Grundfos Conex DIS-C Installation And Operating Instructions Manual

Page 1
Conex® DIS-C
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Page 2
English (GB)
English (GB) Installation and operating instructions
Original installation and operating instructions
CONTENTS
Page
1. Symbols used in this document
2. General information
These installation and operating instructions contain all information important for users of the Conex
®
DIS-C:
technical data
instructions on commissioning, use and maintenance
safety information.
Should you require further information or should you encounter problems that are not handled in sufficient depth in this manual, please contact Grundfos. We shall be pleased to support you with our comprehensive know-how in the fields of measuring and control technology as well as water treatment.
We always welcome suggestions on how to optimise our installation and operating instructions to satisfy our customers.
1. Symbols used in this document
2. General information
3. Description of the device
3.1 Assembly
3.2 Principles of conductivity measurement
4. Applications
4.1 Field of application for measurements
5. Safety
5.1 Obligations of the owner/operations manager
5.2 Avoidance of danger
6. Identification
6.1 Nameplate
6.2 Type key
7. Technical data
7.1 Versions
7.2 General data
7.3 Measuring ranges
7.4 Dimensional sketches / drilling diagram
8. Installation
8.1 Transport and storage
8.2 Unpacking
8.3 Installation requirements
8.4 Assembling the Conex® DIS-C housing for wall mounting
8.5 Assembling the Conex® DIS-C-P, CI housing for installation in control panel
9. Commissioning / electrical connections
9.1 Conex® DIS-C conductive, housing for wall mounting
10
9.2 Conex® DIS-C inductive, housing for wall mounting
11
9.3 Conex® DIS-C conductive, housing for installation in control panel
12
9.4 Important instructions for connecting the device
13
10. Principles of regulatory function
14
10.1 Regulatory behaviour
14
10.2 Limit values
14
10.3 On-off controller with P behaviour
15
10.4 Parameter settings
16
11. Initial operation and settings
17
11.1 Initial steps for operation
17
12. Operation
17
12.1 Device layout for Conex® DIS-C
17
12.2 Menu control
18
12.3 Navigation in the menus
18
12.4 Setup
19
12.5 Relay menu (S1 S2)
23
12.6 Temperature compensation
23
12.7 Displaying / changing code
24
12.8 Controller settings
24
12.9 Alarm value setting A1/A2
25
12.10 Service
26
13. Disposal
26
Warning Prior to installation, read these installation
and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
Warning If these safety instructions are not
observed, it may result in personal injury.
Caution
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Note
Notes or instructions that make the job easier and ensure safe operation.
Page 3
English (GB)
3. Description of the device
Fig. 1 Conex® DIS-C for wall mounting
Fig. 2 Conex
®
DIS-C for installation in control
panel
3.1 Assembly
The complete measuring system comprises:
the measuring amplifier Conex
®
DIS-C
the conductivity measuring cell with temperature sensor.
3.2 Principles of conductivity measurement
In metallic conductors, electricity is transported by freely moving electrons, whereas in electrolytes, the electrical current is carried by ions. All water-dissolved components that are in ionogenic form contribute towards conductivity. The conductivity is a sum parameter.
Different types of ions vary in their electrical charge and migration rate. The migration rate is highly dependent on temperature, which means the influence of temperature must always be taken into account when measuring conductivity.
Specific electrolytic conductivity is measured in Siemens per cm (S/cm). Siemens per cm is the reciprocal value of electrical resistance. This measurement is based on a theoretical liquid cube with sides of a length of 1 cm. In practice, cells rarely have such an even geometric shape. The cell constant C is used to specify the correlation between the actual measured conductivity and the displayed specific conductivity.
The measuring cell is inserted in a flow armature, and the water to be measured flows around it. The Conex
®
DIS-C measuring and regulation device amplifies the signal from the measuring cell and calculates the signal (e.g. against cable and temperature compensation parameters). The result is displayed digitally and can also be registered using the analog output. The result is shown as an actual value.
TM03 6980 3914TM03 6981 4506
Page 4
English (GB)
4. Applications
The Conex® DIS-C is a measuring amplifier for measuring conductivity using a conductive or inductive measuring cell and for regulation of disturbance variables using a connected control element. Two controllers can be set separately as limit values, intermittent pulse controllers or pulse frequency controllers.
The Conex
®
DIS-C is available for installation in a wall-mounted enclosure or for installation in a control panel (only conductive measuring cell for conductivity measurement).
4.1 Field of application for measurements
Principal uses:
waste water treatment
water purification
recycling
in metal processing industries
in the chemical industry
in the foodstuff industry.
5. Safety
The owner/operations manager of the system is responsible for the following:
compliance with country-specific safety
regulations
training of operating personnel.
5.1 Obligations of the owner/operations
manager
The owner/operations manager must ensure that persons working with the device described fulfil these requirements:
They are acquainted with the regulations
concerning working safety and accident prevention.
They have been trained in use of the device.
They have read and understood the warning
information and handling symbols.
The owner/operations manager is also responsible for ensuring that this manual is kept in the immediate vicinity of the device and is always available for the operating personnel.
5.2 Avoidance of danger
Warning Installation and connection of the device
and the associated supplementary components must only be carried out by authorised personnel!
The local safety regulations must be observed!
Switch off the power supply before connecting the power cable and the relay contacts!
Warning Do not dismantle the device! Cleaning, maintenance and repair must
only be carried out by authorised personnel!
Warning Other applications than those described in
section 4. Applications are not approved and not permitted. Grundfos cannot be held liable for any damage resulting from incorrect use.
Caution
The mounting location must be selected so that the housing is not subjected to mechanical loading.
Check that all settings are correct before starting up the device!
Page 5
English (GB)
6. Identification
6.1 Nameplate
Fig. 3 Nameplate, Conex® DIS-C
6.2 Type key
TM04 0331 3914
DIS-C 1-CC, W-G 351-2000-10006 S/N: 08/02809 Conex DIS-C, 230/240V 50/60Hz 10 VA, IP 65 96725733P1108030802809
1
2
3
4
5
67 8 9
10
11
12
Pos. D escription
1 Type designation 2 Model 3 Product name 4 Power consumption [VA] 5 Product number 6 Country of origin 7 Enclosure class 8 Year and week of production
9 Marks of approval, CE mark, etc. 10 Voltage [V] 11 Frequency [Hz] 12 Serial number
Example: DIS -C -P CC -R1 -F -PVC W -G Units for measurement and control
DIS-C
Dosing Instrumentation Standard for conductivity measurement
Assembly
PPrepacked
Measuring cell
CC Conductivity, conductive CI Conductivity, inductive
Measuring range
R1 0 to 200 μS/cm R2 0 to 2000 μS/cm R3 0 to 20,000 μS/cm
Armature type
FFlow I Immersion X No armature
Armature material
PVC Polyvinyl chloride PP Polypropylene
Controller mounting option
W Wall-mounted P Panel-mounted (only for conductive measuring cell)
Power supply
G 1 x 230/240 V, 50/60 Hz H 1 x 115/120 V, 50/60 Hz
Page 6
English (GB)
7. Technical data
7.1 Versions
7.2 General data
7.3 Measuring ranges
7.3.1 Measuring ranges and cell constants for Conex
®
DIS-C with conductive measuring
cell
7.3.2 Measuring ranges for Conex
®
DIS-C with
inductive measuring cell
Power supply
• 230 V (± 10 %), 50/60 Hz (standard version)
• 115/120 V (± 10 %), 50/60 Hz
Type of measuring cell
• Conductive
• Inductive
Mounting variants
• For wall mounting
• For installation in control panel (only Conex
®
DIS-C, CI devices - with conductive measuring cell).
Dimensions (W x H x D)
• 165 x 160 x 80 mm (for wall mounting)
• 96 x 96 x 127 mm (for installation in control panel)
Weight
• 1.0 kg (for wall mounting)
• 0.8 kg (for installation in control panel)
Enclosure class
• IP65 (wall-mounted)
• IP54 (front, installation in control panel)
Internal fuse
• Yes (wall-mounted)
• No (installation in control panel)
Display
LCD display, two lines, 2 x 16 characters
Connections
Terminal strips for cable up to maximum 1.5 mm
2
Power consumption 10 VA
Electrical output
0 (4) to 20 mA galvanically isolated, maximum load 500 Ω
Switching points
Can be set within the measuring range
Contact rating for regulation and alarm relay
6 A / 250 V, maximum ohm resistive load 550 VA (with RC contact protection)
Permissible ambient temperature
0 °C to +50 °C
Permissible storage temperature
-20 °C to +65 °C
Maximum relative humidity
90 % (non-condensing)
Adjustable temperature coefficient of measurement solution
0 to 8 % / °C
Proportional band Xp 1 to 3000 % Reset time Tn 0 to 3000 seconds
Measuring range Cell constant
Conductive measuring cell
0 to 20 MΩ/cm
C = 0.05 96609150
0 to 2 μS/cm
0 to 20 μS/cm
0 to 200 μS/cm
0 to 2 mS/cm C = 0.2 96609151
0 to 20 mS/cm C = 1 96609152
Measuring range
Inductive measuring cell
0 to 2.000 mS/cm
95720194
0 to 20.00 mS/cm 0 to 200.0 mS/cm 0 to 2000 mS/cm
Page 7
English (GB)
7.4 Dimensional sketches / drilling diagram
Fig. 4 Dimensional sketch / drilling diagram for Conex® DIS-C for wall mounting
Fig. 5 Dimensional sketch / mounting sketch for Conex
®
DIS-C for control-panel wall mounting
TM03 6982 4506TM03 6983 4506
10
72.5
1
6
0
165
151
1
2
0
1
5
approx. 129
approx. 137
Page 8
English (GB)
8. Installation
8.1 Transport and storage
Transport the device carefully, do not drop!
Store at dry and cool location between -20 °C and +65 °C.
8.2 Unpacking
Check the device for damage. Install as soon as possible after unpacking.
Do not install or connect damaged devices!
8.3 Installation requirements
The location must be vibration-free, dry, dust-free and free of corrosive, pungent fumes or aggressive solvents.
Observe the data in section 7. Technical data.
8.4 Assembli ng the C one x® DIS-C housing
for wall mounting
Fig. 6 Installation of Conex® DIS-C for wall mounting
1. Drill three dowel holes with a diameter of 8 mm.
See section 7.4 Dimensional sketches / drilling
diagram.
2. Insert the supplied dowel pins.
3. Unscrew the clamp cover from the device.
4. Screw in the top middle screw.
5. Hang the device onto this screw.
6. Secure the device using the other two screws.
7. Screw the clamp cover back on.
Caution
Do not allow any foreign bodies to enter!
Note
Retain the packing material or dispose of it according to local regulations.
Caution
If you do not observe the installation requirements, the device may be damaged! The measurements may not be correct!
Warning Switch off the power supply before
installing! Enclosure class IP65 is only guaranteed if
the clamp covers and the associated threaded cable connections and temporary covers are closed.
TM03 6985 4506
151
120
Caution
Do not damage the gasket. The gasket must be fitted exactly.
Page 9
English (GB)
8.5 Assembling the Conex® DIS-C-P, CI housing for installation in control panel
1. Make an opening of 92 + 0.8 mm x 92 + 0.8 mm
in the control panel.
2. Slip on the supplied gasket.
3. Insert the device into the opening from the front.
4. Hook the clamps into the tightening cones on the
sides at the top and bottom.
5. Secure the device from the rear using a
screwdriver.
9. Commissioning / electrical connections
1. Remove the terminal cover on the front of the device.
2. Use the appropriate cable feedthroughs and tighten the screws carefully.
3. Connect the cables used to the terminals according to the Conex
®
DIS-C terminal
assignment.
4. Close the terminal cover again with correctly positioned gasket.
Caution
Do not damage the gasket. The gasket must be fitted exactly.
Warning Switch off the power supply before
installing! Enclosure class IP65 is only guaranteed
with the front panel of the terminals enclosure closed and with appropriate cable glands or dummy caps.
Warning Switch off the power supply before
connecting the power supply cable and the relay contacts! For safety reasons, the protective conductor must be connected correctly!
Observe the local safety regulations! Protect the cable connections and plugs
against corrosion and humidity.
Caution
Before connecting the power supply cable, check that the supply voltage specified on the nameplate corresponds to the local conditions!
An incorrect supply voltage may destroy the device!
To ensure electromagnetic compatibility (EMC), the input and current output cables must be screened.
Connect the screening to the screen ground on one side.
Refer to the wiring diagram! Route the input, current output and power supply cables in separate cable channels.
Caution
Enclosure class IP65 is only guaranteed if the terminal cover is correctly sealed! Do not damage the gasket on the terminal cover!
The gasket on the terminal cover must be positioned precisely!
Do not damage the gasket!
Note
Unused terminals must remain open.
Page 10
English (GB)
10
9.1 Conex® DIS-C conductive, housing for wall mounting
Fig. 7 Terminal connection diagram for Conex® DIS-C with conductive measuring cell, housing for wall
mounting
Caution
The measurement input must be screened! The screen must not be connected to the Conex
®
DIS-C, but only to the measuring
cell (outer casing of the cell)!
TM03 6986 3914
12
4
5
6
11 12
13
20
21
22
+
L
NPE
14
15 16
17
18 19
A
3
28
27
26
+
29
+
24V
With Pt100, connection with cable: 96611925 (5 m)
96611928 (15 m) 96611929 (25 m) (maximum cable length: 50 m)
Pos. Description
1 White, inner electrode of measuring cell 2 Brown, outer electrode of measuring cell 4 Yellow, Pt100 5 Green, Pt100
A Trimmer contrast setting
11-12 0/4-20 mA output 14 / 15 Control relay 1 output 16 / 17 Control relay 2 output 18 / 19 Alarm relay 3 output
20 / 21 / 22 For supply voltage, see nameplate
26 / 27 Water sensor
28 Screen
Page 11
English (GB)
11
9.2 Conex® DIS-C inductive, housing for wall mounting
Fig. 8 Terminal connection diagram for Conex® DIS-C with inductive measuring cell, housing for wall
mounting
TM03 6987 4011
12
4
5
61112
13
20
21
22
+
L
N
PE
28
27
26
+
14
15 16
17
18 19
A
29
+
24V
3
3b
Connection with 6 m cable, extendable with extension cable 95720380
Caution! Cable length without screen: maximum 30 mm
Caution! When extending the cable, the screen
must also be extended!
Pos. Description
1 Green, measurement 2 White, screen 3 Red, voltage supply
3b Black, voltage supply screen
4 Yellow, temperature sensor NTC, screen 5 Brown, temperature sensor NTC
A Trimmer contrast setting 11 / 12 0/4 to 20 mA output 14 / 15 Control relay 1 output 16 / 17 Control relay 2 output 18 / 19 Alarm relay 3 output
20 / 21 / 22 For supply voltage, see nameplate
26 / 27 Water sensor (external controller stop)
28 +24 V 29 Screen
Page 12
English (GB)
12
9.3 Conex® DIS-C conductive, housing for installation in control panel
Fig. 9 Terminal connection diagram for Conex® DIS-C with conductive measuring cell, housing for
installation in control panel
Caution
The screen must not be connected to the Conex
®
DIS-C, but only to the measuring cell. See the installation and operating instructions for the measuring cell!
TM03 6988 4409
L1
N
PE
+
-
+
-
1
24 25 26
3
2
4 5 6 7 8
9
10 11
12 13
14
15
18
21
16
19
22
17
20
23
With Pt100, connection with cable: 96611925 (5 m)
96611928 (15 m) 96611929 (25 m) (maximum length: 50 m)
Pos. Description
2 White, inner electrode of measuring cell 3 Brown, outer electrode of measuring cell 5 Yellow, Pt100 6 Green, Pt100
9 / 10 0/4 to 20 mA output 11 / 12 Water sensor 18 / 19 Control relay 1 output 20 / 21 Control relay 2 output 22 / 23 Alarm relay 3 output
24 / 25 / 26 For supply voltage, see nameplate
Page 13
English (GB)
13
9.4 Important instructions for connecting the device
As is common in microprocessor-controlled devices, certain precautions must be taken during installation and wiring. In addition to the general guidelines, the following is of particular importance:
Input wires and control wires must be laid
separately from one another and from power supply cables.
Analog output wires must be screened.
The screen can be connected to the device.
Relays and protective spools must remain free of
interference.
If inductive loads are connected, they must either
be screened, or the relay contact must be protected on the clamping strip of the Conex
®
DIS-C by an RC protective circuit, in accordance with the following table and the switching diagrams.
9.4.1 Power supply
The device is connected to the power supply at the clamps (L), (N) and (PE).
Check the correct supply voltage on the nameplate.
9.4.2 Connecting the conductivity measuring cell
9.4.3 Relay outputs
If inductive loads (including relay and protective spools) are connected, they must be screened. If this is not possible, the relay contact must be protected using a protection circuit in accordance with the table below.
For AC current
Fig. 10 Protection circuit with AC current
For DC voltage
The relay or protective spool must be screened with a suppressor diode.
Fig. 11 Protection circuit with DC voltage
9.4.4 Current outputs
Warning Before connecting the device, switch off
the power supply!
Caution
Connection of an incorrect supply voltage may destroy the device!
Caution
For connecting the conductivity cell to the Conex
®
DIS-C, only use the prescribed cable. This cable must not be used in the same cable channel as power supply cables!
Protect cable connections and plugs against corrosion and moisture!
Current up to Capacitor C Resistor R
60 mA 10 nF, 260 V 390 Ω, 2 W
70 mA 47 nF, 260 V 22 Ω, 2 W
150 mA 100 nF, 260 V 47 Ω, 2 W
1.0 A 220 nF, 260 V 47 Ω, 2 W
TM03 6990 4506TM03 7007 4506
Warning If floating relay outputs are used, they
must be supplied with a backup fuse!
Caution
When connecting the electrical outputs, be aware of the polarity and the maximum load (500 Ω)!
Caution
Use a screened cable for connecting the electrical outputs. The screen must be connected to PE with one end.
R = 47 to 390 Ω C = 10 nF to 220 nF / 260 V e.g. Siemens MKC B 81 921
Values can be found in the above table.
+
-
Page 14
English (GB)
14
10. Principles of regulatory function
Freely selectable control functions mean that the Conex
®
DIS-C controller can be adapted to a wide
variety of closed-loop control systems.
10.1 Regulatory behaviour
10.1.1 P regulation behaviour
The P controller has a static characteristic curve. The characteristic proportional band for the P controller is Xp. Within this range, which is limited to a maximum or minimum depending on the control direction, there is a proportional correlation between the input and output quantities of the controller.
The lower limit is the response threshold of the controller. This is the smallest regulatory deviation that leads to a measurable control variable.
The upper limit separates the proportional band from saturation. Above this limit, no further increase in output signal is possible, regardless of increases in the input signal. This range is called the control range of the controller, and the control variable can have any value within this range.
Due to the static characteristic curve, the P controller cannot reach the setpoint in a stationary state. This results in a consistent regulatory deviation, which can be reduced by decreasing Xp, but which cannot be completely eliminated using a P controller.
The controller reacts quicker with small Xp values. The Xp value cannot, however, be reduced arbitrarily, as this causes the controller to become unstable.
10.1.2 I regulation behaviour
The non-delayed relationship between the regulatory deviation and the control variable in a P controller results in an undesirable persistent regulatory deviation. However, if the regulatory deviation is controlled directly by the regulating speed instead of the control variable, this fixed assignment of the two variables no longer applies. The result is an integrated controller.
With a regulatory deviation of zero, i.e. when the setpoint is equal to the actual value, the regulating speed is also zero. Both positive and negative regulatory deviations can be influenced by positive or negative regulating speeds. The control variable covers the whole control range. The control range of the I controller is the range in which the regulatory deviation controls the regulating speed in a linear fashion.
The characteristic value of the I controller is the reset time Tn. The reset time is the time that must elapse, due to the integrated mode of action, for the step response to reach the value that a P controller would reach immediately.
The control circuit reacts slowly. If a regulatory deviation results, an I controller can only react by constantly changing its control variable. For this reason, regulation with I controllers is always slower than with controllers that act proportionally. If the speed of the controller is increased by decreasing the integration constant, the control circuit has a slight tendency towards instability.
At Tn = 0, the controller has no I proportion. In the absence of external influences, a control
circuit with an I controller therefore has no residual regulatory deviation in a stationary state when the control variable is constant.
10.2 Limit values
In principle, the limit value only has two switching states; ON and OFF. Depending on the set control direction, the controller is deactivated when the setpoint value is exceeded, or when the value drops below the setpoint.
10.2.1 Limit values with hysteresis
To prevent constant switching when the setpoint value is reached, it is possible to specify a hysteresis for the controller.
Example:
setpoint 600 μS/cm
hysteresis 10 μS/cm. The hysteresis band is arranged symmetrically
around the switching point.
Switch-off point = measured value + hysteresis / 2
Switch-on point = measured value - hysteresis / 2.
Fig. 12 Limit values with hysteresis
Note
Setting for a limit value: Xp = O.
TM03 6991 4506
605 600 595
µS/cm µS/cm µS/cm
1 0
Relay
605 μS/cm 600 μS/cm 595 μS/cm
μS/cm
Page 15
English (GB)
15
10.3 On-off controller with P behaviour
It is possible to use an on-off controller with P behaviour as an intermittent pulse regulator or as a pulse frequency regulator.
10.3.1 Intermittent pulse regulator
Example:
setpoint = 6 mS/cm
measuring range 0 to 10
Xp = 30
control direction = downwards. Xp determines the size of the proportional band as a
percentage of the measuring range. In the following example, this means that above 6 mS the relay switches on, first with a short activation time and then with an increasing activation time to 9 mS (the total switching on + off time remains constant). For greater measured values, the relay remains constantly switched on.
Fig. 13 Intermittent pulse regulator
The intermittent pulse regulation offers the option to recreate a constant controlling element using very simple control elements, e.g. a magnetic valve. Here, the relationship between switching on and off is changed depending on the calculated control variable. The total time (ON+OFF) is constant in intermittent pulse regulation. The total time can be set to between 1 and 99 seconds depending on the control system. A setting of 10 seconds leads to a good result in most cases.
If the calculated control variable is very low, in some cases it is possible that the control element attached here does not show a reaction within this short time. In this case, it is possible to set a minimum drive pulse. This can be within the range 0.1 to
9.9 seconds.
10.3.2 Pulse-frequency regulator
Example:
setpoint = 6 mS/cm
measuring range 0 to 10
Xp = 20 or 40
pulse frequency = 120
control direction = downwards. Xp determines the size of the proportional band as a
percentage of the measuring range. In the following example, this means that impulses are output from 6 mS and constantly increase to 8 mS (Xp = 20) or 10 mS (Xp = 40). For higher measured values, the prespecified maximum number of impulses (here 120/min) is output.
Fig. 14 Pulse-frequency regulator
The pulse frequency regulator in combination with an appropriate control variable is almost the same as a continuous controller. The disadvantages of the impulse-driven control variable only becomes apparent in the lower control variable range and with a low maximum pulse frequency. The specification of the maximum pulse frequency refers to 100 % dosing flow and can be set within a range from 0 to 180 impulses per minute.
Note
Setting for an on-off controller: Xp > O.
Note
Setting for an intermittent pulse regulator: Xp > O, pulse frequency = 0.
TM03 6992 4506
SP setpoint
MV measured value
6
7
8
9
T
ON
T
ON
T
[]mS/cm
2 3
0 1
4 5
6 7
8
10
9
[mS ]/cm
SP
MV
MV
[mS/cm]
[mS/cm]
Note
The intermittent pulse period must always be at least twice as long as the minimum switch-on time!
Note
Setting for a pulse-frequency regulator: Xp > O, pulse frequency > 0.
TM03 6993 4506
0
30
60
90
100%
6
789
10
120
Xp = 40
Xp = 20
[1 min]/
Pulse frequency
Measured value
Setpoint
[1/min]
[mS/cm]
Page 16
English (GB)
16
10.3.3 Continuous action controllers
The control variables calculated by the controller based on the setpoint S1 or S2 can optionally be output as a continuous control signal via the analog output.
See section 12.4.4 Analog output.
Fig. 15 Continuous-action controllers
10.4 Parameter settings
Make a note here of the parameter settings for the device.
TM03 6994 4506
0
5
10
15
100%
6
789
10
20
Xp = 40
Xp = 20
[mA]
Current output
Measured value
Setpoint
[m/A]
[mS/cm]
Setup Controller
Pulse freq. S1 _____ / min Pulse freq. S2 _____ / min
Ctrl. direction S1
__ downward __ upward
Ctrl. direction S2
__ downward
__ upward Hysteresis _____ μS Int. pulse period _____ s Min. switch-on _____ s
Delay control
Delay ctrl.
__ off
__ on Delay ctrl. _____ s
Analog output
Select output
__ 0-20 mA
__ 4-20 mA Start 0/4 mA _____ μS End 20 mA _____ μS Analog output __ measured value
Temper. coeff. _____ % / °C Cell const. _____ Measur. range _____
Averaging
__ on
__ off
Temperature compensation
Temp. compens.
__ Automat.comp.
__ Manual comp. Manual temp. _____ °C
Controller settings
Setpoint 1 _____ μS Prop. band XP S1 _____ μS Reset time TN S1 _____ s Setpoint 2 _____ μS Prop. band XP S2 _____ μS Reset time TN S2 _____ s
Alarm
Alarm value A1 _____ μS Alarm value A2 _____ μS Delay _____ s
Page 17
English (GB)
17
11. Initial operation and settings
11.1 Initial steps for operation
Once the assembly and connection steps have been completed, carry out the following steps when using the device for the first time.
1. Switch on the power supply.
2. If required, set the measuring range.
3. Check the entered cell constants.
4. If necessary, perform a cable compensation (for a conductive measuring cell).
5. Set the parameters for the device function.
Check the outputs and secondary devices.
12. Operation
12.1 Device layout for Conex® DIS-C
12.1.1 Control and display elements
The Conex
®
DIS-C conductivity measuring amplifier is operated using a touch-sensitive membrane keypad.
Fig. 16 Control and display elements
Display
Control elements
Display fields
Fig. 17 Display fields
Warning Before connecting the power supply,
ensure that the supply voltage corresponds to the power supply specified on the nameplate!
Note
Notes or instructions that make the job easier and ensure safe operation.
TM03 6995 4506
Pos. Description
1LCD display
1
2
6
345
Pos. Function Name
Menu control button
[Up] 3[Left] 4[Down] 5 [Right]
Button for returning to start menu
[OK]
TM03 6996 4506
Pos. Description
1a
Measuring value display
Displays the current measured value in MΩ, μS, mS (depending on the selected measuring range).
1b
Temperature display
Displays the temperature used for compensation. Depending on the setting, this is either the manually specified temperature or the temperature measured using the temperature sensor.
1c
Relay 1 switching status
A filled rectangle indicates switched-on status.
1d
Relay 2 switching status
A filled rectangle indicates switched-on status.
1e
Control function
Displays the preselected regulation type.
1f Display of active menu control buttons.
Page 18
English (GB)
18
12.2 Menu control
12.3 Navigation in the menus
To navigate in and between menus, use the [Up] and [Down] buttons.
Use the [Right] button to open the menu next to it. The currently active menu control buttons are displayed in the corresponding line.
Use the [Left] button to save values.
Use [OK] to exit the menu and return to the start display.
Main menu Default values
Temp. compens.
Temp. compens. Manual comp. Manual temp. 025 °C
Enter password Enter password Code 086
Controller
Setpoint S1 02.5 μS Prop. and xp S1 10 % Reset time TN S1 000 s Setpoint S2 02.0 μS Prop. band xp S2 10 % Reset time TN S2 000 s
Alarm values
Alarm value A1 00.0 μS Alarm value A2 02.0 μS
Delay 0.05 s Setup See table below Service See table below
Setup menu Default values
Corr. temp. Corr. temp. 0 °C
Contr. param.
Pulse freq. S1 0-180 / min Pulse freq. S2 0-180 / min Ctrl. direction S1 Downward control Ctrl. direction S2 Upward control Hysteresis 00.1 μS Int. pulse period 10 s Min. switch-on 0.5 s
Delay ctrl.
Delay ctrl. off Delay ctrl. 180 s
Analog output
Select output 0-20 mA Start 0/4 mA 00.0 μS End 20 mA 200.0 μS
Analog output Measured value Language Sel. language Deutsch Temper. coeff. Temper. coeff. 0.0 % / °C Cell const. Cell const. 0.050 Cable
compens.
Cable compens. 00.0 μS
Measur. range Measur. range 20.00 μS Averaging Averaging off
Service menu Default values
Product info
Unit No. No. 041 Software date M/Y 1.00 Product. date M/Y 1.00
Analog input
Input 1 -019 Input 2 000 °C
Delete setting Delete setting
Note
Important menu selections and changes to data are code-protected to prevent unauthorised access.
Note
The order of the settings in the following section is different to the order of menu navigation. This section describes the basic settings that are made first during setup.
Page 19
English (GB)
19
12.4 Setup
The "Setup" menu contains settings that need to be made or checked the first time the Conex
®
DIS-C is
used.
1. Press the [Down] button to navigate to the "Setup" menu.
2. Press the [Right] button to open the "Setup" menu.
3. Press the [Down] button to navigate to the submenus.
In the submenus, it is possible to enter settings for the following values:
temperature correction
control parameters
switch-on delay
analog output
language
temperature coefficient
cell constant C
bus address
cable compensation/zero point
measuring range
averaging on/off.
12.4.1 Temperature correction
Because the temperature sensor is connected using a 2-conductor method, this can result in deviations in temperature measurement and display. These deviations can be corrected within a range of ± 5 °C.
1. Press the [Right] button to open the "Corr. temp." menu.
2. Press the [Right] button to start value input.
3. Press the [Up] and [Down] buttons to set the value.
12.4.2 Control parameters
The first time the device is used, the regulatory functions must be defined.
In the "Contr. param." menu, the following values can be set:
pulse frequency S1
pulse frequency S2
hysteresis
pulse + pause
minimum impulse.
1. Press the [Right] button to open the "Contr. param." menu.
2. Press the [Down] button to navigate to the submenus.
Pulse frequency S1/S2
1. Press the [Right] button to open the "Pulse freq. S1" or "Pulse freq. S2" menu.
2. Press the [Up] and [Down] buttons to set the value.
TM03 6997 4506TM03 6998 4506TM03 6999 4506
Alarm Setup
Corr. temp.
0.0 °C
TM03 6998 4506
Note
Setting for a limit value: Xp = O. Setting for an intermittent pulse regulator:
Xp > O, pulse frequency = 0. Setting for a pulse frequency regulator:
Xp > O, pulse frequency > 0.
Note
Pulse frequency setting = maximum number of impulses per minute. Set the appropriate pulse frequency for the connected control element.
Note
It is possible to make separate control parameter settings for S1 and S2.
TM03 6998 4506
Corr. temp. Contr. param.
Corr. temp. Contr. param.
Page 20
English (GB)
20
Control direction S1/S2
By default, the control direction is set to exceeded (= downwards) for S1, and for S2 it is set to upwards. This means that if the value set for setpoint S1 is exceeded, relay 1 is switched, and if the value drops below setpoint S2, relay 2 is switched.
It is possible to change the control direction for S1 and S2.
1. Press the [Right] button to open the "Ctrl. direction S1" or "Ctrl. direction S2" menu.
2. Press the [Up] and [Down] buttons to set the value.
Hysteresis
The hysteresis setting only takes effect for a limit value. If a setting is made, the hysteresis band surrounds the selected setpoint symmetrically. If the setpoint S1 is set to 0.500 mS and the hysteresis setting is set to 0.010 mS, the relay switches on or off (depending on the control direction) at 0.505 mS and 0.495 mS.
1. Press the [Right] button to open the "Hysteresis" menu.
2. Press the [Up] and [Down] buttons to set the value.
Intermittent pulse period
The factory setting for the intermittent pulse period is 10 seconds. This setting has proved ideal for nearly all applications.
1. Press the [Right] button to open the "Int. pulse period" menu.
2. Press the [Up] and [Down] buttons to set the value.
Minimum impulse/minimum switch-on time
The minimum switch-on time determines the shortest drive pulse in the intermittent pulse period regulation.
The intermittent pulse period setting must always be at least twice as long as the minimum switch-on time.
1. Press the [Right] button to open the "Min. switch-on" menu.
2. Press the [Up] and [Down] buttons to set the value.
12.4.3 Switch-on delay
If the switch-on delay of the Conex
®
DIS-C is activated, the controller is not activated until the specified time has elapsed after the power supply to the device has been switched on. This menu can be used to switch the switch-on delay on and off, and if the switch-on delay is activated, the delay duration can be entered.
Activating/deactivating the switch-on delay
1. Press the [Right] button to open the "Delay
control" menu.
2. Press the [Right] button to switch between on
and off.
Setting the switch-on delay time
1. Press the [Right] button to open the value input
display.
2. Press the [Up] and [Down] buttons to set the
value.
TM03 6998 4506TM03 6998 4506TM03 6998 4506
Ctrl. direction Upward control
Hysteresis
0.010 mS
Int. pulse period 10 sec.
TM03 6999 4506TM03 6998 4506TM03 6998 4506
Min. switch-on
0.5 sec.
Contr. param. Delay ctrl.
Delay ctrl. On
Page 21
English (GB)
21
12.4.4 Analog output
Using the analog output, it is possible to choose whether the measured value is signalled externally as a registry output, or it is possible to choose the switching points S1 or S2 as continuous control outputs. Any range of 0 to 20 mA or 4 to 20 mA within the measuring range can be assigned to the analog output. The indicated measuring range is defined by the start and end values. This also determines the direction of the analog output.
Press the [Right] button to open the "Analog output" menu.
The following settings are made in the "Analog output" menu:
switching between 0 to 20 mA and 4 to 20 mA
analog output start value
analog output end value
assigning analog output.
Switching between 0 to 20 mA and 4 to 20 mA
1. Press the [Right] button to choose between 0-20 mA and 4-20 mA.
2. Press the [Down] button to open the "Start 0/4 mA" submenu.
Analog output start value
1. Press the [Right] button to open the value input display.
2. Press the [Up] and [Down] buttons to set the value.
3. Press the [Right] button to save the entry.
4. Press the [Down] button to open the "End 20 mA" submenu.
Analog output end value
1. Press the [Right] button to open the value input display.
2. Press the [Up] and [Down] buttons to set the value.
3. Press the [Left] button to save the entry.
4. Press the [Down] button to open the "Analog output" submenu.
Assigning analog output
1. Press the [Right] button to choose between the measured value, continuous controller 1 and continuous controller 2.
12.4.5 Language
The "Language" menu is used to determine the language for the Conex
®
DIS-C.
1. Press the [Right] button to open the "Language" menu.
2. Press the [Right] button to choose between the languages (German, English, French).
TM03 6998 4506TM03 6998 4506
Select output 0-20 mA
Start 0/4 mA
0.000 mS
TM03 6999 4506TM03 6999 4506TM03 6999 4506TM03 6999 4506TM03 6999 4506
End 20 mA
2.000 mS
Analog output Measured value
Analog output Cont. ctrl. S1
Analog output Cont. ctrl. S2
Sel. language Deutsch
Page 22
English (GB)
22
12.4.6 Temperature coefficient
This menu is used for displaying and setting the temperature coefficient.
Because different measuring fluids have different temperature coefficients, the appropriate coefficient must be set. The setting range is 0.0 to 8.0 % / °C. The factory setting is 2.5 % / °C, which is suitable for many applications.
1. Press the [Right] button to open the "Temper. coeff." menu.
2. Press the [Right] button to open the value input display.
3. Press the [Up] and [Down] buttons to set the value.
12.4.7 Cell constant C
The mechanical dimensions used for the measurement of active surfaces of the measuring cell are defined in the cell constant. The measuring cell is characterised by the cell constant.
1. Press the [Right] button to open the "Cell const." menu.
2. Press the [Right] button to open the value input display.
3. Press the [Up] and [Down] buttons to set the value.
Cable compensation (only for conductive measurement)
The capacity of the cable can lead to an incorrect value, particularly for small measuring ranges. This incorrect value can be corrected as follows:
1. Press the [Right] button to select the "Cable compens." menu.
2. Hold the connected, dry measuring cell in the air.
– If the top line of the display reads a measured
value, i.e. the value 0.00 is not displayed, cable compensation must be performed.
3. Simultaneously press the [Left] and [Down] buttons.
– If the compensation is successful, the value
0.00 is displayed.
12.4.8 Measuring range
In this menu, the required measuring range for the device can be set (MΩ, μS, mS).
1. Press the [Right] button to open the "Measur. range" menu.
2. Press the [Right] button (several times) to select a measuring range.
TM03 6998 4506TM03 6999 4506TM03 6999 4506
Language Temper. coeff.
Temper. coeff.
0.0 % / °C
Cell const.
0.050
TM03 7000 4506TM03 6999 4506TM03 6999 4506
Note
When setting the measuring range, ensure that it is suitable for the cell constant of the measuring cell. See section 7. Technical
data.
0.00 μS Press
Measur. range
2.000 μS
Measur. range
20.00 MOhm
Page 23
English (GB)
23
12.4.9 Averaging on/off
In this menu, the averaging function can be switched on or off. If the averaging function is switched on, the mean of the last 10 measured values is calculated and displayed as the measured value.
1. Press the [Right] button to open the "Averaging" menu.
2. Press the [Right] button to select averaging on or off.
12.5 Relay menu (S1 S2)
In the relay menu (S1 S2), it is possible to choose between manual and automatic operation. In manual operation, the relays S1 and S2 can be switched on and off separately.
12.5.1 Automatic and manual operation
In automatic operation, the relay contacts are switched by the built-in controller. "Auto" is shown in the display.
In manual operation, the relay is switched manually. "Man" is shown in the display.
Switching between automatic and manual operation:
Press the [Right] button to switch the controller to manual or automatic operation.
12.5.2 S1/S2 in manual operation Switching the relays S1/S2 on and off:
1. Press the [Up] button to select the chosen relay (S1/S2).
– The corresponding symbol flashes.
2. Press the [Right] button to switch the chosen relay (S1 or S2) on or off.
– The switch status of the relay is displayed as
follows: Relay ON = symbol filled Relay OFF = symbol not filled.
12.6 Temperature compensation
Temperature compensation cancels out the effect of temperature dependency of the medium. It is based on a reference temperature of 25 °C.
This temperature compensation can be performed automatically via a connected temperature sensor or manually by entering the relevant temperature.
Select the "Temp. compens." menu.
Switching between manual and automatic compensation:
Press the [Right] button to select between manual and automatic compensation.
Selecting the default temperature for manual compensation
1. Press the [Down] button to open the "Manual temp." menu.
2. Press the [Right] button to open the temperature selection display.
3. Press the [Up] and [Down] buttons to select the temperature.
TM03 6999 4506
Note
The description of the rest of the menus now continues in the order of menu navigation.
TM03 6997 4506TM03 7001 4506
Note
If the relays are switched on manually, they remain switched on until they are switched off again, or until control is switched back to automatic.
Note
Switching to automatic operation is only possible if the arrow to the right of the "Man" text is visible.
Averaging Off
TM03 6998 4506TM03 6999 4506
Temp. compens. Automat. comp.
Default temp.
25.5 °C
Page 24
English (GB)
24
12.7 Displaying / changing code
The device can be protected against unauthorised or unintentional changing of the programmed data. Two release codes are stored:
Code 086: General access to all functions.
Code 011: Access to temperature compensation
and controller settings.
In all other code settings, the device is protected against unintentional changes to data. If a code is set and a locked menu is selected, the operator is prompted to enter the code.
Displaying the code
Press the [Right] button to open the "Enter password" menu.
– The current code is displayed.
Changing the code
1. Press the [Right] button to open the "Enter password" menu.
2. Press the [Up] and [Down] buttons to enter the required code in the range 000 to 2000.
– Pressing the [Up] button once increases the
value by +1. If the button is held down for longer, the value increases automatically.
– Pressing the [Down] button once decreases the
value by -1. If the button is held down for longer, the value decreases automatically.
3. Press the [Left] button to save the entry.
12.8 Controller settings
In the "Controller" menu, the following values are set:
•setpoint S1
proportional band Xp S1
reset time Tn (I part) S1
•setpoint S2
proportional band Xp S2
reset time Tn (I part) S2.
1. Press the [Right] button to open the "Controller" menu.
2. Press the [Up] and [Down] buttons to select the required value.
3. Press the [Right] button to open the value input display.
12.8.1 Setpoint setting S1/S2
The setpoints S1 and S2 are set separately and can have different values within the measuring range.
1. Press the [Right] button to open the value input display.
2. Press the [Up] and [Down] buttons to set the value.
Note
Important menu selections and changes to data are code-protected to prevent unauthorised access.
TM03 6998 4506TM03 6999 4506TM03 7002 4506
Temp. compens. Enter password
Enter password 011 Code
Enter password 011 Code
Note
This entry is only possible if the corresponding controller function is already set in the "Setup" menu.
TM03 6998 4506TM03 6998 4506
Enter password Controller
Setpoint 2
0.000 mS
Page 25
English (GB)
25
12.8.2 Proportional band Xp S1/S2
The proportional band Xp (P behaviour) is set separately for both setpoints in the range 1 to 3000 %.
1. Press the [Right] button to open the value input display.
2. Press the [Up] and [Down] buttons to set the value.
12.8.3 Reset time Tn (I part) S1/S2
The reset time Tn (I part) is set separately for both setpoints in the range 0 to 3000 seconds.
If the reset time Tn is 0 seconds, the I part is deactivated.
1. Press the [Right] button to open the value input display.
2. Press the [Up] and [Down] buttons to set the value.
12.9 Alarm value setting A1/A2
For the limit value alarm, the alarm values A1 and A2 are set separately. The switch direction for alarm value A1 is set to "exceed", and for alarm value A2 it is set to "drop below". If the alarm value 1 is exceeded or if the value drops below alarm value 2, relay 3 is switched after the specified delay time has elapsed.
The alarm message is delayed by the specified time. If the delay time is set to 000 seconds, the alarm message of the limit value alarm is raised immediately.
Setting the alarm values
1. Press the [Right] button to open the "Alarm values" menu.
2. Press the [Up] and [Down] buttons to select the required value (A1, A2).
3. Press the [Right] button to open the value input display.
4. Press the [Up] and [Down] buttons to set the value.
Setting the alarm delay time
1. Press the [Up] and [Down] buttons to select "Delay".
2. Press the [Right] button to open the value input display.
3. Press the [Up] and [Down] buttons to set the value.
Note
Setting for a limit value: Xp = O. Setting for an intermittent pulse controller
or pulse frequency controller: Xp > O.
TM03 6998 4506TM03 6999 4506
Prop. band xp 3000 %
Reset time TN 000 sec.
TM03 6998 4506TM03 6999 4506
Controller Alarm values
Delay 000 s
Page 26
English (GB)
26
12.10 Service
The "Service" menu contains service information and utilities.
The "Service" menu contains the following options:
device data
analog inputs
resetting factory settings.
Press the [Right] button to open the "Service" menu.
12.10.1 Device data
1. Press the [Right] button to open the "Product info" menu.
2. Press the [Up] and [Down] buttons to switch between the following displays.
Device number
Displays the serial number.
Software status
Displays the latest revision date of the software (e.g. 1.00: The software revision status is January 2000).
Production date
Displays the date of manufacture of the device (e.g. 3.00: The device was produced in March 2000).
12.10.2 Analog inputs/test
In this menu, the analog inputs are tested. The input signals are displayed in mV (analog input 1) and °C (analog input 2).
1. Press the [Right] button to open the "Analog input" menu.
2. Press the [Up] and [Down] buttons to switch between the following displays:
12.10.3 Deleting data/resetting factory settings
In some circumstances it may be necessary to restore the device to its delivered status. All values set by the customer are overwritten with the factory settings.
The initial settings on the device must then be made again.
1. Press the [Right] button to open the "Delete setting" menu.
2. Simultaneously press and hold down the [Left] and [Down] buttons.
– "Please wait!!!" is displayed.
Deleting the data takes approximately 10 seconds. When this display disappears, the Conex
®
DIS-C is
restored to the factory settings.
13. Disposal
This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Subject to alterations.
TM03 6998 4506TM03 7003 4506TM03 7004 4506
Setup Service
Software date M/Y 1.00
Product. date M/Y 3.00
TM03 7003 4506TM03 7004 4506
Note
Before deleting the memory, make a note of the important parameter settings.
TM03 7000 4506
Analog input Input 1 056 mV
Analog output Input 2 023 °C
Delete setting Press
Page 27
Declaration of conformity
27
Declaration of conformity 1
GB: EC/EU declaration of conformity
We, Grundfos, declare under our sole responsibility that the product Conex DIS-C, to which the declaration below relates, is in conformity with the Council Directives listed below on the approximation of the laws of the EC/EU member states.
DE: EG-/EU-Konformitätserklärung
Wir, Grundfos, erklären in alleiniger Verantwortung, dass das Produkt Conex DIS-C, auf das sich diese Erklärung bezieht, mit den folgenden Richtlinien des Rates zur Angleichung der Rechtsvorschriften der EG-/EU-Mitgliedsstaaten übereinstimmt.
ES: Declaración de conformidad de la CE/UE
Grundfos declara, bajo su exclusiva responsabilidad, que el producto Conex DIS-C al que hace referencia la siguiente declaración cumple lo establecido por las siguientes Directivas del Consejo sobre la aproximación de las legislaciones de los Estados miembros de la CE/UE.
FR: Déclaration de conformité CE/UE
Nous, Grundfos, déclarons sous notre seule responsabilité, que le produit Conex DIS-C, auquel se réfère cette déclaration, est conforme aux Directives du Conseil concernant le rapprochement des législations des États membres CE/UE relatives aux normes énoncées ci-dessous.
IT: Dichiarazione di conformità CE/UE
Grundfos dichiara sotto la sua esclusiva responsabilità che il prodotto Conex DIS-C, al quale si riferisce questa dichiarazione, è conforme alle seguenti direttive del Consiglio riguardanti il riavvicinamento delle legislazioni degli Stati membri CE/UE.
NL: EG/EU-conformiteitsverklaring
Wij, Grundfos, verklaren geheel onder eigen verantwoordelijkheid dat product Conex DIS-C, waarop de onderstaande verklaring betrekking heeft, in overeenstemming is met de onderstaande Richtlijnen van de Raad inzake de onderlinge aanpassing van de wetgeving van de EG-/EU-lidstaten.
PT: Declaração de conformidade CE/UE
A Grundfos declara sob sua única responsabilidade que o produto Conex DIS-C, ao qual diz respeito a declaração abaixo, está em conformidade com as Directivas do Conselho sobre a aproximação das legislações dos Estados Membros da CE/UE.
– EMC Directive (2014/30/EU).
Standards used: EN 61326-1:2013, EN 61000-3-2:2015, EN 61000-3-3:2014.
– Low Voltage Directive (2014/35/EU).
Standard used: EN 61010-1:2011-07.
This EC/EU declaration of conformity is only valid when published as part of the Grundfos instructions.
Pfinztal, 20th April 2016
Ulrich Stemick
Technical Director
Grundfos Water Treatment GmbH
Reetzstr. 85, D-76327 Pfinztal, Germany
Person authorised to compile the technical file and
empowered to sign the EC/EU declaration of conformity.
Page 28
Grundfos companies
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 - Garin Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 411 111
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belarus
Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56 Тел.: +7 (375 17) 286 39 72, 286 39 73 Факс: +7 (375 17) 286 39 71
E-mail: minsk@grundfos.com
Bosnia/Herzegovina
GRUNDFOS Sarajevo Trg Heroja 16, BiH-71000 Sarajevo Phone: +387 33 713 290 Telefax: +387 33 659 079 e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
Grundfos Alldos Dosing & Disinfection
ALLDOS (Shanghai) Water Technology Co. Ltd. West Unit, 1 Floor, No. 2 Building (T 4-2) 278 Jinhu Road, Jin Qiao Export Processing Zone Pudong New Area Shanghai, 201206 Phone: +86 21 5055 1012 Telefax: +86 21 5032 0596 E-mail: grundfosalldos-CN@grundfos.com
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 10F The Hub, No. 33 Suhong Road Minhang District Shanghai 201106 PRC Phone: +86-21 6122 5222 Telefax: +86-21 6122 5333
Croatia
GRUNDFOS CROATIA d.o.o. Cebini 37, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.hr.grundfos.com
Czech Republic
GRUNDFOS s.r.o. Čapkovského 21 779 00 Olomouc Phone: +420-585-716 111 Telefax: +420-585-716 299
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Trukkikuja 1 FI-01360 Vantaa Phone: +358-(0)207 889 500 Telefax: +358-(0)207 889 550
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS Water Treatment GmbH Reetzstraße 85 D-76327 Pfinztal (Söllingen) Tel.: +49 7240 61-0 Telefax: +49 7240 61-177 E-mail: gwt@grundfos.com
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 E-mail: infoservice@grundfos.de Service in Deutschland: E-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Park u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 097 Phone: +91-44 4596 6800
Indonesia
PT. GRUNDFOS POMPA Graha Intirub Lt. 2 & 3 Jln. Cililitan Besar No.454. Makasar, Jakarta Timur ID-Jakarta 13650 Phone: +62 21-469-51900 Telefax: +62 21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. Gotanda Metalion Bldg. 5F, 5-21-15, Higashi-gotanda Shiagawa-ku, Tokyo, 141-0022 Japan Phone: +81 35 448 1391 Telefax: +81 35 448 9619
Page 29
Grundfos companies
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Veluwezoom 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
Romania
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундфос Россия, 109544 Москва, ул. Школьная
39
Тел. (+7) 495 737 30 00, 564 88 00 Факс (+7) 495 737 75 36, 564 88 11
E-mail grundfos.moscow@grundfos.com
Serbia
GRUNDFOS Predstavništvo Beograd Dr. Milutina Ivkovića 2a/29 YU-11000 Beograd Phone: +381 11 26 47 877 / 11 26 47 496 Telefax: +381 11 26 48 340
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689
Slovakia
GRUNDFOS s.r.o. Prievozská 4D 821 09 BRATISLAVA Phona: +421 2 5020 1426 sk.grundfos.com
Slovenia
GRUNDFOS LJUBLJANA, d.o.o. Leskoškova 9e, 1122 Ljubljana Phone: +386 (0) 1 568 06 10 Telefax: +386 (0)1 568 0619 E-mail: tehnika-si@grundfos.com
South Africa
Grundfos (PTY) Ltd. Corner Mountjoy and George Allen Roads Wilbart Ext. 2 Bedfordview 2008 Phone: (+27) 11 579 4800 Fax: (+27) 11 455 6066 E-mail: lsmart@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB (Box 333) Lunnagårdsgatan 6 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31-331 94 60
Switzerland
GRUNDFOS ALLDOS International AG Schönmattstraße 4 CH-4153 Reinach Tel.: +41-61-717 5555 Telefax: +41-61-717 5500 E-mail: grundfosalldos-CH@grundfos.com
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-44-806 8111 Telefax: +41-44-806 8115
Taiwan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
Бізнес Центр Європа Столичне шосе, 103 м. Київ, 03131, Україна Телефон: (+38 044) 237 04 00 Факс.: (+38 044) 237 04 01
E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971-4- 8815 166 Telefax: +971-4-8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 4TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Uzbekistan
Grundfos Tashkent, Uzbekistan The Representative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292
Addresses revised 25.01.2016
Page 30
www.grundfos.com
96709879 0416
ECM: 1182149
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks
owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide.
© Copyright Grundfos Holding A/S
Loading...