English (US) Installation and operating instructions
Original installation and operating instructions
CONTENTS
1.Limited warranty
2.General information
2.1Hazard statements
2.2Abbreviations and definitions
3.Receiving the product
3.1Transporting the product
3.2Inspecting the product
4.Installing the product
4.1Mechanical installation
4.2Electrical installation
4.3Installing a communication interface module
4.4Changing the position of the control panel
5.Product introduction
5.1Product description
5.2Identification
5.3Bus signal
5.4Grundfos Eye
5.5Signal relays
6.User interfaces
6.1Advanced control panel
7.Setting the product
7.1Grundfos GO Remote
7.2Menu overview for Grundfos GO Remote
8.Control functions
8.1Description of selected functions
8.2Assist
8.3Selection of control mode
8.4Changing the position of the control panel
8.5Bus signal
8.6Priority of settings
9.Servicing the product
9.1Motor
9.2Pump
9.3Cleaning the product
10.Technical data
10.1 Operating conditions
10.2 Megging
10.3 Technical data, single-phase motors
10.4 Technical data, three-phase motors
10.5 Inputs/outputs
10.6 Other technical data
11.Disposing of the product
Page
13
14
15
15
16
16
17
18
19
19
20
20
21
23
23
27
28
29
30
30
31
31
31
31
31
31
32
32
32
33
34
35
1. Limited warranty
Products manufactured by Grundfos Pumps Corporation
(Grundfos) are warranted to the original user only to be free of
defects in material and workmanship for a period of 24 months
from date of installation, but not more than 30 months from date
4
of manufacture. Grundfos' liability under this warranty shall be
5
limited to repairing or replacing at Grundfos' option, without
5
charge, F.O.B. Grundfos' factory or authorized service station,
5
any product of Grundfos manufacture. Grundfos will not be liable
6
for any costs of removal, installation, transportation, or any other
6
charges that may arise in connection with a warranty claim.
6
Products which are sold, but not manufactured by Grundfos, are
6
subject to the warranty provided by the manufacturer of said
6
products and not by Grundfos' warranty.
7
Grundfos will not be liable for damage or wear to products caused
by abnormal operating conditions, accident, abuse, misuse,
unauthorized alteration or repair, or if the product was not
installed in accordance with Grundfos' printed installation and
operating instructions and accepted codes of good practice. The
warranty does not cover normal wear and tear.
To obtain service under this warranty, the defective product must
be returned to the distributor or dealer of Grundfos' products from
which it was purchased together with proof of purchase and
installation date, failure date and supporting installation data.
Unless otherwise provided, the distributor or dealer will contact
Grundfos or an authorized service station for instructions. Any
defective product to be returned to Grundfos or a service station
must be sent freight prepaid; documentation supporting the
warranty claim and/or a Return Material Authorization must be
included if so instructed.
Grundfos will not be liable for any incidental or consequential
damages, losses, or expenses arising from installation, use, or
any other causes. There are no express or implied warranties,
including merchantability or fitness for a particular purpose, which
extend beyond those warranties described or referred to above.
Some jurisdictions do not allow the exclusion or limitation of
incidental or consequential damages and some jurisdictions do
not allow limitations on how long implied warranties may last.
Therefore, the above limitations or exclusions may not apply to
you. This warranty gives you specific legal rights and you may
also have other rights which vary from jurisdiction to jurisdiction.
Products which are repaired or replaced by Grundfos or
authorized service center under the provisions of these limited
warranty terms will continue to be covered by Grundfos warranty
only through the remainder of the original warranty period set
forth by the original purchase date.
Read this document before installing the product.
Installation and operation must comply with local
regulations and accepted codes of good practice.
4
2. General information
These installation and operating instructions are a supplement to
the installation and operating instructions for the corresponding
standard pumps CR, CRI, CRN, CRK, SPK, MTR and CM.
For instructions not mentioned specifically in this manual, see the
installation and operating instructions for the standard pump.
2.1 Hazard statements
The symbols and hazard statements below may appear in
Grundfos installation and operating instructions, safety
instructions and service instructions.
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate personal injury.
The hazard statements are structured in the following way:
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
The symbols and notes below may appear in Grundfos
installation and operating instructions, safety instructions and
service instructions.
Observe these instructions for explosion-proof
products.
A blue or grey circle with a white graphical symbol
indicates that an action must be taken.
2.2 Abbreviations and definitions
AIAnalog input.
ALAlarm, out of range at lower limit.
AOAnalog output.
AUAlarm, out of range at upper limit.
CIMCommunication interface module.
The ability to draw current into the terminal and
guide it towards GND in the internal circuitry.
The ability to push current out of the terminal
and into an external load which must return it
to GND.
Grundfos Digital Sensor.
Factory-fitted sensor in some Grundfos pumps.
Ground fault circuit interrupter.
(USA and Canada).
Low voltage with the risk of electric shock if the
terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, except earth (ground) faults in
other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, including earth (ground) faults in
other circuits.
English (US)
A red or grey circle with a diagonal bar, possibly with
a black graphical symbol, indicates that an action
must not be taken or must be stopped.
If these instructions are not observed, it may result in
malfunction or damage to the equipment.
Tips and advice that make the work easier.
5
English (US)
D
3. Receiving the product
4.1.2 Mounting
3.1 Transporting the product
WARNING
Falling objects
Death or serious personal injury
- Secure the product during transportation to prevent
it from tilting or falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.
• Motors from 3 to 5 Hp (2.2 to 5.5 kW): Do not stack more than
two motors in their original packaging.
• Motors from 7 1/2 to 15 Hp (5.5 to 11 kW): Do not stack the
motors.
3.2 Inspecting the product
Before you install the product, do the following:
1. Check that the product is as ordered.
2. Check that no visible parts have been damaged.
3. If parts are damaged or missing, contact your local Grundfos
sales company.
4. Installing the product
4.1 Mechanical installation
4.1.1 Handling the product
Observe local regulations setting limits for manual lifting or
handling. The motor weight is stated on the nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting equipment to
the motor eyebolts when handling the product.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation by bolts
through the holes in the flange or the base plate.
In order to maintain the UL mark, additional
requirements apply to the equipment. See Appendix,
page 36.
4.1.3 Cable entries
See the size of the cable entries in section 10.6 Other technical
data.
4.1.4 Cable glands
The number and size of cable glands delivered with the pump
depends on the motor size. See section 10.6 Other technical data.
4.1.5 Ensuring motor cooling
Leave at least 2 in. (50 mm) between the end of the fan cover and
a wall or other fixed objects. See fig. 1.
TM05 5236 3512
Fig. 1 Minimum distance (D) from the motor to a wall or other
fixed objects
4.1.6 Outdoor installation
The enclosure class of MLE motor is a NEMA 3 rating. If you
install the motor outdoors, provide the motor with a suitable cover
and open the drain holes to avoid condensation on the electronic
components. See fig. 2.
When fitting a cover to the motor, observe the
guideline in section 4.1.5 Ensuring motor cooling.
Do not lift the product by the terminal box.
6
The cover must be sufficiently large to ensure that the motor is
B3B14B5
not exposed to direct sunlight, rain or snow. Grundfos does not
supply covers. We therefore recommend that you have a cover
built for the specific application. In areas with high humidity, we
recommend that you enable the built-in standstill heating
function.
Fig. 2 Examples of covers (not supplied by Grundfos)
In order to maintain the UL mark, additional
requirements apply to the equipment. See Appendix,
page 36.
4.1.7 Drain holes
When the motor is installed in moist surroundings or areas with
high humidity, the bottom drain hole must be open. The enclosure
class of the motor will then be lower. This helps prevent
condensation in the motor as the motor becomes self-venting,
and it allows water and humid air to escape.
The motor has a plugged drain hole on the drive side. You can
turn the flange 90 ° to both sides or 180 °.
4.2.1 Protection against electric shock, indirect contact
WARNING
Electric shock
- Death or serious personal injury
- Connect the motor to a protective ground and
provide protection against indirect contact in
accordance with local regulations.
Protective-ground conductors must always have a yellow/green
(PE) or yellow/green/blue (PEN) color marking.
Protection against power supply voltage transients
TM05 3496 3512
The motor is protected against power supply voltage transients in
accordance with EN 61800-3.
Motor protection
The motor requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking.
4.2.2 Cable requirements
Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as to cable
cross-sections.
Single-phase supply
English (US)
Fig. 3 Drain holes
4.2 Electrical installation
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before you
make any connections in the terminal box. Make
sure that the power supply cannot be accidentally
switched on.
DANGER
Electric shock
Death or serious personal injury
- Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If the power supply cable is damaged, it must be replaced by the
manufacturer, the manufacturer's service partner or a similarly
qualified person.
The user or the installer is responsible for the installation of
correct grounding and protection according to local regulations.
All operations must be carried out by a qualified electrician.
Conductor type
Solid
Stranded0.5 - 2.530-12
TM02 9037 1604
Three-phase supply
Conductor type
Solid
Stranded0.5 - 1018-8
Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 140 °F (60 °C).
Temperature rating for outer cable sheath: 167 °F (75 °C).
Conductor
material
Copper
Conductor
material
Copper
[mm
0.5 - 2.528-12
[mm
0.5 - 1018-8
Cross section
2
][AWG]
Cross section
2
][AWG]
7
English (US)
RCD, type B
L1
L2
L3
L2
L1
L3
PE
RCD, type B
4.2.3 Power supply
DANGER
Electric shock
- Death or serious personal injury
- Use the recommended fuse size, see10.3.1 Supply
voltage
Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
If you want to supply the motor through an IT
network, make sure that you have a suitable motor
variant. If you are in doubt, contact Grundfos.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated ground conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see 10.3.1 Supply voltage.
Three-phase supply voltage
• 3 x 440-480 V - 10 %/+ 10 %, 50/60 Hz, PE
• 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated ground conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
In order to avoid loose connections, make sure that you have
pressed home the terminal block for L1, L2 and L3 in its socket
when you connect the supply cable.
For maximum backup fuse, see 10.4.1 Supply voltage.
If you want to supply the motor through an IT
network, make sure that you have a suitable motor
variant. If you are in doubt, contact Grundfos.
Corner grounding is not allowed for supply voltages
above 3 x 480 V, 50/60 Hz.
Fig. 4 Example of a power supply-connected motor with
power supply switch, backup fuse and additional
protection
Fig. 5 Power supply connection, single-phase motors
TM05 4034 1912TM05 3494 1512
TM05 3942 1812TM05 3495 1512
Fig. 6 Example of a power supply-connected motor with
power supply switch, backup fuses and additional
protection
Fig. 7 Power supply connection, three-phase motors
8
4.2.4 Additional protection
DANGER
Electric shock
Death or serious personal injury
- Only use residual-current circuit breakers (ELCB,
GFCI, RCD) of type B.
The residual-current circuit breaker must be marked with the
following symbol:
The total leakage current of all the electrical equipment in the
installation must be taken into account. You find the leakage
current of the motor in sections 10.3.2 Leakage current and
10.4.2 Leakage current (AC).
This product can cause a direct current in the protective ground
conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of unstable
power supply or a faulty installation. The motor is stopped if the
voltage falls outside the permissible voltage range. The motor
restarts automatically when the voltage is again within the
permissible voltage range. Therefore, no additional protection
relay is required.
The motor is protected against transients from the
power supply according to EN 61800-3. In areas with
high lightning intensity, we recommend external
lightning protection.
Overload protection
If the upper load limit is exceeded, the motor automatically
compensates for this by reducing the speed and stops if the
overload condition persists.
The motor remains stopped for a set period. After this period, the
motor automatically attempts to restart. The overload protection
prevents damage to the motor. Consequently, no additional motor
protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor as an
additional protection. When the temperature rises above a certain
level, the motor automatically compensates for this by reducing
the speed and stops if the temperature keeps rising. The motor
remains stopped for a set period. After this period, the motor
automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power supply with a
quality corresponding to IEC 60146-1-1, class C, to ensure
correct motor operation at phase unbalance. This also ensures
long life of the components.
4.2.5 Connection terminals
The descriptions and terminal overviews in this section apply to
both single- and three-phase motors.
For maximum torques, see section, Torques, page 34.
Connection terminals, CREDP pumps
CREDP pumps have a number of inputs and outputs enabling the
pumps to be used in advanced applications where many inputs
and outputs are required.
The pumps have these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop input
where open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV), thus ensuring protection
against electric shock.
• Start-stop: (Digital input 1) = Terminals 2 and 6
• External analog signal input: (Analog input 2) = Terminals 7
and 23
• GENIbus Terminals A, Y and B
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
Power supply (terminals N, PE, L or L1, L2, L3, PE).
Digital input/output,
configurable.
Open collector: Max. 24 V
resistive or inductive.
21LiqTec sensor input 1
20GND
22LiqTec sensor input 2
LiqTec sensor input
(white conductor)
Ground (brown and black
conductors)
LiqTec sensor input
(blue conductor)
Digital input/output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6GNDGround
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
TM05 3509 3512
8+24 VSupply
26+5 V
Supply to potentiometer and
sensor
23GNDGround
25GDS TX
24GDS RX
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
TerminalTypeFunction
NC
C1Common
NO
Normally closed
contact
Normally open
contact
Signal relay 1
(LIVE or PELV)
English (US)
* If you use an external supply source, there must be a
connection to GND.
Fig. 9 Connection terminals, optional for CREDP pumps.
NC
C2Common
NO
Normally closed
contact
Normally open
contact
Signal relay 2
(PELV only)
Digital input/output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6GNDGround
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
TM05 3510 3512
15+24 VSupply
8+24 VSupply
26+5 V
Supply to potentiometer and
sensor
23GNDGround
25GDS TX
24GDS RX
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
11
English (US)
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
4.2.6 Signal cables
• Use screened cables with a cross-sectional area of minimum
28 AWG and maximum 16 AWG for the external on/off switch,
digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to the frame at both ends
with good connection. The screens must be as close as
possible to the terminals. See fig. 10.
Fig. 10 Stripped cable with screen and wire connections
• Always tighten screws for frame connections whether a cable
is fitted or not.
• The wires in the motor terminal box must be as short as
possible.
4.2.7 Bus connection cable
New installations
For the bus connection, use a screened 3-core cable with a
cross-sectional area of minimum 28 AWG and maximum 16 AWG.
If the motor is connected to a unit with a cable clamp which is
identical to the one on the motor, connect the screen to this cable
clamp.
If the unit has no cable clamp leave the screen unconnected at
this end. See fig. 11.
TM02 1325 4402
TM05 3973 1812TM02 8842 0904
Fig. 11 Connection with screened 3-core cable
Replacing a motor
• If a 2-core cable is used in the installation, connect it as shown
in fig. 12.
Fig. 12 Connection with screened 2-core cable
If a screened 3-core cable is used in the installation, follow the
instructions in section, New installations above.
12
4.3 Installing a communication interface module
A
B
B
C
D
A
A
A
B
A
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before
starting any work on the motor. Make sure that the
power supply cannot be accidentally switched on.
3. Remove the securing screw (fig. 16, A).
English (US)
Always use an antistatic service kit when handling
electronic components. This prevents static electricity
from damaging the components.
When unprotected, place the component on the
antistatic cloth.
Fig. 13 Antistatic service kit
1. Loosen the four screws (fig. 14, A) and remove the terminal
box cover (fig. 14, B).
Fig. 16 Removing the securing screw
4. Fit the CIM module by aligning it with the three plastic holders
(fig. 17, A) and the connecting plug (fig. 17, B). Press home
the module using your fingers.
TM06 4462 2315TM06 4081 1515TM06 4084 1515
Fig. 17 Fitting the CIM module
5. Fit and tighten securing screw (fig. 16, A) to 1.3 Nm.
6. Make the electrical connections to the CIM module as
described in the instructions delivered with the module.
7. Connect the cable screens of the bus cables to ground via
one of the ground clamps (fig. 18, A).
TM06 4082 1515TM06 4083 1515TM06 4195 1615
Fig. 14 Removing the terminal box cover
Fig. 18 Connecting the cable screens to ground
2. Remove the CIM cover (fig. 15, A) by pressing the locking tab
(fig. 15, B) and lifting the end of the cover (fig. 15, C). Then lift
the cover off the hooks (fig. 15, D).
Fig. 15 Removing the CIM cover
13
English (US)
FCC
8. Route the wires for the CIM module. See the example in fig.
19.
Fig. 19 Example of wire routing
9. Fit the CIM cover.
10. If the CIM module is supplied with an FCC label, then place
this on the terminal box. See fig. 20.
4.4 Changing the position of the control panel
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before
starting any work on the motor. Make sure that the
power supply cannot be accidentally switched on.
You can turn the control panel 180 °. Follow the instructions
below.
1. Loosen the four screws (TX25) of the terminal box cover.
TM06 4085 1515TM05 7028 0413
TM05 5351 3612TM05 5352 3612TM05 5353 3612
Fig. 21 Loosening the screws
Fig. 20 FCC label
11. Fit the terminal box cover (fig. 14, B) and cross-tighten the
four mounting screws (fig. 14, A) to 6 Nm.
Make sure that the terminal box cover is aligned with
the control panel. See section 4.4 Changing the position of the control panel.
2. Remove the terminal box cover.
Fig. 22 Removing the terminal box cover
3. Press and hold in the two locking tabs (A) while gently lifting
the plastic cover (B).
Fig. 23 Lifting the plastic cover
14
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
Fig. 24 Turning the plastic cover
5. Position the plastic cover correctly on the four rubber pins (C).
Make sure that the locking tabs (A) are placed correctly.
Fig. 25 Positioning the plastic cover
6. Fit the terminal box cover, and make sure that it is also turned
180 ° so that the buttons on the control panel are aligned with
the buttons on the plastic cover.
7. Tighten the four screws (TX25) with 5 Nm.
Fig. 26 Fitting the terminal box cover
5. Product introduction
5.1 Product description
Grundfos E-pumps are fitted with frequency-controlled
permanent-magnet motors for single-phase or three-phase power
supply connection.
5.1.1 Pumps without factory-fitted sensor
The pumps have a built-in PI controller and can be set for an
external sensor enabling the control of the following parameters:
• constant pressure
TM05 5354 3612TM05 5355 3612TM05 5356 3612
• constant differential pressure
• constant temperature
• constant differential temperature
• constant flow rate
• constant level
• constant curve
• constant other value.
The pumps have been factory-set to constant-curve control
mode. You can change the control mode with R100 or Grundfos
GO.
5.1.2 Pumps with factory-fitted pressure sensor
The pumps have a built-in PI controller and are set for a pressure
sensor enabling the control of the outlet pressure.
The pumps have been factory-set to constant-pressure control
mode. The pumps are typically used to keep a constant pressure
in variable-demand systems.
5.1.3 Settings
The description of settings applies both to pumps without
factory-fitted sensor and to pumps with a factory-fitted pressure
sensor.
Setpoint
You can set the desired setpoint in three ways:
• on the pump control panel
• via an input for external setpoint signal
• with the Grundfos wireless R100 remote control or Grundfos
GO.
Other settings
Make all other settings with R100 or Grundfos GO.
You can read important parameters, such as the actual value of
the control parameter and power consumption, via R100 or
Grundfos GO.
If special or customized settings are required, use Grundfos PC
Tool. Contact your local Grundfos company for more information.
English (US)
15
English (US)
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
.
yyp
p
:
S
l
n
o
:
SF
C
:
P
:
Effn W
g
g
t
:DE:
k
g
g
NDE
:
a
b
:
:
.C.
:
PU
T
E
C
yp
yp
e
:
P
:
Uin:
I
:
f
H
z
P
S
p
p
:
:
PB
FM
HMICIM
VARIANT
Hp
rpm
::
:
:
PB
:
HMI
:
C
:
p
pm
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
o
:
F
C
:
:
Eff
n
g
g
t
:
DE
:
g
g
NDE
:
T
amb
:
:
V
.C.
:
PU
T
E
C
yp
yp
e
:
P
:
U
n
:
I
1/1
:
f
H
z
I
S
p
p
:
:
PBFM
HMI
CIM
VARIANT
Hp
rpm
:
:
::
PB
:
CIM
:
H
p
m
:
5.1.4 Radio communication
This product incorporates a radio module for remote control
which is a class 1 device and which you can use anywhere in the
EU without restrictions.
For use in USA and Canada, see page 36.
Some variants of the product and products sold in China and
Korea have no radio module.
This product can communicate with Grundfos GO and other
products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only
Grundfos-approved external antennas may be connected to this
product, and only by a Grundfos-approved installer.
5.1.5 Battery
A Li-ion battery is fitted in CRE, CRIE, CRNE, CRKE, SPKE,
MTRE and CME pumps. The Li-ion battery complies with the
Battery Directive (2006/66/EC). The battery does not contain
mercury, lead and cadmium.
5.2 Identification
5.2.1 Identification of functional module
You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the functional module in the "Fitted modules"
menu under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify
the functional module in the Fitted modules menu under Status.
Motor nameplate
You can identify the fitted module on the motor nameplate. See
fig. 27.
5.2.2 Identification of control panel
You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the control panel in the "Fitted modules" menu
under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify
the control panel in the "Module type" menu under "Status".
Motor nameplate
You can identify the fitted control panel on the motor nameplate.
See fig. 28.
IN
.N.
S
i
eria
e
F
i
L
F Am
F
rp
Fig. 28 Identification of control panel
VariantDescription
HMI 300Advanced control panel
TM06 4013 1415
5.3 Bus signal
.N.
eria
e
IN
F
L
F Am
F
r
/
IM
Fig. 27 Identification of functional module
VariantDescription
FM 300Advanced functional module
The pump supports serial communication via an RS-485 input.
The communication is carried out according to the Grundfos
GENIbus protocol and enables connection to other pumps as well
as a building management system or another external control
system.
Via a bus signal, you can remote-set pump operating parameters,
such as setpoint and operating mode. At the same time, the pump
can, via the bus, provide status information about important
parameters, such as actual value of control parameter, input
power and fault indications.
Contact Grundfos for further information.
TM06 1889 3314
If you use a bus signal, the number of settings
available via R100 or Grundfos GO are reduced.
16
5.4 Grundfos Eye
A
The operating condition of the pump is indicated by the Grundfos
Eye on the control panel. See fig. 29, pos. A.
Fig. 29 Grundfos Eye
Grundfos EyeIndicationDescription
English (US)
TM05 5993 4312
No lights are on.
The two opposite green indicator lights are
rotating in the direction of rotation of the
pump when seen from the non-drive end.
The two opposite green indicator lights are
permanently on.
One yellow indicator light is rotating in the
direction of rotation of the pump when seen
from the non-drive end.
One yellow indicator light is permanently on.
The two opposite red indicator lights flash
simultaneously.
The green indicator light in the middle
flashes quickly four times.
The green indicator light in the middle
flashes continuously.
The power is off.
The pump is not running.
The power is on.
The pump is running.
The power is on.
The pump is running.
Warning.
The pump is running.
Warning.
The pump is stopped.
Alarm.
The pump is stopped.
This is a feedback signal which the pump gives in
order to ensure identification of itself.
Grundfos GO or another pump is trying to
communicate with the pump. Press on the
pump control panel to allow communication.
The green indicator light in the middle is
permanently on.
Remote control with Grundfos GO via radio.
The pump is communicating with Grundfos GO
via radio connection.
The green indicator light in the middle
flashes quickly while Grundfos Go is
exchanging data with the pump. It takes a
few seconds.
Remote control with Grundfos GO via infrared
light.
The pump is receiving data from Grundfos GO via
infrared communication.
17
English (US)
NCNOCNCNOCNCNOCNCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNOCNCNO
C
C
NO NC
C
NO NC
NCNOCNCNOCNCNO
C
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
C
NO NCCNO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NC
NCNO
C
C
NO NC
NCNO
C
NCNOCNCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
NCNOCNCNO
C
5.5 Signal relays
The motor has two outputs for potential-free signals via two
internal relays.
The signal outputs can be set to "Operation", "Pump running",
"Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table
below:
DescriptionGrundfos Eye
Operation
Contact position for signal relays when activated
Pump
running
ReadyAlarmWarning
Operating mode
The power is off.
The pump runs in
"Normal" mode.
The pump runs in
"Manual" mode.
The pump is in
operating mode
"Stop".
Warning, but the
pump is running.
Warning, but the
pump runs in "Manual"
mode.
Off
Green, rotating
Green, rotating
Green, steady
Yellow, rotating
Yellow, rotating
-
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
"Normal",
"Min." or
"Max."
"Manual"
Warning, but the
pump was stopped via
a "Stop" command.
Alarm, but the pump is
running.
Alarm, but the pump
runs in "Manual" mode.
The pump is stopped
due to an alarm.
The pump is stopped
due to "Low-flow stop
function".
18
"Stop"
Yellow, steady
"Normal",
"Min." or
"Max."
Red, rotating
"Manual"
Red, rotating
"Stop"
Red, flashing
"Normal"
Green, steady
6. User interfaces
1
2
3
4
5
6
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as the
product may be very hot.
You can make the pump settings by means of the following user
interfaces:
Control panels
• Advanced control panel.
See section 6.1 Advanced control panel.
Remote controls
• Grundfos GO.
See section 7.1 Grundfos GO Remote.
• Grundfos R100 remote control.
If the power supply to the pump is switched off, the settings are
stored.
6.1 Advanced control panel
The pumps are fitted with the advanced control panel as
standard.
Fig. 30 Advanced control panel
Pos. Symbol Description
1
2
3It goes one step back.
4
TM05 4849 1013
5
-
Grundfos Eye
This shows the operating status of the pump.
For further information, see section
4.4 Changing the position of the control panel.
Graphical color display.
With these buttons you can navigate between
main menus, displays and digits.
When you change the menu, the display
always shows the top display of the new menu.
With these buttons you can navigate between
submenus.
They change value settings.
Note: If you have disabled the possibility to
make settings with the "Enable/disable
settings" function, then you can enable it again
temporarily by pressing these buttons
simultaneously for at least 5 seconds. See
section 7.29 "Buttons on product"
("Enable/disable settings").
It saves changed values, resets alarms and
expands the value field.
It enables radio communication with Grundfos
GO and other products of the same type.
When you try to establish radio communication
between the pump and Grundfos GO or
another pump, the green indicator light in
Grundfos Eye flashes. A note also appears in
the pump display stating that a wireless device
wants to connect to the pump. Press on
the pump control panel to allow radio
communication with Grundfos GO and other
products of the same type.
This makes the pump ready for operation/starts
and stops the pump.
Start:
If you press the button when the pump is
stopped, the pump only starts if no other
functions with higher priority have been
enabled. See section 8. Description of settings.
Stop:
If you press the button when the pump is
running, the pump is always stopped. When
you stop the pump via this button, the
appears in the bottom of the display.
icon
English (US)
6
This button goes to the "Home" menu.
19
English (US)
+
1
2
3
+
+
6.1.1 Home display
Fig. 31 Example of "Home" display
Pos.SymbolDescription
"Home"
This menu shows up to four user-defined
1
2-
3-
4-
5
6
7
8
9
6.1.2 Startup guide
The pump incorporates a startup guide which is started at the first
startup. After the startup guide, the main menus appear in the
display.
parameters. You can select parameters
shown as shortcut icon, and when
pressing you go directly to the"Settings"
display for the selected parameter.
"Status"
This menu shows the status of the pump
and system as well as warnings and
alarms.
"Settings"
This menu gives access to all setting
parameters. You can make detailed
settings of the pump in this menu.
See section 7, Description of functions.
"Assist"
This menu enables assisted pump setup,
provides a short description of the control
modes and offers fault advice.
See section 8.2
This symbol indicates that the pump has
been stopped via the
This symbol indicates that the pump is
functioning as master pump in a multipump
system.
This symbol indicates that the pump is
functioning as a slave pump in a multipump
system.
This symbol indicates that the pump is
operating in a multipump system. See
section 7.44 "Multi-pump setup" ("Setup of
multi-pump system").
This symbol indicates that the possibility to
make settings has been disabled for
protective reasons.
Assist
.
button.
7. Setting the product
7.1 Grundfos GO Remote
The pump is designed for wireless radio or infrared
communication with the Grundfos GO Remote.
The Grundfos GO Remote enables setting of functions and gives
access to status overviews, technical product information and
actual operating parameters.
The Grundfos GO Remote offers three different mobile interfaces
(MI). See fig. 32.
TM06 8915 0417
Fig. 32 Grundfos GO Remote communicating with the pump
via radio or infrared light
Pos.Description
Grundfos MI 201:
1
Consists of an Apple iPod touch 4G and a Grundfos
cover.
Grundfos MI 202:
Add-on module which can be used in conjunction with
Apple iPod touch 4G, iPhone 4G or 4GS.
2
Grundfos MI 204:
Add-on module which can be used in conjunction with
Apple iPod touch 5G or iPhone 5.
Grundfos MI 301:
Separate module enabling radio or infrared
communication. The module can be used in
3
conjunction with an Android or iOS-based Smartphone
with Bluetooth connection.
7.1.1 Communication
When the Grundfos GO Remote communicates with the pump,
the indicator light in the middle of the Grundfos Eye will flash
green. See section .
Communication must be established using one of these
communication types:
• radio communication
• infrared communication.
7.1.2 Radio communication
Radio communication can take place at distances up to 30
meters. It is necessary to enable communication by pressing
or on the pump control panel.
7.1.3 Infrared communication
When communicating via infrared light, the Grundfos GO Remote
must be pointed at the pump control panel.
TM05 5383 4312
20
7.2 Menu overview for Grundfos GO Remote
7.2.1 Main menus
Dashboard
Status
Resulting setpoint
Actual controlled value
Motor speed (rpm, %)
Power consumption
Energy consumption
Operating hours
Pt100/1000 input 1
Pt100/1000 input 2
Analog output
Analog input 1
Analog input 2
Analog input 3
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Fitted modules
SettingsSectionPage
Setpoint8.1.1
Operating mode8.1.2
Control mode8.1.4 Control mode23
Operating range8.1.12
Pump number8.1.14
Radio communication
Analog input 1
Analog input 3
Pt100/1000 input 1
Pt100/1000 input 2
Digital input 1
Digital input 2
Digital in/output 3
Digital in/output 4
Analog output8.1 .11
External setpoint funct.External setpoint influence26
Signal relay 1
Signal relay 2
Standstill heating
Motor bearing monitoring
Service
Reset to factory settings
Store settings
Recall settings
Undo
Pump name
Unit configuration
The setpoint for all control modes can be set in this submenu
when the desired control mode has been selected. See section
8.1.4 Control mode.
8.1.2 Operating mode
Possible operating modes:
• Normal
The pump runs according to the selected control mode.
• Stop
The pump stops.
• Min.
The min. curve mode can be used in periods in which a
minimum flow is required.
• Max.
The max. curve mode can be used in periods in which a
maximum flow is required.
This operating mode is for instance suitable for systems with
hot-water priority.
• Manual
The pump is operating at a manually set speed.
See section 8.1.3
The pump can be set to operate according to the max. or min.
curve, like an uncontrolled pump. See fig. 33.
Set manual speed
.
Proportional pressure
The pump head is reduced at decreasing water demand and
increased at rising water demand. See fig. 34.
This control mode is especially suitable in systems with relatively
large pressure losses in the distribution pipes. The head of the
pump will increase proportionally to the flow in the system to
compensate for the large pressure losses in the distribution
pipes.
The setpoint can be set with an accuracy of 0.14 psi. The head
against a closed valve is half the setpoint, H
set
.
Fig. 34 Proportional pressure
This control mode requires a factory-fitted differential-pressure
sensor as shown in the example below:
Example
• Factory-fitted differential-pressure sensor.
English (US)
TM05 7909 1613
Fig. 35 Proportional pressure
Constant differential pressure
The pump maintains a constant differential pressure,
independently of the flow in the system. See fig. 36. This control
mode is primarily suitable for systems with relatively small
TM00 5547 0995
Fig. 33 Max. and min. curves
pressure losses.
8.1.3 Set manual speed
The pump speed can be set in %. When the operating mode has
been set to "Manual", the pump will run at the set speed.
The operating mode must be set to "Normal" before a
control mode can be enabled.
The setpoint for all control modes
Fig. 36 Constant differential pressure
can be changed in the
TM05 7901 1613
"Setpoint" submenu under "Settings" when the desired control
mode has been selected.
23
English (US)
p
p
p
p
p
H
Q
This control mode requires either a factory-fitted or external
differential-pressure sensor or two external pressure sensors as
shown in the examples below:
Examples
• Factory-fitted differential-pressure sensor.
• One external differential-pressure sensor.
• Two external pressure sensors.
8.1.6 Analog inputs
Available inputs depending on the functional module fitted in the
pump:
Function (terminal)
FM 300
(advanced)
Analog input 1, setup (4)●
Analog input 2, setup (7)●
Analog input 3, setup (14)●
To set up an analog input, make the settings below.
Function
The analog inputs can be set to these functions:
• Not active
• Feedback sensor
• Ext. setpoint infl.
See section 8.1.13
Setpoint influence
.
• Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system by the sensor connected to the actual analog input.
Unit
Available measuring units:
Fig. 37 Constant differential pressure
8.1.5 Constant curve
The pump can be set to operate according to a constant curve,
like an uncontrolled pump. See fig. 38.
The desired speed can be set in % of maximum speed in the
range from 25 to 100 % (110 %).
ParameterPossible units
Pressurebar, m, kPa, psi, ft
Pump flowm
3
/h, l/s, yd3/h, gpm
Liquid temp.°C, °F
Other parameter%
Electrical signal
Select signal type (0.5 - 3.5 V, 0-5 V, 0-10 V, 0-20 mA or 4-20
mA).
Sensor range, min. value
Set the min. value of the connected sensor.
Sensor range, max. value
Set the max. value of the connected sensor.
8.1.7 Pt100/1000 inputs
Available inputs depending on the functional module fitted in the
pump:
FM 300
(advanced)
Fig. 38 Constant curve
Function (terminal)
TM05 7957 1713
Pt100/1000 input 1, setup (17 and 18)●
Pt100/1000 input 2, setup (18 and 19)●
Function
The Pt100/1000 inputs can be set to these functions:
• Not active
• Feedback sensor
• Ext. setpoint infl.
See section 8.1.13
Setpoint influence
.
• Other function.
Measured parameter
Select one of the parameters, i.e. the parameter to be measured
in the system.
24
8.1.8 Digital inputs
Available inputs depending on the functional module fitted in the
pump:
8.1.9 Digital inputs/outputs
Available inputs/outputs depending on the functional module
fitted in the pump:
Function (terminal)
Digital input 1, setup (2 and 6)●
Digital input 2, setup (1 and 9)●
To set up a digital input, make the settings below.
Function
Select one of these functions:
• Not active
When set to "Not active", the input has no function.
• External stop
When the input is deactivated (open circuit), the pump will
stop.
• Min. (min. speed)
When the input is activated, the pump will run at the set min.
speed.
• Max. (max. speed)
When the input is activated, the pump will run at the set max.
speed.
• External fault
When the input is activated, a timer will be started. If the input
is activated for more than 5 seconds, the pump will be stopped
and a fault will be indicated.
• Alarm resetting
When the input is activated, a possible fault indication will be
reset.
The priority of the selected functions in relation to each other
appears from section .
A stop command will always have the highest priority.
FM 300
(advanced)
Function (terminal)
Digital input/output 3, setup (10 and 16)●
Digital input/output 4, setup (11 and 18)●
To set up a digital input/output, make the settings below.
Mode
The digital input/output 3 and 4 can be set to act as digital input
or digital output:
• Digital input
• Digital output.
Function
The digital input/output 3 and 4 can be set to these functions:
It is possible to influence the setpoint by an external signal, either
via one of the analog inputs or, if an advanced functional module
is fitted, via one of the Pt100/1000 inputs.
Before the "Digital inputs" can be enabled, one of the
analog inputs or Pt100/1000 inputs must be set to
"External setpoint function".
See sections 8.1.6
8.1.7
Pt100/1000 inputs
Analog inputs
.
and
If more than one input has been set up for setpoint influence, the
function will select the analog input with the lowest number, for
example "Analog input 2", and ignore the other inputs, for
example "Analog input 3" or "Pt100/1000 input 1".
Example
See fig. 40.
At a lower sensor value of 0 bar, a set setpoint of 30 psi and an
external setpoint of 60 %, the actual setpoint is 0.60 x (30 - 0) + 0
= 18 psi.
Actual setpoint = actual input signal x (setpoint - lower value) +
lower value.
TM00 6785 5095
26
Speeds below 25 % may result in noise from the
shaft seal.
TM06 3636 0215
Fig. 40 Example of setpoint influence
Types of setpoint influence
100
0
100
20406080
Setpoint influence [%]
External input
[%]
100
0
100
20406080
Setpoint influence [%]
External
input [%]
Normal
Min.
• Not active
• Linear function
• Linear with Min.
These functions can be selected:
• Not active
When set to "Not active", the setpoint will not be influenced
from any external function.
• Linear function
The setpoint is influenced linearly from 0 to 100 %. See fig. 41.
Fig. 41 Linear function
– Linear with Min.
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Min.".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 42.
A unique number can be allocated to the pump. This makes it
possible to distinguish between pumps in connection with bus
communication.
8.1.15 General settings
Language
A number of languages is available.
Measuring units are automatically changed according to selected
language.
TM05 6280 4612TM05 6281 4612
8.2 Assist
8.2.1 Alternating operation
Only one pump is operating at a time. The change from one pump
to the other depends on time or energy. If a pump fails, the other
pump will take over automatically.
Pump system:
• Two pumps connected in parallel.
The pumps must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
8.2.2 Back-up operation
One pump is operating continuously. The back-up pump is
operated at intervals to prevent seizing up. If the duty pump stops
due to a fault, the back-up pump will start automatically.
Pump system:
• Twin-head pump.
• Two single-head pumps connected in parallel.
The pumps must be of the same type and size. Each pump
requires a non-return valve in series with the pump.
English (US)
Fig. 42 Linear with Min.
27
English (US)
H
Q
Hset
Hset
2
H
Q
H
Q
H
Q
8.3 Selection of control mode
System applicationSelect this control mode
In systems with relatively large pressure losses in the distribution pipes and in air-conditioning
and cooling systems.
• Two-pipe heating systems with thermostatic valves and
– very long distribution pipes
– strongly throttled pipe balancing valves
– differential-pressure regulators
– large pressure losses in those parts of the system through which the total quantity of
water flows (for example boiler, heat exchanger and distribution pipe up to the first
branching).
• Primary circuit pumps in systems with large pressure losses in the primary circuit.
• Air-conditioning systems with
– heat exchangers (fan coils)
– cooling ceilings
– cooling surfaces.
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and
– dimensioned for natural circulation
– small pressure losses in those parts of the system through which the total quantity of
water flows (for example boiler, heat exchanger and distribution pipe up to the first
branching) or
– modified to a high differential temperature between flow pipe and return pipe (for example
district heating).
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing valves.
• Primary circuit pumps in systems with small pressure losses in the primary circuit.
In systems with a fixed system characteristic.
Examples:
• one-pipe heating systems
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
Proportional pressure
Constant differential pressure
Constant temperature and constant
differential temperature
If an external controller is installed, the pump is able to change from one constant curve to
another, depending on the value of the external signal.
The pump can also be set to operate according to the max. or min. curve, like an uncontrolled
pump:
• The max. curve mode can be used in periods in which a maximum flow is required.
This operating mode is for instance suitable for systems with hot-water priority.
• The min. curve mode can be used in periods in which a minimum flow is required.
Constant curve
28
8.4 Changing the position of the control panel
Note
Note
It is possible to turn the control panel 180 °. Follow the
instructions below.
1. Loosen the four screws (TX25) holding the terminal box cover.
Fig. 43 Loosening the screws
2. Remove the terminal box cover.
English (US)
TM05 5354 3612TM05 5355 3612TM05 5356 3612
Fig. 46 Turning the plastic cover
5. Re-position the plastic cover correctly on the four rubber pins
(pos. C). Make sure that the locking tabs (pos. A) are placed
correctly.
TM05 5351 3612TM05 5352 3612TM05 5353 3612
Fig. 44 Removing the terminal box cover
3. Press and hold in the two locking tabs (pos. A) while gently
lifting the plastic cover (pos. B).
Fig. 45 Lifting the plastic cover
4. Turn the plastic cover 180 °.
Fig. 47 Re-positioning the plastic cover
6. Fit the terminal box cover, and make sure that it is also turned
180 ° so that the buttons on the control panel are aligned with
the buttons on the plastic cover.
Tighten the four screws (TX25) with 3.68 ft.-lbs. (5 Nm).
Fig. 48 Fitting the terminal box cover
Do not twist the cable more than 90 °.
29
English (US)
8.5 Bus signal
The motor enables serial communication via an RS-485 input.
The communication is carried out according to the Grundfos
GENIbus protocol and enables connection to a building
management system or another external control system.
Via a bus signal, it is possible to remote-set motor operating
parameters, such as setpoint and operating mode. At the same
time, the motor can, via the bus, provide status information about
important parameters, such as actual value of control parameter,
input power and fault indications.
Contact Grundfos for further information.
If a bus signal is used, the number of settings
available via the Grundfos GO Remote will be
reduced.
8.6 Priority of settings
The motor can always be set to operation at max. speed or to
stop with the Grundfos GO Remote.
If two or more functions are enabled at the same time, the motor
will operate according to the function with the highest priority.
Example: If, via the digital input, the motor has been set to max.
speed, the motor control panel or the Grundfos GO Remote can
only set the motor to "Manual" or "Stop".
The priority of the settings appears from the table below:
* If the bus communication is interrupted, the motor will resume
its previous operating mode, for example "Stop", selected on
the motor control panel or with the Grundfos GO Remote.
Control panel on motor or
Grundfos GO Remote
Digital inputBus communication
30
9. Servicing the product
1
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0.91
0.90
0.89
0.88
0
0
3281 3937 4593 5249 5906 6562 7218
[ft]
P2
[%]
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before
starting any work on the motor. Make sure that the
power supply cannot be accidentally switched on.
DANGER
Magnetic field
Death or serious personal injury
- Do not handle the motor or rotor if you have a
pacemaker.
9.1 Motor
For servicing the product, download the service instructions for
the motor by using the following link or QR code.
http://net.grundfos.com/qr/i/98413121
9.2 Pump
Service documentation is available in Grundfos Product Center
(http://product-selection.grundfos.com/).
If you have any questions, please contact the nearest Grundfos
company or service workshop.
10.1.2 Ambient temperature
Ambient temperature during storage and transportation
Minimum: -22 °F (-30 °C)
Maximum: 140 °F (60 °C).
Ambient temperature during operation
1 x 200 - 240 and 3 x 440 - 480
Minimum: -4 °F (-20 °C)
Maximum: 122 °F (50 °C).
3 x 200 - 240
Minimum: -4 °F (-20 °C)
Maximum: 104 °F (40 °C).
The motor can operate with the rated power output (P2) at 122 °F
(50 °C), but continuous operation at higher temperatures reduces
the expected product life. If the motor is to operate at ambient
temperatures between 122 °F (50 °C) and 140 °F (60 °C), select
an oversized motor. Contact Grundfos for further information.
10.1.3 Installation altitude
If the motor is installed above 6560 ft (2000 m), it
does not comply with SELV/PELV classification.
Installation altitude is the height above sea level of the installation
site.
QR98413121
Motors installed up to 3280 ft (1000 m) above sea level can be
loaded 100 %.
• Motors installed more than 3280 ft (1000 m) above sea level
must not be fully loaded due to the low density and
consequent low cooling effect of the air. See fig. 49.
English (US)
9.3 Cleaning the product
WARNING
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Check that the terminal box cover is
intact before spraying water on the product.
In order to avoid condensation in the motor, let the motor cool
down before spraying it with cold water.
10. Technical data
10.1 Operating conditions
10.1.1 Maximum number of starts and stops
The number of starts and stops via the power supply must not
exceed four times per hour.
Fig. 49 Derating of motor output power (P2) in relation to
altitude above sea level
When switched on via the power supply, the pump starts after
approximately 5 seconds.
If a higher number of starts and stops is desired, use the input for
external start-stop when starting and stopping the pump.
When started via an external on/off switch, the pump starts
immediately.
TM06 9374 2117
31
English (US)
10.1.4 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %, open the drain
holes in the drive-end flange. See Fig. 2 Examples of covers (not
supplied by Grundfos).
10.1.5 Motor cooling
To ensure cooling of motor and electronics, observe the following:
• Position the motor in such a way that adequate cooling is
ensured. See section 4.1.5 Ensuring motor cooling.
• The temperature of the cooling air must not exceed 122 °F (50
°C).
Keep cooling fins and fan blades clean.
10.2 Megging
Do not meg an installation incorporating MLE motors, as the
built-in electronics may be damaged.
10.3 Technical data, sing le-phase motors
10.3.1 Supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
All voltages refer to ground. All currents return to ground.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in severely
reduced operating reliability and motor life:
Relay 1:
Maximum contact load: 250 VAC, 2 A or 30 VDC, 2 A.
Relay 2:
Maximum contact load: 30 VDC, 2 A.
GENI terminals: -5.5 to 9.0 VDC or less than 25 mADC.
Other input/output terminals: -0.5 to 26 VDC or less than 15
mADC.
Digital inputs, DI
Internal pull-up current greater than 10 mA at V
Internal pull-up to 5 VDC (currentless for V
Certain low logic level: V
Certain high logic level: V
less than 1.5 VDC.
i
greater than 3.0 VDC.
i
Hysteresis: No.
2
Screened cable: 0.5 - 1.5 mm
, 28-16 AWG.
Maximum cable length: 1640 ft (500 m).
Open-collector digital outputs, OC
Current sinking capability: 75 mADC, no current sourcing.
Load types: Resistive or/and inductive.
Low-state output voltage at 75 mADC: Maximum 1.2 VDC.
Low-state output voltage at 10 mADC: Maximum 0.6 VDC.
Overcurrent protection: Yes.
2
Screened cable: 0.5 - 1.5 mm
, 28-16 AWG.
Maximum cable length: 1640 ft (500 m).
Analog inputs, AI
Voltage signal ranges:
• 0.5 - 3.5 VDC, AL AU.
• 0-5 VDC, AU.
•0-10 VDC, AU.
Voltage signal: R
greater than 100 kΩ at 25 °C.
i
Leak currents may occur at high operating temperatures. Keep
the source impedance low.
Current signal ranges:
• 0-20 mADC, AU.
• 4-20 mADC, AL AU.
Current signal: R
is equal 292 Ω.
i
Current overload protection: Yes. Change to voltage signal.
Measurement tolerance: - 0/+ 3 % of full scale (maximum-point
coverage).
2
Screened cable: 0.5 - 1.5 mm
, 28-16 AWG.
Maximum cable length: 500 m excluding potentiometer.
Potentiometer connected to +5 V, GND, any AI:
Use maximum 10 kΩ.
Maximum cable length: 100 m.
equal 0 VDC.
i
greater than 5 VDC).
i
Analog output, AO
Current sourcing capability only.
Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes.
Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (maximum-point coverage).
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
Dispose of the waste battery through the national collective
schemes. If in doubt, contact your local Grundfos company.
English (US)
35
Appendix
Identification numbers
Identification numbers
Appendix
1. Installation in the USA and Canada
In order to maintain the cURus approval, follow these
additional installation instructions. The UL approval
is according to UL 1004-1.
For Canada
This product complies with the Canadian ICES-003 Class B
specifications. This Class B device meets all the requirements of
the Canadian interference-causing equipment regulations.
Cet appareil numérique de la Classe B est conforme à la norme
NMB-003 du Canada. Cet appareil numérique de la Classe B
respecte toutes les exigences du Réglement sur le matériel
brouilleur du Canada.
1.1 Electrical codes
For USA
This product complies with the Canadian Electrical Code and the
US National Electrical Code.
This product has been tested according to the national standards
for Electronically Protected Motors:
CSA 22.2 100-14:2014 (applies to Canada only).
UL 1004-1:2015 (applies to USA only).
Pour le Canada
Codes de l'électricité
Ce produit est conforme au Code canadien de l'électricité et au
Code national de l'électricité américain.
Ce produit a été testé selon les normes nationales s'appliquant
aux moteurs protégés électroniquement:
CSA 22.2 100.04: 2009 (s'applique au Canada uniquement).
UL 1004-1: Juin 2011 (s'applique aux États-Unis uniquement).
This device complies with part 15 of the FCC rules and RSS210
of IC rules.
Operation is subject to the following two conditions:
• This device may not cause interference.
• This device must accept any interference, including
interference that may cause undesired operation of the device.
Users are cautioned that changes or modifications not expressly
approved by Grundfos could void the user's authority to operate
the equipment.
Pour le Canada
Communication radio
Ce dispositif est conforme à la partie 15 des règles de la FCC et
aux normes RSS210 de l'IC.
Son fonctionnement est soumis aux deux conditions suivantes:
• Ce dispositif ne doit pas provoquer de brouillage préjudiciable.
• Il doit accepter tout brouillage reçu, y compris le brouillage
pouvant entraîner un mauvais fonctionnement.
Fig. 2 Identification numbers
36
1.4 Electrical connection
1.4.1 Conductors
See section 7.2 Cable requirements, page 11.
1.4.2 Torques
Maximum tightening torques for the terminals can be found in
section Torques, page 65.
1.4.3 Line reactors
The maximum line reactor sizes are listed below.
Appendix
Motor
[Hp]
.501.5
.751.5
11.5
1.51.5
21.5
32
50.7
7.50.3
100.6
150.3
Short circuit current
If a short circuit occurs, the pump can be used on a mains supply
delivering not more than 5000 RMS symmetrical amperes, 600 V
maximum.
Fuses
Fuses used for motor protection must be rated for minimum
500 V.
Motors up to and including 10 Hp require class K5 UL-listed
fuses.
Any UL-listed fuse can be used for motors of 15 Hp.
Branch circuit protection
When the pump is protected by a circuit breaker, this must be
rated for a maximum voltage of 480 V. The circuit breaker must
be of the "inverse time" type.
Overload protection
Degree of overload protection provided internally by the drive, in
percent of full-load current: 102 %.
Maximum line reactor size
[mH]
1.5 Outdoor installation
According to UL 778/C22.2 No 108-14 pumps that are intended
for outdoor use shall be marked enclosure type 3 and the product
shall be tested with rated surface temperature down to -31 °F
(-35 °C). The MLE enclosure is approved for type 3 or 4 and rated
surface temperature down to 32 °F (0 °C), thus only for indoor
use in UL 778/C22.2 No 108-14 pump applications. For ambient
temperature during operation, see section 10.1.2 Ambient
temperature.