GRUNDFOS CR, CRI, CRN, CRT, ATEX operating instructions

Page 1
CR, CRI, CRN, CRT ATEX-approved pumps
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Page 2
English (GB) Installation and operating instructions
English (GB)
Original installation and operating instructions
The CR pumps comply with ATEX Directive 2014/34/ EU.
The pumps are suitable for use in zones classified according to Directive 1999/92/EC. In case of doubt, consult the above-mentioned directives, or contact Grundfos.

1. General information

1.1 Hazard statements

The symbols and hazard statements below may appear in Grundfos installation and operating instructions, safety instructions and service instructions.
CONTENTS
Page
1. General information
1.1 Hazard statements
1.2 Notes
2. Related installation and operating instructions
3. Receiving the product
4. Explosion protection document
5. Identification
5.1 Nameplate
5.2 Type key
5.3 Drive-end motor bearing
6. Scope of ATEX categories for CR pumps
7. Installing the product
7.1 Pump with single seal
7.2 Pump with MAGdrive
7.3 Pump with double seal
7.4 Bare-shaft pumps
8. Operating conditions
8.1 Maximum ambient temperature
8.2 Maximum liquid temperature
8.3 Temperature calculation
9. Before starting up and during operation of an ATEX-approved pump
9.1 Checklist
10. Maintenance and inspection
10.1 Tightening torques
10.2 Shaft seal
2
2 3
3 3 3 4
4
The hazard statements are structured in the following way:
5 6
7 8
8 8 9 9
10
10 10 11
12
12
14
14 14
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
Read this document before installing the product. Installation and operation must comply with local regulations and accepted codes of good practice.
2
Page 3

1.2 Notes

The symbols and notes below may appear in Grundfos installation and operating instructions, safety instructions and service instructions.
Observe these instructions for explosion­proof products.
A blue or grey circle with a white graphical symbol indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
Tips and advice that make the work easier.

2. Related installation and operating instructions

The X on the nameplate indicates that the pump is subject to special conditions for safe use as described in these instructions. The nameplate markings are described in the table in section
5. Identification.
In addition to these instructions, observe the following installation and operating instructions:
• CR, CRI, CRN: for standard pumps
• CR, CRI, CRN, CRT: removal of transport bracket and fitting of motor. For pumps without motor
• MG: Grundfos standard motors.
For special versions of the CR pumps, observe the relevant installation and operating instructions:
•CRN MAGdrive
• CR, CRI, CRN: double seal, back-to-back
• CR, CRI, CRN: double seal, tandem
• MG: Grundfos standard motors.

3. Receiving the product

If the pump is delivered without a motor, mount the motor and then adjust the chamber stack and shaft seal according to the procedure described in the installation and operating instructions, "Removal of transport bracket and fitting of motor", supplied with the pump.

4. Explosion protection document

The combination of CR pump and all monitoring equipment must be described in the explosion protection document according to Directive 1999/92/ EC.
English (GB)
3
Page 4

5. Identification

DK-8850 Bjerringbro,Denmark
Model-PN-SN Type Hz
pmax/tmax
Tech file no
Made in Denmark
P code: P115482
bar/°C
min
-1
excl.motor 500kg
/hm
3
kW [P2]
H/H max m 0(,
ȘS 
B-96123526-98438832
CR255-1-1A-F-A-E-HQQE
435/248
2917 64
CCW
98964685X
99356347
50/60
4.0
0.7 69.7
14.2/22.1
21
435-580/176
II 3G Ex h IIC T4...T3 Gb
English (GB)

5.1 Nameplate

The nameplate on the pump head gives the following details:
• data of standard pump
• data of ATEX marking – technical file number – serial number – Ex category.
Fig. 1 Example of a CR nameplate with ATEX
approval
ATEX rating
Pos. Description
Group
II
I: Underground in mines II: Surface equipment
Category M2: Mining
3G
2G, 3G: Gas/vapours 2D, 3D: Dust
Ex h Protection type
Environment group IIC: Gas/vapours
IIC
1
T4...T3
TM07 5039 0719
98964685
2
IIIC: Combustible dust IIIB: Non-magnetic dust
Maximum surface temperature according to 80079-36. Temperature range or specific temperature. T4...T3: Gas T125 °C: Dust
EPL (Equipment Protection Level).
Gb
Gb, Gc: Gas Db, Dc: Dust
File number for technical file stored at DEKRA.
Indicates that the equipment is subject to special
X
conditions for safe use. The conditions are mentioned in this document.
Data for the ATEX marking only refers to the part including the coupling. The motor has a separate nameplate.
4
Page 5

5.2 Type key

5.2.1 Type key example

Example CR 32- 2 1- X- X- X- X- XXXX
Type range: CR, CRN Rated flow rate in m Number of stages Number of impellers with reduced diameter Code for pump version Code for pipe connection Code for materials Code for rubber pump parts Code for shaft seal

5.2.2 Key to codes for pump version

Codes for pump version
A Basic version BOversize motor E Pump with certificate H Horizontal version I Different pressure rating K Pump with low NPSH M Magnetic drive O Cleaned and dried P Undersize motor S High-pressure pump T Thrust handling device (THD) U ATEX approved pump Y Electropolished Z Pumps with bearing flange
3
/h
English (GB)
5
Page 6

5.3 Drive-end motor bearing

English (GB)
Make sure to use the correct type of drive-end (DE) motor bearing for the bare-shaft pump. Please check the specific pump range and pump version stated on the nameplate and select the corresponding DE bearing.
Pump version
DE bearing
CR 1-64 pump range
1)
Deep-groove ball
bearing
(62/63xx)
Angular contact
bearing
(73xx)
Deep-groove ball
(62/63xx)
DE bearing
CR 95-255 pump range
Angular contact
bearing
bearing
(73xx)
A Standard pump 0.37 - 3 kW 4-45 kW 75-200 kW 5.5 - 55 kW
Pump with thrust
T
handling device
2)
(THD) Pump with bearing
Z
1)
2)
2)
flange
Refer to the codes for pump version in section 5.2 Type key. Factory product variants (FPV).
- - 5.5 - 55 kW Not allowed
0.37 - 45 kW Not allowed 5.5 - 200 kW Not allowed
6
Page 7

6. Scope of ATEX categories for CR pumps

Directive ATEX-approved CR pumps
2014/34/EU GROUP I
Category M Environment: EPL1): Ma Mb 1999/92/EC
2)
CR pumps None
Motors None None
2014/34/EU GROUP II
Category 1 Category 2 Category 3
Environment:
1)
EPL
: Ga Da Gb Db Gc Dc
1999/92/EC
2)
G D G D G D
Zone 0 Zone 20 Zone 1 Zone 21 Zone 2 Zone 22
CR pumps None None
Motors None None
1)
EPL: Equipment Protection Level.
2)
Important: The link between groups, categories and zones is explained in Directive1999/92/EC. Note that this is a minimum directive. Some EU countries may therefore have stricter local rules. The user or installer is always responsible for checking that the group and category of the pump correspond to the zone classification of the installation site.
1 2
-­CR
CRI
CRN
CR
CRI CRN CRT
• II 2G Ex eb IIC T3 Gb
• II 2G Ex db IIC T4 Gb
CR
CRI CRN CRT
• II 2D Ex tb IIIC T125 °C Db
CR
CRI CRN CRT
• II 2G Ex eb IIC T3 Gb
• II 2G Ex db IIC T4 Gb
CR
CRI CRN CRT
• II 3D Ex tc IIIC T125 °C Dc
English (GB)
7
Page 8

7. Installing the product

English (GB)
DANGER
Explosion risk
Death or serious personal injury
- Do not let the pump run dry.
- Make sure that the pump is filled with pumped liquid during operation.
DANGER
Explosion risk
Death or serious personal injury
- Replace the shaft seal if increased leakage is observed.
DANGER
Explosion risk
Death or serious personal injury
- Always install the pump with the motor above the pump to avoid overheating of the motor bearings. See fig. 2.
The responsibility for checking the functions of the dry-running protection, such as flow rate, sealing pressure and temperature of the barrier or flushing liquid, rests with the installer or owner.
Fig. 2 Positioning the pump

7.1 Pump with single seal

7.1.1 Non-flammable liquids Category 2G/D/M2

Make sure that the pump is filled with pumped liquid during operation. If this is not possible, ensure appropriate monitoring, for example dry-running protection to stop the pump in case of malfunction.
Category 3G/D
No additional monitoring, for example dry-running protection, is required for the pump system.

7.1.2 Flammable liquids, pump unit Category 2G/D/M2 and 3G/D/M2

Make sure that the pump is filled with pumped liquid during operation. If this is not possible, ensure appropriate monitoring, for example dry-running protection to stop the pump in case of malfunction. Ensure sufficient ventilation around the pump.
The leakage rate of a shaft seal is 1-10 ml for each 24 hours of operation. For some types of liquids, the leakage will not be visible due to evaporation. During the run-in period, larger leakage of 1-20 ml per 24 hours of operation can occur. Liquids like oil or glycol-water mixtures evaporate slower than water and will leave residuals. Ensure proper ventilation to maintain the zone classification.
Category M2
Protect the pump with a guard to prevent damage from falling or ejected objects.

7.2 Pump with MAGdrive

DANGER
TM01 1241 4102
See the CRN MAGdrive installation and operating instructions at http://net.grundfos.com/qr/i/
96464310.
Explosion risk
Death or serious personal injury
- Always fill the pump with liquid and ensure that the required minimum flow rate is obtained.
8
Page 9

7.3 Pump with double seal

40 50 60 70 80 90 100 110 120
t [°C]
0
10
20
30
Qmin
[%]
Back-to-back or tandem

7.3.1 Non-flammable liquids, pump unit Category 2G/D

Make sure that the pump is filled with pumped liquid during operation. If this is not possible, ensure appropriate monitoring, for example dry-running protection to stop the pump in case of malfunction.
Category 3G/D
No additional monitoring, such as dry-running protection, is required for the pump system.

7.3.2 Flammable liquids, pump unit Category 2G/D/M2 and 3G/D/M2

Make sure that the pump is filled with pumped liquid during operation. If this is not possible, ensure appropriate monitoring, for example dry-running protection to stop the pump in case of malfunction. Ensure sufficient ventilation around the pump.
The leakage rate of a shaft seal is 1-10 ml for each 24 hours of operation. For some types of liquids, the leakage will not be visible due to evaporation. During the run-in period, larger leakage of 1-20 ml per 24 hours of operation can occur. Liquids like oil or glycol-water mixtures evaporate slower than water and will leave residuals. Ensure proper ventilation to maintain the zone classification.
Category M2
Protect the pump by a guard to prevent damage from falling or ejected objects.

7.4 Bare-shaft pumps

Bare-shaft pumps with motors of 4 kW and up must use angular contact bearings.
However, if the pumps are fitted with a thrust handling device (THD) or a bearing flange, they must never be used with angular contact bearings. If in doubt, contact Grundfos.
Check if the pump is fitted with a thrust handling device (THD). If the pump is a THD marked pump, follow the instructions below.
The thrust handling device (THD) is factory-fitted on CR, CRN 95-255 for motor sizes of 75 kW and above.

7.4.1 Bare-shaft pumps with a thrust handling device

DANGER
Explosion risk
Death or serious personal injury
- Temperature monitoring of the motor bearings is required to ensure that the pump stops in case of overheating.
DANGER
Explosion risk
Death or serious personal injury
- Do not use ATEX motors with angular contact bearings on pumps fitted with a thrust handling device (THD).
DANGER
Explosion risk
Death or serious personal injury
- Temperature sensors must be installed by qualified persons in accordance with local regulations.
Minimum flow rate
Due to the risk of overheating, do not use the pump at flows below the minimum flow rate.
The curve below shows the minimum flow rate as a percentage of the rated flow rate in relation to the liquid temperature.
Fig. 3 Minimum flow rate in percentage of
nominal flow
English (GB)
TM02 8290 4903
9
Page 10

8. Operating conditions

English (GB)
DANGER
Explosion risk
Death or serious personal injury
- Ensure that the required minimum inlet pressure is always available.
See the CR, CRI, CRN installation and operating instructions:
– http://net.grundfos.com/qr/i/96462123 – http://net.grundfos.com/qr/i/99078486
DANGER
Explosion risk
Death or serious personal injury
- Do not operate the pump with higher liquid temperature than the maximum liquid temperature (t pump nameplate.
- The calculated maximum permissible liquid temperature must not be exceeded.
) stated on the
max

8.1 Maximum ambient temperature

The maximum ambient temperature for the pump: ­20 to +60 °C.

8.2 Maximum liquid temperature

In normal pump operation, the highest temperatures are to be expected at the surface of the pump casing and at the shaft seal. The surface temperature will normally follow the temperature of the liquid.
You can calculate the permissible liquid temperature by finding the maximum permissible temperature at the surface of the pump during operation in the table shown in section 8.3.1 Temperature class, and reduce it with the temperature contribution from shaft seals, see table in section 8.3.2 Shaft seal
temperature.
Section 8.3 Temperature calculation contains a diagram which shows how the maximum surface temperature depends on the liquid temperature and the temperature contribution from the shaft seal.
Calculation example
Based on temperature contribution from a HQQX shaft seal, media class 1, shaft diameter 22 and pressure 2.5 Mpa.
Temperature class (T4) = 135 °C, see section
8.3.1 Temperature class.
Temperature contribution from HQQX shaft seal = 24 °C, see section 8.3.2 Shaft seal temperature.
Safety margin for Group II = 5 °C according to the ATEX standard.
Result
Maximum permissible liquid temperature: T4-contribution from shaft seal-safety margin = 135 -
24 - 5 = 106 °C. Pumps that are allowed to pump liquids up to a
maximum of 150 °C are equipped with a tandem shaft seal. In this case, the temperature and flow rate of the flushing liquid must be according to the description in the installation and operating instructions "CR, CRI, CRN-Double seal (tandem)" at http://net.grundfos.com/qr/i/96477555.
Make sure that the combination of CR pump and dry­running protection is described in the explosion protection document according to Directive 1999/92/ EC.
The responsibility for checking the correct flow rate and the temperature of the flushing liquid rests with the installer or owner.
Increased leakage rate can indicate damaged elastomers and rubber parts in the pump. For some liquid types, the leakage is not visible due to evaporation.
10
Page 11

8.3 Temperature calculation

1
2
3
The illustration below shows the maximum surface temperature of the pump as a result of the maximum liquid temperature and temperature rise in the shaft seal.
Fig. 4 Maximum surface temperature
Pos. Figure legend
Maximum surface temperature of the
1
pump Temperature rise in the shaft seal.
2
Calculated by Grundfos. See section
8.3.2 Shaft seal temperature.
3 Maximum liquid temperature

8.3.1 Temperature class

Temperature class
T1 450 T2 300 T3 200 T4 135 T5 100 T6 85
The maximum surface temperature for dust is stated on the nameplate.
Maximum surface
temperature
[°C]

8.3.2 Shaft seal temperature

In order to calculate the pump surface temperature and temperature class, the below tables show the temperature rise in the shaft seal for different shaft diameters, different pressure values and various media classes.
Shaft seal: HQQx/HUUx/HQUx and
AUUx/AQQx/DQQx
Rpm: 2900/3500
Pressure [MPa]
12.54
Shaft seal temperature rise [°C]
22 24 26
Rpm: 2900/3500
Pressure [MPa]
12.54
Shaft seal temperature rise [°C]
18 20 22
TM06 4445 2315
Shaft
diameter
[mm]
12 16 22 28 36
Shaft
diameter
[mm]
12 16 22 28 36
Shaft seal: HQBx/HUBx
English (GB)
11
Page 12
9. Before starting up and during
English (GB)
operation of an ATEX-approved pump
DANGER
Explosion risk
Death or serious personal injury
- Do not run the pump at speeds exceeding the rated speed. See pump nameplate.

9.1 Checklist

DANGER
Explosion risk
Death or serious personal injury
- Follow the checklist below.
Observe this checklist:
1. Check that the ATEX rating of the motor, pump and accessories corresponds to the specified category. See section 6. Scope of ATEX
categories for CR pumps. If the motor, pump or
accessory categories differ, the lower rating is valid.
2. If the pump falls under category M2, check that the pump is protected by a guard to prevent damage from falling or ejected objects.
3. Clean the cavities behind the pump's coupling guard on a regular basis to avoid hazardous dust deposits.
4. Check that the motor output power corresponds to the required P
5. Check that the pump is as ordered, see nameplates.
6. Check the axial alignment of the chamber stack. See the label on the inside of the coupling guard. Check that the shaft seal components, rubber parts and seal surfaces are suitable for the pumped liquid.
7. Check that the shaft can rotate freely. There must be no mechanical contact between impeller and chamber.
8. Check that the pump has been filled with liquid and vented. The pump must never run dry.
9. Check the direction of rotation of the motor, see the arrow on the top of the fan cover.
10. If you have chosen a pump with double seal, back-to-back, check that the seal chamber is pressurised. Always pressurise the chamber during operation. Always use ATEX-approved equipment.
of the pump, see nameplates.
2
11. If you have chosen a pump with double seal, tandem, check that the seal chamber is completely filled with liquid. The seal chamber must always be filled with flushing liquid during operation. The dry-running protection must be ATEX-approved.
12. Follow the special startup procedures for these pump types:
– MAGdrive pumps – pumps with double seal, back-to-back – pumps with double seal, tandem.
For further information, see the installation and operating instructions for the pump in question.
13. Check that the liquid temperature never exceeds the maximum liquid temperature, t the nameplate.
14. Avoid overheating of the pump. Operation against a closed outlet valve may cause overheating. Install a bypass with a pressure relief non-return valve.
15. Check for abnormal noise during operation to avoid overheating of the pump.
16. Re-vent the pump in either of these situations:
– the pump has been stopped for a period of
time.
– air has accumulated in the pump.
17. If the pump is with bearing bracket, check for bearing noise every week. Replace the bearing if it shows signs of wear.
18. The auto-ignition temperature of the pumped liquid must be 50 K above the maximum surface temperature of the pump.
19. Make sure to apply the correct inlet pressure. Use the correct table for the vapour pressure for the pumped liquid. See section
9.1.1 Specification and calculation of inlet pressure.
, stated on
max
12
Page 13
9.1.1 Specification and calculation of inlet
Hv
H
NPSH
Pb
Hf
20
15
12 10
8,0
6,0 5,0
4,0 3,0
2,0
1,0 0,8
0,6
0,4 0,3
0,2
0,1
1,5
120
110
90
100
80
70
60
50
40
30
20
10
0
Hv (m)
tm
(°C)
150
130
140
25
35
45 40
30
160
170
180
190
62
79
100
126
pressure
Fig. 5 Schematic view of open system with a
CR pump
Calculation of inlet pressure
Calculate the maximum suction lift "H" in m head as follows:
H = Pb x 10.2 - NPSH - Hf - Hv - Hs
English (GB)
TM02 0118 3800
Pb = Barometric pressure in bar.
Barometric pressure can be set to 1 bar. In closed systems, Pb indicates the system pressure in bar.
(10 bar = 1 MPa)
NPSH = Net Positive Suction Head in m head, to
Hf = Friction loss in the inlet pipe in m head
Hv = Vapour pressure for water in m head.
tm = Liquid temperature. Hs = Safety margin = minimum 0.5 m head.
be read from the NPSH curve in the appendix* (at the highest flow rate the pump will be delivering).
* Link to appendix, see section
Appendix with NPSH curves.
at the highest flow rate the pump will be delivering.
See fig. 6. If the pumped liquid is not water, then use the vapour pressure for the liquid which is being pumped.
Fig. 6 Vapour pressure for water in m head
If the calculated "H" is positive, the pump can operate at a suction lift of maximum "H" m head.
If the calculated "H" is negative, an inlet pressure of minimum "H" m head is required. There must be a pressure equal to the calculated "H" during operation.
Example:
Pb = 1 bar. Pump type: CR 15, 50 Hz. Flow rate: 15 m
3
/h. NPSH (see the appendix*): 1.1 m head. Hf = 3.0 m head. Liquid temperature: 60 °C. Hv (see fig. 6): 2.1 m head. H = Pb x 10.2 - NPSH - Hf - Hv - Hs [m head]. H = 1 x 10.2 - 1.1 - 3.0 - 2.1 - 0.5 = 3.5 m head. This means that the pump can operate at a suction
lift of maximum 3.5 m head. Pressure calculated in bar: 3.5 x 0.0981 = 0.343 bar. Pressure calculated in kPa: 3.5 x 9.81 = 34.3 kPa. * Link to appendix, see section Appendix with
NPSH curves.
TM02 7445 3503
13
Page 14

9.1.2 Appendix with NPSH curves

Coupling screw (4 pcs)
Shaft seal
Shaft seal set screw (3 pcs)
Shaft seal set screw (3 pcs)
Shaft seal flange screw (4 pcs)
English (GB)
Appendix:
The appendix referred to in section 9.1.1 is found in the standard CR, CRI, CRN installation and operating instructions:
http://net.grundfos.com/qr/i/96462123

10. Maintenance and inspection

Service documentation is available in Grundfos Product Center (http://product­selection.grundfos.com/).
If you have any questions, please contact the nearest Grundfos company or service workshop.

10.1 Tightening torques

DANGER
Explosion risk
Death or serious personal injury
- The coupling screws, shaft seal, shaft seal flange screws and shaft seal set screws must be tightened according to the specified torque values.

10.1.1 Coupling

10.2 Shaft seal

CR, CRI, CRN 1s, 1, 3, 5, 10, 15, 20, 95, 125, 155, 185, 215, 255
Fig. 8 Shaft seal and shaft seal set screws for
Pump size
CR, CRI, CRN 1s, 1, 3, 5
CR, CRI, CRN 10, 15, 20
CR, CRN 95, 125, 155, 185, 215, 255
CR, CRN 32, 45, 64, 90, 120, 150
CR, CRI, CRN 1s, 1, 3, 5, 95, 125, 155, 185, 215, 255
Tightening torque
Shaft seal
Shaft seal set
screws (3 pcs)
M28-35 Nm
M5 - 2.5 Nm
M33-35 Nm
Hex 60-100 Nm Hex 75-150 Nm
M6-6 Nm
TM07 2395 3418
Fig. 7 Coupling screws
Pump size
CR, CRI, CRN 1s, 1, 3
CR, CRI, CRN 10, 15, 20
CR, CRI, CRN 32, 45, 64, 90
CR, CRI, CRN 120, 150
CR, CRN 95, 125, 155, 185, 215, 255
14
Coupling screws (4 pcs)
Tightening torque
M6-13 Nm M8-31 Nm
M10-61 Nm
M6-13 Nm M8-31 Nm
M10-62 Nm
M10-85 Nm
M10-85 Nm
M16-100 Nm
M10-85 Nm
M16-100 Nm
TM07 2396 3418
Fig. 9 Shaft seal flange screws and shaft seal
set screws for CR, CRN 32, 45, 64, 90, 120, 150
Tightening torque
Pump size
CR, CRI, CRN 32, 45, 64, 90
CR, CRI, CRN 120, 150
Shaft seal
flange screws
(4 pcs)
M10-62 Nm M6-6 Nm
TM07 2397 3418
Shaft seal set
screws (3 pcs)
Page 15
YETKİLİ GRUNDFOS SERVİSLERİ
Firma Adres
GRUNDFOS POMPA KOCAELİ
SUNPO ELEKTRİK ADANA
ARDA POMPA ANKARA
UĞUR SU POMPALARI ANKARA
GROSER A.Ş. ANTALYA
KOÇYİĞİTLER ELEKTRİK BOBİNAJ ANTALYA
TEKNİK BOBİNAJ BURSA
ASİN TEKNOLOJİ GAZİANTEP
ARI MOTOR İSTANBUL
SERİ MEKANİK İSTANBUL
DAMLA POMPA İZMİR
ÇAĞRI ELEKTRİK KAYSERİ
MAKSOM OTOMASYON SAMSUN
DETAY MÜHENDİSLİK TEKİRDAĞ
ROTATEK ENDÜSTRİYEL TEKİRDAĞ
İLDEM TEKNİK ISITMA VAN
BARIŞ BOBİNAJ K.K.T.C.
GEBZE ORGANİZE SANAYİ BÖLGESİ. İHSAN DEDE CADDESİ.2.YOL
200.SOKAK.NO:204 GEBZE KOCAELİ YEŞİLOBA MAH. 46003 SOK.
ARSLANDAMI İŞ MERK. C BLOK NO:6/2­I SEYHAN ADANA
26 NOLU İŞ MERKEZİ 1120.SOKAK NO:5/1,5/5 OSTİM/ANKARA
AHİ EVRAN MAHALLESİ ÇAĞRIŞIM CADDESİ NO:2/15 SİNCAN /ANKARA
ŞAFAK MAHALLESİ.5041.SOKAK.SANAYİ 28 C BLOK NO:29 KEPEZ ANTALYA
ORTA MAH. SERİK CAD. NO.116 SERİK ANTALYA
ALAADDİN BEY MH.624.SK MESE 5 İŞ MERKEZİ NO:26 D:10 NİLÜFER/BURSA
MÜCAHİTLER MAHALLESİ 54 NOLU SOKAK.GÜNEYDOĞU İŞ MERKEZİ NO:10/A ŞEHİTKAMİL
ORHANLI MESCİT MH.DEMOKRASİ CD.BİRMES SAN.SİT.A-3 BLOK NO:9 TUZLA İSTANBUL
SEYİTNİZAM MAH. DEMİRCİLER SİT.
7.YOL . NO:6 ZEYTİNBURNU İSTANBUL
1203/4 SOKAK NO:2/E YENİŞEHİR İZMİR
ESKİ SANAYİ BÖLGESİ 3.CADDE NO;3­B KOCASİNAN-KAYSERİ
19 MAYIS MAHALLESİ.642.SOKAK.NO:23 TEKKEKÖY SAMSUN
ZAFER MAHALLESİ ŞEHİT YÜZBAŞI YÜCEL KENTER CADDESİ 06/A BLOK NO:5-6 ÇORLU TEKİRDAĞ
ZAFER MH. ŞEHİT YÜZBAŞI YÜCEL KENTER CD. YENİ SANAYİ SİTESİ 08-A BLOK NO:14 ÇORLU / TEKİRDAĞ
ŞEREFİYE MAH ORDU CAD ARAS AP NO 75 İPEKYOLU VAN
LARNAKA YOLU ÜZERİ.PAPATYA APT.NO:3-4 GAZİMAĞUSA
Telefon
Cep telefonu
Faks
0262 679 79 79 0553 259 51 63 0262 679 79 05
0322 428 50 14 0533 461 71 14 0322 428 48 49
0312 385 98 93 0541 805 89 44 0312 385 8904
0312 394 37 52 0532 505 12 62 0312 394 37 19
0242 221 43 43 0532 793 89 74 0242 221 43 42
0242 722 48 46 0532 523 29 34 0242 722 48 46
0224 443 78 83 0507 311 19 08 0224 443 78 95
0342 321 69 66 0532 698 69 66 0342 321 69 61
0216 394 21 67 0532 501 47 69 0216 394 23 39
0212 679 57 23 0532 740 18 02 0212 415 61 98
0232 449 02 48 0532 277 96 44 0232 459 43 05
0352 320 19 64 0532 326 23 25 0352 330 37 36
0362 256 23 56 0532 646 61 42
-
0282 673 51 33 0549 668 68 68 0282 673 51 35
0282 654 51 99 0532 788 11 39 0282 654 51 81
0432 216 20 83 0532 237 54 59 0432 216 20 83
0542 884 06 62 0542 854 11 35 0533 884 06 62
İlgili Kişi
Eposta
EMRAH ŞİMŞEK
esimsek@grundfos.com
LEVENT BAKIRKOL
sunpo-elektrik@hotmail.com
METİN ENGİN CANBAZ
metincanbaz@ardapompa.com.tr
UĞUR YETİŞ ÖCAL
uguryetisocal@gmail.com
DOĞAN YÜCEL
servis@groseras.com
BİLAL KOÇYİĞİT
kocyigitler@kocyigitlerbobinaj.com
GÜLDEN MÜÇEOĞLU
gulden@tbobinaj.com.tr
MEHMET DUMAN
mduman@asinteknoloji.com.tr
EMİN ARI
aycan@arimotor.com.tr
TAMER ERÜNSAL
servis@serimekanik.com
NEVZAT KIYAK
nkiyak@damlapompa.com
ADEM ÇAKICI
kayseri.cagrielektrik@gmail.com
MUSTAFA SARI
info@maksom.com
EROL KARTOĞLU
erol@detay-muhendislik.com
ÖZCAN AKBAŞ
ozcan@rotaendustriyel.com
BURHAN DEMİREKİ
il-dem-teknik@hotmail.com
BARIŞ KIZILKILINÇ
barisbobinaj@hotmail.com
Grundfos companies
Page 16
Grundfos companies
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 Garín Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belarus
Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56, БЦ «Порт» Тел.: +375 17 397 397 3
+375 17 397 397 4 Факс: +375 17 397 397 1 E-mail: minsk@grundfos.com
Bosnia and Herzegovina
GRUNDFOS Sarajevo Zmaja od Bosne 7-7A, BH-71000 Sarajevo Phone: +387 33 592 480 Telefax: +387 33 590 465 www.ba.grundfos.com e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 10F The Hub, No. 33 Suhong Road Minhang District Shanghai 201106 PRC Phone: +86 21 612 252 22 Telefax: +86 21 612 253 33
COLOMBIA
GRUNDFOS Colombia S.A.S. Km 1.5 vía Siberia-Cota Conj. Potrero Chico, Parque Empresarial Arcos de Cota Bod. 1A. Cota, Cundinamarca Phone: +57(1)-2913444 Telefax: +57(1)-8764586
Croatia
GRUNDFOS CROATIA d.o.o. Buzinski prilaz 38, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.hr.grundfos.com
GRUNDFOS Sales Czechia and Slovakia s.r.o.
Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Trukkikuja 1 FI-01360 Vantaa Phone: +358-(0) 207 889 500
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Tópark u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800
Indonesia
PT. GRUNDFOS POMPA Graha Intirub Lt. 2 & 3 Jln. Cililitan Besar No.454. Makasar, Jakarta Timur ID-Jakarta 13650 Phone: +62 21-469-51900 Telefax: +62 21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. 1-2-3, Shin-Miyakoda, Kita-ku, Hamamatsu 431-2103 Japan Phone: +81 53 428 4760 Telefax: +81 53 428 5005
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Page 17
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Veluwezoom 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
Romania
Grundfos Pompe România SRL S-PARK BUSINESS CENTER, Clădirea A2, etaj 2, Str. Tipografilor, Nr. 11-15, Sector 1, Cod 013714, Bucuresti, Romania, Tel: 004 021 2004 100 E-mail: romania@grundfos.ro www.grundfos.ro
Russia
ООО Грундфос Россия ул. Школьная, 39-41 Москва, RU-109544, Russia Тел. (+7) 495 564-88-00 (495) 737-30­00 Факс (+7) 495 564 8811 E-mail grundfos.moscow@grundfos.com
Serbia
Grundfos Srbija d.o.o. Omladinskih brigada 90b 11070 Novi Beograd Phone: +381 11 2258 740 Telefax: +381 11 2281 769 www.rs.grundfos.com
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689
Slovakia
GRUNDFOS s.r.o. Prievozská 4D 821 09 BRATISLAVA Phona: +421 2 5020 1426 sk.grundfos.com
Slovenia
GRUNDFOS LJUBLJANA, d.o.o. Leskoškova 9e, 1122 Ljubljana Phone: +386 (0) 1 568 06 10 Telefax: +386 (0)1 568 06 19 E-mail: tehnika-si@grundfos.com
South Africa
Grundfos (PTY) Ltd. 16 Lascelles Drive, Meadowbrook Estate 1609 Germiston, Johannesburg Tel.: (+27) 10 248 6000 Fax: (+27) 10 248 6002 E-mail: lgradidge@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31 331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-44-806 8111 Telefax: +41-44-806 8115
Tai wan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
Бізнес Центр Європа Столичне шосе, 103 м. Київ, 03131, Україна Телефон: (+38 044) 237 04 00 Факс.: (+38 044) 237 04 01 E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971 4 8815 166 Telefax: +971 4 8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 4TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 9300 Loiret Blvd. Lenexa, Kansas 66219 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Uzbekistan
Grundfos Tashkent, Uzbekistan The Representative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292
Addresses Revised 09.09.2020
Grundfos companies
Page 18
96506846 12.2020
ECM: 1307740
© 2021 Grundfos Holding A/S, all rights reserved.
Trademarks displayed in this material, incl uding but not limited to Grundfos, the Grundfos logo and “be
think innovate” are registered trademarks owned by The Grundfos Group. All rights reserved.
www.grundfos.com
Loading...