Grundfos cu300 Installation And Operating Instructions Manual

CU 300
Installation and operating instructions
No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
GRUNDFOS INSTRUCTIONS
Other languages
www.grundfos.com/CU300-manual
English (GB) Installation and operating instructions

English (GB)

Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
2. General
2.1 Expansion possibilities
2.2 On/Off button
3. Mechanical installation
3.1 Location
3.2 Mounting CU 300
4. CU 300 as an alarm unit
4.1 Description
4.2 Electrical installation
4.3 Description of dry-running protection
4.4 Settings
4.5 Description of the dewatering function
5. CU 300 with constant-pressure control ­0 to 6 bar
5.1 Description
5.2 Function
5.3 Positioning the pressure sensor
5.4 System sizing
5.5 Electrical installation
5.6 Startup
6. CU 300 with constant-pressure control ­0 to 10 bar
6.1 Description
6.2 Function
6.3 Positioning the pressure sensor
6.4 System sizing
6.5 Electrical installation
6.6 Startup
7. CU 300 with constant-pressure control ­two-pump operation
7.1 Description
7.2 Function
7.3 Positioning the pressure sensor
7.4 System sizing
7.5 Electrical installation
7.6 Startup
8. CU 300 with sensors
8.1 General
8.2 Sensor functioning
8.3 Electrical installation
9. CU 300 connected to potentiometer
9.1 Description
9.2 Electrical installation
10. CU 300 connected to water meter
10.1 Description
10.2 Electrical installation
11. Constant water level
11.1 De scription
11.2 Function
2
11.3 Electrical installation
12. CU 300 connected to RS-485
12.1 Description
12.2 CU 300 connected to a PC directly
12.3 Electrical installation
3
13. Alarm functions
3
13.1 No contact
3
13.2 Overvoltage
3
13.3 Undervoltage
4
13.4 Dry running
4
13.5 Speed reduction
4
13.6 Overtemperature
4
13.7 Overload
4
13.8 Sensor alarm
5
14. CU 300 with Grundfos GO
6
14.1 Menu overview
6
15. Description of functions
7
15.1 Status
15.2 Settings
8
15.3 Alarms and warnings
8
16. Technical data
8 9
17. Disposal
9 10 11
12
12 12 13 13 14 15
16
16 16 17 17 18 19
20
20 21 22
24
24 25
26
26 27
28
28 28
Warning Prior to installation, read these
installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
Warning This product can be used by children of
eight years and up and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they are under supervision or have been instructed in the safe use of the product and understand the hazards involved.
Children must not play with the product. Cleaning and maintenance of the product must not be made by children without supervision.
29
31
31 31 32
34
34 34 35 35 36 36 37 37
37
38
40
40 40 45
46 47

1. Symbols used in this document

Note
Green
Red
Warning If these safety instructions are not
observed, it may result in personal injury.
Notes or instructions that make the job easier and ensure safe operation.

2. General

The control unit CU 300 is developed for the SQE submersible pumps.
CU 300 covers the voltage range 1 x 100-240 V - 10 %/+ 6 %, 50/60 Hz, PE.
CU 300 has the following functions:
• control of the pump on the basis of sensor signals
• setting of operating parameters
• monitoring of operation and alarm indication, if any.
CU 300 indicates the following alarms:
• no contact
• overvoltage
• undervoltage
• dry running
• speed reduction
• overtemperature
• overload
• sensor alarm.
The individual alarms are described in details in section 13. Alarm functions.
CU 300 receives alarm signals from the motor for the following parameters:
• dry running
• incipient pump or motor defect
• too high temperature in motor electronics
• supply failure.
As standard, CU 300 incorporates an alarm signal relay.

2.1 Expansion possibilities

CU 300 enables the use of the following devices:
Grundfos GO: Wireless infra-red remote control that enables change of factory settings and monitoring of the installation by calling up actual operating data, e.g. speed, operating hours and power consumption.
External sensors: Reception of data from external sensors and control according to the data received, e.g. flow rate, pressure, water level and conductivity.
External potentiometer SPP 1: Manual speed control.

2.2 On/Off button

By means of the On/Off button on CU 300, you can do the following:
• Start or stop the pump.
• Reset alarms.
Fig. 1
The green and red indicator lights in the On/Off button indicate pump operating condition as follows:
Indication Description
Green indicator light permanently on
Green indicator light flashing
Red indicator light permanently on
Red indicator light flashing
* If you use the On/Off button to stop the pump,
you must also use this button for restarting the pump. If you press the On/Off button for minimum 5 seconds, you start the pump, irrespective of any active fault or alarm indications. When you release the On/Off button, the pump will stop.
Pump is operating
Pump has been stopped by one of the following:
• a sensor
• an external on/off switch
• a stop command from the Grundfos GO
Pump has been stopped by means of the On/Off button*
CU 300 is communicating with the Grundfos GO
English (GB)
TM01 2829 4601
3

3. Mechanical installation

104.5
104.5
100
140.5
English (GB)
Warning Before starting any work on CU 300,
make sure that the power supply has been switched off and that it cannot be accidentally switched on.

3.1 Location

You can place CU 300 both indoors and outdoors. The control unit must not be exposed to direct sunlight.

3.2 Mounting CU 300

CU 300 is designed for wall mounting. The box has six mounting holes (4). See fig. 2. The
dimensions are in mm. CU 300 must be mounted as follows:
• Horizontally to allow condensed water, if any, to escape. See fig. 2.
• On a plane surface to avoid deformation of the box.
Fig. 2
CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables or wires to ensure tight connections, IP55, and cable relief.

4. CU 300 as an alarm unit

4.1 Description

When CU 300 is connected to an SQE pump, one of the eight red indicator lights on CU 300 will indicate any alarm.
The indications are based on signals from the motor and from sensors, if installed. The individual alarms are described in details in section 13. Alarm
functions.
You can connect an external alarm-signal transmitter and an external on/off switch. See section
4.2 Electrical installation concerning connection, etc.
Figure 3 shows an example of an installation with CU 300 as an alarm unit.
Fig. 3
CU 300 functions as an alarm unit for the pump. Furthermore, you can communicate with the pump via the remote control Grundfos GO, see also
TM01 2824 2498
section 14. CU 300 with Grundfos GO.
TM01 3150 4601
4

4.2 Electrical installation

K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX
RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
567
12
1098
34
111213 161514 171819
PE
TXD
LNLN
H
S1
Note
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 4
Pos. Description
S1 On/off switch for start or stop of pump
H Alarm signal transmitter (optional)
Internal alarm signal relay
K1
Relay data: 250 VAC, 1 A, AC1
4.2.1 Mains supply
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
The maximum cross-section of the leads to be connected is 6 mm
Backup fuse: Maximum 16 A.
2
.
You must not connect the leads of the mains supply to terminals 3 and 4.
English (GB)
TM01 3067 3398
5
4.2.2 Pump supply
Note
3000 min-1Max. speed
-1000 min
-1
Max. speed as set in section
15.2.22
10,700 min
-1
Motor speed
Watt
Pump power input
Pump power curve
Dry-running power limit set
English (GB)
PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
The maximum cross-section of the leads to be connected is 6 mm
2
.
4.2.3 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay is activated when the alarm and warning limits are exceeded.
You can select manual or automatic restarting in the Grundfos GO display "Automatic restarting".
Manual restarting is carried out by means of the On/ Off button on CU 300.
4.2.4 Digital input
DIG IN, terminals 11, 12 and 13
In fig. 4, the digital input is used to start and stop the pump.
You can select the function of the digital input by means of the Grundfos GO in the display "Digital input".

4.3 Description of dry-running protection

When the pump sucks air, the pump power input decreases.
If the pump power input falls below the dry-running power limit set in the Grundfos GO display "Dry­running stop", the pump will stop and CU 300 will indicate the dry-running alarm.
4.3.1 Function
The dry-running protection applies only if the motor speed lies within the maximum speed range (i.e. maximum speed less than 1000 min
Normally, maximum speed is 10,700 min you can reduce the maximum speed in the Grundfos GO display "Maximum speed". The dry-running power limit set in the display "Dry-running stop" must match the speed.
Changing the setpoint:
If you use the Grundfos GO display "Setpoint" or "External setpoint" to change the setpoint, the pump can be forced to run at a reduced speed in relation to the maximum speed. The dry-running protection will not protect the pump if the reduced speed lies outside the maximum speed range (i.e. maximum speed less 1000 min
6
-1
). See fig. 5.
-1
). See fig. 5.
-1
. However,
Constant-pressure control
In constant-pressure control mode, the dry-running protection is active, as the motor will operate at maximum speed in connection with dry running.
Pump power input curve
The curve shows the pump power input in relation to the pump speed.
Fig. 5

4.4 Settings

For a detailed description of the Grundfos GO displays, see section 14. CU 300 with Grundfos GO.
4.4.1 Required Grundfos GO settings
If the maximum speed of the pump has been reduced by more than 1000 min stop value must be changed. In order to change the dry-running protection function, you must make the following Grundfos GO settings.
1. Set "Dry-running protection" to "Active".
In certain installations, it may be necessary to disable the dry-running protection. The disabling applies to the dry-running power limit set in the display 15.2.21 Dry-running stop. See fig. 5.
Set the dry-running power limit in the display
15.2.21 Dry-running stop by following the
procedure below:
– Start the pump against a closed discharge
pipe.
– Read the input power (P1) in the display
15.1.9 Power consumption.
– Calculate the dry-running power limit: P1 x 0.9
[W].
– Set this value in the display 15.2.21 Dry-
running stop.
-1
, the dry-running
TM01 2689 2598

4.5 Description of the dewatering function

Note
35
1
125
60
60
Off time [minutes]
On time [minutes]
When the pump sucks air, the pump power input decreases.
If the pump power input falls below the dry-running power limit set in the display 15.2.21 Dry-running
stop, the pump will stop.
During dewatering, the green indicator light in the On/Off button on CU 300 is flashing to indicate that the pump has stopped.
4.5.1 Applications
You can use the dewatering function in applications where the pump often runs dry, e.g.:
• In boreholes with a low yield.
• In boreholes and building sites where the water table should be lowered.
4.5.2 Function
The dewatering function works as follows:
1. The pump is operating.
2. The pump sucks air due to a drop in the water level.
3. The load decreases, and consequently the pump power input does as well.
4. The pump stops when the power input falls to the dry-running power limit set in the Grundfos GO display 15.2.21 Dry-running stop.
The length of the stop time depends on the setting you have made in the Grundfos GO display "Dewatering max off time". See section
15.2.19 Dewatering, maximum "On" and "Off" time.
4.5.3 Required Grundfos GO settings
In order to activate the dewatering function, you must make the following Grundfos GO settings:
1. Set "Dry-running protection" to "Active".
2. Set the dry-running power limit, i.e. dry-running stop. See "Setting of dry-running power limit (dry­running stop)" below.
3. Set the relation between run and stop times.
Indication of operation:
The dry-running alarm indication on CU 300 is automatically disabled, when you make the setting in the display 15.2.19 Dewatering,
maximum "On" and "Off" time.
To disable the dewatering function and return to dry-running protection, simply disable the "Dewatering" function in the display
15.2.18 Dewatering.
Setting of dry-running power limit (dr y-running stop):
1. Start the pump against a closed discharge pipe.
2. Read the input power (P1) in the display
15.1.9 Power consumption.
3. Calculate the dry-running power limit: P1 x 0.9 [W].
4. Set this value in the display 15.2.21 Dry-running
stop.
4.5.4 On/off times
The dewatering function means that there is a dependence between the period of time during which the pump is running, the on time, and the period of time during which the pump is stopped, the off time.
Figure 6 shows an example of on and off times set in the display 15.2.19 Dewatering, maximum "On" and
"Off" time.
Fig. 6
Explanation:
The on and off times are set to 60 minutes each. The pump has been running for 25 minutes when dry running occurs. The pump will be stopped for 35 minutes. If the pump has been running for e.g. 120 minutes, the stop time will be 1 minute.
English (GB)
TM06 3501 0415
7
5. CU 300 with constant-pressure
Note
Note
Pressure
Low flow
High flow
Time
English (GB)
control - 0 to 6 bar

5.1 Description

Using constant-pressure control enables automatic adjustment of the pump performance according to consumption. The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption.
Figure 7 shows an example of an installation with constant-pressure control within the range from 0 to 6 bar.
Fig. 7
Pos. Description
1CU 300
Diaphragm tank
2
Absorbs pressure variations. Pressure sensor
3
The required pressure is set using the Grundfos GO.

5.2 Function

The pressure is registered by means of the pressure sensor, which transmits a signal to CU 300. CU 300 adjusts the pump performance accordingly by changing the pump speed.
Mains borne signalling
The communication between CU 300 and the pump is effected via the power supply cable.
This communication principle is called mains borne signalling or power line communication. Using this principle means that no additional cables to the pump are required.
The communication of data is effected by means of a high-frequency signal transmitted to the power supply cable and led into the electronics unit by means of signal coils incorporated in the motor and CU 300 respectively.
When does the pump start?
The pump starts as a consequence of:
•high flow
• low pressure
• a combination of both.
To ensure that the pump is started when water is consumed, a flow detection is required. The flow is detected via pressure changes in the system. When water is consumed, the pressure will drop accordingly depending on the size of the diaphragm tank and the water flow:
• At a low flow, the pressure will drop slowly.
• At a high flow, the pressure will drop quickly.
See fig. 8.
TM01 9649 4601
Fig. 8
When the pressure is dropping 0.1 bar/ s or faster, the pump will start immediately.
If you use a diaphragm tank of 8 litres, the pump will start at a flow rate of approx. 0.18 m
If a you use a larger tank, the flow must be higher before the pump starts.
Consumption up to 0.18 m
The pump will start when the pressure has dropped to 0.5 bar below the pressure setting.
The pump will run until the pressure is 0.5 bar above the pressure set.
3
/h.
3
/h
TM01 8545 0400
8
Flow detection
Pressure
Flow detection
Time10 s 10 s
A
Stop
Star t
Pressure
Controlling
Dynamic variation
Flow
m
3
/h
0.18
12
8 l
CU 300
During pump operation, i.e. when water is consumed, CU 300 will adjust the pump speed to maintain a constant pressure. In order to stop the pump when no water is consumed, CU 300 performs flow detection every 10 seconds.
The pump speed is reduced until a small pressure drop is registered. This pressure drop indicates that water is consumed and the pump speed is resumed. See fig. 9.
If the pump speed can be reduced without any pressure drop being registered, this indicates that no water is consumed. The diaphragm tank will be filled with water and the pump will be stopped.
Fig. 9
System limits
Even though CU 300 is controlling the pressure within ± 0.2 bar, bigger pressure variations may occur in the system.
If the consumption is suddenly changed, e.g. if a tap is opened, the water must start flowing before the pressure can be made constant again. Such dynamic variations depend on the pipework, but, typically, they will lie between 0.5 and 1 bar.
If the desired consumption is higher than the quantity the pump is able to deliver at the desired pressure, the pressure follows the pump curve as illustrated in fig. 10.

5.3 Positioning the pressure sensor

Pressure loss often causes inconvenience to the user. CU 300 keeps the pressure constant in the place where the pressure sensor is positioned. See fig. 11.
Fig. 11
In fig.11, tap 1 is placed close to the pressure sensor. Therefore, the pressure will be kept nearly
TM01 8546 0400TM01 8634 0500
constant at tap 1, as the friction loss is small. At the shower and tap 2, the friction loss is bigger. This, of course, depends on the piping. However, old and furred-up piping may cause inconvenience due to friction loss.
Therefore, we recommend that you position the pressure sensor as close to the places of consumption as possible.

5.4 System sizing

Warning The installation must be designed for
the maximum pump pressure.
In normal installations with CU 300 and an SQE pump set to constant-pressure control, the required tank size is 8 litres. You can use bigger tanks without causing any problems.
English (GB)
TM01 9670 4601
Fig. 10
A = Required pressure
9

5.5 Electrical installation

K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX
RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
567
12
1098
34
111213 161514 171819
PE
TXD
LNLN
H
1
3
2
4
English (GB)
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 12
Pos. Description
1 Pressure sensor, brown lead, terminal 14 2 Pressure sensor, black lead, terminal 15 3 Pressure sensor, screen, terminal GND
Pressure sensor
4
Must be connected to analog input 1.
H Alarm signal transmitter (optional).
Internal alarm signal relay
K1
Relay data: 250 VAC, 1 A, AC1
10
TM01 9650 2400
5.5.1 Mains supply
Note
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
5.5.2 Pump supply PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
5.5.3 Alarm signal relay ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open). The relay operates when the alarm and warning
limits are exceeded. You can select manual or automatic restarting in the
Grundfos GO display "Automatic restarting". Manual restarting is carried out by means of the On/
Off button on CU 300.
5.5.4 Required Grundfos GO settings
You must make the following Grundfos GO settings:
1. In display "Control mode" select "Closed loop".
2. Set the sensor in the "Analog input 1" or "Analog input 2" display. Example:
– sensor output signal (4-20 mA) – setting range unit (m) – setting range - head
min.: 0.0 max.: 40
3. Set the stop type in the "Stop type, sensor 1" display.
– "Fill".
4. Set the digital input.
– "Not active"
5. Set the setpoint Example: Desired head 35 m. Rule: The maximum setting of the setpoint corresponds to the maximum value set in display
15.2.4 Analog inputs less 5 m.
In this case, 40 less 5 = 35 m.

5.6 Startup

Prior to startup, the precharge pressure of the diaphragm tank must be set to 70 % of the setpoint set in the Grundfos GO display "Setpoint".
English (GB)
11
6. CU 300 with constant-pressure
1
2
3
4
A
Stop (+ 0.5 bar)
Star t (- 0.5 bar)
Pressure
Controlling (± 0.2 bar)
Dynamic (± 0.5 bar)
Flow m
3
/h
0.18
English (GB)
control - 0 to 10 bar

6.1 Description

Using constant-pressure control enables automatic adjustment of the pump performance according to consumption. The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption.
Figure 13 shows an example of an installation with constant-pressure control within the range from 0 to 10 bar.
Fig. 13
Pos. Description
1CU 300
Diaphragm tank
2
Absorbs pressure variations. Flow switch
3
The pump starts at once when water is consumed at the taps.
Pressure sensor
4
The required pressure is set using the Grundfos GO.

6.2 Function

The pressure is registered by means of the pressure sensor and transmitted to CU 300. CU 300 adjusts the pump performance accordingly. To ensure that the pump is started when water is consumed, include a flow switch in the system.
The required pressure (setpoint) is set in the Grundfos GO display "Setpoint".
Consumption up to 0.18 m The flow switch contact is open. The pump starts when the pressure is equal to the setpoint less 0.5 bar. The pump will fill the tank and stop when the pressure is equal to the setpoint plus 0.5 bar. Consequently, the pump runs on/off operation.
Consumption above 0.18 m The flow switch contact is closed. The pump starts when the flow switch contact closes and the speed control ensures that the pressure is kept constant. If the flow is below
3
/h and the flow switch contact is opened,
0.18 m the tank is filled to a pressure equal to the setpoint plus 0.5 bar. When this pressure is reached, the pump stops. Stopping is a combination of the flow switch contact opening and the pressure being equal to the setpoint plus
0.5 bar.
If the flow is larger than the quantity the pump is able to deliver at the desired pressure, the pressure follows the pump curve as illustrated in fig. 14.
TM01 2653 4601
Fig. 14
A = Required pressure
3
/h.
3
/h.
TM01 8634 0500
12

6.3 Positioning the pressure sensor

1
2
CU 300
8 l
Pressure loss often causes inconvenience to the user. CU 300 keeps the pressure constant in the place where the pressure sensor is positioned. See fig. 15.
Fig. 15
In fig. 15, tap 1 is placed close to the pressure sensor. Therefore, the pressure will be kept nearly constant at tap 1, as the friction loss is small. At the shower and tap 2, the friction loss is bigger. This, of course, depends on the piping. However, old and furred-up piping may cause inconvenience due to friction loss.
Therefore, we recommend that you position the pressure sensor as close to the places of consumption as possible.

6.4 System sizing

English (GB)
TM01 2834 4601
Warning The installation must be designed for
the maximum pump pressure.
In normal installations with CU 300 and an SQE pump set to constant-pressure control, the required tank size is 8 litres. You can use bigger tanks without causing any problems.
13

6.5 Electrical installation

5
6
4
K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX
RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
567
12
1098
34
1112 13 161514 17 1819
PE
TXD
LNLN
H
1
3
2
English (GB)
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 16
Pos. Description
1 Pressure sensor, brown lead, terminal 14 2 Pressure sensor, black lead, terminal 15 3 Pressure sensor, screen, terminal GND
Pressure sensor
4
Must be connected to analog input 1.
5 Diaphragm tank connection
Flow switch Must be connected to the digital input,
6
terminals 12 and 13. Cannot be connected wrongly.
H Alarm signal transmitter (optional)
Internal alarm signal relay
K1
Relay data: 250 VAC, 1 A, AC1
14
TM01 3089 3398
6.5.1 Mains supply
Note
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
6.5.2 Pump supply PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
6.5.3 Alarm signal relay ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open). The relay operates when the alarm and warning
limits are exceeded. You can select manual or automatic restarting in the
Grundfos GO display "Automatic restarting". Manual restarting is carried out by means of the On/
Off button on CU 300.
6.5.4 Required Grundfos GO settings
You must make the following Grundfos GO settings:
1. In display 15.2.2 Control mode" select "Closed loop".
2. Set the sensor in the "Analog input 1" or "Analog input 2" display. Example:
– sensor output signal (4-20 mA) – setting range unit (m) – setting range - head
min.: 0.0 max.: 40.
3. Set the stop type in the "Stop type, sensor 1" display.
– "Fill".
4. Set the digital input.
– "Not active"
5. Set the setpoint Example: Desired head 35 m. Rule: The maximum setting of the setpoint corresponds to the maximum value set in display "Analog input 1" less 5 m. In this case, 40 less 5 = 35 m.

6.6 Startup

Prior to startup, the precharge pressure of the diaphragm tank must be set to 70 % of the setpoint set in the Grundfos GO display "Setpoint".
English (GB)
15
7. CU 300 with constant-pressure
Note
1A
1B
2
3
4
English (GB)
control - two-pump operation

7.1 Description

Using constant-pressure control in connection with two-pump operation enables automatic adjustment of the pump performance according to the consumption in systems where a high flow is required. The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption.
During two-pump operation, the two pumps must have the same nominal flow, e.g. two SQE 2.
Figure 17 shows an example of a two-pump installation with constant-pressure control.
Fig. 17

7.2 Function

The pressure is registered by means of the pressure sensor and transmitted to CU 300 (master). CU 300 adjusts the pump speed to ensure that the pressure is kept constant. To ensure that the pump connected to CU 300 (master) is started when water is consumed, a flow switch must be included in the system.
Set CU 300 (master) to the desired pressure (setpoint) in the Grundfos GO display "Setpoint".
Consumption up to 0.18 m The flow switch contact is open. The pump connected to CU 300 (master) starts when the pressure is equal to the setpoint less
0.5 bar. The pump will fill the tank and stop when the pressure is equal to the setpoint plus 0.5 bar. Consequently, the pump runs on/off operation.
Consumption above 0.18 m The flow switch contact is closed. The pump connected to CU 300 (master) starts when the flow switch contact closes and the speed control ensures that the pressure is kept constant. If the flow is lower than 0.18 m switch contact is opened, the tank is filled to a pressure equal to the setpoint plus 0.5 bar. When this pressure is reached, the pump stops. Stopping is a combination of the flow switch contact opening and the pressure being equal to the setpoint plus 0.5 bar. If the consumption exceeds the quantity the pump connected to CU 300 (master) is able to deliver, the pressure in the diaphragm tank will fall.
TM01 2654 4601
3
/h.
3
/h.
3
/h and the flow
Pos. Description
1A, 1B
1A = CU 300 (master) 1B = CU 300 (slave)
Diaphragm tank, minimum 24 litres
2
Absorbs pressure variations. Flow switch
3
The pump starts at once when water is consumed at the taps.
Pressure sensor
4
The required pressure is set using the Grundfos GO.
16
The pump connected to CU 300 (slave) will be
A
Stop (+ 0.5 bar)
Start (- 0.5 bar)
Pressure
Controlling (± 0.2 bar)
Dynamic (± 1.0 bar)
Flow
m
3
/h
0.18
started in the two following situations:
1. If the pressure in the diaphragm tank falls to 1 bar below the setpoint.
2. If the pump connected to CU 300 (master) has been operating at maximum performance for more than 5 seconds and the water requirement has increased.
The pump connected to CU 300 (slave) will be stopped in the three following situations:
1. If the system pressure is 1 bar higher than the setpoint.
2. If the pump connected to CU 300 (master) has been operating at minimum performance for more than 5 seconds and the water requirement has fallen.
3. If the flow switch indicates "No flow" and the system pressure is 0.5 bar higher than the setpoint.
If the flow is larger than the quantity the pumps are able to deliver at the desired pressure, the pressure follows the pump curve. See fig. 18.

7.3 Positioning the pressure sensor

See section 6.3 Positioning the pressure sensor.

7.4 System sizing

Warning The installation must be designed for
the maximum pump pressure.
In two-pump installations set for constant-pressure control, the required tank size is 24 litres. You can use bigger tanks without any problems.
English (GB)
A = Required pressure
Fig. 18
TM01 8634 0500
17

7.5 Electrical installation

K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS 232
B
GND
ARIDTR
RXD
GND
567
12
109834111213 161514 171819
PE
TXD
LNLN
1
3
2
NLNL
TXD
PE
191817141516131211438910
21
765
GND
RXD
DTRRIA
GND
B
232
RS
485
RS
GND
+24VDC
IN
SENSOR
21
SENSOR
IN
+24VDC
GND
GND
+24VDC
IN
DIG
IN
RELAY
AUX
COMNCNO
NO
NC
COM
ALARM RELAY
PUMP
PE
POWER
A
B
5
6
4
D
C
5
4
7
English (GB)
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 19
TM01 9671 2500
Pos. Description
A CU 300 (master) B CU 300 (slave)
3
/h
3
/h
3
/h)
3
/h)
C Installation for Q < 5 m D Installation for Q > 5 m 1 Pressure sensor, brown lead, terminal 14 2 Pressure sensor, black lead, terminal 15 3 Pressure sensor, screen, terminal GND
4
5 Diaphragm tank connection
6
7
K1
Pressure sensor Must be connected to analog input 1.
Flow switch (Q < 5 m Must be connected to the digital input, terminals 12 and 13. Cannot be connected wrongly.
Flow switch (Q > 5 m Must be connected to the digital input, terminals 12 and 13. Cannot be connected wrongly.
Internal alarm signal relay Relay data: 250 VAC, 1 A, AC1
18
7.5.1 Auxiliary relay
Note
Connect CU 300 (master) to CU 300 (slave) as follows:
Connections
CU 300 (master) CU 300 (slave)
Terminal 9 (COM) Terminal 12 (IN)
Terminal 10 (NO) Terminal 13 (GND)
See fig. 19.
7.5.2 Mains supply
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. See fig. 19.
You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
7.5.3 Pump supply
PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. See fig. 19.
You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
7.5.4 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay operates when the alarm and warning limits are exceeded.
You can select manual or automatic restarting in the Grundfos GO display "Automatic restarting".
Manual restarting is carried out by means of the On/ Off button on CU 300.
7.5.5 Flow switch and pressure sensor
Connect the flow switch and the pressure sensor to the control unit (A = master) as illustrated in fig. 19.
Flow switch:
Pump type Product number
SQE 1 96037332 SQE 2, SQE 3, SQE 5, SQE 7 96037559
7.5.6 Required Grundfos GO settings
You must make the following Grundfos GO settings on CU 300 (master):
1. In display "Control mode" select "Closed loop".
2. Set the sensor in the "Analog input 1" or "Analog input 2" display. Example:
– sensor output signal (4-20 mA) – setting range unit (m) – setting range - head
min.: 0.0 max.: 40.
3. Set the stop type in the "Stop type, sensor 1" display.
– "Fill".
4. Set the digital input in "Digital input 1" display:
– "Start".
5. Set the setpoint Example: Desired head 35 m. Rule: The maximum setting of the setpoint corresponds to the maximum value set in display
15.2.4 Analog inputs less 5 m.
In this case, 40 less 5 = 35 m.
You must make the following Grundfos GO setting on CU 300 (slave):
6. Set the digital input in "Digital input 1" display:
– "Start"

7.6 Startup

Prior to startup, you must set the precharge pressure of the diaphragm tank to 70 % of the setpoint set in the Grundfos GO display "Setpoint".
English (GB)
19

8. CU 300 with sensors

pH
100%
0
2
1
3
4
Alarm Warning
Warning
Warning Max. (start)
Min. (stop)
Max.
Max.
Max.
Min.
Min.
Min.
Status
100%
Sensor signal
0
Stop
Warning
Alarm
English (GB)

8.1 General

CU 300 can be used in systems with one to three sensors connected.
Figure 20 shows an example of an installation incorporating sensors.
Fig. 20
Pos. Description
1 CU 300
pH sensor
2
Detects the water quality. Pulse flow meter
3
Detects the water quantity.
4 Level sensor
You can set the alarm, warning and stop limits individually for all sensors connected. The limit settings do not influence each other, and each setting offers its own functioning.
Figure 21 shows a schematic presentation of the setting of maximum and minimum limits for alarm, warning and stop respectively.
Fig. 21
You must only set the limits applying to the selected sensor.
TM01 2672 4601
These settings are made in the displays
15.2.4 Analog inputs and 15.2.5 Limits, sensor 1 and
2 to 15.2.5 Limits, sensor 1 and 2.
TM01 2697 2298
20

8.2 Sensor functioning

Max. (start)
Min. (stop)
Max. (stop)
Min. (start)
8.2.1 Alarm limits
When an alarm limit is exceeded, the following takes place:
1. The pump is stopped.
2. The alarm signal relay operates.
3. The "Sensor alarm" indicator light on CU 300 is on.
4. The alarm appears in the Grundfos GO display "Alarms and warnings".
If the pump has stopped already or if the alarm signal relay has operated, this condition is maintained.
8.2.2 Warning limits
When a warning limit is exceeded, the following takes place:
1. The alarm signal relay operates.
2. Pump operation is continued. No "Sensor alarm" indication.
3. The warning appears in the Grundfos GO display "Alarms and warnings".
8.2.3 Start and stop limits
Start and stop limits must be used in connection with the emptying and filling of e.g. water tanks.
The start and stop function depends on the application, i.e. emptying or filling.
• Emptying means that the pump must start at a given maximum water level and stop at a given minimum water level. See fig. 22.
• Filling means that the pump must start at a given minimum water level and stop at a given maximum water level. See fig. 23.
Fig. 23
English (GB)
TM01 2699 4601
Fig. 22
TM01 2700 4601
21

8.3 Electrical installation

K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX
RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
567
12
1098
34
111213 161514 171819
PE
TXD
LNLN
H
D1
4-20 mA
D1
A1
A2
0-20 mA
0-10V/2-10V
A3
English (GB)
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 24
Pos. Description
A1 Analog sensor, output signal 4-20 mA A2 Analog sensor, output signal 0-20 mA A3 Analog sensor, output signal 0-10/2-10 V D1 Digital sensor, NO (normally open) D1 Digital sensor, NC (normally closed)
H Alarm signal transmitter (optional)
Internal alarm signal relay
K1
Relay data: 250 VAC, 1 A, AC1
22
TM01 3088 2500
8.3.1 Mains supply
Note
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
8.3.2 Pump supply PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
8.3.3 Alarm signal relay ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open). The relay operates when the alarm and warning
limits are exceeded. You can select manual or automatic restarting in the
Grundfos GO display "Automatic restarting". Manual restarting is carried out by means of the On/
Off button on CU 300.
8.3.4 Sensors
SENSOR 1 and SENSOR 2, terminals 14, 15, 16, 17, 18 and 19:
Terminals 14, 15 and 16 (SENSOR 1) and terminals 17, 18 and 19 (SENSOR 2) are used for external sensors, e.g. a pressure gauge, a flow meter or another type of sensor.
You set the limits for the signal from an external sensor in the Grundfos GO in the "Analog input 1" and "Analog input 2" displays.
You can use the signal to do the following:
• To start and stop the motor.
• To operate the alarm signal relay, without stopping the motor.
The sensors must give signals within the ranges 0-20 or 4-20 mA, 0-10 or 2-10 VDC. Changeover between current and voltage signals is carried out by means of the Grundfos GO.
The total load of terminals 11, 14 and 17 (+24 VDC) must not exceed 100 mA.
8.3.5 Required Grundfos GO settings
You must make the following Grundfos GO settings:
1. Set "Analog input 1".
– sensor output signal (4-20 mA) – setting range unit (m) – setting range - head min.: 0.0
max.: 50.
2. Set "Analog input 2" to "Not active".
3. Set the minimum stop value for sensor 1 in display "Min. stop value, sensor 1".
4. Set the maximum stop value for sensor 1 in display "Max. stop value, sensor 1".
5. Set the "Warning limits" and "Alarm limits" for sensor 1 in display "Limits, sensor 1".
6. Set the desired stop type in display "Stop type, sensor 1: Example:
– "Fill".
English (GB)
23

9. CU 300 connected to potentiometer

Note
1
2
3
English (GB)

9.1 Description

Using an external potentiometer enables:
• Manual control of the motor speed, and thereby of pump performance.
Manual starting/stopping of the pump.
To stop the pump, turn the potentiometer (SPP 1) to "STOP".
Figure 25 shows an example of an installation with a potentiometer.
Fig. 25
Pos. Description
1CU 300
External Grundfos potentiometer, SPP 1 The required flow is obtained by changing
2
the motor speed manually using the external potentiometer.
3 Water tank
TM01 2660 4601
24

9.2 Electrical installation

K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX
RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
567
12
1098
34
111213 161514 171819
PE
TXD
LNLN
H
4
3
21
SPP 1
SENSOR IN
GND
DIG IN
+24 VDC
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
English (GB)
Fig. 26
Pos. Description
Internal alarm signal relay
K1
Relay data: 250 VAC, 1 A, AC1
H Alarm signal transmitter (optional)
SPP 1 External Grundfos potentiometer, SPP 1
TM01 3091 3398
25
9.2.1 Mains supply
Note
1
2
English (GB)
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
9.2.2 Pump supply
PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
9.2.3 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay operates when the alarm and warning limits are exceeded.
You can select manual or automatic restarting in the Grundfos GO display "Automatic restarting".
Manual restarting is carried out by means of the On/ Off button on CU 300.
9.2.4 Potentiometer SPP 1
Connections between the SPP 1 and CU 300:
9.2.5 Required Grundfos GO settings
You must make the following Grundfos GO settings:
1. In display "Control mode" select "Open loop".
2. Set the external setpoint to "SPP 1", enabling speed control using the SPP 1. "Analog input 2" is set to "SPP 1".
3. Set "Digital input 1" to "Start"

10. CU 300 connected to water meter

10.1 Description

Using a water meter (pulse flow meter) enables:
• Monitoring of the flow.
• Stop of pump after a given quantity of water has been pumped.
• Indication of accumulated flow and the energy consumption required to pump 1 m
Figure 27 shows an example of an irrigation system incorporating a water meter.
Fig. 27
Pos. Description
1CU 300 2 Water meter (pulse flow meter)
3
.
TM01 2659 4601
SPP 1 CU 300
1 17 (SENSOR 2 +24 VDC) 2 19 (SENSOR 2 GND) 3 12 (DIG IN) 4 18 (SENSOR 2 IN)
26

10.2 Electrical installation

D1
K1
POWER
PE
PUMP
RELAY
ALARM
COM
NC
NO
NONCCOM
AUX
RELAY
IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
567
12
1098
34
111213 161514 171819
PE
TXD
LNLN
H
Note
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 28
English (GB)
TM01 6223 1899
Pos. Description
D1 Water meter (pulse flow meter)
H Alarm signal transmitter (optional)
Internal alarm signal relay
K1
Relay data: 250 VAC, 1 A, AC1
10.2.1 Mains supply POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm
2
.
Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
27
10.2.2 Pump supply
1
2
Warning
Desired level
Warning
English (GB)
PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
10.2.3 Alarm signal relay ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open). The relay operates when the alarm and warning
limits are exceeded. You can select manual or automatic restarting in the
Grundfos GO display "Automatic restarting". Manual restarting is carried out by means of the On/
Off button on CU 300.
10.2.4 Water meter (pulse flow meter) DIG IN, terminals 12 and 13
Connect terminals 12 and 13 to the water meter:
• Terminal 12 IN (signal input).
• Terminal 13 GND (earth).
10.2.5 Required Grundfos GO settings
You must make the following Grundfos GO settings:
1. Set "Digital input 1". – Function: "Pulse-flow meas."
2. Set "Flow per pulse":
Example: "10 l/pulse".
When you have set a value in this display, the actual flow will appear in status display "Digital input".
You must only set a value in the display "Stop limit, accum. flow" if stop of pump after a given quantity of water has been pumped is required.
Example:
• Stop limit, accum. flow: "7.5 m
3
".
• Sensor, accum. flow stop: "Digital input".
When you have set a value in this display, the "Accumulated flow" and "Energy per m in the status displays "Accumulated flow" and "Specific energy".
3
" will appear

11. Constant water level

11.1 Description

The water level can be kept constant by connecting an analog level sensor.
Figure 29 shows an example of an installation designed for maintaining a constant water level in the borehole.
Fig. 29
Pos. Description
1CU 300 2 Level sensor

11.2 Function

CU 300 controls the pump speed and consequently adjusts the pump performance to the borehole yield.
1. When the water level is much higher than the desired level (setpoint), the pump is running at maximum performance.
2. When the level is coming closer to the desired level, the pump performance will be reduced.
3. When the desired level is reached, the pump speed will be so low that the pump performance is zero. After further 60 seconds, the pump will stop.
TM01 2671 4601
28

11.3 Electrical installation

POWERPEPUMP
RELAY
ALARM
COMNCNO
NONCCOM
AUX
RELAY IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS 232
B
GND
A
RI
DTR
RXD
GND
567
12
1098
34
111213 161514 171819
PE
TXD
+24VDC
4-20 mA / IN
1
1
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 30
English (GB)
TM01 6213 2400
Pos. Description
Connection of level sensor:
1
• Terminal 14, 24 VDC supply
• Terminal 15, signal input
29
11.3.1 Mains supply
Note
English (GB)
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
11.3.2 Pump supply PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
11.3.3 Alarm signal relay ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open). The relay operates when the alarm and warning
limits are exceeded. See section 15.2.5 Limits,
sensor 1 and 2.
11.3.4 Digital input
Connect terminals 12 and 13 with a short piece of wire to create a short circuit between them.
11.3.5 Level sensor
Connect terminals 14 and 15 to the level sensor:
• Terminal 14, 24 VDC (voltage supply).
• Terminal 15, IN (signal input).
11.3.6 Required Grundfos GO settings
You must make the following Grundfos GO settings:
1. In display "Control mode" select "Closed loop".
2. Set "Analog input 1". Example:
– sensor output signal (4-20 mA), – setting range unit (m) – setting range - head
Min.: 0.0 Max.: 60. Set the stop type.
– Sensor 1: "Empty".
3. Set the "Setpoint" e.g. desired water level (m). Example: 55 m.
– Rule: The maximum setting of the setpoint
corresponds to the maximum value set in display "Analog input 1" less 5 m. In this case, 60 less 5 = 55 m. The water level can be kept within a tolerance of ± 1 % of the setting range.
4. Set "Digital input 1".
– "Start".
30

12. CU 300 connected to RS-485

5
1
1
3
2
WWW
CIU 27X

12.1 Description

Using the RS-485 input enables:
• communication via Grundfos fieldbus GENIbus
• connection to the Grundfos Remote Management (CIU 270) gateway for communication over long distances.

12.2 CU 300 connected to a PC directly

Figure 31 shows an example of an installation which is connected to a PC directly via the PC Tool link and GENIbus.
The installation shown in the example enables configuration, fault finding and servicing of the installation by means of a PC with a PC Tool CU 300 software. See fig. 31.
Fig. 31
CU 300 connected to GENIbus network:
Figure 32 shows an example of an installation connected to a GENIbus network with two CU 300 installations via the RS-485 input. The GENIbus network is connected to Grundfos Remote Management (CIU 270) through a PC with internet access.
The installation shown in the example enables configuration, fault finding, servicing, data logging of the connected installations over long distances. See fig. 32.
You can connect and communicate with up to 32 GENIbus units on one network.
The units can be:
• CU 300 units only
• CU 300 units in combination with other Grundfos products with GENIbus connection.
Contact Grundfos for further details.
TM06 3619 0715
English (GB)
Pos. Description
1CU 300
E.g. a pH sensor for monitoring of water
2
quality
Fig. 32
TM06 3618 0715
3 Level sensor 4PC 5 PC Tool Link
Pos. Description
1CU 300 2 CIU 270 3PC
31

12.3 Electrical installation

POWER
PE
PUMP
RELAY
ALARM
COMNCNO
NONCCOM
AUX
RELAY IN
DIG
IN
+24VDC
GND
GND
+24VDC
IN
SENSOR
12
SENSOR
IN
+24VDC
GND
RS
485
RS 232
B
GND
ARIDTR
RXD
GND
56712109834111213 161514 171819
PE
TXD
RS-485 BRS-485-A
IN
GND
RS
485
RS
232
B
GND
ARIDTR
RXD
GND
18 19
TXD
Y
RS-485
English (GB)
Warning Never make any connections in the CU 300 unit unless the power supply has been switched off.
CU 300 must be connected in accordance with the rules and standards in force for the application in question.
The supply voltage and frequency are marked on the nameplate. Make sure that CU 300 is suitable for the power supply on which it will be used.
Fig. 33
Pos. Description
RS-485 Connection of RS-485, GENIbus
32
TM06 3600 0615
12.3.1 Mains supply
Note
POWER, terminals 1, 2 and PE
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm Backup fuse: Maximum 16 A.
You must not connect the leads of the mains supply to terminals 3 and 4.
12.3.2 Pump supply PUMP, terminals 3, 4 and PE
Connect terminals 3 and 4 to the phase and neutral leads of the pump. You can connect each terminal to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. You must connect each PE terminal to an earth lead of its own.
Maximum cross-section of the leads to be connected
2
.
is 6 mm
12.3.3 Alarm signal relay ALARM RELAY, terminals 5, 6 and 7
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open). The relay operates when the alarm and warning
limits are exceeded. You can select manual or automatic restarting in the
Grundfos GO display "Automatic restarting". Manual restarting is carried out by means of the On/
Off button on CU 300.
12.3.4 RS-485 input
The RS-485 input, terminals A, Y (GND) and B, is for external bus communication.
The communication is effected according to the Grundfos bus protocol, GENIbus, and is two-way communication.
CU 300 can communicate with a PC with the PC Tool CU 300 installed.
You need a PC Tool link adapter to communicate with a PC. Connect the adaptor to CU 300, terminals A, Y (GND) and B, for direct communication with a PC on a GENIbus network.
The PC Tool CU 300 enables configuration, monitoring and fault finding of the actual installation.
The RS-485 input is a low-voltage circuit. Therefore, you must separate all connections to terminals A, Y (GND) and B from network circuits by means of double or reinforced insulation.
A screened, twisted-pair cable is required. The maximum cable length is 1200 m.
English (GB)
33

13. Alarm functions

No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
English (GB)

13.1 No contact

The connection and/or communication between CU 300 and the motor is not established.
"No contact"
is permanently on. See fig. 34.

13.2 Overvoltage

The supply voltage to the motor exceeds the maximum value allowed.
For more information about factory settings, see section 16. Technical data.
The motor is stopped and "Overvoltage" is permanently on. See fig. 35.
Fig. 34
Possible cause Remedy
Motor is not an MSE 3 motor.
Motor is not connected. Check connections. Cable breakage. Check cable. Poor or no connection. Check connections. The cable length
exceeds 200 m. CU 300 is defective. Replace CU 300. The motor is defective. Replace motor.
Important:
The alarm indication "No contact" will also appear if the pump and CU 300 do not have the same number (allocated by the Grundfos GO). The problem may occur e.g. in connection with replacing a motor or a CU 300.
Solution: The pump and CU 300 must be allocated the same
number via the Grundfos GO display "Number". The alarm "No contact" makes the On/Off button on
CU 300 inactive, and actual operating parameters cannot be called up. However, installation parameters can be called up.
"No contact" does not cause a pump stop.
Install an MSE 3 motor.
Reduce cable length.
TM01 2782 0415
Fig. 35
Possible cause Remedy
Unstable power supply.
Too high supply voltage.
Supply voltage outside voltage range of motor.
Restarting
When the supply voltage lies within the voltage range of the motor, the motor will restart automatically.
Contact the power supply authorities.
Contact the power supply authorities. Check installation.
Check installation.
TM01 2783 0415
34

13.3 Undervoltage

No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
The supply voltage to the motor is lower than the minimum value allowed.
For more information about the factory setting, see section 16. Technical data.
The motor is stopped and "Undervoltage" is permanently on. See fig. 36.
Fig. 36

13.4 Dry running

The purpose of the dry-running protection is to protect the pump in case of insufficient water flow.
The dry-running protection makes the conventional dry-running protection unnecessary.
No additional cables to the motor are required. The dry-running alarm is activated when the load has
been below the dry-running power limit for an accumulated time of 5 seconds.
The motor is stopped and "Dry running" is permanently on. See fig. 37.
TM01 2784 0415
English (GB)
Possible cause Remedy
Unstable power supply.
Supply voltage outside voltage range of motor.
Voltage drop in mains is too big.
Restarting
When the supply voltage lies within the voltage range of the motor, the motor will restart automatically.
Contact the power supply authorities.
Check installation.
Increase wire cross­section.
Fig. 37
Possible cause Remedy
Replace pump with a
The pump performance is too high compared to the borehole yield.
Borehole filter is blocked.
Restarting
After 5 minutes (factory setting), or the period set by means of the Grundfos GO display "Automatic restarting", the motor will restart automatically.
smaller one. Reduce pump
performance using the Grundfos GO display "Maximum speed".
Borehole service is required.
35
TM01 2785 0415

13.5 Speed reduction

No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
English (GB)
At a moderate undervoltage or overload of the motor, the speed is reduced, but the motor is not stopped. The speed reduction indicator light is on, and at the same time the undervoltage or overload light is on.
"Speed reduction" and "Undervoltage" or "Overload" are permanently on.
In fig. 38, the "Speed reduction" alarm was caused by undervoltage.
Fig. 38
Possible cause Remedy
Pump is worn, causing overload.
Wrong combination of pump and motor, causing overload.
Unstable power supply, causing undervoltage.
Too big voltage drop over the cable, causing undervoltage.
Speed resuming
When the supply voltage lies within the voltage range of the motor again and the cause of the overload has disappeared, the motor resumes normal speed.
Pump must be serviced.
Replace pump or motor.
Contact the power supply authorities.
Size cable to avoid too big voltage drop.

13.6 Overtemperature

The motor temperature is monitored continuously during operation.
The motor is factory-set to a maximum value. See section 16. Technical data.
The motor temperature has exceeded the maximum temperature limit. If the temperature is too high, there is a risk that the motor electronics will be damaged.
The motor is stopped and "Overtemperature" is permanently on. See fig. 39.
TM01 2786 0415
Fig. 39
A too high operating temperature may indicate that the installation needs service.
Possible cause Remedy
Insufficient cooling or flow velocity along motor.
Insufficient cooling due to incrustation of the motor.
Restarting
When the motor electronics has cooled sufficiently, the motor will restart automatically. See section
16. Technical data.
Take out pump and install flow sleeve.
Clean motor. Install flow sleeve.
TM01 2787 0415
36

13.7 Overload

No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm
A
The motor is overloaded, i.e. the current consumption of the motor exceeds the limit value.
For more information about the factory setting, see section 16. Technical data.
The motor is stopped and "Overload" is permanently on. See fig. 40.
Fig. 40
Possible cause Remedy
Pump is defective. Pump must be serviced. Sand or gravel in pump. Pump must be serviced. Wrong combination of
pump and motor.
Restarting:
After 5 minutes (factory setting), or the period set by means of the Grundfos GO display "Automatic restarting", the motor will restart automatically.
Replace pump or motor.

13.8 Sensor alarm

The sensor alarm is activated in two incidents:
• If a connected sensor has detected that an alarm limit has been exceeded.
• If the sensor signal has fallen outside the measuring range set.
The motor is stopped and the "Sensor alarm" is permanently on. See fig. 41.
Restarting
After 5 minutes (factory setting), or the period set by means of the Grundfos GO display "Automatic restarting", the motor will restart automatically.

14. CU 300 with Grundfos GO

The remote control Grundfos GO is used for wireless infra-red communication with CU 300. During communication, there must be visual contact between CU 300 and the Grundfos GO. See fig. 42.
Fig. 42 CU 300 communicating with Grundfos
TM01 2788 0415
The Grundfos GO offers possibilities of setting and status displays for CU 300.
When the communication between the Grundfos GO and CU 300 has been established, the red indicator light (A) in the On/Off button will flash.
For general use of the Grundfos GO, see the operating instructions for this unit.
The menu structure for the Grundfos GO and CU 300 is divided into three main menus, each containing a number of displays.
• Status
• Settings
• Alarms and warnings See 14.1 Menu overview on page 38.
GO
English (GB)
TM06 3502 0415
Fig. 41
TM01 2789 0415
37

14.1 Menu overview

English (GB)
Status Section Page
External setpoint 15.1.1 External setpoint 40 Controlled from 15.1.2 Controlled from 40 Value, sensor 1 Value, sensor 2 Motor temperature 15.1.4 Motor temperature 40 Motor speed 15.1.5 Motor speed 40 Digital input 15.1.6 Digital input 40 Specific energy 15.1.7 Specific energy 40 Accumulated flow 15.1.8 Accumulated flow 40 Power consumption 15.1.9 Power consumption 40 Energy consumption 15.1.10 Energy consumption 40 Operating hours 15.1.11 Operating hours 40 Number of starts 15.1.12 Number of starts 40
Settings Section Page
Operating mode 15.2.1 Operating mode 40 Control mode 15.2.2 Control mode 40 Setpoint 15.2.3 Setpoint 41 Analog input 1 Analog input 2 Limits, sensor 1 15.2.5 Limits, sensor 1 and 2 41 Min. stop value, sensor 1 15.2.6 Min. stop value, sensor 1 and 2 41 Max. stop value, sensor 1 15.2.7 Max. stop value, sensor 1 and 2 41 Limits, sensor 2 15.2.5 Limits, sensor 1 and 2 41 Min. stop value, sensor 2 15.2.6 Min. stop value, sensor 1 and 2 41 Max. stop value, sensor 2 15.2.7 Max. stop value, sensor 1 and 2 41 External setpoint 15.2.8 External setpoint 41 Warning temperature 15.2.9 Warning, temperature 42 Digital input 1 15.2.10 Digital input 42 Flow per pulse 15.2.11 Flow per pulse 42 Stop limit, accum. flow 15.2.12 Stop limit, accumulated flow 42 Sensor, accum. flow stop 15.2.13 Sensor, accumulated flow stop 42 Stop type, sensor 1 Stop type, sensor 2 Automatic restarting 15.2.15 Automatic restarting 42 Double restarting time 15.2.16 Double restarting time 42 Start delay 15.2.17 Start delay 43 Dewatering 15.2.18 Dewatering 43 Dewatering max. on time Dewatering max. off time
15.1.3 Value, sensor 1 and 2 40
15.2.4 Analog inputs 41
15.2.14 Stop type, sensor 1 and 2 42
15.2.19 Dewatering, maximum "On" and "Off" time
Continues on page 39.
43
38
Continued from page 38.
Settings Section Page
Dry-running protection 15.2.20 Dry-running protection 43 Dry-running stop 15.2.21 Dry-running stop 43 Maximum speed 15.2.22 Maximum speed 43 Buttons on product 15.2.23 Buttons on product 44 Number 15.2.24 Number 44 Store settings 15.2.25 Store settings 44 Recall settings 15.2.26 Recall settings 44 Undo 15.2.27 Undo 44 Unit configuration 15.2.28 Unit configuration 44
Alarms and warnings Section Page
Alarm log Warning log
15.3.1 Alarm and warning logs 45
English (GB)
39

15. Description of functions

English (GB)

15.1 Status

The "Status" menu for CU 300 offers the possibility of reading operating parameters.
15.1.1 External setpoint
You can read the value of the external setpoint in this display.
15.1.2 Controlled from
This display shows the control source:
• CU 300
• external.
15.1.3 Value, sensor 1 and 2
You can read the values measured by sensor 1 and 2 in these displays.
15.1.4 Motor temperature
The actual temperature of the motor electronics stated in "° C" or "° F".
Tolerance: ± 5 %.
Relation to other disp lays :
To select "° F", choose this in display 15.2.28 Unit
configuration.
15.1.5 Motor speed
The actual speed stated in min Tolerance: ± 1 %.
15.1.6 Digital input
You can read the value measured by the digital input in this display. For instance, the actual flow is shown if the digital input has been connected to a pulse flowmeter and is setup to monitor the flow.
15.1.7 Specific energy
You can read the specific energy in this display.
15.1.8 Accumulated flow
You can read the pumped water quantity in this display.
15.1.9 Power consumption
You can read the actual power consumption in this display.
15.1.10 Energy consumption
You can read the total energy consumption in this display.
15.1.11 Operating hours
The value of operating hours is accumulated from the pump's birth and it cannot be reset.
The value is stored in the motor electronics, and it is kept even if CU 300 is replaced.
The value is updated in the software every 2 minutes of continuous operation. The displayed value is updated every two hours.
-1
(rpm).
15.1.12 Number of starts
The value of number of starts is accumulated from the pump's birth and it cannot be reset.
The value is stored in the motor electronics, and it is kept even if CU 300 is replaced.

15.2 Settings

The "Settings" menu for CU 300 offers the possibility of setting operating parameters.
15.2.1 Operating mode
Select one of the following operating modes:
Max.
Pump operation is set to maximum speed, irrespective of setpoint. The maximum speed is set in display 15.2.22 Maximum speed (default: 10,700 min
Normal.
Normal operating mode, i.e. pump operation is based on the setpoint set in display
15.2.3 Setpoint.
Examples: Speed set in display 15.2.3 Setpoint or sensor control.
Min.
Pump operation is set to minimum speed, 3000 min
Stop.
The pump is stopped.
Factory setting
"Stop".
15.2.2 Control mode
The following settings are available:
Open loop.
The speed is set to normal operation based on the setpoint set in display 15.2.3 Setpoint (e.g. 10,700 min connected to analog input 2. See section 9. CU 300 connected to
potentiometer.
Closed loop.
Controlling according to sensor 1 (type and unit). Example: Constant-pressure control. See section 6. CU 300 with constant-pressure
control - 0 to 10 bar.
Relation to other disp lays :
The unit (min changed according to the unit of the sensor installed.
Factory setting
"Open loop"
-1
).
-1
, irrespective of setpoint.
-1
) or controlled by means of a signal
-1
) of display 15.2.3 Setpoint is
40
15.2.3 Setpoint
Setting range: 3000-10,700 min intervals).
-1
(100 min-1
Dry-running protection
If you use "Setpoint" to reduce the speed, the dry­running protection will apply only in the "maximum speed" range, i.e. maximum speed less than 1000
-1
min
. See section 4.3.1 Function.
Relation to other disp lays
The setting in display 15.2.3 Setpoint is overridden by the "Max." and "Min." settings in display
15.2.1 Operating mode.
If you select "Closed loop" in display 15.2.2 Control
mode, the setpoint is set within the setting range of
the installed sensor. Example: If the analog input 1 is connected to a pressure sensor using the unit metre (m) and the measuring range (0-60), you can set the setpoint between 0 and 55 m in display 15.2.3 Setpoint.
Factory setting
"10,700 min
-1
"
15.2.4 Analog inputs
Make the following settings according to sensor type:
• Sensor output signal: "-" (not active), 0-20 mA, 4-20 mA, 0-10 V, 2-10 V.
• Setting range unit: m
3
/h, m, %, GPM, ft.
Setting range:
• Minimum value: 0-249 (0, 1, 2, ....249).
• Maximum value: 1-250 (1, 2, ....250).
Factory setting
Sensor output signal: "Not active" Setting range unit: "m".
15.2.5 Limits, sensor 1 and 2
In these displays, you can set the warning and alarm limits for sensor 1 and 2.
15.2.6 Min. stop value, sensor 1 and 2
In these displays, you can set the minimum value at which the pump must stop for sensor 1 and 2.
15.2.7 Max. stop value, sensor 1 and 2
In these displays, you can set the maximum value at which the pump must stop for sensor 1 and 2.
15.2.8 External setpoint
Set the pump performance control by means of an external signal.
To be used in the following two situations:
• For installations including a potentiometer.
• In large SCADA systems. In SCADA systems, this function makes it possible to control pump performance via remote controlling (e.g. via a PC).
The following settings are available:
• SPP 1. Grundfos potentiometer. See section 2.1 Expansion possibilities.
• 4-20 mA.
• 0-20 mA.
• 2-10 V.
• 0-10 V.
• "Not active" No external setpoint setting made.
Description
By connecting a current or voltage signal to analog input 2, you can control the motor speed between the setpoint set in display 15.2.3 Setpoint and the lowest speed of 3000 min
If the setpoint is set to 10,700 min display15.2.3 Setpoint, the motor speed can be changed between 3000 and 10,700 min
-1
.
-1
in
-1
.
The actual setpoint is calculated by CU 300 and shown in display 15.2.3 Setpoint.
If an SPP 1 potentiometer is connected, the internal voltage supply of CU 300 is used to generate the signal.
See section 9. CU 300 connected to potentiometer.
Relation to other disp lays
If you have set display 15.2.2 Control mode to "Closed loop" instead of "Open loop" (factory setting), the controlling is based on signals from analog input 1. Therefore, the unit in display
15.2.3 Setpoint is changed from min
sensor 1 (m
3
/h, m, %, GPM, ft).
-1
to the unit of
Factory setting
"Not active".
English (GB)
41
15.2.9 Warning, temperature
Note
English (GB)
Set the temperature warning limit of the motor.
Setting range: "-" (not active), 2, 4, 6, ....85 °C.
The maximum temperature depends on the motor type.
Set the temperature warning limit between normal operating temperature and maximum temperature.
Relation to other disp lays
You find the actual operating temperature in display
15.1.4 Motor temperature.
If the temperature warning limit is exceeded, the alarm signal relay operates.
Advantage
Instead of a sudden stop without a warning, you get the following:
• Information that the motor temperature is rising.
• The possibility of planning service of the installation.
Usage
You can use this function e.g. if the pumped liquid contains a relatively high level of ochre.
Factory setting
"Not active".
15.2.10 Digital input
Select one of the following functions:
• The digital sensor connected to the digital input (flow measuring).
• The external on/off switch for the pump.
The following functions are available:
Not active.
Stop. The pump is stopped when a switch connected to terminals 12 and 13 is closed. No l/pulse to be set. See section 15.2.10 Digital input.
Start. The pump is started when a switch connected to terminals 12 and 13 is closed. No l/pulse to be set. See section 15.2.10 Digital input.
Flow. If you have selected "Flow", the l/pulse value must also be set.
Setting range: "-" (not active), 0.1, 0.2, 0.3,....20,
21, 22, ....100 l/pulse.
Relation to other disp lays :
The selection of "Flow" in this display makes display
15.2.10 Digital input available, i.e. status of digital
input.
Factory setting
"Not active".
15.2.11 Flow per pulse
In this display the pumped volume per pulse is set.
Setting range: 0.0, 0.1, 0.2, 0.3, ....20, 21, 22, ....100
l/pulse. For more information, see section 15.2.10 Digital
input.
Factory setting
"0.0 l/pulse"
15.2.12 Stop limit, accumulated flow
In this display, you can set a limit at a specific amount of pumped water where the pump must stop.
Factory setting
"Disabled".
15.2.13 Sensor, accumulated flow stop
In this display, you can select the sensor for monitoring the accumulated flow.
Factory setting
"Disabled".
15.2.14 Stop type, sensor 1 and 2
In these displays, you can set the stop type for sensor 1 and 2. For further information, see
8.2.3 Start and stop limits.
Factory setting
"Disabled".
15.2.15 Automatic restarting
Set the automatic restart time from stop to restart attempt.
The following settings are available:
• "Enabled"
• "Disabled"
• 0 to 254 minutes.
Factory setting
"5 minutes".
15.2.16 Double restarting time
The following settings are available:
• enabled
• disabled. When you have selected "Enabled", the restart time
set will be doubled automatically for every 10 motor stops caused by an alarm. The time is doubled up to a stop time of 4 hours. After 10 hours of operation without an alarm, the restart time is automatically set to:
• The time set in the "Time" field.
•5 minutes (factory setting) if no setting was made
in the "Time" field.
Relation to other disp lays :
If you have selected "Double", the dewatering function is disabled.
42
15.2.17 Start delay
Set a start delay. This function is used in installations where several
pumps are connected to the same pipeline and where it is required that the pumps do not start up at the same time.
The SQE pumps have a built-in soft starter, which takes the starting current into account.
Setting range: 0-60 s.
Factory setting
"0 s"
15.2.18 Dewatering
For more information about the dewatering function, see 4.5 Description of the dewatering function.
The following settings are available:
• enabled
• disabled.
Relation to other disp lays
You can set the pump on and off times in the displays 15.2.19 Dewatering, maximum "On" and
"Off" time.
Factory setting
"Disabled".
15.2.19 Dewatering, maximum "On" and "Off"
time
In these displays, you set the maximum "On" and "Off" time for the pump for the dewatering function.
For more information, see section 4.5 Description of
the dewatering function.
Operating indication
The dry-running alarm indication on CU 300 is automatically disabled, when this display setting is made.
When you select the setting "Disabled", the dewatering function is disabled, and the dry-running alarm indication can be activated again.
Relation to other disp lays :
If you select "Double" in display 15.2.15 Automatic
restarting, the dewatering function is disabled.
Factory setting
"Disabled"
15.2.20 Dry-running protection
The following settings are available:
• enabled
• disabled. The setting in this display applies to both the
dewatering function and the dry-running protection. In certain installations, it may be necessary to
disable the dry-running protection. For further information, see section 4.3 Description
of dry-running protection.
Factory setting
"Enabled".
15.2.21 Dry-running stop
The dry-running stop value (dry-running power limit) is factory-set.
The value depends on the actual motor. The factory setting depends on the power rating of
the motor. See section 16. Technical data. When the dry-running protection or the dewatering
function is to be enabled, the minimum value of the pump power input must be set in this display.
For further information, see section 4.5 Description
of the dewatering function.
Setting range: 0-2500 W.
Relation to other disp lays
15.2.20 Dry-running protection must be set to
"Enabled". If you have enabled "Double" in display
15.2.16 Double restarting time, the dewatering
function is disabled. You can read the actual pump power input in display
15.1.9 Power consumption.
Factory setting
Motor size Dry-running stop
0.7 kW 300 W
0.7 kW (SQ/SQE 2-55) 550 W
1.15 kW 680 W
1.55 kW 800 W
1.85 kW 900 W
15.2.22 Maximum speed
Set the maximum speed. Setting range: 3000 - 10,700 min
Factory setting
10,700 min
-1
.
-1
.
English (GB)
43
15.2.23 Buttons on product
Note
English (GB)
In this display, you can disable the On/Off button on the control unit for protective reasons.
You can set the On/Off button to:
•"Active"
• "Not active".
Factory setting
"Active".
15.2.24 Number
Allocate a number to CU 300 and the pump connected. CU 300 and the pump must have the same number.
When allocating a number, the power supply to other CU 300 units, if any, must be switched off.
Setting range: "Not active", 1, 2, ....199.
Once a number setting has been made, the factory setting (not active) is no longer available.
In connection with bus communication, you must allocate a number to CU 300 and the pump.
If CU 300 and the pump do not have the same number, the alarm "No contact" will be indicated.
Factory setting
"Not active".
15.2.25 Store settings
You can store the actual settings for later use in this display.
15.2.26 Recall settings
You can recall the last stored settings that the pump will then use in this display.
15.2.27 Undo
You can undo previously made settings in this display.
15.2.28 Unit configuration
You can select between SI and US units in this display. The setting can be made generally for all parameters or customised for each individual parameter.
44

15.3 Alarms and warnings

15.3.1 Alarm and warning logs
These displays show the types of warnings and alarms that may have appeared.
Possible warnings and alarms are described in the following table:
Indication Description
No fault indication No alarms are registered by CU 300. No contact to pump No communication between CU 300 and the pump. Overvoltage The supply voltage exceeds the limit value. Undervoltage The supply voltage is below the limit value. Dry running The dry-running protection of the pump has been activated. Overtemperature The motor temperature exceeds the limit value. Overload The current consumption of the motor exceeds the limit value.
Alarm, sensor 1
Alarm, sensor 2
Sensor 1 defective
Sensor 2 defective
Warning, sensor 1 The sensor 1 warning limit has been exceeded. Warning, sensor 2 The sensor 2 warning limit has been exceeded. Warning, temperature The temperature warning limit has been exceeded.
Relation to other disp lays :
The setting in display 15.2.3 Setpoint is overridden by the "Max." and "Min." settings in display
15.2.1 Operating mode.
If you select "Closed loop" in display 15.2.2 Control
mode, the setpoint is set within the setting range of
the installed sensor. Example: If the analog input 1 is connected to a pressure sensor using the unit metre (m) and the measuring range (0-60), you can set the setpoint between 0 and 55 m in display 15.2.3 Setpoint.
The sensor 1 signal has fallen outside the measuring range set. Note: The sensor number refers to the terminal connection input number.
The sensor 2 signal has fallen outside the measuring range set. Note: The sensor number refers to the terminal connection input number.
The sensor signal of a 4-20 mA or 2-10 V sensor is below 2 mA or 1 V respectively.
The sensor signal of a 4-20 mA or 2-10 V sensor is below 2 mA or 1 V respectively.
English (GB)
45

16. Technical data

232
114
195
English (GB)
Supply voltage
1 x 100-240 V - 10 %/+ 6 %, 50/60 Hz, PE.
Power consumption
5 W.
Backup fuse
Maximum 16 A.
Current consumption
Maximum 130 mA.
Mains borne signalling
Frequency shift keying (FSK). (132.45 kHz, ± 0.6 kHz).
Enclosure class
IP55.
Maximum difference between CU 300 and pump
200 metres.
Ambient temperature
• During operation: -30 to 50 °C (must not be exposed to direct sunlight).
• During storage: -30 to 60 °C.
Weight
2.0 kg.
Relative air humidity
Maximum 95 %.
Materials
The CU 300 box is made of black PPO.
EMC (Electromagnetic compatibility)
See Declaration of conformity on page 48.
Dimensional sketch
Inputs/output
Potential-free changeover contact. Maximum contact load: 250 VAC. Maximum current: 1 A. Minimum contact load: 5 VDC, 10 mA.
Alarm relay
Specifications: 250 VAC, 8 A, AC1. Potential-free changeover contact.
Maximum contact load: Safety extra-low voltage to be used only. Maximum current: 1 A. Minimum contact load: 5 VDC, 10 mA. Specifications: 250 VAC, 8 A, AC1.
Auxiliary relay
External potential-free contact. Logic "0": U Logic "1": U
Digital input
Voltage signal: 0-10 VDC/2-10 VDC, Ri = 11 kΩ. Tolerance: at maximum voltage signal. Screened cable is recommended. Maximum cable length: 500 m. Current signal: DC 0-20 mA/4-20 mA, R
Sensor 1
Ω. Tolerance: ± 3 % at maximum current signal. Screened cable is recommended.
> 3.2 V.
in
< 0.9 V.
in
Maximum cable length: 500 m. Potentiometer SPP 1: 0-24 VDC, 10 k (via
internal voltage supply). Screened cable is recommended. Maximum cable length: 100 m. Voltage signal: 0-10 VDC/2-10 VDC, R kΩ. Tolerance: ± 3 % at maximum voltage signal. Screened cable is recommended.
Sensor 2
Maximum cable length: 500 m. Current signal: DC 0-20 mA/4-20 mA, Ri = 500 Ω. Tolerance: ± 3 % at maximum current signal. Screened cable is recommended. Maximum cable length: 500 m.
Grundfos fieldbus, GENIbus.
0.25 - 1 mm Maximum cable length: 1200 m.
RS-485
2
screened 2-core cable.
= 500
i
= 11
i
46
Fig. 43
TM01 2781 4601
Factory settings
Alarm
0.7 kW 1.15 kW 1.55 kW 1.85 kW 0.7 kW
Overvoltage
Undervoltage
Dry-running stop
Dry-running protection
Speed reduction
Electronics temperature
Overload 5.2 A 8.4 A 11 A 12.3 A 12.1 A Sensor alarm "No sensor used" (Grundfos GO setting). See section 15.2.4 Analog inputs)
1) 200-240 V motors: Operation is guaranteed up to 280 VAC. 100-115 V motors: Operation is guaranteed up to 150 VAC. In order to avoid unnecessary stops, the overvoltage stop limit is as stated.
2) Applies only to SQ/SQE 2-55.
Accuracy of Grundfos GO readings
Display Accuracy
External setpoint ± 5 % Motor temperature ± 5 % Motor speed ± 1 % Power input ± 5 % Power consumption ± 5 % Energy consumption ± 5 %
Sensors
The sensor signal accuracy depends on the sensor type. See the sensor specifications in question.
1)
320 VAC 320 VAC 320 VAC 320 VAC 185 VAC Speed reduction:
190 V Stop limit: 150 V Stop limit: 150 V Stop limit: 150 V Stop limit: 150 V Stop limit: 75 V 300 W
2)
550 W "Active" (Grundfos GO setting). See section 15.2.20 Dry-running protection)
In connection with undervoltage or overload
Stop limit: 65 °C Stop limit: 75 °C Stop limit: 85 °C Stop limit: 85 °C Stop limit: 85 °C Restart: 55 °C Restart: 65 °C Restart: 75 °C Restart: 75 °C Restart: 75 °C
200-240 V motors
Speed reduction: 190 V
680 W 800 W 900 W 300 W
Speed reduction: 210 V
Speed reduction: 210 V
100-115 V motors
Speed reduction: 90 V
English (GB)

17. Disposal

This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Subject to alterations.
47

Declaration of conformity

Declaration of conformity 1
GB: EC/EU declaration of conformity
We, Grundfos, declare under our sole responsibility that the product CU 300, to which the declaration below relates, is in conformity with the Council Directives listed below on the approximation of the laws of the EC/EU member states.
Note: There are two sets of Council Directives and standards listed below. One set applies until and including 19th April 2016. The other set applies from 20th April 2016 and onwards.
These Directives and standards apply until and including 19th April 2016: – Low Voltage Directive (2006/95/EC).
Standards used: EN 60335-1:2012
– EMC Directive (2004/108/EC).
Standards used: EN 55014-1:2006 + A1:2009 + A2:2011 EN 55014-2:1997 + A1:2001 + A2:2008
This EC/EU declaration of conformity is only valid when published as
These Directives and standards apply from 20th April 2016 and onwards: — Low Voltage Directive (2014/35/EU).
Standards used: EN 60335-1:2012
— EMC Directive (2014/30/EU).
Standards used: EN 55014-1:2006 + A1:2009 + A2:2011 EN 55014-2:1997 + A1:2001 + A2:2008
part of the Grundfos installation and operating instructions (publication number 96427972 0915).
Bjerringbro, 15th June 2015
Svend Aage Kaae
Director
Grundfos Holding A/S
Poul Due Jensens Vej 7
8850 Bjerringbro, Denmark
Person authorised to compile the technical file and
empowered to sign the EC declaration of conformity.
48
49
Grundfos companies
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 Garín Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belarus
Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56, БЦ «Порт» Тел.: +7 (375 17) 286 39 72/73 Факс: +7 (375 17) 286 39 71
E-mail: minsk@grundfos.com
Bosna and Herzegovina
GRUNDFOS Sarajevo Zmaja od Bosne 7-7A, BH-71000 Sarajevo Phone: +387 33 592 480 Telefax: +387 33 590 465 www.ba.grundfos.com e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 10F The Hub, No. 33 Suhong Road Minhang District Shanghai 201106 PRC Phone: +86 21 612 252 22 Telefax: +86 21 612 253 33
Croatia
GRUNDFOS CROATIA d.o.o. Buzinski prilaz 38, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.hr.grundfos.com
Czech Republic
GRUNDFOS s.r.o. Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111 Telefax: +420-585-716 299
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Trukkikuja 1 FI-01360 Vantaa Phone: +358-(0) 207 889 500 Telefax: +358-(0) 207 889 550
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Park u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800
Indonesia
PT. GRUNDFOS POMPA Graha Intirub Lt. 2 & 3 Jln. Cililitan Besar No.454. Makasar, Jakarta Timur ID-Jakarta 13650 Phone: +62 21-469-51900 Telefax: +62 21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. Gotanda Metalion Bldg., 5F, 5-21-15, Higashi-gotanda Shiagawa-ku, Tokyo 141-0022 Japan Phone: +81 35 448 1391 Telefax: +81 35 448 9619
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Veluwezoom 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
Romania
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундфос Россия 109544, г. Москва, ул. Школьная, 39- 41, стр. 1 Тел. (+7) 495 564-88-00 (495) 737-30­00 Факс (+7) 495 564 88 11 E-mail grundfos.moscow@grundfos.com
Serbia
Grundfos Srbija d.o.o. Omladinskih brigada 90b 11070 Novi Beograd Phone: +381 11 2258 740 Telefax: +381 11 2281 769 www.rs.grundfos.com
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689
Slovakia
GRUNDFOS s.r.o. Prievozská 4D 821 09 BRATISLAVA Phona: +421 2 5020 1426 sk.grundfos.com
Slovenia
GRUNDFOS d.o.o. Šlandrova 8b, SI-1231 Ljubljana-Črnuče Phone: +386 31 718 808 Telefax: +386 (0)1 5680 619 E-mail: slovenia@grundfos.si
South Africa
GRUNDFOS (PTY) LTD Corner Mountjoy and George Allen Roads Wilbart Ext. 2 Bedfordview 2008 Phone: (+27) 11 579 4800 Fax: (+27) 11 455 6066 E-mail: lsmart@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31 331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-44-806 8111 Telefax: +41-44-806 8115
Taiwan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
Бізнес Центр Європа Столичне шосе, 103 м. Київ, 03131, Україна Телефон: (+38 044) 237 04 00 Факс.: (+38 044) 237 04 01
E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971 4 8815 166 Telefax: +971 4 8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 4TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Uzbekistan
Grundfos Tashkent, Uzbekistan The Rep­resentative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292
Addresses Revised 29.09.2015
Grundfos companies
96427972 0915
ECM: 1156881
www.grundfos.com
© Copyright Grundfos Holding A/S
owned by Grundfos Holding A/S or Grundfos A/ S, Denmark. All rights reserved worldwide.
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks
Loading...