English (GB) Installation and operating instructions
Note
Note
English (GB)
Original installation and operating instructions.
CONTENTS
1.General information
1.1Introduction
1.2Service documentation
1.3Information about the product
1.4Applications
1.5Warranty
2.Safety
2.1Identification of safety instructions in this manual
2.2Qualification and training of personnel
2.3Risks when safety instructions are not observed
2.4Safety-conscious working
2.5Safety instructions for the operator/user
2.6Safety instructions for maintenance, inspection and
installation work
2.7Unauthorised modification and manufacture of spare
parts
2.8Improper operating methods
2.9Safety of the system in the event of a failure in the
dosing system
2.10 Dosing chemicals
2.11 Diaphragm breakage
3.Transport and intermediate storage
3.1Transport
3.2Delivery
3.3Unpacking
3.4Intermediate storage
3.5Return
4.Technical data
4.1Identification
4.2Type key
4.3General description
4.4Safety functions
4.5Dimensional sketches
4.6Weight
4.7Materials
4.8Control unit
5.Installation
5.1General information on installation
5.2Installation location
5.3Mounting
5.4Installation examples
5.5Tube / pipe lines
6.Electrical connections
6.1Connecting the signal lines for DDI 222
6.2Connecting the power supply cable
7.Start-up/shutdown
7.1Initial start-up / subsequent start-up
7.2Operating the pump
7.3Shutdown
8.Operation
8.1Control and display elements
8.2Switching on/off
9.How to use the control unit
9.1Menu levels
9.2General functions of the control unit
9.3Signal outputs
9.4First function level
9.5Second function level
9.6Calibration
9.7Service level
9.8Resetting to default settings
9.9Current signal control 0-20 mA / 4-20 mA
9.10 Flow Monitor
9.11 Batch menu / batch mode
9.12 Timer menu / timer mode
9.13 Creating a master/slave application
9.14 Hotkeys / info keys
Page
10
11
11
11
12
12
12
12
12
14
15
15
17
17
17
18
18
18
18
18
19
19
19
21
22
23
27
29
32
32
36
41
42
43
44
9.15 Pump safety functions
10.Maintenance
10.1 General notes
10.2 Maintenance intervals
2
2
2
2
4
4
5
5
5
5
5
5
5
5
5
10.3 Cleaning suction and discharge valves
10.5 Diaphragm breakage
10.6 Replacing the diaphragm
10.7 Repair
11.Fault finding chart
12.Disposal
Warning
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
These complete installation and operating
instructions are also available on
www.grundfos.com.
1. General information
5
1.1 Introduction
6
6
These installation and operating instructions contain all the
information required for starting up and handling the DDI 222
6
diaphragm dosing pump.
6
6
If you require further information or if any problems arise, which
6
are not described in detail in this manual, please contact the
6
nearest Grundfos company.
6
1.2 Service documentation
7
If you have any questions, please contact the nearest Grundfos
7
company or service workshop.
8
9
1.3 Information about the product
9
1.3.1 Pump types
The DDI 222 dosing pump is available for a variety of
performance ranges in various sizes:
Pump types
DDI 60-10
DDI 150-4
The following is indicated on the pump nameplate
(see section 4.1 Identification):
• The pump type which specifies the stroke volume, connection
size and performance data (see below).
• The pump serial number which is used to identify the pump.
• The most important characteristics of the pump configuration,
e.g. dosing head and valve materials. They are described in
section 4.2 Type key.
• Maximum flow rate and maximum counter-pressure.
• Supply voltage or mains voltage and mains frequency.
The pump for viscous liquids is called HV variant
in the following.
1.3.2 Connection size
Pump typeConnection sizeHV variant
DDI 60-10DN 8DN 20
DDI 150-4DN 20DN 20
45
46
46
46
46
47
47
48
49
50
2
1.3.3 Pump performance
Note
Note
Caution
Note
Performance data at maximum pump counter-pressure
Normal operationSlow-mode operationSlow-mode-2 operation
* Observe the maximum permissible temperatures and that the friction loss increases with the viscosity of the dosing medium.
** The maximum dosing flow of HV-variant pumps is up to 10 % lower.
The pump can be operated in the range between
0.125 % and 100 % of the maximum dosing
capacity.
The maximum display indication is higher than
the nominal capacity of the pump because it
refers to the default setting.
1.3.4 Accuracy
• Applies to:
– water as dosing medium
– fully deaerated dosing head
– standard pump version.
• Dosing flow fluctuation and linearity deviation: ± 1.5 % of the
full-scale value.
• Construction tolerance: according to VDMA 24284.
1.3.5 Inlet pressure and counter-pressure / suction lift during
operation
Maximum inlet pressure
Operating conditions / version
Pump type
All*
Maximum suction lift* (start-up) for media with a viscosity
similar to water
Operating conditions / version
Pump type
Continuous operation
[m]
DDI 60-10 - DDI 150-41
* Deaeration valve open.
Maximum suction lift* (continuous operation) for
non-degassing media with a viscosity similar to water
Operating conditions / version
Pump type
Normal operation
[m]
DDI 60-106
DDI 150-43
* Dosing head and valves filled with dosing medium.
1.3.6 Sound pressure level
65 dB(A), testing according to DIN 45635-01-KL3.
[bar]
1.3.7 Enclosure class
DDI 60-10 - DDI 150-42
* For pumps with pressure sensor (Flow Monitor pump option),
the inlet pressure on the suction side must not exceed 1 bar.
Minimum counter-pressure at the pump discharge valve
Operating conditions / version
Pump type
All*
[bar]
DDI 60-10 - DDI 150-41
* For pumps with pressure sensor (Flow Monitor pump option),
the minimum system pressure is 2 bar and the minimum
pressure difference between the suction and discharge sides
is 2 bar. If the volume flow is not constant (as, for example, in
the case of contact or analog control), even small volume
flows should not fall below the minimum pressure or the
minimum pressure difference.
• Pump with mains plug: IP65.
• Pump without mains plug: IP65 can only be ensured if the
power supply cable is connected with IP65 protection.
1.3.8 Required energy
Power supply for AC voltage
• Rated voltage range: 110-240 V.
Deviation from the rated value: ± 10 %.
• Mains frequency: 50/60 Hz.
• Maximum power consumption: 70 W including all sensors
(reduced input power according to pump type and connected
sensors).
The enclosure class is only met if the sockets are
protected! The data regarding the enclosure
class applies to pumps with correctly inserted
plugs or screwed-on caps.
The power supply must be electrically isolated
from the signal inputs and outputs.
English (GB)
3
1.3.9 Ambient and operating conditions
Caution
Caution
Caution
Caution
English (GB)
• Permissible ambient temperature: 0 °C to +40 °C.
• Permissible storage temperature: -10 °C to +50 °C.
• Permissible air humidity: max. relative humidity:
92 % (non-condensing).
Warning
The DDI 222 is NOT approved for operation in
potentially explosive areas!
The installation site must be under cover!
Ensure that the enclosure class of motor and
pump is not affected by the atmospheric
conditions.
Pumps with electronics are only suitable for
indoor use! Do not install outdoors!
1.3.10 Dosing medium
Warning
The pump must be equipped with a diaphragm
leakage detection when used for crystallising
media.
In the event of questions regarding the material
resistance and suitability of the pump for specific
dosing media, please contact Grundfos Water
Treatment.
The dosing medium must have the following basic characteristics:
• liquid
• non-abrasive
• non-inflammable.
Maximum permissible viscosity at operating temperature*
Maximum viscosity*
Pump type
DDI 60-10100200500
DDI 150-4100200500
DDI 60-1070100200
DDI 150-450100200
DDI 60-10120020003000
DDI 150-470012001800
* The stated values are approximate values and apply to
Newtonian liquids.
Note that the viscosity increases with decreasing temperature!
Normal
operation
[mPa s][mPa s][mPa s]
Standard with Flow Monitor
HV variant with/without Flow Monitor
Slow-mode-1
operation
Standard
Slow-mode-2
operation
Permissible media temperature
Dosing head
material
PVC0 40
Stainless steel,
DIN 1.4571*
PP040
PVDF**-1060*
* A temperature of 120 °C at a counter-pressure of max. 2 bar is
permitted for a short period (15 minutes).
** At 70 °C, the maximum counter-pressure is 3 bar.
Warning
Observe the chemical manufacturer's safety
instructions when handling chemicals!
The dosing medium must be in liquid form!
Observe the freezing and boiling points of the
dosing medium!
The resistance of the parts that come into contact
with the media depends on the media, media
temperature and operating pressure. Ensure that
parts in contact with the media are chemically
resistant to the dosing medium under operating
conditions!
Make sure that the pump is suitable for the actual
dosing medium!
Min. media
temperature
[°C][°C]
-1070
Max. media
temperature
p < 10 bar
1.4 Applications
1.4.1 Appropriate, acceptable and correct usage
The DDI 222 pump is suitable for liquid, non-abrasive and
non-inflammable media strictly in accordance with the
instructions in this manual.
Warning
Other applications or the operation of pumps in
ambient and operating conditions, which are not
approved, are considered improper and are not
permitted. Grundfos accepts no liability for any
damage resulting from incorrect use.
1.5 Warranty
Warranty in accordance with our general terms of sale and
delivery is only valid
• if the pump is used in accordance with the information within
this manual.
• if the pump is not dismantled or incorrectly handled.
• if repairs are carried out by authorised and qualified
personnel.
4
2. Safety
Caution
Note
This manual contains general instructions that must be observed
during installation, operation and maintenance of the pump.
This manual must therefore be read by the installation engineer
and the relevant qualified personnel/operators prior to installation
and start-up, and must be available at the installation location of
the pump at all times.
It is not only the general safety instructions given in this "Safety"
section that must be observed, but also all the specific safety
instructions given in other sections.
2.1 Identification of safety instructions in this manual
If the safety instructions or other advice in this manual are not
observed, it may result in personal injury or malfunction and
damage to the pump. The safety instructions and other advice are
identified by the following symbols:
Warning
If these safety instructions are not observed,
it may result in personal injury.
If these safety instructions are not observed,
it may result in malfunction or damage to the
equipment.
Notes or instructions that make the job easier
and ensure safe operation.
Information provided directly on the pump, e.g. labelling of fluid
connections, must be observed and must be maintained in a
readable condition at all times.
2.2 Qualification and training of personnel
The personnel responsible for the operation, maintenance,
inspection and installation must be appropriately qualified for
these tasks. Areas of responsibility, levels of authority and the
supervision of the personnel must be precisely defined by the
operator.
If the personnel do not have the necessary knowledge, the
necessary training and instruction must be given. If necessary,
training can be performed by the manufacturer/supplier at the
request of the operator of the pump. It is the responsibility of the
operator to make sure that the contents of this manual are
understood by the personnel.
2.3 Risks when safety instructions are not observed
Non-observance of the safety instructions may have dangerous
consequences for the personnel, the environment and the pump.
If the safety instructions are not observed, all rights to claims for
damages may be lost.
Non-observance of the safety instructions may lead to the
following hazards:
• failure of important functions of the pump/system
• failure of specified methods for maintenance
• harm to humans from exposure to electrical, mechanical and
chemical influences
• damage to the environment from leakage of harmful
substances.
2.5 Safety instructions for the operator/user
Hazardous hot or cold parts on the pump must be protected to
prevent accidental contact.
Leakages of dangerous substances (e.g. hot, toxic) must be
disposed of in a way that is not harmful to the personnel or the
environment. Legal regulations must be observed.
Damage caused by electrical energy must be prevented (for more
details, see for example the regulations of the VDE and the local
electricity supply company).
2.6 Safety instructions for maintenance, inspection
and installation work
The operator must ensure that all maintenance, inspection and
installation work is carried out by authorised and qualified
personnel, who have been adequately trained by reading this
manual.
All work on the pump should only be carried out when the pump is
stopped. The procedure described in this manual for stopping the
pump must be observed.
Pumps or pump units which are used for media that are harmful
to health must be decontaminated.
All safety and protective equipment must be immediately
restarted or put into operation once work is complete.
Observe the points described in the initial start-up section prior to
subsequent start-up.
Warning
Electrical connections must only be carried out
by qualified personnel!
The pump housing must only be opened by
personnel authorised by Grundfos!
2.7 Unauthorised modification and manufacture of
spare parts
Modification or changes to the pump are only permitted following
agreement with the manufacturer. Original spare parts and
accessories authorised by the manufacturer are safe to use.
Using other parts can result in liability for any resulting
consequences.
2.8 Improper operating methods
The operational safety of the supplied pump is only ensured if it is
used in accordance with section 1. General information.
The specified limit values must under no circumstances be
exceeded.
2.9 Safety of the system in the event of a failure in the
dosing system
DDI 222 dosing pumps are designed according to the latest
technologies and are carefully manufactured and tested.
However, a failure may occur in the dosing system. Systems in
which dosing pumps are installed must be designed in such a
way that the safety of the entire system is still ensured following a
failure of the dosing pump. Provide the relevant monitoring and
control functions for this.
English (GB)
2.4 Safety-conscious working
The safety instructions in this manual, applicable national health
and safety regulations and any operator internal working,
operating and safety regulations must be observed.
5
2.10 Dosing chemicals
Caution
Caution
Caution
Caution
English (GB)
Warning
Before switching the supply voltage back on, the
dosing lines must be connected in such a way
that any chemicals in the dosing head cannot
spray out and put people at risk.
The dosing medium is pressurised and can be
harmful to health and the environment.
Warning
When working with chemicals, the accident
prevention regulations applicable at the
installation site should be applied (e.g. wearing
protective clothing).
Observe the chemical manufacturer's safety data
sheets and safety instructions when handling
chemicals!
Warning
The pump must be equipped with a diaphragm
leakage detection when used for crystallising
media.
2.11 Diaphragm breakage
If the diaphragm leaks or is broken, dosing liquid escapes from
the drain opening (H) (fig. 2) on the dosing head. Observe section
10.6 Replacing the diaphragm.
Warning
Danger of explosion, if dosing liquid has entered
the pump housing!
When operating the pump with a damaged
diaphragm, dosing liquid can enter the pump
housing.
In case of diaphragm breakage, immediately
separate the pump from the power supply!
Make sure that the pump cannot be put back into
operation by accident!
Dismantle the dosing head without connecting
the pump to the power supply. Make sure that no
dosing liquid has entered the pump housing.
Proceed as described in section 10.6 Replacing
the diaphragm.
To avoid any danger resulting from diaphragm breakage, observe
the following:
• Perform regular maintenance.
See section 10.2 Maintenance intervals.
• Never operate the pump with blocked or soiled drain opening.
– If the drain opening is blocked or soiled, proceed as
described in section 10.6 Replacing the diaphragm.
• Never attach a hose to the drain opening. If a hose is attached
to the drain opening, it is impossible to recognise escaping
dosing liquid.
• Take suitable precautions to prevent harm to health and
damage to property from escaping dosing liquid.
• Never operate the pump with damaged or loose dosing head
screws.
3. Transport and intermediate storage
3.1 Transport
Do not throw or drop the pump.
3.2 Delivery
The DDI 222 dosing pump is delivered in a cardboard box.
Place the pump in the packaging during transport and
intermediate storage.
3.3 Unpacking
Retain the packaging for future storage or return, or dispose of
the packaging in accordance with local regulations.
3.4 Intermediate storage
• Permissible storage temperature: -10 °C to +50 °C.
• Permissible air humidity: max. relative humidity:
92 % (non-condensing).
3.5 Return
Return the pump in its original packaging or equivalent.
The pump must be thoroughly cleaned before it is returned or
stored. It is essential that there are no traces of toxic or
hazardous media remaining on the pump.
Grundfos accepts no liability for damage caused
by incorrect transportation or missing or
unsuitable packaging of the pump!
Before returning the pump to Grundfos Water Treatment for
service, the safety declaration at the end of these instructions
must be filled in by authorised personnel and attached to the
pump in a visible position.
If a pump has been used for a medium which is
injurious to health or toxic, the pump will be
classified as contaminated.
If Grundfos Water Treatment is requested to service the pump, it
must be ensured that the pump is free from substances that can
be injurious to health or toxic. If the pump has been used for such
substances, the pump must be cleaned before it is returned.
If proper cleaning is not possible, all relevant information about
the chemical must be provided.
If the above is not fulfilled, Grundfos Water Treatment can refuse
to accept the pump for service. Possible costs of returning the
pump are paid by the customer.
The safety declaration can be found at the end of these instructions.
The replacement of the power supply cable must
be carried out by an authorised Grundfos service
workshop.
1Type designation
2Model
3Maximum capacity [l/h]
4Voltage [V]
5Frequency [Hz]
6Product number
7Country of origin
8Year and week code
9Marks of approval, CE mark, etc.
10Maximum pressure [bar]
11Serial number
English (GB)
TM03 8687 5112
7
4.2 Type key
English (GB)
Example:DDI150- 4 AR -PP /E /G -S -3 1 B2 B2 F
Type rangeMains plug
DDIXNo plug
Maximum flow [l/h]FEU (Schuko)
Maximum counter-pressure [bar]BUSA, Canada
Control variantIAustralia, New Zealand
ARStandardESwitzerland
AFAR with Flow MonitorConnection, suction/discharge
APAR with PROFIBUS4Tube, 6/9 mm
APFAR with Flow Monitor and PROFIBUS
Dosing head variantQTube, 19/27 mm
PPPolypropylene
PVPVDF (polyvinylidene fluoride)
PVCPolyvinyl chloride
SSStainless steel, DIN 1.4401
PP-LPP + integrated diaphragm leakage detection
PV-LPV + integrated diaphragm leakage detection
PVC-LPVC + integrated diaphragm leakage detection
SS-LSS + integrated diaphragm leakage detection
Gasket material1Standard
EEPDM (ethylene propylene diene monomer)
VFKM
TPTFE
Valve ball material
CCeramics
GGlass
TPTFE
SSStainless steel, DIN 1.4401Supply voltage
Control panel position31 x 100-240 V, 50/60 Hz
FFront-mounted
SSide-mounted
6Tube, 9/12 mm
STube, 0.375"/0.5"
Tube 6/12 mm/
B1
cementing diameter 12 mm
Tube 13/20 mm/
B2
cementing diameter 25 mm
AThreaded, Rp 1/4, female
A1Threaded, Rp 3/4, female
A3Threaded, 3/4" NPT, female
VThreaded, 1/4" NPT, female
A9Threaded, 1/2" NPT, male
B3Welding diameter 16 mm
B4Welding diameter 25 mm
Valve type
Spring-loaded
0.05 bar suction opening
2
pressure; 0.05 bar discharge
opening pressure
For abrasive media
5
(stainless steel only)
Spring-loaded
(DN 20, stainless-steel balls)
6
0.8 bar discharge opening
pressure
8
Note
3a
3b
2
D
H
Caution
Caution
Q1Q2Q3
2
D
L
L
4.3 General description
The DDI 222 is a dosing pump with an EC motor (brushless
DC motor) as the drive and electronic power control. The pump is
operated via the diagonal display in a user-friendly menu
structure.
The pump incorporates an overpressure safety feature. When an
adjustable cut-off pressure is exceeded, the pump can be
switched off automatically.
The DDI 222 is available in various versions.
See also section 1. General information.
Option:
The pump can also be equipped with the following:
• diaphragm leakage sensor (MBS)
• interface for PROFIBUS.
The functions are described, but only apply to the relevant pump
version.
Fig. 2 DDI 222
Pos.Components
3aSuction valve
3bDischarge valve
2Dosing head
DMBS pressure switch (optional)
HDrain opening
4.3.1 HV variant for liquids which are more viscous than
water
All HV-variant pumps are equipped with spring-loaded DN 20
valves with an opening pressure of 0.1 bar (or 0.8 bar for the
pressure side) and connection for PVC tube 19 x 27.
DDI 60-10 has a special dosing head.
Note that the HV-variant pump has other
dimensions than the standard pump and that
other connection line dimensions might be
required!
4.4 Safety functions
4.4.1 Diaphragm leakage detection (optional)
Pumps with diaphragm leakage signal have a special dosing
head with a diaphragm set and pressure switch. The pressure
switch (socket 1) is fitted and connected to the pump on delivery.
Fig. 3 Dosing head with diaphragm set and pressure switch
for diaphragm leakage detection
Pos. Components
2Dosing head
DPressure switch
Q1Working diaphragm
Q2Signal diaphragm (intermediate layer made from fabric)
Q3Protection diaphragm
In the event of a leak in the diaphragm:
• Dosing medium penetrates between the working diaphragm
and the protection diaphragm and is transferred to the
pressure switch via the signal diaphragm.
• On the next pressure stroke, pressure is applied to the
pressure switch, which is activated. The pump indicates an
TM03 6661 4506
error but continues operating.
• The electronics operates two contacts, which can be used, for
example, to trigger an alarm signal or to switch off the pump.
• In emergency mode, the pump can continue operating for a
short time.
Warning
Danger of explosion, if dosing liquid has entered
the pump housing!
If the diaphragm is possibly damaged, don’t
connect the pump to the power supply!
Proceed as described in section 10.5 Diaphragm
breakage!
After a diaphragm leakage detection, the
pressure switch has to be checked. In case the
diaphragm of the pressure switch is broken or
affected by the dosing liquid, the pressure switch
must be replaced.
4.4.2 Pressure control
The DDI 222 pump incorporates a pressure control function.
The pressure is calculated from the motor current consumption or
is measured directly in the dosing head if a pressure sensor is
present (Flow Monitor pump option). At a user-defined pressure,
the pump is switched off automatically.
English (GB)
TM03 6611 4506
To protect the pump and system against
excessive pressure build-up, install an overflow
valve in the discharge line.
This function protects the pump, but not the system. It is
recommended that the system is protected by an overflow valve.
This function can be enabled and disabled in the second function
level of the electronics.
The pressure sensor (Flow Monitor pump option) is used as a
dosing controller and to monitor the pressure for the whole power
ranges.
The Flow Monitor for dosing control consists of a pressure sensor
integrated in the dosing head.
The pressure sensor is available as Flow Monitor pump option.
The pressure sensor is fitted to the pump on delivery.
Upgrades are not possible.
Pressure control is primarily used to protect the
pump. This function is not a substitute for the
overflow valve.
4.5 Dimensional sketches
4.4.4 Flow compensation
The flow compensation is a function to keep the dosing flow
constant with changing system pressure. Pressure changes are
detected by the pressure sensor and the motor speed is adjusted
accordingly.
To use this function, pressure control or dosing control (Flow
Monitor) has to be activated in the electronics.
When dosing media with a viscosity similar to
water, the pump needs not to be calibrated, as
the pump already responds to the possible
change of the system pressure.
When dosing media with a viscosity different
from water or after a software update, the pump
has to be calibrated.
DDI 60-10PVC, PP, PVDF5
DDI 60-10Stainless steel, DIN 1.45717
DDI 150-4PVC, PP, PVDF6.5
DDI 150-4Stainless steel, DIN 1.457112
4.7 Materials
Pump housing material
Pump and control unit housing: PPE-SB (fibre-reinforced
Lurranyl).
Pressure sensor (Flow Monitor)
Sensor: Aluminium oxide Al
O-rings: FKM, EPDM or PTFE.
Pressure switch (MBS)
Pressure switch: Stainless steel, DIN 1.4305.
Diaphragm of the pressure switch: EPDM.
Warning
Observe the manufacturer's safety instructions
when handling chemicals!
The resistance of the parts that come into contact
with the media depends on the media, media
temperature and operating pressure. Ensure that
parts in contact with the media are chemically
resistant to the dosing medium under operating
conditions!
Further information on resistance with regard to
the media, media temperature and operating
pressure is available on request.
2O3
(96 %).
4.8 Control unit
Functions of pumps with control unit
• "continuous operation" button for function test and suction
• memory function (stores a maximum of 65,000 pulses)
• two-stage tank-empty signal (e.g. via Grundfos tank-empty
sensor)
• stroke / pulse signal / pre-empty signal (adjustable)
• dosing controller or Flow Monitor function (only with sensor optional)
• diaphragm leakage detection (only with sensor - optional)
• access-code-protected settings
• remote on/off
• calibration (adjust the pump to local operating conditions)
• pressure control function / counter-pressure display
• dosing capacity display (can be reset)
• operating hours counter (cannot be reset)
• interface: PROFIBUS (optional).
Operating modes:
• manual
input/display of the dosing flow in l/h or gal/h.
quasi continuous dosing (short suction stroke, dosing stroke
as long as possible).
• contact signal control
input/display in ml/contact, most constant dosing
• current signal control 0-20 mA / 4-20 mA
adjustment of volumetric flow proportional to the current signal
(displayed in l/h).
weighting of current input/output.
• batch dosing
Setting the dosing capacity and dosing flow per batch
triggered manually or by an external contact signal.
• batch dosing with timer functions
– setting the dosing capacity and dosing flow per batch
– setting the start time for first batch
– setting the repeat time for subsequent batches.
• slow mode (for viscous media)
two-stage reduction of the maximum dosing flow to 66 %
(slow mode 1) or 41 % (slow mode 2).
Inputs and outputs
Inputs
Contact signal
Current 0-20 mAMaximum load: 22 Ω
Remote on/offMaximum load: 12 V, 5 mA
Tank-empty signalMaximum load: 12 V, 5 mA
Dosing controller and diaphragm leakage sensor
Outputs
Current 0-20 mAMaximum load: 350 Ω
Error signal
Stroke signalContact time/stroke: 200 ms
Pre-empty signal
4.8.1 Interface (optional)
•PROFIBUS.
Maximum load: 12 V, 5 mA
Minimum pulse length: 10 ms
Minimum pause time: 25 ms
Maximum ohmic load:
50 VDC / 75 VAC, 0.5 A
Maximum ohmic load:
50 VDC / 75 VAC, 0.5 A
English (GB)
11
5. Installation
Note
Caution
Caution
7
9.95
7
(159)
172.5
16.5
105
C1
1i
2i
3i
4i
5i
6i
7i
9i
10i
8i
15i
11i
12i
English (GB)
5.1 General information on installation
Warning
Observe the specifications for the range of
applications and installation location described
in sections 1. General information and
5.2 Installation location.
Warning
Faults, incorrect operation or faults on the pump or
system can, for example, lead to excessive or
insufficient dosing, or the permissible pressure
may be exceeded. Consequential faults or damage
must be evaluated by the operator and appropriate
precautions must be taken to avoid them!
5.2 Installation location
Warning
Danger to life due to non-tripping of the residual
current device (RCD)!
If the pump is connected to an electric
installation where a residual current device (RCD)
is used as an additional protection, this RCD
must trip when earth fault currents with DC
content (pulsating DC) and smooth DC earth fault
currents occur. This means that a RCD type B,
sensitive to universal current, must be used.
5.2.1 Space required for operation and maintenance
5.2.2 Permissible ambient influences
Permissible ambient temperature: 0 °C to +40 °C.
Permissible air humidity: max. relative humidity:
92 % (non-condensing).
The installation site must be under cover!
Ensure that the enclosure class of motor and
pump is not affected by the atmospheric
conditions.
Pumps with electronics are only suitable for
indoor use! Do not install outdoors!
5.2.3 Mounting surface
The pump must be mounted on a flat surface.
5.3 Mounting
Carefully tighten the screws, otherwise the
plastic housing may be damaged.
The pump must be installed in a position where it
is easily accessible during operation and
maintenance work.
The control elements must be easily accessible during operation.
Maintenance work on the dosing head and the valves must be
carried out regularly.
Provide sufficient space for removing the dosing head and the valves.
5.4 Installation examples
TM03 6664 4506
Fig. 5 Drilling scheme
• Use four M6 screws to mount the pump on the tank or on a
console so that the suction valve is at the bottom and the
discharge valve is at the top (dosing always flows upwards).
Fig. 6 Installation example of pump with manual deaeration
10iInjection unit
11iDeaeration and evacuation valve
12iCheck-back valve
15iFilter
5.4.1 Installation tips
13i
6i
10i
p
15i
7i
>
p _ 1bar
p 1 bar
7i
14i
1
2
>
p -p _ 1bar
p
1
p
2
p2 - p1 1 bar
15i
10i
6i
p
4i
8i
• For non-degassing media with a viscosity similar to water, the
pump can be mounted on the tank (observe the permissible
suction lift).
• Flooded suction preferred.
• For media with a tendency to sedimentation, install the suction
line with filter (15i) so that the suction valve remains a few
millimetres above the possible level of sedimentation.
Fig. 7 Tank installation
With open outflow of the dosing medium or low
counter-pressure
A positive pressure difference of at least 1 bar must be ensured
between the counter-pressure at the injection point and the
pressure of the dosing medium at the pump suction valve.
• If this cannot be ensured, install a pressure-loading valve (7i)
immediately before the outlet or the injection unit.
• To protect the dosing pump against excessive pressure
build-up, install a relief valve (6i) in the discharge line.
• For degassing media:
– Flooded suction.
– Install a filter (15i) in the suction line to prevent the valves
being contaminated.
Fig. 10 Installation with relief valve and filter
• For line lengths above 1 metre a suction pulsation damper (4i)
TM03 6666 4506TM03 6667 4506TM03 6668 4506
may be required, depending on the flow rate.
Fig. 11 Installation with suction pulsation damper
• For damper and line lengths above 3 metres and for flexible
pipework and line lengths above 5 metres, a pulsation
damper (8i) must be used to protect the system.
English (GB)
TM03 6669 4506TM03 6670 4506TM03 6671 4506
Fig. 8 Installation with pressure-loading valve
• To avoid the siphon effect, install a pressure-loading valve (7i)
in the discharge line and, if necessary, a solenoid valve (14i) in
the suction line.
Fig. 9 Installation to avoid the siphon effect
Fig. 12 Installation with pulsation damper
13
• When installing the suction line, observe the following:
Caution
12i
11i
Caution
A
B
C
D
3b
D
C
3a
English (GB)
– Keep the suction line as short as possible. Prevent it from
becoming tangled.
– If necessary, use swept bends instead of elbows.
– Always route the suction line up towards the suction valve.
– Avoid loops as they may cause air bubbles.
5.5.2 Sizing of tube / pipe lines
Warning
Observe the pressure stage of the used lines.
The maximum permissible inlet pressure and the
pressure stage of the discharge lines must not be
exceeded!
Minimum internal diameter
Pump version
Fig. 13 Installation of suction line
• In the case of long discharge lines, install a non-return valve
(12i) in the discharge line.
Fig. 14 Installation with non-return valve
5.5 Tube / pipe lines
5.5.1 General
Warning
To protect the dosing pump against excessive
pressure build-up, install a relief valve in the
discharge line.
All lines must be free from strain!
Avoid loops and buckles in the tubes!
Keep the suction line as short as possible!
The flow must run in the opposite direction to
gravity!
Observe the manufacturer's safety instructions
when handling chemicals!
The resistance of the parts that come into contact
with the media depends on the media, media
temperature and operating pressure. Ensure that
parts in contact with the media are chemically
resistant to the dosing medium under operating
conditions!
Only use the specified line types!
Maximum suction line length
• 5 m for standard pumps when dosing media with a viscosity
similar to water and using a pulsation damper.
• 1.2 m when dosing media with a higher viscosity than water.
• 1.2 m for pumps with Flow Monitor (2 m for standard
DDI 60-10) when dosing media with a viscosity similar to water
and not using a pulsation damper.
Pump type
StandardHV variant
[mm][mm]
DDI 60-10
Suction side: 9
Discharge side: 6
DDI 150-413
TM03 6672 4506TM03 6673 4506
5.5.3 Connecting the suction and discharge lines
• Connect the suction line to the suction valve (3a).
– Install the suction line in the tank so that the foot valve
remains approximately 5 to 10 mm above the bottom of the
tank or the possible level of sedimentation.
• Connect the discharge line to the discharge valve (3b).
Fig. 15 Connecting the suction and discharge lines
Pos.Components
3aSuction valve
3bDischarge valve
CPipe connection
DTube connection
Observe the pressure limits specified in section
1. General information!
Suction side: 19
Discharge side: 13
Suction side: 19
Discharge side: 13
TM03 6235 4506
14
6. Electrical connections
Caution
1
3
5
42
1
2
3
4
5
6
1
2
3
4
optional
5
1
2
3
4
2
1
4
3
1
2
3
4
5
1
2
4
3
Optional
Note
Make sure that the pump is suitable for the electricity supply on
which it will be used.
Warning
Electrical connections must only be carried out
by qualified personnel!
Disconnect the power supply before connecting
the power supply cable and the relay contacts!
Observe the local safety regulations!
6.1 Connecting the signal lines for DDI 222
Warning
The pump housing must only be opened by
personnel authorised by Grundfos!
Warning
Protect the cable connections and plugs against
corrosion and humidity.
Only remove the protective caps from the
sockets that are being used.
The power supply must be electrically isolated
from the signal inputs and outputs.
English (GB)
Fig. 16 DDI 222 connection diagram
6.1.1 Diaphragm leakage signal / (pressure sensor - Flow Monitor)
Socket 1
For diaphragm leakage signal (MBS) and/or pressure sensor (Flow Monitor pump option).
The diaphragm leakage signal and pressure sensor are pre-assembled with an M12 plug for socket 1.
• Connect the cables according to the table below.
Socket 1Used for / wire colours
PinAssignmentDiaphragm leakage signal (MBS)Pressure sensor
6.1.2 Current output / Flow Monitor (pressure sensor)
Socket 2
For pressure sensor for Flow Monitor option.
The pressure sensor is supplied ready-made with M12 plug for socket 2 or socket 1.
The current output indicates the current dosing flow and can be weighted independently of the selected operating mode.
See section
9.6.4 Weighting of current input/output.
Pressure sensor (Flow Monitor):
If socket 2 is also used for current output, the pressure sensor can be either connected to socket 1 or preferably
together with the current output to socket 2 using the plug set (product number 96645265 (321-327)).
TM03 6583 4506
Socket 2CableUsed for
PinAssignmentWire colour+/- current outputPressure sensor
6.1.3 Stroke/pulse signal / pre-empty signal / error signal
Caution
English (GB)
Socket 3
Electrically isolated output for stroke/pulse signal or pre-empty signal and error signal.
Socket 3CableUsed for
PinAssignmentWire colour
1Error signal contactBrownx
2Stroke/pulse signal or pre-empty signal contactWhitex
3Stroke/pulse signal or pre-empty signal contactBluex
4Error signal contactBlackx
6.1.4 Remote on/off / contact input / current input
Socket 4
For the remote on/off input and contact input or current input.
If the remote on/off and contact inputs are to be used at the same time, wire 1 is assigned twice.
For the connection of one cable, use a plug adapter with simple cable entry, for the connection of two cables, use a
plug adapter with double cable entry, otherwise the protection will be lost!
6.1.5 Empty signal only / pre-empty and empty signal
Socket 5
For the empty signal only or pre-empty and empty signal input.
The suction lines with empty signal or pre-empty and empty signal are pre-assembled with a plug for socket 5.
Remote on/off
input
Stroke/pulse signal /
pre-empty signal
Contact input+/- current input
Error signal
Socket 5Used for
PinAssignmentEmpty signalPre-empty signal
1Pre-empty signalx
2Empty signalx
3GNDxx
6.1.6 PROFIBUS (optional)
Socket 6
Socket 6 for PROFIBUS is only used when the PROFIBUS option is selected.
For pumps with PROFIBUS option, please refer to the separate "PROFIBUS-DP" manual provided.
16
6.2 Connecting the power supply cable
Caution
Caution
Caution
Caution
7. Start-up/shutdown
Warning
Disconnect the power supply before connecting
the power supply cable!
Before connecting the power supply cable, check
that the rated voltage stated on the pump
nameplate corresponds to the local conditions!
Do not make any changes to the power supply
cable or plug!
The pump can be automatically started by
connecting the power supply!
The assignment between the plug-and-socket
connection and the pump must be labelled
clearly (e.g. by labelling the socket outlet).
• Do not switch on the power supply until you are ready to start
the pump.
6.2.1 Versions without mains plug
Warning
The pump must be connected to an external
clearly labelled mains switch with a minimum
contact gap of 3 mm in all poles.
• Connect the pump to the mains in accordance with local
electrical installation regulations.
Warning
IP65 can only be ensured if the power supply
cable is connected with IP65 protection.
6.2.2 Version with mains plug
• Insert the mains plug in the mains socket.
Warning
The electronic printed circuit board may be live
even if the mains voltage is not connected!
The printed circuit board may only be replaced
by service personnel authorised by Grundfos.
Warning
Risk of chemical burns!
Wear protective clothing (gloves and goggles)
when working on the dosing head, connections
or lines!
Before each start-up, check the dosing head
screws.
After initial start-up and after each time the
diaphragm is changed, tighten the dosing head
screws.
After approximately 6-10 operating hours or two
days, cross-tighten the dosing head screws
using a torque wrench.
Torque: 7 Nm (+ 1 Nm).
7.1 Initial start-up / subsequent start-up
7.1.1 Checks before start-up
• Check that the rated voltage stated on the pump nameplate
corresponds to the local conditions!
• Check that all connections are secure and tighten, if
necessary.
• Check that the dosing head screws are tightened with the
specified torque and tighten, if necessary.
• Check that all electrical connections are correct.
7.1.2 Assisting suction for systems without flooded suction
At the dry suction/discharge valves:
1. Remove the suction line.
2. Hold a small container of water directly next to the suction
valve and draw water until the dosing head is full.
3. Reinsert the suction line.
7.1.3 Starting the pump
1. Open the suction and discharge isolating valves, if installed.
2. Depressurise the system on the discharge side of the pump:
– Open the system deaeration and evacuation valve.
3. Let the pump run in continuous operation:
– Switch on the power supply.
– Press the "Start/Stop" button and keep it pressed.
– The pump switches to continuous operation at maximum
stroke frequency.
4. Leave the pump running until the dosing head and the valves
are filled with medium and dosing medium flows from the
deaeration line on the discharge side.
5. Close the system deaeration and evacuation valve.
The pump is now ready for operation.
7.1.4 Tightening dosing head screws
English (GB)
After initial start-up and after each time the
diaphragm is changed, tighten the dosing head
screws.
After approximately 6-10 operating hours or two
days, cross-tighten the dosing head screws using
a torque wrench.
Torque: 7 Nm (+ 1 Nm).
17
7.2 Operating the pump
Note
Note
Caution
Caution
Stop
Start
Menu
Down
Up
Mode
Mode
Stop
Start
Menu
Info
Down
Up
English (GB)
To operate the pump, see sections 8. Operation,
9. How to use the control unit and
10. Maintenance and, if necessary, section
11. Fault finding chart.
7.3 Shutdown
Warning
Risk of chemical burns!
Wear protective clothing (gloves and goggles)
when working on the dosing head, connections
or lines!
Do not allow any chemicals to leak from the
pump. Collect and dispose of all chemicals
correctly!
If possible, rinse the dosing head before shutting
down the pump, e.g. by flushing it with water.
7.3.1 Switching off / uninstalling
1. Switch off the pump and disconnect it from the power supply.
2. Depressurise the system.
3. Take suitable steps to ensure that the returning dosing
medium is safely collected.
4. Carefully remove all lines.
5. Uninstall the pump.
7.3.2 Cleaning
1. Rinse all parts that have come into contact with the medium
very carefully:
– lines
– valves
– dosing head
– diaphragm.
2. Remove any trace of chemicals from the pump housing.
7.3.3 Storage
Storage of the pump:
1. After cleaning (see above), carefully dry all parts and reinstall
the dosing head and valves, or
2. change the valves and diaphragm.
See section
7.3.4 Disposal
Disposal of the pump:
• After cleaning (see above), dispose of the pump in accordance
with the relevant regulations.
10. Maintenance.
8. Operation
In the event of a diaphragm leakage, the dosing
liquid may leak out of the hole in the intermediate
flange between the pump and the dosing head.
The parts inside the housing are protected from
the dosing liquid for a short time (depending on
the type of liquid) by the housing sealing. It is
necessary to check regularly (daily) if liquid is
leaking out of the intermediate flange.
Observe section 10.5 Diaphragm breakage
For maximum safety, we recommend the pump
version with diaphragm leakage detection.
8.1 Control and display elements
TM03 6257 4506
Fig. 17 Display of DDI 222
ElementDescription
Light-emitting diode (LED)
• Lights up red when the pump is stopped.
• Lights up green when the pump is started
and briefly goes out during a suction
stroke.
• Lights up yellow when the pump is
switched off remotely.
• Flashes red if an error signal is present.
• Flashes red/green when an error message
is present and the pump is running, or
restarts automatically after the error has
been corrected.
• Goes out when the pump is in menu mode.
"Start/Stop"
• Use this button to start or stop the pump.
• Error signals can be acknowledged by
pressing the "Start/Stop" button.
Use the "Menu/Info" button to switch between
the operating modes.
Use the "Down" and "Up" buttons to change
values in the display.
18
8.1.1 Display test
A display test is automatically performed when the pump is
switched on. All the segments of the LCD are switched on for
3 seconds and the software version number is then displayed for
2 seconds.
8.1.2 Display indicator
When switched on (if the pump was stopped) and during pump
operation, the dosing flow setpoint is displayed. With contact
control the set ml/contact value is displayed.
8.2 Switching on/off
Before switching on the pump, check that it is
installed correctly. See sections 5. Installation
and 7.1 Initial start-up / subsequent start-up.
• To start the pump, switch on the power supply.
• To stop the pump, switch off the power supply.
9. How to use the control unit
Note
Note
Manual
l/h
Stop
1.20
Manual
l/h
Stop
1.20
First see sections 5. Installation,
7. Start-up/shutdown and 7.2 Operating the
pump. Only the additional functions are
described in this section.
9.1 Menu levels
Menu levels used in the control unit
• First function level: for selecting and setting the operating
modes of the pump (Manual, Contact, Analog), performing the
batch and timer functions and starting the pump.
•
Second function level: for setting and viewing additional
functions, selecting and setting the batch and timer functions
and setting the access code to protect the pump against
unintentional or unauthorised access to pump settings.
•
Service level: for setting the pump type and the unit of display
for the dosing flow (l/h or gal/h) and setting the inputs and
outputs.
Saving user settings
The pump settings are automatically saved approximately every
10 minutes and remain as they are even after the power supply
has been switched off.
9.2 General functions of the control unit
9.2.1 Suction
If the "Start/Stop" button is pressed for longer than 1 second, the
pump switches to continuous operation for as long as the button
is held down (e.g. for suction).
This happens regardless of the selected operating mode.
(In batch or timer mode, the pump has to be stopped first.)
9.2.2 Locking "run"
The pump can be locked to avoid manual stopping.
When activating this function (service level), the pump starts
running with the present settings and cannot be stopped using
the "Start/Stop" button.
It is still possible to acknowledge error messages using the
"Start/Stop" button.
Stopping the pump when the locking "run" is activated
• If remote on/off is connected, use remote off.
• Disconnect the pump from the power supply.
For "Batch manual", the "Run" button should not
be locked as the pump then runs in continuous
operation.
9.2.3 Two-stage tank-empty signal
This function is used to provide a warning when the tank is almost
empty and to switch off the pump when the tank is empty. To use
the pre-empty signal, ensure that the suction line is equipped with
two float switches.
Pre-empty signal
The pre-empty signal can be an error signal or a pre-empty signal
at socket 3. For a pre-empty signal, relay 1 must be set to
"Pre-empty signal". See sections
9.7.1 Modifying the switch assignment.
When the contact of the corresponding float switch closes,
• the error signal relay or pre-empty signal relay switches on,
but the pump is not switched off.
• The LED flashes red.
• The empty-signal symbol flashes in the display.
Fig. 18 Display: pre-empty signal
Once the error has been corrected,
• the error signal relay or pre-empty relay switches off.
• The pump returns to the state it was in before the error
occurred.
Empty signal
When the contact of the corresponding float switch closes,
• the pump is switched off.
• The error signal relay switches on.
• The LED flashes red.
• The empty-signal symbol lights up in the display.
Fig. 19 Display: empty-signal symbol
Once the error has been corrected,
• the pump starts running again (if it was running before).
• The error signal relay switches off.
• The pump returns to the state it was in before the error
occurred.
6. Electrical connections and
English (GB)
TM03 6596 4506TM03 6597 4506
19
9.2.4 Diaphragm leakage sensor (MBS)
Note
Manual
l/h
1.20
MBS
Manual
l/h
Stop
1.20
ERROR
MBS
Analog
Run
0
ERROR
1/min
bar
Analog
Stop
0
ERROR
1/min
bar
Note
Analog
Run
0
ERROR
1/min
bar
English (GB)
As an option, the pump can be equipped with a sensor for
diaphragm leakage detection.
The electronics automatically detects whether a sensor is
connected. The following appears in the display.
Fig. 20 Display: MBS sensor is connected
When a diaphragm leakage is detected by the sensor,
• the pump is switched off.
• The error signal relay switches on.
• The LED flashes red.
• "MBS" and "ERROR" flash in the display.
Fig. 21 Display: diaphragm leakage detected
Once the error has been corrected (the contact is no longer
closed),
• press the "Start/Stop" button to acknowledge the error.
• The pump starts running again (if it was running before).
• The error signal relay switches off.
• The pump returns to the state it was in before the error
occurred.
A cable break of the pressure switch is also
indicated as a diaphragm leakage signal
(MBS error). After acknowledging the MBS error,
the pump continues to operate without error
indication!
9.2.5 Blocking safety
If the pump has existing strokes to process, a check is carried out
to determine whether the drive is turning. If the drive motor is
blocked, e.g. due to excess counter-pressure in the dosing
system, this is detected and indicated by the integrated motor
monitoring function.
• The error signal relay switches on.
• "1/min", "bar" and "ERROR" flash in the display.
Fig. 22 Display: motor monitoring
9.2.6 Power off
If the power consumption of the drive motor is too high, e.g. due
to excess counter-pressure in the dosing system, this is detected
and indicated by the power monitoring function.
• The error signal relay switches on.
• "1/min", "bar" and "ERROR" flash in the display.
• The pump is stopped. Every 10 minutes, an attempt is made to
automatically restart the pump.
• The LED flashes red/green.
TM03 6598 4506TM03 6599 4506
Fig. 23 Display: power off
For possible errors and their correction,
see section
Once the error has been corrected,
• the pump restarts automatically, or
• press the "Start/Stop" button to acknowledge the error.
9.2.7 Remote on/off
The pump can be switched off remotely (e.g. from a control
room).
• If switched off remotely, the pump does not respond to any
input signals or to operator input.
Exception: The pump can still be stopped manually (press the
"Start/Stop" button) and run in continuous operation (press
and hold down the "Start/Stop" button).
• "Stop" lights up in the display.
• The yellow LED lights up.
• When switched on remotely, the pump returns to the state it
was in before it was switched off. If, for example, the pump
was previously in "Stop" mode, it returns to this mode once it
is switched on.
9.2.8 Memory function
Contact signals, which cannot be processed immediately, can be
stored and subsequently made available to the pump for
processing. A maximum of 65,000 contact signals can be stored.
•
Without memory: If the pump is running when a contact
signal is received, the signal is ignored. The pump performs
the current dosing, then it is again ready to receive new
contact signals, i.e. it rejects excess contacts.
•
With memory: If the pump is running when a contact signal is
received, the signal is stored in the memory. First, the pump
performs the current dosing, then it processes the contact
signals from the memory.
The contents of the memory are deleted:
• by switching off the power supply
• by switching the operating mode.
The contents of the memory are not deleted:
• by actuating the remote on/off contact
TM03 6763 4506
• by pressing the "Start/Stop" button
• by continuous operation.
11. Fault finding chart.
TM03 6360 4506
• The pump is stopped.
• The red LED flashes.
For possible errors and their correction,
see section
Once the error has been corrected,
• press the "Start/Stop" button to acknowledge the error.
20
11. Fault finding chart.
The memory function can be enabled and
disabled in the second function level.
9.2.9 Flow Monitor
Caution
Note
Note
Note
The pump can be equipped with a pressure sensor (Flow Monitor
pump option).
Based on the pressure measured by the sensor and on the motor
position, an indicator diagram is created. Possible dosing faults
or the exceeding of the permissible counter-pressure are
detected reliably and indicated by the display or the error
message output.
The following errors are recognised:
• Pressure exceeded (the pump is stopped and restarts
automatically when the pressure decreases).
• Dosing error (the pump doses 30 % to 100 % less due to a
leaking discharge valve or suction valve, a clogged suction
line or an air bubble in the dosing head).
Depending on the operating conditions, it may be
impossible to detect dosing errors due to several
faults occurring simultaneously (e.g. leaking
suction and discharge valves)!
The dosing controller and dosing control functions can be
switched on and off independently of each other. It is always
possibly to display the pressure that has been measured during
operation whenever the pressure sensor is connected.
For information about operating the pump with
the Flow Monitor, see section 9.10 Flow Monitor.
9.3 Signal outputs
The control unit has the following signal outputs, e.g. in order to
return a signal to the control room.
9.3.1 Current signal output
English (GB)
To use the control signal output, see section
9.9 Current signal control 0-20 mA / 4-20 mA.
The current flow rate of the pump is output as a current
signal.
• Current output 0-20 mA in the following mode:
– Current control 0-20 mA.
• Current output 4-20 mA in the following modes:
– Current control 4-20 mA
– Manual
– Contact
– Batch dosing with manual/contact start
– Timer with manual/contact start.
The current output is linear between 4 (0) mA at
flow rate = 0 and 20 mA at maximum flow rate
Q
(default setting) or the corresponding
max.
weighting value pair.
9.3.2 Error signal
Used to return various error states to the control room.
9.3.3 Stroke signal / pre-empty signal / pulse input
Depending on the relay setting, the contact output receives a
signal in these cases:
• for each complete stroke of the pump, or
• a pre-empty signal input, or
• each pulse input at the pump.
To set the relay, see section
assignment
.
9.7.1 Modifying the switch
21
9.4 First function level
Stop
Start
Stop
Start
Stop
Start
Stop
Start
Down
Up
Down
Up
Analog
0.000
4-20 mA
l/h
Analog
0.000
0-20 mA
l/h
Contact ml
1.75
l/h
Manual
1.20
Run
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Down
Up
Down
Up
Pump not running (LED lights up red)
Pump running (LED lights up green)
Manual control
Contact signal
control
Current signal
control
0-20 mA
Current signal
control
4-20 mA
Set the dosing rate to approx.
0.125 % to 100 % of max. dosing
rate [l/h]
Set the dosing quantity/signal to
0.111 - 22.2 ml (DDI 60-10)
0.278 - 55.5 ml (DDI 150-4)
Dosing rate proportional to current signal*
20 mA:Continuous operation, max. dosing rate
< 0.2 mA:Pump stops
0.2 - 20 mA: Dosing rate proportional to current
signal
Dosing rate proportional to current signal*
20 mA:Continuous operation, max. dosing rate
< 4.2 mA:Pump stops
4.2 - 20 mA: Dosing rate proportional to current
signal
< 2 mA:Fault signal switches on
> Display:"ERROR", LED flashes red
Setting the weighting
(max. dosing rate)
Setting the weighting
(max. dosing rate)
English (GB)
Fig. 24 First function level
* You can modify the assignment between the current input and the flow rate. See section
9.9 Current signal control 0-20 mA / 4-20 mA.
TM03 6674 4506
22
9.4.1 Setting the operating modes
Manual
l/h
Run
1.20
Note
Note
Contact ml
1.75
The operating modes are selected in the first function level, and
settings can be made for the modes.
This function level can only be opened when the pump is
stopped.
1. When the pump is stopped (LED lights up red), press the
"Menu/Info" button.
– The first function level is opened.
2. Navigate in the first function level by repeatedly pressing the
"Menu/Info" button.
3. Use the "Up" and "Down" buttons to modify the settings in the
relevant menu as shown in fig. 24.
4. Press the "Start/Stop" button to confirm the settings and to
exit the first function level.
– The pump is running (LED lights up green).
9.4.2 Manual control
Dosing with manual on/off and manually adjustable dosing
flow
In this operating mode, all the settings are entered on the pump
by the operator.
• Use the "Start/Stop" button to start or stop the pump.
• Use the "Up" and "Down" buttons to increase or decrease the
flow rate. This can be done when the pump is stopped or when
it is running.
9.4.3 Contact signal control
The pump must be started first in this operating
mode (LED lights up green and "Run" appears in
the display).
• Use the "Start/Stop" button to start or stop the pump.
For continuous dosing in a process
For each signal received at the contact input of the pump
(e.g. from a water meter with reed contact output), the pump
doses the set dosing capacity. The dosing is continuously
distributed between the incoming contacts via a controller.
The maximum dosing capacity must not be exceeded.
Input range for the dosing capacity per contact
Min. dosing capacity
Pump type
DDI 60-100.11122.2
DDI 150-40.27855.5
Even if the pump receives more contact signals than it can
process at the maximum flow rate, it only runs in continuous
operation with a maximum stroke frequency of
180/min. 120/min. in slow mode).
(= 1/50 stroke/contact)
[ml] [ml]
Max. dosing capacity
(= 4 strokes/contact)
English (GB)
Fig. 25 Display: manual control
The maximum displayed/adjustable flow rate is automatically set
according to the selected pump type and the calibrated stroke
volume.
Input range for the flow rate
Q
Pump type
DDI 60-100.075
DDI 150-40.188
min.
[l/h]
Resolution of flow rate
20 ml/h for Q < 10 l/h
100 ml/h for Q
20 ml/h for Q < 10 l/h
100 ml/h for Q
1 l/h for Q
10 l/h
10 l/h
100 l/h
TM03 6601 4506
Fig. 26 Display: contact signal control
Use the "Up" and "Down" buttons in the first function level to set
the dosing volume for each contact signal.
1. When the pump is stopped (LED lights up red), press the
"Menu/Info" button.
– The first function level is opened.
2. Use the "Up" and "Down" buttons in the "contact signal
control" menu to set the dosing volume per contact signal.
3. Press the "Start/Stop" button to confirm the settings and to
exit the first function level.
– The pump is running (LED lights up green).
Due to the constant dosing control, the pump can
continue dosing for a short time even when no
contact has been received.
9.4.4 Current signal control 0-20 mA / 4-20 mA
For current signal control, see section 9.9 Current signal control
0-20 mA / 4-20 mA
.
9.5 Second function level
9.5.1 Opening / exiting the second function level
Open the second function level
• to set the access code,
• to enable or disable functions such as Flow Monitor or
memory,
• to enter settings for operating modes such as batch mode,
• to display the total number of operating hours and total dosing
capacity,
• to carry out a calibration, or
• to modify the assignment between the current input/output and
dosing rate.
This function level can only be opened when the pump is stopped
(LED lights up red).
TM03 6602 4506
23
9.5.2 Setting the access code
Note
Down
Up
Stop
Start
Stop
Start
Stop
Start
Menu
Info
Menu
Info
Pump running (LED lights up green)
Pump not running (LED lights up red)
Keep pressed for 3 seconds
Second function level
Setting code 111
• Calibration
• Pressure control
•Flow on/off
• Memory function on/off
• Weighting of current
input/output
•Batch mode
•Timer mode
•PROFIBUS
•Slow mode
• Display or resetting of total
dosing capacity
• Display of total number of
operating hours
English (GB)
The access code is used to protect the pump against
unintentional/unauthorised access to pump settings.
The default setting is 111. Code 111 gives access to all settings
described in sections
function level
1. Press the "Start/Stop" button while the pump is running
(LED lights up green).
– The pump is stopped (LED lights up red).
2. Press and hold down the "Menu/Info" button for 3 seconds.
– The second function level is opened.
– The input arrow appears in the display.
– "C:111" (default setting is "111") or a user-defined code
3. Use the "Up" and "Down" buttons to set the code in the range
between 1 and 999.
Code 111 is required to open the second function level.
.
The "Start/Stop" button for stopping the pump is
active with any code.
appears in the display.
9.4 First function level and 9.5 Second
Fig. 27 Opening / exiting the second function level
24
TM03 6371 4506
1. Navigate in the second function level by repeatedly pressing
Note
Stop
Start
Stop
Start
Stop
Start
Stop
Start
Stop
Start
Down
Up
C:111
Code
Memory
OFF
Analog
L: 00
mA
Down
Up
Down
Up
4-20 mA
OFF
CAL
Stop
Start
Down
Up
P:OFF
bar
Stop
Start
Down
Up
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Stop
Start
flow
OFF
Down
Up
Menu
Info
Keep pressed for 3 seconds
Setting code 111
Calibration
Dosing controller
Pressure control
Memory function
Weighting of current
input/output
Press "Up" to start calibration,
see section
9.6 Calibration
Switch dosing controller on/off
ON/OFF
Press "Up" to switch on pressure
control function
For maximum counter-pressure
settings, see section
2. Use the "Up" and "Down" buttons to modify the settings in the
relevant menu as shown in figs 28 and 29.
3. Press the "Start/Stop" button to exit the second function level.
You can only change the parameters in the
shown order. When the "Menu/Info" button is
pressed again (after one run), the first function
level opens automatically.
English (GB)
Fig. 28 Second function level, part 1
TM03 6609 4506
25
English (GB)
Stop
Start
Stop
Start
1
h
Stop
Start
Down
Up
OFF
9999
OFF
OFF
BUS
SL : OF
Stop
Start
Stop
Start
Stop
Start
Stop
Start
Down
Up
Down
Up
t
B
l /
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Menu
Info
Setting code 111
Calibration
Dosing controller
Pressure control
Memory function
Weighting of current input/output
Batch on/off
ON/OFF
Adjustment of batch quantity and
dosing rate for batch operation, see
section
9.11 Batch menu / batch mode
Timer on/off
ON/OFF
Adjustment of batch quantity, dosing
rate and times for timer operation, see
section
9.12 Timer menu / timer mode
Slow mode on/off
ON/OFF
To set the slow-mode factor, see
section
9.6.8 Slow mode
Display of total dosing quantity [l] (resettable)
0.000 - 9.999
10.00 - 99.99
100.0 - 999.9
1000 - 9999
Display of operating time of drive
1 = 10 h to 9999 = 99,990 h
Batch
PROFIBUS
(only with
PROFIBUS)
Slow mode
(anti-cavitation)
Dosing quantity
counter
Operating hours
counter
See previous page
Bus address indication
Timer
Fig. 29 Second function level, part 2
TM03 6610 4506
26
9.6 Calibration
Note
Note
Note
red LED
red LED
Down
Up
Stop
Start
Stop
Start
Stop
Start
OFF
Up
Down
CAL
- - -
CAL
Menu
Info
Menu
Info
Menu
Info
Menu
Info
OFF
CAL
99
Run
CAL
200
Stop
CAL
87
StopCAL
1315
Stop
CAL
ml
1295
Stop
CAL
On
CAL
Up
Flashing
Green LED flashingProcess 200 strokes
Manual stop at user-defined
stroke number
Value of manufacturing calibration - calculated for stroke number of
actual calibration
Input of actual ascertained
calibration volume
Flashing
Wait until ON CAL (not
flashing) is displayed
Red LED
Red LED
The dosing flow display is set by default for an operating
counter-pressure of 3 bar. Calibration can be used to set the
pump flow to the actual operating conditions.
With activated flow compensation (see section
4.4.4 Flow compensation):
When dosing media with a viscosity different
from water or after a software update the pump
has to be calibrated. After a software update
"cal" is flashing in the display.
Calibrate the pump under normal operating conditions with the
discharge line connected and at operating counter-pressure.
The dosed volume must be gauged in litres
during calibration, e.g. by drawing the dosing
medium from a gauged tank.
"OFF CAL" appears in the display.
1. Press the "Up" button.
– "- - -" and "CAL" (flashing) appear in the display.
2. Wait until "ON" and "CAL" (not flashing) appear in the display.
– "ON CAL" appears in the display.
3. Press the "Start/Stop" button.
– Calibration is started. The LED flashes green and "Run"
flashes in the display.
• 200 strokes are performed by default. The number of strokes
performed appears in the display.
• Press "Start/Stop" to stop at any stroke value.
– The LED lights up red.
4. Press the "Start/Stop" button.
The current calibration value is displayed (not with replacement
circuit boards!).
5. Use the "Up" and "Down" buttons to enter the calibration
value (gauged volume in ml).
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
second function level).
The calibration process does not change the
setting for the assignment/weighting of the
current input and output for the flow rate.
If a current input or output is used, check after
calibration to determine whether a new current
weighting is required.
English (GB)
Fig. 30 Calibration
TM03 6678 4506
27
Adjusting the operating counter-pressure without gauging
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
012345678910
p
sys
[bar]
V
kal
[ml]
DDI 60 -10
DDI 150 - 4
p
sys.
[bar]
V
cal
[ml]
Note
Note
English (GB)
the dosed volume during calibration
If you do not gauge the dosed volume, you can determine the
"calibration value" from the following dosing capacity curves in
order to adjust your pump to the operating counter-pressure.
The curves represent 200 strokes:
• Dosing medium with a viscosity similar to water
• 0.5 m flooded suction.
Fig. 31 Dosing capacity curves
TM03 6679 4506
Values are approximate values and do not take
into consideration deviations due to construction
tolerance according to VDMA 24284.
9.6.1 Flow Monitor
In order for the pressure sensor (if installed) to function as a
dosing controller, the dosing controller must be switched on.
See section
9.10 Flow Monitor.
9.6.2 Pressure control
In the pressure control menu, the pressure control function is
switched on or off and the stop counter-pressure is set.
See section
9.10 Flow Monitor.
9.6.3 Memory function
The memory function is used to store excess contact signals for
processing later. See section
9.6.3 Memory function.
• Switch the memory function on/off with "Up" / "Down".
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
second function level).
9.6.4 Weighting of current input/output
In current input/output operation, the dosing capacity is controlled
via the current signal. The pump emits a current signal as a
feedback for control rooms or master/slave applications.
For weighting of current input/output, see also
9.9 Current signal control 0-20 mA / 4-20 mA.
9.6.5 Batch menu / batch mode
In batch mode, a defined batch quantity is dosed with a defined
dosing flow. The batch can be dosed manually or by a contact.
See section
9.6.6 Timer menu / timer mode
In timer mode, a defined batch quantity is dosed with a defined
dosing flow and a defined start time. See section
menu / timer mode
9.11 Batch menu / batch mode.
.
9.12 Timer
28
9.6.7 PROFIBUS menu
Note
Note
Note
Note
The "PROFIBUS" menu item is only displayed for pumps with
PROFIBUS interfaces. The PROFIBUS interface is
activated/deactivated in this menu and the bus address is
specified.
9.6.8 Slow mode
Slow mode reduces the maximum dosing flow of the pump in two
stages to 66 % (slow mode 1) or 41 % (slow mode 2).
By increasing the minimum suction time, cavitation is, for
example, reduced with viscous media.
Slow mode can be activated in any operating mode. In the
slow-mode menu, the slow mode function is set and the
slow-mode factor is selected.
Setting slow mode
In the second function level, "SL:OF" appears in the display.
• Use the "Up" and "Down" buttons to switch between normal
operation (SL:OF), slow mode 1 (SL:01) and slow mode 2
(SL:02).
– The current slow-mode factor appears in the display.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
second function level).
The maximum flow rate of the pump decreases.
The maximum stroke rate is 120 l/min. in slow
mode 1 and 74 l/min. in slow mode 2.
The minimum adjustable flow rate is maintained.
9.6.9 Display/resetting of total dosing capacity
The total capacity dosed since the value was last reset is
displayed.
The maximum value that can be displayed is
9999 l. If this value is exceeded, the counting
starts again at zero.
To reset the value,
1. press the "Up" button.
– "dEL" appears in the display.
2. Press the "Start/Stop" button.
– The total dosing capacity is deleted.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
second function level).
Display of value during pump operation (in "Run" mode)
• Press the "Menu/Info" button.
– The total capacity dosed since the value was last reset is
displayed.
9.6.10 Display of total number of operating hours
The operating hours counter indicates the operating time of the
drive, e.g. to check maintenance intervals. The maximum number
of operating hours that can be displayed is 99,990 h
(display = 9999).
The operating hours counter cannot be reset.
Multiply the number displayed by 10 to determine
the number of operating hours.
9.7 Service level
Open the service level
• to modify the switch assignments of the electronics,
• to set the pump type, or
• to select the unit of measurement for the dosing flow
(l/h or gal/h) that will be displayed.
9.7.1 Modifying the switch assignment
You are modifying the default settings of your
control unit. They will therefore differ from the
technical data.
The service level can only be accessed when the power supply is
switched on.
1. Simultaneously press the "Menu/Info" and "Down" buttons
and hold them down.
2. Switch on the power supply.
– The LED alternately flashes red and green.
3. Release the "Menu/Info" and "Down" buttons.
4. Press the "Start/Stop" button.
5. Press the "Up" button.
– The LED lights up yellow.
– "Func" appears in the display.
6. Press the "Menu/Info" button.
– The service level is opened.
English (GB)
29
English (GB)
Up
Stop
Start
Down
+
Stop
Start
Menu
Info
Menu
Info
Pump not connected to power supply
LED flashes up red and green alternating
LED lights up yellow
Service level
1. Relay function (stroke / pre-empty / pulse selection)
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
service level).
3. Pre-empty signal, NO/NC input
"3:NO" or "3:NC" appears in the display (empty-signal symbol
flashes in display).
• Use the "Up" and "Down" buttons to switch between:
– "3:NO": Pre-empty signal = normally open contact, and
– "3:NC": Pre-empty signal = normally closed contact.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
service level).
4. Empty signal, NO/NC input
"4:NO" or "4:NC" appears in the display (empty-signal symbol
lights up in the display).
• Use the "Up" and "Down" buttons to switch between:
– "4:NO": Empty signal = normally open contact, and
– "4:NC": Empty signal = normally closed contact.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
service level).
5. Error signal, NO/NC output
"5:NO" or "5:NC" appears in the display ("ERROR" flashes in the
display).
• Use the "Up" and "Down" buttons to switch between:
– "5:NO": Error signal relay = normally open contact, and
– "5:NC": Error signal relay = normally closed contact.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
service level).
6. Remote off, NO/NC input
"6:NO" or "6:NC" appears in the display ("Run" and "Stop" flash in
the display).
• Use the "Up" and "Down" buttons to switch between:
– "6:NO": Remote off = normally open contact, and
– "6:NC": Remote off = normally closed contact.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
service level).
7. Locking "run" on/off
The locking of the "Start/Stop" button to prevent manual stopping
of the pump can be enabled and disabled.
The display indicates "7:ON" or "7:OFF" (the "Run" symbol is
displayed).
• Use the "Up" and "Down" buttons to switch between:
– "7:ON": Locking "run" on, and
– "7:OFF": Locking "run" off.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
service level).
P: CAL on/off (only for Flow Monitor)
"CAL:ON" or "CAL:OFF" appears in the display ("CAL" appears).
• Use the "Up" and "Down" buttons to switch between:
– "CAL:ON": Calibration of the pressure sensor for the Flow
Monitor enabled, and
– "CAL:OFF": Calibration of the pressure sensor for the Flow
Monitor disabled.
For calibration, see section 9.10.7 Calibrating the
sensor after the sensor has been replaced.
St: e.g. "60" (only for Flow Monitor)
• Use the "Up" and "Down" buttons to set the "number of error
strokes permitted when starting". If the number of error strokes
is exceeded, the "Flow error" error message appears.
FE: e.g. "7" (only for Flow Monitor)
• Use the "Up" and "Down" buttons to set the "number of error
strokes permitted during operation". If the number of error
strokes is exceeded, the "Flow error" error message appears.
Selection of unit (display)
"Unit l/h" or "Unit gph" appears in the display.
• Use the "Up" and "Down" buttons to switch between:
– "Unit l/h": Unit Q = l/h, and
– "Unit gph": Unit Q = gal/h.
• Press the "Start/Stop" button (confirm the setting and close the
service level), or
• press the "Menu/Info" button for a minimum of 10 seconds
(confirm the setting and open the pump selection).
Pump selection
The actual pump type must always be selected to
ensure error-free operation of the electronic
control function. Otherwise the displayed pump
and signals differ from the actual conditions.
"-60" or "-150" appears in the display.
• Use the "Up" and "Down" buttons to switch between the pump
types DDI 60-10 and DDI 150-4.
• Select your pump type, which is indicated on the pump
nameplate.
• Press the "Start/Stop" button (confirm the setting and close the
service level).
English (GB)
31
9.8 Resetting to default settings
Note
Note
Note
Analog
0-20mA
l/h
Run
0
Analog
l/h
Run
2.50
4-20mA
Analog
l/h
Run
0.000
ERROR
4-20mA
English (GB)
You can reset the first and second function levels to the default
settings when the power supply is being connected.
The service level settings (pump type, unit of
display for the dosing flow, input and output
settings) and the values for the total dosing
capacity and operating hours counter remain as
they are.
The pump is disconnected from the power supply.
1. Simultaneously press the "Up" and "Down" buttons and hold
them down.
2. Switch on the power supply.
– "boot" appears in the display.
3. Release the "Up" and "Down" buttons.
– All modified settings at the first and second function levels
are reset to the default settings.
9.9 Current signal control 0-20 mA / 4-20 mA
For controlling the dosing pump via an external current
signal of 0-20 mA (4-20 mA)
4-20 mA current signal control
If the current input signal falls below 2 mA, the error relay is
switched, as an error has probably occurred at the signal source
or on the cable.
• The error signal relay switches on. The LED flashes red.
• "4-20 mA" and "ERROR" flash in the display.
TM03 6605 4506
Fig. 35 Display: 4-20 mA current signal control
Fig. 33
Fig. 34 Display: 4-20 mA current signal control
• The flow rate is proportional to a current input signal of
• Above 19.5 mA, the pump runs in continuous operation at
• Below 0.2 (4.2) mA, the pump switches off.
• Use the "Start/Stop" button to start or stop the pump.
Display: 0-20 mA current signal control
0-20 mA (4-20 mA).
maximum dosing flow (Q
Default setting for Q
3 bar (default calibration value). Once the pump
has been calibrated, the current signals must be
weighted. See sections 9.9.2 With calibrated
pump and 9.9.3 Setting the weighting.
The pump must be started first in this operating
mode (LED lights up green and "Run" appears in
the display).
max.
).
is the dosing flow up to
max.
TM03 6603 4506TM03 6604 4506
32
The assignment between the current signal and flow rate is
0 mA4 mA8 mA12 mA16 mA20 mA
0
I
in
[mA]
Q [l/h]
I
in
/ I
out
0-20mA
I
in
4-20 mA
I
out
4-20mA,manual,
kontakt
1a
2a
1..
2..
Q
max
default (Q
kal
)
50 l/h
20 l/h
40 l/h
10 l/h
30 l/h
Q
max.
default (Q
cal
)
Iin / I
out
0-20 mA
I
in
4-20 mA
I
out
4-20 mA, manual,
contact
Iin [mA]
Note
Note
Note
linear.
• With 0-20 mA current signal control, the curve for current input
and current output passes through Q = 0 at 0 mA and the
value pair Q
max.
(Q
) at 20 mA (curve 1a).
cal
• With 4-20 mA current signal control, the curve for current input
and current output passes through Q = 0 at 4 mA and the
value pair Q
max.
(Q
) at 20 mA (curve 2a).
cal
• With manual or contact control, the curve for current output
passes through Q = 0 at 4 mA and the value pair Q
at 20 mA (curve 2a).
The default setting for Q
default calibration at 3 bar.
is the maximum dosing flow at
max.
max.
(Q
cal
English (GB)
)
Fig. 36 Current input and current output with default setting
9.9.1 Direct weighting of the current signal input and output
Weighting while the pump is running can be carried out in the first
function level. The currently set value increases or decreases for
the maximum flow rate Q
Q
select mA max.
.
max. (Qcal
), or with weighting set value
Setting the weighting
The parameters for 0-20 mA and for 4-20 mA are
independent of one another. The weighting
parameters are modified and saved according to
the set operating mode.
Select the current control used (0-20 mA /
4-20 mA) before weighting.
Weighting can be set independently of the current
input value that is currently set. The dosing flow
value [l/h] that corresponds to the set current
input value [mA] always appears in the display.
1. When the pump is running or stopped, press and hold down
the "Up" button for approximately 5 seconds.
– "0-20 mA" or "4-20 mA", "Analog" and "l/h" flash in the
display.
2. Use the "Up" and "Down" buttons to increase or decrease the
currently set value for the maximum flow rate.
The curve for current input / current output now passes as
follows:
• With 0-20 mA (4-20 mA) current signal control, the curve for
current input and current output passes linearly through Q = 0
at 0 mA (4 mA) and the currently set value for the maximum
flow rate Q
select max.
The set weighting is saved in the pump.
The values are retained, e.g. when the power
supply is switched off, and are also active when
current weighting is called in the second function
level.
at 20 mA (curves 1b and 2b).
TM03 6675 4506
33
Even for current input / current output assignments that are
0 mA4 mA8 mA12 mA16 mA20 mA
0
I
in
[mA]
Q [l/h]
I
in
/ I
out
0-20mA
I
in
4-20mA
I
out
4-20 mA, manual,
kontakt
1a
2a
1..
2..
Q
max
default (Q
kal
)
50 l/h
20 l/h
1b
2b
Q
select max.
40 l/h
10 l/h
30 l/h
Q
max.
default (Q
cal
)
Iin / I
out
0-20 mA
I
in
4-20 mA
I
out
4-20 mA, manual,
contact
Q
select max.
Iin [mA]
0 mA4 mA8 mA12 mA16 mA20 mA
0
I
in
[mA]
3a
3b
Q
select mA max. b
/
mA
max.
Q
select mA max.a
/
mA
max.
Q
select mA min.
/
mA
min.
Q [l/h]
50 l/h
20 l/h
40 l/h
10 l/h
30 l/h
Q
select mA max. a
/ mA
max.
Q
select mA min.
/ mA
min.
Iin [mA]
Q
select mA max. b
/ mA
max.
Note
Note
English (GB)
already weighted in the second function level (see curve 3a),
subsequent weighting can be set or weighting can be shifted
here. The value for the maximum flow rate Q
mA
is shifted (curve 3b).
max.
Fig. 37 Current input and current output with direct weighting
select mA max.
at
TM03 6676 4506
Fig. 38 Current input and current output with subsequent weighting
9.9.2 With calibrated pump
When calibrating the pump for your application and using current
signal control and/or current output, proceed as follows:
1. Calibrate the pump.
2. Determine the maximum flow rate Q
the pump: Q
calibration, e.g. in manual mode, or the displayed flow rate in
is the maximum adjustable flow rate after
cal
by taking a reading on
cal
continuous operation (press and hold down the "Start/Stop"
button for longer than 1 second).
3. To set the current input / current output weighting, see section
9.9.3 Setting the weighting.
For unweighted assignment (curves 1a, 2a, see
fig. 34) select the following reference points:
L: mA
H: mA
Q
cal
is re-calibrated. This protects the user-defined
= 0 (4) mA / Q
min.
= 20 mA / Q
max.
select mA min.
select mA max.
is not updated automatically when the pump
value pairs. After calibration, new weighting may
be required!
34
TM03 6677 4506
= 0 l/h
= Q
.
cal
9.9.3 Setting the weighting
Note
Analog
L:0.0
mA
Down
Up
Stop
Start
Analog
6
mA
Analog
0.000
l / h
0-20 mA
Down
Up
Analog
10.00
l / h
0-20 mA
Stop
Start
0-20 mA
Menu
Info
Menu
Info
0-20 mA
Analog
H:20.0
mA
Down
Up
Stop
Start
Analog
16
mA
Analog
71.00
l / h
0-20 mA
Down
Up
Analog
40.00
l / h
0-20 mA0-20 mA
0-20 mA
Stop
Start
Flashing
Flashing
Select value for
current input
mA
min.
0-20 mA
Select value for
current input mA
max.
> mA
min.
Set the flow rate Q
mA min.
0 - 0.999 l/h
1 - 9.9 l/h
10 - 99.9 l/h
100 - Q
max.
[l/h]
Set the flow rate Q
mA max.
0 - 0.999 l/h
1 - 9.9 l/h
10 - 99.9 l/h
100 - Q
max.
[l/h]
The setting options for weighting depend on the
selected current signal control. The parameters
for 0-20 mA and for 4-20 mA are independent of
one another. The weighting parameters are
modified and saved according to the set
operating mode.
Select the current control operating mode used
later (0-20 mA / 4-20 mA) manually or via contact
signal before weighting. (Weighting of the
control output for manual control mode or
contact signal control is the same as current
weighting 4-20 mA.)
English (GB)
Fig. 39
Setting the weighting
In the second function level, first enter the values for reference
pair L:
The display shows
• the current value for mA
The default value is "L:0.0 mA" ("L:4.0 mA").
• "Analog"
• "0-20 mA" ("4-20 mA") (flashing).
Proceed as follows:
1. Use the "Up" and "Down" buttons to enter the minimum
current input mA
(e.g. mA
2. Press the "Start/Stop" button.
= 6 mA).
min.
min.
– The current value for the mA
appears in the display (the default value is 0.000).
min.
between 0 mA (4 mA) and 20 mA
assigned flow rate Q
min.
3. Use the "Up" and "Down" buttons to enter the desired value
for flow rate Q
mA min.
at mA
min.
(e.g. Q
mA min.
= 10 l/h).
mA min.
Now enter the values for reference pair H:
1. Press the "Start/Stop" button.
– The current value for mA
appears in the display (the
max.
default value is "H:20.0 mA").
2. Use the "Up" and "Down" buttons to enter the maximum
current input mA
3. Press the "Start/Stop" button.
– The current value for the mA
appears in the display (the default value is Q
max.
4. Use the "Up" and "Down" buttons to enter the desired value
for flow rate Q
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
second function level).
mA max.
max.
> mA
at mA
(e.g. mA
min.
assigned flow rate Q
max.
(e.g. Q
max.
= 16 mA).
max.
mA max.
max.
= 40 l/h).
mA
).
TM03 6682 4506
35
Result of weighting
Note
0 mA4 mA8 mA12 mA16 mA20 mA
0
I
in
[mA]
Q [l/h]
1d
50 l/h
20 l/h
Q
select mA max.d
40 l/h
10 l/h
30 l/h
1e
Q
select mA max.e
Q
select mA min.d
Q
select mAmin. e
Iin [mA]
Q
select mA min. d
Q
select mA max. e
Q
select mA max. d
Q
select mA min. e
0 mA4 mA8 mA12 mA16 mA20 mA
0
I
in/out
[mA]
Q [l/h]
L: Q
select mAmin.
= ____ / ____mA
min.
H: Q
select mA max.
= ____ /____mA
max.
Q
kal
L: Q
select mA min.
____/____ mA
min.
H: Q
select mA max.
____/____ mA
max.
Q
cal
Q [l/h]
I
in/out
[mA]
Note
Note
English (GB)
In the example, the following values were entered as reference
points L
L
H
: mA
d
d
: mA
and Hd:
d
= 6 mA, Q
min.
= 16 mA, Q
max.
select mA min.
select mA max.
= 10 l/h
= 40 l/h.
The curve for current input / current output now passes through
Q = 0 at < 6 mA, from Q = 10 l/h at 6 mA to Q = 40 l/h at 16 mA,
and through Q = 40 l/h at > 16 mA (curve 1d).
In the same way, it is also possible to enter a current weighting
with a negative gradient. In order to do this, the value pair for
reference point L must first be entered with the smaller mA value
followed by reference point H.
In the example, the following values were entered as reference
points L
L
H
: mA
e
e
: mA
and He:
e
= 2 mA, Q
min.
= 16 mA, Q
max.
select mA min.
select mA max.
= 60 l/h
= 10 l/h.
The curve for current input/current output now passes through
Q = 0 at < 2 mA, from Q = 60 l/h at 2 mA to Q = 10 l/h at 16 mA,
and through Q = 10 l/h at > 16 mA (curve 1e).
Fig. 40 Result of weighting
The maximum flow rate of the pump must not be
exceeded!
Note down the set current weighting in the following diagram
for current input/current output:
1. Label the Q [l/h] axis for your working area.
2. Mark your reference points with the value pairs:
L: mA
H: mA
min.
max.
/ Q
select mA min.
/ Q
select mA max.
and
in the diagram.
3. Draw the curve as a line from L to H, vertically from
Q
select mA min.
Q
select mA max.
to the mA axis, and horizontally from
to the edge of the diagram.
9.10 Flow Monitor
9.10.1 Application notes
Dosing of degassing media (H
agents)
• For a robust operation, set the number of permissible error
strokes to a value higher than 10.
Dosing of antiscalent (viscosity higher than 20 mPa s)
• Use spring-loaded valves for high-viscosity media.
• When dosing viscous media, see also section
medium
.
Dosing of viscous media
• For media with a viscosity higher than 20 mPa s,
spring-loaded suction and discharge valves are
recommended.
For batch or timer operation
• Set the number of permissible error strokes to a value lower
than the number of working strokes.
• If, while the pump is stopped, the pressure in the discharge
line falls below the minimum pressure of 2 bar (e.g. in the
event of a leak in the pressure-loading valve), increase the
number of permissible error strokes so as to prevent
unnecessary error messages.
Ensuring the counter-pressure by a pressure-loading valve:
• Check the counter-pressure 2 to 3 weeks after start-up.
– If it is below 2 bar, the pressure-loading valve has to be
re-adjusted.
– If the volume flow is not constant (as, for example, in the
case of contact or analog control), even small volume flows
should not fall below the minimum pressure or minimum
pressure difference of 2 bar.
TM03 6683 4506
9.10.2 Setting the Flow Monitor
In order for the pressure sensor (if installed) to function as a
dosing controller, the dosing controller must be switched on.
To allow the pump to switch off in the event of overpressure and
to set the cut-off pressure of the pump, the pressure control
function must be switched on and set.
If no pressure sensor is connected, the pump determines the
pressure from the motor current.
For applications with high requirements in terms
of precision, the pressure control function must
be used with a pressure sensor.
Switching on dosing controller
Menu item "flow" is open.
– "flow OFF" appears in the display.
1. Press the "Up" button.
– "flow ON" appears in the display.
– The dosing controller is activated.
Switching on pressure control function
, chlorine bleaching
2O2
1.3.10 Dosing
Fig. 41 Diagram for current input / current output
36
This menu item only appears if the pressure
sensor has already been detected once.
1. Press the "Menu/Info" button.
– Menu item "P" is open.
– "P:OFF" appears in the display.
2. Press the "Up" button.
– "P:ON" appears in the display.
TM03 6614 4506
– The pressure control function is activated.
Fig. 42 Set cut-off pressure
P:OFF
bar
Up
Down
10.0
Down
Up
P:OFF
P:on
Stop
Start
6.0
Stop
Start
Menu
Info
Menu
Info
Menu
Info
bar
bar
bar
bar
Second function level
Note
Caution
1.210
flow
l/h
Manual
1.210
flow*ERROR*
l/h
Manual
English (GB)
TM03 6680 4506
"P:ON" in the display:
1. Press the "Start/Stop" button.
– The currently defined cut-off pressure is shown in the
display. The default value is the maximum counter-pressure
of the pump type + 1 bar (pumps < 10 bar) or + 2 bar
(pumps from 10 bar and up).
2. Use the "Up" and "Down" buttons to enter the desired cut-off
pressure.
– You can set the cut-off pressure at which the pump is to be
stopped at around 2 bar up to the default value.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting and close the
second function level).
The actual cut-off pressure p
the set pressure p
set
: p
cut-off
is higher than
cut-off
= p
+ 0.5 bar.
set
When you are setting the cut-off pressure, be
aware that the pressure measured in the dosing
head is higher than the system pressure. It is
advisable to display the measured pressure first,
see section Displaying the pressure that has
been measured. The set cut-off pressure should
be higher than the measured pressure in the
dosing head.
9.10.3 Dosing controller function
The pump software monitors the dosing process and emits a
pulse for each dosing stroke. For each stroke, the "flow" display
is momentarily turned off.
• When switched on, the electronics detects whether the dosing
controller is activated.
– "flow" appears in the display.
Suppression of dosing control function during start-up
operation
60 error strokes* are permitted during the start-up operation,
before an error signal is emitted. After a further 7 error strokes*,
a dosing error is signalled.
* Default values, see also section
assignment
.
9.7.1 Modifying the switch
The start-up operation is triggered as follows:
• By switching on the power supply.
• Deaeration operation (continuously pressing the "Start/Stop"
button).
The start-up operation is completed
• after 60 strokes.
• after the first valid stroke signalled by the dosing controller.
• after short switching on and off the pump by pressing the
"Start/Stop" button.
The number of permissible error strokes can be increased or
decreased since, depending on pump type for example,
60 strokes may take a considerable time during the start-up
operation.
Dosing error (after start-up operation)
If, after seven successive strokes or after the number of strokes
which have been defined by the user, the dosing controller does
not emit a signal. This is recognised as an error:
• The error signal relay switches on, but the pump is not
switched off.
• The LED flashes red.
• "flow" and "ERROR" flash in the display.
Fig. 43 Display: "Dosing controller"
TM03 6576 4506
Fig. 44 Display: "Dosing error"
Once the error has been corrected and seven valid strokes have
TM03 6574 4506
been measured or the "Start/Stop" button has been pressed, the
error signal relay switches off.
• The pump returns to the state it was in before the error
occurred.
37
9.10.4 Pressure control function
Caution
1.210
bar
l/h
Manual
8.99
ERROR*bar*
Manual
RUN*
….
Pump running
Pump waiting
2 sec.
10 min.
10 min.
Pressure exceeded
English (GB)
To protect the pump and system against
excessive pressure build-up, install an overflow
valve in the discharge line.
The pressure sensor monitors the pressure in the dosing head.
If the set pressure is exceeded by 0.5 bar, the pump switches off.
When switched on, the electronics detects whether the chamber
pressure control function is activated.
• "bar" appears in the display.
Fig. 45 Display: "Pressure control"
Pressure exceeded
If, after one stroke, the cut-off pressure is exceeded, this is
recognised as an error:
• The pump is stopped.
• The error signal relay switches on.
• The LED alternately flashes red and green.
• The last pressure value to be measured is displayed.
• "RUN", "ERROR" and "bar" flash in the display.
TM03 6577 4506TM03 6578 4506
Fig. 46 Display: "Pressure exceeded"
Pump restart attempts:
• First the pump makes four attempts to restart, each separated
by a 2-second pause, if the chamber pressure has fallen below
the cut-off pressure (p
• After the pressure was exceeded, the pump restarts smoothly.
If the set cut-off pressure is exceeded, the pump is stopped
again immediately.
• After four attempts, the pump waits 10 minutes before
attempting to automatically restart again.
• The pump continuously attempts to restart if the chamber
pressure decreases in this way.
Fig. 47 Pump restart attempts
Error correction
• Press the "Start/Stop" button to stop the pump and prevent it
from restarting.
• Check the discharge valve and the installation on the
discharge side and correct any errors, if necessary.
For maintenance work, see section
• Check and correct the pressure setting, if necessary.
Once the error has been corrected,
• press the "Start/Stop" button to restart the pump.
– The pump returns to the state it was in before the error
occurred.
< p
act
).
set
10. Maintenance.
TM03 6579 4506
Displaying the pressure that has been measured
The pressure that has been measured during the pump operation
can be displayed at any time.
• Press the "Menu/Info" button twice. (If only pressed once, the
dosed quantity is displayed.)
– The pressure is displayed for approximately 10 seconds.
38
9.10.5 Error message - broken cable or faulty sensor
Note
Note
2.42
ERROR*
Manual
RUN
l/h
Stop
Start
Down
Up
Stop
Start
Down
Up
St:60
ERROR
FE: 7
ERROR
Menu
Info
Permissible error
strokes during start-up
operation
Number of error
strokes until the error
message is triggered
Use the "Up" and "Down" buttons to
set the number of permissible error
strokes during the start-up operation in
the range between 1 and 99.
Use the "Up" and "Down" buttons to
set the number of error strokes until
the error message is triggered during
normal dosing operation in the range
between 3 and 99.
Service level
If the dosing controller and/or the pressure control function are/is
switched on, the missing signal is recognised and emitted as an
error.
A faulty pressure sensor (broken cable) is displayed as follows:
• The error signal relay switches on.
• The pump is not stopped!
• The LED flashes red.
• "ERROR" flashes in the display.
Fig. 48 Display: "Broken cable"
Correct error
• Press the "Start/Stop" button twice to confirm the error and to
stop the pump.
• Repair the cable break.
Once the error has been corrected,
• press the "Start/Stop" button to restart the pump.
– The pump returns to the state it was in before the error
occurred.
If the cable is broken, the dosing controller and
pressure control/pressure display functions are
not active. When the "Menu/Info" button is
pressed twice to display the chamber pressure,
only "— — —" is displayed.
English (GB)
TM03 6580 4506
If the sensor fault cannot be corrected
immediately and if the pump is to continue to run
without a sensor, switch off the dosing controller
(flow: OFF) and pressure control function
(P:OFF).
9.10.6 Changing the number of permissible error strokes
To change the number of permissible error strokes during the
start-up operation and during normal dosing operation.
Fig. 49 Permissible error strokes
1. Open the service level.
2. Repeatedly press the "Menu/Info" button to navigate in the
service level until you reach menu item "St:60" (error stroke
during start-up operation).
– The display shows "St" and the number of currently defined
error strokes that are permissible during the start-up
operation.
3. Use the "Up" and "Down" buttons to set the number of
permissible error strokes during the start-up operation in the
range between 1 and 99.
4. Press the "Start/Stop" button.
– Confirm the setting and go to menu item "FE: 7".
– The display shows "FE" and the number of currently defined
error strokes that are permissible during normal dosing
operation.
5. Use the "Up" and "Down" buttons to set the number of error
strokes until the error message is triggered during normal
dosing operation in the range between 3 and 99.
6. Press the "Start/Stop" button
– to confirm the new settings
– to exit the service level
– to open the first function level.
TM03 6575 4506
39
9.10.7 Calibrating the sensor after the sensor has been
Up
Stop
Start
Stop
Start
P:OFF
CAL
P:ON
CAL
P:- - -
CAL
P:CAL
CAL
Menu
Info
Calibration of pressure sensor
Prepare the pump first!
Wait approximately 2 seconds
Service level
Caution
English (GB)
replaced
Once a sensor has been replaced, the new sensor must be
calibrated to the ambient pressure.
Prepare the pump for the calibration:
1. Before screwing in the sensor, check that no dosing liquid is
left in the place where the pressure sensor will be screwed in!
2. Screw in the new sensor with the correctly fitting O-ring.
3. Screw the sensor plug into socket 2.
4. Unscrew the suction valve.
Calibration of sensor
Fig. 50
Calibration of pressure sensor
1. Open the service level.
2. Repeatedly press the "Menu/Info" button to navigate in the
service level until you reach menu item "P" (calibration of
pressure sensor).
– "P:OFF" appears in the display.
3. Press the "Up" button to prepare the calibration.
– "P:ON" appears in the display.
When the pump is prepared for the calibration, calibrate the
pressure sensor:
1. Press the "Start/Stop" button.
– "P:- - -" is displayed for approximately 2 seconds.
– "P:CAL" appears in the display.
– The pressure sensor has been calibrated.
2. Press the "Start/Stop" button
– to confirm the new settings
– to exit the service level
– to open the first function level.
3. Fit the pump back on.
4. Screw in the suction valve.
TM03 6581 4506
40
Warning
Risk of chemical burns!
Wear protective clothing (gloves and goggles)
when working on the dosing head, connections or
lines!
Do not allow any chemicals to leak from the
pump. Collect and dispose of all chemicals
correctly!
The O-rings must be correctly placed in the
specified groove.
Observe the flow direction (indicated by an
arrow)!
Only tighten the valve by hand.
9.11 Batch menu / batch mode
Caution
OFF
B
Up
Down
2,00
B
Down
Up
l/h
Stop
Start
B
B
OFF
On
Stop
Start
1,05 L
B
Down
Up
Stop
Start
Menu
Info
Menu
Info
Menu
Info
Input of dosing rate with
"Up" / "Down"
Input of batch quantity
with "Up" / "Down"
In batch mode, a defined batch quantity is dosed with a defined
dosing flow. The batch can be dosed manually or by an external
contact signal.
Risk of dosing errors!
Batch dosing using contact inputs may be
insufficiently or excessively triggered in the
event of an error if the pump/system is not
monitored. The system must be protected
redundantly.
Batch mode is controlled at the first and second function levels.
• The batch quantity is set in the second function level.
• The batch function is enabled in the first function level.
Input range for the batch quantity:
0.0 - 999.9 ml / 1.00 - 99.99 l / 100.0 - 999.9 l.
Setting batch dosing
English (GB)
Fig. 51
Setting batch dosing
In the second function level, "OFF B" appears in the display.
1. Press the "Up" button.
– "ON B" appears in the display.
2. Press the "Start/Stop" button.
– The currently defined flow rate appears in the display.
3. Use the "Up" and "Down" buttons to enter the desired flow
rate.
4. Press the "Start/Stop" button.
– The currently defined batch quantity appears in the display.
5. Use the "Up" and "Down" buttons to enter the desired batch
quantity.
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
• press the "Start/Stop" button (confirm the setting, close the
second function level and enable batch dosing in the first
function level).
Performing batch dosing
• In the first function level, only the batch function is displayed
with the "Batch manual" and "Batch contact" menu items.
• "Stop" and the preset batch quantity appear in the display.
The LED lights up red.
Use the "Menu/Info" button to select
• "Batch manual", or
• "Batch contact".
Enabling batch mode
Batch manual
Batch dosing is triggered manually.
• Press the "Start/Stop" button.
– The LED and the "Stop" segment are turned off and "Run"
flashes in the display.
– The preset batch quantity is dosed.
Batch contact
Batch dosing is triggered by an external contact signal.
To activate the batch contact function,
• press the "Start/Stop" button.
– The LED lights up green, the "Stop" segment is turned off
and "Run" appears in the display.
When the external contact signal is received, "Run" flashes in the
display.
• The preset batch quantity is dosed.
During batch dosing
The batch quantity still to be dosed appears in the display.
To display the batch quantity already dosed,
• press the "Down" button.
To display the total batch quantity,
• press the "Up" button.
Stop/start of pump during batch dosing
To stop the pump,
• press the "Start/Stop" button, or
• actuate remote on/off.
To re restart the pump,
• press the "Start/Stop" button.
– The preset batch cycle continues.
– For the "Contact" timer, an external contact signal must also
be received.
Deactivating the batch function
1. Open the second function level.
2. Repeatedly press the "Menu/Info" button.
– "ON B" appears in the display.
3. Press the "Up" button.
– "OFF B" appears in the display.
– The batch function is deactivated.
TM03 6615 4506
41
9.12 Timer menu / timer mode
Batch 1 Batch 2 Batch n
Dosing
Dosing
Dosing
Start time t
1
Repetition time t
2
Repetition time t
2
Caution
t
t
OFF
On
OFF
t
Up
Down
Stop
Start
Down
Up
Stop
Start
Stop
Start
Stop
Start
Down
Up
Stop
Start
Down
Up
Down
Up
6.00
t
l/h
890.0
t
ml
1:00
t
h
t 1
t
2:00
t
h
t 2
t
Menu
Info
Menu
Info
Menu
Info
English (GB)
In timer mode, a defined batch quantity is dosed with a defined
dosing flow. The first dosing starts after the start time t
elapsed. Batch dosing is then repeated after the repetition time t
has elapsed until the user stops the process by pressing the
"Start/Stop" button or with remote off.
• Input range for the batch quantity:
0.0 - 999.9 ml / 1.00 - 99.99 l / 100.0 - 999.9 l
• Input range for the times t
1 min. < t
< 999 h / 1 min. < t2 < 999 h
1
and t2:
1
Input: hh:mm.
Fig. 52 Timer mode
Risk of dosing errors!
If repetition time t
the batch quantity at the set dosing flow within
is not long enough to dose
2
this time, the pump continues dosing until the
current batch quantity is finished. The pump is
then stopped and the next batch dosing is
triggered after the next repetition time.
Batch dosing in timer mode may be insufficiently
or excessively triggered in the event of an error if
the pump/system is not monitored. The system
must be protected redundantly.
Timer mode is controlled at the first and second function levels.
• The batch quantity and times t
function level.
and t2 are set in the second
1
• Timer mode is enabled in the first function level.
has
1
2
TM03 6616 4506
Fig. 53 Setting timer mode
"OFF t" appears in the display.
1. Press the "Up" button.
– "ON t" appears in the display.
2. Press the "Start/Stop" button.
3. Use the "Up" and "Down" buttons to enter the desired dosing
flow.
– The selected dosing flow appears in the display.
4. Press the "Start/Stop" button.
5. Use the "Up" and "Down" buttons to enter the desired batch
quantity.
– The selected batch quantity appears in the display.
42
6. Press the "Start/Stop" button.
– "t1" appears in the display.
7. Use the "Up" and "Down" buttons to enter start time t
.
1
8. Press the "Start/Stop" button.
– "t2" appears in the display.
9. Use the "Up" and "Down" buttons to enter repetition time t
• Press the "Menu/Info" button (confirm the setting and move on
to the next menu item), or
.
2
• press the "Start/Stop" button (confirm the setting, close the
second function level and enable timer mode in the first
function level).
TM03 6617 4506
Selecting "Manual" or "Contact" timer mode
Note
Note
Caution
• When the pump is running (LED lights up green), press the
"Start/Stop" button.
– "Stop" and the preset start time t
The LED lights up red.
appear in the display.
1
– "Manual" or "Contact" appears in the display ("Manual" is
default setting).
In the first function level, only the timer function is displayed with
the "Timer manual" and "Timer contact" menu items.
• Use the "Menu/Info" button to select
– "Timer manual", or
– "Timer contact".
Enabling timer mode
Timer manual
Batch dosing with the preset pause time is triggered manually.
• Press the "Start/Stop" button.
– The LED lights up green, the "Stop" segment is turned off
and "Run" flashes in the display.
– The preset batch cycle is started.
Timer contact
Batch dosing with the preset pause time is triggered by an
external contact signal.
To activate the batch contact function,
• press the "Start/Stop" button.
– The LED lights up green, the "Stop" segment is turned off
and "Run" appears in the display.
When the external contact signal is received, "Run" flashes in the
display.
• The preset batch cycle is started.
During pause times
The time remaining until the next dosing appears in the display.
To display the time already elapsed,
• press the "Down" button.
To display the total time t
or t2,
1
• press the "Up" button.
During timer dosing
The batch quantity still to be dosed appears in the display.
To display the batch quantity already dosed,
• press the "Down" button.
To display the total batch quantity,
• press the "Up" button.
Stop/start of pump during timer dosing
To stop the pump,
• press the "Start/Stop" button, or
• actuate remote on/off.
To restart the pump,
• press the "Start/Stop" button.
– The preset batch cycle continues.
– For the "Contact" timer, an external contact signal must also
be received.
Deactivating the timer function
1. Open the second function level.
2. Repeatedly press the "Menu/Info" button.
– "ON t" appears in the display.
3. Press the "Up" button.
– "OFF t" appears in the display.
– The timer function is deactivated.
9.13 Creating a master/slave application
You can connect several secondary pumps and control the
secondary pumps (slaves) via the first pump (master).
9.13.1 Master
All operating modes are available for the master pump:
• Manual
• Contact
• Batch dosing with manual/contact start
• Timer mode with manual/contact start
• Current control.
Select the output signal of the master pump in the service
level (relay 1) (output socket 3):
• Stroke signal (emits one output signal per stroke) must be
used for manual or current control of the master pump, or
• pulse input (emits one output signal per contact input signal)
must be used for contact control of the master pump.
Alternatively select the current output (output socket 2) for
current control of the slave pump.
Please note that the current output can differ
from the current input, e.g. when the pump is
stopped, and please observe the modified
current output values with weighted current
control.
9.13.2 Slave
The following operating modes are available for slave pumps in
contact or current control (input socket 4):
• Contact
• Batch dosing with contact start
• Timer mode with contact start
• Current control.
The settings for the operating modes of the slave
pumps are implemented independently of
settings for the master pump.
Unused pulse inputs from the master pump are
forwarded to the slave pumps when output signal
= pulse input is set. They are processed on the
slave pumps according to the slave pump
settings!
English (GB)
43
9.14 Hotkeys / info keys
English (GB)
The following important displays and functions of the DDI 222 can
be accessed quickly using button combinations (hotkeys).
Service functions
FunctionOperating state of the pumpActivate function / displayDeactivate function / display
Suction.
Move back the diaphragm for
servicing.
Boot function.
Delete the total dosing
capacity.
Display functions in batch and timer operation
Display/functionOperating state of the pumpActivate function / displayDeactivate function / display
Display the batch quantity
already dosed since start of
the batch.
Display total batch quantity.Press the "Up" button.Release the "Up" button.
Display the time that has
already elapsed.
Display the total time.Press the "Up" button.Release the "Up" button.
In "Run", "Stop" or "Menu/Info"
mode.
The pump must be in "Stop"
mode.
The pump is disconnected from
the power supply.
In "Run" mode.
During the batch dosing in batch
or timer operation.
During pause times in timer
operation.
Press the "Start/Stop" button for
at least 1 second.
Simultaneously press the "Up"
and "Down" buttons.
Simultaneously press the "Up"
and "Down" buttons while
switching on the power supply.
Press the "Menu/Info" button for
5 seconds.
Press the "Down" button.Release the "Down" button.
Press the "Down" button.Release the "Down" button.
Release the "Start/Stop" button.
—
—
—
Other display functions
Display/functionOperating state of the pumpActivate function / displayDeactivate function / display
Display the total dosing
capacity.
Display the input current.
Display of pressure in the
dosing head.
In "Run" mode.Press the "Menu/Info" button.
In "Analog" mode
(0-20 mA / 4-20 mA).
In "Run" mode.
Press the "Down" button.
Press the "Menu/Info" button
twice.
Display automatically jumps back
after 5 seconds.
Display automatically jumps back
after 10 seconds.
44
9.15 Pump safety functions
The DDI 222 pump is equipped with various safety functions as
standard, which are indicated by the following indicators and
behaviour of the pump.
Safety functions
DesignationErrorPump behaviourLED/display/relay
The LED flashes
red/green.
"ERROR", "bar" and
"l/min" appear in the
display.
The error signal relay
switches on.
The LED flashes red.
"ERROR", "bar" and
"l/min" appear in the
display.
The error signal relay
switches on.
The LED flashes
red/green.
"ERROR" and "bar" flash
in the display.
The LED flashes red.
"ERROR" and "MBS"
flash in the display.
The error signal relay
switches on.
Power off.
Blocking safety.
Pressure control (can be
switched on and off).
Diaphragm leakage
detection (optional).
Flow Monitor
(dosing controller).
Excess pressure in the
dosing head, or motor
power consumption too
high.
Clogged discharge line /
blocked motor.
When the pressure
control function is
switched on:
Excess pressure in the
dosing head (with
pressure sensor) or
motor power
consumption too high.
Diaphragm leakage.
See section
9.10 Flow Monitor.
The pump stops.
An attempt to restart
automatically is made
every 10 minutes.
The pump stops after
1 stroke.
The pump stops after
3 strokes. An attempt to
restart automatically is
made every 10 minutes
up to 5 times with an
increasing number of
strokes.
The pump starts running
again (in emergency
mode).
Behaviour after error
removal
Restart after error
confirmation and
pressing the "Start/Stop"
button, or on an
automatic restart attempt.
Restart after error
confirmation and
pressing the "Start/Stop"
button.
Restart after error
confirmation and
pressing the "Start/Stop"
button, or on an
automatic restart attempt.
The error signal relay
switches off after error
confirmation.
English (GB)
45
10. Maintenance
Caution
Note
Caution
Stainless
steel
Plastic
2)1)
Stainless
steel
Plastic
English (GB)
10.1 General notes
Warning
When dosing dangerous media, observe the
corresponding safety precautions!
Risk of chemical burns!
Wear protective clothing (gloves and goggles)
when working on the dosing head, connections
or lines!
Do not allow any chemicals to leak from the
pump. Collect and dispose of all chemicals
correctly!
Warning
The pump housing must only be opened by
personnel authorised by Grundfos!
Repair must only be carried out by authorised
and qualified personnel!
Switch off the pump and disconnect it from the
power supply before carrying out maintenance
work and repair!
10.2 Maintenance intervals
In the event of a diaphragm leakage, the dosing
liquid may leak out of the hole in the intermediate
flange between the pump and the dosing head.
The parts inside the housing are protected from
the dosing liquid for a short time (depending on
the type of liquid) by the housing sealing. It is
necessary to check regularly (daily) if liquid is
leaking out of the intermediate flange.
Observe section 10.5 Diaphragm breakage
For maximum safety, we recommend the pump
version with diaphragm leakage detection.
• At least every 12 months or after 4,000 operating hours.
When dosing crystallising liquids, more frequently.
• In the event of a fault.
10.2.1 Cleaning
• If necessary, clean all pump surfaces with a dry and clean
cloth.
10.2.2 Cleaning the valves and diaphragm
• Clean the diaphragm and valves and replace, if necessary (for
stainless-steel valves: inner valve parts).
10.3.2 Unscrewing suction and discharge valves / cleaning
valves
1. Unscrew the suction and discharge valves.
2. Remove the screw part and valve seat with round nose pliers.
3. Dismantle the inner parts.
4. Clean all parts. Replace faulty parts by new ones.
– For plastic DN 8 valve, replace the valve completely.
– For stainless-steel DN 8 valve or DN 20 valve, replace the
inner valve parts.
5. Re-assemble the valve.
6. Replace the O-rings by new ones. Refit the valve.
TM03 6685 4506TM03 6686 4506
Fig. 54 Stainless-steel or plastic DN 20 valve, spring-loaded
as an option
10.3 Cleaning suction and discharge valves
If possible, rinse the dosing head, e.g. by
flushing it with water.
10.3.1 Switching off the pump
1. Switch off the pump and disconnect it from the power supply.
2. Depressurise the system.
3. Take suitable steps to ensure that the returning dosing
medium is safely collected.
Fig. 55 Stainless-steel or plastic DN 20 valve, spring-loaded
as an option
The O-rings must be correctly placed in the
specified groove.
Observe the flow direction (indicated by an arrow
on the valve body)!
Only tighten the valve by hand.
46
10.4 Resetting the diaphragm
Note
Caution
Caution
10.6 Replacing the diaphragm
Warning
Danger of explosion, if dosing liquid has entered
the pump housing!
If the diaphragm is possibly damaged, don’t
connect the pump to the power supply!
If nothing indicates that dosing liquid has entered the pump
housing, the diaphragm must be reset to the back dead point
(end of suction stroke). As the stroke usually ends at the front
dead point, reset the diaphragm as follows:
• Stop the pump (LED lights up red),
• Press the "Up" and "Down" buttons simultaneously.
– The diaphragm is reset.
10.5 Diaphragm breakage
If the diaphragm leaks or is broken, dosing liquid escapes from
the drain opening (fig. 56, 57, pos. H) on the dosing head flange.
In case of diaphragm breakage, the safety diaphragm (pos. S)
and the O-rings (pos. Y) protect the pump housing against
ingress of dosing liquid.
When dosing crystallising liquids the drain opening can be
blocked by crystallisation. If the pump is not taken out of
operation immediately, pressure can build up between the
diaphragm (pos. Q) and the safety diaphragm in the flange (pos.
S) and the O-rings (pos. Y). The pressure can press dosing liquid
through the safety diaphragm or the screw holes into the pump
housing.
Most dosing liquids don’t cause any danger when entering the
pump housing. However a view liquids can cause a chemical
reaction with inner parts of the pump. In the worst case, this
reaction can produce explosive gases in the pump housing.
Warning
Danger of explosion, if dosing liquid has entered
the pump housing!
When operating the pump with a damaged
diaphragm, dosing liquid can enter the pump
housing.
In case of diaphragm breakage, immediately
separate the pump from the power supply!
Make sure that the pump cannot be put back into
operation by accident!
Dismantle the dosing head without connecting
the pump to the power supply. Make sure that no
dosing liquid has entered the pump housing.
Proceed as described in section 10.6 Replacing
the diaphragm.
To avoid any danger resulting from diaphragm breakage, observe
the following:
• Perform regular maintenance.
See section
• Never operate the pump with blocked or soiled drain opening.
– If the drain opening is blocked or soiled, proceed as
described in section
• Never attach a hose to the drain opening. If a hose is attached
to the drain opening, it is impossible to recognise escaping
dosing liquid.
• Take suitable precautions to prevent harm to health and
damage to property from escaping dosing liquid.
• Never operate the pump with damaged or loose dosing head
screws.
10.2 Maintenance intervals.
10.6 Replacing the diaphragm.
Warning
Risk of chemical burns!
Wear protective clothing (gloves and goggles)
when working on the dosing head, connections
or lines!
Do not allow any chemicals to leak from the
pump. Collect and dispose of all chemicals
correctly!
If possible, rinse the dosing head, e.g. by
flushing it with water.
10.6.1 Resetting the diaphragm
If nothing indicates that dosing liquid has entered the pump
housing when replacing the diaphragm, reset the diaphragm as
described in section
10.6.2 Switching off the pump
1. Switch off the pump and disconnect it from the power supply.
2. Depressurise the system.
3. Take suitable steps to ensure that the returning dosing
medium is safely collected.
10.6.3 Replacing the diaphragm
The O-rings must be correctly placed in the
specified groove.
See fig. 56 or 57.
1. Loosen the screws (1q) on the dosing head (2).
2. Remove the dosing head (2) with dosing head disk (2q).
3. Unscrew the diaphragm (Q) counter-clockwise.
4. Make sure that the drain opening (H) is not blocked or soiled.
Clean if necessary.
5. Only for DDI 150-4: loosen the screws (X) on the intermediate
flange (5q) and remove the intermediate flange.
6. Check the safety diaphragm (S) for wear and damage.
Additional check the screws (X) and o-rings (Y) for signs of
contact with medium.
– If dosing liquid has possibly entered the pump housing
proceed as described in section
pump housing
– If nothing indicates that dosing liquid has entered the pump
housing, go on with the next step.
7. Replace the O-rings (Y) by new ones.
8. Only for DDI 150-4: replace the intermediate flange (5q) and
cross-tighten the screws (X).
Torque: 7 Nm (+ 1 Nm).
9. Screw in the new diaphragm (Q).
– For pumps with diaphragm leakage detection: Screw in the
complete diaphragm package.
10. Replace the dosing head (2) with dosing head disk (2q) and
cross-tighten the screws (1q).
Torque: 7 Nm (+ 1 Nm).
11. Restart the dosing pump.
After initial start-up and after each time the
diaphragm is changed, tighten the dosing head
screws.
After approximately 6-10 operating hours or two
days, cross-tighten the dosing head screws
using a torque wrench.
Torque: 7 Nm (+ 1 Nm).
10.4 Resetting the diaphragm
10.6.4 Dosing liquid in the
.
English (GB)
47
English (GB)
Caution
Fig. 56 Replacing the diaphragm for DDI 60-10
10.7 Repair
Warning
The pump housing must only be opened by
personnel authorised by Grundfos!
Repair must only be carried out by authorised
and qualified personnel!
Switch off the pump and disconnect it from the
voltage supply before carrying out maintenance
work and repair!
After consulting Grundfos, please send the pump, together with
the safety declaration completed by a specialist, to Grundfos.
The safety declaration can be found at the end of these
TM06 1274 2014TM06 1275 2014
instructions. It must be copied, completed and attached to the
pump.
The pump must be cleaned prior to dispatch!
If dosing liquid has possibly entered the pump
housing, state that explicitly in the safety
declaration! Observe section 10.5 Diaphragm
breakage.
If the above requirements are not met, Grundfos may refuse to
accept delivery of the pump. The shipping costs will be charged
to the sender.
Fig. 57 Replacing the diaphragm for DDI 150-4
Pos.Components
QDiaphragm (package)
2Dosing head
1qDosing head screws
2qDosing head disk
3qIntermediate ring
5qIntermediate flange
Immediately separate the pump from the power
supply!
Make sure that the pump cannot be put back into
operation by accident!
If dosing liquid has entered the pump housing:
• Send the pump to Grundfos for repair following the instructions
given in section
• If a repair isn’t economically reasonable, dispose of the pump
observing the information in section
10.7 Repair.
12. Disposal.
48
11. Fault finding chart
Note
FaultCauseRemedy
1. Dosing pump does
not run.
2. Pump does not suck
in or dose.
3. Dosing pump does
not suck in.
4. Dosing pump does
not dose.
5. Dosing flow of the
pump is inaccurate.
6. Liquid leaks out of
the hole in the
intermediate flange
between the pump
and the dosing head.
a) Not connected to the mains.Connect the power supply cable.
b) Incorrect mains voltage.Switch off the pump. Check voltage and motor. If the
motor is faulty, return the pump for repair.
c) Electrical failure.Return the pump for repair.
a) Crystalline deposits in the valves.Clean the valves.
b) Empty dosing tank.Fill dosing tank.
c) Air in the suction line and dosing head.Fill dosing head and suction line.
d) Valves not correctly assembled.Assemble the valve inner parts in the right order and
check or possibly correct the flow direction.
a) Leaking suction line.Replace or seal the suction line.
b) Cross-section of the suction line too small or
suction line too long.
c) Clogged suction line.Rinse or replace the suction line.
d) Foot valve covered by sediment.Suspend the suction line from a higher position.
e) Buckled suction line.Install the suction line correctly. Check for damage.
f) Crystalline deposits in the valves. Clean the valves.
g) Diaphragm broken or diaphragm tappet torn out. Replace the diaphragm.
h) Excess counter-pressure.Depressurise the system on the discharge side of the
i) Empty dosing tank.Fill the dosing tank.
a) Viscosity or density of medium too high.Check the installation.
b) Crystalline deposits in the valves.Clean the valves.
c) Valves not correctly assembled.Assemble the inner valve parts in the right order and
d) Injection unit blocked.Check and possibly correct the flow direction, or
e) Incorrect installation of lines and peripheral
equipment.
f) Empty dosing tank.Fill the dosing tank.
g) Sealing elements not chemically resistant.Replace sealing elements.
a) Degassing medium.Check the installation.
b) Parts of the valves covered in dirt or incrusted.Clean the valves.
c) Incorrect dosing flow display.Calibrate.
d) Counter-pressure fluctuations.Install a pressure-loading valve and a pulsation
e) Suction lift fluctuations.Keep the suction level constant.
f) Siphon effect (inlet pressure higher than
counter-pressure).
g) Leaking or porous suction line or discharge line. Replace the suction line or discharge line.
h) Parts in contact with the medium are not
resistant to it.
i) Dosing diaphragm worn (incipient tears).Replace the diaphragm. Also observe the
j) Variation of the dosing medium (density,
viscosity).
k) Overflow.Install or check suction and pressure pulsation
a) A diaphragm leakage has occurred.
Check with Grundfos specification.
pump.
check or possibly correct the flow direction.
remove the obstruction.
Check the lines for free passage and correct
installation.
damper, if necessary.
Install a pressure-loading valve.
Replace with resistant materials.
maintenance instructions.
Check the concentration. Use an agitator, if necessary.
damper, recalculate installation, install a
pressure-loading valve.
Replace the diaphragm.
English (GB)
For further error signals for the control unit, refer to the relevant section.
49
12. Disposal
English (GB)
This product or parts of it must be disposed of in an
environmentally sound way. Use appropriate waste collection
services. If this is not possible, contact the nearest Grundfos
company or service workshop.
Subject to alterations.
50
Appendix1
Note
Safety declaration
Please copy, fill in and sign this sheet and attach it to the pump returned for service.
Fill in this document using english or german language.
Product type (nameplate)
Model number (nameplate)
Dosing medium
Fault description
Please make a circle around the damaged parts.
In the case of an electrical or functional fault, please mark the cabinet.
Appendix
Please describe the error/cause of the error in brief.
Dosing liquid has possibly entered the pump housing.
The pump must not be connected to the power supply! Danger of explosion!
We hereby declare that the pump has been cleaned and is completely free from chemical, biological and radioactive substances.
_____________________________________
Date and signature
_____________________________________
Company stamp
GrA3502
51
Declaration of conformity
Declaration of conformity2
GB: EC declaration of conformity
We, Grundfos, declare under our sole responsibility that the products
DDI 222, to which this declaration relates, are in conformity with these
Council directives on the approximation of the laws of the EC member
states:
ES: Declaración CE de conformidad
Nosotros, Grundfos, declaramos bajo nuestra entera responsabilidad
que los productos DDI 222, a los cuales se refiere esta declaración,
están conformes con las Directivas del Consejo en la aproximación de
las leyes de las Estados Miembros del EM:
IT: Dichiarazione di conformità CE
Grundfos dichiara sotto la sua esclusiva responsabilità che i prodotti
DDI 222, ai quali si riferisce questa dichiarazione, sono conformi alle
seguenti direttive del Consiglio riguardanti il riavvicinamento delle
legislazioni degli Stati membri CE:
PL: Deklaracja zgodności WE
My, Grundfos, oświadczamy z pełną odpowiedzialnością, że nasze
wyroby DDI 222, których deklaracja niniejsza dotyczy, są zgodne z
następującymi wytycznymi Rady d/s ujednolicenia przepisów prawnych
krajów członkowskich WE:
RU: ДекларацияосоответствииЕС
Мы, компания Grundfos, со всей ответственностью заявляем, что
изделия DDI 222, к которым относится настоящая декларация,
соответствуют следующим Директивам Совета Евросоюза об
унификации законодательных предписаний стран-членов ЕС:
SI: ES izjava o skladnosti
V Grundfosu s polno odgovornostjo izjavljamo, da so naši izdelki
DDI 222, na katere se ta izjava nanaša, v skladu z naslednjimi
direktivami Sveta o približevanju zakonodaje za izenačevanje pravnih
predpisov držav članic ES:
TR: EC uygunluk bildirgesi
Grundfos olarak bu beyannameye konu olan DDI 222 ürünlerinin, AB
Üyesi Ülkelerin kanunlarını birbirine yaklaştırma üzerine Konsey
Direktifleriyle uyumlu olduğunun yalnızca bizim sorumluluğumuz altında
olduğunu beyan ederiz:
DE: EG-Konformitätserklärung
Wir, Grundfos, erklären in alleiniger Verantwortung, dass die Produkte
DDI 222, auf die sich diese Erklärung bezieht, mit den folgenden
Richtlinien des Rates zur Angleichung der Rechtsvorschriften der
EU-Mitgliedsstaaten übereinstimmen:
FR: Déclaration de conformité CE
Nous, Grundfos, déclarons sous notre seule responsabilité, que les
produits DDI 222, auxquels se réfère cette déclaration, sont conformes
aux Directives du Conseil concernant le rapprochement des législations
des Etats membres CE relatives aux normes énoncées ci-dessous:
NL: EC overeenkomstigheidsverklaring
Wij, Grundfos, verklaren geheel onder eigen verantwoordelijkheid dat de
producten DDI 222 waarop deze verklaring betrekking heeft, in
overeenstemming zijn met de Richtlijnen van de Raad in zake de
onderlinge aanpassing van de wetgeving van de EG Lidstaten
betreffende:
PT: Declaração de conformidade CE
A Grundfos declara sob sua única responsabilidade que os produtos
DDI 222, aos quais diz respeito esta declaração, estão em conformidade
com as seguintes Directivas do Conselho sobre a aproximação das
legislações dos Estados Membros da CE:
RO: Declaraţie de conformitate CE
Noi, Grundfos, declarăm pe propria răspundere că produsele DDI 222, la
care se referă această declaraţie, sunt în conformitate cu aceste
Directive de Consiliu asupra armonizării legilor Statelor Membre CE:
SE: EG-försäkran om överensstämmelse
Vi, Grundfos, försäkrar under ansvar att produkterna DDI 222, som
omfattas av denna försäkran, är i överensstämmelse med rådets direktiv
om inbördes närmande till EU-medlemsstaternas lagstiftning, avseende:
GRUNDFOS Sarajevo
Trg Heroja 16,
BiH-71000 Sarajevo
Phone: +387 33 713 290
Telefax: +387 33 659 079
e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo Branco,
630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: bulgaria@grundfos.bg