Grundfos DID BF1, DID BF3 Installation And Operating Instructions Manual

DID
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Other languages
http://net.grundfos.com/qr/i/99037650
English (GB) Installation and operating instructions

English (GB)

These installation and operating instructions describe Grundfos DID (Dosing Instrumentation Digital).
Sections 1-6 give the information necessary to be able to unpack, install and start up the product in a safe way.
Sections 7-13 give important information about the product, as well as information on service, fault finding and disposal of the product.
CONTENTS
Page
1. General information
1.1 Target group
1.2 Symbols used in this document
1.3 Symbols on the product
2. Safety instructions
3. Receiving the product
3.1 Inspecting the product
3.2 Transporting the product
4. Installation
4.1 Installation location
4.2 Installation of the DID
4.3 Hydraulic connection
4.4 Installing the sensors
4.5 Checking the tightness
5. Starting up the product
5.1 Initial startup
6. Electrical connection
6.1 Terminal connection
6.2 Connecting the sensors to the CU 382 control unit
6.3 Connecting the valve for automatic cleaning
6.4 Connecting further inputs and outputs
6.5 Connecting the CU 382 to the power supply
6.6 Start-up of the operating software
6.7 Sensor initialisation
7. Storing and handling the product
8. Product introduction
8.1 Product description
8.2 Intended use
8.3 Functional principle
8.4 Identification
9. Operation
9.1 Operating elements
9.2 Software overview
9.3 General setup
9.4 Parameter setup
9.5 Controller setup
9.6 Alarm setup
9.7 USB menu / Data transfer
10. Maintenance
10.1 Cleaning
10.2 Functional check
11. Fault finding
12. Technical data
12.1 Hydraulic specifications of DID
12.2 CU 382 control unit
12.3 Weights
12.4 Dimensions
13. Disposal
14. Appendix
14.1 Symbols on the product
10 13 18 21 21
22
22 23
24
25
25 25 28 28
29
30
30

1. General information

1.1 Target group

1.1.1 Qualification and training
The persons responsible for installation, startup and service must be appropriately qualified for these tasks.
If the persons do not have the necessary knowledge, training and instruction must be given. If necessary, training can be performed by the manufacturer or supplier on request.
1.1.2 Obligations of the operating company
• Observe the local safety regulations.
2
• Instruct the operating persons.
2
• Provide the stipulated safety equipment and personal
2 2
3
3
3 3
3
3 3 3 4 4
4
4
4
4 5 5 5 5 5 5
6
6
6 7 7 7
8
8 9
protective equipment.
• Arrange regular maintenance.
1.1.3 Obligations of the user
• Read this manual thoroughly before taking the product into operation.
• Observe the recognised health and safety regulations as well as the accident prevention regulations.
• Wear protective equipment in accordance with national health and safety regulations when working on the system and handling chemicals.

1.2 Symbols used in this document

DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
If these instructions are not observed, it may result in malfunction or damage to the equipment.

1.3 Symbols on the product

For symbols on the product see section 14. Appendix.
Prior to installation, read this document. Installation and operation must comply with local regulations and accepted codes of good practice.
2

2. Safety instructions

4. Installation

WARNING
Electric shock
- Switch off the power supply before connecting the power supply cable and relay contacts.
- Do not dismantle the control unit.
- Installation and connection of the device and the associated supplementary components must only be carried out by qualified persons.
- Maintenance and repair must only be carried out by qualified persons.
- Observe the local safety regulations.
WARNING
Toxic material
- Parts of the DID can be contaminated with dangerous chemicals or pathogenic germs.
- If the DID has been in contact with dangerous chemicals or pathogenic germs, wear protective clothing and take all necessary precautions to prevent endangering your health when installing or dismantling the DID.
Modification of the DID is strictly prohibited.

3. Receiving the product

3.1 Inspecting the product

• Check the received consignment for completeness.
• Check the DID for damage.
• Install as soon as possible after unpacking.
• Do not install or connect damaged products.

3.2 Transporting the product

• Before transporting the DID, empty all pipes, hoses and flow cells, remove the sensors and pack them separately.
• Observe the permissible ambient conditions. See section
12. Technical data.
• Transport the DID carefully, do not drop. Do not expose the DID to strong impact, mechanical loads or vibrations.
• Keep the DID away from corrosive substances, vapours of organic solvents, nuclear radiation and strong electromagnetic radiation.
• Use the original packaging or equivalent to protect the DID during transport.
WARNING
Electric shock
- Switch off the power supply before installation.
- IP65 only applies, if the housing cover and the terminal compartment of the CU 382 are properly closed, and the appropriate cable glands or dummy caps are fitted.
- Installation must be carried out by qualified and authorised persons.

4.1 Installation location

Correct installation is important for proper functioning of the DID.
• Make the DID easily accessible for all tasks.
• Provide sufficient space for all components of the DID.
• Avoid external interferences, such as electric and electro­magnetic interferences by leakage current, earth fault of pumps, electric motors, high voltage currents.
• Protect the DID from direct sunlight and rain.
• Provide a reliable power supply for the control unit.
See also section 12. Technical data and the manual "Sensors V1".

4.2 Installation of the DID

DID with flow cell
All parts of the DID with flow cell are assembled on a mounting plate with pre-drilled holes for quick and easy installation.
• Use spacers (min. 10 mm) for installation of the DID with flow cell on a flat wall.
See also sections 8. Product introduction and 12.4 Dimensions.
DID with sensor for tank immersion
The CU 382 control unit of the DID with sensor for tank immersion can be mounted directly on a wall. See also sections 8. Product
introduction and 12.4 Dimensions.

4.3 Hydraulic connection

See also the labels on the mounting plate as well as the sections
12. Technical data and 14. Appendix.
The maximum flow through the flow cell of the DID is limited by the integrated flow restrictor.
Use a vented outlet or a pressure-loading valve to avoid siphon effect. Do not install a shut-off valve in the outlet line.
English (GB)
3
4.3.1 Installing the measuring water inlet and outlet
Hose
Union nut
Tensioning ring
Cone part
13 579
RS485
11 13 15 17 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53
2 4 6 8 10 12 14 16 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 55 5418
19
12 V Out
GND
4/20 #1
4/20 #2
4/20 #3
4/20 ln #1
4/20 ln #1
ln #1
ln #2
Flow #1
RS485
MOD 1
MOD 1
MOD 2
MOD 2
Relay 1 Relay 2
Err
Err
RS485
Valve
Clean in
4/20 #1
4/20 #2
4/20 #3
4/20 ln #1
ln #1
ln #2
Flow #1
RS485
MOD 1
MOD 1
MOD 2
MOD 2
Relay 1 Relay 2
Err
Err
90...240 VAC
90...240 VAC
P
A-
A-
PS
+
+
+
+
+
+
+
NO
NO
NO
NC
N
B+
B+
-
+
-
-
-
-
-
C
C
C
C
+
English (GB)
1. Remove the blind plugs from the inlet thread and the outlet thread of the flow cell.
Fig. 1 Blind plug
2. Connect the Rp 1/2" hose adaptor fittings to the inlet and the outlet.
– The Rp 1/2" hose adaptor fittings are included in the
standard delivery of the DID.
3. Assemble the inlet and the outlet hose as follows: – Push union nut and tensioning ring across the hose. – Push the cone part fully into the hose, see fig. 2. – Attach the cone part with hose to the adaptor fitting. – Tighten the union nut manually. Do not use tools.
Fig. 2 Connecting the inlet hose
Avoid high loads caused by long or heavy hoses hanging from the outlet port of the flow cell. A strain-relief for the outlet hoses may be required.

4.4 Installing the sensors

All sensors used in the DID are packed separately to avoid damage. They have to be prepared before installation according to the "Installation" section in the manual "Sensors V1" supplied with the sensor.
• For installation of the sensors in the flow cell, see the manual
"Sensors V1" supplied with the sensors.
• As soon as the sensors are ready for operation, they must be
wetted.

5. Starting up the product

5.1 Initial startup

WARNING
Electric shock
- Switch off the power supply before startup.
- IP65 only applies, if the housing cover and the
TM06 5927 0316TM04 1155 0110
1. Connect all sensors to the CU 382 control unit. See also section 6.2 Connecting the sensors to the CU 382 control unit.
2. Slowly open the inlet valve.
3. Check the hydraulic system of the DID for leakages.
terminal compartment of the CU 382 are properly closed, and the appropriate cable glands or dummy caps are fitted.
- Initial startup must be carried out by qualified and authorised persons.

6. Electrical connection

6.1 Terminal connection

WARNING
Electric shock
- Switch off the power supply of the DID and all devices you plan to connect before terminal connection.
- Terminal connection must be carried out by qualified and authorised persons.
6.1.1 Connecting the terminals
1. Remove the two cross-head screws on the terminal compartment of the CU 382 control unit.
2. Open the terminal compartment.
3. Connect the terminals according to the terminal connection plan shown in fig. 3.
• Sensors equipped with electrolyte and membrane cap must

4.5 Checking the tightness

1. Carefully open the inlet valve and check for any leakage of the
2. Check if any air bubbles are visible within the hose.
3. Purge the bubbles out by temporary increase of the flow.
4
remain powered.
flow cell assembly.
TM06 5958 0316
Fig. 3 Terminal connection plan
Description and use of the terminals
Terminal Description Use
1Phase 2 Neutral 3PE 4PE
5-8 Unused, can be used to connect S::CAN sensors
9 12 V output
Cleaning valve output (provides
10
power for the valve +12 V) GND, for cleaning valve and
11
external trigger 12 External trigger for cleaning valve 13 4-20 mA output #1 (+) 14 4-20 mA output #1 (-) 15
Shield connections (optional) 16
17 4-20 mA-output #2 (+) 18 4-20 mA-output #2 (-) 19
Shield connections (optional) 20
21 4-20 mA-output #3 (+) 22 4-20 mA-output #3 (-)
Power supply for 4-20 mA input 23
(only for passive sources) 24 4-20 mA-input #1 (-) 25 4-20 mA-input #1 (+) 26 Shield connection (optional)
Digital input #1 (+), relay to switch 27
on/off or as pulse source 28 Digital input #1 (-)
Digital input #2 (+), relay to switch 29
on/off or as pulse source 30 Digital input #2 (-)
Flow #1, flow switch of bypass flow 31
cell, pre-wired in BF1/BF3
Flow #1, flow switch of bypass flow 32
cell, pre-wired in BF1/BF3 33 RS485 A­34 RS485 B+ 35 RS485 GND 36 RS485 shield
37-46 Unused, for later add-ons
Relay 1-NO, switches on/off or 47
provides pulse frequency 48 Relay 1-C, common connector
Relay 2-NO, switches on/off or 49
provides pulse frequency 50 Relay 2-C, common connector
Alarm relay NO 51
Relay closes on alarm 52 Alarm relay C, common connector
Alarm relay NC 53
Relay opens on alarm
Alarm relay C, common connector, 54
duplication of 52
Power supply
(100-240 V,
50-60 Hz)
Cleaning valve
control
Analog outputs
Analog input
Digital inputs
Flow cell - flow
switch
Modbus to
upper controls
(CU 382 is
slave)
Digital output
(with relays)
Alarm relay

6.2 Connecting the sensors to the CU 382 control unit

All sensors for the DID have plugs. Sensors for immersion have fixed cables with plugs.
1. Make sure that the sensor plug and the socket of the CU 382 control unit are dry and clean.
– Otherwise communication errors may occur and the DID
might be damaged.
2. Connect the sensor to a compatible socket on the CU 382 control unit using the connection cable provided.
3. Cover the connectors that are not used with protective caps.

6.3 Connecting the valve for automatic cleaning

Only DID with sensor for tank immersion with valve for automatic cleaning:
• Connect the valve to terminals 10 ("Valve", "12 VDC") and 11
(GND). See fig. 3.
• If an external cleaning signal is used, connect the signal line to
terminal 12 ("Clean In", minimum 5 V).

6.4 Connecting further inputs and outputs

Observe the supplier manuals when connecting actuator devices, such as dosing pumps or regulators.

6.5 Connecting the CU 382 to the power supply

WARNING
Electric shock
- Switch off the power supply before connecting the CU 382 control unit.
- IP65 only applies, if the housing cover and the terminal compartment of the CU 382 are properly closed, and the appropriate cable glands or dummy caps are fitted.
- Electrical connection must be carried out by qualified and authorised persons.
• Install an earth leakage circuit breaker for the power supply.
• If the installation is in an area prone to lightning strikes, install surge protection.
• Use an AC power supply with an earthed conductor wire.
– PE: potential earth
• Connect the process medium (e.g. waste water) to the same earth ground with less than 0.5 Ohm.

6.6 Start-up of the operating software

If the CU 382 control unit is connected to the power supply, it starts up and shows the s::can logo for 5 seconds. At first start-up or if the internal settings have been reset to default, the CU 382 control unit starts with the selection of the language. See also section 9.3.7
After this, the parameter screen is shown and the most recent information is displayed.
Select language...
.

6.7 Sensor initialisation

Every sensor that is connected to the CU 382 control unit must be installed and initiated individually. This can be done using the software-supported initialisation process.
• Connect only the sensor you want to initialise to the CU 382.
– An individual address is allocated to the initialised sensor.
If no sensor was connected before, the CU 382 jumps into the "Add MODBUS sensor..." menu to check for connected sensors, right after setting the language.
English (GB)
5

7. Storing and handling the product

9
5
4
3
2
1
11
10
10
12 13 14
15 15
15
15
7
6
6a
8
18
T
OK
W
X
S
19
6c
6b
8
11
10
10
8
7
16
17
T
OK
W
X
S
12 13 14
English (GB)
• Before storing the DID, empty all pipes, hoses and flow cells, remove the sensors and pack them separately.
• Observe the permissible ambient conditions. See section
12. Technical data.
• Do not expose the DID to strong impact, mechanical loads or vibrations.
• Keep the DID away from corrosive substances, vapours of organic solvents, nuclear radiation and strong electromagnetic radiation.
• Use the original packaging or equivalent to protect the DID during storage.

8. Product introduction

8.1 Product description

TM06 8089 3416
Fig. 5 Components of DID with immersed sensor
Pos. Description
1 Water inlet 2 Inlet valve 3 Inlet strainer 4 Flow restrictor, mechanical 5 Flow detector, digital
6 Flow cell for up to three sensors 6a Sampling valve 6b Sampling point 6c Water outlet
7 Sensors
8 CU 382 control unit
9 Opening for power supply and sensor cables
TM06 8088 3416
Fig. 4 Components of DID with flow cell
10 Screws for the terminal compartment 11 Latch of CU 382 cover 12 Cable gland for power supply 13 Connectors for Modbus sensors 14 Cable gland for signal inputs and outputs 15 Holes for wall mounting 16 Sensor holder 17 Protective cover 18 Mounting plate 19 DID nameplate
6

8.2 Intended use

1
2
3
5
7
8
10,11,12 13 14
4
6
9
1
2 3
4
5
6
7
The DID is designed for online monitoring of water quality parameters and offers control functions for these parameters.
The DID must be used in accordance with the instructions given in this manual. The values mentioned in this manual must be observed.

8.3 Functional principle

The CU 382 control unit has a display and 7 operating buttons on the front. The operating software starts automatically when the CU 382 is powered-on.
The CU 382 control unit collects and displays readings from all sensors via a digital bus connection. The CU 382 control unit includes a PID (Proportional-Integral-Derivative) controller. With the PID controller and dosing units, a closed control loop can be set up.
The hydraulic part of the DID manages the complete water flow from the inlet to the outlet. This includes filtration, pressure reduction, flow restriction and flow control. The DID comprises specifically designed flow cells for mounting of the sensors and appropriate sampling.

8.4 Identification

8.4.1 Nameplate
Fig. 6 Nameplate on the CU 382 control unit
Pos. Description
1 Manufacturer and country of origin 2 s::can product name 3 Number of sensors 4 Bar code 5 Serial number (S/N) 6 Enclosure class 7 Certification marks 8 QR code
9Type 10 Voltage [V] 11 Frequency [Hz] 12 Power consumption [W] 13 Humidity limits 14 Temperature limits
Fig. 7 Nameplate on the DID
Pos. Description
1 s::can product name 2 Parameter 3 Mounting type 4Type 5 Part number 6 Bar code 7 Serial number (S/N)
8.4.2 Type key
Example: DID-3 BF3-FCL2/TCL2/pH
Code Description
CU 382 control unit variants
DID-1
DID-3
CU 382-1 for 1 parameter + temperature, 100-240 VAC, 50-60 Hz
CU 382-3 for 3 parameters + temperature, 100-240 VAC, 50-60 Hz
BF1 Bypass flow cell, 1 sensor
TM06 5920 0316
Installation variant
BF3 Bypass flow cell, 3 sensors TI1 Tank immersion, 1 sensor TI2 Tank immersion, 2 sensors FCL2 Free chlorine 0-2 ppm FCL20 Free chlorine 0-20 ppm TCL2 Total chlorine 0-2 ppm TCL20 Total chlorine 0-20 ppm CDI2 Chlorine dioxide 0-2 ppm CDI20 Chlorine dioxide 0-20 ppm
Parameters/ Sensors
HP2 Hydrogen peroxide 0-200 ppm HP20 Hydrogen peroxide 0-2000 ppm PA2 Peracetic acid 0-200 ppm PA20 Peracetic acid 0-2000 ppm pH pH 2-12 pH up to 10 bar and 70 °C
ORP
CND
ORP, -2000 mV to +2000 mV up to 10 bar, up to 70 °C
Conductivity, 1-500,000 µS/cm (2-42 PSU), up to 20 bar, up to 70 °C
Remarks:
• All sensors include temperature measurement
• Disinfectant parameters (FCL,TCL, CDI, HP or PA) are only possible with BF1 or BF3
• BF1 and BF3 include flow detection
• BF1 and BF3 systems include 1.0 m sensor cables
• Installation variants TI1 and TI2 are only possible for parameters PH, ORP or CND
• TI1 and TI2 systems include 7.5 m sensor cable(s)
• Mains cable is generally not included, please select and order from accessories list.
English (GB)
TM06 8610 0817
7

9. Operation

OK
1 2 3
45
OK
English (GB)

9.1 Operating elements

Fig. 8 CU 382 operating elements
Pos. Description
1 Power LED, green
Communication LED, orange
2
• Flashes during communication with a sensor. 3USB slot 4 Display
Operating buttons
TM06 5854 0216
[Back] button
• Exits the current menu
[Up] button
• Moves the marker to the line above – The first character of the selected
line is a triangle
• Increases values
[Function] button
• Enters the setup menus
• Disables or deletes values
5
[Left] button
• Moves the marker to the left
[OK] button
• Enters the selected menu
• Confirms the selected line or value
• Acknowledges alarms
[Right] button
• Moves the marker to the right
[Down] button
• Moves the marker to the line below – The first character of the selected
line is a triangle
• Decreases values
8

9.2 Software overview

The CU 382 has four different screens and menus, which can be selected by the [Right] and [Left] buttons. The default screen is the "Parameter" screen.
When pressing the [Back] button several times in a submenu, you come back to one of the following screens:
Status Parameter Controller Alarm
Status
Version : V7.05B1 Serial : 9999999 Waiting 1 s
YYYY/MM/DD hh:nn:ss 22.1
> <
General setup Parameter setup Controller setup Alarm setup
Manage sensors
Cleaning1 Monitor... Settings ... PID/2-P/None
Meas. settings Display settings... Source: Date/Time Alarm settings... Output: DI/mA MODBUS slave Output: Output settings... Update software Output settings... Alarm settings... Select language... pH compensation... Reset state Service Parameter info... Diagnosis Remove parameter
9.2.1 Status screen 9.2.2 Parameter screen
Status >
Version : V7.05B1 Serial: 9999999 Waiting 1 s
2015/Oct/05 16:40:49
"Version :" Software version "Serial:" Serial number of the CU 382 "Waiting" Waiting time until the next action (start of
measurement or start of cleaning) starts. The waiting time can be set in the "Meas. settings" menu.
"YYYY/MM/DD" Current date and time
P1/3 pH
9.49 Type: PID/Running %ls below
Calibrate expert...
>
pH
Temp.:
<
pH >4-20mA #2 lower alarm limit AV/SP: 6.86/7.00 (ext.)
C
Setpoint...
C2/2
15 % YYYY/MM/DD
>
<
Acknowledgment of alarms
Up to 8 parameters can be configured and displayed in the parameter screen, for example:
• Sensor reading
• Analog input
• Digital input
• Flow guard Scroll through the list of configured parameters with the [Up] and
[Down] buttons.
< P1/3 FCL >
0.531
7.8
English (GB)
AP001 A1/1
FCL mg/l
pH
"FCL" Parameter name "mg/l" Parameter unit "pH" Parameter name
Calibration
"Span" calibration and "Offset" calibration can be started directly from the parameter screen. For the calibration procedures, see
Calibrate expert...
9.4.1
.
9
9.2.3 Controller screen
English (GB)
Up to 3 controllers can be configured and displayed. Scroll through the list of controllers with the [Up] and [Down]
buttons.

9.3 General setup

In the "Setup" menu, general settings can be made.
• Press the [Function] button in the status screen to open the "Setup" menu.
< C2/2 pH >
15 %
Type: PID/Running pH >4-20mA #2 AV/SP: 6.86/7.00 (ext.)
"C2" Controller 2 "15 %" Output of the controller in % "Type:" Controller type: "2-P" or "PID"
Controller status
•"Running": the controller is running and dosing is activated
•"Stopped": the controller is stopped and no dosing takes place
For more information see section 9.5 Controller
setup.
"pH" Input parameter
• Input options: sensor reading, analog input, digital input
">4-20mA #2" Output of the controller
• Output options: analog outputs (4-20mA), digital outputs (PULSE or PWM)
"AV/SP" "AV" is the actual value (input parameter reading)
"SP" is the setpoint (desired value of the input parameter reading) Source of the setpoint:
•"External"
•"Manual"
Adjusting the output manually
1. Press [OK].
2. Select a value with the [Up] and [Down] buttons.
3. Confirm with [OK]. – The controller type changes to "Hand".
4. Press [OK] again to go back.
5. Press the [Function] button to clear the manual value of the output.
– The value changes to "---".
6. Press [OK] to set the controller back to "2-P" or "PID".
9.2.4 Alarm screen
< AP001 A1/1
2015/Oct/05 16:42:21
Setup
Manage sensors...
Cleaning 1...
Meas. settings...
Date/Time...
MODBUS slave...
Setup
MODBUS slave...
Update software...
Select language...
Service...
Diagnosis...
Submenu Settings
"Manage sensors..."
"Cleaning 1..."
"Meas. settings..."
"Date/Time..." Adjust date and time.
"MODBUS slave..."
"Update software..."
"Select language..." Choose the operating language.
"Service..."
"Diagnosis"
9.3.1 Manage sensors
Manage sensors
pH::lyser
chlori::lyser digital in #1
Add sensor...
Add, remove, configure sensors or parameters.
DID with immersed sensor and cleaning device: Configure cleaning device.
Set the measurement interval between 1­99 s.
If CU 382 is used as MODBUS-Slave: Change MODBUS settings.
Update the software of the control unit via the USB port.
Make additional settings and function checks. This menu is protected by a password and should only be opened by an authorised person.
Only for service, if the DID is sent back to the manufacturer.
%ls below
lower alarm limit
"AP001 A1/1" The amount of alarms and the number of the
selected alarm "2015/Oct/05" The date of occurrence of the alarm "16:42:21" The time of occurrence of the alarm "%ls below" "lower alarm limit"
An alarm can be acknowledged with [OK]. If the reason of the alarm is still present, a new alarm will be generated immediately.
The alarm message
10
"pH::lyser/0/1" "chlori::lyser/0/2" "digital in #1" Configured inputs (digital or analog)
"Add sensor..." Add a new sensor
Names of the connected sensors
Sensor configuration
• Select a sensor or an input with the [UP] and [DOWN] buttons.
Confirm with [OK].
– The "Sensor configuration" menu opens.
Sensor configuration
Configure...
Add parameters...
Remove
Configure...
• Select "Configure..." with the [Up] and [Down] buttons.
Confirm with [OK].
– The "Configure..." menu opens.
Configure...
Type: 4-20mA
The "Configure..." menu is available for analog and digital inputs. If an analog input is chosen, the following settings can be
configured:
•"0-20mA"
•"4-20mA"
Configure...
Type: State
Invert pol. : No
Removing a sensor
1. Select "Remove" with the [Up] and [Down] buttons.
2. Confirm with [OK]. The sensor and the parameters for the sensor are removed. If an
input of a controller is linked to the sensor or parameter, the controller is deactivated.
Adding a new sensor
1. Select "Add sensor..." in the "Manage sensors" menu with the [Up] and [Down] buttons.
2. Confirm with [OK]. – The "Add new sensor" menu opens.
Add new sensor
Add 0/4-20mA...
Add digital in...
Add MODBUS sensor...
• To add an analog sensor select "Add 0/4-20mA..." with the
[Up] and [Down] buttons. Confirm with [OK].
• To add a digital sensor select "Add digital in..." with the [Up]
and [Down] buttons. Confirm with [OK].
• To add a MODBUS sensor select "Add MODBUS sensor..."
with the [Up] and [Down] buttons. Confirm with [OK].
– The MODBUS port for a new sensor is searched and the
new sensor is added to the sensor list automatically. No further interaction is required.
After adding a sensor, a parameter has to be added. See section
Adding a parameter.
9.3.2 Cleaning device
The "Cleaning 1..." menu is used for the DID with sensor for tank immersion, if an automatic cleaning device is installed.
English (GB)
Configure...
Type: Count
Interval [s] : 60
If a digital input is chosen, the following settings can be configured:
•"State": Depending on the contact type of the digital input, the result is 1 or 0.
– The contact type of the digital input can be changed with
"Invert pol. :".
•"Count": Counts the digital pulses within the interval.
– The interval can be defined with "Interval [s] :".
Adding a parameter
Add para.
Add pH
Add pH-mV Add Temp.:
1. Select a parameter with the [Up] and [Down] buttons.
2. Confirm with [OK].
Cleaning 1...
Interval [s] : 120
Duration[s] : 2 Wait [s] : 0
"Interval [s] :" The time between two cleaning actions "Duration[s] :" The time the cleaning device is activated for one
cleaning action
"Wait [s] :" The time before starting a new measurement
after a cleaning action is finished
Changing the cleaning interval
1. Select "Interval [s] :" with the [Up] and [Down] buttons. Confirm with [OK].
2. Change the interval value with the [Up] and [Down] buttons. Confirm with [OK].
Changing the cleaning duration
1. Select "Duration[s] :" with the [Up] and [Down] buttons. Confirm with [OK].
2. Change the duration value with the [Up] and [Down] buttons. Confirm with [OK].
Changing the delay before a new measurement
1. Select "Wait [s] :" with the [Up] and [Down] buttons. Confirm with [OK].
2. Change the delay value with the [Up] and [Down] buttons. Confirm with [OK].
11
Loading...
+ 23 hidden pages