Grundfos CU 301 Installation And Operating Instructions Manual

Page 1
CU 301
GRUNDFOS INSTRUCTIONS
Installation and operatin g instructi on s
Page 2
LIMITED WARRANTY
Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repair­ing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manu­facturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions.
To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation sup­porting the warranty claim and/or a Return Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUEN­TIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WAR­RANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or conse­quential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.
2
Page 3
3
CU 301
Installation and operating instructions 4
Page 4
4
CONTENTS
Page
1. Constant-pressure control 5
1.1 Description 5
1.2 Function 5
1.3 System sizing 7
1.4 SQE and SQE-NE 7
1.5 Positioning the pressure sensor 8
1.6 Precharge pressure setting 8
1.7 Pressure relief valve 8
2. Operating functions 9
2.1 On/Off button 9
2.2 Indication of pump operation 9
2.3 Pressure setting 9
2.4 Button locking 10
3. Alarm functions 10
3.1 Service alarm 10
3.2 Dry-running protection 11
4. Position of LEDs 12
5. CU 301 with R100 13
5.1 Menu OPERATION 15
5.1.1 Pressure setting 15
5.1.2 Operating mode 15
5.1.3 Alarm 15
5.2 Menu STATUS 16
5.2.1 Operating mode 16
5.2.2 Actual pressure 16
5.2.3 Speed 16
5.2.4 Temperature 16
5.2.5 Power input and power consumption 16
5.2.6 Operating hours and number of starts 17
5.3 Menu INSTALLATION 17
5.3.1 Sensor 17
5.3.2 Choice of sensor 17
5.3.3 Maximum pressure setting 17
5.3.4 Automatic restart 18
5.3.5 Dry-running stop 18
5.3.6 Maximum speed 18
5.3.7 Cut-in speed 18
5.3.8 Buttons on the CU 301 19
5.3.9 Indication of pump operation 19
5.3.10 Number 19
6. Print 20
7. Troubleshooting 21
7.1 Service 21
8. Technical data 25
8.1 Electrical connection 26
8.1.1 Mains supply 27
8.1.2 Pump supply 27
8.1.3 Pressure sensor 27
9. Pressure sensor voltage chart 28
10. Disposal 29
Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regula­tions and accepted codes of good prac­tice.
Page 5
5
1. Constant-pressure control
The control unit CU 301 is for use only with Grundfos SQE pumps incorporating electronic power factor correction (PFC).
1.1 Description
The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption.
The CU 301 is designed for wall mounting only.
Fig. 1 Example of a system with constant-
pressure control
1.2 Function
The pressure is registered by means of the pressure sensor, which transmits a 4-20 mA signal to the CU 301. The CU 301 adjusts the pump performance accordingly to maintain constant pressure by chang­ing the pump speed.
Mains borne signalling
The communication between the CU 301 and the pump is via the power supply cable.
This communication principle is mains borne signal­ling (or power line communication). Using this princi­ple means that no additional cables to the pump are required.
The communication of data is effected via a high-fre­quency signal transmitted to the power supply cable and led into the electronics unit by means of signal coils incorporated in the motor and the CU 301 respectively.
In situations where multiple CU 301 pump power cables are run parallel in wiring trays or conduit and less than 10-12 inches apart, the possibility for undesired communication between units exists. When this occurs, intermittent or continuous "No contact" is typically seen. Other unexpected errors may also be seen.
Refer to section 5.3.10 for further instructions.
Fig. 2 Principle of mains borne signalling
TM01 7862 4999
Pos. Description
1 CU 301
2 Diaphragm tank (2 gal.)
3 Pressure sensor
4 SQE pump
1
4
2
3
TM01 8495 1606
Pos. Description
1 Supply to the electronics
2 Signal coils
3 Capacitor
4
Electronics for the control of the communication
5 On/Off button
6 Sensor signal
7 Mains supply
8 Communication signals
R 100
CU 301
1
5
2
4
3
6
7
8
CU 301
Page 6
6
When does the pump start?
The pump starts as a consequence of
• a high flow or
• a low pressure or
• a combination of both. To ensure that the pump is started when water is
consumed, a flow detection is required. The flow is detected via pressure changes in the system. When water is consumed, the pressure will drop accord­ingly depending on the size of the diaphragm tank and the water flow:
• at a low flow, the pressure will drop slowly.
• at a high flow, the pressure will drop quickly. See fig. 3.
Fig. 3 Pressure changes in relation to flow
Note: When the pressure is dropping 1.4 psi/s or
faster, the pump will start immediately. With a diaphragm tank of 2 gal., the pump will start at
a flow rate of approx. 0.8 gpm.
Note: If a larger tank is used, the flow must be higher
before the pump starts.
Consumption up to 0.8 gpm
The pump will start when the pressure has dropped to 7 psi below the pressure setting.
The pump will run until the pressure is 7 psi above the pressure setting.
Flow detection
During pump operation, i.e. when water is con­sumed, the CU 301 will adjust the pump speed to maintain a constant pressure. In order to stop the pump when no water is consumed, the CU 301 per­forms flow detection every 10 seconds.
The pump speed is reduced and pressure is read. A pressure drop indicates that water is being con­sumed and the pump speed is resumed, see fig. 4.
If the pump speed can be reduced without any pres­sure drop being registered, this indicates that no water is consumed. The diaphragm tank will be filled with water and the pump will be stopped.
Fig. 4 Flow detection every 10 seconds
during operation
System limits
Even though the CU 301 is controlling the pressure within ±3 psi, bigger pressure variations may occur in the system. If the consumption is suddenly changed, e.g. if a tap is opened, the water must start flowing before the pressure can be made constant again. Such dynamic variations depend on the pipework, but, typically, they will lie between 7 and 14 psi.
If the desired consumption is higher than the quantity the pump is able to deliver at the desired pressure, the pressure follows the pump curve as illustrated in the far right of fig. 5.
Fig. 5 Possible pressure variations during
constant-pressure operation
A = Pressure setting
TM01 8545 0400
Pressure
Time
Low flow
High flow
TM01 8546 0400TM01 8634 0500
Pressure
Time
Flow detection
10 s10 s
Controlling ±3 psi
Dynamic variations ±7 psi
Pressure
Start
-7 psi
A
Stop +7 psi
gpm
0.8
low
Flow
Page 7
7
1.3 System sizing
To ensure the correct function of the system, it is important that the pump is of the right type.
During operation, the CU 301 controls the pump speed within the range from 3,000 rpm to 10,700 rpm, see fig. 6.
It is recommended to follow the guidelines below.
Fig. 6 Pump curves at 3,000 rpm and
10,700 rpm
A: Minimum head at no flow. B: Maximum head at rated flow. The following must be fulfilled:
• Minimum head at no flow < static head + system pressure.
Comment: If this is not fulfilled, the pressure may
exceed the pressure set on the CU 301.
• Maximum head at rated flow > dynamic head + system pressure.
Comment: If this is not fulfilled, the pressure may
fall below the pressure set on the CU 301.
Maximum head at rated flow and minimum head at no flow can be found in the following sections.
1.4 SQE and SQE-NE
TM01 8547 0400
H [ft]
Q [gpm]
B
A
Pump curve at 10,700 rpm
Pump curve at 3,000 rpm
Q
rated flow
Pump type
Min. head
at 0 gpm,
3,000 rpm
Max. head
at rated flow,
10,700 rpm
[feet] [feet]
5 SQE-90 12 104
5 SQE-140 18 161
5 SQE-180 24 218
5 SQE-230 31 275
5 SQE-270 37 332
5 SQE-320 43 389
5 SQE-360 49 446
5 SQE-410 55 503
5 SQE-450 61 560
10 SQE-110 12 102
10 SQE-160 17 158
10 SQE-200 23 214
10 SQE-240 29 270
10 SQE-290 34 326
10 SQE-330 40 382
15 SQE-70 10 80
15 SQE-110 4 121
15 SQE-150 19 161
15 SQE-180 24 202
15 SQE-220 29 242
15 SQE-250 33 283
15 SQE-290 38 323
22 SQE-40 5 35
22 SQE-80 9 75
22 SQE-120 14 115
22 SQE-160 18 155
22 SQE-190 23 195
22 SQE-220 27 235
30 SQE-40 5 31
30 SQE-90 11 78
30 SQE-130 16 125
10 SQE-100 NE 10 96
10 SQE-140 NE 15 134
10 SQE-180 NE 20 173
10 SQE-220 NE 25 212
10 SQE-260 NE 30 251
10 SQE-300 NE 34 290
10 SQE-340 NE 39 329
22 SQE-40 NE 35 290
22 SQE-80 NE 39 322
22 SQE-110 NE 42 353
22 SQE-140 NE 46 385
22 SQE-180 NE 50 417
22 SQE-210 NE 54 448
Page 8
8
1.5 Positioning the pressure sensor
Pressure losses often cause inconvenience to the user. The CU 301 keeps the pressure constant in the place where the pressure sensor is positioned, see fig. 7.
Fig. 7 Pressure sensor position
In fig. 7, tap 1 is placed close to the pressure sensor. Therefore, the pressure will be kept nearly constant at tap 1, as the friction loss is small. At the shower and tap 2, the friction loss is greater. This, of course, depends on the piping.
Therefore, it is recommended that the pressure sen­sor be positioned as close to the places of consump­tion as possible.
1.6 Precharge pressure setting
The CU 301 is designed to work with a 2 gal. dia­phragm tank.
The precharge pressure of the diaphragm tank must be set to 70% of the pressure setting in order to use the tank to the limit of its capacity. This is of course especially important when the tank volume is limited to 2 gal.
Use the values in the following table. Prechange pressure is measured with 0 psi in the
pipeline:
Note: If the precharge pressure is higher than the
pressure setting, the system will have difficulty con­troling the pressure.
If the user wants to adjust the pressure without changing the precharge pressure of the diaphragm tank, the precharge pressure must be equal to the lowest pressure setting used. This means that the control will work but that the pressure fluctuations might increase.
1.7 Pressure relief valve
In order to provide protection against the possibility of an overpressurization, a pressure relieve valve should be installed down stream of the well head. The setpoint of the pressure relief valve should be at least 30 psi above the pressure setting, see section
2.3.
If a relief valve is installed, it is recommended that its discharge be plumbed into an appropriate drainage point.
TM01 7862 4999
Setting
[psi]
Precharge pressure
[psi]
40 28
50 35
60 42
70 49
80 56
90 63
100 70
Tap 1
Tap 2
Pressure sensor
Page 9
9
2. Operating functions
2.1 On/Off button
Fig. 8 On/Off button
The green and red indicator lights in the On/Off but­ton indicate pump operating condition as follows:
* If the On/Off button has been used to stop the
pump, this button must also be used for restarting.
Any alarm indication can be reset by pressing the On/Off button.
If the On/Off button is pressed for more than 5 sec­onds, the pump is started, irrespective of any active fault/alarm indications and sensor signals.
When the On/Off button is released, the pump will stop, if the alarm still exists.
IMPORTANT Setting this button to the OFF position DOES
NOT remove power from the pump. Before ser­vicing the pump, remove power at the service breaker.
2.2 Indication of pump operation
On the graphical illustration on the CU 301 front, the riser pipe shows running light when the pump is operating. When the pump is not operating, none of the indicator lights are on, see fig. 9.
Fig. 9 Indication of pump operation
The indication of pump operation can be changed by means of the R100.
Possible settings:
• "Running light" during pump operation (factory setting).
• "Constant light" during pump operation.
2.3 Pressure setting
The two arrow buttons on the CU 301 front are used for the pressure setting, see fig. 10.
Fig. 10 Pressure setting and indication
TM02 4169 1606
Indication Description
Green indicator light permanently on
The system is operational.
Green indicator light off
The system is not opera­tional.
Red indicator light permanently on
Pump has been stopped by means of the On/Off button.*
Red indicator light flashing
The CU 301 is communicat­ing with the R100.
PSI 100
90
80
70
60
50
40
Green indi­cator light
Red indica­tor light
TM02 4170 1606TM02 4171 1606
PSI 100
90
80
70
60
50
40
PSI 100
90
80
70
60
50
40
PSI 100
90
80
70
60
50
40
Page 10
10
Indication of pressure setting
The system pressure set is indicated by a yellow indicator light, which is permanently on.
Setting range: 40-100 psi.
Arrow-up button
When this button is pressed, the system pressure setting is increased in steps of 10 psi.
Arrow-down button
When this button is pressed, the system pressure setting is decreased in steps of 10 psi.
2.4 Button locking
The buttons on the CU 301 can be locked/unlocked by pressing the two arrow buttons simultaneously for 5 seconds or via the R100 remote control.
Note: When the arrow buttons are used for locking,
take care not to inadvertently change the pressure setting.
Use the following procedure:
1. Set the pressure one step up.
2. Press the arrow-down button as the first one when pressing the two buttons.
Fig. 11 Button lock indication
When the buttons are locked, the indicator light is permanently on, see fig. 11.
For further information, see section 5.3.8 Buttons on the CU 301.
3. Alarm functions
The CU 301 continuously receives operating data from the pump. The alarm functions indicated on the CU 301 front are described in the following sections.
3.1 Service alarm
If one or more factory-set alarm values are exceeded, the indicator light for service alarm is per­manently on, see fig. 12.
Fig. 12 Service alarm indicator
Possible alarms:
• Sensor defective
• Overload
• Overtemperature
• Speed reduction
• Voltage alarm
• No contact to pump. The possible alarms and how to identify them and
make the relevant corrections are described in sec-
tion 7.1 Service.
TM02 4172 1606
PSI 100
90
80
70
60
50
40
TM02 4173 1606
PSI 100
90 80
70 60 50
40
Page 11
11
3.2 Dry-running protection
The purpose of the dry-running protection is to pro­tect the pump in case of insufficient water flow.
The dry-running protection makes the conventional dry-running protection unnecessary.
No additional cables to the motor are required. The
dry-running settings shown in section 8. Technical data, are built into the pump and automatically trans-
mitted to the CU 301. These settings can be changed via the R100.
When air enters the pump together with water, the pump power decreases, and pressure drops, caus­ing the motor to increase speed. If the power con­sumption falls below the dry run setting for an accu­mulated time of 5 seconds, and the motor speed is within 1,000 rpm of the maximum speed setting as
defined in the section 5.3.6, the CU 301 stops the
pump and declares a dry-running alarm. When the motor is stopped, the dry-running indicator
light is permanently on, see fig. 13, pos. A.
Fig. 13 Dry-running indicator light
Restarting
After 5 minutes (factory setting) or the period set by
means of the R100, display 5.3.4 Automatic restart,
the motor will restart automatically.
TM02 4170 1606
Possible cause Remedy
The pump performance is too high compared to the well yield.
Replace the pump with a smaller one.
Reduce pump perfor­mance using the R100,
display 5.3.6 Maximum speed.
Well screen is blocked. Well service is required.
PSI 100
90
80
70
60
50
40
A
Page 12
12
4. Position of LEDs
Fig. 14 Position of the LEDs inside the CU 301
TM01 8537 1606
1
2
3
4
5
Pos. Indication Descript ion
1 +24 V overload Permanent red light when the internal 24 VDC supply is overloaded.
2 +24 V Permanent green light when the internal 24 VDC supply is OK.
3 +10 V Permanent green light when the internal 10 VDC supply is OK.
4 +5 V Permanent green light when the internal 5 VDC supply is OK.
5
9 indicator lights:
Control indicator Flashing green light when the pump control is working correctly.
Min. speed
Permanent yellow light when the pump is running at minimum speed, 3,000 rpm.
Max. speed
Permanent yellow light when the pump is running at maximum speed, 10,700 rpm.
Sensor defective *) Permanent red light when the sensor signal is out of signal range.
Overload *)
Permanent red light when the motor load exceeds the stop limit,
see section 8. Technical data.
Overtemperature *)
Permanent red light when the motor temperature exceeds the stop limit,
see section 8. Technical data.
Speed reduction *)
Permanent red light when the pump speed is reduced,
see section 8. Technical data.
Voltage alarm *)
Permanent red light when the supply voltage is out of range, see section
8. Technical data.
No contact to pump *)
Permanent red light when communication between the CU 301 and the pump is impossible.
*) Press the On/Off button to reset the alarm indication.
Page 13
13
5. CU 3 01 with R100
The R100 remote control can be used as a supple­ment for the installer and as an excellent trouble­shooting tool. Grundfos highly recommends the use of one for diagnosing problems and accessing sys­tem information unavailable through other means. The R100 provides wireless communication with the CU 301.
Note: It is not necessary to use the R100 to operate
the system. The R100 offers additional features. The R100 communicates via infrared light. During
communication, there must be visual contact between the CU 301 and the R100. The best visual contact between the two units is obtained by pointing the R100 at the lower arrow button or by removing the front cover and pointing the R100 at the right side of the CU 301, see fig. 15.
Fig. 15 IR communication between the CU 301
and the R100
The R100 offers possibilities of altering factory set­tings and reviewing operating status of the pump.
When the communication between the R100 and CU 301 has been established, the red indicator light in the On/Off button will flash.
For general use of the R100, see the operating instructions included with it.
The menu structure for the R100 and CU 301 is divided into four parallel menus, each including a number of displays.
0. GENERAL , see operating instructions for the
R100.
1. OPERATION
2. STATUS
3. INSTALLATION
Menu overview, see fig. 16, page 14.
Note: The number stated at each individual display
in fig. 16 refers to the section in which the display is described.
TM01 7861 4701
R100
R100
Page 14
14
Fig. 16 Menu overview
5.1.1
5.1.2
5.1.3
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.3.2
5.3.1
5.3.3
5.3.4
5.3.5
5.3.6
5.3.7
5.3.8
5.3.9
5.2.6
5.3.10
0. GENERAL 1. OPERATION 2. STATUS 3. INSTALLATION
5.1.3
Page 15
15
5.1 Menu OPERATION
The OPERATION menu for the CU 301 offers the possibility of setting and reading operating parame­ters.
Factory settings are marked in bold-faced type
under each individual display.
5.1.1 Pressure setting
Set the required pressure.
Setting range
40-100 psi (10 psi intervals), 50 psi.
Relation to other displays
The setting in display 5.1.1 Pressure setting is over-
ridden by the "Max." and "Min." settings in the dis-
plays 5.1.2 Operating mode and 5.3.3 Maximum pressure setting.
5.1.2 Operating mode
Select one of the following operating modes:
Max.
Pump operation is set to maximum speed, irre­spective of the pressure setting. The maximum
speed is set in display 5.3.6 Maximum speed
(factory setting: 10,700 min
-1
).
Normal
Normal operating mode, i.e. pump operation is based on the pressure set in display
5.1.1 Pressure setting.
Min.
Pump operation is set to minimum speed, 3,000 min
-1
, irrespective of the pressure setting.
Stop
The pump is stopped.
If the On/Off button has been used to stop the pump, this button must also be used for restarting.
Relation to other displays
The "Max." and "Min." settings override the pressure
setting in display 5.1.1 Pressure setting.
5.1.3 Alarm
This display shows the current alarm status. Possible alarms are described in the following table:
* The pump will attempt to operate in on/off mode
starting at 7 psi below pressure setting and stop­ping at 7 psi above pressure setting. The system must be reset every 250 stops.
The R100 can retrieve the last five alarms that the CU 301 experienced. They are displayed in order of occurrence with "Alarm log 1" being the most recent.
TM CU301_1_01 US TM CU301_1_02 US
TM CU301_1_03 US
Alarm indication
Description
No fault indica­tion
No alarms are registered by the CU 301.
No contact to pump
No communication between the CU 301 and the pump.*
Overvoltage
The supply voltage exceeds the limit value.
Undervoltage
The supply voltage is below the limit value.
Dry running
The dry-running protection of the pump has been activated.
Overtemperature
The motor temperature exceeds the limit value.
Overload
The current consumption of the motor exceeds the limit value.
Sensor defective
The sensor signal has fallen out­side the measuring range set. The sensor signal of a 4-20 mA or 2-10 V sensor is below 2 mA or 1 V respectively.
TM CU301_1_04 US
Page 16
16
5.2 Menu STATUS
The STATUS menu for the CU 301 provides operat­ing data about pump/motor and sensor. It is not pos­sible to change or set values in this menu.
When [OK] is pressed continuously in this display, the displayed value is being updated.
The measuring accuracy is stated in section
8. Technical data.
5.2.1 Operating mode
Possible operating modes:
Max.
Pump operation has been set to maximum speed, i.e. 10,700 min
-1
.
Normal
Normal operating mode, i.e. pump operation is based on the pressure set in display
5.1.1 Pressure setting.
Min.
Pump operation has been set to minimum speed, 3,000 min
-1
.
Stop
The pump has stopped.
The operating mode was selected from one of the following:
CU 301 (On/Off button on the CU 301)
R100
Sensor (signals received via the sensor input).
5.2.2 Actual pressure
The actual system pressure measured by the pres­sure sensor.
Tolerance: ±1%.
5.2.3 Speed
The actual speed stated in min
-1
(rpm).
Tolerance: ±1%.
5.2.4 Temperature
The actual temperature of the motor electronics stated in "C" or "F", based on language selected in "settings".
Tolerance: ±5%.
Relation to other dis play s
To select "F", choose the language "US English" in the settings menu.
5.2.5 Power input and power consumption
Power input
The actual motor power from the electricity supply. The power input is displayed in W (watt).
Note: This value is used for the calculation of mini-
mum power limit (dry-running stop).
Power consumption
The accumulated motor power consumption in kWh. The value of power consumption is accumulated
from the pump’s birth and it cannot be reset. The value
• is stored in the motor electronics, and it is kept even if the CU 301 is replaced.
• is updated in the software every 2 minutes of con­tinuous operation. The displayed value is updated every two hours.
Tolerance: ±5%.
TM CU301_2_01 USTM CU301_2_02 US
TM CU301_2_03 USTM CU301_2_04 US TM CU301_2_05 US
Page 17
17
5.2.6 Operating hours and number of starts
Operating hours
The number of operating hours is accumulated from the pump’s birth and it cannot be reset.
The value
• is stored in the motor electronics, and it is kept even if the CU 301 is replaced.
• is updated in the software every 2 minutes of con­tinuous operation. The displayed value is updated every two hours.
Number of starts
The number of starts is accumulated from the pump’s birth and it cannot be reset.
The value is stored in the motor electronics, and it is kept even if the CU 301 is replaced.
5.3 Menu INSTALLATION
The INSTALLATION menu for the CU 301 offers the possibility of configuring the CU 301, pump/motor and sensor.
Factory settings are marked in bold-faced type
under each individual display.
5.3.1 Sensor
Make the following settings according to sensor type:
• Sensor output signal: "–" (not active), 0-20 mA,
4-20 mA, 0-10 V, 2-10 V.
• Setting range unit: bar, psi.
Setting range, psi:
• Minimum value: 0.
• Maximum value: 40-120 (40, 50, 60, 70 ... 120).
Setting range, bar:
• Minimum value: 0.
• Maximum value: 2-6 (2, 2.5, 3, 3.5 ... 6.0).
Note: The pressure sensor used must measure the
pressure in the actual measuring unit.
Relation to other displays
The measuring unit appearing in display 5.2.2 Actual pressure will be identical to the measuring unit in the
front cover.
Exception: If "Manual" is selected in display
5.3.2 Choice of sensor, the sensor can be set, irre-
spective of the front cover.
If changes are made in display 5.3.1 Sensor, the set­ting in display 5.3.2 Choice of sensor is changed to
"Manual". If the original setting is resumed, it is necessary to
change the setting in display 5.3.2 Choice of sensor
from "Manual" to "Automatic".
5.3.2 Choice of sensor
The following settings are available:
Automatic
Manual.
Relation to other displays
If, for some reason, the setting in this display has changed to "Manual" and this is changed to
"Automatic", the setting of the displays 5.3.1 Sensor and 5.3.3 Maximum pressure setting will change to
the factory setting.
5.3.3 Maximum pressure setting
The setting of this display overrules the possibility of using the arrow button on the CU 301 front to increase the pressure to a setting above the "Maximum pressure setting".
The following settings are available:
40-100 psi (10 psi intervals).
Relation to other displays
The setting of this display overrules the possibility of
using the display 5.1.1 Pressure setting to increase
the pressure to a setting above the "Maximum pres­sure setting".
If the setting is changed from 100 psi, the setting in
display 5.3.2 Choice of sensor changes from
"Automatic" to "Manual".
TM CU301_2_06 USTM CU301_3_01 US
TM CU301_3_02 USTM CU301_3_03 US
Page 18
18
5.3.4 Automatic restart
Set the automatic restart time from stop, caused by an alarm, to restart attempt.
The following settings are available:
Time
0:05
• "–" (not active)
1, 2, ... 30 m (1 min. intervals)
30, 45, 1 h, ... 2 h (15 min. intervals) 2 h 30 m, 3 h, ... 4 h (30 min. intervals).
Double
Yes
No.
When "Yes" is selected, the restart time set will be doubled automatically for every 10 motor stops caused by an alarm. The time is doubled up to a stop time of 4 hours.
After 10 hours of operation without an alarm, the restart time is automatically set to:
• the time set in the "Time" field or
5 min. (factory setting) if no setting was made in
the "Time" field.
5.3.5 Dry-running stop
The dry-running stop value is factory-set. The factory setting depends on the power rating of
the motor. The following settings are default:
• Motor type 0.5 hp, dry-running stop = 300 W. Note: For 10 SQE 160 and 10 SQE 160 N pumps,
the value is 550 W.
• Motor type 0.75 hp, dry-running stop = 680 W.
• Motor type 1.0 hp, dry-running stop = 800 W.
• Motor type 1.5 hp, dry-running stop = 900 W.
When the dry-running protection is to be active, the minimum value of the pump power input must be set in this display.
Setting range: 0-2500 W (10 W intervals).
Relation to other dis play s
The actual pump power input can be read in display
5.2.5 Power input and power consumption.
If the maximum pump speed has been reduced in
display 5.3.6 Maximum speed, the dry-running stop
value must be changed.
5.3.6 Maximum speed
Set the maximum speed.
Setting range: 3,000-10,700 min
-1
(100 min
-1
inter-
vals).
Dry-running stop at reduced maximum pump speed
If the maximum pump speed has been reduced, the
dry-running stop value in display 5.3.5 Dry-running stop must be changed.
Calculating the minimum power limit Note: The calculated value is used in display
5.3.5 Dry-running stop.
Note: If the pump is worn, a renewed calculation of
the minimum power limit may be required.
5.3.7 Cut-in speed
In the case of an oversized pump or drastically changing water levels, this function may cause an excess pressure, at start-up, in relation to the desired discharge pressure. The cut-in speed can therefore be lowered to compensate.
Setting range: 3,000-10,700 min
-1
(8,200 min
-1
)
(100 min
-1
intervals).
TM CU301_3_04 USTM CU301_3_05 US
TM CU301_3_06 US
Step Action
1
Start the pump against closed discharge valve.
2
Read the power input (P
1
) in display
5.2.5 Power input and power consumption.
3
Calculate the minimum power limit as follows: Power limit [W] = P
1
· 0.9.
TM CU301_3_07US
Page 19
19
Relation to other displays
The maximum speed setting can be read in display
5.3.6 Maximum speed.
The maximum pump speed setting overrules the cut­in speed setting.
5.3.8 Buttons on the CU 301
The buttons on the CU 301 can be set to:
Active
Not active.
5.3.9 Indication of pump operation
The following settings are available:
Running light
• Constant light.
5.3.10 Number
Allocate a number to the CU 301 and the pump con­nected. The CU 301 and the pump must have the same number.
The CU 301 control unit communicates with the SQE pumps via the pump power cable to turn the pumps on and off, set motor speed and monitor pump sta­tus.
The technique used for performing this communica­tion impresses a high frequency data signal on the pump power cable that is picked off by internal pump electronics and then decoded into command instruc­tions. This is the reason for assigning unique num­bers to each CU 301 in a multiple unit installation.
The unique number serves as a communication address between each CU 301 control unit/motor pair.
In situations where multiple CU 301 pump power cables are run parallel in wiring trays or conduit and less than 10-12 inches apart, the possibility for undesired communication between units exists. When this occurs, intermittent or continuous "No contact" is typically seen. Other unexpected errors may also be seen.
There are two approaches available to eliminating the possibility of this occurring:
• Physical separation of cables: Maintain a minimum distance of 10-12 inches between pump power cables, and never place more than one cable in a conduit.
• Use shielded cable: The use of shielded cable prevents cross commu­nication between parallel cables and allows shar­ing of conduit and cable trays. Tie the cable shield to earth only at the CU 301 control unit.
Suitable cables:
In addition, Grundfos recommends applying power to only one CU 301 unit/motor at a time while program­ming the CU 301 number with the R100. This will prevent the possibility of two pumps hearing the same number assignment command.
TM CU301_3_08 USTM CU301_3_09 US TM CU301_3_10 US
Manf. Part# Gage
Anixter 2A-1403S 14
Anixter 2A-1203S 12
Anixter 2A-1003S 10
Anixter (1-800-321-1486)
Page 20
20
6. Print
The actual data in the R100 can be printed on a Hewlett-Packard printer type HP82240B.
Navigate the R100 to the print menu and point the R100 at the IR sensor of the printer and press [OK]. The following information will be printed:
TM03 4040 1406
Page 21
21
7. Troubleshooting
7.1 Service
The CU 301 continuously receives operating data from the pump. In case of an alarm, the service indi­cator light is permanently on, see fig. 17.
Fig. 17 Service alarm indicator
The service indicator light will be permanently on if one of the following alarm situations occurs:
• Sensor defective
• Overload
• Overtemperature
• Speed reduction
• Voltage alarm
• No contact to pump. To identify the cause of the service alarm, it is
necessary to remove the front cover from the CU 301 or use the R100. Fit the front cover as shown in fig. 18 to avoid disconnecting the multi-core cable.
A number of LEDs are mounted on the supply board
inside the CU 301, see section 4. Position of LEDs.
Fig. 18 LEDs and alarm texts on the supply board
Before starting any work on the CU 301, make sure that the electricity supply has been switched off and that it cannot be accidentally switched on.
TM02 4173 1606
PSI 100
90 80
70 60 50
40
TM01 8435 1606
MIN. SPEED
CONTROL INDICATOR
SENSOR DEFECTIVE
OVER LOAD
OVERTEMPERATURE
SPEED REDUCTION
VOLTAGE ALARM
NO CONTACT TO PUMP
MAX. SPEED
CU 301
b
ar
5.0
4.5
4.0
3.5
3.0
2
.5
2.0
Page 22
22
Fault Possible cause Remedy
1. No light in the front cover.
a) The ribbon cable con-
nection is loose or de­fective.
• Is the control indicator LED flashing? If not, the CU 301 is defective.
• Check that the ribbon cable connection is secure.
2. The pump does not start. The green indicator light in the On/Off but­ton is on. No alarm is indicated.
a) The CU 301, the
pressure sensor or the pump is defective.
Check
• that the control indicator LED is flashing. If not, the CU 301 is defective.
• that the system pressure is 7 psi below the pressure setting. If so, the pump is supposed to start. Open a tap to be sure. If the pump starts, the system is probably OK. The system pressure can be read on the pressure gauge.
• Refer to fault 13 to troubleshoot the pressure sensor.
If the pump has not started yet, proceed as follows:
• Press the On/Off button for 5 seconds. If the pump starts, the CU 301 or the sensor may be defective.
Note: The pressure is not controlled and may rise to
a high level.
3. The pressure is not constant.
a) The pump is not of
the correct type or the precharge pressure of the diaphragm tank is incorrect.
Check
• that the LED for Max. speed or Min. speed is on. If so, this indicates that the pump has reached a limit.
See section 1.3 System sizing.
Replace the pump, if necessary.
• the precharge pressure of the diaphragm tank.
Note: Remember to stop and drain the system before the pressure is checked.
• Make sure the diaphragm tank is the 2 gal. size.
• whether the sensor is positioned far away from the tap. If so, the pressure variations may be caused by fric-
tion losses, see section 1.5 Positioning the pressure sensor.
b) No contact between
SQE pump and CU 301 control unit.
Check that the LED for "No contact to pump" is on. If so, go to fault no. 14.
4. The pump is running continuously.
a) The pump cannot de-
liver the set pressure. The CU 301 or the sensor is defective.
• Try to lower the pressure setting, see section
1.3 System sizing. Note that the pump may run for
about 15 to 20 seconds before it stops.
• Check that the control indicator LED is flashing.
• Check that the pipe end of the sensor is not blocked. If so, remove the blockage.
• Try to stop the pump by means of the On/Off button. If this is not possible, the CU 301 is defective. Replace the CU 301.
• Refer to fault 13 to troubleshoot the pressure sensor.
(continued on the following page)
Page 23
23
5. The CU 301 indi­cates "No contact to pump".
a) The motor is not an
MSE 3.
If the pump has already worked satisfactorily with a CU 301 or a CU 300, the motor can be expected to be an MSE 3. There is no technical way of determining the motor type. The only way is to read the nameplate engraved in the motor sleeve.
b) The pump cable is
longer than 650 feet.
Reduce the length of the pump cable.
c) Cable breakage. Switch off the mains supply to the CU 301.
Connect motor leads directly to the mains supply. Switch on the mains supply again. The pump is now connected direct to the mains supply without interfer­ence from the CU 301. Does the motor start?
Yes: The cable is OK. Go to point d). No: Switch off the mains supply again. Remove cable
and cable plug from the motor and ohm out cable in­cluding plug. Is the cable OK?
Yes: The motor is defective. Replace the motor. No: Replace the cable.
d) Cross communica-
tion with adjacent CU 301.
If another CU 301 is installed:
• Insure each unit has a unique number assigned.
See section 5.3.10 Number.
• If pump cables run parallel to each other, physically separate them by 12-14 inches or rewire using shielded cable.
e) The CU 301 commu-
nication part is defec­tive.
Are the three CU 301 supply board LEDs in pos. 2, 3 and 4 on and is the control indicator LED flashing?
See section 4. Position of LEDs.
Yes:
• The mains supply is OK.
• Assign the system a new number.
If this does not work, the CU 301 or the motor commu­nication part is defective. Replace the CU 301 and give the new system a num­ber between 1 and 64 in order to obtain correspon­dence between the numbering of the SQE pump and the CU 301.
Note: Two systems on the same mains supply must not
have the same number! Is the LED "No contact to pump" of the new CU 301 also on?
Yes: The CU 301 is OK. Go to point f). No: The CU 301 which was removed is defective.
f) The MSE 3 motor
communication part is defective.
As a consequence of the above-mentioned checks, replace the MSE 3 motor.
6. Even AFTER replace­ment, the CU 301 in­dicates "No contact to pump".
a) Numbering of SQE
pump and CU 301 is different.
If an SQE/CU 301 system has been given a number, this number is stored in both the SQE and CU 301. A new CU 301 or SQE may not have a number corre­sponding to the number stored in the previous unit. Therefore, "No contact to pump" is indicated even if there is no fault. Give a new system the number between 1 and 64 in order to obtain correspondence between the numbering of the SQE pump and the CU 301.
Note: Two systems on the same mains supply must not
have the same number!
(continued on the following page)
Page 24
24
7. The CU 301 indi­cates "Overvoltage" or "Undervoltage".
a) The supply voltage is
unstable or outside the voltage range specified for the in­stalled motor type.
Check - possibly over a period of time - that the supply voltage is according to the values below.
• Motor type 0.5 hp = 198-315 V
• Motor type 0.75 hp = 198-315 V
• Motor type 1.0 hp = 207-315 V
• Motor type 1.5 hp = 207-315 V. Voltage range for 100-115 V motors:
• Motor type 0.5 hp = 90-180 V.
Note: As the voltage is detected at the motor, allow for
the voltage drop in the pump cable.
8. The CU 301 indi­cates "Dry running".
If the power consumption is lower than the dry-running stop setting and the motor speed is within 1,000 rpm of programmed maximum speed, for an accumulated period of 5 seconds, the pump will be stopped.
a) The pump perfor-
mance is too high for the well yield.
Replace the pump with a smaller pump or reduce the pump performance, by lowering maximum speed, or re­ducing set pressure.
b) The well screen is
blocked.
Check the well capacity and restore water supply to the well.
c) The dry-running stop
setting is incorrect.
Check and correct the setting, see section 5.3.5 Dry- running stop.
9. The CU 301 indi­cates "Speed reduc­tion" and "Undervoltage".
Speed reduction is activated so as to maintain a reduced performance. When the supply voltage falls so low that it can no longer supply the necessary current to maintain 3,000 min
-1
, the pump will be stopped.
a) The supply voltage is
unstable or lower than the voltage range specified for the installed motor type.
Restore correct supply voltage.
b) The pump is not of
the correct type.
Install correct pump type.
c) The voltage drop in
the pump cable is too great.
Replace the pump cable with lower gauge wires.
10. The CU 301 indi­cates "Speed reduc­tion" and "Overload".
Speed reduction is activated so as to maintain a reduced performance.
a) The pump is worn or
blocked.
The pump must be serviced.
b) The pump is too large
for the installed mo­tor.
Replace pump or motor.
11. The CU 301 indi­cates "Overtempera­ture".
The temperature sensor in the motor is sensing a temperature above the values
stated in 8. Technical data, factory settings.
a) Insufficient cooling of
the motor.
Restore correct cooling of the motor. The flow velocity past the motor should be at least 0.5 ft/s.
12. The CU 301 indi­cates "Overload".
a) The pump is worn or
blocked.
The pump must be serviced.
b) The pump is too large
for the installed mo­tor.
Replace pump or motor.
(continued on the following page)
Page 25
25
8. Technical data
Supply voltage
1 x 100-240 V –10%/+6%, 50/60 Hz, PE.
Power consumption
5 W.
Back-up fuse
Maximum 16 A.
Current consumption
Maximum 130 mA.
Mains borne signalling
Frequency shift keying (FSK). (132.45 kHz ±0.6 kHz).
Enclosure class
IP 55.
Maximum length between CU 301 and pump
650 feet.
Ambient temperature
• During operation: –22 to +113°F (–30 to +45°C) (must not be exposed to direct sunlight).
• During storage: –22 to +140°F (–30 to +60°C).
Weight
4.5 lb.
Relative air humidity
Maximum 95%.
Materials
The CU 301 box is made of black PPO.
EMC (electromagnetic compatibility)
According to EN 55014 and EN 55014-2.
Dimensional sketch
Fig. 19 Dimensional sketch
13. The CU 301 indi­cates "Sensor defec­tive".
a) The pressure sensor
is defective.
Check that the sensor is wired correctly. Check that the R100 setting of the sensor is correct,
see section 5.3.1.
If the sensor type is 4-20 mA, measure the DC voltage across the sensor input terminals. If the DC voltage measured at the sensor input terminals is not between 2 and 10 V the sensor or wiring is defective. Refer to
section 9., page 28, for additional troubleshooting as-
sistance. Replace defective parts. Are the LED "Sensor defective" and the LED, pos. 1, on?
See section 4. Position of LEDs. Yes: The total load of 24 VDC from terminal 5 is above
100 mA. Disconnect the sensor in order to determine if it is de­fective. Replace defective sensor.
No: The load is OK, but the CU 301 sensor input may
be defective.
14. The pump is operat­ing on/off.
a) No communication. Check that the LED "No contact to pump" is on.
If so, the control unit CU 301 starts and stops the pump, based on the sensor signal only. The CU 301 has to be reset every 250 stops. Refer to fault no. 5 for remedy.
15. Excess pressure, for a short moment, at start of consumption.
a) Cut-in speed is too
high. Reduce the cut-in speed, see section 5.3.7 Cut-in speed.
TM02 4174 1606
8.8"
3.7"
7.68"
PSI 100
90 80 70 60 50
40
4.11"
4.11"
3.94"
5.53"
Page 26
26
Input for external sensor
• Voltage signal:
0-10 VDC/2-10 VDC, R
i
= 11 kΩ. Tolerance: ±3% at maximum voltage signal. #22 ga. Screened cable is recommended. Maximum cable length: 1640 ft (500 m).
• Current signal: DC 0-20 mA/4-20 mA, R
i
= 500 Ω. Tolerance: ±3% at maximum current signal. #22 ga. Screened cable is recommended. Maximum cable length: 1640 ft (500 m).
Factory settings
*) 200-240 V motors: Operation is guaranteed up to 280 VAC.
100-115 V motors: Operation is guaranteed up to 150 VAC. In order to avoid unnecessary stops, the overvoltage stop limit is as stated.
**) The 550 W dry-running limit only applies to 10 SQE 160 and 10 SQE 160 N pumps.
Accuracy of R100 readings Operation
Sensor
The sensor signal accuracy depends on the sensor type. See the sensor specifications in question.
8.1 Electrical connection
The electrical connection should be carried out by an authorized electrician.
IMPORTANT The On/Off button on the CU 301 must not be
used as a safety switch when installing and ser­vicing the pump.
Mains disconnector must be provided by the installer.
"Raintight or wet location hubs that comply with the requirements in the standard for Fittings for Conduit and Outlet Boxes, UL514B, are to be used. Suitable devices for CU 301 are rated with enclosure type 3, 3R, 3S, 4, 4X, 6 or 6P".
The supply voltage and frequency are marked on the nameplate. Make sure that the CU 301 is suitable for the electricity supply on which it will be used.
If the CU 301 is connected to an electric installation where a Ground Fault Circuit Interrupter (GFCI) is
used as an additional protection, this device must
trip out when earth fault currents with DC content (pulsating DC) occur.
The CU 301 has two terminal blocks:
• Terminals 1 to 4.
• Terminals 5 to 7. Furthermore, the CU 301 is equipped with two screw
terminals for the protective earth leads (PE). Always use copper conductors approved for 60/75°C
(140/167°F).
Alarm
200-240 V motors 100-115 V motors
SQ/SQE/ SQE-NE
0.5 hp
SQ/SQE/ SQE-NE
0.75 hp
SQ/SQE/ SQE-NE
1.0 hp
SQ/SQE/ SQE-NE
1.5 hp
All models
Sensor defective 4-20 mA (the value is stored in the CU 301)
Overload 5.2 A 8.4 A 11.2 A 12 A 11 A
Overtemperature
Stop limit: 167°F (75°C)
Stop limit:
180°F (82°C)
Stop limit:
198°F (92°C)
Stop limit:
203°F (95°C)
Stop limit:
185°F (85°C)
Restart: 145°F (63°C)
Restart: 162°F (72°C)
Restart: 180°F (82°C)
Restart: 185°F (85°C)
Restart: 167°F (75°C)
Speed reduction In connection with undervoltage or overload
Overvoltage *) 315 VAC 315 VAC 315 VAC 315 VAC 180 VAC
Undervoltage
Speed reduction when the supply voltage is below:
198 V 198 V 207 V 207 V 90 V
Stop limit: 150 V
Stop limit: 150 V
Stop limit: 150 V
Stop limit: 150 V
Stop limit: 75 V
Dry running 300 W/550 W** 680 W 800 W 900 W 300 W/550 W**
Display Accuracy
5.2.2 Actual pressure ±1.4 psi
5.2.3 Speed ±1%
5.2.4 Temperature ±5%
5.2.5 Power input and power consumption
±5%
Never make any connections on the CU 301 terminal block unless the electric­ity supply has been switched off. The CU 301 must be connected in accordance with the local rules and regulations.
Page 27
27
Fig. 20 Electrical connection of the CU 301
Legend
8.1.1 Mains supply POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. Each terminal can be con­nected to any of the two leads. Torque: 15 lbf-in.
Connect the PE terminal to the green/yellow earth lead. Torque: 9.0 - 15.3 lbf-in. Each PE terminal must be connected to an earth lead of its own.
Maximum wire size of the leads to be connected is 10 AWG.
Circuit breaker: Maximum 16 A.
Note: The leads of the mains supply must not be
connected to terminals 3 and 4 (PUMP).
8.1.2 Pump supply PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. Each terminal can be connected to any of the two leads. Torque: 15 lbf-in.
Connect the PE terminal to the green/yellow earth lead. Torque: 9.0 - 15.3 lbf-in. Each PE terminal must be connected to an earth lead of its own.
Maximum wire size of the leads to be connected is 10 AWG.
In situations where multiple CU 301 pump power cables are run parallel in wiring trays or conduit and less than 10-12 inches apart, the possibility for undesired communication between units exists. When this occurs, intermittent or continuous "No contact" is typically seen. Other unexpected errors may also be seen.
Refer to section 5.3.10 Number for further instruc-
tions.
8.1.3 Pressure sensor SENSOR, terminals 5, 6 and 7
Terminals 5, 6 and 7 (SENSOR) are used for the pressure sensor.
Sensor signals
The sensor to be connected must provide signals within one of the following ranges:
• 0-10 V
• 2-10 V
• 0-20 mA
• 4-20 mA - factory default. Changeover between current and voltage signals is
carried out by means of the R100.
Important!
The total load of terminal 5 (+24 VDC) must not exceed 100 mA.
RELAY, terminals 8 and 9
Terminals 8 and 9 (RELAY) are used for the connec­tion of an external signal transmitter (sound or light).
The operating relay is a normally open contact when the pump is not running, and closes while the pump is running.
Relay specifications
Maximum load: 230 VAC, 0.5 A.
TM03 3004 5005
SENSOR
5
6
98
7
+24V IN
GND
POWER
PE
PUMP
PE
LNLN
4
1
3
2
12 3 4
5
Pos. Description
1
Standard pressure sensor +24 VDC, brown lead, terminal 5
2
Standard pressure sensor Input signal, black lead, terminal 6
3
Standard pressure sensor Braid, terminal 7
4 Standard pressure sensor
5 Connections for operating relay
Page 28
28
9. Pressure sensor voltage chart
Voltage to pressure chart for CU 301 pressure sensors. Measure the DC voltage between "SENSOR IN" and "SENSOR GND". Voltages lower than 2 or higher than 10 indicate an incorrectly wired or a faulty sensor.
DC voltage psi DC voltage psi DC voltage psi
1.9 0.0 4.5 40.5 7.1 81.0
2.0 0.7 4.6 41.2 7.2 81.7
2.0 1.5 4.6 42.0 7.2 82.5
2.1 2.2
4.7 42.7 7.2 83.2
2.1 3.0 4.7 43.5 7.3 84.0
2.2 3.7 4.8 44.2 7.3 84.7
2.2 4.5 4.8 45.0 7.4 85.5
2.3 5.2 4.8 45.7 7.4 86.2
2.3 6.0 4.9 46.5 7.5 87.0
2.4 6.7 4.9 47.2 7.5 87.7
2.4 7.5 5.0 48.0 7.6 88.5
2.4 8.2 5.0 48.7 7.6 89.2
2.5 9.0 5.1 49.5 7.7 90.0
2.5 9.7 5.1 50.2 7.7 90.7
2.6 10.5 5.2 51.0 7.8 91.5
2.6 11.3 5.2 51.7 7.8 92.2
2.7 12.0 5.3 52.5 7.9 93.0
2.7 12.8 5.3 53.2 7.9 93.7
2.8 13.5 5.4 54.0 8.0 94.5
2.8 14.3 5.4 54.7 8.0 95.2
2.9 15.0 5.5 55.5 8.1 96.0
2.9 15.7 5.5 56.2 8.1 96.7
3.0 16.5 5.6 57.0 8.2 97.5
3.0 17.2 5.6 57.7 8.2 98.2
3.1 18.0 5.7 58.5 8.3 99.0
3.1 18.7 5.7 59.2 8.3 99.7
3.2 19.5 5.8 60.0 8.4 100.5
3.2 20.2 5.8 60.7 8.4 101.3
3.3 21.0 5.9 61.5 8.4 102.0
3.3 21.7 5.9 62.2 8.5 102.8
3.4 22.5 6.0 63.0 8.5 103.5
3.4 23.2
6.0 63.7 8.6 104.3
3.5 24.0 6.0 64.5 8.6 105.0
3.5 24.7 6.1 65.2 8.7 105.8
3.6 25.5 6.1 66.0 8.7 106.5
3.6 26.2 6.2 66.7 8.8 107.3
3.6 27.0 6.2 67.5 8.8 108.0
3.7 27.7 6.3 68.2 8.9 108.8
3.7 28.5 6.3 69.0 8.9 109.5
3.8 29.2 6.4 69.7 9.0 110.3
3.8 30.0
6.4 70.5 9.0 111.0
3.9 30.7 6.5 71.2 9 .1 111. 8
3.9 31.5 6.5 72.0 9.1 112.5
4.0 32.2 6.6 72.7 9.2 113.3
4.0 33.0 6.6 73.5 9.2 114.0
4.1 33.7 6.7 74.2 9.3 114.8
4.1 34.5 6.7 75.0 9.3 115.5
4.2 35.2 6.8 75.7 9.4 116.3
4.2 36.0 6.8 76.5 9.4 117.0
4.3 36.7 6.9 77.2 9.5 117.8
4.3 37.5 6.9 78.0 9.5 118.5
4.4 38.2 7.0 78.7 9.6 119.3
4.4 39.0 7.0 79.5 9.6 120.0
4.5 39.7 7.1 80.2
Page 29
29
10. Disposal
This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Subject to alterations.
Page 30
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
Mexico
Bombas GRUNDFOS de Mexico S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L.C.P. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Addresses revised 22.09.2005
Page 31
www.grundfos.com
Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence
L-SP-TL-019 5/06
US
R PRINTED IN USA
Loading...