Grundfos DID Installation And Operating Instructions Manual

DID
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
English (GB)
2
English (GB) Installation and operating instructions
CONTENTS
Page
1. General information
These installation and operation instructions describe Grundfos DID (Dosing Instrumentation Digital).
Sections 1-6 give the information necessary to be able to unpack, install and start up the product in a safe way.
Sections 7-13 give important information about the product, as well as information on, fault finding and disposal of the product service.
1.1 Target group
The responsible staff must read these installation and operating instructions prior to any work at the product. These installation and operating instructions must be available at the installation location at all times.
1.1.1 Qualification and training of staff
The staff responsible for the installation, startup, operation and maintenance must be qualified for these tasks. Areas of responsibility, levels of authority and the supervision of the staff must be precisely defined by the operating company. If necessary, the staff must be trained.
1.1.2 Obligations of the operating company
• Observe the local safety regulations.
• Instruct the operating staff.
• Provide the stipulated safety equipment and personal protective equipment.
• Arrange regular maintenance.
1.1.3 Obligations of the user
• Read this manual thoroughly before putting the product into operation.
• Observe the recognised health and safety regulations as well as the accident prevention regulations.
• Wear protective equipment in accordance with national health and safety regulations when working at the system and handling chemicals
1.2 Symbols used in this document
The text accompanying the three hazard symbols DANGER, WARNING and CAUTION will be structured in the following way:
Example
1. General information
2
1.1 Target group
2
1.2 Symbols used in this document
2
1.3 Symbols on the product
3
1.4 Safety of the system in the event of product failure
3
1.5 Working with chemicals
3
2. Safety instructions
3
3. Receiving the product
3
3.1 Transporting the product
3
3.2 Scope of delivery
3
3.3 Product updates, other
3
4. Installing the product
3
4.1 Installation location
3
4.2 Installing of DID
3
4.3 Installing of hydraulic system
3
4.4 Installing of sensors
4
4.5 Checking of tightness
4
5. Starting up the product
4
5.1 Initial startup
4
5.2 Terminal connection
4
5.3 Connection of sensors to the control unit CU 382
5
5.4 Connection of valves for automatic cleaning
5
5.5 Connection of further in/outputs
5
5.6 Connection of power supply
5
5.7 Starting up of operating software
5
5.8 Sensor initialisation
5
6. Storing and handling the product
5
7. Product introduction
6
7.1 Intended use
6
7.2 Functional principle
6
7.3 Components
6
7.4 Identification
7
8. Control functions
9
8.1 Operating elements
9
8.2 Functions overview
9
9. Operating the product
10
9.1 Software overview
10
9.2 General set up / status
11
9.3 Parameter / settings
13
9.4 Controllers / settings
17
9.5 Alarms
20
9.6 USB menu / Data transfer
20
10. Servicing the product
21
10.1 Cleaning
21
10.2 Functional check
21
11. Troubleshooting
22
12. Technical data
23
12.1 Hydraulic specifications
23
12.2 Control unit 382
23
12.3 Weights
26
12.4 Dimensions
26
13. Appendix
28
13.1 Symbols on the product
28
Prior to installation, read this document. Installation and operation must comply with local regulations and accepted codes of good practice.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
Action to avoid the hazard.
DANGER
Electric shock
Death or serious personal injury.
Before starting any work on the product, make sure that the power supply has been switched off and that it cannot be accidentally switched on.
English (GB)
3
1.3 Symbols on the product
Symbols on the product see section13. Appendix
1.4 Safety of the system in the event of product failure
If the product fails, the safety of the overall system must be ensured. Use appropriate monitoring and control functions.
Any kind of manipulation of the instrument is strictly prohibited ­except for the activities described in this document. Conversions and changes to the device must not be made, otherwise all certifications and guarantee / warranty become invalid. For details regarding guarantee and warranty please refer to our general terms and conditions.
1.5 Working with chemicals
2. Safety instructions
Non-observance of the safety instructions may have dangerous consequences for the staff, the environment and the product and may result in the loss of any claims for damages.
The operating software of control unit 382 does not contain any safety-related functions.
Should you require further information, please contact Grundfos.
3. Receiving the product
3.1 Transporting the product
The temperature and humidity limits for device transport, which are described in the section Technical data, are to be observed at all times. The device shall not be exposed to strong impacts, mechanical loads or vibrations. The device should be kept free of corrosive or organic solvent vapours, nuclear radiation as well as strong electromagnetic radiation.
Transport should be done in a packaging that protects the device (original packaging or protective covering if possible). Before transport, piping and flow cells have to be emptied, and sensors removed and if necessary separately packed.
3.2 Scope of delivery
Immediately upon receipt, please check the received consignment for completeness on the basis of the delivery note and check for any possible damage incurred during shipping. Please inform the delivering dispatcher and Grundfos immediately in case of any damages in transit.
In case of incompleteness please contact your local sales partner immediately!
3.3 Product updates, other
The manufacturer reserves the rights to implement, without prior notice, technical developments and modifications in the light of continuous product care.
4. Installing the product
4.1 Installation location
As the correct installation of the DID is an important prerequisite for satisfactory operation the following checklist for the installation can be used to ensure that all sources for potential operational problems can be ruled out to the greatest possible extent during the installation, allowing the DID to operate properly.
• Easy accessibility (mounting, sampling, functional check, demounting)
• Availability of sufficient space sensor, installation fitting, control unit, etc.)
• No external interferences (i.e. no electric and electro-magnetic interferences by leakage current, earth fault of pumps, electric motors, high voltage currents, etc.)
• Best possible weather and splash water proof set-up
• The panel is to be protected from UV (direct sunlight) to avoid premature aging of plastic components.
• Power supply for control unit (operational reliability, voltage, power)
For environment limits of installed sensors please refer to the sensor manual.
The DID is designed to operate with drinking water at pressures up to 0.3 MPa (43 psi) and temperatures from 0 (non freezing) to 45 °C (32 to 113 °F). Enclosure class of CU 382 is IP65.
4.2 Installing of DID
All parts of the DID are mounted onto a flat panel (see section
7.3 Components). The complete DID can be mounted quickly and
easily with spacer (min. 10 mm) onto a flat wall. The mounting holes for bolts or screws have been pre-drilled and are indicated in the dimensional drawings. For the correct dimensions and space required for mounting please refer to the figure in section
12.4 Dimensions.
For DID versions with tank immersed sensors the control unit CU382 is mounted directly on the wall. The drilling scheme is shown in section 12.4_dimensions.
4.3 Installing of hydraulic system
Sample water inlet and outlet have to be mounted onto the DID, which will require the following actions, in the order presented below:
• Remove the two blind bolts used for transport from the inlet threat and the outlet threat of the flow cell using a 10 mm hexagon socket screw key (see Fig. 1 below).
• Mount the specific fitting onto the outlet
• Mount the customer inlet tube onto the 1/2" inlet fitting
Fig. 1 Outlet fitting
WARNING
Danger of personal injury due to contact with chemicals!
Wear the stipulated personal protective equipment (protective clothing, goggles, respirator etc.) when handling chemicals!
Observe the chemical manufacturer's safety data sheets (MSDS) and safety instructions of the used chemicals!
WARNING
Electric shock
• Switch off the power supply before connecting the power supply cable and relay contacts!
• Do not dismantle the device!
• Maintenance and repair must only be carried out by qualified personnel!
WARNING
Toxic material
Because the DID can be installed in industrial and waste water applications, one has to take care during mounting and demounting of the system, as parts of the device can be contaminated with dangerous chemicals or pathogenic germs. All necessary precautions should be taken to prevent endangering of one’s health during work with the measuring device.
WARNING
Electric shock
Switch off the power supply before installing! Enclosure class IP65 is only guaranteed if the terminal cover is correctly sealed, if the front panel of the terminal enclosure is closed and the appropriate cable glands or dummy caps fitted
TM06 5927 0316
English (GB)
4
Please note the pressure and flow limitation of the DID as explained in the technical data on the warning label. Independent of the inlet discharge the flow within the DID will be reduced by the flow restrictor to the correct amount.
• Mount the customer outlet tube onto the 1/2" outlet fitting
• Ensure proper layout of the outlet tube to avoid soaking
The tubing on the outlet has to be designed in that way that a draining of the flow cell is not possible. To ensure this a vented outlet has to be used. Furthermore no shut-off valve should be used to avoid back pressure within the flow cell.
• Install strain-relief in case of long / heavy outlet tubes to avoid mechanical load of the flow cell.
• Due to sealing plugs on in- and outlet, proper 1/2" fittings have to be mounted by the costumer (part of delivery).
• High loads due to heavy tubes on the outlet port of the flow cell can damage the mounting of flow cell. Therefore it is recommended to install a strain-relief for the outlet tubing.
4.4 Installing of sensors
All sensors used in the DID are packed separately to avoid any damage. They have to be prepared before installation according to the section Installation in the sensor manual. Within this manual you will also find a detailed explanation how to mount the sensors into the flow cell.
As soon as the sensors are ready for operation they should be wetted all the time. All sensors equipped with electrolyte and membrane cap have to be powered all the time.
4.5 Checking of tightness
Carefully open the inlet valve on the inlet and check for any leakage of the DID. Check if any air bubbles are visible within the tubes and spill them out by temporary increase of the discharge.
5. Starting up the product
5.1 Initial startup
Once the mounting and installation have been completed and checked, the initial start up of the DID will require the following actions, in the order presented below:
Described below are the steps that are specific for the DID and that are not covered in the specific manuals of the sensors included in your DID. The DID specific actions are to be performed in the following order:
1. Connect all sensors to the control unit CU 382
2. Open inlet valve slowly
3. Check for leakage in the hydraulic system of the DID
5.2 Terminal connection
Once the cover has been opened (two cross head screws removed) you have access to the cable terminal compartment of the control unit CU 382.
Be aware that cable clamps of relay contacts you have connected to the device might also have power supply (230 VAC), depending on how they have been interconnected!
Fig. 2 Plan of terminal connections within control unit CU 382
WARNING
Electric shock
Switch off the power supply before installing! Enclosure class IP65 is only guaranteed if the terminal cover is correctly sealed, if the front panel of the terminal enclosure is closed and the appropriate cable glands or dummy caps fitted.
This type of work must be carried out by authorized persons only and after disconnecting the power supply!
TM06 5958 0316
13 579
RS485
11 13 15 17 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53
2 4 6 8 10 12 14 16 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 55 5418
19
12 V Out
GND
4/20 #1
4/20 #2
4/20 #3
4/20 ln #1
4/20 ln #1
ln #1
ln #2
Flow #1
RS485
MOD 1
MOD 1
MOD 2
MOD 2
Relay 1
Relay 2
∑ Err
∑ Err
RS485
Valve
Clean in
4/20 #1
4/20 #2
4/20 #3
4/20 ln #1
ln #1
ln #2
Flow #1
RS485
MOD 1
MOD 1
MOD 2
MOD 2
Relay 1
Relay 2
∑ Err
∑ Err
90...240 VAC
90...240 VAC
P
A-
A-
PS
+
+
+
+
+
+
+
NO
NO
NO
NO
N
B+
B+
-
+
-
-
-
-
-
C
C
C
C
+
English (GB)
5
5.3 Connection of sensors to the control unit CU 382
All sensors for the DID will be delivered with a plug connection on the sensor itself. The connection cable C-1-010 has to be used to connect the sensor to a compatible socket provided on the control unit CU 382. Sensors for submersed installation are equipped with a fixed cable already including the plug.
Before connecting the sensor, ensure that the sensor plug and the connector on the control unit are dry and clean. Otherwise communication errors and / or device damage might occur. Connectors not in use should always be covered with the protective cap.
5.4 Connection of valves for automatic cleaning
Valves, used for steering of the automatic sensor cleaning in case of submersed installation, can be wired to the terminals 10 (Valve) and 11 (GND) to supply the valve with 12 VDC power (see Fig. 2). In case a separate cleaning signal is used, this can be wired to the terminal 12 (Clean In). This steering signal has to be at least 5 V.
5.5 Connection of further in/outputs
For connecting actuator devices (e.g. dosing pumps or chlorine regulators), please observe the relevant documentation.
5.6 Connection of power supply
The control unit CU 382 has to be connected to the appropriate power supply. The connection of power supply (AC), has, without fail, to include an earthed conductor wire (PE - "potential earth")!
The power supply earth (PE) is to be made properly. Process medium (e.g. waste water) must be connected to the same earth ground with less than 0.5 Ohm.
The power supply has to be equipped with an earth leakage circuit breaker.
5.7 Starting up of operating software
Once the control unit CU 382 has been connected to the power supply, it will show the s::can logo for 5 seconds while starting-up. If the CU 382 internal settings have been reset to default, the CU 382 will start with the selection of the language (see section
9.2.8 Select language). Subsequently, reading and information display will be shown. The
most recent information obtained by the CU 382 will be displayed, even when no sensor is connected.
When no communication to an installed sensor is possible, only those menus are available that are not concerning a sensor’s settings (see section 9.2 General set up / status). In this case the error relay will be in "error" mode. In case of such an error, an entry to that effect is made in the logbook (see section 9.6 USB menu / Data transfer).
5.8 Sensor initialisation
For operating the control unit CU 382 with one or several sensors it is necessary to install (initialise) every single sensor on the CU
382. This can be done using the software supported initialization process. During this process one sensor has to be connected to the CU 382 and all other sensors are disconnected. Doing so an individual address will be allocated to every sensor. The corresponding address will be stored on the respective sensor.
Section 9.2.2 Manage parameters will guide you through this task.
6. Storing and handling the product
The temperature and humidity limits for device storage, which are described in the section Technical data, are to be observed at all times. The device shall not be exposed to strong impacts, mechanical loads or vibrations. The device should be kept free of corrosive or organic solvent vapours, nuclear radiation as well as strong electromagnetic radiation.
Damage to the sensor caused by wrong storage will not be covered by warranty (please refer to the sensor manual).
Observe the permissible ambient conditions! See section
12. Technical data
WARNING
Electric shock
Switch off the power supply before installing! Enclosure class IP65 is only guaranteed if the terminal cover is correctly sealed, if the front panel of the terminal enclosure is closed and the appropriate cable glands or dummy caps fitted.
This type of work must be carried out by authorized persons only and after disconnecting the power supply!
English (GB)
6
7. Product introduction
7.1 Intended use
The DID is designed for online monitoring of water quality and controlling of disinfectants in clean media, such as drinking water. The required components - sensors and control unit CU 382 - are assembled with required flow cells, mounting fittings and pipework on a compact panel.
In all types of applications, the respective acceptable limits, which are provided in the technical data in the respective manuals, have to be observed. All applications falling outside of these limits, and which are not authorised by the manufacturer in written form, do not fall under the manufacturer’s liability.
The device must only be used for the purpose described in this manual. Use in applications not described in this manual, or modification of the device without written agreement from the manufacturer, is not allowed. The manufacturer is not liable for claims following from such unauthorised use. In such a case, the risks are the sole responsibility of the operator.
7.2 Functional principle
The control unit CU 382 is equipped with a display and can be operated via 7 buttons on the front panel of the device. The operating software starts automatically when the CU 382 is powered on.
The CU 382 collects readings from all sensors using a digital bus connection. It displays the data and makes it available for dosing purpose. The CU 382 also includes a PID (Proportional-Integral­Derivative) controller which is capable of dosing disinfectants to the monitored water (drinking-, bathing-, waste-water, ...).
The hydraulic part of the station manages the complete water flow from the inlet to the outlet of the DID. This includes filtration, pressure reduction, flow restriction and flow control as well as specific designed flow cells for proper mounting of the sensors and appropriate sampling.
7.3 Components
Fig. 3 Components of measurement and control system with
flow cell
.
Fig. 4 Components of measurement system immersed
sensor
TM06 5926 0316
8
9
5
4
3
2
1
11
10
10
12
13 14
15
15
15
15
7
6
6a
OK
8
18
TM06 6038 05166
Pos. Description
1 Water inlet 1/2" 2 Inlet valve 1/4" NPT 3 Inlet strainer with screw cap for sieve removal/cleaning 4 Flow restrictor (mechanical)
5
Flow detector (digital) indicates alarm on the control unit if water flow decreases below minimal flow rate (approx.
0.25 l/min.
6
Flow cell for one or three sensors. Combined flow cell for up to 3 sensors provides quick connect / disconnect design by safety pins to reduce offline time during sensor maintenance. Includes also ½” outlet and a sampling point
(6a). 7Sensors 8 Control unit CU 382 for 1 or 3 sensors
9
Opening in the panel to pass through power supply and /
or sensor cables
10 Screw joints to open cable terminal compartment 11 Clip to open housing cover 12 Cable bushing for power supply 13 Connector for s::can sensors 14 Cable bushing for signal outputs 15 Holes for wall mounting 16 Sensor holder 17 Protective cover 18 Flat panel
8
11
10
10
12
13 14
OK
8
7
16
17
English (GB)
7
7.4 Identification
The following device variants of the DID are available. Regarding detailed information of the device variants please refer to the technical data located at the end of the manual:
7.4.1 Nameplate
The control unit CU 382 is typified by a nameplate, as shown on the right, that contains the following information:
Fig. 5 Nameplate
7.4.2 Type key
Example: DID-3 BF3-FCL2/TCL2/pH
TM06 5920 0316
Pos. Description
1 Manufacturer‘s name and country of origin 2 Item number (type) 3 Max. numbers of sensor 4 Bar code 5 Device serial number (S/N) 6 Enclosure class 7 Several certification marks 8 QR code
9 Voltage [V] 10 Frequency [Hz] 11 Power consumption [W] 12 Acceptable humidity limits 13 Acceptable temperature limits
1
2 3
5
7
8
9, 10, 11 12
13
4
6
Code Description
Control unit CU 382 variants
DID-1
CU 382-1 for 1parameter + temperature, 100-240 VAC, 50-60 Hz
DID-3
CU 382-3 for 3 parameters + temperature, 100-240 VAC, 50-60 Hz
Installation variant
BF1 Bypass flow cell, 1 sensor BF3 Bypass flow cell, 3 sensors TI1 Tank immersion clean water, 1 sensor
TI2
Tank immersion clean water, 2 sensors
Parameters/ Sensors
FCL2 Free chlorine 0-2 ppm FCL20 Free chlorine 0-20 ppm TCL2 Total chlorine 0-2 ppm TCL20 Total chlorine 0-20 ppm CDI2 Chlorine dioxide 0-2 ppm CDI20 Chlorine dioxide 0-20 ppm HP2 Hydrogen peroxide 0-200 ppm HP20 Hydrogen peroxide 0-2000 ppm PA2 Peracetic acid 0-200 ppm PA20 Peracetic acid 0-2000 ppm pH pH 2-12 pH up to 10 bar and 70 °C
ORP
ORP, -2000 mV to +2000 mV up to 10 bar and 70 °C
CND
Conductivity, 1-500000 µS/cm (2-42 PSU), up to 20 bar and 70 °C
Remarks:
• All sensors include temperature measurement
• Disinfectant parameters (FCL,TCL, CDI, HP or PA) are only possible with BF1 or BF3
• BF1 and BF3 include flow detection
• BF1 and BF3 systems include 1.0 m sensor cables
• Installation variants TI1 and TI2 are only possible for parameters PH, ORP or CND
• TI1 and TI2 systems include 7.5 m sensor cable(s)
• Mains cable is generally not included, please select and order from accessories list
English (GB)
8
7.4.3 Standard range DID pre-assembled system
Hydraulic setup: Bypass flowcell with flow switch
1
wide pH variation means the pH value can go up to values grater than approx. pH 8.5
7.4.4 Hydraulic setup: Tank immersed sensors
Purpose/applications Parameter 1 Parameter 2 Parameter 3 Description
Product number
Free chlorine dosing control
Free Chlorine
0-2 ppm
DID-1 BF1-FCL2 98915656
ClO
2
dosing control
Chlorine dioxide
0-2 ppm
DID-1 BF1-CDI2 98915657
PAA dosing control
Peracetic acid
0-200 ppm
DID-1 BF1-PA2 98915658
H
2O2
dosing control
Hydrogen peroxide
0-200 ppm
DID-1 BF1-HP2 98915659
Chloramination dosing control - incl. calculation
Free Chlorine
0-2 ppm
Total Chlorine
0-2 ppm
DID-3 BF3-FCL2/TCL2 98915660
Free chlorine dosing control with wide pH variation
1
Free Chlorine
0-2 ppm
pH 2-12 DID-3 BF3-FCL2/PH 98915661
Chloramination dosing control - incl. calculation with wide pH variation
1
Free Chlorine
0-2 ppm
Total Chlorine
0-2 ppm
pH 2-12 DID-3 BF3-FCL2/TCL2/PH 98915662
Free chlorine dosing control with validation via ORP
Free Chlorine
0-2 ppm
ORP
-2000 - +2000 mV
DID-3 BF3-FCL2/ORP 98915663
Free chlorine dosing control with wide pH variation and validation via ORP
Free Chlorine
0-2 ppm
pH 2-12
ORP
-2000 - +2000 mV
DID-3 BF3-FCL2/PH/ORP 98915664
pH control (neutralisation, pH adjustment for further processes), dosing control of acids and bases
pH 2-12 DID-1 BF1-PH 98915665
Dosing control in oxidation/reduction processes (i.e. chromic acid, nitrite or cyanide removal)
ORP
-2000 - +2000 mV
pH 2-12 DID-3 BF3-ORP/PH 98915669
Chemical dosing control in CIP­processes, high purity water, cooling towers
Conductivity
1-500000 µS/cm
DID-1 BF1-CND 98915670
Purpose/applications Parameter 1 Parameter 2 Description
Product number
pH control (neutralisation for further processes), dosing control of acids and bases
pH 2-12 DID-1 TI1-PH 98915666
Denitrification - blower control
ORP
-2000 - +2000 mV
DID-1 TI1-ORP 98915667
Dosing control in oxidation/reduction processes (i.e. chromic acid, nitrite or cyanide removal)
ORP
-2000 - +2000 mV
pH 2-12 DID-3 TI2-ORP/PH 98915668
Chemical dosing control in CIP­processes, high purity water, cooling towers
Conductivity
1-500000 µS/cm
DID-1 TI1-CND 98915671
English (GB)
9
8. Control functions
8.1 Operating elements
Fig. 6 Operating elements
Fig. 7 Control unit CU 382
8.2 Functions overview
TM06 5854 0216
Pos. Description
1 Green power LED
2
Orange communication LED
• Flashes when there is a communication with a sensor.
3
USB slot
• USB stick support for data export or software update.
4 Display
5
Operating buttons
[Back] button
– Leaves the current menu
[Up] button
– Moves one line upward (the selected
line has a triangle as first character)
– Increases values
[Function] button
– Enters the settings menus – Disables / deletes values
[Left] button
– Moves left in views or values
[OK] button
– Enters the selected menu – Confirms the selected line or value. – Acknowledges alarms in the alarm
screen
[Right] button
– Moves right in views or values
[Down] button
– Moves one line downward (the
selected line has a triangle as first character)
– Decreases values
OK
1 2 3
45
OK
TM06 5891 0216
Features CU 382-1 CU 382-3
1 plug for connection of digital s::can sensors
3 plugs for connection of digital s::can sensors
3 PID controllers
●●
2 digital (relay) outputs (adjustable as controller and/or limit switch outputs)
●●
3 analog outputs (adjustable as controller and/or measured value output)
●●
1 alarm relay output
●●
1 cleaning valve output
●●
2 digital inputs (adjustable as remote on/off, water meter pulse input or setpoint switch)
●●
1 analog input (adjustable as flow meter or external setpoint input)
●●
Data logger functionality (measured values, logfile, configuration)
●●
USB host interface
●●
Multilingual user interface
●●
Modbus (over RS485)
●●
Flow switch input (from flow cell)
●●
English (GB)
10
9. Operating the product
9.1 Software overview
The CU 382 has four different views which can be selected by using [Right]- and [Left]-button. The default screen (i.e. after restart) is the Parameter screen.
Pressing [Back] button several times (depends on level of sub menu) will always get the user back to one of these screens
9.1.1 .Status screen
.
The first row shows the version of the software. In case problems make it necessary to contact our service department, the Status menu enables the operator to easily identify the software version (Version) and the serial number (Serial) of the actual device.
The third row (Waiting) shows the waiting time to the next action (start of measurement or start of cleaning). This interval can be set in menu Measurement settings (Meas. Settings…).
The last row (YYYY/MM/DD) shows current date and time. This can be set in menu.
9.1.2 Parameter screen
This is the default parameter screen. It shows two measured values at once. Besides the reading itself the parameter name (FCL) and the unit (mg/l) is displayed. The inverted font in the header displays the selected parameter which is marked with a triangle symbol. To scroll through the list of configured parameters use [Up]- and [Down] buttons. Up to 8 parameters can be configured and therefore displayed.
These displayed parameters can be:
– Sensor reading – Analog input – Digital input – Flow guard
Quick calibration
It is possible to make a quick calibration directly from the parameter screen.
Choose the parameter you want to calibrate with [Up]- and [Down] buttons and pressing [OK] button will open up the Quick calibration menu.
Before taking a sample to perform a calibration, rinse the sampling point of the flow cell at least 3 times to remove all residuals from the sampling point. After this, approx. 10 ml should be analysed by a reference method and the result has to be entered into field Lab 1.
At the same time the sample is taken, Sample 1 has to be selected with [Up]- and [Down] buttons and [OK] button has to be pressed to measure the raw value of this sample. This current measured raw value will be stored onto the sensor.
As soon as the Sample 1 is measured and the corresponding Lab 1 value has been entered, the calibration can be executed by selecting Perform Calibration with [Up]- and [Down] buttons and pressing [OK] button.
The Quick calibration menu will be closed and the new calibration coefficient will be used for measurement.
Status Parameter Controller Alarm
Status
> <
P1/3 pH
>
<
C2/2
>
<
AP001 A1/1
Vers io n V7.05B1
pH
15 % YYYY/MM/DD
Serial: 9999999
9.49 Type PID/Running Follow below
Waiting: 1s
Tem p.
pH >4/20 mA #2 lower alarm limit
YYYY/MM/ DD
h/min/sec 22.1
C
AV/SP: 6.86/7.00
(ext.)
General set up Parameter set up Controller set up
Alarm set up
Manage sensor
Calibrate expert
Setpoint
Acknowledgment of alarms
Manage parameters Monitor
Settings PID/2-P/
None Cleaning 1 Display settings Source Measuring settings Alarm settings Output DI/mA Date/Time Output Output settings Modbus slave Output settings Alarm settings
Update software
pH compensation
Reset state
Select language Parameter info Service Remove parameter
Status >
Version: V7.05B1 Serial: 9999999 Waiting: 1s 2015/Oct/05 16:40:49
< P1/3 FCL >
0.531
FCL
mg/l
7.8
pH
P1 Quick calibration
Lab 1: 0.35
Sample 1: 2.41 Perform calibration
Loading...
+ 22 hidden pages