EU­medlemsstaternas lagstiftning, avseende
– Elektromagnetisk kompatibilitet (89/336/EC).
Använda standarder: EN 61000-6-2 och EN 61000-6-3.
– Elektrisk material avsedd för användning inom vissa spännings-
gränser (73/23/EC) [95]. Använd standard: EN 61010-1.
Overensstemmelseserklæring
Vi Grundfos erklærer under ansvar, at produkterne Profibus-DP og Radio/Modem/PLC-udgave, som denne erklæring omhandler, er i
overensstemmelse med Rådets direktiver om indbyrdes tilnærmelse til EF medlemsstaternes lovgivning om
– Elektromagnetisk kompatibilitet (89/336/EØF).
Anvendte standarder: EN 61000-6-2 og EN 61000-6-3.
– Elektrisk materiel bestemt til anvendelse inden for visse spændings-
grænser (73/23/EØF) [95]. Anvendt standard: EN 61010-1.
Свидетельство о соответствии требованиям
Мы, фирма Grundfos, со всей ответственностью заявляем, что изделия Profibus-DP и исполнение с функциями радиосвязи/ модема/программируемого процессора, к которым и относится данное свидетел ьст во, отвеча ют требованиям следующих указаний Совета ЕС об унификации законодательных предписаний стран­членов ЕС:
– Электромагнитная совместимость (89/336/ЕЭС).
Применявшиеся стандарты: Евростандарт EN 61000-6-2 и
EN 61000-6-3.
Электрические машины для эксплуатации в
пределах определенного диапазона значений напряжения (73/23/ЕЭС)[95]. Применявшиеся стандарты: Евростандарт EN 61010-1.
Bjerringbro, 1st April 2006
Svend Aage Kaae Technical Director
2
3
G100
Installation and operating instructions 4
Montage- und Betriebsanleitung 18
Notice d'installation et d'entretien 34
Monterings- och driftsinstruktion 49
Monterings- og driftsinstruktion 63
Руководство по монтажу и эксплуатации 77
4
CONTENTS
Page
1. General description 4
2. Installation 5
2.1 Electrical connection 5
2.2 Installation requirements 5
2.3 Master programming 5
2.4 Start-up 5
3. Description of function 6
3.1 Data communication 6
3.2 Service port 6
3.3 Data logging 6
3.4 Digital inputs 6
3.5 Automatic call-back and SMS messages (G100 Radio/Modem/PLC only) 7
3.6 Other functions 7
4. Profibus-DP 7
4.1 Profibus-DP settings 7
4.2 Profibus-DP front cover 8
4.3 Common connectors 9
4.4 Profibus-DP connector 9
5. Radio/Modem/PLC 10
5.1 Radio/Modem/PLC settings 10
5.2 Radio/Modem/PLC front cover 12
5.3 Common connectors 13
5.4 Radio/Modem/PLC connectors 13
6. Fault finding chart 14
7. Technical data 16
7.1 Data applying to all versions 16
7.2 Profibus-DP expansion board 17
7.3 Radio/Modem/PLC expansion board 17
7.4 Emission (applies to the USA) 17
8. Disposal 17
1. General description
Definition
The G100 is a gateway enabling communicatio n between units connected to a Grundfos GENIbus and a main network.
Communication
The G100 functions as a master to the GENIbus. Only one G100 can be installed on a GENIbus net-
work, and a maximum of 32 units can be handled.
Data logging
Besides functioning as a gateway, the G100 basic and Radio/Modem/PLC versions provide data log­ging facilities.
Data logging enables continual storage of measured values in the G100 with a resolution down to 4 sec­onds.
Digital inputs
As standard, the G100 has four digital inputs to be used as required. It is up to the user to determine the function of the digital inputs.
Status of digital inputs can be reafd via the communi­cation to the main network and can be used to trigger SMS messages.
Automatic call-back and SMS messages
The G100 with a modem connection can be config­ured for automatic call-back to one or more phone numbers (central management system) when one of the connected GENIbus units goes into alarm condi­tion, e.g. blocked pump.
The G100 can also be configured to send SMS m es­sages in case of an alarm condition or other selecta­ble events.
Other functions
• Stop of all pumps in case of failing communication with the building mangement system (optional).
• Acces s code for mode m communication (optional).
• Logging of the last 10 alarms with address, time stamp and cause.
Software
A software package is supplied with the G100. The package includes two programs:
• PC Tool G100 and
• PC Tool G100 Data Log.
PC Tool G100
The program PC Tool G100 is a combined configura­tion/analysis tool to be used by the system integra­tor.
The program offers the following functions:
• Showing the unit hierarchy of the GENIbus net­work.
• Showing/managing the data points of the individ­ual units.
• Showing the status of the G100.
• Configuring the G100.
PC Tool G100 Data Log
The program PC Tool G100 Data Log enables the user
• to configure the data logging facility in a G100.
• to retrieve the logged data values from the G100.
• to visualize the units connected to the G100.
• to retrieve a logging status of a connected G100 at any time.
Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regula­tions and accepted codes of good prac­tice.
5
Help menu
The software for the G100 includes a help menu to be used in connection with the installation and oper­ation of the G100.
Software downloading
The software in the G100 can be updated by down­loading new software via the service port directly or by modem using the PC Tool G100.
2. Installation
2.1 Electrical connection
The electrical connection should be carried out in accordance with local regulations.
The operating voltage and frequency are marked on the nameplate. Please make sure that the G100 is suitable for the electricity supply on which it will be used.
Use the plug supplied for the electrical connection.
Supply voltage: 1 x 110-240 V, 45-65 Hz.
2.2 Installation requirements
The G100 must be positioned in a way ensuring that electromagnetic noise from contactors, relays and electric devices does not influence the functioning of the G100.
Distance to power cables G100: Place the G100 at a distance of minimum
15 cm from power cables. Cables: Cables for the connection of
• Profibus,
• radio, modem, PLC and direct,
• GENIbus,
• DI (digital inputs) and
• Service must also keep a distance of minimum 15 cm to
power cables.
G100 on control panel
When positioning the G100 on a control panel, it is recommended that the G100 be located as close to the bottom of the panel as possible due to tempera­ture conditions.
G100 in control cabinet
The G100 is designed for mounting in a control cabi­net, directly on a mounting plate.
Fig. 1
2.3 Master programming
Master programming on the main network must be carried out by the system integrator according to the instructions given on the "G100 Support Files" CD­ROM supplied with the G100.
Handling G100 from the management system
The management system on the main network must be prepared for communication with the G100.
This involves adding some software
• handling the transfer of data,
• using data for monitoring and control purposes. Reference: The "G100 Support Files" CD-ROM sup-
plied with the G100 contains the necessary docu­mentation.
2.4 Start-up
Before powering on the G100,
• complete the GENIbus wiring and
• assign a unique address to each unit conn ected (via the Grundfos remote control R100 or via the control panel on the unit).
Switch on the electricity supply and make sure that the light-emitting diodes on
• mother board (see section 4.2 Profibus-DP front cover) and
• expansion board, if any, (see the relevant section)
light up correctly.
As a precaution, the G100 must be earthed. It is recommended to fit the instal­lation with an earth leakage circuit breaker (ELCB) with a tripping current < 30 mA.
Never dismantle the G100 unless the elec­tricity supply has been switched off.
TM01 1712 1602
B
u
s In
Bus
O
u
t
M
a
in
N
etwo
rk
C
on
n
ec
tio
n
P
O
W
ER
P
OW
E
R M
NC
P
O
W
E
R G
E
N
I
GE
N
I T
xD
G
E
NI
Rx
D
F
A
UL
T
R
B
D
A TR B
A R
C
GE
N
Ibu
s
S
e
rv
ice
D
I
6
3. Description of function
3.1 Data communication
It is possible to connect up to 32 units to the GENIbus. A unit may be a UPE pump with GENIbus connection, a CU 3 control unit, etc.
The main network may be
• another fieldbus,
• radio,
• modem,
•PLC,
• direct RS-232 connection.
Information retrieval
Information such as
• measured values,
• operating status,
• fault status,
• configuration parameters and more can be retrieved from each individual unit via the
G100.
Remote configuration
• Setpoints,
• commands and
• configuration parameters can be sent to the GENIbus units via the G100. Reference: The "G100 Support Files" CD-ROM sup-
plied with the G100 contains an overview of the data which can be communicated between the main net­work and the different types of Grundfos products having a GENIbus connection.
3.2 Service port
The service port enables the connection of a PC directly or via radio modem to the G100.
By means of the PC Tool G100, the following can be read:
• status of the units connected to the GENIbus,
• internal error codes i n the G100. The PC Tool G100 can also be used:
• to display the individual data points with their actual values,
• to change setpoints, change configuration param­eters and send commands.
3.3 Data logging
Description
The G100 basic and Radio/Modem/PLC versions include data logging facilities. Data logging means that the G100 stores data point values sampled over a given period.
The data logging facility is configured by means of the program PC Tool G100 Data Log.
Purpose
The logged data can be used for various analyses of e.g. flow, head, energy consumption, etc. enabling optimum pump control.
Subsequently, stored data may be transmitted to a PC. For example, the stored data can be analysed in a spreadsheet.
Logging data points
By configuring the data logging of the individual data points, each value may continually be monitored/reg­istered, each logging being time-stamped to indicate the date/time of the value.
G100 logging capacity
The number of log data points and the logging fre­quency determine for how long the G100 can per­form data logging.
The 2 Mb memory installed makes it possible to log up to 350,000 values. For example 20 data points for
• 120 days at 10-minute resolution or
• 2 days at 10-second resolution. Maximum logging resolution is 4 seconds.
3.4 Digital inputs
The G100 features four digital inputs for optional use.
The four digital inputs should be considered data points, and they can thus be referenced from the main network in the same way as the other da ta points.
Purpose
An example could be the monitoring of an Uninter­ruptable Power Supply (UPS) or the registration of status, e.g. alarms.
7
3.5 Automatic call-back and SMS mes­sages (G100 Radio/Modem/PLC only)
A G100 with a modem connection can be configured for automatic call-back to one or more phone num­bers (central management system) when one of the connected GENIbus units goes into alarm condition, e.g. blocked pump. The advantage of this function is that regular dial-ups, or a fixed online connection, to the system to be monitored are unnecessary.
The G100 can also be configured to send SMS mes­sages via a GSM data modem (or via a UCP server when a fixed-line modem is used) in case of an alarm condition or other selectable events.
SMS messages can be combined with automatic call-back so that both functions are carried out or one is carried out only if the other fails. It is possible to call back to five different phone numbers and the call-backs can be controlled by other events than faults:
• A GENIbus unit goes into alarm condition.
• A GENIbus unit comes out of alarm condition.
• A GENIbus unit goes into warning condition.
• A GENIbus unit comes out of warning condition.
• The G100 loses connection with a GENIbus unit
or gets into contact with a new GENIbus unit.
• Change of digital input.
These events can be selected or deselected as desired. In addition, the "heartbeat" SMS function can be set to send a message at fixed intervals, indi­cating that the telephone modem connection is oper­ational.
3.6 Other functions
The G100 is capable of monitoring the communica­tion via the service port as well as the communica­tion port to the main network. If the communication is disconnected within a given configurable period, the G100 will stop all connected GENIbus units using bus commands. This function can be enabled or dis­abled for each of the two communication ports.
In a given application, this function can be used to stop all pumps in case of failing communication with the central management system.
The G100 has an access code option for modem communication. If the access code is not written cor­rectly, the transmission of data to the G100 and the GENIbus units will not be allowed. In this way, unau­thorized persons are prevented from causing dam­age to the system.
The G100 will log the last 10 ala rms w ith addres s, time stamp and cause. The alarm log can be useful in connection with fault finding. The log can be deleted by giving a command to the G100.
4. Profibus-DP
Description
The Profibus-DP builds upon a master-slave-princi­ple, where the bus master (PC or PLC) also func­tions as the link to an overlying management system (SCADA system). The G100 functions as a slave on the Profibus-DP network.
G100 Profibus-DP address
When installing the G100, the G100 Profibus-DP address must be set manually by the use of DIP switches on the Profibus-DP expansion board. See section 4.1 Profibus-DP settings.
4.1 Profibus-DP settings
The physical Profibus-DP address must be set on the Profibus-DP expansion board, fig. 2. This should be done before connecting the G100 to the Profibus­DP.
Fig. 2
The G100 must be assigned a Profibus-DP address which is not already being used on the Profibus-DP network.
Example: The Profibus-DP address is set to No. 3 on the DIP switches in fig. 3.
Fig. 3
It is possible to set the address from No. 1 to 255. The address No. 0 is reserved.
TM01 1706 5097
TM01 1707 5097
Connection to mother board
Address
1
2 3
4 5
6
7
8
8
Master configuration
The Profibus-DP master (e.g. PLC) must be config­ured according to the specifications of the Profibus­DP master in question.
Data transmission and system demands
As the DP protocol does not transmit data via objects. Consequently, the G100 uses a superim­posed telegram format for the DP protocol. This tele­gram format must be implemented in the Profibus­DP master by the system integrator.
Reference: The telegram format is described in the "G100 Support Files" CD-ROM supplied with the G100. The necessary GSD file for the DP master is also available on the CD-ROM.
4.2 Profibus-DP front cover
Front cover
Light-emitting diodes: Operating/fault indications
Colour
Normal condition
POWER:
The G100 is powered.
Green
Perma­nently on
POWER MNC: The network communication chip to the main network is powered.
Green
Perma­nently on
POWER GENI:
The GENIbus RS-485 communication chips are powered.
Green
Perma­nently on
GENI TxD:
Data is sent via GENIbus RS-485.
Yellow Flashing
GENI RxD:
Data is received from GENIbus RS-485.
Yellow Flashing
FAULT:
Data memory fau lt.
Red Off
DES: Data Exchange State.
Connection to DP network is OK.
Green
Perma­nently on
G100 connectors
GENIbus
DI
Service See section 4.3 G100 common connectors.
Main Network Connection: See section 4.4 Profibus-DP connector.
Power Power MNC Power Geni Geni T xD Geni RxD Fault
DES
Genibus DI Service
Main
Network
Connection
G100 Gateway
Profibus
TM01 1705 1602
9
4.3 Common connectors
This section describes G100 connectors (male) for
• GENIbus,
• DI (digital inputs) and
• Service. Figure 4 shows the three G100 male connectors and
a 9-pin D-sub female connector with pin numbers.
Fig. 4
GENIbus connector
The GENIbus is a serial RS-485 connection. A, B and Y are placed as follows:
DI connector
The digital inputs are paired as follows:
Service connector
The service port is a serial RS-232 connection. RxD, TxD and GND are placed as follows:
:
4.4 Profibus-DP connector
Fig. 5
The connection of the G100 to the Profibus-DP is made by connecting the Profibus-DP cable to the Profibus-DP connector shown in fig. 5.
The network topology on Profibus-DP is multidrop.
Pin configuration
The pin configuration of the connector is made according to the Profibus-DP standard.
* The assignment of pin Nos. 1, 2, 7 and 9 corre-
sponds to that of the connected unit.
When connecting to Profibus-DP, a standard con­nector from Siemens should be used.
Example: 6ES7 972-OBA10-OXAO.
TM01 1700 1602 / 6904 3699
Connections
GENIbus Pin number
A2 B3
Y (screen) 5
Connections
DI Pin number
DI 1 1 + 6 DI 2 2 + 7 DI 3 3 + 8 DI 4 4 + 9
Connections
Service Pin number
RxD 2 TxD 3
GND 5
1 2 3 4
5
6 7 8
9
Genibus DI Service
TM01 1705 1602
Illustration
Pin No.
Signal Description
1* – 2* – 3 RxD/TxD-P Data line B
4RTS
Request to send
5M5V2
Data refer­ence poten­tial (from station)
6P5V2
Supply plus
(from station) 7* – 8 RxD/TxD-N Data line A 9*
Main
Network
Connection
Profibus
1 2 3 4
5
6 7 8
9
TM01 6904 3699
10
5. Radio/Modem/PLC
Description
In addition to the GENIbus protocol, the G100 Radio/ Modem/PLC can communicate via the standard PLC protocols COMLI and Modbus.
For all three protocols, direct connection (RS-232) or connection via telephone modem or radio modem can be used. The G100 usually functions as a slave on the network.
When using direct connection or modem connection, it is possible to multiplex the connection to the G100 (port 1, RS-232). This means that several G100 units with different addresses can be connected to a sin­gle serial port of a PC, when the appropriate equip­ment is used, e.g. modem data splitter or radio modems.
G100 address
When installing the G100, the physical bus address must be set manually by the use of DIP switches on the expansion board. See section 5.1 Radio/Modem/PLC settings.
5.1 Radio/Modem/PLC settings
When the G100 is incorporated in a network together with other G100 units, an address must be allocated to each unit. Note that the address 0 is the "broad­cast" address (default). All units will reply to this address when asked.
The physical bus address must be set on the Radio/ Modem/PLC expansion board.
This should be done before start-up.
Fig. 6
The G100 must be assigned a bus address which is not already being used on the network.
Example: The bus address is set to No. 3 on the DIP switches in fig. 7.
Fig. 7
It is possible to set the address from No. 1 to 255. The address 0 is reserved.
In Port 1, the switches 1 to 8 have the following pur­poses:
TM01 1711 5097
Address
Port 2
Port 2
Port 1
TM01 1707 5097
DIP switch Purpose
1 - 2 IO type 3 - 5 Protocol 6 - 8 Communication speed
1
2 3
4 5
6
7
8
11
The following table shows how the DIP switches in Port 1 should be set.
.
Data transmission
The data transmission itself is made via objects (identified by means of an index No.).
Reference: The "G100 Support Files" CD-ROM supplied with the G100 contains a description of the objects available.
Note: The G100 is not supplied with a radio, modem or PLC. They must all be acquired separately.
Port 1
Function
DIP switch setting
12345678
IO type
Direct 00––––––
Modem 1 0––––––
Radio 01––––––
PLC 11––––––
Protocol
Auto detect
––000–––
G100 ––100–––
Satt Control COMLI
––010–––
Communication speed
1200 baud –––––000
2400 baud –––––100
4800 baud –––––010
9600 baud –––––110
19200 baud ––––001
Reserved –––––101
Reserved –––––011
Reserved –––––111
12
5.2 Radio/Modem/PLC front cover
*) For explanation to Power, Power MNC, Power Geni, Geni TxD, Geni RxD, Fault, see section 4.2 Profibus-
DP front cover.
Front cover
Light-emitting diodes: Operating/fault indications *)
Colour
Normal condition
DCD: Data Carrier Detect
DCD pin is active. Light diode indica­tion according to the IO type selected:
Radio
DCD is on
when a unit in the radio sys­tem has asked for and received permis­sion to send data. Modem (G100 with modem (dial-up) connection to main system. G100 can make alarm dial-up). DCD is on
when G100 is connected to main system.
PLC
DCD is permanently on
when G100 is powered. Direct (G100 permanently connected to main system). DCD is permanently on
when G100 is powered. Direct (G100 with modem (dial-up) con­nection to main system. G100 cannot make alarm dial-up). DCD is on
when G100 is connected to
the main system.
Green
RTS: Request To Send
RTS pin on line is active. Light diode in­dication according to the IO type se­lected:
Radio
RTS is o n
when G100 desires to send
data or data is actually being sent.
Modem, PLC or Direct
RTS is permanently on
when G100 is
powered.
Green
TxD1:
Data transmission on line 1.
Yellow Flashing
RxD1:
Data reception from line 1.
Yellow Flashing
TxD2:
Data transmission on line 2. Reserved for future use.
––
RxD2:
Data reception from line 2. Reserved for future use.
––
G100 connectors
GENIbus
DI
Service See section 4.3 G100 common connectors.
Main Network Connection: See section 5.4 Radio/Modem/
PLC connectors.
TM01 1710 1602
Power Power MNC Power Geni Geni T xD Geni RxD Fault
DCD RTS TxD1 RxD1 TxD2 RxD2
Genibus DI Service
Port 1 Port 2
Main
Network
Connection
G100 Gateway
13
5.3 Common connectors
This section describes G100 connectors (male) for
• GENIbus,
• DI (digital inputs) and
• Service. Figure 8 shows the three G100 male connectors and
a 9-pin D-sub female connector with pin numbers.
Fig. 8
GENIbus connector
The GENIbus is a serial RS-485 connection. A, B and Y are placed as follows:
DI connector
The digital inputs are paired as follows:
Service connector
The service port is a serial RS-232 connection. RxD, TxD and GND are placed as follows:
:
5.4 Radio/Modem/PLC connectors
Fig. 9
The connection of the G100 to radio, modem or PLC is made by connecting the cable to the Port 1 con­nector shown in fig. 9.
Port 2 is not used.
Pin configuration
TM01 1700 1602 / 6904 3699
Connections
GENIbus Pin number
A2 B3
Y (screen) 5
Connections
DI Pin number
DI 1 1 + 6 DI 2 2 + 7 DI 3 3 + 8 DI 4 4 + 9
Connections
Service Pin number
RxD 2 TxD 3
GND 5
1 2 3 4
5
6 7 8
9
Genibus DI Service
TM01 1710 1602
Illustration
Pin No.
Signal Description
1DCD
Data carrier detect
2 RxD Received data 3TxD
Transmitted data
4DTR
Data terminal
ready 5 GND Ground 6 DSR Data set ready 7 RTS Request to send 8 CTS Clear to send 9 RI Ring indicator
Port 1 Port 2
Main
Network
Connection
1
2 3 4
5
6 7 8
9
TM01 6904 3699
14
6. Fault finding chart
Additional instructions for fault finding in the communication with the G100 can be found on the "G100 Support Files" CD-ROM supplied with the G100.
G100 mother board
Indication Cause Remedy
1. POWER off.
a) No electricity supply. • Check the electricity supply.
• Check that the G100 is OK by removing connection to main network and to GENIbus.
• Contact the system supplier.
b) Fault in components/fatal component
fault.
2. POWER MNC faint or off.
a) Fault in main network or in the G100. • Check that the G100 is OK by removing
connection to main network. POWER MNC must now be on.
• Check MNC cables for faults.
b) Cable fault, possibly short-circuit.
3. POWER GENI faint or off.
a) GENIbus is overloading the G100. • Check that the G100 is OK by removing
connection to GENIbus. All POWER di­odes must now be permanently on.
• Check the GENIbus connection and ca­bling.
• Contact the system supplier.
4. GENI TxD not flashing.
a) The G100 is not communicating. • Disconnect/connect the electricity sup-
ply.
• Check the bus. If this does not help, then replace the
G100.
b) GENIbus connection or cable may be
short-circuited.
5. GENI RxD not flashing.
a) GENIbus connection or cable may be
short-circuited.
Check the GENIbus connection and cabling.
b) No units are connected to GENIbus.
6. FAULT permanently on.
a) RAM memory fault. Replace the G100.
Profibus-DP expansion board
Indication Cause Remedy
1. DES off.
a) Cable fault. • Check the cable.
• Check that the master applies the cor­rect maker’s ID No., address and ID size.
- Maker’s ID No.
- Address: As set on DIP switch.
b) Configuration fault on master.
15
Radio/Modem/PLC expansion board
Indication Cause Remedy
1. DCD
- Modem off.
a) Wrong modem type. • Check that the modem initialization
commands are compatible.
• Make a redial.
b) Poor telephone line.
2. DCD
- Radio permanently on.
a) Fault in a radio network unit. Reset or disconnect/connect the unit in
case of fault. If this does not help, then replace the unit in case of fault.
3. RTS
- Radio permanently on.
a) The G100 is constantly attempting to
send.
• Disconnect/connect the electricity sup­ply or
• reset the G100 using the PC Tool G100.
4. RTS
- Direct/modem not perma­nently on.
a) Fault in the G100. • Disconnect/connect the electricity sup-
ply or
• reset the G100 using the PC Tool G100.
If this does not help, then replace the G100.
5. TxD1 not flashing.
a) No communication with the G100. • Connect the G100.
• Check the cable.
• Check that the cable is connected cor­rectly according to IO type (radio, mo­dem, PLC or direct).
6. RxD1 not on as expected.
a) Cable is connected incorrectly. Check that the cable is connected cor-
rectly according to IO type (radio, modem, PLC or direct).
16
7. Technical data
7.1 Data applying to all versions
Mains supply
Rated voltage 110-240 V AC.
Voltage tolerance –25%/+15% of rated voltage. Mains frequency 45-65 Hz. Power consumption 6 W. Construction
• Number of slots
• Dimensi ons (W x H x D) in mm
• Weight (incl. expansion board)
• 2 (1 for the mother board and 1 for one expansion board).
• 73 x 227 x 165.
• 1800 g.
Operating range
• Ambient tempera ture during operation
• Transportation and storage temperature
• Relative air humidity
• –20°C to +60°C.
• –20°C to +60°C.
• Maximum 95% (without condensation).
Materials, housing Steel. Enclosure class IP 20. Approvals The G100 has been CE marked. CPU
• Proce ssor
• Instruction size
• Proce ssor speed
• Intel 80251.
• 16-bit.
• 20 MHz.
Data logging
FLASH memory size 2 Mb ~ up to 350,000 time-stamped values.
Note: This feature applies to the G100 basic and Radio/ Modem/PLC versions.
GENIbus connection
•Bus
• Connection
• Electri cally separated
• Cable
• RS-485 up to 32 units.
• 9-pin D-sub male connector.
•Yes.
• 0.25 - 1 mm
2
screened 2-core cable.
Maximum cable length: 1200 m.
Connection for service/analysis
•Serial
• Connection
• Electri cally separated
• RS-232.
• 9-pin D-sub male connector.
•No.
Real time clock
• Accuracy
•Battery
• Battery durability
• ±5 min./year.
• DC 3 V, lithium battery for preservation of real time clock during power off.
• When in use > 5 years, when stored > 10 years.
Dig i ta l i npu ts
• Number of inputs
• Input
• Logic "0"
• Logic "1"
• Connection
•4.
• External potential- free NO contact.
• Open (U > 3.2 V).
• Closed (U < 0.9 V).
• 9-pin D-sub male connector, screened cable.
Visual indication
Operating status 6 light-emitting diodes.
17
7.2 Profibus-DP expansion board
7.3 Radio/Modem/PLC expansion board
7.4 Emission (applies to the USA)
8. Disposal
This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Profibus-DP connection
• Communi cation chip
• Communication speed
• Connection
• SPC3.
• 9.6 kbaud to 12 Mbaud.
• RS-485, 9-pin D-sub male connector.
Visual indication
Operating status 1 light-emitting diode.
Radio/modem/PLC connectio n
•Port 1
• Connection
• Communication speed
• Modem type
• Radio type
• RS-232.
• 9-pin D-sub male connector.
• 1.2 to 19.2 kbaud.
• Zyxel or others.
• Radio modem or protocol -based Niros 2001.
Visual indication
Operating status 6 light-emitting diodes.
Radio/Modem/PLC
This equipment has been tested and found to comply with the limits for a Class B digital device, pur­suant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause harmful interference to radio communica­tions. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interfer­ence by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and recei ver.
• Connect the equipme nt into an outlet on a circuit different from that to which the receiver is con­nected.
• Consult the dealer or an experienced radio/T V technician for help.
Profibus-DP
This equipment has been tested and found to comply with the limits for a Class A digital device, pur­suant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause harmful interference to radio communica­tions.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Subject to alterations.
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Lote 34A 1619 - Garin Pcia. de Buenos Aires Phone: +54-3327 414 444 Telefax: +54-3327 411 111
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belorussia
Представительство ГРУНДФОС в Минске 220090 Минск ул.Олешева 14 Телефо н: (8632) 62-40-49 Факс: (8632) 62-40-49
Bosnia/Herzegovina
GRUNDFOS Sarajevo Paromlinska br. 16, BiH-71000 Sarajevo Phone: +387 33 713290 Telefax: +387 33 231795
Brazil
GRUNDFOS do Brasil Ltda. Rua Tomazina 106 CEP 83325 - 040 Pinhais - PR Phone: +55-41 668 3555 Telefax: +55-41 668 3554
Bulgaria
GRUNDFOS Pumpen Vertrieb Representative Office - Bulgaria Bulgaria, 1421 Sofia Lozenetz District 105-107 Arsenalski blvd. Phone: +359 2963 3820, 2963 5653 Telefax: +359 2963 1305
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 22 Floor, Xin Hua Lian Building 755-775 Huai Hai Rd, (M) Shanghai 200020 PRC Phone: +86-512-67 61 11 80 Telefax: +86-512-67 61 81 67
Croatia
GRUNDFOS predstavništvo Zagreb Cebini 37, Buzin HR-10000 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499
Czech Republic
GRUNDFOS s.r.o. Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111 Telefax: +420-585-438 906
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 44 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Mestarintie 11 Piispankylä FIN-01730 Vantaa (Helsinki) Phone: +358-9 878 9150 Telefax: +358-9 878 91550
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706/27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Park u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Lim­ited Flat A, Ground Floor 61/62 Chamiers Aptmt Chamiers Road Chennai 600 028 Phone: +91-44 432 3487 Telefax: +91-44 432 3489
Indonesia
PT GRUNDFOS Pompa Jl. Rawa Sumur III, Blok III / CC-1 Kawasan Industri, Pulogadung Jakarta 13930 Phone: +62-21-460 6909 Telefax: +62-21-460 6910/460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290/95838461
Japan
GRUNDFOS Pumps K.K. 1-2-3, Shin Miyakoda Hamamatsu City Shizuoka pref. 431-21 Phone: +81-53-428 4760 Telefax: +81-53-484 1014
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de Mexico S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Mexico Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Nederland B.V. Postbus 104 NL-1380 AC Weesp Tel.: +31-294-492 211 Telefax: +31-294-492244/492299
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Phone: (+48-61) 650 13 00 Telefax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
România
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундфос Росс ия, 109544 Москва, Школьная 39 Тел. (+7) 095 737 30 00, 564 88 00 Факс (+7) 095 737 75 36, 564 88 11
E-mail grundfos.moscow@grundfos.com
Serbia and Montenegro
GRUNDFOS Predstavništvo Beograd Dr. Milutina Ivkovića 2a/29 YU-11000 Beograd Phone: +381 11 26 47 877, 11 26 47 496 Telefax: +381 11 26 48 340
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 24 Tuas West Road Jurong Town Singapore 638381 Phone: +65-6865 1222 Telefax: +65-6861 8402
Slovenia
GRUNDFOS PUMPEN VERTRIEB Ges.m.b.H., Podružnica Ljubljana Blatnica 1, SI-1236 Trzin Phone: +386 1 563 5338 Telefax: +386 1 563 2098 E-mail: slovenia@grundfos.si
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Lunnagårdsgatan 6 431 90 Mölndal Tel.: +46-0771-32 23 00 Telefax: +46-31 331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-1-806 8111 Telefax: +41-1-806 8115
Taiwan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 947/168 Moo 12, Bangna-Trad Rd., K.M. 3, Bangna, Phrakanong Bangkok 10260 Phone: +66-2-744 1785 ... 91 Telefax: +66-2-744 1775 ... 6
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
ТОВ ГРУНДФОС Укра ин а ул. Владимирская, 71, оф. 45 г. Киев, 01033,
Украина, Тел. +380 44 289 4050 Факс +380 44 289 4139
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971-4- 8815 166 Telefax: +971-4-8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 8TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Usbekistan
Представительство ГРУНДФОС в Ташк енте 700000 Ташк ент ул.Усм ан а Носира 1­й тупик 5 Телефо н: (3712) 55-68-15 Факс: (3712) 53-36-35
Addresses revised 18.04.2006
www.grundfos.com
Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence
96417298 0406
169
Repl. 96417298 0504
Loading...