We Grundfos declare under our sole responsibility that the products CUE,
to which this declaration relates, are in conformity with these Council
Directives on the approximation of the laws of the EC Member States:
— Low Voltage Directive (2006/95/EC).
Standard used: EN 61800-5-1: 2003.
— EMC Directive (2004/108/EC).
Standard used: EN 61800-3: 2005.
Bjerringbro, 1st February 2008
Jan Strandgaard
Technical Director
2
CONTENTS
Caution
Note
Page
1.Symbols used in this document3
2.Introduction3
2.1General description3
2.2Applications3
2.3References3
3.Safety and warnings4
3.1Warning4
3.2Safety regulations4
3.3Installation requirements4
3.4Reduced performance under certain conditions4
4.Identification 4
4.1Nameplate4
4.2Packaging label4
5.Mechanical installation5
5.1Reception and storage5
5.2Transportation and unpacking5
5.3Space requirements and air circulation 5
5.4Mounting6
6.Electrical connection7
6.1Electrical protection7
6.2Mains and motor connection7
6.3Connecting the signal terminals9
6.4Connecting the signal relays10
6.5Connecting the MCB 114 sensor input module11
6.6EMC-correct installation11
6.7RFI filters12
6.8Output filters12
7.Operating modes13
8.Control modes13
9.Menu overview14
10.Setting by means of the control panel16
10.1 Control panel16
10.3 Start-up guide 16
10.4 Menu GENERAL20
10.5 Menu OPERATION21
10.6 Menu STATUS 22
10.7 Menu INSTALLATION 23
11.Setting by means of PC Tool E-products30
12.Priority of settings30
13.External control signals30
13.1 Digital inputs30
13.2 External setpoint31
13.3 GENIbus signal 31
13.4 Other bus standards31
14.Maintenance and service31
14.1 Cleaning the CUE31
14.2 Service parts and service kits31
15.Fault finding32
15.1 Warning and alarm list32
15.2 Resetting of alarms32
15.3 Indicator lights32
15.4 Signal relays32
16.Technical data33
16.1 Enclosure33
16.2 Main dimensions and weight33
16.3 Surroundings34
16.4 Terminal tightening torques34
16.5 Cable length34
16.6 Fuses and cable cross-section34
16.7 Inputs and outputs36
16.8 Sound pressure level36
17.Disposal36
1. Symbols used in this document
Warnin g
If these safety instructions are not observed, it
may result in personal injury!
If these safety instructions are not observed, it
may result in malfunction or damage to the
equipment!
Notes or instructions that make the job easier
and ensure safe operation.
2. Introduction
This manual introduces all aspects of your Grundfos CUE
frequency converter in the power range of 110-250 kW.
Always keep this manual close to the CUE.
2.1 General description
CUE is a series of external frequency converters especially
designed for pumps.
Thanks to the start-up guide in the CUE, the installer can quickly
set central parameters and put the CUE into operation.
Connected to a sensor or an external control signal, the CUE will
quickly adapt the pump speed to the actual demand.
2.2 Applications
The CUE series and Grundfos standard pumps are a supplement
to the Grundfos E-pumps range with integrated frequency
converter.
A CUE solution offers the same E-pump functionality
• in the mains voltage or power ranges not covered by the Epump range.
• in applications where an integrated frequency converter is not
desirable or permissible.
2.3 References
Technical documentation for Grundfos CUE:
• The manual contains all information required for putting the
CUE into operation.
• The data booklet contains all technical information about the
construction and applications of the CUE.
• Service instructions contain all required instructions for
dismantling and repairing the frequency converter.
Technical documentation is available on www.grundfos.com >
International website > WebCAPS.
If you have any questions, please contact the nearest Grundfos
company or service workshop.
Warnin g
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
Wait only for shorter time if stated so on the nameplate of the
CUE in question.
3.2 Safety regulations
• The on/off button of the control panel does not disconnect the
CUE from the mains voltage and must therefore not be used
as a safety switch.
• The CUE must be earthed correctly and protected against
indirect contact according to national regulations.
• The leakage current to earth exceeds 3.5 mA.
• Enclosure class IP20/21 must not be installed freely
accessible, but only in a panel.
• Enclosure class IP54/55 must not be installed outdoors
without additional protection against water and the sun.
• Always observe national and local regulations as to cable
cross-section, short-circuit protection and overcurrent
protection.
Warnin g
At altitudes above 2000 m, PELV cannot be met.
PELV = Protective Extra Low Voltage.
At low air pressure, the cooling capacity of air is reduced, and the
CUE automatically reduces the performance to prevent overload.
It may be necessary to select a CUE with a higher performance.
3.4.2 Reduction in connection with long motor cables
The maximum cable length for the CUE is 300 m for unscreened
and 150 m for screened cables. In case of longer cables, contact
Grundfos.
The CUE is designed for a motor cable with a maximum crosssection as stated in section 16.6 Fuses and cable cross-section.
4. Identification
4.1 Nameplate
The CUE can be identified by means of the nameplate. An
example is shown below.
Prod. no: 12345678 S
IN: 3x380-500 V 50/60Hz 3.7A
Listed 76X1 E134261 Ind. Contr. Eq.
See manual for prefuse
G234
MADE IN DENMARK
CAUTION:
3.3 Installation requirements
The general safety necessitates special considerations as to
these aspects:
• fuses and switches for overcurrent and short-circuit protection
• selection of cables (mains current, motor, load distribut ion and
relay)
• net configuration (IT, TN, earthing)
• safety on connecting inputs and outputs (PELV).
3.3.1 IT mains
Warnin g
Do not connect 380-500 V CUE frequency
converters to mains supplies with a voltage
between phase and earth of more than 440 V.
In connection with IT mains and earthed delta mains, the mains
voltage may exceed 440 V between phase and earth.
3.3.2 Aggressive environment
The CUE should not be installed in an
The CUE contains a large number of mechanical and electronic
components. They are all vulnerable to environmental effects.
3.4 Reduced performance under c ertain conditions
The CUE will reduce its performance under these conditions:
• low air pressure (at high altitude)
• long motor cables.
The required measures are described in the next two sections.
environment where the air contains liquids,
particles or gases which may affect and damage
the electronic components.
4
4
CHARGE RESIDUELLE,ATTENDRE
4
Fig. 1 Example of nameplate
TextDescription
T/C:
CUE (product name)
202P1M2... (internal code)
Prod.no:Product number: 12345678
Serial number: 123456G234
S/N:
The last three digits indicate the production date:
23 is the week, and 4 is the year 2004
1.5 kWTypical shaft power on the motor
IN:
Supply voltage, frequency and maximum input
current
Motor voltage, frequency and maximum output
OUT:
current. The maximum output frequency usually
depends on the pump type.
CHASSIS/
IP20
Enclosure class
Tamb.Maximum ambient temperature
4.2 Packaging label
The CUE can also be identified by means of the label on the
packaging.
TM04 3272 4808
5. Mechanical installation
Note
Min. 225
Min. 225
399
526
The individual CUE cabinet sizes are characterised by their
enclosures. The table in section 16.1 shows the relationship of
enclosure class and enclosure type.
5.1 Reception and storage
Check on receipt that the packaging is intact, and the unit is
complete. In case of damage during transport, contact the
transport company to complain.
Note that the CUE is delivered in a packaging which is not
suitable for outdoor storage.
5.2 Transportation and unpacking
The CUE must only be unpacked at the installation sit e to preven t
damage during the transport to the site.
Remove the cardboard box, and keep the CUE on the pallet as
long as possible.
The packaging contains accessory bag(s), documentation and
the unit itself.
The cardboard box has a drilling template for the
mounting holes. See fig. 2.
5.3 Space requirements and air circulation
CUE units can be mounted si de by side, but as a sufficient air
circulation is required for c ooling these requirements must be
met:
• Sufficient free space above and below the C UE to allow airflow
and cable connection. See fig. 4.
• Ambient temperature up to 45 °C.
Fig. 2 CUE packaging with drilling template
5.2.1 Lifting the CUE
Always lift the CUE using the lifting holes. Use a bar to avoid
bending the lifting holes. See fig. 3.
Fig. 3 Recommended lifting method
TM03 9898 4607TM03 9897 4607
Fig. 4 Airflow direction and required space for cooling [mm]
TM03 9893 4607TM03 9896 4607
Furthermore, there must be sufficient space in front of the CUE
for opening the door of the CUE. See fig. 5.
Fig. 5 Free space in front of the CUE [mm]
5
5.4 Mounting
Caution
Note
b
a
a
b
Caution
Note
Back
Front
5.4.1 Mounting the drip shield
To comply with the IP21 rating, a separate drip shield is to be
fitted:
1. Remove the two screws. See fig. 6.
2. Fit the drip shield.
3. Fit and tighten the screws to 5.6 Nm.
Fig. 6 Fitting the drip shield
5.4.3 Mounting on the floor
Warnin g
The CUE is top-heavy and may fall over if the
pedestal is not anchored to the floor.
The user is responsible for mounting the CUE
securely on a firm surface.
See the pedestal kit instructions for further
information.
By means of a pedestal (option), the CUE can also be mounted
on the floor.
1. Mark the mounting holes on the floor. See fig. 8.
2. Drill the holes.
3. Mount the pedestal on the floor.
4. Mount the CUE on the pedestal using the enclosed screws.
See fig. 9.
TM03 9901 4607
5.4.2 Mounting on the wall
The user is responsible for mounting the CUE
securely on a firm surface.
See the main dimensions and weights in section
16.2.
1. Mark the mounting holes on the wall using the drilling
template. See fig. 2.
2. Drill the holes. See fig. 7.
3. Fit the screws at the bottom, but leave loose. Lift the CUE up
on the screws. Move the CUE against the wall, and fit the
screws at the top. Tighten all four screws. See fig. 3.
TM03 9923 4607TM03 9895 4607
Fig. 8 Drilling template for pedestal [mm]
Fig. 7 Drilling of holes in the wall
6
TM03 8860 2607
Fig. 9 CUE on a pedestal
6. Electrical connection
Caution
Caution
ELCB
ELCB
Mains
Motor
Warnin g
The owner or installer is responsible for ensuring
correct earthing and protection according to
national and local standards.
Warnin g
Before making any work on the CUE, the mains
supply and other voltage inputs must be
switched off for at least as long as stated in
section 3. Safety and warnings.
Fig. 10 Example of three-phase mains connection of the CUE
with mains switch, back-up fuses and additional
protection
6.1 Electrical protection
6.1.1 Protection against electric shock, indirect contact
6.1.5 Protection against overcurrent
The CUE has an internal overcurrent protection for overload
protection on the motor output.
6.1.6 Protection against mains voltage transients
The CUE is protected against mains voltage transients according
to EN 61800-3, second environment.
6.2 Mains and motor connection
The supply voltage and frequency are marked on the CUE
nameplate. Make sure that the CUE is suitable for the power
supply of the installation site.
6.2.1 Mains switch
A mains switch can be installed before the CUE according to local
regulations. See fig. 10.
6.2.2 Wiring diagram
The wires in the terminal box must be as short as possible.
Excepted from this is the earth conductor which must be so long
that it is the last one to be disconnected in case the cable is
TM03 8525 1807
inadvertently pulled out of the cable entry.
Warnin g
The CUE must be earthed correctly and protected
against indirect contact according to national
regulations.
The leakage current to earth exceeds 3.5 mA, and
a reinforced earth connection is required.
Protective conductors must always have a yellow/green (PE) or
yellow/green/blue (PEN) colour marking.
Instructions according to EN IEC 61800-5-1:
• The CUE must be stationary, installed permanently and
connected permanently to the mains supply.
• The earth connection must be carried out with duplicate
protective conductors.
6.1.2 Protection against short-circuit, fuses
The CUE and the supply system must be protected against shortcircuit.
Grundfos demands that the back-up fuses mentioned in section
16.6 are used for protection against short-circuit.
The CUE offers complete short-circuit protection in case of a
short-circuit on the motor output.
6.1.3 Additional protection
The leakage current to earth exceeds 3.5 mA.
If the CUE is connected to an electrical installation where an
earth leakage circuit breaker (ELCB) is used as additional
protection, the circuit breaker must be of a type marked with the
following symbols:
Cables are connected through the gland plate from the bottom.
The gland plate must be fitted to the CUE to ensure the specified
protection degree as well as to ensure sufficient cooling.
Drill holes in the marked areas. See fig. 12.
TM03 8799 2507
The circuit breaker is type B.
The total leakage current of all the electrical equipment in the
installation must be taken into account.
The leakage current from the CUE in normal operation can be
seen in section 16.7.1 Mains supply (L1, L2, L3).
During start and in asymmetrical supply systems, the leakage
current can be higher than normal and may cause the ELCB to
trip.
6.1.4 Motor protection
The motor requires no external motor protection. The CUE
protects the motor against thermal overloading and blocking.
TM03 9900 4607
Fig. 12 CUE viewed from the bottom
7
6.2.4 Motor connection
Caution
Caution
Mains:
95 (PE)
Motor:
99 (PE)
Mains:
91 (L1)
92 (L2)
93 (L3)
Motor:
96 (U)
97 (V)
98 (W)
MainsMotor
For information about enclosure, see table in section 16.1.
The motor cable must be screened for the CUE to
meet EMC requirements.
1. Connect the earth conductor to terminal 99 (PE). See fig. 14.
2. Connect the motor conductors to the terminals 96 (U), 97 (V),
98 (W), see fig. 15.
3. Fix the screened cable with a cable clamp.
4. Fit the EMC metal cover to ensure best EMC performance
before connecting the mains cable. See fig. 13.
TM03 9967 4707TM03 9899 4607
Fig. 15 Mains and motor connection
Fig. 13 Fitting the EMC metal cover
6.2.5 Mains connection
Check that mains voltage and frequency
correspond to the values on the nameplate of the
CUE and the motor.
1. Connect the earth conductor to terminal 95 (PE). See fig. 14.
2. Connect the mains conductors to the terminals 91 (L1),
92 (L2), 93 (L3), see fig. 15.
3. Fix the mains cable with a cable clamp.
6.2.6 Terminal location
Take the following terminal positions into consideration when you
design the cable connection. See figs 14 to 16.
TM03 9894 4607
Fig. 16 Position of mains and motor terminals, side view
Fig. 14 Earth connection
8
TM03 9905 4607
6.3 Connecting the signal terminals
Caution
Note
Note
+24 V out
+24 V out
DI 2
DI 3
DI 4
GND
GND
AO 1
+10 V out
Ext. setpoint
Sensor 1
GND
RS-485 GND Y
RS-485 A
RS-485 B
0/4-20 mA
1 K
0-20 mA
0/4-20 mA
0-10 V0-10 V
Start/stop
Terminals
53 and 54:
See section
6.3.5
Start/stop
GND
Signal terminals
Signal relays
As a precaution, signal cables must be separated
from other groups by reinforced insulation in
their entire lengths.
If no external on/off switch is connected, shortcircuit terminals 18 and 20 using a short wire.
Connect the signal cables according to the guidelines for good
practice to ensure EMC-correct installation. See section
6.6 EMC-correct installation.
• Use screened signal cables with a conductor cross-section of
min. 0.5 mm
• Use a 3-conductor screened bus cable in new systems.
6.3.1 Wiring diagram, signal terminals
2
and max. 1.5 mm2.
6.3.2 Minimum connection, signal terminals
Operation is only possible when the terminals 18 and 20 are
connected, for instance by means of an external o n/off switch or a
short wire.
TM03 9057 3207TM03 9902 4607TM03 9026 2807
Fig. 18 Required minimum connection, signal terminals
6.3.3 Access to signal terminals
All terminals for signal cables are located beneath the control
panel and can be accessed by opening the door of the CUE.
See fig. 19.
Terminal TypeFunction
12+24 V outSupply to sensor
13+24 V outAdditional supply
18DI 1Digital input, start/stop
19DI 2Digital input, programmable
20GNDCommon frame for digital inputs
32DI 3Digital input, programmable
33DI 4Digital input, programmable
39GNDFrame for analog output
42AO 1Analog output, 0-20 mA
50+10 V outSupply to pote ntio me ter
53AI 1External setpoint, 0-10 V/4-20 mA
54AI 2Sensor input, sensor 1, 0/4-20 mA
55GNDCommon frame for analog inputs
61RS-485 GND Y GENIbus, GND
68RS-485 AGENIbus, signal A (+)
69RS-485 BGENIbus, signal B (-)
Terminals 27, 29 and 37 are not used.
Fig. 17 Wiring diagram, signal terminals
The RS-485 screen must be connected to frame.
TM03 8800 2507
Fig. 19 Signal cable routing
6.3.4 Fitting the conductor
1. Remove the insulation at a length of 9-10 mm.
2. Insert a screwdriver with a tip of maximum 0.4 x 2.5 mm into
the square hole.
3. Insert the conductor into the corresponding round hole.
Remove the screwdriver. The conductor is now fixed in the
terminal.
Fig. 20 Fitting the conductor into the signal terminal
9
6.3.5 Setting the analog inputs, terminals 53 and 54
Note
UI
A53
UI
A54
Bus Ter = ON
Caution
OFFON
BUS TER
C 1
NC 1
NO 1
NC 2
NO 2
C2
The contacts A53 and A54 are positioned behind the control
panel and used for setting the signal type of the two analog
inputs.
The factory setting of the inputs is voltage signal "U".
If a 0/4-20 mA sensor is connected to terminal 54,
the input must be set to current signal "I".
Switch off the power supply before setting the
A54.
Remove the control panel to set the contact. See fig. 21.
Fig. 21 Setting contact A54 to current signal "I"
Remove the control panel to set the contact. See fig. 23.
Fig. 23 Setting the termination contact to "ON"
6.4 Connecting the signal relays
As a precaution, signal cables must be separated
from other groups by reinforced insulation in
TM03 9104 3407TM03 9005 2807
their entire lengths.
TM03 9006 2807
6.3.6 RS-485 GENIbus network connection
One or more CUE units can be connected to a control unit via
GENIbus. See the example in fig. 22.
Fig. 22 Example of an RS-485 GENIbus network
The reference potential, GND, for RS-485 (Y) communication
must be connected to terminal 61.
If more than one CUE unit is connected to a GENIbus network,
the termination contact of the last CUE must be set to "ON"
(termination of the RS-485 port).
The factory setting of the termination contact is "OFF"
(not terminated).
TM03 8801 2507
Fig. 24 Terminals for signal relays in normal state
(not activated)
TerminalFunction
C 1C 2Common
NO 1NO 2Normally open contact
NC 1NC 2Normally closed contact
10
6.5 Connecting the MCB 114 sensor input module
CUEController
CUEController
The MCB 1 14 is a n option o f fering a dditional analog input s f or the
CUE.
6.5.1 Configuration of the MCB 114
The MCB 114 is equipped with three analog inputs for these
sensors:
• One additional sensor 0/4-20 mA. See section 10.7.13 Sensor 2 (3.16).
• Two Pt100/Pt1000 temperature sensors for measurement of
motor bearing temperature or an alternative temperature, such
as liquid temperature. See sections 10.7.18 Temperature sensor 1 (3.21) and 10.7.19 Temperature sensor 2 (3.22).
When the MCB 114 has been in stalle d, the CUE will automatically
detect if the sensor is Pt100 or Pt1000 when it is switched on.
6.5.2 Wiring diagram, MCB 114
GND
WIRE
TEMP
GND
TEMP
WIRE
GND
12111
0
VDO
198765432
I IN
6.6 EMC-correct installation
This section gives guidelines for good practice when installing the
CUE. Follow these guidelines to meet EN 61800-3, first
environment.
• Use only motor and signal cables with a braided metal screen
in applications without output filter.
• There are no special requirements to supply cables, apart
from local requirements.
• Leave the screen as close to the connecting terminals as
possible. See fig. 26.
• Avoid terminating the screen by twisting the ends. See fig. 27.
Use cable clamps or EMC screwed cable entries instead.
• Connect the screen to frame at both ends for both motor and
signal cables. See fig. 28. If the controller has no cable
clamps, connect only the screen to the CUE. See fig. 29.
• Avoid unscreened motor and signal cables in electrical
cabinets with frequency converters.
• Make the motor cable as short as possible in applications
without output filter to limit the noise level and minimise
leakage currents.
• Screws for frame connections must always be tightened
whether a cable is connected or not.
• Keep main cables, motor cables and signal cables separated
in the installation, if possibl e.
Other installation methods may give similar EMC results if the
above guidelines for good practice are followed.
+
-
+
Fig. 25 Wiring di agra m, MCB 114
Terminal TypeFunction
1 (VDO)+24 V out Supply to sensor
2 (I IN)AI 3Sensor 2, 0/4-20 mA
3 (GND)GNDCommon frame for analog input
4 (TEMP)
5 (WIRE)
6 (GND)GNDCommon frame for temperature sensor 1
7 (TEMP)
8 (WIRE)
9 (GND)GNDCommon frame for temperature sensor 2
Terminals 10, 11 and 12 are not used.
AI 4Temperature sensor 1, Pt100/Pt1000
AI 5Temperature sensor 2, Pt100/Pt1000
TM04 3273 3908
Fig. 26 Example of stripped cable with screen
Fig. 27 Do not twist the screen ends
Fig. 28 Example of connection of a 3-conductor bus cable with
Fig. 29 Example of connection of a 3-conductor bus cable with
screen connected at the CUE (controller with no cable
clamps)
11
6.7 RFI filters
Unscreened cable
screened motor cable
M
CUE
Unscreened cable
screened motor
cable
M
CUEFilter
M
CUE and filter close to well
CUE
Screened
cable
Unscreened
drop cable
Unscreened
cable
Filter
CUE
Screened
cable
* Both ends of the screened cable between filter and
connection box must be connected to earth
Connection
box *
M
Screened
cable
Unscreened
drop cable
Unscreened
cable
Filter
To meet the EMC requirements, the CUE comes with the
following types of built-in radio frequency interference filter (RFI).
VoltageTypical shaft power P2RFI filter type
Figures 30 and 31 show installations with and without filter and
where to use screened and unscreened cable.
3 x 380-500 V110-250 kWC2
3 x 525-690 V110-250 kWC3
Description of RFI filter types
For use in domestic and industrial areas, connected
permanently to the mains supply. In domestic areas,
C2:
special care should be taken regarding EMC-correct
installation.
For use in industrial areas with own low-voltage
C3:
transformer.
RFI filter types are according to EN 61800-3.
6.7.1 Equipment of category C2
• In a domestic environment this product may cause radio
interference in which case supplementary mitigation measures
may be required.
6.7.2 Equipment of category C3
• This type of power drive system (PDS) is not intended to be
used on a low-voltage public network which supplies domestic
premises.
• Radio frequency interference is expected if used on such a
network.
6.8 Output filters
Output filters are used for reducing the voltage stress on the
motor windings and the stress on the motor insulation system as
well as for decreasing acoustic noise from the frequency
converter-driven motor.
Two types of output filter are available as accessories for the
CUE:
Fig. 31 Example of installation with filter. The cable between
the CUE and filter must be short.
Fig. 32 Submersible pump without connection box
Fig. 33 Submersible pump with connection box and screened
cable
Pump type
SP, BM, BMB with
380 V motor and up
Other pumps, noise
reduction
Other pumps, higher
noise reduction
Pumps with 690 V
motor
Typical shaft
power P2
110 kW and up0-150 m150-300 m
110 kW and up0-150 m150-300 m
110 kW and up
All–0-300 m
The lengths stated apply to the motor cable.
12
dU/dt
filter
–0-300 m
Sine-wave
filter
7. Operating modes
Min.
Max.
CUE
Δp
CUE
Δp
CUE
Δp
CUE
p
CUE
p
CUE
L
CUE
L
CUE
Q
CUE
t
The following operating modes are set on the control panel in
menu OPERATION, display 1.2. See section 10.5.2.
Operating mode Description
Normal
Stop
Min.The pump is running at minimum speed
Max.The pump is running at maximum speed
Example: Max. curve operation can for instance be used in
connection with venting the pump during installation.
Example: Min. curve operation can for instance be used in
periods with a very small flow requirement.
The pump is running in the control mode
selected
The pump has been stopped (green indicator
light is flashing)
Min. and max. curves.
The pump speed is kept at a given
set value for minimum and maximu m
speed, respectively.
TM03 8813 2507
8.0.2 Controlled operation (closed loop)
TM03 8475 1607
TM03 8476 1607
TM03 8476 1607
Proportional
differential
pressure.
The differential
pressure is reduced
at falling flow rate
and increased at
rising flow rate.
TM03 8804 2507
Constant
differential
pressure, pump.
The differential
pressure is kept
constant,
independently of
the flow rate.
TM03 8804 2507
Constant
differential
pressure, system.
The differential
pressure is kept
constant,
independently of
the flow rate.
TM03 8806 2507
8. Control modes
The control mode is set on the control panel in menu
INSTALLATION, display 3.1. See section 10. 7.1 .
There are two basic control modes:
• Uncontrolled operation (open loop).
• Controlled operation (closed loop) with a sensor connected.
See sections 8.0.1 and 8.0.2.
8.0.1 Uncontrolled operation (open loop)
Constant curve.
The speed is kept at a set value in
the range between the min. and max.
curve.
The setpoint is set in %
corresponding to the required speed.
TM03 8479 1607
Example: Operation on constant curve can for instance be used
for pumps with no sensor connected.
Example: Typically used in connection with an overall control
system such as the MPC or another external controller.
Constant pressure.
The pressure is
kept constant,
independently of
the flow rate.
TM03 8476 1607
TM03 8805 2507
Constant pressure
with stop function.
The outlet pressure
is kept constant at
high flow rate. On/
off operation at low
TM03 8477 1607
flow rate.
TM03 8807 2507
Constant level.
The liquid level is
kept constant,
independently of
the flow rate.
TM03 8482 1607
TM03 8808 2607
Constant level with
stop function.
The liquid level is
kept constant at
high flow rate.
On/off operation at
TM03 8482 1607
low flow rate.
TM03 8809 2607
Constant flow rate.
The flow rate is
kept constant,
independently of
the head.
TM03 8478 1607
TM03 8810 2507
Constant
temperature.
The liquid
temperature is kept
constant,
independently of
TM03 8482 1607
the flow rate.
TM03 8811 2507
13
9. Menu overview
Automatic or manual
setting of the direction
of rotation
START-UP GUIDE0. GENERAL1. OPERATION
0.11.1
1/160.21.2
2/160.241.3
3/168/161.4
4/169/161.5-1.9
5/1610/16-14/16
6/1615/161.10-1.14
7/1616/16
Fig. 34 Menu overview
Menu structure
The CUE has a start-up guide, which is started at the first startup. After the start-up guide, the CUE has a menu structure
divided into four main menus:
1. GENERAL gives access to the start-up guide for the general
setting of the CUE.
2. OPERATION enables the setting of setpoint, selection of
operating mode and resetting of alarms. It is also possible to
see the latest five warnings and alarms.
3. STATUS shows the status of the CUE and the pump. It is not
possible to change or set values.
4. INSTALLATION gives access to all parameters. Here a
detailed setting of the CUE can be made.
14
2. STATUS3. INSTALLATION
2.12.103.13.12
2.22.113.23.13
2.32.123.33.15
2.42.133.3A3.16
2.52.143.43.17
2.62.153.53.18
2.72.163.63.19
2.82.173.73.20
2.93.83.21
3.93.22
3.103.23
3.113.24
15
10. Setting by means of the control panel
On/
Off
CUE
On/
Off
On
Off
Alarm
On/
Off
+
-
>
>
>
Note
Display name
Current display / total number
Value field
Display name
Display number, menu name
Value field
10.1 Control panel
Warnin g
The on/off button on the control panel does not
disconnect the CUE from the mains voltage and
must therefore not be used as a safety switch.
On/
The control panel is used for local setting of the CUE. The
functions available depend on the pump family connected to the
CUE.
The on/off button has the highest priority. In "of f"
condition, pump operation is not possible.
CU
On/
Adjusting the display contrast
Press OK and + for darker display.
Press OK and – for brighter display.
Indicator lights
The operating condition of the pump is indicated by the indicator
lights on the front of the control panel. See fig. 35.
The table show the function of the indicator lights.
Indicator
light
On (green)
Off (orange)
Alarm (red)Indicates an alarm or a warning.
Displays, general terms
Figures 36 and 37 shows the general terms of the display.
Function
The pump is running or has been stopped by a
stop function.
If flashing, the pump has been stopped by the
user (CUE menu), external start/stop or bus.
The pump has been stopped with the on/off
button.
+
>
On
>
OK
>
-
>
Alarm
Fig. 35 Control panel of the CUE
Editing buttons
ButtonFunction
On/
OK
Navigating buttons
ButtonFunction
>
The editing buttons of the control panel can be set to these
values:
•Active
• Not active
When set to Not active (locked), the editing buttons do not
function. It is only possible to navigate in the menus and read
values.
Activate or deactivate the buttons by pressing the arrow up and
arrow down buttons simultaneously for 3 seconds.
Makes the pump ready for operation/starts and
stops the pump.
Saves changed values, resets alarms and expands
the value field.
Changes values in the value field.
Navigates from one menu to another. When the
menu is changed, the display shown will always be
the top display of the new menu.
Navigates up and down in the individual menu.
Fig. 36 Example of display in the start-up guide
TM03 8719 2507
Fig. 37 Example of display in the user menu
10.2 Back to factory setting
Follow this procedure to get back to the factory setting:
1. Switch off the power supply to the CUE.
2. Press On/Off, OK and + while switching on the power supply.
The CUE will reset all parameters to factory settings. The display
will turn on when the reset is com pleted .
10.3 Start-up guide
Check that equipm ent co nnec ted is read y for
start-up, and that the CUE has been connected to
supply voltage.
Have nameplate data for motor, pump and CUE at
hand.
Use the start-up guide for the general setting of the CUE
including the setting of the correct direction of rotation.
The start-up guide is started the first time when the CUE is
connected to supply voltage. It can be restarted in menu
GENERAL. Please note that in this case all previous settings will
be erased.
Bulleted lists show possible settings. Factory settings are shown
in bold.
16
10.3.1 Welcoming display
10.3.6 Supply voltage (5/16)
• Press OK. You will now be guided through the start-up guide.
10.3.2 Language (1/16)
Select the language to be used in the display:
•English UK
• English US
•German
• French
•Italian
• Spanish
• Portuguese
• Greek
•Dutch
• Swedish
• Finnish
•Danish
•Polish
•Russian
• Hungarian
• Czech
• Chinese
• Japanese
• Korean.
10.3.3 Units (2/16)
Select the units to be used in the display:
• SI: m, kW, bar...
• US: ft, HP, psi...
10.3.4 Pump family (3/16)
Select supply voltage according to the rated supply voltage of the
installation site.
Unit 1 x 200-240 V: *
• 1 x 200 V
• 1 x 208 V
• 1 x 220 V
• 1 x 230 V
• 1 x 240 V.
Unit 3 x 200-240 V:
• 3 x 200 V
• 3 x 208 V
• 3 x 220 V
• 3 x 230 V
• 3 x 240 V.
Unit 3 x 380-500 V:
• 3 x 380 V
• 3 x 400 V
• 3 x 415 V
• 3 x 440 V
• 3 x 460 V
• 3 x 500 V.
Unit 3 x 525-600 V:
• 3 x 575 V.
Unit 3 x 525-690 V:
• 3 x 575 V
• 3 x 690 V.
* Single-phase input - three-phase output.
The setting range depends on the CUE type, and the factory
setting corresponds to the rated supply voltage of the CUE.
10.3.7 Max. motor current (6/16)
Set the maximum motor current according to the motor
nameplate:
• 0-999 A
The setting range depends on the CUE type, and the factory
setting corresponds to a typical motor current at the motor power
selected.
10.3.8 Speed (7/16)
Select pump family according to the pump nameplate:
• CR, CRI, CRN, CRT
• SP, SP-G, SP-NE
•...
Select "Other" if the pump family is not on the list.
10.3.5 Rated motor power (4/16)
Set the rated motor power, P2, according to the motor nameplate:
• 0.55-90 kW
The setting range is size-related, and the factory setting
corresponds to the rated power of the CUE.
Set the rated speed according to the pump nameplate:
• 0-9999 min
-1
The factory setting depends on previous selections. Based on the
set rated speed, the CUE will automatically set the motor
frequency to 50 or 60 Hz.
10.3.9 Frequency (7A/16)
This display appears only if manual entering of the frequency is
required.
Set the frequency according to the motor nameplate:
• 40-200 Hz
The factory setting depends on previous selections.
17
10.3.10 Control mode (8/16)
Note
Select the desired control mode. See section 10.7.1.
• Open loop
• Constant pressure
• Constant differential pressure
• Proportional differential pressure
• Constant flow rate
• Constant temperature
• Constant level
• Constant other value.
The possible settings and the factory setting depend on the pump
family.
The CUE will give an alarm if the control mode selected requires
a sensor and no sensor has been installed. To continue the
setting without a sensor, select "Open loop", and proceed. When
a sensor has been connected, set the sensor and co ntrol mode in
menu INSTALLATION.
10.3.11 Rated flow rate (8A/16)
Constant pressure:
• 0-2.5 bar
•0-4 bar
•0-6 bar
• 0-10 bar
• 0-16 bar
Constant flow rate:
3
•1-5 m
• 2-10 m
• 6-30 m
• 15-75 m
/h
3
/h
3
/h
3
/h
•Other.
• 0-25 bar
• Other.
Constant temperature:
• –25 to 25 °C
• 0 to 25 °C
• 50 to 100 °C
• 0 to 150 °C
• Other.
Constant level:
• 0-0.1 bar
•0-1 bar
• 0-2.5 bar
•0-6 bar
• 0-10 bar
•Other.
If the control mode selected is "Constant other value", or if the
measuring range selected is "Other", the sensor must be set
according to the next section, display 9A/16.
10.3.14 Another sensor connected to terminal 54 (9A/16)
This display appears only if the control mode selected is
proportional differential pressure.
Set the rated flow rate according to the pump nameplate:
3
• 1-6550 m
/h
10.3.12 Rated head (8B/16)
This display only appears if the control mode selected is
proportional differential pressure.
Set the rated head according to the pump nameplate:
• 1-999 m
10.3.13 Sensor connected to terminal 54 (9/16)
This display only appears when the control mode "Constant other
value" or the measuring range "Other" has been selected in
display 9/16.
• Sensor output signal:
0-20 mA
4-20 mA.
• Unit of measurement of sensor:
bar, mbar, m, kPa, psi, ft, m
gal/h, gal/m, gal/s, ft
3
3
/h, m3/min, m3/s, l/h, l/min, l/s,
/min, ft3/s,°C, °F, %.
• Sensor measuring range.
The measuring range depends on the sensor connected and the
measuring unit selected.
10.3.15 Priming and venting (10/16)
See the installation and operating instructions of the pump.
The general setting of the CUE is now completed, and the start-
up guide is ready for setting the direction of rotation:
• Press OK to go on to automatic or manual setting of the
direction of rotation.
10.3.16 Automatic setting of the direction of rotation (11/16)
Set the measuring range of the connected sensor with a signal
range of 4-20 mA. The measuring range depends on the control
mode selected:
Proportional differential pressure:
• 0-0.6 bar
•0-1 bar
• 0-1.6 bar
• 0-2.5 bar
•0-4 bar
•0-6 bar
• 0-10 bar
Constant differential pressure:
• 0-0.6 bar
• 0-1.6 bar
• 0-2.5 bar
•0-4 bar
•0-6 bar
• 0-10 bar
•Other.
•Other.
18
Warnin g
During the test, the pump will run for a short
time. Ensure no personnel or equipment is in
danger!
Before setting the direction of rotation, the CUE
will make an automatic motor adaptation of
certain pump types. This will take a few minutes.
The adaptation is carried out during standstill.
The CUE automatically tests and sets the correct direction of
rotation without changing the cable connections.
This test is not suitable for certain pump types and will in certain
cases not be able to determine for certainty the correct direction
of rotation. In these cases, the CUE changes over to manual
setting where the direction of rotation is determined on the basis
of the installer’s observations.
Information displays.
• Press OK to continue.
10.3.18 General settings are completed (16/16)
• Press OK to make the pump ready for operation or start the
pump in the operating mode Normal. Then display 1.1 of menu
OPERATION will appear.
10.3.19 Manual setting when the direction of rotation is
visible (13/16)
It must be possible to observe the motor fan or shaft.
Information displays.
• Press OK to continue.
The pump starts after 10 seconds.
It is possible to interrupt the test and return to the previous
display.
The pump runs with both directions of rotation and stops
automatically.
It is possible to interrupt the test, stop the pump and go to manual
setting of the direction of rotation.
The correct direction of
rotation has now been set.
• Press OK to set the
setpoint. See Setpoint (15/
16) on page 19.
10.3.17 Setpoint (15/16)
The automatic setting of the
direction of rotation has failed.
• Press OK to go to manual
setting of the direction of
rotation.
The pump starts after 10 seconds.
It is possible to interrupt the test and return to the previous
display.
The pressure will be shown during the test if a pressure sensor is
connected. The motor current is always shown during the test.
State if the direction of rotation is correct.
•Yes•No
Set the setpoint according to the control mode and sensor
selected.
The correct direction of
rotation has now been set.
• Press OK to set the
setpoint. See Setpoint (15/
16) on page 19.
The direction of rotation is not
correct.
• Press OK to repeat the test
with the opposite direction
of rotation.
19
10.3.20 Manual setting when the direction of rotation is not
Note
Note
visible (13/16)
It must be possible to observe the head or flow rate.
Information displays.
• Press OK to continue.
The pump starts after 10 seconds.
It is possible to interrupt the test and return to the previous
display.
The second test is completed.
Write down the pressure and/or flow rate, and state which test
gave the highest pump performance:
• First test
• Second test
• Make new test.
The correct direction of rotation has now been set.
• Press OK to set the setpoint. See Setpoint (15/16) on page 19.
10.4 Menu GENERAL
If the start-up guide is started, all previous
settings will be erased!
The start-up guide must be carried out on a cold
motor!
Repeating the start-up guide may lead to a
heating of the motor.
The menu makes it possible to return to the start-up guide, which
is usually only used dur ing t he firs t start-u p of th e CUE.
10.4.1 Return to start-up guide (0.1)
The pressure will be shown during the test if a pressure sensor is
connected. The motor current is always shown during the test.
The first test is completed.
• Write down the pressure and/or flow rate, and press OK to
continue the manual test with the opposite direction of
rotation.
The pump starts after 10 seconds.
It is possible to interrupt the test and return to the previous
display.
State your choice:
•Yes
•No.
If Yes is selected, all settings will be erased, and the entire startup guide must be completed.
10.4.2 Type code change (0.2)
This display is for service use only.
The pressure will be shown during the test if a pressure sensor is
connected. The motor current is always shown during the test.
20
10.4.3 Copy of settings
Alarm (1.3)
It is possible to copy the settings of a CUE and reuse them in
another one. Options:
• No copy.
• to CUE (copies the settings of the CUE).
• to control panel (copies the settings to another CUE).
The CUE units must have the same firmware version. See section
10.6.16 Firmware version (2.16).
10.5 Menu OPERATION
10.5.1 Setpoint (1.1)
Setpoint set
Actual setpoint
Actual value
Set the setpoint in units of the feedback sensor.
In control mode Open loop, the setpoint is set in % of the
maximum performance. The setting range will lie between the
min. and max. curves. See fig. 44.
In all other control modes except proportional differential
pressure, the setting range is equal to the sensor measuring
range. See fig. 45.
In control mode Proportional differential pressure, the setting
range is equal to 25 % to 90 % of max. head. See fig. 46.
If the pump is connected to an external setpoint signal, the value
in this display will be the maximum value of the external setpoint
signal. See section 13.2 External setpoint.
10.5.2 Operating mode (1.2)
In case of an alarm, the cause will appear in the display.
See section 15.1 Warning and alarm list.
Warning (1.4)
In case of warning, the cause will appear in the display.
See section 15.1 Warning and alarm list.
10.5.4 Fault log
For both fault types, alarm and warning, the CUE has a log
function.
Alarm log (1.5-1.9)
In case of an "alarm", the last five alarm indications will appear in
the alarm log. "Alarm log 1" shows the latest alarm, "Alarm log 2"
shows the latest alarm but one, etc.
The display shows three pieces of information:
• the alarm indication
• the alarm code
• the number of minutes the pump has been connected to the
power supply after the alarm occurred.
Warning log (1.10-1.14)
Set one of the following operating modes:
• Normal (duty)
• Stop
• Min.
• Max.
The operating modes can be set without changing the setpoint
setting.
10.5.3 Fault indications
Faults may result in two types of indication: Alarm or warning.
An "alarm" will activate an alarm indication in CUE and cause
the pump to change operating mode, typically to stop. However,
for some faults resulting in alarm, the pump is set to continue
operating even if there is an alarm.
A "warning" will activate a warning indication in CUE, but the
pump will not change operating or control mode.
In case of a "warning", the last five warning indications will
appear in the warning log. "Warning log 1" shows the latest fault,
"Warning log 2" shows the latest fault but one, etc.
The display shows three pieces of information:
• the warning indication
• the warning code
• the number of minutes the pump has been connected to the
power supply after the warning occurred.
21
10.6 Menu STATUS
The displays appearing in this menu are status displays only. It is
not possible to change or set values.
The tolerance of the displayed value is stated unde r each disp lay.
The tolerances are stated as a guide in % of the maximum values
of the parameters.
10.6.1 Actual setpoint (2.1)
This display shows the actual setpoint and the external setpoint.
The actual setpoint is shown in units of feedback sensor.
The external setpoint is shown in a range of 0-100 %. If the
external setpoint influence is disactivated, the value 100 % is
shown. See section 13.2 External setpoint.
10.6.2 Operating mode (2.2)
10.6.6 Speed (2.6)
Tolerance: ± 5 %
This display shows the actual pump speed.
10.6.7 Input power and motor current (2.7)
Tolerance: ± 10 %
This display shows the actual pump input power in W or kW and
the actual motor current in Ampere [A].
10.6.8 Operating hours and power consumption (2.8)
This display shows the actual operating mode (Normal, Stop, Min.
or Max.). Furthermore, it shows where this operating mode was
selected (CUE menu, Bus, External or On/off button).
10.6.3 Actual value (2.3)
This display shows the actual value controlled.
If no sensor is connected to the CUE, "–" will appear in the
display.
10.6.4 Measured value, sensor 1 (2.4)
This display shows the actual value measured by sensor 1
connected to terminal 54.
If no sensor is connected to the CUE, "–" will appear in the
display.
10.6.5 Measured value, sensor 2 (2.5)
Tolerance: ± 2 %
This display shows the number of operating hours and the power
consumption. The value of operating hours is an accumulated
value and cannot be reset. The value of power consumption is an
accumulated value calculated from the unit’s birth, and it cannot
be reset.
10.6.9 Lubrication status of motor bearings (2.9)
This display shows how many times the user has given the
lubricated information and when to replace the motor bearings.
When the motor bearings have been relubricated, confirm this
action in the INSTALLATION menu. See section
10.7.17 Confirming relubrication/replacement of motor bearings
(3.20). When relubrication is confirmed, the figure in the above
display will be increased by one.
10.6.10 Time until relubrication of motor bearings (2.10)
This display is only shown if an MCB 114 sensor input module
has been installed.
This display shows the actual value measured by sensor 2
connected to an MCB 114.
If no sensor is connected to the CUE, "–" will appear in the
display.
22
This display is only shown if display 2.11 is not shown.
This display shows when to relubricate the motor bearings. The
controller monitors the operating pattern of the pump and
calculates the period between bearing relubrications. If the
operating pattern changes, the calculated time till relubrication
may change as well.
The estimated time until relubrication takes into account if the
pump has been running with reduced speed.
See section 10.7.17 Confirming relubrication/replacement of motor bearings (3.20).
10.6.11 Time until replacement of motor bearings (2.11)
Note
10.6.15 Accumulated flow (2.15)
This display is only shown if display 2.10 is not shown.
This display shows when to replace the motor bearings. The
controller monitors the operating pattern of the pump and
calculates the period between bearing replacements.
The estimated time until replacement of motor bearings takes into
account if the pump has been running with reduced speed.
See section 10.7.17 Confirming relubrication/replacement of motor bearings (3.20).
10.6.12 Temperature sensor 1 (2.12)
This display is only shown if an MCB 114 sensor input module
has been installed.
This display shows the measuring point and the actual value
measured by Pt100/Pt1000 temperature sensor 1 connected to
the MCB 114. The measuring point is selected in display 3.21.
If no sensor is connected to the CUE, "–" will appear in the
display.
10.6.13 Temperature sensor 2 (2.13)
This display is only shown if a flowmeter has been configured.
This display shows the value of the accumulated flow and the
specific energy for the transfer of the pumped liquid.
The flow measurement can be connected to the digital p ulse input
(terminal 33) or the analog input (terminal 54).
10.6.16 Firmware version (2.16)
This display shows the version of the software.
10.6.17 Configuration file (2.17)
This display shows the configuration file.
10.7 Menu INSTALLATION
10.7.1 Control mode (3.1)
This display is only shown if an MCB 114 sensor input module
has been installed.
This display shows the measuring point and the actual value
measured by Pt100/Pt1000 temperature sensor 2 connected to
the MCB 114. The measuring point is selected in display 3.22.
If no sensor is connected to the CUE, "–" will appear in the
display.
10.6.14 Flow rate (2.14)
This display is only shown if a flowmeter has been configured.
This display shows the actual value measured by a flowmeter
connected to the digital pulse input (terminal 33) or the analog
input (terminal 54).
Select one of the following control modes:
• Open loop
• Constant pressure
• Constant differential pressure
• Proportional differential pressure
• Constant flow rate
• Constant temperature
• Constant level
• Constant other value.
If the pump is connected to a bus, the control
mode cannot be selected via the CUE. See
section 13.3 GENIbus signal.
23
10.7.2 Controller (3.2)
CUE
p
CUE
p
CUE
Q
CUE
L
t
L
2
CUE
Δt
L
2
CUE
t
L
2
CUE
CUE
Δp
Δp
L
1
CUE
System/application
Heating
system
K
p
Cooling
1)
system
2)
0.20.5
T
i
The CUE has a factory setting of gain (K
) and integral time (Ti).
p
However, if the factory setting is n ot the opt imum set ting, the ga in
and the integral time can be changed in the display.
•The gain (K
• The integral time (T
) can be set within the range from 0.1 to 20.
p
) can be set within the range from 0.1 to
i
3600s. If 3600s is selected, the controller will function as a P
controller.
• Furthermore, it is possible to set the controller to inverse
control, meaning that if the setpoint is increased, the speed
will be reduced. In the case of inverse control, the gain (K
)
p
must be set within the range from –0.1 to –20.
The table below shows the suggested controller settings:
SP, SP-G, SP-NE: 0.50.5
0.20.5
SP, SP-G, SP-NE: 0.50.5
0.20.5
–2.5100
0.5–0.510 + 5L
2
0.510 + 5L
2
0.5–0.530 + 5L2 *
0.50.5 *
< 5 m: 0.5 *
L
1
0.5
L
> 5 m: 3 *
1
L
> 10 m: 5 *
1
* Ti = 100 seconds (factory setting).
1. Heating systems are systems in which an increase in pump
performance will result in a rise in temperature at the sensor.
2. Cooling systems are systems in which an increase in pump
performance will result in a drop in temperature at the sensor.
= Distance in [m] between pump and sensor.
L
1
= Distance in [m] between heat exchanger and sensor.
L
2
24
How to set the PI controller
Note
For most applications, the factory setting of the controller
constants K
and Ti will ensure optimum pump operation.
p
However, in some applications an adjustment of the controller
may be needed.
Proceed as follows:
1. Increase the gain (K
) until the motor becomes unstable.
p
Instability can be seen by observing if the measured value
starts to fluctuate. Furthermore, instability is audible as the
motor starts hunting up and down.
As some systems, such as temperature controls, are slowreacting, it may be difficult to observe that the motor is
unstable.
2. Set the gain (K
) to half the value of the value which made the
p
motor unstable. This is the correct setting of the gain.
3. Reduce the integral time (T
) until the motor becomes
i
unstable.
4. Set the integral time (T
) to twice the value which made the
i
motor unstable. This is the correct setting of the integral time.
General rules of thumb:
• If the controller is too slow-reacting, increase K
.
p
• If the controller is hunting or unstable, dampen the system by
reducing K
or increasing Ti.
p
10.7.3 External setpoint (3.3)
10.7.4 Signal relays 1 and 2 (3.4 and 3.5)
The CUE has two signal relays. In the display below, select in
which operating situations the signal relay should be activated.
Signal relay 1Signal relay 2
• Ready
• Alarm
• Operation
• Pump running
• Not active
• Warning
• Relubricate.
• Ready
• Alarm
• Operation
• Pump running
• Not active
• Warning
• Relubricate.
For distinction between alarm and warning, see
section 10.5.3 Fault indications.
10.7.5 Buttons on the CUE (3.6)
The input for external setpoint signal (terminal 53) can be set to
the following types:
• Active
• Not active.
If Active is selected, the actual se tpoint is inf luenced by the signal
connected to the external setpoint input. See section
13.2 External setpoint.
The editing buttons (+, –, On/Off, OK) on the control panel can be
set to these values:
•Active
• Not active.
When set to Not active (locked), the editing buttons do not
function. Set the buttons to Not active if the pump should be
controlled via an external control system.
Activate the buttons by pressing the arrow up and arrow down
buttons simultaneously for 3 seconds.
10.7.6 Protocol (3.7)
This display shows the protocol selection for the RS-485 port of
the CUE. The protocol can be set to these values:
• GENIbus
•FC
•FC MC.
If GENIbus is selected, the com municat io n is set accord ing to the
Grundfos GENIbus standard. FC and FC MC is for service
purpose only.
10.7.7 Pump number (3.8)
This display shows the GENIbus number. A number between 1
and 199 can be allocated to the pump. In the case of bus
communication, a number must be allocated to each pump.
The factory setting is "–".
25
10.7.8 Digital inputs 2, 3 and 4 (3.9 to 3.11)
Stop pressure
ΔH
Start pressure
Continuous operation
On/off operation
The digital inputs of the CUE (terminal 19, 32 and 33) can
individually be set to different functions.
Select one of the following functions:
• Min. (min. curve)
• Max. (max. curve)
• Ext. fault (external fault)
• Flow switch
• Alarm reset
• Dry running (from external sensor)
• Accumulated flow (pulse flow, only terminal 33)
• Not active.
The selected function is active when the digital input is activated
(closed contact). See also section 13.1 Digital inputs.
Min.
When the input is activated, the pump will operate according to
the min. curve.
Max.
When the input is activated, the pump will operate according to
the max. curve.
Ext. fault
When the input is activated, a timer will be started. If the input is
activated for more than 5 seconds, an external fault will be
indicated. If the input is deactivated, the fault condition will cease
and the pump can only be restarted manually by resetting the
fault indication.
Flow switch
When this function is selected, the pump will be stopped when a
connected flow switch detects low flow.
It is only possible to use this function if the pump is connected to
a pressure sensor or a level sensor, and the stop function is
activated. See sections 10.7.10 and 10.7.11.
Alarm reset
When the input has been activated, the alarm is reset if the cause
of the alarm no longer exists.
Dry running
When this function is selected, lack of inlet pressure or water
shortage can be detected. This requires the use of an accessory,
such as:
®
• a Grundfos Liqtec
dry-running switch
• a pressure switch installed on the suction side of a pump
• a float switch installed on the suction side of a pump.
When lack of inlet pressure or water shortage (Dry running) is
detected, the pump will be stopped. The pump cannot restart as
long as the input is activated.
Restarts may be delayed by up to 30 minutes, depending of the
pump family.
Accumulated flow
When this function is set for digital input 4 and a pulse sensor is
connected to terminal 33, the accumulated flow can be
measured.
10.7.9 Digital flow input (3.12)
This display appears only if a flowmeter has been configured in
display 3.11.
The display is used for setting the volume for every pulse for the
function Accumulated flow with a pulse sensor connected to
terminal 33.
Setting range:
• 0-1000 litre/pulse.
The volume can be set in the unit selected in the start-up guide.
10.7.10 Constant pressure with stop function (3.13)
Settings
The stop function can be set to these values:
• Active
• Not active.
The on/off band can be set to these values:
• ΔH is factory-set to 10 % of actual setpoint.
• ΔH can be set within the range from 5 % to 30 % of the actual
setpoint.
Descriptions
The stop function is used for changing between on/off operation
at low flow and continuous operation at high flow.
TM03 8477 1607
Fig. 38 Constant pressure with stop function. Difference
between start and stop pressures (ΔH)
Low flow can be detected in two different ways:
1. A built-in "low-flow detection function" which functions if the
digital input is not set up for flow switch.
2. A flow switch connected to the digital input.
1. Low-flow detection function
The pump will check the flow regularly by reducing the speed for
a short time. If there is no or only a small change in pressure, this
means that there is low flow.
The speed will be increased until the stop pressure (actual
setpoint + 0.5 x ΔH) is reached and the pump will stop after a few
seconds. The pump will restart at the latest when the pressure
has fallen to the start pressure (actual setpoint – 0.5 x ΔH).
If the flow in the off period is higher than the low-flow limit, the
pump will restart before the pressure has fallen to the start
pressure.
26
When restarting, the pump will react in the following way:
Caution
Pressure sensor
Diaphragm tank
Non-return
valve
Pump
Diaphragm tank
Pressure sensor
PumpNon-return valve
Sta rt leve l
ΔH
Stop level
1. If the flow is higher than the low-flow limit, the pump will return
to continuous operation at constant pressure.
2. If the flow is lower than the low-flow limit, the pump will
continue in start/stop operation. It will continue in start/stop
operation until the flow is higher than the low-flow limit. When
the flow is higher than the low-flow limit, the pump will return to
continuous operation.
2. Low-flow detection with flow switch
When the digital input is activated because there is low-flow, the
speed will be increased until the stop pressure (actual setpoint +
0.5 x ΔH) is reached, and the pump will stop. When the pressure
has fallen to start pressure, the pump will start again. If there is
still no flow, the pump will reach the stop pressure and stop. If
there is flow, the pump will continue operating according to the
setpoint.
Operating conditions for the stop function
It is only possible to use the stop function if the system
incorporates a pressure sensor, a non-return valve and a
diaphragm tank.
The non-return valve must always be installed
before the pressure sensor. See figs 39 and 40.
If a flow switch is used to detect low flow, the
switch must be installed on the system side after
the diaphragm tank.
10.7.11 Constant level with stop function (3.13)
Settings
The stop function can be set to these values:
• Active
• Not active.
The on/off band can be set to these values:
• ΔH is factory-set to 10 % of actual setpoint.
• ΔH can be set within the range from 5 % to 30 % of actual
setpoint.
A built-in low-flow detection function will automatically measure
and store the power consumption at approx. 50 % and 85 % of
the rated speed.
If Active is selected, proceed as follows:
1. Close the isolating valve to create a no-flow condition.
2. Press OK to start the auto-tuning.
Description
The stop function is used for changing between on/off operation
at low flow and continuous operation at high flow.
Fig. 39 Position of the non-return valve and pressure sensor in
system with suction lift operation
Fig. 40 Position of the non-return valve and pressure sensor in
system with positive inlet pressure
Diaphragm tank
The stop function requires a diaphragm tank of a certain minimum
size. The tank must be installed as close as possible after the
pump and the precharge pressure must be 0.7 x actual setpoint.
Recommended diaphragm tank size:
Rated flow rate of pump
[m³/h]
Typical diaphragm tank size
[litres]
0-68
7-2418
25-4050
41-70120
71-100180
If a diaphragm tank of the above size is installed in the system,
the factory setting of ΔH is the correct setting.
If the tank installed is too small, the pump will start and stop too
often. This can be remedied by increasing ΔH.
TM03 8582 1907TM03 8583 1907
Fig. 41 Constant level with stop function. Difference between
start and stop levels (ΔH)
Low flow can be detected in two different ways:
1. With the built-in low-flow detection function.
2. With a flow switch connected to a digital input.
1. Low-flow detection function
The built-in low-flow detection is based on the measurement of
speed and power.
When low flow is detected, the pump will stop. When the level has
reached the start level, the pump will st art a gain. If there is still no
flow, the pump will reach the stop level and stop. If there is flow,
the pump will continue operating according to the setpoint.
2. Low-flow detection with flow switch
When the digital input is activated because of low flow, the speed
will be increased until the stop level (actual setpoint – 0.5 x ΔH) is
reached, and the pump will stop. When the level has reached the
start level, the pump will start again. If there is still no flow, the
pump will reach the stop level and stop. If there is flow, the pump
will continue operating according to the setpoint.
Operating conditions for the stop function
It is only possible to use the constant level stop function if the
system incorporates a level sensor, and all valves can be closed.
TM03 9099 3307
27
10.7.12 Sensor 1 (3.15)
Note
Nominal speedMax. speed
Actual speed range
Min. speed
Pump-dependent speed range
Min. speed, adjusted
Max. speed, adjusted
Speed [%]
Min.
Max.
100 %
Setting of sensor 1 connected to terminal 54. This is the feedback
sensor.
Select among the following values:
• Sensor output signal:
0-20 mA
4-20 mA.
• Unit of measurement of sensor:
bar, mbar, m, kPa, psi, ft, m3/h, m3/s, l/s, gpm, °C, °F, %.
• Sensor measuring range.
10.7.13 Sensor 2 (3.16)
Setting of sensor 2 connected to an MCB 114 sensor input
module.
Select among the following values:
• Sensor output signal:
0-20 mA
4-20 mA.
• Unit of measurement of sensor:
bar, mbar, m, kPa, psi, ft, m3/h, m3/s, l/s, gpm, °C, °F, %.
• Sensor measuring range:
0-100 %.
10.7.14 Duty/standby (3.17)
Settings
The duty/standby function can be set to these values:
• Active
• Not active.
Activate the duty/standby function as follows:
1. Connect one of the pumps to the mains supply.
Set the duty/standby function to Not active.
Make the necessary settings in menu OPERATION and
INSTALLATION.
2. Set the operating mode to Stop in menu OPERATION.
3. Connect the other pump to the mains supply.
Make the necessary settings in menu OPERATION and
INSTALLATION.
Set the duty/standby function to Active.
The running pump will search for the other pump and
automatically set the duty/standby function of this pump to Active.
If it cannot find the other pump, a fault will be indicated.
The two pumps must be connected electrically
via the GENIbus, and nothing else must be
connected on the GENIbus.
The duty/standby function applies to two pumps connected in
parallel and controlled via GENIbus. Each pump must be
connected to its own CUE and sensor.
The primary targets of the function is the following:
• To start the standby pump if the duty pump is stopped due to
an alarm.
• To alternate the pumps at least every 24 hours.
10.7.15 Operating range (3.18)
How to set the operating range:
• Set the min. speed within the range from a pump-dependent
min. speed to the adjusted max. speed. The factory setting
depends on the pump family.
• Set the max. speed within the range from adjusted min. speed
to the pump-dependent maximum speed. The factory setting
will be equal to 100 %, i.e. the speed stated on the pump
nameplate.
The area between the min. and max. speed is the actual
operating range of the pump.
The operating range can be changed by the user within the
pump-dependent speed range.
For some pump families, oversynchronous operation (max. speed
above 100 %) will be possible. This requires an oversize motor to
deliver the shaft power required by the pump during
oversynchronous operation.
Fig. 42 Setting of the min. and max. curves in % of maximum performance
28
TM04 3581 4608
10.7.16 Motor bearing monitoring (3.19)
Note
Note
10.7.18 Temperature sensor 1 (3.21)
The motor bearing monitoring function can be set to these values:
• Active
• Not active.
When the function is set to Active, the CUE will give a warning
when the motor bearings are due to be relubricated or replaced.
Description
The motor bearing monitoring function is used to give an
indication when it is time to relubricate or replace the motor
bearings. See display 2.10 and 2.11.
The warning indication and the estimated time t ake into account if
the pump has been running with reduced speed. The bearing
temperature is included in the calculation if temperature sensors
are installed and connected to an MCB 114 sensor input module.
The counter will continue counting even if the
function is switched to Not active, but a warning
will not be given when it is time for relubrication.
10.7.17 Confirming relubrication/replacement of motor
bearings (3.20)
This function can be set to these values:
• Relubricated
• Replaced
• Nothing done.
When the motor bearings have been relubricated or replaced,
confirm this action in the above display by pressing "OK".
Relubricated cannot be selected for a period of
time after confirming relubrication.
Relubricated
When the warning Relubricate motor bearings has been
confirmed,
• the counter is set to 0.
• the number of relubrications is increased by 1.
When the number of relubrications has reached the permissible
number, the warning Replace motor bearings appears in the
display.
Replaced
When the warning Replace motor bearings has been confirmed,
• the counter is set to 0.
• the number of relubrications is set to 0.
• the number of bearing changes is increased by 1.
This display is only shown if an MCB 114 sensor input module
has been installed.
Select the function of a Pt100/Pt1000 temperature sensor 1
connected to an MCB 114:
• D-end bearing
• ND-end bearing
• Other liq. temp. 1
• Other liq. temp. 2
• Motor winding
• Pumped liq. temp.
• Ambient temp.
• Not active.
10.7.19 Temperature sensor 2 (3.22)
This display is only shown if an MCB 114 sensor input module
has been installed.
Select the function of a Pt100/Pt1000 temperature sensor 2
connected to an MCB 114:
• D-end bearing
• ND-end bearing
• Other liq. temp. 1
• Other liq. temp. 2
• Motor winding
• Pumped liq. temp.
• Ambient temp.
• Not active.
10.7.20 Standstill heating (3.23)
The standstill heating function can be set to these values:
• Active
• Not active.
When the function is set to Active and the pump is stopped by a
stop command, a current will be applied to the motor windings.
The standstill heating function pre-heats the motor to avoid
condensation.
29
Rated
Ramp-upRamp-down
Speed
Time
Minimum
Initial rampFinal ramp
On/
Off
10.7.21 Ramps (3.24)
Set the time for each of the two ramps, ramp-up and ramp-down:
• Factory setting:
Depending on power size.
• The range of the ramp parameter:
1-3600 s.
-1
The ramp-up time is the acceleration time from 0 min
to the
rated motor speed. Choose a ramp-up time such that the output
current does not exceed the maximum current limit for the CUE.
The ramp-down time is the deceleration time from rated motor
speed to 0 min
-1
. Choose a ramp-down time such that no
overvoltage arises and such that the generated current does not
exceed the maximum current limit for the CUE.
Fig. 43 Ramp-up and ramp-down, display 3.24
11. Setting by means of PC Tool E-products
Special setup requirements differing from the settings available
via the CUE require the use of Grundfos PC Tool E-products. This
again requires the assistance of a Grundfos service technician or
engineer. Contact your local Grundfos company for more
information.
12. Priority of settings
The on/off button has the highest priority. In "off"
On/
condition, pump operation is not possible.
The CUE can be controlled in various ways at the same time. If
two or more operating modes are active at the same time, the
operating mode with the highest priority will be in force.
12.0.1 Control without bus signal, local operating mode
PriorityCUE menuExternal signal
1Stop
2Max.
3Stop
4
5Min.Min.
6NormalNormal
Example: If an external signal has activated the operating mode
Max., it will only be possible to stop the pump.
12.0.2 Control with bus signal, remote-controlled operating
mode
Priority CUE menuExternal signal Bus signal
1Stop
2Max.
3StopStop
4
5
6
Example: If the bus signal has activated the operating mode
Max., it will only be possible to stop the pump.
TM03 9439 4007
13. External control signals
13.1 Digital inputs
The overview shows functions in connection with closed contact.
Terminal TypeFunction
18DI 1• Start/stop of pump
•Min. (min. curve)
•Max. (max. curve)
• Ext. fault (external fault)
19DI 2
32DI 3
33DI 4
The same function must not be selected for more than one input.
See fig. 17.
• Flow switch
• Alarm reset
• Dry running (from external sensor)
• Not active.
•Min. (min. curve)
•Max. (max. curve)
• Ext. fault (external fault)
• Flow switch
• Alarm reset
• Dry running (from external sensor)
• Not active.
• Min. (min. curve)
• Max. (max. curve)
• Ext. fault (external fault)
• Flow switch
• Alarm reset
• Dry running (from external sensor)
• Accumulated flow (pulse flow)
• Not active.
Max.
Max.
Min.
Normal
30
13.2 External setpoint
Setpoint
Max. curve
Setpoint, CUE menu
Min. curve
Ext. setpoint signal
Actual setpoint
010 V
Actual
setpoint
range
Setpoint
Sensor max.
Setpoint, CUE menu
Sensor min.
Ext. setpoint signal
Actual setpoint
010 V
Actual
setpoint
range
Note
Setpoint
90 % of max. head
Setpoint, CUE menu
25 % of max. head
Ext. setpoint signal
Actual setpoint
010 V
Actual
setpoint
range
Terminal TypeFunction
53AI 1• External setpoint (0-10 V)
The setpoint can be remote-set by connecting an analog signal
transmitter to the setpoint input (terminal 53).
Open loop
In control mode Open loop (constant curve), the actual setpoint
can be set externally within the range from the min. curve to the
setpoint set via the CUE menu. See fig. 44.
Fig. 44 Relation between the actual setpoint and the external
setpoint signal in control mode Open loop
Closed loop
In all other control modes, except proportional differential
pressure, the actual setpoint can be set externally within the
range from the lower value of the sensor measuring range
(sensor min.) to the setpoint set via the CUE menu. See fig. 45.
Proportional differential pressure
In control mode Proportional differential pressure, the actual
setpoint can be set externally within the range from 25 % of
maximum head to the setpoint set via the CUE menu. See fig. 46.
Fig. 46 Relation between the actual setpoint and the external
setpoint signal in control mode Proportional differential
pressure
Example: At a maximum head of 12 metres, a setpoint of 6
metres set via the CUE menu and an external setpoint of 40 %,
the actual setpoint will be as follows:
TM03 8856 2607TM03 8856 2607
(setpoint, CUE menu – 25 % of maximum
Actual setpoint =
head) x % external setpoint signal + 25 % of
maximum head
= (6 – 12 x 25 %) x 40 % + 12/4
=4.2 m
13.3 GENIbus signal
The CUE supports serial communication via an RS-485 input.
The communication is carried out according to the Grundfos
GENIbus protocol and enables connection to a building
management system or another external control system.
Operating parameters, such as setpoint and operating mode can
be remote-set via the bus signal. At the same time, the pump can
provide status information about important parameters, such as
actual value of control parameter, input power and fault
indications.
Contact Grundfos for further details.
TM03 8856 2607
Fig. 45 Relation between the actual setpoint and the external
Example: At a sensor min. value of 0 bar, a setpoint set via the
CUE menu of 3 bar and an external setpoint of 80 %, the actual
setpoint will be as follows:
Actual setpoint =
setpoint signal in control mode Controlled
(setpoint set via the CUE menu – sensor min.)
x % external setpoint signal + sensor min.
= (3 – 0) x 80 % + 0
= 2.4 bar
If a bus signal is used, the number of settings
available via the CUE will be reduced.
13.4 Other bus standards
Grundfos offers various bus solutions with communication
according to other standards.
Contact Grundfos for further details.
14. Maintenance and service
14.1 Cleaning the CUE
Keep the cooling fins and fan blades clean to ensure sufficient
cooling of the CUE.
14.2 Service parts and service kits
For further information on service parts and service kits, visit
www.grundfos.com > International website > WebCAPS.
31
15. Fault finding
15.1 Warning and alarm list
Status
Code and display text
Warning
Alarm
Too high leakage
1
current
2Mains phase failure
3External fault
16Other fault
zStopAut.
z StopMan.
z StopAut.
30Replace motor bearings z
32Overvoltage
40Undervoltage
48Overload
49Overload
55Overload
57Dry running
Too high CUE
64
temperature
Too high motor
70
temperature
Communication fault,
77
duty/standby
89Sensor 1 outside range
Temperature sensor 1
91
outside range
z
zStopAut.
z
zStopAut.
zStopAut.
zStopAut.
z
zStopAut.
zStopAut.
zStopAut.
zStopAut.
z
z
z
93Sensor 2 outside range z
Setpoint signal outside
96
range
Too high bearing
148
temperature
Too high bearing
149
temperature
155 Inrus h faul t
Temperature sensor 2
175
outside range
Relubricate motor
240
bearings
241 Motor phase failure
2)
242 AMA
1)
In case of an alarm, the CUE will change the operating mode
did not succeedz–Man.
z
z
zStopAut.
z
zStopAut.
zStopAut.
z
z
z
zStopAut.
depending on the pump type.
2)
AMA, Automatic Motor Adaptation. Not active in the present
software.
3)
Warning is reset in display 3.20.
Operat-
ing mode
Locked alarm
zStopMan.
zStopMan.
–Man.
–Aut.
–Aut.
zStopMan.
–Aut.
–Aut.
1)
–Aut.
–Aut.
1)
–Aut.
–Aut.
–Aut.
–Man.
–Aut.
Reset-
ting
Aut.
Aut.
15.2 Resetting of alarms
In case of fault or malfunction of the CUE, check the alarm list in
menu OPERATION. The latest five alarms and latest five
warnings can be found in the log menus.
Contact a Grundfos technician if an alarm occurs repeatedly.
15.2.1 Warning
The CUE will continue the operation as long as the warning is
active. The warning remains active until the cause no longer
exists. Some warnings may switch to alarm condition.
15.2.2 Alarm
In case of an alarm, the CUE will stop the pump or change the
operating mode depending on the alarm typ e and pump type. See
section 15.1 Warning and alarm list.
Pump operation will be resumed when the cause of the alarm has
been remedied and the alarm has been reset.
Resetting an alarm manually
3)
• Press OK in the alarm display.
• Press On/Off twice.
• Activate a digital input DI 2-DI 4 set to Alarm reset or the
digital input DI 1 (Start/stop).
If it is not possible to reset an alarm, the reason may be that the
fault has not been remedied, or that the alarm has been locked.
15.2.3 Locked alarm
In case of a locked alarm, the CUE will stop the pump and
become locked. Pump operation cannot be resumed until the
cause of the locked alarm has been remedied and the alarm has
been reset.
Resetting a locked alarm
• Switch off the power supply to the CUE for approx. 30
seconds. Switch on the power supply, and press OK in the
alarm display to reset the alarm.
15.3 Indicator lights
The table show the function of the indicator lights.
Indicator
light
Function
The pump is running or has been stopped by a
On (green)
stop function.
If flashing, the pump has been stopped by the
user (CUE menu), external start/stop or bus.
Off (orange)
The pump has been stopped with the on/off
button.
Alarm (red)Indicates an alarm or a warning.
15.4 Signal relays
The table show the function of the signal relays.
TypeFunction
3)
Relay 1
• Ready
•Alarm
• Operation
• Ready
Relay 2
•Alarm
• Operation
See also fig. 24.
• Pump running
• Warning
• Relubricate.
• Pump running
• Warning
• Relubricate.
32
16. Technical data
16.1 Enclosure
The individual CUE cabinet sizes are characterised by their
enclosures. The table shows the relationship of enclosure class
and enclosure type.
Example:
Read from the namepl ate :
• Supply voltage =3 x 380-500 V.
• Typical shaft power = 110 kW.
• Enclosure class =IP21.
The table shows that the CUE enclosure is D1.
The dimensions are maximum height, width and depth. Dimensions are without options
Height [mm]
AaBbCc∅d∅ef
1)
Width [mm]
1)
Depth [mm]
1)
Screw holes [mm]
Weight [kg]
TM03 9922 4607
33
16.3 Surroundings
Relative humidity5-95 % RH
Ambient temperatureMax. 45 °C
Average ambient temperature over 24 hoursMax. 40 °C
Minimum ambient temperature at full
operation
Minimum ambient temperature at reduced
operation
Temperature during storage and
transportation
–25 to 65 °C
0 °C
–10 °C
Storage durationMax. 6 months
Maximum altitude above sea level without
performance reduction
Maximum altitude above sea level with
performance reduction
1000 m
3000 m
Note: The CUE comes in a packaging which is not suitable for
outdoor storage.
16.4 Terminal tightening torques
Screws M1019 Nm
Screws M89.5 Nm
16.5 Cable length
Maximum length, screened motor cable150 m
Maximum length, unscreened motor cable300 m
Maximum length, signal cable300 m
16.6 Fuses and cable cross-section
Warnin g
Always comply with national and local
regulations as to cable cross-sections.
16.6.1 Cable cross-section to signal terminals
Maximum cable cross-section to signal
terminals, rigid conductor
Maximum cable cross-section to signal
terminals, flexible conductor
Minimum cable cross-section to signal
terminals
16.6.2 Non-UL fuses and conductor cross-section to mains
and motor
Typical shaft
power P2
[kW][A]
3 x 380-500 V
110300gG2 x 70
132350gG2 x 70
160400gG2 x 185
200500gG2 x 185
250600gR2 x 185
3 x 525-690 V
110225–2 x 70
132250–2 x 70
160350–2 x 185
200400–2 x 185
250500–2 x 185
1)
Screened motor cable, unscreened supply cable. AWG,
Maximum
fuse size
Fuse
type
Maximum conductor
cross-section
see section 16.6.3.
[mm
2
]
1.5 mm
1.0 mm
0.5 mm
1)
2
2
2
34
16.6.3 UL fuses and conductor cross-section to mains and motor
Typical shaft
power P2
[kW]
3 x 380-500 V
110FWH-300JJS-300NOS-300170M30172028220-315L50S-300A50-P3002 x 2/0
132FWH-350JJS-350NOS-350170M3018 2028220-315L50S-350A50-P3502 x 2/0
160FWH-400JJS-400NOS-400170M4012206xx32-400L50S-400A50-P4002 x 350 MCM
200FWH-500JJS-500NOS-500170M4014206xx32-500L50S-500A50-P5002 x 350 MCM
250FWH-600JJS-600NOS-600170M4016206xx32-600L50S-600A50-P6002 x 350 MCM
––––Bussmann
3 x 525-690 V
110–––170M30172061032.315–6.6URD30D08A03152 x 2/0
132–––170M30182061032.350–6.6URD30D08A03502 x 2/0
160–––170M40112061032.350–6.6URD30D08A03502 x 2/0
200–––170M40122061032.400–6.6URD30D08A04002 x 350 MCM
250–––170M40142061032.500–6.6URD30D08A05002 x 350 MCM
1)
Screened motor cable, unscreened supply cable.
2)
American Wire Gauge.
Bussmann
E1958
JFHR2
Bussmann
E4273
T/JDDZ
Bussmann
E4274
H/JDDZ
Fuse typeMaximum conductor
Bussmann
E125085
JFHR2
E125085
JFHR2
SIBA
E180276
RKI/JDDZ
SIBA
E180276
JFHR2
Littel Fuse
E71611
JFHR2
–Ferraz-Shawmut
Ferraz-Shawmut
E60314
JFHR2
E76491
JFHR2
cross-section
2)
[AWG]
–
1)
35
16.7 Inputs and outputs
Note
Subject to alterations.
16.7.1 Mains supply (L1, L2, L3)
Supply voltage380-500 V ± 10 %
Supply voltage525-690 V ± 10 %
Supply frequency50/60 Hz
Maximum temporary imbalance between
phases
Leakage current to earth>3.5 mA
Number of cut-ins, enclosure Dmax. 1 time/2 min.
Do not use the supply voltage for switching the
CUE on and off.
16.7.2 Motor output (U, V, W)
Output voltage0-100 %
Output frequency0-100 Hz
Switching on outputnot recommended
1)
Output voltage in % of supply voltage.
2)
Depending on the pump family selected.
16.7.3 RS-485 GENIbus connection
Terminal number68 (A), 69 (B), 61 GND (Y)
The RS-485 circuit is functionally separated from other central
circuits and galvanically separated from the supply voltage
(PELV).
16.7.4 Digital inputs
Terminal number18, 19, 32, 33
Voltage level0-24 VDC
Voltage level, open contact> 19 VDC
Voltage level, closed contact< 14 VDC
Maximum voltage on input28 VDC
Input resistance, R
i
All digital inputs are galvanically separated from the supply
voltage (PELV) and other high-voltage terminals.
The sound pressure of the CUE is measured at a distance of 1 m
from the unit.
The sound pressure level of a motor controlled by a frequency
converter may be higher than that of a corresponding motor
which is not controlled by a frequency converter. See section
6.7 RFI filters.
17. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
36
Argentina
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Lote
34A
1619 - Garin
Pcia. de Buenos Aires
Phone: +54-3327 414 444
Telefax: +54-3327 411 111
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Paromlinska br. 16,
BiH-71000 Sarajevo
Phone: +387 33 713290
Telefax: +387 33 231795
Brazil
Mark GRUNDFOS Ltda.
Av. Humberto de Alencar Castelo
Branco, 630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015