English (GB) Installation and operating instructions
Caution
Note
English (GB)
Original installation and operating instructions.
CONTENTS
Page
1.Symbols used in this document
2.Parameter settings
3.General information
4.Applications
5.Safety instructions
5.1Obligations of the owner
5.2Avoiding danger
6.Identification
6.1Nameplate
7.Technical data
7.1Enclosure class
7.2General data
7.3Electronic data and functions
7.4RS-485 interface
7.5Dimensions
8.Installation
8.1Transport and storage
8.2Unpacking
8.3Installation requirements
8.4Installation in control panel
8.5Installation in wall housing
9.Electrical connection
9.1Terminals
9.2Power supply connection
9.3Current inputs and outputs
9.4Feedback potentiometer of the final
control element
9.5Relay outputs
10.Operation
10.1 Function
10.2 Controls and displays
10.3 Operating the controller
11.Fault finding
12.Maintenance
12.1 Replacing mains fuses (wall housing)
13.Spare parts
14.Disposal
15.Appendix
15.1 Measuring and control technology
15.2 Application examples of different output
signals and final control elements
15.3 RS-485 serial interface
Warning
Prior to installation, read these
installation and operating instructions.
Installation and operation must comply
2
3
4
4
4
4
4
4
4
4
4
1. Symbols used in this document
5
5
6
6
6
6
6
6
6
7
7
8
9
9
9
10
11
11
13
14
26
26
26
26
26
27
27
34
58
with local regulations and accepted
codes of good practice.
Warning
These complete installation and
operating instructions are also
available on www.grundfos.com.
Prior to installation, read these
installation and operating instructions.
Installation and operation must comply
with local regulations and accepted
codes of good practice.
Warning
If these safety instructions are not
observed, it may result in personal
injury.
If these safety instructions are not
observed, it may result in malfunction
or damage to the equipment.
Notes or instructions that make the job
easier and ensure safe operation.
2
Page 3
2. Parameter settings
Controller settings
LED1st level2nd level3rd level
M
Code
SP 1
SP 2
XP
TN (s)
TV (s)
Measured valueCode functions
---%
Code numberHysteresisDevice number for RS-485
---%
Switching point SP 1Pulse frequency for SP 1Transmits alarm via RS-485
%
Switching point SP 2Pulse frequency for SP 2
%
Proportional band XpInterpulse period
%sec
Reset time TnActuating time
secsec
Derivative action time TvDisturbance variableRange of current input 2
sec---%
Position of feedback
potentiometer
x 100
pulses/
hour
x 100
pulses/
hour
English (GB)
01 (yes)
00 (no)
% at 0 (4) mA
% at 20 mA
---%
TM03 7053 2108
Maximum dosing timeMinimum pulse length
secsec
TM03 7054 2108
3
Page 4
3. General information
Caution
342-5000-10000
S/N: 08/61557
230/240V 50/60Hz 8 VA, IP 65
Conex DIS-2Q
96732494P1108270861557
1
3
4
789
10
11
6
2
5
English (GB)
This manual contains all important information about
the Conex DIS-2Q:
• technical data
• instructions for startup, use and maintenance
• safety information.
If you need further information, or if problems occur
which are not described in details in this manual,
please contact Grundfos.
4. Applications
The Conex DIS-2Q is a multipurpose device
designed to carry out high-precision controls of
disinfection parameters, pH-value and redox
potential.
Conex DIS-2Q microprocessor-based controllers
controls any measured variables using appropriate
final control elements.
Warning
Other applications than those
described in section 4. Applications
are considered as non-approved and
are not permissible.
Grundfos cannot be held liable for any
damage resulting from incorrect use.
5. Safety instructions
5.1 Obligations of the owner
The owner of the plant is responsible for:
• compliance with country-specific safety
regulations
• training of operating personnel
• provision of prescribed protective equipment
• implementation of regular maintenance.
5.2 Avoiding danger
Warning
Installation and connection of the
device and the associated
supplementary components must only
be carried out by authorised personnel!
The local safety regulations must be
observed!
Warning
Switch off the power supply before
connecting the power supply cable and
relay contacts!
Do not open the device!
Maintenance and repair must only be
4
carried out by authorised personnel!
Select the mounting location so that
the housing is not subject to
mechanical loading.
Check that all settings are correct
before starting the device!
6. Identification
6.1 Nameplate
Fig. 1Nameplate, Conex DIS-2Q
Pos.Description
1Model
2Serial number
3Voltage [V]
4Frequency [Hz]
5Product name
6Product number
7Country of origin
8Year and week of production
9CE mark
10Power consumption [VA]
11Enclosure class
7. Technical data
7.1 Enclosure class
Control panel enclosureIP54 (front)
Control panel enclosure
with optional front door
Wall-mounted enclosure
(optional wall housing)
IP55
IP65
TM04 1218 1213
Page 5
7.2 General data
Note
Input powerApproximately 8 VA
Permissible
ambient
0 to 50 °C
temperature
Permissible
storage
temperature
Maximum relative
humidity
-20 to +65 °C
90 % (non-condensing)
Weight0.8 kg
EnclosureNoryl, chemically resistant
Connections
Versions of power
supply
Screw-plug terminals for
cables up to 2.5 mm
• 230/240 V (50/60 Hz)
(standard model)
2
• 115/120 V (50/60 Hz)
7.3 Electronic data and functions
7.3.1 Inputs and outputs
Continuous control output for
SP 1:
Current output 1
Current output 2
Current input 1
Current input 2
Contact rating
• 0 (4) to 20 mA
• electrically isolated
• max. load 400 Ω.
Position of feedback
potentiometer or continuous
control output for SP 2
• 0 (4) to 20 mA
• electrically isolated
• max. load 400 Ω.
Measured value (actual
value):
• 0 (4) to 20 mA
• electrically isolated
• load 50 Ω.
Disturbance variable/
command variable:
• 0 (4) to 20 mA
• electrically isolated
• load 50 Ω.
6 A / 250 V, max. 550 VA
resistive load (with contact
protection circuit) of relay
outputs.
• controller with disturbance
variable feedforward.
• Proportional action
Control action
• integral action
• differential action.
7.3.3 Display ranges
Measured value (actual value)0-100 %
Disturbance variable0-1,999 %
Position of final control element 0-100 %
7.3.4 Adjustment ranges
Switching points0-100 %
Control direction
Proportional band X
Reset time T
Derivative action time
T
v
Setting for current
output 2
n
Can be set to upward or
downward.
0-500 %
p
0-1,999 s
0-500 s
Ratio: -1,999 to +1,999 %
Disturbance variable:
0-1,999 %
Hysteresis0-50 %
Interpulse period1-99 s
Minimum pulse width 0 - 9.9 s
Pulse frequency
(selectable
separately for each
switching point)
0.1 - 72 (correlates with
10-7,200 pulses/hour)
Actuating time1-240 s
Time delay for alarm
signal
0-1,999 s (maximum
dosing time)
English (GB)
The current inputs are electrically
isolated from the current outputs, but
are applied together to the same
potential.
5
Page 6
7.4 RS-485 interface
Note
96
138
96
198
212,5
163
Note
Caution
Caution
92
+0.8
92
+0.8
> 10.5
> 30.5
English (GB)
Data transfer rate9,600 baud
•8 bits
Data format
Maximum cable
length
Further data: See 15.3 RS-485 serial
interface.
• 1 start bit
• 1 stop bit
• no parity.
2-wire cable up to 1,200 m
7.5 Dimensions
Fig. 2Control panel enclosure Conex DIS-2Q
8. Installation
8.1 Transport and storage
• Transport the device carefully.
• Do not drop the device!
• Store at a dry and cool location.
8.2 Unpacking
1. Check the device for damage.
2. Install the device as soon as possible after
unpacking.
3. Do not install or connect damaged devices!
Retain packing material or dispose of it
according to local regulations.
8.3 Installation requirements
• Dry room
• room temperature: 0-50 °C
• vibration-free location.
If you do not observe the installation
requirements, the device may be
damaged! The measurements may not
be correct!
8.4 Installation in control panel
TM03 7056 1213
Fig. 3Conex DIS-2Q in wall mounting housing
6
Fig. 4Control panel enclosure Conex DIS-2Q
TM03 7055 1213
1. Make an opening 92 + 0.8 mm x 92 + 0.8 mm in
the control panel.
2. Slip on the supplied gasket.
3. Insert the Conex DIS-2Q into the opening from
the front.
Do not damage the gasket!
The gasket must be fitted exactly!
1. Hook the clamps into the tightening cones on the
sides at the top and bottom.
2. Secure the device from the rear using a
screwdriver.
TM03 7057 1213
Page 7
8.5 Installation in wall housing
Caution
Caution
Caution
Note
The plastic housing is designed for the
Conex DIS-2Q controller and is very easy to install
and service.
– 300-115 (91835231) for one Conex DIS-2Q
controller
– 300-114 (95709720) for one Conex DIS-2Q
controller with RS-485 interface.
Technical data
MaterialABS
Enclosure classIP65
Complete with four cable glands
Warning
Switch off the power supply before
installing!
1. Loosen the four fastening screws of the front
panel.
2. Remove the front panel.
3. Insert the device from the front.
4. Hook the clamps into the tightening cones on the
sides at the top and bottom.
5. Secure the device from the rear using a
screwdriver.
6. When the front panel is mounted, plug the device
onto the base plate.
7. Screw the front panel into the wall housing.
Enclosure class IP65 is only
guaranteed if the transparent cover is
closed and the appropriate cable
glands or dummy caps are fitted.
9. Electrical connection
Warning
Disconnect the mains voltage before
connecting the power supply cable and
the relay contacts!
Observe the local safety regulations!
Protect the cable connections and
plugs against corrosion and humidity.
Before connecting the power supply
cable:
Check that the mains voltage specified
on the type plate correlates with the
local conditions!
An incorrect mains voltage may
destroy the device!
To ensure electromagnetic
compatibility (EMC):
Input and current output cables must
be shielded.
Connect the shielding to the shield
ground on one side.
Refer to the connection diagram! Input,
current output and mains cables must
be in separate cable channels.
Unused terminals remain open.
1. Connect the cables used to the terminals
according to the Conex DIS-2Q terminal
assignment.
English (GB)
7
Page 8
9.1 Terminals
1 2 3 4 5 6 7 8 9
10 11 12 13 1415 16 17 18 19 20 21 22 2324 25 26
27 28 29 30 31 32
PE
SP 1SP 2AlarmL1 N PE
H2O
mA 1
mA 2
AA
+
-
+
-
C
RS 485
mA 1
+
-
mA 2
+
-
AA
100 %
0 %
B
English (GB)
Fig. 5Terminals Conex DIS-2Q
Pos.Description
External inputs
mA 1Current input 1 (measured variable)
mA 2Current input 2 (disturbance variable or command variable)
Outputs
mA 1Current output 1 (control signal for SP 1)
mA 2Current output 2 (position of feedback potentiometer or control signal for SP 2)
0 % / 100 %Feedback potentiometer
H2OWater sensor or potential free output for stopping control
Potential free relay outputs
SP 1Set point 1
SP 2Set point 2
AlarmAlarm
Power supply
PEProtective earth conductor
L1Phase
NNeutral conductor
TM03 7058 1213
8
Page 9
9.1.1 Cable types and length
Caution
Caution
Caution
Caution
Caution
Cable Conductors
A21,000Single
B31,000Single
C21,200Single
Max. length
[m]
Screen
9.2 Power supply connection
1. Connect the plugs to the rear of the device.
2. Ensure correct orientation.
3. Connect the protective earth conductor (PE) to
terminal 26.
4. Connect the neutral conductor (N) to terminal 25.
5. Connect phase (L1) to terminal 24.
6. Switch the device on and off by switching the
power supply on and off accordingly.
The device itself does not feature a separate on/off
switch.
9.3 Current inputs and outputs
9.3.1 Current input 1 (measured value)
The signal from a measuring amplifier or transmitter
which determines the actual value of the measured
variable is connected to current input 1.
Make sure that the polarity of the
current input is correct!
Maximum load: 50
1. Connect the + conductor to terminal 2.
2. Connect the - conductor to terminal 1.
3. Connect the screen to earth (PE) at one end.
9.3.2 Current input 2 (disturbance variable or
command variable)
The signal from a measuring amplifier or transmitter
which specifies the disturbance variable or command
variable is connected to this current input.
Make sure that the polarity of the
current input is correct!
Maximum load: 50
1. Connect the + conductor to terminal 4.
2. Connect the - conductor to terminal 5.
3. Connect the screen to earth (PE) at one end.
Ω
.
Ω
.
9.3.3 Current output 1 (measured value)
Current 1 output outputs the displayed measured
value as an analog current (0 (4) to 20 mA).
Use of current signal:
• As input signal for another indicator.
Make sure that the polarity of the
current output is correct!
Maximum load: 400
1. Connect the + conductor to terminal 6.
2. Connect the - conductor to terminal 7.
3. Connect the screen to earth (PE) at one end.
9.3.4 Current output 2 (position of feedback
potentiometer)
Current output 2 outputs the position of the feedback
potentiometer of the final control element as an
analog current (0 (4) to 20 mA).
Use of current signal:
• As input signal for another indicator
Make sure that the polarity of the
current output is correct!
Maximum load: 400
1. Connect the + conductor to terminal 13.
2. Connect the - conductor to terminal 14.
3. Connect the screen to earth (PE) at one end.
Ω
.
Ω
.
9.4 Feedback potentiometer of the final
control element
Minimum resistance of feedback
potentiometer: 500
1. Connect terminal 9 to the "Start" connection
(0 %).
2. Connect terminal 10 to the "End" connection
(100 %).
3. Connect terminal 8 to the "Wiper" connection.
4. Connect the screen to earth (PE) at one end.
Ω
.
English (GB)
9
Page 10
9.5 Relay outputs
Note
Caution
+
-
R
C
ACDC
English (GB)
The connection of the relay outputs
depends on the application and the
final control elements used.
Therefore consider the connections
described below as guidelines.
See 15.2 Application examples of
different output signals and final
control elements and the
documentation of the final control
element.
With inductive loads (also relays and contactors),
interference suppression is necessary. If this is not
possible, protect the relay contacts using a
suppressor circuit as described below.
• With AC voltage:
Current up to Capacitor CResistor R
60 mA10 nF, 275 V390 Ω, 2 W
70 mA47 nF, 275 V22 Ω, 2 W
150 mA100 nF, 275 V47 Ω, 2 W
1.0 A220 nF, 275 V47 Ω, 2 W
• With DC voltage: Connect the free-wheeling
diode in parallel to the relay or contactor.
Provide the relay outputs with a
corresponding backup fuse!
Fig. 6Suppressor circuit, DC/AC
9.5.1 SP 1 (as N/O contact)
1. Connect terminal 16 to the power supply terminal
for L1 of the first final control element.
2. Connect terminal 17 to the power supply
cable L1.
9.5.2 SP 2 (as N/O contact)
1. Connect terminal 19 to the power supply terminal
for L1 of the first final control element.
2. Connect terminal 20 to the power supply
cable L1.
9.5.3 Alarm relay
1. Connect terminal 21 to the power supply terminal
for L1 of the alarm unit.
2. Connect terminal 22 to the power supply
cable L1.
10
TM03 7209 4513
Page 11
10. Operation
Note
9
IDM
5
10
8687
1
2
3
4
Conex DIA-1
Man
Cal
OKEsc
Alarm
Conex DIA-1
Man
Cal
OKEsc
Alarm
Conex DIS-2Q
Conex DIS-2Q
10.1 Function
Conex DIS-2Q is a configurable, microprocessorbased controller for exact control of any measured
variables. It can therefore be used for many tasks
associated with measuring and control technology.
10.1.1 Application example
The controller is used e.g. in conjunction with other
Grundfos products to control the dosing of chlorine
and to correct the pH value.
This is only one of a multitude of
possible applications.
See 15.2 Application examples of
different output signals and final
control elements
English (GB)
Fig. 7Application example
T
he complete measuring and control system comprises:
Pos.Description
1Measuring cell AQC for chlorine and pH
2Water sensor
3Water sampler
4Dirt trap
5Electromagnetic flowmeter
6Conex DIA measuring amplifier and controller for pH
7Conex DIA measuring amplifier and controller for chlorine
8Conex DIS-2Q controller
9Gas dosing unit with servomotor
10Dosing pump with servomotor
TM03 7061 1213
11
Page 12
10.1.2 Chlorine control principle
English (GB)
• The water is sampled and passed through the
measuring cell.
• An electric current is generated in the measuring
cell:
– In the µA range.
– Proportional to the concentration of chlorine.
– The measuring cell is controlled resistant to
interference by a local potentiostat.
• The Conex DIA measuring amplifier for chlorine:
– Amplifies the current.
– Calculates the concentration using the
calibration parameters.
– Indicates the concentration as a digital value.
– Outputs this value as a signal of 0 (4) to 20 mA
via current output 1.
• The electromagnetic flowmeter:
– Measures the water flow.
– Outputs this value as a signal of 0 (4) to 20 mA,
• The Conex DIS-2Q controller:
– Calculates the manipulated variable signal
from the measured concentration of chlorine
and the signal from the electromagnetic
flowmeter.
– Controls the servomotor of the gas dosing unit.
10.1.3 pH control principle
• The water is sampled and passed through the
measuring cell.
• The pH combination electrode generates a
potential.
• The Conex DIA measuring amplifier for pH:
– Amplifies the potential.
– Calculates the potential using the calibration
parameters.
– Indicates the pH as a digital value.
– Outputs this value as a signal of 0 (4) to 20 mA
via current output 1.
• The Conex DIS-2Q controller:
– Calculates the manipulated variable signal
from the measured pH value.
– Controls the servomotor of the dosing pump.
12
Page 13
10.2 Controls and displays
123
4
5
6
78
9
10
11
+100 %
+75 %
+50 %
+25 %
0 %
-100 %
-75 %
-50 %
-25 %
0 %
Fig. 8Front of Conex DIS-2Q
Pos. Description
Control elements
• LEDs to display the control deviation:
The combination of illuminating and
flashing LEDs indicates the magnitude of
the deviation (See Fig. 9 Control
3
deviation (% of Xp))
• Option: Deviation of switching point 1
or 2.
• LED strip indicator:
9
• Indication of selected function.
10 • Alarm LED.
11 • Display.
Operator keys
"Up" key
1
• Manual activation of relay 1.
• LED indicating status of relay 1.
"Down" key
2
• Manual activation of relay 2.
• LED indicating status of relay 2.
If the keys "Up" and "Down are" pressed
simultaneously, the alarm relay is activated.
Pos. Description
4
5
6
7
8
TM03 7062 1213
"Man" key
• Switch between automatic and manual
mode.
• LED indicating automatic or manual
mode.
– Illuminates in automatic mode.
"-" key
• Reduce value to be set.
"Save" key
• Save value to be set.
"Function" key
• Switch to next function.
"+" key
• Increase value to be set.
English (GB)
TM03 7063 1213
Fig. 9Control deviation (% of X
)
p
13
Page 14
10.3 Operating the controller
Note
n+1
M
CODE
SP 1
SP 2
XP
TN (s)
TV (s)
s
n+1n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+1
LED
1st level
2nd level
3rd level
Display measured
value (actual value)
in %.
Display and set code
functions.
Enter code number.
Display and set
hysteresis.
Display and set
device number for
RS-485.
Display and set
switching point 1.
Display and set pulse
frequency for
switching point 1.
Transmit alarms via
RS-485.
Display and set
switching point 2.
Display and set pulse
frequency for
switching point 2.
Display and set X
p.
Display and set
interpulse period.
Display and set T
n.
Display and set
actuating time.
Display and set T
v.
Display manipulated
variable.
Set ratio for ratio
controller or
disturbance variable.
Display and adjust
position of feedback
potentiometer.
Display and set
maximum dosing
time.
Display and set
minimum pulse length.
English (GB)
This combination means: Keep the first key pressed and then briefly press the
second key.
14
TM03 7064 1213
Page 15
10.3.1 Basic settings for the controller functions
Note
All parameters are factory-set to zero. A setting is always required prior to startup.
See 10.3.6 Summary of code functions and 15.2 Application examples of different output
Hysteresisa.r.a.r.a.r.a.r.a.r.a.r.
Interpulse period -a.r.---a.r.
Actuating time000a.r.00
Minimum pulse
width
Required code
functions
*)
"-": without function (no setting required).
**)
"a.r.": setting as required.
***)
Switch off with disturbance variable feedforward or ratio control as they require feedback of positioning
angle.
0a.r.a.r.a.r.1 seca.r.
***)
6, 8, 10NoneNone
18
(without
feedback of
positioning
angle)
None
3, 4, 8, 9, 10,
11, 17 ( with
feedback of
positioning
angle)
The following applies to all types of controller:
• Use as ratio controller:
– Switch on code function 22 in addition.
• Use as controller with disturbance value
feedforward:
– Switch on code function 14 in addition.
English (GB)
15
Page 16
10.3.2 Setting and displaying codes
XXX
086
+
-
Currently set
code
Settings can now be
modified.
XXX
086
+
-
Currently set
code.
Set a number
not equal to 086.
Device is protected.
XX.X
%
Measured value is
displayed.
Note
XX.X
%
00
00
00
+
+ +
01
-
+
02
-
+
+++
03
-
+
n+1
Lowest
function that is
switched on.
Code number
+: Switch on
function.
-: Switch off
function.
+: Switch on
function.
-: Switch off
function.
+: Switch on
function.
-: Switch off
function.
English (GB)
The code function is used to protect the device
against unintentional or unauthorised adjustment.
• If settings on the device are to be changed:
Fig. 10 Code setting
• If the device is to be protected against
unauthorised adjustment:
10.3.4 Switching the code functions on and off
TM03 7066 1213TM03 7067 1213TM03 7069 1213
Fig. 11 Code setting
10.3.3 Reading measured value (actual value)
Fig. 12 Actual value
16
TM03 7068 1213
Fig. 13 Switching code functions
The triangle in the display indicates the
second level.
Page 17
10.3.5 Scanning the active code functions
01
+
05
02
......
XX.X
%
n+1
+
+
Only functions that
are on are
displayed.
Fig. 14 Scanning code numbers
10.3.6 Summary of code functions
No.
Control direction of switching point 1
Downward control
SP 1 is the upper limit and the relay is
OFF
1
activated when the actual value
exceeds the setpoint.
Upward control
SP1 is the lower limit and the relay is
ON
activated when the actual value falls
below the setpoint.
Control direction of switching point 2
Upward control
SP 2 is the lower limit and the relay is
OFF
2
3
4
activated when the actual value falls
below the setpoint.
Downward control
SP 2 is the upper limit and the relay is
ON
activated when the actual value
exceeds the setpoint.
Dosing time monitoring of switching point 1.
OFF
ON
Dosing time monitoring of switching point 2.
OFF
ON
Alarm when maximum dosing time is
overrun.
No alarm when maximum dosing time
is overrun.
Alarm when maximum dosing time is
overrun.
No alarm when maximum dosing time
is overrun.
No.
Alarm relay
Alarm relay is energised permanently
OFF
5
on alarm.
Alarm relay is energised for
approximately 1 second (momentary
ON
pulse), e.g. to trigger an alarm
English (GB)
recorder.
Proportional action control for switching
point 1
6
7
TM03 7070 1213
Switching point 1 with proportional
OFF
action control.
Switching point 1 without proportional
ON
action control.
Proportional action control for switching
point 2
Switching point 2 with proportional
OFF
action control.
Switching point 2 without proportional
ON
action control.
Integral action control for switching point 1
Switching point 1 with integral action
OFF
8
control.
Switching point 1 without integral
ON
action control.
Integral action control for switching point 2
9
control.
Switching point 2 without integral
ON
action control.
Switching point 2 with integral action
OFF
Differential action control for switching point 1
Switching point 1 with differential
OFF
10
action control.
Switching point 1 without differential
ON
action control.
Differential action control for switching point 2
11
action control.
Switching point 2 without differential
ON
action control.
Switching point 2 with differential
OFF
Signal of current input 1 (actual value)
12
OFF Signal 0 to 20 mA.
ON Signal 4 to 20 mA.
Signal of current output 2 (disturbance
variable or command variable)
13
OFF Signal 0 to 20 mA.
ON Signal 4 to 20 mA.
17
Page 18
English (GB)
No.
Disturbance variable feedforward
14
15
16
17
18
19
20
21
Without disturbance variable
OFF
feedforward.
ON With disturbance variable feedforward.
Enabling of third operator level
OFF Third operator level disabled.
Third operator level enabled (a colon
ON
flashes in display)
Inversion of disturbance variable
OFF Disturbance variable not inverted.
ON Disturbance variable inverted.
Controller configuration
Device operates as two two-position
OFF
controllers for SP 1 and SP 2 (if code
function 18 is also OFF).
Device operates as three-position
ON
controller with feedback of positioning
angle.
Controller configuration
Device operates as two two-position
OFF
controllers for SP 1 and SP 2 (if code
function 17 is also OFF).
Device operates as three-position
ON
controller without feedback of
positioning angle.
Signal of current output 1 (control output for
SP 1)
OFF Signal 0 to 20 mA.
ON Signal 4 to 20 mA.
Signal of current output 2 (position of
feedback potentiometer or control output for
SP 2)
OFF Signal 0 to 20 mA.
ON Signal 4 to 20 mA.
Function of current output 2
OFF Position of feedback potentiometer.
ON Control output for switching point 2.
No.
Controller configuration
OFF Device operates as setpoint controller.
22
23
24
Device operates as ratio controller.
ON
Setpoint is entered via current input 2.
Assignment of LEDs for display of control
deviation
LEDs indicate deviation of actual value
OFF
from SP 1.
LEDs indicate deviation of actual value
ON
from SP 2.
Assignment of current input 2
0 (4) mA correspond to 0 %.
OFF
20 mA correspond to 100 %.
When used as a ratio controller or
controller with disturbance variable
ON
feedforward:
Current input is assigned to a specific
range (third operator level).
18
Page 19
10.3.7 Settings for switching point SP 1
31.0 %
-
+
XX.X %
Current setpoint
Set setpoint.
Setpoint is saved.
Note
03
-
+
XX
n+1
31.0
%
Set setpoint.
Setpoint is saved.
Current setpoint
-
+
18.0
%
XX.X
%
Current
setpoint
Set setpoint.
Setpoint is saved.
• Display and set switching point SP 1.
Fig. 15 Setting switching point 1
Setting control direction for switching point 1
• Select code function 1:
– OFF: The relay is activated when the actual
value exceeds the setpoint.
– ON: The relay is activated when the actual
value falls below the setpoint.
Setting dosing time monitoring for switching
point 1
• Select code function 3:
– OFF: Alarm when maximum dosing time is
overrun.
– ON: No alarm when maximum dosing time is
overrun.
Selecting proportional action control for
switching point 1
• Select code function 6:
– OFF: Switching point 1 with integral action
control.
– ON: Switching point 1 without integral action
control.
Selecting integral action control for switching
point 1
• Select code function 8:
– OFF: Switching point 1 with integral action
control.
– ON: Switching point 1 without integral action
control.
Selecting differential action control for switching
point 1
• Select code function 10:
– OFF: Switching point 1 with differential action
control.
– ON: Switching point 1 without differential action
control.
Displaying and setting pulse frequency for
switching point 1
Range of adjustment: 0.1 (correlates with 10 pulses/
hour) to 72 (correlates with 7,200 pulses/hour).
If 0 is set as the pulse frequency, the
device operates as an interpulse
controller.
TM03 7071 1213
Fig. 16 Setting setpoint for switching point 1
10.3.8 Settings for switching point 2
• Display and set switching point 2.
Fig. 17 Setting switching point 2
Setting control direction for switching point 2
• Select code function 2:
– OFF: The relay is activated when the actual
value falls below the setpoint.
– ON: The relay is activated when the actual
value exceeds the setpoint.
Setting dosing time monitoring for switching
point 2
• Select code function 4:
– OFF: Alarm when maximum dosing time is
runover.
– ON: No alarm when maximum dosing time is
runover.
English (GB)
TM03 7072 1213TM03 7073 1213
19
Page 20
Selecting proportional action control for
Note
03
-
+
n+1
31.0
%
XX
Current
setpoint
Set setpoint.
Setpoint is saved.
Note
Hysteresis
SP 1
SP 2
Hysteresis
1/2 hysteresis
1/2 hysteresis
1/2 hysteresis
1/2 hysteresis
English (GB)
switching point 2
• Select code function 7:
– OFF: Switching point 2 with proportional action
control.
– ON: Switching point 2 without proportional
action control.
Selecting integral action control for switching
point 2
• Select code function 9:
– OFF: Switching point 2 with integral action
control.
– ON: Switching point 2 without integral action
control.
Selecting differential action control for switching
point 2
• Select code function 11:
– OFF: Switching point 2 with differential action
control.
– ON: Switching point 2 without differential action
control.
10.3.9 Displaying and setting hysteresis
The hysteresis is set for both switching points together.
Range of adjustment: 0 to 50 %.
Distribution of hysteresis:
Displaying and setting pulse frequency for
switching point 2
Range of adjustment: 0.1 (correlates with 10 pulses/
hour) to 72 (correlates with 7,200 pulses/hour).
If 0 is the pulse frequency, the device
operates as an interpulse controller.
Fig. 18 Setting setpoint for switching point 2
TM03 7074 1213
20
Fig. 19 Hysteresis
TM03 7075 2208
Page 21
Fig. 20 Setting hysteresis
Note
18.0 %
XXX %
086
n+1
-
+
Current
setpoint
Set setpoint.
Setpoint is saved.
018 %
-
+
XXX %
Current
setpoint
Set setpoint.
Setpoint is saved.
Note
Note
134
-
+
XXX
Current
setpoint
Set setpoint.
Setpoint is saved.
178
-
+
XXX
Current
setpoint
Set setpoint.
Setpoint is saved.
10.3.10 Displaying and setting proportional band
Range of adjustment: 0 to 500 %.
If 0 is the proportional band, the device
operates as a limit contact sensor.
10.3.11 Displaying and setting reset time
Range of adjustment: T
If the reset time is 0, the device
operates as a proportional action
controller (only P action).
This is not possible if the device is to
be used as a three-position step
= 0 to 1,999 s.
n
controller.
TM03 7076 1213
Fig. 22 Setting reset time
10.3.12 Displaying and setting derivative action
time
Range of adjustment: T
If the derivative action time is 0, the
device operates as a proportional
action controller (only P action) or as a
= 0 to 500 s.
v
PI controller.
English (GB)
TM03 7078 1213
Fig. 21 Setting proportional band
TM03 7077 1213
TM03 7079 1213
Fig. 23 Setting derivative action time
21
Page 22
10.3.13 Displaying and setting interpulse period
Note
Note
10
XX
042
%
n+1
-
+
Current
setpoint
Set setpoint.
Setpoint is saved.
000
XXX
005
n+1
-
+
Current
setpoint
Set setpoint.
Setpoint is saved.
0.5
X.X
008
n+1
-
+
Current
setpoint
Set setpoint.
Setpoint is saved.
134
-
+
XXX
Current
setpoint
Set setpoint.
Setpoint is saved.
English (GB)
Range of adjustment: 1 to 99 s.
If the pulse frequency is 0, the device
operates as an interpulse controller.
Fig. 24 Setting interpulse period
10.3.14 Displaying and setting actuating time
Range of adjustment: 1 to 240 s.
If you enter an actuating time, the
device operates as a three-position
step controller.
10.3.15 Displaying and setting minimum pulse
width
Range of adjustment: 0 to 9.9 s.
Fig. 26 Setting minimum pulse width
TM03 7080 1213
10.3.16 Settings for the alarm relay
Selecting operating mode for alarm relay
• Select code function 5:
– OFF: Alarm relay is energised permanently on
alarm.
– ON: Alarm relay is energised for approximately
1 second (momentary pulse, e.g. to trigger an
alarm recorder).
Displaying and setting maximum dosing time
TM03 7082 1213TM03 7083 1213
Fig. 25 Setting actuating time
22
Fig. 27 Setting maximum dosing time
TM03 7081 1213
10.3.17 Set current input 1 (measured value)
Select signal
• Select code function 12:
– OFF: Signal 0 to 20 mA.
– ON: Signal 4 to 20 mA.
Page 23
10.3.18 Set current input 2 (disturbance variable/
1:5.0
%
0:21
n+1
-
+
n+1
0:00
%
M2
X:XX
%
M2
-
-
+
Y:YY
%
M2
+
Set start-of-scale
setpoint
(correlates with
0 (4) mA).
Save start-of-scale
setpoint.
Save full-scale
setpoint.
Set full-scale
setpoint
(correlates with
20 mA).
XX.X
%
The positioning angle is displayed
0:04 %
-
0:00 %
Lower setpoint is set to 0 %.
command variable)
Selecting signal
• Select code function 13:
– OFF: Signal 0 to 20 mA.
– ON: Signal 4 to 20 mA.
• Assign current input 2 to range 0-100 %.
– Switch off code function 24: 0 (4) mA
corresponds to 0 % and 20 mA corresponds to
100 %.
Assigning current output 2 to a freely selectable
range
• Switch on code functions 14, 24 and 15.
– A colon flashes in the display.
10.3.19 Setting current output 1 (control output
for SP 1)
Selecting signal
• Select code function 19:
– OFF: Signal 0 to 20 mA.
– ON: Signal 4 to 20 mA.
10.3.20 Setting current output 2
Selecting function of current output 2
• Select code function 21:
– OFF: Position of feedback potentiometer.
– ON: Control output for switching point 2.
Selecting signal
• Select code function 20:
– OFF: Signal 0 to 20 mA.
– ON: Signal 4 to 20 mA.
10.3.21 Settings for the feedback potentiometer
Reading current positioning angle
Fig. 29 Reading the position angle
Adjusting feedback potentiometer
• Switch on code function 15.
– A colon flashes in the display.
• Close the servomotor completely using the
"Down" button.
English (GB)
TM03 7085 1213TM03 7086 1213
Fig. 28 Setting current input 1
• Switch off code function 15.
TM03 7084 1213
Fig. 30 Closing servomotor
23
Page 24
• Open the servomotor completely using the "Up"
1:00 %
+
0:98 %
Upper setpoint is set to 100 %.
0:0.0
%
0:86
n+1
-
+
n+1
:01
M2
:XX
M2
Number of the
current device.
Set device
number.
Save device
number.
English (GB)
button.
Fig. 31 Opening the servomotor
• Switch off code function 15.
– The colon no longer flashes in the display.
10.3.22 Settings for RS-485 interface
Displaying and setting device number
• Switch on code function 15.
– A colon flashes in display.
TM03 7087 1213TM03 7088 1213
Fig. 32 Setting device number
• Switch off code function 15.
– The colon no longer flashes in display.
24
Page 25
Switch transmission of alarms on and off
:00
0:0.0
%
n+1
n+1
:XX
M2
:01
M2
-
+
:00
M2
Current status (00 or 01)
Alarms are not
transmitted.
Alarms are transmitted.
Save status.
Caution
X:XX
-
+
19:90
+
Current code
After approx. 30 s the
device has the factory
settings.
• Switch on code function 15.
– A colon flashes in the display.
Fig. 33 Switching transmissions of alarms
• Switch off code function 15.
– The colon no longer flashes in display.
10.3.23 Reset device to factory settings
Only use this function in case of
emergency. All device settings are lost
and must be re-entered!
Do not disconnect the device from the
power supply during resetting!
• Switch on code function 15
– A colon flashes in the display.
English (GB)
TM03 7089 1213
Fig. 34 Resetting factory settings
TM03 7090 1213
25
Page 26
11. Fault finding
Caution
English (GB)
Fault CauseRemedy
1. No display after startup.a) No supply voltage.Connect supply voltage.
b) Mains fuse is blown.Replace mains fuse.
2. Display indicates 0.a) Short-circuit in the cable between
3. Display indicates the full-scale
value.
4. Device cannot be set.a) Incorrect code set (the device is
5. Faulty control.a) Device is incorrectly
the measuring amplifier and
controller.
b) Moisture in the connectors.
a) Open-circuit in the cable between
the measuring amplifier and
controller.
protected against adjustment).
parameterised.
Check connection cable and
eliminate short-circuit.
Remove the moisture.
Check connection cable and
make connection.
Enter code 086.
Check settings and match to
local conditions.
Reset analyser to factory
settings.
12. Maintenance
The device is maintenance-free. The device must
only be repaired in the factory and by authorised
personnel.
12.1 Replacing mains fuses (wall housing)
• Mains fuse SI1:
– Backup fuse for floating contacts
– 315 mA slow-blow fuse
– order No. 96726013.
• Mains fuse SI2:
– Backup fuse for measuring amplifier
– 4 A slow-blow fuse
– order No. 96726014.
Warning
Switch off mains voltage before
opening the housing!
1. Switch off the mains voltage.
2. Loosen the screws of the junction box cover.
3. Open the junction box.
4. Replace the blown fuse.
5. Close the junction box.
Do not damage the gasket! The gasket
must fit exactly!
6. Tighten the screws of the cover.
7. Switch on the mains voltage.
13. Spare parts
Product numberComponent
96726013315 mA slow-blow fuse
967260144 A slow-blow fuse
14. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
26
Page 27
15. Appendix
Input
element
Open loop
controller
Final control
element
Controlled
variable
Disturbance
variable
Control
factor
Manipulated
variable
Input
variable
15.1 Measuring and control technology
15.1.1 Terminology
Below you find explanations on the terminology used
within the measuring and control technology.
The examples are based on dosing of chlorine:
Controlled variable
The controlled variable is the concentration of
chlorine.
Actual value of the controlled variable
The actual value of the controlled variable is the
measured concentration of chlorine in the water.
Measuring element
The measuring element is the device which is used
to measure the actual setpoint of the controlled
variable. In this case, it is the measuring cell and the
measuring amplifier.
Setpoint of controlled variable
The setpoint of the controlled variable is the required
concentration of chlorine.
Disturbance variable
The disturbance variable is everything that can
change the controlled variable e.g. impurities in the
water.
Control deviation
The control deviation is the difference between the
measured chlorine concentration and the required
chlorine concentration.
Manipulated variable
The manipulated variable is the dosed quantity of
chlorine.
Final control element
The final control element that changes the
manipulated variable e.g. a chlorine gas dosing
device or a dosing pump for chlorine bleaching
leach.
Controller
The controller is the device which calculates the
manipulated variable on the basis of the control
deviation.
Dead time
The dead time is the time between the modification
of the dosed quantity of chlorine and modification of
the measured chlorine concentration.
15.1.2 Open-loop and closed-loop control
Open-loop control
In an open-loop control, the manipulated variable is
modified independent of the result. An example is
the dosing of chlorine proportional to the flow.
A water meter as input element signals the flowing
quantity of water as input variable to the controller.
The dosed quantity of chlorine is set proportional to
the water flow. The actual concentration of chlorine
is not checked. An open-loop control is only
meaningful, if all the disturbance variables are
known and if they do not change simultaneously. The
manipulated variable can be assigned accordingly.
Automatic corrections cannot be made, if unforeseen
changes occur.
English (GB)
Fig. 35 Open-loop control
TM03 7091 1713
27
Page 28
Closed-loop control
Closed-loop
controller
Final control
element
Controlled
variable
Disturbance
variable
Control
factor
Manipulated
variable
Setpoint
Control
process
Measuring
element
Actual value of
Controlled variable
English (GB)
In a closed-loop control, the controlled variable is
measured and the result, the actual setpoint, is sent
to the controller. The actual value is compared with
the setpoint. Then the manipulated variable is
calculated in order to bring the controlled variable
back to the setpoint. Opposite to the open-loop
control, a check is constantly performed to see
whether the required result occurs. Any deviations
will be corrected. A closed-loop control is meaningful
if the disturbance variables are unknown or subject
to large variation. The closed-loop control ensures
that the setpoint is retained.
Fig. 36 Closed-loop control
TM03 7092 1713
28
Page 29
15.1.3 Design and function of a controller
1
2
3
4
5
3
4
6
7
8
...
9
101112
13
The controller calculates the manipulated variable
for the setpoint and the actual value. Based on the
setpoint and the actual value, the controller
generates an output signal which the corresponding
final control element processes.
Fig. 37 Function of a controller
Pos. Description
1Setpoint
2Actual value
3Deviation
4Manipulated variable
5Parameter settings
6Two-position
7Three-position
8Continuous
9Output signal
10Setpoint/actual value comparator
11Control function
12Output module
13Controller
The control function calculates the manipulated
variable on the basis of the deviation. The various
control actions and their corresponding parameters,
define the dependance between the manipulated
variable and the deviation.
English (GB)
TM03 7093 1613
29
Page 30
15.1.4 Control actions and parameters
P
X
p
P
t
0
Manipulated variable
Manipulated variable
Deviation
Time
Note
English (GB)
Step-forced response is theoretically used to
characterise the various control actions. Step-forced
response refers to the response of the controlled
variable calculated by the controller if the deviation
suddenly assumes or retains a specific value.
The characteristic parameters of the various control
actions depend on the step-forced response. In the
diagrams below, the deviation occurs at the time to
and then remains constant.
The diagrams below are essential for defining how
the parameters are used in a theoretical way as they
assume that the controlled variable does not react to
all attempts to control it.
Fig. 38 Proportional action
With a controller with a pure P action, a certain
steady-state deviation always remains since the
manipulated variable becomes smaller and smaller
as the actual value approaches the setpoint.
Once the setpoint has been reached, the
manipulated variable is also equal to zero.
As an example, the concentration of chlorine in the
water corresponds e.g. exactly to the setpoint, but a
small supply of chlorine is always necessary to
permanently retain the setpoint. This cannot be
achieved using the P controller since this outputs a
manipulated variable of zero in this case.
Integral action, proportional-plus-integral action
With an integral action (I) controller, the manipulated
value increases linearly with the deviation.
The magnitude of the deviation linearly influences
the positioning speed. With the P controller, the
magnitude of the deviation linearly influences the
manipulated variable.
The upper limit is only limited by the maximum of the
final control element. Thus step-forced response of
the upper limit is a straight line increasing from zero
which changes to a horizontal line at the maximum of
the final control element.
Proportional action
With a proportional action (P) controller, the
manipulated variable is proportional to the deviation.
The range within which this applies is referred to as
the proportional band X
is limited e.g. by the maximum of the final control
element, but can also be set below this. The lower
limit is defined by the smallest signal which the
controller can recognise as a deviation. The two
diagrams below show this relationship. The diagram
on the right side illustrates the step-forced response.
See fig. 38.
Therefore a sufficiently large manipulated variable is
still generated close to the setpoint and there is no
steady-state deviation. In the case of very high
deviations, the manipulated variable may be too
small at the beginning and thus the controller is too
slow.
For that reason a PI controller is often used in
practice. A PI controller is a combination of a P and I
controller.
When a deviation occurs, a manipulated variable
corresponding to X
increases with time. The reset time Tn can be
obtained from the corresponding diagram. The reset
time defines the slope of the straight line and thus
the speed with which the control signal increases.
The longer the reset time, the slower the control
signal increases with time.
= ∞ , a pure P action is present.
If T
n
In the setting of Conex DIS-2Q, Tn = ∞
is often printed as T
reasons.
. The upper limit of this band
p
is immediately generated which
p
= 0 for technical
n
TM03 7094 1613
30
Page 31
English (GB)
t
0
I
max.
t
0
PI
T
n
P
I
max.
t
t
Manipulated variable
Manipulated variable
Time
Time
action
action
t0T
n
P
I
D
max.
Tv /4
PID
t
0
D
t
t
Manipulated variable
Manipulated variable
Time
Time
action
action
action
t
SP
Manipulated variable
Time
Fig. 39 Integral action
Differential action, PID action
With a differential action (D) controller, a deviation
initially generates a very high manipulated variable
which rapidly decays. In theory, the step-forced
response is an infinitely high "needle function" since
it only reacts to a change in the deviation. In reality,
the magnitude of the deflection depends on the
magnitude of the change in deviation. The D
controller is only used together with P and I
controllers e.g. as a PD or PID controller.
The advantage is that fast adjustments are possible
as the controlled variable changes rapidly e.g. in the
case of faults. The characteristic of the D controller
is the derivative action time T
.
v
TM03 7095 1613
Fig. 40 Differential action
15.1.5 Adaptation and error correction
When adapting the controller to the controlled
system, use the basic parameter settings gained
from experience and the response of the controlled
variable which you observed when starting up the
control loop.
• The controlled variable rapidly reaches the
setpoint without overshoots:
– In this case the controller is optimally set.
Fig. 41 Optimally set controller
• The controlled variable oscillates around the
setpoint:
– The reset time T
is too small.
n
TM03 7096 1613TM03 7097 1613
31
Page 32
English (GB)
SP
t
Manipulated variable
Time
SP
t
Manipulated variable
Time
SP
t
Manipulated variable
Time
SP
t
Manipulated variable
Time
t
1
2
Fig. 42 T
• The controlled variable reaches the setpoint very
slowly:
– The reset time T
Fig. 43 T
• The controlled variable exceeds the setpoint and
then reaches it very slowly:
– The proportional band X
Fig. 44 X
• The controlled variable reaches the setpoint very
slowly or with a jump:
– The proportional band X
too small
n
too large
n
too small
p
is too large.
n
is too small.
p
is too large.
p
TM03 7098 1613TM03 7099 1613TM03 7100 1613
Fig. 45 X
too large
p
15.1.6 Control modes for dosing applications
Proportional control
The purpose is to chlorinate a flow of water
uniformly.
Fig. 46 Chlorine dosing
Pos. Description
1Water flow
2Quantity of dosed chlorine
If the water quality is constant, it is not necessary to
check the result as a specific quantity of dosed
chlorine results in a specific excess of chlorine.
Therefore this is an open-loop control. If the flow of
water is constant, an open-loop control is
unnecessary as the gas dosing unit is simply set to
the required dosing quantity.
However, this is not possible if the flow of water
varies. Then you must control the dosed quantity
according to the amount of flowing water:
TM03 7101 1613TM03 7102 1613
32
Page 33
Fig. 47 Proportional control
M
CODE
SP 1
SP 2
XP
TN (s)
s
CONEX DIS-2Q
IDM
TV (s)
Open-loop
controller
Dosing unit with
servomotor
Flowmeter
Conex
DIA-1
Ma
n
Ca
l
OKEs
c
Alar
m
Measuring amplifier
and closed-loop
controller
Dosing unit with
servomotor
Swimming pool
Measuring
cell
Conex
DIA-1
Ma
n
Ca
l
OKEs
c
Alar
m
M
CODE
SP 1
SP 2
XP
TN (s)
s
CONEX DIS-2Q
TV (s)
IDM
Flowmeter
Dosing unit with
servomotor
Measuring
cell
Closed-loop
controller
Measuring amplifier
pH
Conex
DIA-1
Man
Cal
OK
Esc
Alarm
pH
Water to be neutralised.
pH electrode and
temperature
sensor
Measuring amplifier
and controller
Dosing pump for
leach
Dosing pump for
acid
Setpoint control
The purpose is e.g. to keep the excess chlorine in
the swimming pool at a constant value, the setpoint.
To do this, constantly measure the excess chlorine in
the water. The chlorination of the supplied water is
influenced accordingly.
Fig. 48 Setpoint control
Proportional control with disturbance variable
feedforward
The purpose is to chlorinate a flow of water
uniformly. A purely proportional control is not
possible if the water quality varies greatly since the
same dosing quantities do not necessarily result in a
uniform excess of chlorine. Therefore the
concentration of chlorine is also measured.
A controller processes the two signals into the
manipulated variable:
• The flowing quantity of water which results in a
specific quantity of dosed chlorine.
• The measured concentration of chlorine with
which the quantity of dosed chlorine proportional
to the flow is varied upwards or downwards.
English (GB)
TM03 7103 1613TM03 7104 1613
TM03 7105 1613TM03 7106 1613
Fig. 49 Proportional control with disturbance
Dual setpoint control with acid and leach
The purpose is to retain the pH value in the water at
a specific value. If the pH value increases or
decreases as a result of the disturbance variables,
acid or leach must be dosed depending on the
situation. Therefore you must be able to control the
two dosing pumps alternately.
Fig. 50 Dual setpoint control
33
Page 34
15.2 Application examples of different
Note
t
SP 1
Off
On
{
Hysteresis
Chlorine concentration
Switching status of the pump.
time
English (GB)
output signals and final control
elements
The purpose of the output module of the controller is
to convert the calculated manipulated variable into a
signal which can be processed by a corresponding
final control element. If you use a dosing pump with
a current input, it must be controlled differently from
e.g. a gas dosing unit with servomotor.
As the values of the different parameters depend on
the type of control element, you must consider
different parameters for each of these output signals.
Always adapt the parameter settings of
the following examples to the local
conditions!
15.2.1 Limit contact controller
Application
• Upward control direction of chlorine
concentration using chlorine bleaching leach.
• Control of dosing pump by power supply.
Description
• The actual value of the required chlorine
concentration falls below the setpoint:
– Dosing pump for chlorine bleaching leach is
switched on.
• The actual value of the required chlorine
concentration exceeds the setpoint:
– Dosing pump for chlorine bleaching leach is
switched off.
• The hysteresis
– Widens the setpoint into a band.
– Prevents unsteady switching on and off of
dosing pump.
Fig. 51 Limit contact controller
Parameter settings
SP 1Required chlorine concentration, e.g. 55 %.
Pulse frequency for SP 10
SP 2-
15.2.6 Dual two-position pulse frequency controller
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
SP 1
SP 2
pH value
Deviation from
setpoint
Switching status of
the acid pump
(individual dosing
strokes).
Switching status of
the leach pump
(individual dosing
strokes).
English (GB)
Application
• Setpoint control of pH value using acid and
leach.
• Control of dosing pumps via contact input.
Description
• Set a pH value of 7.00.
• Set switching point 1 slightly above this value.
• Set switching point 2 slightly below this value.
Never set the two switching points to the same
value; in this case acid and leach are constantly and
alternately dosed. This does not improve the result, it
merely leads to an unnecessarily high consumption
of chemicals.
• The actual value of switching point 1 exceeds the
setpoint:
– Dosing pump for acid carries out individually
controlled dosing strokes.
• The actual value of switching point 2 falls below
the setpoint:
– Dosing pump for leach carries out individually
controlled dosing strokes.
• The measured value deviates from the respective
switching point:
– Frequency of dosing strokes of the respective
pump increases
– If the deviation is large, the respective pump
runs continuously with maximum frequency of
dosing strokes.
Fig. 61 Dual two-position pulse frequency controller
44
TM03 7114 1613
Page 45
Parameter settings
15 16 17 18 19 20 21 22 2324 25 26
L1 N PE
L1 N PE
L1 N PE
1
2a
3
4
4
2b
Required pH value: e.g. pH 7.00.
SP 1Above the required pH value, e.g. 52 % (correlates with pH 7.28).
Pulse frequency for SP 1
72 (maximum value (correlates with 7,200 strokes per hour).
The dosing capacity of the pump is then fully utilised.
SP 2Below the required pH value, e.g. 48 % (correlates with pH 6.72).
Pulse frequency for SP 2
72 (maximum value (correlates with 7,200 strokes per hour).
The dosing capacity of the pump is then fully utilised.
According to local conditions, e.g. 100 %
X
p
• Higher setting results in smaller control steps.
• Lower setting results in larger control steps.
According to local conditions, e.g. 300 sec
1Free relay outputs
2aDosing pump for leach
2bDosing pump for acid
3Power supply
4Contact input
English (GB)
Fig. 62 Connection diagram for dosing pump,
contact input
TM03 7115 1613
45
Page 46
15.2.7 Dual two-position interpulse controller
Off
On
Off
On
Off
On
{
Off
On
Off
On
Off
On
{
Off
On
Off
On
Off
On
Off
On
SP 1
SP 2
pH value
Deviation from
setpoint
Switching status of the
acid pump.
Switching status of the
leach pump.
Interpulse period
Interpulse period
English (GB)
Application
• Setpoint control of pH value using acid and
leach.
• Control of dosing pumps by power supply.
Description
• Set a pH value of 7.00.
• Set switching point 1 slightly above this value.
• Set switching point 2 slightly below this value.
Never set the two switching points to the same
value; in this case acid and leach are constantly and
alternately dosed. This does not improve the result, it
merely leads to an unnecessarily high consumption
of chemicals.
• The actual value of switching point 1 exceeds the
setpoint:
– Dosing pump for acid is switched on for brief
periods.
• The actual value of switching point 2 falls below
the setpoint:
– Dosing pump for leach is switched on for brief
periods.
• The measured value deviates from the respective
switching point:
– The respective dosing pump runs longer during
the interpulse period.
– If the deviation is large, the respective pump
runs continuously.
Fig. 63 Dual two-position interpulse controller
46
TM03 7116 1613
Page 47
Parameter settings
15 16 17 18 19 20 21 22 2324 25 26
L1 N PE
L1 N PE
L1 N PE
1
2a
3
2b
Required pH value, e.g. pH 7.00.
SP 1Above the required pH value, e.g. 52 % (correlates with pH 7.28).
Pulse frequency for SP 10
SP 2Below the required pH value, e.g. 48 % (correlates with pH 6.72).
Pulse frequency for SP 20
According to local conditions, e.g. 100 %
X
p
• Higher setting results in smaller control steps.
• Lower setting results in larger control steps.
According to local conditions, e.g. 300 sec
• Open-loop control of dosed chlorine proportional
to the flow.
Description
A varying flow of water is to be chlorinated by a
uniform amount. The electromagnetic flowmeter
measures the flow quantity and passes it on to the
controller.
15.2.10 Three-position step controller with disturbance variable feedforward
English (GB)
Application
• Open-loop control of dosed chlorine proportional
to the flow and closed-loop control dependent on
the measured value.
• Control of dosing pump or gas dosing unit using
servomotor.
Description
A varying flow of water is to be chlorinated by a
uniform amount. The electromagnetic flowmeter
measures the flow quantity and passes it on to the
controller. The result (the chlorine concentration) is
also measured and the dosed quantity controlled
accordingly.
• When the flow of water increases:
– The servomotor moves in the direction of the
increased dosing capacity.
• When the flow of water decreases:
– The servomotor moves in the direction of the
decreased dosing capacity.
• The closed-loop control is dependent on the
measured value:
– When the chlorine concentration decreases,
the servomotor moves additionally in the
direction of the increased dosing capacity.
– When the chlorine concentration increases, the
servomotor moves additionally in the direction
of decreased dosing capacity.
Parameter settings
SP 1Required chlorine concentration, e.g. 55 %.
Pulse frequency for SP 1-
15.2.12 Continuous controller with disturbance variable feedforward
English (GB)
Application
• Open-loop control of dosed chlorine proportional
to the flow and closed-loop control dependent on
the measured value.
• Control of dosing pump or gas dosing unit via the
current input.
Description
A varying flow of water is to be chlorinated by a
uniform amount. The electromagnetic flowmeter
measures the flow quantity and passes it on to the
controller. The result (the chlorine concentration) is
also measured and the dosed quantity controlled
• When the flow of water increases:
– The current signal increases.
• When the flow of water decreases:
– The current signal decreases.
• The closed-loop control is dependent on the
measured value:
– When the chlorine concentration decreases,
the current signal is additionally increased.
– When the chlorine concentration increases, the
current signal is additionally decreased.
accordingly.
Parameter settings
SP 1Required chlorine concentration, e.g. 38 %.
Pulse frequency for SP 10
SP 2-
*)
Pulse frequency for SP 2-
e.g. 100 % (transmission ratio 1:1)
X
p
• > 100 % (transmission ratio 1: > 1)
• < 100 % (transmission ratio 1: < 1)
e.g. 300 sec
T
n
T
v
• Higher setting results in slower control.
• Lower setting results in faster control.
0
HysteresisInterpulse periodActuating time0
Minimum pulse width
1 sec - so that the relays required here do not activate
100 m. Only to be connected at one side)
– pin 3: data +.
– pin 8: data -.
The bus function of the device must be adjusted by
jumpers (in the plug).
• If the device is used as MASTER (device
number 32), carry out the following adjustment:
– jumper 4-7
• If the device is used as SLAVE (device
number 1-31), carry out the following adjustment:
– no jumpers
• If the device is used as last SLAVE (device
number 1-31), carry out the following adjustment:
– jumper 4-7
Data transfer format
– 9,600 baud
– 1 start bit
– 1 stop bit
– 8 data bits
– no parity
Software
Data transmission consists of several parts:
– the function request
– the information
– the end of the data transmission.
The data transmission starts with calling the
demanded device. The devices connected to the bus
are identified by the device number which must be
selected at the single devices.
The function request for starting a transmission is
"line feed" (LF). Then the corresponding device
number is transmitted. After that, "carriage return"
(CR) is transmitted, which always indicates the end
of a function request or data transmission.
The called device answers with the device code (see
device codes). The device code contains the type of
the device and the operating status.
If the operation mode is "automatic" and no alarm
indication is present, a Conex DIS-2Q controller
answers with code "54". If an indication is present,
the code "5C" is transmitted. Now you can read the
reason of the alarm from the corresponding list,
which can be called up with "$". Set the
corresponding bit to acknowledge the alarm.
Transmit the corresponding function number to call
the demanded function. Now the device transmits
the contents of this function as a two-digit or fourdigit binary number and again completes the
transmission with "CR". Now you can change the
settings of this function. An example of this dialog is
given below.
Operations set of the transmission
Character Hexadecimal Function
LF0A H
CR0D HInput is finished
$24 H
C43 H
H41 H
If you change a value via the interface, the
corresponding numbers are transmitted as four-digit
binary numbers without decimal point.
Read and change the switching point 1 of a
Conex DIA with the device number 00.
• Establish the connection to the device.
• Select device No. 00:
ASCII
character
LF(0AH)Line feed
00(30H, 30H) Device number
CR(0DH)Carriage return
This device is active until you select a device with a
different number.
• Answer of the selected device:
ASCII
character
00(30H, 30H) Device number
94(39H, 34H)
CR(0DH)Carriage return
The selected device is in the automatic mode, and
there are no unacknowledged alarm indications.
• Read switching point 1 from the selected device:
ASCII
character
$(24H)Select function
24(32H, 34H) Function number
CR(0DH)Carriage return
54(35H), (34H)
5C(35H), (3CH)
Hex codeFunction
Hex codeFunction
Hex codeFunction
Transmitted
hex code
Device code
Conex DIS-2Q
ASCII
character
0038
CR(0DH)Carriage return
• Change selected value (SP1) to 0.45mg/l:
ASCII
character
C002=
CR(0DH)Carriage return
• Answer of the selected device:
ASCII
character
002=
CR(0DH)Carriage return
• Call the same function again:
ASCII
character
A(41H)Call value again
CR(0DH)Carriage return
• Answer of the selected device:
Hex codeFunction
Value of the selected
function SP1 as binary
(30H, 30H,
33H, 38H)
Hex codeFunction
(43H, 30H,
30H, 32H,
3DH)
Hex codeFunction
(30H, 30H,
32H, 3DH)
Hex codeFunction
number without
decimal point:
This means 0056 and
correlates with
0.56 mg/l chlorine.
Change value.
New value of the
selected function:
002D. This means
0045 and correlates
with 0.45 mg/l
chlorine.
New value of the
function (SP1) as
binary number without
decimal point: 002D.
This means 0045 and
correlates with
0.45 mg/l chlorine.
English (GB)
ASCII
character
002=
CR(0DH)Carriage return
Hex codeFunction
New value of the
(30H, 30H,
32H, 3DH)
function: 002D.
This means 0045 and
correlates with
0.45 mg/l chlorine.
59
Page 60
Functions list
English (GB)
• General functions
Function
number
10
46Serial number of the device
47Software state (month, year)
48Manufacturing date (month, year)
06Measuring input 1 in mV
07Measuring input 2 in mV
08Measuring input 3 in mV
00Actual value in %
01Input 2 in %
02Check-back signal in %
21Code
22Setpoint SP 1
23Setpoint SP 2
24Proportional band
25Reset time
26Rate time
27
28Alarm delay time
2AHysteresis
2BPulse frequency for SP1
2CPulse frequency for SP2
2DPulse - interpulse period
2EMotor running time
2FIndication influencing variable
31Minimum pulse length
33Device number
Function
State identifier (bit-oriented alarm list
see below)
Check-back signal of the correcting
variable
• State identifier (alarm list)
BitFunction
0Dosing alarm
1
2Input control stop
3Automatic mode of controller
4Dosing alarm: change recognized
5
6Input control stop: change recognized
Automatic mode of controller: change
7
recognized
8
9
10
11
12
13
14
15No indications present
Subject to alterations.
60
Page 61
Declaration of conformity1
GB: EC declaration of conformity
We, Grundfos, declare under our sole responsibility that the product
®
Conex
DIS-2Q, to which this declaration relates, is in conformity with
these Council directives on the approximation of the laws of the EC
member states:
DE: EG-Konformitätserklärung
Wir, Grundfos, erklären in alleiniger Verantwortung, dass das Produkt
®
Conex
DIS-2Q, auf das sich diese Erklärung bezieht, mit den
folgenden Richtlinien des Rates zur Angleichung der
Rechtsvorschriften der EU-Mitgliedsstaaten übereinstimmt:
CZ: ES prohlášení o shodě
My firma Grundfos prohlašujeme na svou plnou odpovědnost,
že výrobek Conex
souladu s ustanoveními směrnice Rady pro sblížení právních
předpisůčlenských států Evropského společenství v oblastech:
FR: Déclaration de conformité CE
Nous, Grundfos, déclarons sous notre seule responsabilité, que
le produit Conex
conforme aux Directives du Conseil concernant le rapprochement
des législations des Etats membres CE relatives aux normes
énoncées ci-dessous:
– EMC Directive (2004/108/EC).
Standards used: EN 61000 6-1(3), VDE 0839 Teil 6-1(3): 2002, EN
61000 6-2(4), VDE 0839 Teil 6-2(4): 2006, EN 61326-1: 2006,
VDE 0843-20-1: 2006, EN 61010-1 :2002-08.
This EC declaration of conformity is only valid when published as part
of the Grundfos installation and operating instructions.
Pfinztal, 15 July 2014
®
DIS-2Q, na nějž se toto prohlášení vztahuje, je v
®
DIS-2Q, auquel se réfère cette déclaration, est
Ulrich Stemick
Technical Director
Grundfos Water Treatment GmbH
Reetzstr. 85, D-76327 Pfinztal, Germany
Person authorised to compile technical file and
empowered to sign the EC declaration of conformity.
Declaration of conformity
61
Page 62
Argentina
Grundfos companies
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Centro
Industrial Garin
1619 - Garin Pcia. de B.A.
Phone: +54-3327 414 444
Telefax: +54-3327 411 111
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Trg Heroja 16,
BiH-71000 Sarajevo
Phone: +387 33 713 290
Telefax: +387 33 659 079
e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo
Branco, 630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: bulgaria@grundfos.bg
ALLDOS (Shanghai) Water Technology
Co. Ltd.
West Unit, 1 Floor, No. 2 Building (T 4-2)
278 Jinhu Road, Jin Qiao Export Processing Zone
Pudong New Area
Shanghai, 201206
Phone: +86 21 5055 1012
Telefax: +86 21 5032 0596
E-mail: grundfosalldos-CN@grundfos.com
China
GRUNDFOS Pumps (Shanghai) Co. Ltd.
50/F Maxdo Centre No. 8 Xing Yi Rd.
Hongqiao Development Zone
Shanghai 200336
PRC
Phone: +86-21 6122 5222
Telefax: +86-21 6122 5333