Grundfos CIM 150 PROFIBUS DP, CIM 500 Ethernet for PROFINET IO Functional Profile And User Manual

GRUNDFOS INSTRUCTIONS
PROFIBUS and PROFINET for Digital Dosing
CIM 150 PROFIBUS DP CIM 500 Ethernet for PROFINET IO
Functional profile and user manual

English (GB)

Original functional profile and user manual.
This functional profile describes Grundfos PRIOFIBUS and PROFINET for DDA digital dosing pumps.
CONTENTS
1. General information

1.1 Hazard statements

1.2 Notes

2. Introduction
2.1 About this functional profile
2.2 PROFIBUS DP-V0
2.3 PROFIBUS DP-V1
2.4 Assumptions
2.5 Definitions and abbreviations
3. System description
4. Specifications
4.1 CIM module
4.2 CIM 150 PROFIBUS DP
4.3 CIM 500 PROFINET IO
5. PROFIBUS DP, CIM 150 setup
5.1 PROFIBUS bus topology
5.2 CIM 150 PROFIBUS module
5.3 Connecting the PROFIBUS
5.4 Setting the PROFIBUS address
5.5 Termination resistors
5.6 Status LEDs
5.7 Communication watchdog
5.8 Reaction to PLC "Stop button"
6. PROFINET IO, CIM 500 setup
6.1 Connecting the ethernet cable
6.2 Setting the Industrial Ethernet protocol
6.3 Setting up the IP addresses
6.4 Establish connection to the webserver
6.5 Status LEDs
6.6 DATA and LINK LEDs
7. Detailed description of data modules
7.1 Data types
7.2 Control module (ControlModule, module 1)
7.3 Dosing settings
7.4 Other settings
7.5 Bus settings compared to pump HMI settings
7.6 Status module (StatusModule, module 11)
7.7 Measurement data modules
7.8 Alarms and warning
7.9 Device identification (DeviceIdentification, module 40)
8. Product simulation
8.1 CIM 150 product simulation
8.2 CIM 500 Product Simulation
9. Fault finding
9.1 CIM 150
9.2 CIM 500
Page
10
10 10 13 13 14 14 17 19 20
21
21 21
22
22 22

1. General information

1.1 Hazard statements
The symbols and hazard statements below may appear in Grundfos installation and operating instructions, safety instructions and service instructions.
2
2 2
3
3 3 3 3 3
4
5
5 5 5
The hazard statements are structured in the following way:
6
6 6 6 7 7 7
1.2 Notes
7
The symbols and notes below may appear in Grundfos
7
installation and operating instructions, safety instructions and
8
service instructions.
8 8 8 9 9 9
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
Observe these instructions for explosion-proof products.
A blue or grey circle with a white graphical symbol indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with a black graphical symbol, indicates that an action must not be taken or must be stopped.
If these instructions are not observed, it may result in malfunction or damage to the equipment.
Tips and advice that make the work easier.
Read this document before installing the product. Installation and operation must comply with local regulations and accepted codes of good practice.
2

2. Introduction

2.1 About this functional profile

This functional profile describes the following modules/units:
• CIM 150 PROFIBUS DP
• CIM 500 ethernet for PROFINET IO. They are for PROFIBUS DP and PROFINET IO communication
with the Smart Digital Dosing pump, type DDA, referred to as ’DDA pump’ in this document.
Grundfos cannot be held responsible for any problems caused directly or indirectly by using information in this functional profile.

2.2 PROFIBUS DP-V0

The PROFIBUS DP interface conforms to the PROFIBUS DP-V0 standard for cyclic data transmission.
The option of setting the PROFIBUS DP address via bus is not supported as CIM 150/500 has two switches for setting the address.

2.3 PROFIBUS DP-V1

Only the diagnostic part and the extra three bytes of parameterisation data are supported. Acyclic data transmission is not supported.

2.4 Assumptions

This functional profile assumes that the reader is familiar with the commissioning and programming of PROFIBUS and PROFINET devices.

2.5 Definitions and abbreviations

ARP
Auto-MDIX
CAT5
CAT5e
CAT6
CIM Communication Interface Module.
CRC
DHCP
DNS
Enumeration List of values. GENIbus Proprietary Grundfos fieldbus standard. GENIpro Proprietary Grundfos fieldbus protocol.
Grundfos GO
H Head (pressure).
HTTP
IANA Internet Assigned Numbers Authority. IP Internet Protocol. LED Light-emitting Diode.
Local mode
MAC
Address Resolution Protocol. Translates IP addresses into MAC addresses.
Ensures that both crossover cable types and non-crossover cable types can be used.
Ethernet cable type with four twisted pairs of wires.
Enhanced CAT5 cable with better performance.
Ethernet cable compatible with CAT5 and CAT5e and with very high performance.
Cyclic Redundancy Check. A data error detection method.
Dynamic Host Configuration Protocol. Used to configure network devices so that they can communicate on an IP network.
Domain Name System. Used to resolve host names to IP addresses.
A Grundfos handheld remote control device for controlling Grundfos products via infrared or radio. Based on smart phone technology.
Hyper Text Transfer Protocol. The protocol commonly used to navigate the world wide web.
The DDA pump uses the setpoint and operating mode set with a handheld remote control (R100 or Grundfos GO Remote) or by the use of buttons on the pump.
Media Access Control. Unique network address for a piece of hardware.
Packet InterNet Groper. A software utility
Ping
QFlow rate.
Remote mode
SELV Separated or Safety Extra-Low Voltage.
SELV-E
SMA
SMTP Simple Mail Transfer Protocol.
SNTP
TCP
TCP/IP
Transmission speed
URL
UTC
UTF-8
DDA Digital Dosing Advanced.
HMI
PLC Programmable Logic Controller.
that tests the connectivity between two TCP/ IP hosts.
The DDA pump uses the setpoint and operating mode set from the fieldbus.
Separated or Safety Extra-Low Voltage with earth connection.
SubMiniature version A. Coaxial radio signal cable connection standard.
Simple Network Time Protocol. Used for clocks synchronization between computer systems.
Transmission Control Protocol. Protocol for Internet communication and Industrial Ethernet communication.
Transmission Control Protocol/Internet Protocol. Protocol for Internet communication.
Bits transferred per second, bits/s.
Uniform Resource Locator. The address used to connect to a server.
Coordinated Universal Time. The primary time standard by which the world regulates clocks and time.
Unicode Transformation Format. Character encoding.
Human Machine Interface. Display and buttons on the DDA pump.
English (GB)
3

3. System description

E-box with CIM 150 or CIM 500
GENIbus connection to DDA pump
PROFIBUS DP or
PROFINET IO
DDA pump
PROFIBUS DP or
PROFINET IO
English (GB)
The system diagram provide an overview of the two different technologies and how to connect the CIM module to the Grundfos DDA E-box that you connect to a PROFIBUS DP or PROFINET IO network.
CIM 150/500 is a communication module installed internally in the Grundfos DDA E-box using a 10-pin connection. In this setup, the E-box supplies power to CIM. See fig. 1.
For mounting of the CIM module, see the installation and operating instructions for the DDA E-box.
Fig. 1 DDA pump with E-box connected to a daisy chained
PROFIBUS/PROFINET network
TM05 2088 4611
4

4. Specifications

4.1 CIM module

General data Description Comments
Ambient humidity 30-95 % Relative, non-condensing. Operating temperature -20 °C to +45 °C Storage temperature -25 °C to +70 °C
Will be in one of these states: Off, permanently green, flashing red, permanently
GENIbus visual diagnostics LED2

4.2 CIM 150 PROFIBUS DP

The table below provides an overview of the specifications for Grundfos CIM 150. For further details, refer to the specific sections of this functional profile.
PROFIBUS DP specifications Description Comments
PROFIBUS implementation class DP-V0 Intelligent pump profile. PROFIBUS connector Screw-type terminal A, B, DGND, VP (+5 V). PROFIBUS connection type RS-485, two-wire Conductors: A, B.
Maximum cable length 100 metres at 12 Mbits/s
Slave address 1-126
Line termination On or off
Recommended cable cross-section 0.20 - 0.25 mm Supported transmission speed 9.6 Kbits/s to 12 Mbits/s Auto detected.
PROFIBUS visual diagnostics LED1
Maximum number of PROFIBUS devices at a physical network segment
32
2
red. See section 5.6 Status LEDs for PROFIBUS DP and section 6.5 Status LEDs for PROFINET IO.
Corresponds to 328 feet. See section 5.3.1 Data
transmission rates and cable length.
For DDA dosing pumps the address is selected on the pump display in the Settings menu. Address 126 is reserved for special purposes. See section 5.4 Setting the PROFIBUS address.
Set via DIP switches SW1 and SW2. See section 5.5 Termination resistors. Auto detected
AWG24 or AWG23
Off, permanently green, flashing red, permanently red. See section 5.6 Status LEDs.
Up to 125 devices if repeaters are used (physically segmented network).
English (GB)

4.3 CIM 500 PROFINET IO

The table below provides an overview of the specifications for the Grundfos CIM 500 ethernet for PROFINET IO. For further details, refer to the specific sections of this functional profile.
PROFINET IO specifications Description Comments
Application layer
Transport layer TCP Internet layer Internet protocol V4 (IPv4) Link layer ARP, Media Access Control (ethernet)
Ethernet cable
Maximum cable lenth 100 metres Corresponds to 328 feet. Transmission speed 10 Mbits/s, 100 Mbits/s Auto-detected.
Industrial Ethernet protocols PROFINET IO, Modbus TCP
DHCP, HTTP, Ping, FTP, SMTP, SNTP, PROFINET IO
Screened/unscreened, twisted-pair cables, CAT5, CAT5e or CAT6
Rotary switch in position 0.
Supports auto cable-crossover detecting (Auto­MDIX).
Selected with rotary switch, section 6.2 Setting the
Industrial Ethernet protocol.
5

5. PROFIBUS DP, CIM 150 setup

LT
LT
Master
Slave
Slave
Slave
21 3 45 67
8
9
3
1
2
5
4
English (GB)

5.1 PROFIBUS bus topology

The PROFIBUS-preferred bus topology is daisy chaining as illustrated in fig. 2. The end devices of a physical bus segment must be terminated (LT = Line Termination). Each device must have a unique physical address [1-126]. Up to 32 PROFIBUS devices can be connected to a bus segment, and by using a repeater another 32 devices can be connected. This can be repeated until the maximum number of addresses are used. Make sure that each device is connected to a proper earth potential.
Fig. 2 Example of PROFIBUS bus segment with line
termination

5.2 CIM 150 PROFIBUS module

5.3 Connecting the PROFIBUS

5.3.1 Data transmission rates and cable length
We recommend using a cable according to IEC 61158.
Example
Siemens, 6XV1 830-0EH10. Cable length
Kbits/s
9.6 1200/4000
19.2 1200/4000
45.45 1200/4000
93.75 1000/3300
187.5 1000/3300
TM04 9635 4810TM04 1699 0908
500 400/1300 1500 200/660 3000 100/330 6000 100/330 12000 100/330
Fitting the cable
See fig. 4.
1. Connect the red conductor(s) to terminal B (pos. 1).
2. Connect the green conductor(s) to terminal A (pos. 2).
3. Connect the cable screens to earth via the earth clamp (pos.
3).
For maximum safety and reliability, connect the cable screen to earth via the earth clamp, and make sure that all CIU 150 units are properly earthed via the mains supply earth-wire.
Maximum cable length
[m/ft]
Fig. 3 CIM 150 PROFIBUS module
Pos. Designation Description
1 B (RxD/TxD-P)
2 A (RxD/TxD-N)
3DGND
4VP
5SW1/SW2
6LED1
PROFIBUS terminal B (positive data signal)
PROFIBUS terminal A (negative data signal)
PROFIBUS terminal DGND (only for external termination)
+5 VDC (only for external termination)
On and off switches for termination resistors
Red and green status LED for PROFIBUS communication
TM04 1700 0908
Fig. 4 Connecting the PROFIBUS
Pos. Description
1PROFIBUS terminal B 2PROFIBUS terminal A 3 Earth clamp 4+5 VDC 5DGND
Red and green status LED for
7LED2
GENIbus communication between the CIM 150 and the
DDA pump 8 SW3 Not used for DDA 9 SW4 Not used for DDA
The power supply (pos. 4, fig. 3) must only be used for external termination.
6

5.4 Setting the PROFIBUS address

+5V
390
220
390
SW1
SW2
SW1 SW2
Select the PROFIBUS address via the menu system in the pump display.
Set the PROFIBUS address decimally from 1 to 126. The address 126 is normally used for special purposes and should not be used.
A restart of CIM 150 has to be performed for a PROFIBUS address change to take effect.
For complete overview of the PROFIBUS addresses, see section
.

5.5 Termination resistors

The termination resistors are fitted on the CIM 150 PROFIBUS module. See fig. 5.
Fig. 5 Internal termination resistors
CIM 150 has a DIP switch with two switches, SW1 and SW2, for cutting the termination resistors in and out. Figure 6 shows the DIP switches in cut-out state.

5.6 Status LEDs

The CIM 150 PROFIBUS module has two LEDs. See fig. 3.
• Red and green status LED1 for PROFIBUS communication.
• Red and green status LED2 for GENIbus communication between CIM 150 and the connected DDA pump.
LED1
Status Description
Off. CIM 150 has been switched off.
Permanently green.
Permanently red.
Flashing red.
LED2
Status Description
Off. CIM 150 is switched off.
Permanently green.
TM04 1961 1508TM04 1703 0908
Permanently red.
Flashing red.
During startup, there may be a delay of up to 5 seconds before the LED2 status is updated.
CIM 150 is ready for PROFIBUS data transmission (Data Exchange State).
CIM 150 module fault. CIM 150 does not support the connected DDA pump.
Wrong or missing PROFIBUS configuration or no contact to the PROFIBUS master.
GENIbus communication between CIM 150 and the DDA pump is OK.
CIM 150 does not support the connected DDA pump.
No GENIbus communication between the CIM 150 and the DDA pump.
English (GB)
Fig. 6 Cutting termination resistors in and out
DIP switch settings
Status SW1 SW2
Cut in ON ON Cut out OFF OFF
Undefined state
ON OFF
OFF ON
To ensure stable and reliable communication, it is important that only the termination resistors of the first and last units in the PROFIBUS network are cut in.

5.7 Communication watchdog

The state of the PROFIBUS communication watchdog can be changed with a PROFIBUS commissioning tool, for example Siemens Simatic Manager. If the watchdog is enabled, all bits in the ControlModule (see section 7.2 Control module
(ControlModule, module 1)) are automatically set to "0" if the
PROFIBUS communication is broken. As a result, the DDA pump will be set to local mode and then be
operating according to the local operating mode, local setpoint and local control mode.

5.8 Reaction to PLC "Stop button"

If the PLC is stopped by the operator, all output registers will be set to "0".
As a result, the control bit RemoteAccessReq will be cleared, and the DDA pump will be set to local mode and then be operating according to the local operating mode, local setpoint and local control mode.
7

6. PROFINET IO, CIM 500 setup

Ethernet
switch
CIM 500
CIM 500
CIM 500
CIM 500
1
2
3
8
9
4
7
5
6
English (GB)

6.1 Connecting the ethernet cable

CAUTION
Electric shock
Minor or moderate personal injury
- Connect CIM 500 only to SELV or SELV-E circuits.
Use RJ45 plugs and ethernet cable. Connect the cable shield to protective earth at both ends.
It is important to connect cable shield to earth through earth clamp or to connect cable shield to earth in the connector.
CIM 500 is designed for flexible network installation; the built-in two port switch makes it possible to daisy chain from product to product without the need of additional ethernet switches. The last product in the chain is only connected to one of the ethernet ports. Each ethernet port has its own MAC address.
Fig. 7 Example of Industrial Ethernet network

6.2 Setting the Industrial Ethernet protocol

The CIM 500 ethernet module has a rotary switch for selection of the Industrial Ethernet protocol. See fig. 9.
Fig. 9 Selecting the Industrial Ethernet protocol
Pos. Description
0 PROFINET IO (Default from factory) 1 Modbus TCP
Reserved, LED1 will be permanently red to indicate an
2..E invalid configuration
Reset to factory default Note: The rotary switch has to be set in this position for 20 seconds before CIM 500 resets to factory default.
F
During this period LED1 will be flashing red and green at the same time to indicate that a reset will occur.
TM05 6435 4711TM05 7431 1013
Every change of the rotary switch, when the module is powered on, will cause the module to restart.
TM05 7481 1013
Fig. 8 Example of ethernet connection (CIM 500)
Pos. Description Designation
1 Industrial Ethernet RJ45 connector 1 ETH1 2 Industrial Ethernet RJ45 connector 2 ETH2 3 Rotary switch for protocol selection SW1 4 Data activity LED for connector 1 DATA1 5 Link LED for connector 1 LINK1 6 Data activity LED for connector 2 DATA2 7 Link LED for connector 2. LINK2
Green and red status LED for ethernet
8
communication. Green and red status LED for internal
9
communication between module and pump.
LED1
LED2
8

6.3 Setting up the IP addresses

The CIM 500 ethernet module is by default set to a fixed IP address. It is possible to change the IP address settings from the built-in webserver.
Default IP settings used by the webserver
IP settings for Modbus TCP
Device name and IP settings for PROFINET IO
IP address:192.168.1.100 Subnet mask: 255.255.255.0 Gateway: 192.168.1.1
Must be set via the webserver
Static configuration from webserver or configuration from PROFINET IO configuration tool.

6.4 Establish connection to the webserver

You can configure the CIM 500 module using the built-in webserver. To establish connection from a PC to CIM 500, the following steps are required:
• Connect the PC and the CIM 500 module using an ethernet cable
• Configure the PC ethernet port to the same subnetwork as CIM 500, for example 192.168.1.101, and the subnet mask to
255.255.255.0. See section A.2 Web server configuration on page 26.
• Open a standard Internet browser and type 192.168.1.100 in the URL field.
• Log in to the webserver using:
LED2
Status Description
Off CIM 500 is switched off.
Flashing red
Permanently red
Permanently green
Permanently red and green
No internal communication between the CIM 500 and the Grundfos product.
CIM 500 does not support the Grundfos product connected.
Internal communication between CIM 500 and the Grundfos product is OK.
Memory fault.
English (GB)
Username Default: admin Password Default: Grundfos
Username and password may have been changed from their factory default values.
Fig. 10 CIM 500 connected to PC
You can use both ETH1 and ETH2 to establish a connection to the webserver.
You can access the webserver while the selected Industrial Ethernet protocol is active.

6.5 Status LEDs

The CIM 500 ethernet module has two status LEDs, LED1 and LED2.
See fig. 8.
• Red and green status LED1 for ethernet communication
• Red and green status LED2 for internal communication between CIM 500 and the Grundfos product.
LED1
During startup, there is a delay of up to 5 seconds before LED1 and LED2 status is updated.

6.6 DATA and LINK LEDs

The CIM 500 ethernet module has two connectivity LEDs related to each RJ45 connector. See fig. 8.
DATA1 and DATA2
These yellow LEDs indicate data traffic activity.
Status Description
Yellow off No data communication on the RJ45 connector.
TM05 6436 4712
Yellow flashing
Steady yellow
LINK1 and LINK2
These green LEDs show whether the ethernet cable is properly connected.
Status Description
Green off No ethernet Link on the RJ45 connector Green on Ethernet Link on the RJ45 connector is OK
Data communication ongoing the on RJ45 connector.
Heavy network traffic on the RJ45 connector.
Status Description
Off CIM 500 is switched off.
Flashing green
Permanently green
Flashing red (3 Hz, duty cycle 50 %)
Pulsing red (0.3 Hz, duty cycle 10 %)
Permanently red
Permanently red and green
Flashing red and green
Wink function. LED will flash 10 times when activated from master.
CIM 500 is ready for data transmission (data exchange state).
Wrong or missing PROFINET IO configuration. See section 9.2.1 LED
status.
Configured, but connection to master lost. See section 9.2.1 LED status.
Product not supported. See section
9.2.1 LED status.
Error in the firmware download. See section 9.2.1 LED status.
After 20 seconds in this state, the CIM 500 factory settings are restored and the device is restarted.
9

7. Detailed description of data modules

English (GB)

7.1 Data types

Grundfos CIM 150/500 supports the following data types. All data types, except for data type 10, comply with specification
IEC 61158-6 standard data types for use in PROFIBUS/ PROFINET profiles.
Data type Description
1 Boolean 2 Integer 8 3 Integer 16 4 Integer 32 5 Unsigned 8 6 Unsigned 16 7 Unsigned 32 8 Floating point 9 Visible string 10 Non-standard
All multi-byte data types are transmitted with MSB (Most Significant Byte) first.
7.1.1 Explanation of event trigger
State
Control bits with a state event trigger behave like a ’state’ that is forced upon the DDA pump. CIM 150/500 will attempt to make the pump operate according to the ’requested’ state in the ControlModule. Due to certain state/mode restrictions, this might not always be possible (see explanation of the bit in question). The ’actual state’ of the pump can be read from the corresponding bit in StatusModule (module 11).
Value change
Control bits/bytes with a value-change event trigger behave like a command that is executed when the bit/byte changes its value. CIM 150/500 will attempt to make the DDA pump operate according to the ’requested’ value in the ControlModule. The change will be reflected in the corresponding bit/byte in StatusModule (module 11). Bits/bytes that are controlled by a "value-change event trigger" can be controlled from both PROFIBUS/PROFINET and the pump HMI. The last value change, no matter from which source, will become active if not prevented by other conditions (see explanation of the bit/byte in question).
Rising edge
Control bits with a rising-edge event trigger behave like a command that is executed when a bit transition from "0" to "1" occurs. Each of them has a corresponding acknowledge bit in the StatusModule (module 11) which is set when the command is executed and cleared when the control bit is written back to "0".

7.2 Control module (ControlModule, module 1)

This is a PROFIBUS/PROFINET output module used for the control of the DDA pump. Its data type is 10, non-standard.
Mode/state settings
Bit Name Event trigger
0 RemoteAccessReq State 1 De-aerating (100 %) Value change
Byte 1 (data type 5)
Byte 2 (data type 5)
Byte 3 (data type 5)
Byte 4 (data type 5)
Byte 5 (data type 5)
2 AnalogMode Value change 3 TimerMode Value change 4 SlowMode Value change 5 Velocity Value change
6-7 - -
Enable/disable function
Bit Name Event trigger
0 AutoDeaeratingEnable Value change 1 FlowControlEnable Value change 2 ProfiWatchdogEnable Value change 3 AutoFlowAdaptEnable Value change 4 PulseMemoryEnable Value change
5-7 - -
Action commands
Bit Name Event trigger
0 ResetFault Rising edge 1 Pulse Rising edge 2 ResetVolumeCounter Rising edge 3 SetRTC Rising edge
4-7 - -
ReqStartStop [enumeration]
Triggered by value change
Value Name
0 ReqStart 1 ReqStop
2-255 -
OperatingMode [enumeration]
Triggered by value change
Value Name
0 Manual 1Pulse 2Analog 3Timer 4Batch
5-255 -
10
7.2.1 Explanation of control bits in ControlModule
RemoteAccessReq
Control bit used by CIM 150/500 to activate control from the bus.
The pump can only be controlled via the pump HMI and from its external signal inputs. With this setting, all control
0:
bits in ControlModule and writing to any output module will have no influence.
CIM 150/500 can control the pump according to the settings in the ControlModule and the writing to the other
1:
output modules. The pump can also be controlled via the pump HMI and from its external signal inputs.
De-aerating
Control bit used to start and stop de-aerating the pump.
0: Stop de-aerating the pump.
Start de-aerating the pump.
1:
Equivalent to keep pressing .
If the pump has been stopped via the pump HMI (symbol ), it is still possible to start and stop de-aerating the pump from the bus.
If de-aerating of the pump has been started from the bus, it can be stopped by pressing or on the pump.
AnalogMode
Control bit used to select type of analog input signal.
0: 0-20 mA. 1: 4-20 mA.
Toggling this bit has no effect unless the pump is in operating mode "Analog". The actual state (readable from StatusModule) will be reset to 4-20 mA whenever another operating mode is selected.
TimerMode
Control bit used to select timer mode.
Cycle timer mode. The pump repeats a cyclical dosing of the batch volume which can be programmed from PROFIBUS/PROFINET
0:
with data modules SetBatchDosingVolume and SetBatchDosingTime.
Week timer mode. Up to 16 time-controlled dosing procedures are defined
1:
for a week. These procedures have to be programmed via the pump HMI.
SlowMode
Control bit used to slow down the suction stroke velocity.
SlowMode disabled.
0:
No slow-down of suction stroke velocity. SlowMode enabled.
1:
Slows down the suction stroke velocity to the velocity selected with control bit velocity.
Velocity
Control bit used to select SlowMode suction stroke velocity.
0: Select SlowMode velocity 50 %. 1: Select SlowMode velocity 25 %.
Toggling this bit has no effect unless the pump operates in SlowMode. Suction stroke will be reset to 50 % velocity whenever SlowMode is disabled.
AutoDeaeratingEnable
0: Automatic pump de-aeration disabled.
Automatic pump de-aeration enabled.
1:
The pump is automatically de-aerated (degassed) at regular intervals.
Data module 34 DigitalOutputs, bit 2, will signal whenever automatic pump de-aeration is active.
FlowControlEnable
When the FlowControl function is enabled, various faults and deviations related to the dosing process will be detected and indicated.
0: FlowControl function disabled. 1: FlowControl function enabled.
The enabling/disabling of FlowControl means the enabling/ disabling of all alarms/warnings that are associated with flow measurement. See section 7.7 Measurement data modules.
If the FlowControl function is disabled, the AutoFlowAdapt function (see control bits AutoFlowAdaptEnable) cannot be enabled.
ProfiWatchdogEnable
The PROFIBUS/PROFINET software watchdog is used to monitor the PROFIBUS/PROFINET connection. If the connection is broken, the DDA pump will stop dosing and indicate a bus communication fault. See section 7.8 Alarms and warning.
0: PROFIBUS/PROFINET software watchdog disabled. 1: PROFIBUS/PROFINET software watchdog enabled.
When "Bus control" is selected via the pump HMI, the PROFIBUS/PROFINET watchdog is automatically enabled every time the pump is powered on. If the bus communication is somehow interrupted (no communication with a PROFIBUS/ PROFINET master), this will be detected and the DDA pump will stop with an alarm indicating "bus error" (event code 15).
Enabling of PROFIBUS/PROFINET will at the same time automatically enable the monitoring of the cable connection from the E-box to the DDA pump (event code 152).
After power-on, the PROFIBUS/PROFINET master can at any time control the enabling and disabling of the PROFIBUS/ PROFINET software watchdog. The monitoring of the E-box cable connection will follow this choice.
When "Bus control" is disabled via the pump HMI, the PROFIBUS/PROFINET software watchdog is also automatically disabled and so is the monitoring of the E-box connection.
English (GB)
11
AutoFlowAdaptEnable
English (GB)
The AutoFlowAdapt function detects changes in various parameters and responds accordingly to keep the flow constant. Dosing accuracy is increased when this function is enabled.
0: AutoFlowAdapt function disabled. 1: AutoFlowAdapt function enabled.
The AutoFlowAdapt function can only be enabled if the FlowControl function is also enabled.
PulseMemoryEnable
The Pulse memory function can be used in operating mode "Pulse". When it is enabled, up to 65000 unprocessed pulses can be saved for subsequent processing.
0: Pulse memory function disabled. 1: Pulse memory function enabled.
ResetFault
When this control bit is toggled 01, the pump will attempt to reset pending alarms and warnings and to restart the pump if it was stopped due to an alarm.
Pulse
When this control bit is toggled 0 1, a pulse signal is sent to the pump. This can be used in operating modes "Pulse" and "Batch" and is equivalent to a pulse signal from the signal inputs.
ResetVolumeCounter
When this control bit is toggled 0 1, VolumeTripCounter (module
30) is reset to "0".
SetRTC
When this control bit is toggled 01, the internal real-time clock (RTC) in the DDA pump will be updated. The values must have been previously written to SetDataTime (module 9).
7.2.2 Explanation of control mode
Control enumeration for remote start/stop of the pump.
Value Name
ReqStart If the pump is ready to be controlled from PROFIBUS/ PROFINET (StatusModule:ActRemoteAccess = "1"), this value will start the pump and it will start dosing
0
according to the selected operating mode. If the pump is stopped via the pump HMI, it will restart when is pressed.
ReqStop If the pump is ready to be controlled from PROFIBUS/ PROFINET (StatusModule:ActRemoteAccess = "1"), this value will stop the pump and the pump HMI will
1
show . If the pump is stopped from the bus, it cannot be started via the pump HMI (unless "Bus control" is deselected). ReqStop cannot stop the pump when it is de-aerating.
7.2.3 Explanation of operating mode
Control enumeration for selection of operating mode.
Value Name
Manual
In this operating mode, the pump permanently doses
0
the dosing flow set via SetpointManual (module 2) or the pump HMI.
Pulse
In this operating mode, the pump doses the volume set via SetPulseVolume (module 3) or the pump HMI for each incoming pulse. Reception of the Pulse command from PROFIBUS/PROFINET has the same
1
effect as an incoming contact pulse signal. If the pump receives more pulses than it can process at the maximum dosing flow, excess pulses will be ignored if the Memory function (PulseMemoryEnable bit) is not enabled.
Analog
In this operating mode, the pump doses according to the external analog signal. It can operate according to a 4-20 mA or 0-20 mA signal selected via the AnalogMode bit or the pump HMI.
2
If the input value in Analog mode 4-20 mA falls below 2 mA, an alarm is displayed and the pump stops. The relation between analog signal and dosing value is called analog scaling and must be set via the pump HMI.
Timer
The time the dosing should take place is controlled by a cyclic timer or by week timers. The selection is done
3
via the TimerMode bit or the pump HMI. Some other parameters are related to timer dosing. They can only be programmed via the pump HMI.
Batch
In this operating mode, the pump doses the volume set via SetBatchDosingVolume (module 4) over a time period of SetBatchDosingTime (module 5) for each
4
incoming pulse (or PROFIBUS/PROFINET Pulse command). The remaining batch volume during dosing can be read from RemainingDosingVolume (module 28).
12

7.3 Dosing settings

Module Name Data type Unit Description
Setting of the setpoint used in operating mode "Manual".
2 SetSetpointManual 8 l/h
3 SetPulseVolume 8 l
4 SetBatchDosingVolume 8 l
5 SetBatchDosingTime 7 0.1 s
6 SetPressureMax 8 bar
Can also be set via the pump HMI. The present value can always be read from ActSetpointManual (module 12).
Setting of the pulse volume used in operating mode "Pulse". Can also be set via the pump HMI. The present value can always be read from ActPulseVolume (module 13).
Setting of the batch dosing volume used in operating mode "Batch". Can also be set via the pump HMI. The present value can always be read from ActBatchDosingVolume (module
14). Setting of the batch dosing time used in operating mode "Batch".
Can also be set via the pump HMI. The present value can always be read from ActBatchDosingTime (module
15). Setting of the (relative) pressure alarm limit.
Can also be set via the pump HMI. The present value can always be read from ActPressureMax (module 16).

7.4 Other settings

Module Name Data type Unit Description
Used to enable and disable the output relays 1 and 2. A relay has to be set to "Bus control" via the pump HMI if it should be controllable from the bus via the SetOutputRelays module. Via the pump HMI, the relays can also be individually configured to be of type NO or NC.
English (GB)
7 SetOutputRelays 5 Bits
8 SetAnalogOutput 8 A
9 SetDateTime 10
BCD
string
Bit 0:Relay 1 control: 0: Not active 1: Active. Bit 1:Relay 2 control: 0: Not active 1: Active.
The present status of the output relays can always be read from OutputRelays (module 34).
Used to control the analog output signal. The type of signal (4-20 mA or 0-20 mA) follows the setting of the AnalogMode bit. The analog output has to be set to "Bus control" via the pump HMI if it should be controllable from the bus. The present value of the analog output signal can always be read from AnalogOutput (module 32).
Used to set the internal real-time clock (RTC).
Byte 1: Year (from year 2000) Byte 2: Month [1-12] Byte 3: Day [1-31] Byte 4: Hour [0-23] Byte 5: Minute [0-59] Byte 6: Second [0-59].
Each byte is a binary-coded decimal (BCD) value.
Example 15:38:00, April 24 2011, is coded with hexadecimal numbers as: Year = 11h, Month = 04h, Day = 24h, Hour = 15h, Minute = 38h, Second = 00h.
Can also be set via the pump HMI.
The present value of the real-time clock can always be read from DateTime (module 21).
13

7.5 Bus settings compared to pump HMI settings

English (GB)
Name
Mode/state settings
RemoteAccessReq No Yes* De-aerating (100 %) Yes Yes/No* AnalogMode Yes Yes TimerMode Yes Yes SlowMode Yes Yes Velocity Yes Yes
Enable/disable function
AutoDeaeratingEnable Yes Yes FlowControlEnable Yes Yes ProfiWatchdogEnable Yes** Yes AutoFlowAdaptEnable Yes Yes PulseMemoryEnable Yes Yes
Action commands
ResetFault Yes ­Pulse No ­ResetVolumeCounter Yes ­SetRTC Yes -
Operation control
ReqStart Yes Yes ReqStop Yes No OperatingMode Yes Yes
Dosing settings
SetpointManual Yes Yes SetPulseVolume Yes Yes SetBatchDosingVolume Yes Yes SetBatchDosingTime Yes Yes SetFlowControlPressMax Yes Yes
Output signal control
SetOutputRelay (value) No Yes SetAnalogOutput (value) No Yes SetDateTime Yes Yes
* Will only be preserved if the CIM module is not powered off. ** De-aerating will be preserved if commanded from bus. *** Selecting and deselecting "Bus control" will implicitly enable
and disable the PROFIBUS/PROFINET watchdog and the monitoring of the E-box connection to the DDA pump.
Selectable
from HMI
Setting preserved
during power-off

7.6 Status module (StatusModule, module 11)

This is a PROFIBUS/PROFINET input module used for the status of the DDA pump settings. Its data type is 10, non-standard. The actual status of all the pump modes and states are reflected, no matter if it is a result of a pump HMI setting or a setting written from PROFIBUS/PROFINET via ControlModule (module 1).
Actual mode/state settings [bits]
Bit Name
0 ActRemoteAccess
Byte 1 (data type 5)
Byte 2 (data type 5)
Byte 3 (data type 5)
Byte 4 (data type 5)
Byte 5 (data type 5)
1 ActDeaerating (100 %) 2 ActAnalogMode 3 ActTimerMode 4 ActSlowMode 5 ActVelocity
6-7 -
Actual enable/disable function [bits]
Bit Name
0 ActAutoDeaeratingEnable 1 ActFlowControlEnable 2 ActProfiWatchdogEnable 3 ActAutoFlowAdaptEnable 4 ActPulseMemoryEnable
5-7 -
Action command acknowledgement [bits]
Bit Name
0 ResetFaultAck 1PulseAck 2 ResetVolumeCounterAck 3SetRTCAck
4-7 -
Miscellaneous status [bits]
Bit Name
0 Dosing (running) 1 Warning 2 Fault 3 BusControlLocallyEnabled
4-7 -
ActualStartStop [enumeration]
Value Name
0Started 1 Stopped 2 Calibrating 3Service
4-255 -
ActualOperatingMode [enumeration]
14
Byte 6 (data type 5)
Value Name
0 Manual 1Pulse 2Analog 3Timer 4Batch
5-255 -
7.6.1 Explanation of status bits
ActRemoteAccess
Status bit indicating whether the pump is in a state where it is controllable from the bus.
The pump can only be controlled from its HMI and its external signal inputs. In this state, all control bits in
0:
ControlModule and writing to any output module will have no influence.
In this state, the pump can be controlled by the bit settings in the ControlModule (as well as from the pump HMI and external signal inputs) and the writing to the other output
1:
modules. To enter this state, the ControlModule bit 0 must be set and the pump must be started via the pump HMI by pressing .
ActDeaerating
Status bit indicating whether the pump is de-aerating or not.
0: The pump is not de-aerating. 1: The pump is de-aerating.
ActAnalogMode
Status bit indicating the selected type of the analog input signal.
0: 0-20 mA.
4-20 mA.
1:
This will always be the reading if the operating mode is not "Analog".
ActTimerMode
Status bit indicating the selected timer mode.
0: Cycle timer mode. 1: Week timer mode.
ActSlowMode
Status bit indicating whether SlowMode has been enabled.
SlowMode disabled.
0:
No slow-down of suction stroke velocity. SlowMode enabled.
1:
Slows down the suction stroke velocity to the velocity selected with control bit Velocity.
Velocity
Status bit indicating the selected SlowMode suction stroke velocity.
Selected SlowMode velocity 50 %.
0:
This will always be the reading if SlowMode is disabled.
1: Selected SlowMode velocity 25 %.
ActAutoDeaeratingEnable
Status bit indicating whether automatic pump de-aeration has been enabled.
0: Automatic pump de-aeration disabled.
Automatic pump de-aeration enabled.
1:
DigitalOutputs (module 34), bit 2, will signal whenever the automatic pump de-aeration is active.
ActFlowControlEnable
Status bit indicating whether the FlowControl function has been enabled.
ActProfiWatchdogEnable
Status bit indicating whether the PROFIBUS/PROFINET software watchdog has been enabled.
0: PROFIBUS/PROFINET software watchdog disabled. 1: PROFIBUS/PROFINET software watchdog enabled.
The PROFIBUS/PROFINET software watchdog is automatically enabled/disabled when "Bus control" is selected/deselected via the pump HMI. The software watchdog can be enabled/disabled independently via the bus.
ActAutoFlowAdaptEnable
Status bit indicating whether the AutoFlowAdapt function has been enabled.
AutoFlowAdapt function disabled.
0:
This will always be the reading if the FlowControl function is disabled.
1: AutoFlowAdapt function enabled.
ActPulseMemoryEnable
Status bit indicating whether the Pulse memory function is enabled.
0: Pulse memory function disabled. 1: Pulse memory function enabled.
Dosing (running)
Status bit indicating whether the DDA pump is dosing (running) at the moment.
0: The pump is not dosing at the moment. 1: The pump is dosing at the moment.
Warning
Warning status bit.
0: No warning is present.
A warning is present.
1:
The pump can however continue its precise dosing for the time being, but we recommend to have it serviced.
For further details about possible warnings and faults as well as the pump behaviour in these situations, see section 7.8 Alarms
and warning.
Fault
Fault status bit. The pump will stop dosing as long as the fault is present.
0: No fault is present.
A fault is present, and the pump will remain stopped until
1:
the fault has been corrected.
For further details about possible warnings and faults as well as the pump behaviour in these situations, see section 7.8 Alarms
and warning.
BusControlLocallyEnabled
Status bit indicating whether "Bus control" has been enabled in the Settings menu on the pump HMI.
Bus control has not been enabled via the pump HMI.
0:
Setting of the RemoteAccess bit in ControlModule has no effect.
1: Bus control has been enabled via the pump HMI.
English (GB)
0: FlowControl function disabled. 1: FlowControl function enabled.
15
7.6.2 Explanation of command acknowledge bits
English (GB)
If the ActRemoteAccess bit is not set, PROFIBUS/PROFINET commands (and writings in general) will be prohibited and none of the acknowledge bits will ever be set. Command acknowledge bits can thus be used to check whether a command from ControlModule was sent or not.
ResetFaultAck
Acknowledge bit belonging to the ResetFault control bit. It will be set when the control bit is set and the command has been executed. It will be cleared when the control bit is cleared.
PulseAck
Acknowledge bit belonging to the Pulse control bit. It will be set when the control bit is set and the command has been executed. It will be cleared when the control bit is cleared.
ResetVolumeCounterAck
Acknowledge bit belonging to the ResetVolumeCounter control bit. It will be set when the control bit is set and the command has been executed. It will be cleared when the control bit is cleared.
SetRTCAck
Acknowledge bit belonging to the SetRTC control bit. It will be set when the control bit is set and the command has been executed. It will be cleared when the control bit is cleared.
Explanation of ActualStartStop
Status enumeration for reading whether the pump is started, stopped, calibrating or in service mode:
7.6.3 Explanation of ActualOperatingMode
Status enumeration for reading of the actual operating mode. For an explanation of these modes and the belonging enumeration, see section 7.2.3 Explanation of operating mode.
Value Name
Started
This has the following meaning for the different operating modes:
• "Manual": The pump will be dosing according to ActualSetpointManual (module 12).
• "Analog": The pump will be dosing according to the analog input signal and the analog scaling.
•"Pulse":
0
1
The pump will be dosing according to the reception of pulses and the value of ActualPulseVolume (module 13).
•"Batch": The pump will be dosing according to the reception of pulses and the values of ActualBatchDosingVolume (module 14) and ActualBatchDosingTime (module 15).
•"Timer": The pump will be dosing according to the timer functions using the batch dosing settings.
Stopped
The pump has been stopped by one of the control sources. The state of the control sources can be read from ControlSourceStates (module 17).
16
Calibrating
The pump is calibrating the dosing accuracy.
2
This is only possible via the pump HMI by selecting Calibration in the Setup menu.
Service
The pump has stopped and has been brought into Service mode.
3
This is only possible via the pump HMI and can be done by pressing and simultaneously.

7.7 Measurement data modules

Module Name Data type Unit Description
12 ActualSetpointManual 8 l/h
13 ActualPulseVolume 8 l
14 ActualBatchDosingVolume 8 l
15 ActualBatchDosingTime 7 0.1 s
16 ActualPressureMax 8 bar
17 ControlSourceStates 5 Bits
18 FaultCode 5 Enum
20 WarningBits 6 Bits
21 DateTime 10
The actual setpoint used in operating mode "Manual". Can be set via SetpointManual (module 2) or via the pump HMI.
The actual pulse volume used in operating mode "Pulse". Can be set via SetPulseVolume (module 3) or via the pump HMI.
The actual batch dosing volume used in operating mode "Batch". Can be set via SetBatchDosingVolume (module 4) or via the pump HMI.
The actual batch dosing time used in operating mode "Batch". Can be set via SetBatchDosingTime (module 5) or via the pump HMI.
Actual value of (relative) pressure alarm limit setting. Can be set via SetPressureMax (module 6) or via the pump HMI.
Status of start/stop control sources, "1" means "Active". They can be active simultaneously. Bit 0: Stop via pump HMI Bit 1: External stop Bit 2: Stop from bus.
See section 7.6 Status module (StatusModule, module 11).19 WarningCode 5 Enum
Present value of the internal real-time clock (RTC). Can be set via SetDateTime (module 9) or via the pump HMI.
Byte 1: Year (from year 2000) Byte 2: Month [1-12] Byte 3: Day [1-31] Byte 4: Hour [0-23] Byte 5: Minute [0-59]
BCD
Byte 6: Second [0-59].
string
English (GB)
Each byte is a binary-coded decimal (BCD) value.
Example
15:38:00, April 24 2011, is coded with hexadecimal numbers as: Year = 11h, Month = 04h, Day = 24h, Hour = 15h, Minute = 38h, Second =
00h. 22 DosingPressureMax 8 bar Maximum dosing pressure, fixed factory-set value for this pump type. 23 DosingCapacityMax 8 l/h Maximum dosing capacity, fixed factory-set value for this pump type.
24 DosingCapacityReference 8 l/h
25 MeasuredDosingCapacity 8 l/h
26 MeasuredPressure 8 bar
27 PulseInputFrequency 8 Hz
28 RemainingDosingVolume 8 l Actual remaining volume to be dosed. Used in "Batch" mode. 29 VolumeTotal 8 l Total volume dosed (non-resettable).
30 VolumeTripCounter 8 l
31 AnalogInput 8 A Analog input signal 0-20 mA or 4-20 mA (used as setpoint in Analog mode).
32 AnalogOutput 8 A
The dosing capacity setpoint shown in the pump display. It represents the
actual setpoint belonging to the actual operating mode and dosing state.
Measured (actual) dosing capacity.
FlowControl bit in ControlModule (module 1) must be enabled for this value
to be available.
Measured absolute pressure.
FlowControl bit in ControlModule must be enabled. Except for the
atmospheric pressure, it corresponds to "Backpressure" reading in the
display.
Frequency of pulse input (external pulse input signal or PROFIBUS/
PROFINET Pulse command in ControlModule).
Dosed-volume trip counter (reset with ResetVolumeCounter command in
ControlModule).
Analog output signal.
The parameter to map to the output is selected via the pump HMI. If control
from PROFIBUS/PROFINET is selected, the analog output signal will be
controlled from SetAnalogOutput (module 8).
17
English (GB)
Module Name Data type Unit Description
Status of the external digital inputs.
Logical "0": The input is not active.
Logical "1": The input is active.
33 DigitalInputs 5 Bits
34 OutputRelays 5 Bits
35 NumberOfPowerOns 6 -
36 RunTime 7 s Counts the time the DDA pump has been dosing (non-resettable).
37 OperatingHours 7 s
38 StrokeCounter 7 - Counts the number of strokes (non-resettable). 39 TimeToNextDosing 7 s Time before the next dosing takes place (only in timer mode).
The relay input type (NO or NC) is selected via the pump HMI.
Signals are fixed to the following:
Bit 0: Low-level signal
Bit 1: Empty signal
Bit 2: External stop.
Status of the two output relays.
Logical "0": The output is not active.
Logical "1": The output is active.
The relay output type (NO or NC) is selected via the pump HMI.
The output relay modules are defined as follows:
Bit 0: Relay 1 (select signal parameter via the pump HMI).
Bit 1: Relay 2 (select signal parameter via the pump HMI).
Bit 2: Auto-deaerating (de-aerating valve open).
If "Bus control" has been selected as the relay signal parameter, the relay
can be controlled from SetOutputRelays (module 7).
Counts the number of times the pump has been powered on (non-
resettable).
Counts the number of hours the DDA pump has been switched on. It counts
both when the pump is dosing and when it is not dosing.
18

7.8 Alarms and warning

Module Name Data type Description
18 FaultCode 5
19 WarningCode 5
20 WarningBits 6
* Requires FlowControlEnable bit in ControlModule to be set. In case of a pump alarm or pump warning the modules
WarningCode and FaultCode will contain an event code for the cause of the problem.
The complete list of possible alarm/warning codes from a DDA pump is shown in the table below.
Code for active pump alarm. See event code in the table below.
Code for first active pump warning. See event code in the table below.
All active warnings. The belonging event code in parenthesis.
Byte 1
Bit 0:Backpressure low (211)* Bit 1:Air bubbles (35)* Bit 2:Cavitation (208)* Bit 3:Discharge valve leakage (36)* Bit 4:Suction valve leakage (37)* Bit 5:-- reserved -­Bit 6:Service now (12) Bit 7:Service soon (33)
Byte 2
Bit 0:Low level in tank (206) Bit 1:-- reserved -­Bit 2:FlowControl cable breakdown (169)* Bit 3:­Bit 4:­Bit 5:Flow deviation (17)* Bit 6:­Bit 7:-
Alarm events will make the pump stop. Some of them require acknowledgement of the alarm before the pump can be restarted. This acknowledgement can come from the pump HMI or PROFIBUS/PROFINET by usage of the ResetFault command.
The pump can only indicate one active alarm at a time, whereas there can be many simultaneously active warnings. The complete status of warnings can be read from the WarningBits module.
English (GB)
Event code Event group Event description
210 Pump head
211 Pump head
Maximum pressure limit exceeded. ActualPressureMax (module 16).
Backpressure too low. Fixed low-pressure limit (1.5 bar).
Depends on FlowControl
enabled
Yes Alarm Yes
Yes
Event
action
Alarm/
Warning
1)
35 Pump head Air bubbles, gas in pump head, de-aerating problem. Yes Warning Yes
208 Pump head Cavitation. Yes Warning Yes
36 Pump head Discharge (pressure) valve leakage. Yes Warning Yes 37 Pump head Suction valve leakage. Yes Warning Yes 12 Pump head Service now (time for service exceeded). No Warning No 33 Pump head Soon time for service (general service information). No Warning No 17 Pump head Flow deviation (performance requirement not met). Yes Warning Yes 51 Pump head Blocked motor/pump. No Alarm Yes
206 Tank Low level in tank. No Warning Yes
57 Tank Empty tank (dry running). No Alarm Yes
169 Input signals Cable breakdown on FlowControl. Yes Warning Yes
97 Input signals Defective analog 4-20 mA cable. No Alarm Yes
15 Communication
152 Communication
PROFIBUS/PROFINET communication fault (main network communication fault).
Extension box communication fault (GENIbus communication fault). Defective cable between E-box
No Alarm
No Alarm
2)
2)
and DDA pump.
1)
Warning or alarm is selected in the Settings menu via the pump HMI.
2)
An alarm only occurs when the ActProfiWatchdogEnable bit has been set. See sections 7.2.1 Explanation of control bits in
ControlModule and 7.6.1 Explanation of status bits.
Auto-
acknowledge
Yes
No
No
19

7.9 Device identification (DeviceIdentification, module 40)

English (GB)
The data type is 10, non-standard.
Byte Name/description
UnitFamily [enumeration] UnitType [enumeration]
1: UPE/MAGNA circulator pump
2: E-pump, 1-phase/3-phase, based on MGE motor or CUE frequency converter
1
7: MP 204 motor protector 1: MP 204
17: Hydro Multi-E model G and earlier models
21: Hydro MPC/Control MPC, Hydro Multi-B
25: CR Monitor 1: CR Monitor, CU 351 26: Dedicated Controls 1: Dedicated Controls, CU 361 30: Smart Digital Dosing, DDA 1: Smart Digital Dosing, DDA
39: Hydro Multi-E model H and later models
UnitType [enumeration]
2
According to description above. UnitVersion [enumeration]
3
Used by Grundfos. 4 CIMSoftwareVersion [number] 5 CIMSoftwareRevision [number] 6 CIMModel [enumeration]
5: UPE, 3-phase 7: MAGNA, 1-phase 9: MAGNA, 1-phase, small 10: MAGNA3
2: MGE, 1-phase 3: MGE, 3-phase 4: MGE, 3-phase, large 5: CUE frequency converter 6: MGE, 3-phase, model G 7: MGE, 3-phase, model H/I
1: With 3-phase pumps 2: With 1-phase pumps
1: Hydro MPC/Control MPC, CU 351 2: Hydro Multi-B, CU 323
1: With 3-phase pumps 2: With 1-phase pumps
20

8. Product simulation

The CIM module can be put in product simulation mode in which case it will generate life-like simulated values of all the PROFIBUS/PROFINET input data modules.
It will thus be possible to connect a PROFIBUS/PROFINET master to CIM 150/CIM 500 without this device being connected to a real pump in a real-life system. In an office environment, it can then be verified that communication works and data is being received and handled correctly by the PROFIBUS/PROFINET master application program (e.g. PLC program) before the equipment is installed under real-life conditions.

8.1 CIM 150 product simulation

Product simulation mode is entered when the hexadecimal address switch has one of the values shown in the table below:
Address setting (section
5.4 Setting the PROFIBUS address)
SW3 SW4
F 0 Pump profile F 1 Booster system profile F 2 CR Monitor profile
F3
F 4 Digital Dosing DDA profile F 5 Wastewater system profile
The effective address will be 15 (0x0F). Only input modules are simulated. The data read has dummy
values and no real product functionality is simulated.
Simulated product
MP 204 motor protector profile
English (GB)

8.2 CIM 500 Product Simulation

Product simulation mode is entered via the webserver. See section A.4 PROFINET IO configuration on page 27.
21

9. Fault finding

English (GB)

9.1 CIM 150

You can detect faults in a CIM 150 PROFIBUS module by observing the status of the two communication LEDs. See the table below.
9.1.1 LED status
Fault (LED status) Possible cause Remedy
1. Both LED1 and LED2 remain off when the power supply is connected.
2. The LED2 for internal communication is flashing red.
3. LED2 for internal communication is permanently red.
4. The PROFIBUS LED1 is permanently red.
5. The PROFIBUS LED1 is flashing red. a) Fault in CIM 150 PROFIBUS
a) CIM 150 is fitted incorrectly in the DDA
pump. b) CIM 150 is defective. Replace CIM 150. a) No internal communication between
CIM 150 and the DDA pump. a) CIM 150 does not support the
connected DDA pump. a) Fault in CIM 150.
configuration.
Check that CIM 150 is fitted/connected correctly.
Check that CIM 150 is fitted correctly in the DDA pump.
Contact the nearest Grundfos company.
Contact the nearest Grundfos company.
• Check in the DDA settings menu that the PROFIBUS address has a valid value [1­125]. See section 5.4 Setting the PROFIBUS
address.
• Check that the GSD file used is correct.
• Check that the PROFIBUS cable has been fitted correctly. See section 5.3 Connecting the
PROFIBUS.
• Check that the PROFIBUS termination is correct. See section 5.5 Termination resistors.

9.2 CIM 500

You can detect faults in the CIM 500 by observing the status of the two communication LEDs. See the table below and section
4.3 CIM 500 PROFINET IO.
9.2.1 LED status
Fault (LED status) Possible cause Remedy
1. Both LED1 and LED2 remain off when the power supply is connected.
2. The PROFINET IO LED1 remains off. a) The protocol selection switch (SW1)
3. LED2 for internal communication is flashing red.
4. LED2 for internal communication is permanently red.
5. The PROFINET IO LED1 is permanently red.
6. The PROFINET IO LED1 is flashing red. a) Fault in the CIM 500 PROFINET IO
7. The PROFINET IO LED1 is pulsing red. a) Connection to master lost. • Check cables.
8. LED1 is permanently red and green at the same time.
9. LED2 is permanently red and green at the same time.
a) CIM 500 is fitted incorrectly in the
Grundfos product.
b) CIM 500 is defective. Replace CIM 500.
has been set in Modbus TCP position
a) No internal communication between
CIM 500 and the Grundfos product.
a) CIM 500 does not support the Grundfos
product connected.
a) Connected Grundfos product is not
supported.
b) Illegal position of protocol switch (SW1) Check that the rotary switch SW1 is set to
configuration.
a) Error in the firmware download. Use the webserver to download the
a) Memory fault. Replace CIM 500.
Check that CIM 500 is fitted/connected correctly.
Set the switch to "0".
Check that CIM 500 is fitted correctly in the Grundfos product.
Contact the nearest Grundfos company.
Contact the nearest Grundfos company.
"0".
• Check that the right GSDML file is used. Check that PROFINET IO IP address configuration is correct. See section A.4
PROFINET IO configuration on page 27.
• Check device name in the CIM 500 and PROFINET IO master.
• Check that the master is running.
firmware again. See section A.2 Web se rver
configuration on page 26.
22

10. Grundfos alarm and warning codes

This is a complete list of alarm and warning codes for Grundfos products. For the codes supported by this product, see the alarms and warnings section.
Code Description Code Description Code Description
1 Leakage current 36 Outlet valve leakage 71
2 Missing phase 37 Inlet valve leakage 72 Hardware fault, type 1 3 External fault signal 38 Vent valve defective 73 Hardware shutdown (HSD) 4 Too many restarts 39 Valve stuck or defective 74 Internal supply voltage too high 5 Regenerative braking 40 Undervoltage 75 Internal supply voltage too low 6 Mains fault 41 Undervoltage transient 76 Internal communication fault
7 Too many hardware shutdowns 42 Cut-in fault (dV/dt) 77
8 PWM switching frequency reduced 43 - 78 Fault, speed plug 9 Phase sequence reversal 44 - 79 Functional fault, add-on module
10 Communication fault, pump 45 Voltage asymmetry 80 Hardware fault, type 2
11 Water-in-oil fault (motor oil) 46 - 81 Verification error, data area (RAM)
Time for service (general service
12
information)
13 Moisture alarm, analog 48 Overload 83
Electronic DC-link protection
14
activated (ERP) Communication fault, main system
15
(SCADA)
16 Other 51 Blocked motor or pump 86 Fault (add-on) I/O module
Performance requirement cannot
17
be met
18 Commanded alarm standby (trip) 53 Stalled motor 88 Sensor fault
19 Diaphragm break (dosing pump) 54
20 Insulation resistance low 55
21 Too many starts per hour 56 Underload 91 Signal fault, temperature sensor 1
22 Moisture switch alarm, digital 57 Dry running 92
23 Smart trim gap alarm 58 Low flow 93 Signal fault, sensor 2 24 Vibration 59 No flow 94 Limit exceeded, sensor 1 25 Setup conflict 60 Low input power 95 Limit exceeded, sensor 2
Load continues even if the motor
26
has been switched off External motor protector activated
27
(for example MP 204)
28 Battery low 63 - 98
Turbine operation (impellers
29
forced backwards) Change bearings (specific service
30
information) Change varistor(s) (specific
31
service information)
32 Overvoltage 67
Soon time for service (general
33
service information)
34 No priming water 69
Gas in pump head, de-aerating
35
problem
47 - 82
49 Overcurrent (i_line, i_dc, i_mo) 84 Memory access error
Motor-protection function, general
50
shutdown (MPF)
52 Motor slip high 87 -
Motor-protection function, 3 sec. limit
Motor current protection activated (MCP)
61 - 96 Setpoint signal outside range
62 - 97 Signal fault, setpoint input
64 - 99
Motor temperature 1 (t_m or t_mo
65
or t_mo1) Temperature, control electronics
66
(t_e) Temperature too high, internal
frequency converter module (t_m) External temperature or water
68
temperature (t_w) Thermal relay 1 in motor, for
example Klixon Thermal relay 2 in motor, for
70
example thermistor
Motor temperature 2 (Pt100, t_mo2)
Communication fault, twin-head pump
Verification error, code area (ROM, FLASH)
Verification error, FE parameter area (EEPROM)
Verification error, BE parameter
85
area (EEPROM)
89 Signal fault, (feedback) sensor 1
90 Signal fault, speed sensor
Calibration fault, (feedback) sensor
Signal fault, input for setpoint influence
Signal fault, input for analog setpoint
RTC time synchronisation with
100
cellular network occurred
101 -
102 Dosing pump not ready
103 Emergency stop
104 Software shutdown
Electronic rectifier protection
105
activated (ERP)
English (GB)
23
English (GB)
Code Description Code Description Code Description
106
107 - 142 - 177 Signal fault, Smart trim gap sensor 108 - 143 - 178 Signal fault, vibration sensor
109 - 144
110 Skew load, electrical asymmetry 145
111 Current asymmetry 146
112 Cosφ too high 147
113 Cosφ too low 148
114
115
116 Grinder motor overtemperature 151 Fault, display (HMI) 186 Signal fault, power meter sensor
117 Intrusion (door opened) 152
118
119 Signal fault, analog input AI4 154 Communication fault, display 189 Signal fault, level sensor
120
121
122
123
124
125
126
127
128 Strainer clogged 163
129 - 164 Signal fault, LiqTec sensor 199
130 - 165 Signal fault, analog input 1 200 Application alarm 131 - 166 Signal fault, analog input 2 201 External sensor input high 132 - 167 Signal fault, analog input 3 202 External sensor input low 133 - 168 Signal fault, pressure sensor 203 Alarm on all pumps 134 - 169 Signal fault, flow sensor 204 Inconsistency between sensors
135 - 170
136 - 171 Signal fault, moisture sensor 206 Water shortage, level 1
137 - 172
138 - 173
139 - 174 Signal fault, rotor origo sensor 209 Non-return valve fault
140 - 175
Electronic inverter protection activated (EIP)
Motor heater function activated (frost protection)
Too many grinder reversals or grinder reversal attempt failed
Signal fault, hydrogen sulfide H2S sensor
Auxiliary winding fault (single phase motors)
Auxiliary winding current too high (single-phase motors)
Auxiliary winding current too low (single-phase motors)
Start capacitor, low (single-phase motors)
Run capacitor, low (single-phase motors)
Signal fault, outdoor temperature sensor
Signal fault, air temperature sensor
Signal fault, shunt relative pressure sensor
141 - 176
Motor temperature 3 (Pt100, t_mo3)
Bearing temperature high (Pt100), in general or top bearing
Bearing temperature high (Pt100), middle bearing
Bearing temperature high (Pt100), bottom bearing
Motor bearing temperature high (Pt100) in drive end (DE)
Motor bearing temperature high
149
(Pt100) in non-drive end (NDE)
150 Fault (add-on) pump module 185 Unknown sensor type
Communication fault, add-on module
153 Fault, analog output 188 Signal fault, user-defined sensor
155 Inrush fault 190
Communication fault, internal
156
frequency converter module
157 Real-time clock out of order 192
Hardware circuit measurement
158
fault
CIM fault (Communication
159
Interface Module)
160 Cellular modem, SIM card fault 195 Limit exceeded, sensor 6
161 Sensor supply fault, 5 V 196 Operation with reduced efficiency
162 Sensor supply fault, 24 V 197 Operation with reduced pressure
Measurement fault, motor protection
Signal fault, water-in-oil (WIO) sensor
Signal fault, atmospheric pressure sensor
Signal fault, rotor position sensor (Hall sensor)
Signal fault, temperature sensor 2 (t_mo2)
Signal fault, temperature sensor 3 (t_mo3)
Signal fault, bearing temperature
179
sensor (Pt100), general or top bearing
Signal fault, bearing temperature
180
sensor (Pt100), middle bearing Signal fault, PTC sensor (short-
181
circuited) Signal fault, bearing temperature
182
sensor (Pt100), bottom bearing Signal fault, extra temperature
183
sensor Signal fault, general-purpose
184
sensor
187 Signal fault, energy meter
Limit exceeded, sensor 1 (for example alarm level in WW application)
Limit exceeded, sensor 2 (for
191
example high level in WW application)
Limit exceeded, sensor 3 (for example overflow level in WW application)
Limit exceeded, sensor 4 (for
193
example low level in WW/tank filling application)
194 Limit exceeded, sensor 5
Operation with increased power
198
consumption Process out of range (monitoring,
estimation, calculation, control)
Level float switch sequence
205
inconsistency
207 Water leakage
208 Cavitation
210 High pressure
24
Code Description Code Description Code Description
211 Low pressure 226 Communication fault, I/O module 241 Motor phase failure
Diaphragm tank precharge
212
pressure out of range
213 VFD not ready 228 Night flow max. limit exceeded 243
214 Water shortage, level 2 229 Water on floor 244 Fault, On/Off/Auto switch 215 Soft pressure buildup time-out 230 Network alarm 245 Pump continuous runtime too long
216 Pilot pump alarm 231
Alarm, general-purpose sensor
217
high 218 Alarm, general-purpose sensor low 233 Ethernet: IP address conflict 248 Fault, battery/UPS 219 Pressure relief not adequate 234 Backup pump alarm 249 User-defined event 1 220 Fault, motor contactor feedback 235 Gas detected 250 User-defined event 2 221 Fault, mixer contactor feedback 236 Pump 1 fault 251 User-defined event 3 222 Time for service, mixer 237 Pump 2 fault 252 User-defined event 4
223 Time for service, mixer 238 Pump 3 fault 253
Pump fault, due to auxiliary 224
component or general fault
Communication fault, pump 225
module
227 Combi event 242
Ethernet: No IP address from DHCP server
Ethernet: Auto-disabled due to
232
misuse
239 Pump 4 fault 254 Inconsistent data model
Lubricate bearings (specific
240
service information)
Automatic motor model recognition failed
Motor relay has been forced (manually operated or commanded)
User-defined relay has been
246
forced (manually operated or commanded)
Power-on notice, (device or
247
system has been switched off)
SMS data from DDD sensor not received within time limit
English (GB)
25

Appendix

Appendix 1
The appendix describes the parts of the CIM 500 web server needed for the configuration of a PROFINET IO Ethernet connection. For other CIM 500 web server features, not specifically related to PROFINET IO, see the installation and operating instructions for the CIM 500.

A.1 How to configure an IP address on your PC

For connecting a PC to the CIM 500 via Ethernet, the PC must be set up to use a fixed (static) IP address belonging to the same subnetwork as the CIM 500.
1. Open "Control Panel".
2. Enter "Network and Sharing Center".
3. Click "Change adapter settings".
4. Right-click and select "Properties" for Ethernet adapter. Typically "Local Area Connection".
5. Select properties for "Internet Protocol Version 4 (TCP/IPv4).
6. Select the "Alternate Configuration" tab.
7. Configure an IP address and subnet mask to be used by your PC. See fig. 1.
Fig. 1 Example from Windows XP

A.2 Web server configuration

The built-in web server is an easy and effective way to monitor the status of the CIM 500 module and configure the available functions and Industrial Ethernet protocols. The web server also makes it possible to update the firmware of the CIM module, and store/restore settings.
Before configuration
• Check that the PC and CIM module are connected via an
Ethernet cable.
• Check that the PC Ethernet port is set to the same network as
the CIM module. For network configuration, see section A.1
How to configure an IP address on your PC.
To establish a connection from a PC to CIM 500 the first time, the following steps are required:
1. Open a standard Internet browser and type 192.168.1.100 in the URL address field.
2. Log in to the web server.
TM05 7422 0913
26

A.3 Login

Note
Fig. 2 Login
User name Enter user name. Default: admin. Password Enter password. Default: Grundfos.
User name and password can be changed on the web server under "Grundfos Management"

A.4 PROFINET IO configuration

This web page is used to configure all the parameters relevant to the PROFINET IO protocol standard. All settings can also be configured from a standard PROFINET IO configuration tool, for instance Siemens Primary Setup Tool (PST). It is available on internet.
Appendix
TM05 6063 4412
Fig. 3 Real Time Ethernet Protocol Configuration - PROFINET IO
Object Description
Device Name The PROFINET IO device name. It must be unique. IP Address The static IP address for CIM 500 on the PROFINET IO network. Subnet Mask Configure the subnet mask for the CIM 500 module on the PROFINET IO network. Gateway Configure the default gateway for the PROFINET IO network.
Use DHCP
Grundfos product simulation
The CIM 500 module can be configured to automatically obtain the IP address from a DHCP server on the network.
The CIM 500 can be put in product simulation mode to generate realistic simulated values of all the PROFINET IO input data modules. It will thus be possible to connect a PROFINET IO master to a CIM 500 fitted in a CIU or E-box without installing this device in a real industrial process system. In an office environment, it can then be verified that communication works and data are received and handled correctly by the PROFINET IO master application program (e.g. PLC program) before installing the device. To enable product simulation, select a product type from the drop down list. Product simulation will be terminated by a module power cycle.
TM05 6065 4412
27
28
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 Garín Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belarus
Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56, БЦ «Порт» Тел.: +7 (375 17) 286 39 72/73 Факс: +7 (375 17) 286 39 71 E-mail: minsk@grundfos.com
Bosnia and Herzegovina
GRUNDFOS Sarajevo Zmaja od Bosne 7-7A, BH-71000 Sarajevo Phone: +387 33 592 480 Telefax: +387 33 590 465 www.ba.grundfos.com e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 10F The Hub, No. 33 Suhong Road Minhang District Shanghai 201106 PRC Phone: +86 21 612 252 22 Telefax: +86 21 612 253 33
COLOMBIA
GRUNDFOS Colombia S.A.S. Km 1.5 vía Siberia-Cota Conj. Potrero Chico, Parque Empresarial Arcos de Cota Bod. 1A. Cota, Cundinamarca Phone: +57(1)-2913444 Telefax: +57(1)-8764586
Croatia
GRUNDFOS CROATIA d.o.o. Buzinski prilaz 38, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.hr.grundfos.com
GRUNDFOS Sales Czechia and Slovakia s.r.o.
Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Trukkikuja 1 FI-01360 Vantaa Phone: +358-(0) 207 889 500
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Tópark u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800
Indonesia
PT. GRUNDFOS POMPA Graha Intirub Lt. 2 & 3 Jln. Cililitan Besar No.454. Makasar, Jakarta Timur ID-Jakarta 13650 Phone: +62 21-469-51900 Telefax: +62 21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. 1-2-3, Shin-Miyakoda, Kita-ku, Hamamatsu 431-2103 Japan Phone: +81 53 428 4760 Telefax: +81 53 428 5005
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Velu wezo om 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
Romania
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундфос Россия ул. Школьная, 39-41 Москва, RU-109544, Russia Тел. (+7) 495 564-88-00 (495) 737-30-00 Факс (+7) 495 564 8811 E-mail grundfos.moscow@grundfos.com
Serbia
Grundfos Srbija d.o.o. Omladinskih brigada 90b 11070 Novi Beograd Phone: +381 11 2258 740 Telefax: +381 11 2281 769 www.rs.grundfos.com
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689
Slovakia
GRUNDFOS s.r.o. Prievozská 4D 821 09 BRATISLAVA Phona: +421 2 5020 1426 sk.grundfos.com
Slovenia
GRUNDFOS LJUBLJANA, d.o.o. Leskoškova 9e, 1122 Ljubljana Phone: +386 (0) 1 568 06 10 Telefax: +386 (0)1 568 06 19 E-mail: tehnika-si@grundfos.com
South Africa
Grundfos (PTY) Ltd. 16 Lascelles Drive, Meadowbrook Estate 1609 Germiston, Johannesburg Tel.: (+27) 10 248 6000 Fax: (+27) 10 248 6002 E-mail: lgradidge@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31 331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-44-806 8111 Telefax: +41-44-806 8115
Taiwan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
Бізнес Центр Європа Столичне шосе, 103 м. Київ, 03131, Україна Телефон: (+38 044) 237 04 00 Факс.: (+38 044) 237 04 01 E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971 4 8815 166 Telefax: +971 4 8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 4TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 9300 Loiret Blvd. Lenexa, Kansas 66219 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Uzbekistan
Grundfos Tashkent, Uzbekistan The Repre­sentative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292
Addresses Revised 15.01.2019
Grundfos companies
98125976 1119
ECM: 1271284
www.grundfos.com
Trademarks displayed in this material, including but not limited to Grundfos, the Grundfos logo and “be think innovate” are registered trademarks owned by The Grundfos Group. All rights reserved. © 2019 Grundfos Holding A/S, all rights reserved.
Loading...