Grundfos BMS 30-26 HS-E-C-P-A, BMS 46-17 HS-E-C-P-A, BMS 60-17 HS-E-C-P-A, BMS 17-22 HS-E-C-P-A Installation And Operating Instructions Manual

BMS
BMS hs, BMST, BMSX
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Declaration of conformity
Declaration of conformity
GB: EC declaration of conformity
— Machinery Directive (2006/42/EC).
Standard used: EN 809:2009.
— EMC Directive (2004/108/EC).
Standards used: EN 61000-6-2:2005, EN 61000-6-3:2007. This EC declaration of conformity is only valid when published as part of the Grundfos installation and operating instructions (publication number 98567337 1013).
DK: EF-overensstemmelseserklæring
Vi, Grundfos, erklærer under ansvar at produktet BMS som denne erklæring omhandler, er i overensstemmelse med disse af Rådets direktiver om indbyrdes tilnærmelse til EF-medlemsstaternes lovgivning:
— Maskindirektivet (2006/42/EF).
Anvendt standard: EN 809:2009.
— EMC-direktivet (2004/108/EF).
Anvendte standarder: EN 61000-6-2:2005, EN 61000-6-3:2007. Denne EF-overensstemmelseserklæring er kun gyldig når den publiceres som en del af Grundfos-monterings- og driftsinstruktionen (publikations­nummer 98567337 1013).
Bjerringbro, 10th May 2010
Jan Strandgaard
Technical Director
Grundfos Holding A/S
Poul Due Jensens Vej 7
8850 Bjerringbro, Denmark
Person authorised to compile technical file and
empowered to sign the EC declaration of conformity.
2
English (GB) Installation and operating instructions
Caution
Note
Caution
Original installation and operating instructions.
CONTENTS
1. Symbols used in this document
2. Product introduction
2.1 Delivery and handling
2.2 Nameplate
2.3 Commissioning
2.4 Pumped liquids
2.5 Filtration
2.6 Flushing and salinity
2.7 Foundation
3. Before installation
3.1 Reading guide
4. Mechanical installation
4.1 BMS hs pump
4.2 BMST system
4.3 BMSX system
5. Electrical installation
5.1 BMS hs pump
5.2 BMS hp pump
5.3 BMST system
5.4 BMSX system
6. Commissioning
6.1 BMS hs system
6.2 BMST system
6.3 BMSX system
6.4 Low-pressure flow control
7. Shutdown
7.1 BMS hs system
7.2 BMST system
7.3 BMSX system
7.4 Flushing
8. Operation
8.1 Motor bearings
9. Periods of inactivity
9.1 Startup after a period of inactivity
10. Fault finding
10.1 BMS hs and BMST
10.2 BM hp
10.3 Pressure exchanger
11. Checking the motor and cable
12. Technical data
13. Disposal
Page
10
11
11 11 11 11
11
11 12 13 15
15
15 16 16 17
17
17
17
17
18
18 19 20
21 22 22

1. Symbols used in this document

Warnin g If these safety instructions are not observed,
3 3
3 4 4 4 4 4 4
5
5
5
5

2. Product introduction

8
Grundfos BMS, BMST and BMSX booster systems are designed for desalination of seawater or brackish water in reverse osmosis systems, the so-called SWRO systems (SWRO = Sea Water Reverse Osmosis). The design of the systems ensure high energy recovery.

2.1 Delivery and handling

2.1.1 Delivery

The pumps are supplied from the factory in proper packing in which they should remain until installation.

2.1.2 Frost protection

If the pumps have to be stored, the location must be frost-free.
it may result in personal injury.
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Warnin g The sound pressure level is so high that hearing
protection must be used.
Notes or instructions that make the job easier and ensure safe operation.
During delivery and storage, the pumps must never be preserved with glycerine or similar liquids which are aggressive to the pump materials.
English (GB)
Warning Prior to installation, read these installation and
operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
3
English (GB)
Note
N/A
1 2
3 4 5
6
7 8
9
10
11 12 13
1
2
3
4
5
6
Filter

2.2 Nameplate

Fig. 1 Nameplate
Pos. Description
1 Type designation
Model designation:
• generation
2
• product number
• production code (ddmmyy). 3 Rated flow rate 4 Rated head 5 Rated speed 6 Minimum and maximum inlet pressure 7 Maximum discharge pressure 8 Minimum and maximum liquid temperature 9 Net weight of booster module
10 Minimum efficiency index 11 Country of origin 12 CE mark 13 TR mark

2.3 Commissioning

Commissioning of BMSX booster systems must be carried out by certified Grundfos employees to ensure long and trouble-free operation.
If this requirement is not met, the warranty will be invalidated.
Commissioning includes onsite training of the people who will be responsible for maintaining and monitoring the system.

2.4 Pumped liquids

Thin, non-explosive liquids, not containing solid particles or fibres. The liquid must not chemically attack the pump materials. In case of doubt, contact Grundfos.
The pumps must never operate with water/liquid containing substances which would remove the surface tension, e.g. soap. If this type of detergent is used to clean the system, the water/ liquid must be led around the pumps via a bypass.
Warnin g The pumps must not be used for pumping
flammable or combustible liquids such as diesel oil, petrol or similar liquids.

2.5 Filtration

BMS hs, BMST: The raw water must be filtered to maximum 30 microns.
BMSX: The raw water must be filtered to maximum 10 microns.
TM05 9242 3613
Fig. 2 Filtration
Pos. Description
1 Raw-water feed pump 2 Pressure gauge (raw water) 3 Low-pressure switch 4Flowmeter 5 Pressure gauge (fresh-water pump) 6 Fresh-water flush pump
Pump type
Filter
[micron absolute]
BMS hs 30
BM hp 30 BMST 30
Pressure exchanger 10

2.6 Flushing and salinity

When the booster system is stopped, it is very important to flush the system according to these guidelines.
See also the flush procedure in section 9.1.1 Frequency of starts and stops.
Pump type
Fresh water
p
min
[bar]
Max. salinity
[ppm TDS]
BMS hs 2 1000 5-10 BM hp 2 1000 5-10 BMST 2 1000 5-10 Pressure
exchanger
2 1000 5-10

2.7 Foundation

The foundation must be constructed to safely support the booster system or pump(s) under all conditions. The pump and motor must be installed at the same level.
The foundation must be strong enough to support the weight of the both units.

2.7.1 Vibration dampening

The vibration dampeners supplied with the BMS hs pump must be used.
TM05 8862 2813
Flush time
[min.]
4

3. Before installation

Caution
1. Check that the pump has not been damaged during transportation.
2. Check that the type designation corresponds to the order. See the pump nameplate.
3. Compare the motor voltage and frequency details on the motor and frequency converter nameplates with the power supply available.

3.1 Reading guide

Select system/pump type.
English (GB)
System/ pump
BMS hs
BMST
BMSX
Step Action Section
Mechanical
1
installation Electrical
2
installation
3 Commissioning 6.1 BMS hs system.
Mechanical
1
installation Electrical
2
installation
3 Commissioning 6.2 B MST system.
Mechanical
1
installation Electrical
2
installation
3 Commissioning 6.3 BMSX system.
4.1 BMS hs pump.
5.1 BMS hs pump.
4.2 BMST system.
5.3 BMST system.
4.3 BMSX system.
5.4 BMSX system.

4. Mechanical installation

4.1 BMS hs pump

The pump can be mounted directly on the floor or on a base frame (accessory).
Fig. 4 Example of how to lift the motor
The positions of the lifting eyes and the minimum dimensions of the lifting bars are shown below.
Fig. 5 Dimensions of lifting equipment
Horizontal position
Motor
type
200 260 225 300 150
A
[mm]
e
[mm]
260
H
[mm]
165
t
[mm]
25
TM05 9235 3613TM05 9556 3913
Fig. 3 BMS hs pump

4.1.1 Location

To ensure sufficient cooling of the motor, a free space of minimum 100 mm behind the motor (NDE) is required.

4.1.2 Lifting and handling the motor

Warning Observe local regulations concerning limits for
manual lifting or handling.
Use all lifting eyes when lifting the motor, and lower it down slowly.
Warning Use all lifting eyes on the motor, and make sure
that the crane is suitable for the job. Use certified and approved lifting equipment. See nameplate.
TM05 9569 4113
If these instructions are not followed, there is a risk of warping or crushing some equipment such as the terminal box, cover or drip cover.
5

4.1.3 Motor installation

Caution
Caution
English (GB)
Use vibration dampers.
The motor must be level. If there is a gap between the foundation and motor, use a spirit level, a feeler gauge and shims to level the motor. Then secure the motor by means of suitable bolts depending on the foundation.
Direction of rotation
Warning The electrical installation should be carried out
by an authorised person in accordance with local regulations.
Connect the power supply (see section 5. Electrical installation) and check the direction of rotation. The direction of rotation must correspond to the direction under normal operation. See the installation and operating instructions for the motor.

4.1.4 Lifting and handling the pump

Hoist the pump into place, and lower it down slowly.

4.1.5 Alignment of m otor and pump

Align the motor and pump before you tighten the bolts. To ensure correct installation, follow this procedure:
Step Description Picture
Fit all four bolts for motor and pump connection.
1
Do not tighten the bolts yet.
Adjust the gap by means of a feeler gauge or similar tool.
2
Tighten one bolt by hand.
Adjust the gap 180 ° opposite the bolt you just tightened.
3
Do not tighten the bolt. Move the pump to adjust the gap.
TM05 9234 3613
TM05 9232 3613
TM05 9251 3613
Fig. 6 Example of how to lift the pump
Make the pump fit the motor flange. Fit the pump support foot delivered with the product. Lower the pump until the support foot reaches the floor.
Move the pump, and adjust the gap by
TM05 9236 3613
means of the feeler gauge. Tighten the bolt by hand. If the
4
inlet pipe has to be turned, see section
4.1.6 Position of the inlet pipe.
TM05 9345 3613
When the gap has been adjusted, cross-
5
tighten all bolts to 33 Nm.
TM05 9346 3613
Fasten the support
6
foot to the foundation.
TM05 9345 3613
The support foot must not impose any tension on the pump!
6

4.1.6 Position of the inlet pipe

Caution
Caution
Service connector
If you want to change the position of the pipe, follow this procedure.
Step Description Picture
Remove M10 bolts.
1
Loosen M12 bolts.
Mark up the pump
2
sleeve and union nut.
Turn the inlet pipe to the needed position,
3
and make sure the union nut follows.

4.1.7 Flushing the system

To avoid impurities in the pump, flush the pipes before you connect the pump inlet and discharge pipes.

4.1.8 Pipe connection

Both the inlet and the discharge pipe are fitted with clamp liners for Victaulic couplings and must be supported close to the end of the pipe.
TM05 9347 3613
TM05 9573 4013
Fig. 7 Pipe support
Avoid stress in the pipe system.
When fitting the couplings, it is important to allow a gap of 3.5 mm between the two pipes. See fig. 8.
TM05 9343 3613
English (GB)
TM05 9230 3613
4 Check the marking.
Fit all bolts again.
5
Tighten all bolts to 33 Nm.
Fasten the support
6
foot to the foundation.
TM05 9342 3613
TM05 9344 3613
Fig. 8 Gap between pipes
TM05 9343 3613
TM05 9345 3613
7
Discharge pipe
Caution
Caution
English (GB)
In order to facilitate service of the pump and motor, it is important that the delivered service connector is built into the system.
1. Fit the two rubber parts.
2. Install the service connector.

4.2 BMST system

A BMST system is built by using a BMS hs as primary pump and a BMT as secondary pump. The BMT pump is driven by the high­pressure concentrate from the membrane and used as feed pump for the primary BMS hs pump.
Fig. 9 Position of rubber parts
3. Move the two rubber parts over the service connector.
Fig. 10 Position of service connector and rubber parts
4. Fit the Victaulic couplings and tighten the bolts to 33 Nm.
TM05 9339 3613TM05 9340 3613TM05 9341 3613
Fig. 12 BMST system
Fig. 13 BMT pump

4.2.1 BMS hs pump installation

See section 4.1 BMS hs pump.

4.2.2 Lifting and handling the BMT pump

1. Hoist the pump into place, and lower it down slowly.
2. Install and secure the pump.
3. Support the pump close to the turbine, using the bracket behind the turbine housing.
4. Use a clamp or similar device at the other end. See the example in fig. 12.

4.2.3 BMT pump installation

Use vibration dampers.
The BMT pump must be level. If there is a gap between the foundation/frame and the BMT pump, use a spirit level, a feeler gauge and shims to level the pump. Then secure the pump by means of suitable bolts depending on the foundation/frame.

4.2.4 Flushing the system

TM05 9334 3613TM05 9350 3613
To avoid impurities in the pump, flush the pipes before you connect the pump inlet and discharge pipes.
Fig. 11 Victaulic couplings
If installing a BMS hs pump, you are now ready for electrical installation. See section 5.1 BMS hs pump.
If building a BMST system, see section 4.2.2 Lifting and handling the BMT pump.
If building a BMSX system, see section 4.3.2 Installation of BM hp pump.
8

4.2.5 Inlet and discharge pipes (BMT and BMS hs pump)

Caution
Caution
Caution
Min. 300 mm
Min. 30°
Service connector
The inlet and discharge pipes are fitted with clamp liners for Victaulic couplings.
To ensure correct installation, follow this procedure.
Step Description Picture
The turbine is driven by the high-pressure concentrate from the membrane.
1
Connect the high­pressure outlet to the BMT pump’s turbine inlet.
English (GB)
TM05 9474 5107
TM05 9334 3613
Fig. 14 Drain from Pelton turbine
The concentrate outlet must be free under all operating conditions.
Connect the BMT
2
pump inlet.
Connect the BMT
3
pump and BMS hs pump.
Connect the hose (300) to the outlet of the turbine housing with a strap. Lead the hose to a drain tank, drain channel or a
4
similar drain. Fit the end of the hose above the highest possible water level in the drain. The hose should be supported.
The concentrate from the turbine must be able to flow freely to a drain under all operating conditions. The minimum height above the water level in the drain must be 300 mm. The tube from the turbine to the drain must have the same diameter in its entire length. The drain must be larger than the tube and open so that the concentrate, a mixture of air and water (foam), can escape freely.
If a discharge pipe is connected to the concentrate outlet, this pipe must have an air outlet.

4.2.6 Pipe connection

Both the inlet and the discharge pipe must be supported close to the end of the pipe.
TM05 9375 3613
TM05 9336 3613
Fig. 15 Horizontal and vertical support of pipes
Avoid stress in the pipe system.
When fitting the couplings, it is important to allow a gap of 3.5 mm between the two pipes. See fig. 16.
TM05 9337 3613
TM05 9230 3613
TM05 9344 3613
Fig. 16 Position of clamp liners
9

4.3 BMSX system

Caution
Caution
English (GB)
A BMSX system is built by using a BMS hs pump as high­pressure pump and a BM hp pump as booster pump. The pressure exchanger is installed in order to recover energy from the high-pressure concentrate.

4.3.5 Pipe connection

Low-pressure and high-pressure inlet and discharge pipes are fitted with clamp liners for Victaulic couplings. See the pipe location on the unit.
Both the inlet and the discharge pipes must be supported close to the end of the pipes.
TM05 9348 3613
Fig. 19 Horizontal and vertical support of pipes
Fig. 17 BMSX system

4.3.1 Installation of BMS hs pump

See section 4.1 BMS hs pump.

4.3.2 Installation of BM hp pump

See the installation and operating instructions for Grundfos BM and BM hp.

4.3.3 Pressure exchanger

Fig. 18 Pressure exchanger
Lifting and handling the pressure exchanger
Warning Observe local regulations concerning limits for
manual lifting or handling.
Use suitable straps when lifting the unit. Carefully hoist the pressure exchanger into place, and lower it down. Secure the unit(s) to a frame, and ensure a stress-free installation.
TM05 9569 4113 - TM05 9571 4113 - TM05 9570 4113 - Gr0559Gr-1015354
Avoid stress in the pipe system.
When fitting the couplings, it is important to allow a gap of 3.5 mm between the two pipes.
Warning Make sure the crane is suitable for the job.
Use certified and approved lifting equipment. See nameplate.

4.3.4 Flushing the system

To avoid impurities in the pump, flush the pipes before you connect the pump inlet and discharge pipes.
10

5. Electrical installation

1
2
3
4
5
6
7
8
12
13
11
9
14
15
10
Warning Make sure that the power supply cannot be
accidentally switched on during electrical installation.
The pump must be connected to an external mains switch with a minimum contact gap of 3 mm in all poles.
The pump must be earthed.
The electrical connection must be carried out by an authorised electrician in accordance with local regulations and the diagrams for the motor protection, starter and monitoring devices used. The electrical connections are made in the terminal box.
Wiring must be done according to the wiring diagram supplied with the Grundfos product.

5.1 BMS hs pump

See the installation and operating instructions for the drive and motor.
If installing a BMS hs pump, you are now ready for commissioning. See section 6.1 BMS hs system.

5.2 BMS hp pump

See the installation and operating instructions for Grundfos BM and BM hp.
See the nameplate to identify the motor type and type of control board.

6. Commissioning

These commissioning guidelines concern systems only.
– BMS hs system. – BMST system (see section 6.2 BMST system). – BMSX system (see section 6.3 BMSX system).
Warnin g The sound pressure level is so high that hearing
protection must be used.

6.1 BMS hs system

6.1.1 Before startup

Follow these instructions to ensure correct startup of the BMS hs system.
Check the following:
1. greasing of the motor bearings
2. power supply compared to the nameplate.
English (GB)

5.3 BMST system

See section 5.1 BMS hs pump. If installing a BMS hs pump, you are now ready for
commissioning. See section 6.2 BMST system.

5.4 BMSX system

See sections 5.1 BMS hs pump and 5.2 BMS hp pump. If installing a BMS hs pump, you are now ready for
commissioning. See section 6.3 BMSX system.
TM05 8860 2813
Fig. 20 Example of BMS hs booster system
Pos. Description
1 Raw-water feed pump 2 Pressure gauge (raw water) 3Filter 4 Low-pressure switch 5Flowmeter 6 BMS hs pump 7 High-pressure switch 8 Pressure gauge (BMS hs discharge pressure)
9Air vent 10 Pressure relief valve 11 Membrane filter 12 Permeate 13 Pressure control valve 14 Pressure gauge (fresh-water pump) 15 Fresh-water flush pump
11

6.1.2 Startup

Note
Caution
Caution
2
3
1
4
rpm
3 seconds
t [seconds]
1700
1
2
4
3
5
6
6.1
7
14
13
12
15
16
8
109
11
English (GB)
If a discharge valve is installed, we recommend that you open the valve 1/4 of a turn when starting the pump/system.
Never operate pumps against a closed valve.
To start up a BMS hs system, proceed as follows:
1. Start the feed pump (1), and check that the inlet pressure (2) of the BMS hs pump (6) is higher than 1.0 bar (10 metres head) and lower than 35.0 bar (350 metres head).
2. Vent the BMS hs pump (6).
3. Start the BMS hs pump (6). Ramp up the BMS hs pump (6) according to factory settings. See fig. 21 (1 and 2).
Ensure a ramp-up time of 0-1700 rpm within 3 seconds.

6.2 BMST system

6.2.1 Before startup

Follow these instructions to ensure correct startup of the BMST system.
Check the following:
1. greasing of the motor bearings
2. power supply compared to the nameplate
3. pipework compared to the diagram.
Fig. 21 Ramp up
Default ramp-up time:
• 0 to 1700 rpm max. 3 seconds (1).
• Ramp up from 1700 rpm is set to 1500 rpm per minute (2).
4. Set the discharge pressure of the pump (8) to the desired value. See fig. 20.
5. Check that the inlet pressure (2) of the pump is higher than
1.0 bar (10 metres head) and lower than 35.0 bar (350 metres head).
Make sure that the BMS hs pump is protected by a low-pressure switch or flow switch.
TM05 8860 2813
TM05 8861 2813
Fig. 22 Example of BMST booster system
Pos. Description
1 Raw-water feed pump 2 Pressure gauge (raw water) 3Filter 4 Low-pressure switch 5Flowmeter 6 BMT pump
6.1 BMS hs pump 7 Pressure gauge (BMST discharge pressure) 8Flowmeter 9Air vent
10 High-pressure switch 11 Pressure relief valve 12 Membrane filter 13 Permeate 14 Pressure gauge (high-pressure concentrate) 15 Pressure gauge (fresh-water pump) 16 Fresh-water flush pump
12

6.2.2 Startup

Caution
Caution
1
2
3
4
16
15
14
12
8
9
10
11
18
19
20
13
21
22
24
23
17
5
6
7
25
26
To start up a BMST system, proceed as follows:
1. Start the raw-water feed pump (1), and check that the inlet pressure (2) of the pump is higher than 2.0 bar (20 metres head) and lower than 5.0 bar (50 metres head).
2. Vent the BMT pump (6). The pump is fully vented when liquid runs out of the air vent (9).
3. Start the BMS hs pump (6.1). See section 6.1.2 Startup.
4. Set the discharge pressure (7) of the pump to the desired value.
5. Check that the inlet pressure (2) of the pump is higher than
2.0 bar (20 metres head) and lower than 5.0 bar (50 metres head).
6. The system is now ready for operation.
Make sure that the BMS hs pump is protected by a low-pressure switch or flow switch.
Ensure a ramp-up time of 0-1700 rpm within 3 seconds.

6.3 BMSX system

6.3.1 Flow control and balancing

Flow rates and pressures in a typical BMSX system vary slightly over the life of the system due to temperature variations, membrane fouling and feed salinity variations. The rotor of the pressure exchanger is powered by the flow of fluid through the unit. The speed of the rotor is self-adjusting over the operating range of the pressure exchanger pump.

6.3.2 Before startup

Follow these instructions to ensure correct startup of the BMSX system.
Check the following:
1. greasing of the motor bearings (see nameplate)
2. power supply compared to the nameplate
3. pipework compared to the diagram.
Fig. 23 Example of BMSX booster system
English (GB)
TM05 8856 3713
Pos. Description
1 Raw-water feed pump 2Filter 3 Low-pressure switch 4Flowmeter 5 Pressure gauge (raw water) 6 BMS hs pump 7 Non-return valve 8 Pressure gauge (BMS hs discharge pressure)
9Air vent 10 High-pressure switch 11 Pressure relief valve 12 Pressure gauge (BM hp inlet pressure) 13 Pressure gauge (BM hp discharge pressure) 14 BM hp pump 15 Flowmeter (high-pressure raw water) 16 Pressure gauge (low-pressure raw water) 17 Flowmeter (low-pressure raw water) 18 Membrane filter 19 Permeate 20 Cleaning flush valve. 21 Pressure gauge (high-pressure concentrate) 22 Pressure gauge (low-pressure concentrate) 23 Pressure exchanger 24 Concentrate valve 25 Pressure gauge (fresh-water pump) 26 Fresh-water flush pump
13

6.3.3 Startup

Caution
1
2
3
4
16
15
14
12
8
7
9
10
18
19
20
13
21
22
24
23
17
5
6
25
26
11
Note
1
2
3
4
16
15
14
12
8
7
9
10
18
19
20
13
21
22
24
23
17
5
6
25
26
11
1
2
3
4
16
15
14
12
8
7
9
10
18
19
20
13
21
22
24
23
17
5
6
25
26
11
English (GB)
To start up a BMSX system, proceed as follows:
1. All valves should be in their normal operating positions.
2. Start the raw-water feed pump (1). When the raw-water feed pump is started, the system is filled with water. Ensure that the entire system is vented. The feed flow (17) (max. 10 bar, min. 2 bar feed pressure) through the pressure exchanger pump (23) may or may not cause the rotor to begin to rotate. Rotation will be confirmed by a humming noise.
Fig. 24 Start the seawater feed pump
TM05 8864 2813TM05 8864 2813
Fig. 25 System pressure and flow, BM hp
The rotor speed will increase, and remaining air will be released from the pressure exchanger. Vent any remaining air from the system.
Adjust the frequency converter of the BM hp pump (14) on the discharge side of the pressure exchanger (23) until the low­pressure seawater inlet flow (17) equals the calculated seawater flow (15).
TM05 8863 2813
3. Adjust the concentrate valve (24) to the system flow.
4. Vent the system.
5. When you have filled the system with water and vented it, then see the BM hp startup procedure.
The maximum flow rate of the pressure exchanger must never be exceeded. See the nameplate of the pressure exchanger.
The BM hp pump must not run against a closed discharge valve for more than 5 seconds as this will cause an increase in the temperature/ formation of steam in the pump which may damage the pump and motor. If there is any risk of the BM hp pump running against a closed discharge valve or risk of no flow, ensure a minimum liquid flow through the pump by connecting a bypass/drain to the discharge side of the pump. The drain can be connected to a tank.
6. Start the BM hp pump (14).
14
Fig. 26 Balanced flows
To achieve a balanced flow through the pressure exchanger (23), use the flowmeters installed on the low-pressure seawater inlet pipe (17) and the high-pressure seawater pipe (15). All flows in and out of the pressure exchanger (23) should be balanced to within 5 % for optimum operation.
Operating the pressure exchanger with unbalanced flows may result in contamination of the seawater feed by the concentrate and consequently lower efficiency.
A lower flow in the seawater inlet than the seawater discharge will
Caution
1
2
3
4
16
15
14
12
7
9
8
10
18
19
20
13
21
22
24
23
17
5
6
25
26
11
Caution
Caution
Note
Note
1
2
3
4
5
6
7
8
12
13
11
9
14
15
10
1000 ppm TDS
2
3
1
4
rpm
3 seconds
t [seconds]
1700
result in lower-quality permeate, increased feed pressure and higher energy consumption. We recommend that you use a slightly oversized BM hp pump (14) to handle projected membrane concentrate flows, taking into account seasonal variations, membrane fouling and manifold losses. The flow and pressure of the BM hp pump (14) must be controlled with a frequency converter.
Neither the low-pressure nor the high-pressure flow through the pressure exchanger must ever exceed the rated maximum flow. The only reliable way to determine the flows is to use a low­pressure flowmeter (16) or a high-pressure flowmeter (14), respectively.
To start up the BMS hs pump, proceed as follows:
1. Start the BMS hs (6). See section 6.1.2 Startup.

7. Shutdown

Carefully follow these instructions to safely shut down your booster system.

7.1 BMS hs system

This procedure describes how to shut down the BMS hs system.
English (GB)
TM05 8860 2813TM05 8860 2813
Fig. 28 Example of BMS hs system
Procedure
1. Ramp down the BMS hs pump (6) according to factory settings. See fig. 29 (3 and 4).
Fig. 27 System in operation
The BMSX system pressure will increase. The sound pressure level from the pressure exchanger (23) will increase. Small variations in sound pressure level and rotor speed are normal.

6.4 Low-pressure flow control

The concentrate valve (24) on the discharge side of the system must be adjusted to control the flow rate of the low-pressure seawater inlet (17) and low-pressure concentrate discharge (22) (min. 1 bar backpressure). This valve (24) also adds backpressure on the pressure exchanger (23) required to prevent destructive cavitation. The low-pressure seawater inlet flow (17) equals the high-pressure concentrate inlet flow (15).
TM05 8857 2813
Fig. 29 Ramp down
Ramp down from 1700 to 0 rpm in 3 seconds.
2. Stop the seawater feed pump (1).
3. Start the fresh-water flush pump (15), and flush the system with fresh water (14) (min. 2 bar for flushing).
4. Flush the system for 5 to 10 minutes or until the salinity is lower than 1000 ppm TDS.
5. Stop the fresh-water pump (15).
6. Close all valves to keep the fresh water in the system during shutdown.
To flush the thrust bearing of the BMS hs pump, start the pump for 30 seconds to allow the fresh water to enter into the thrust bearing.
If the flushing takes more than 10 minutes, the flow must be reduced to maximum 10 % of the rated flow rate.
During periods of inactivity, the pump must be filled with clean fresh water.
15

7.2 BMST system

Caution
Note
Note
1
2
4
3
5
6
6.1
7
14
13
12
15
16
8
109
11
Note
Note
Caution
1
2
3
4
16
15
14
12
8
9
10
11
18
19
20
13
21
22
24
23
17
5
6
7
25
26
1000 ppm TDS
English (GB)
This procedure describes how to shut down the BMST system.
Fig. 30 Example of BMST system

7.3 BMSX system

This procedure describes how to shut down the BMSX system.
TM05 8861 2813
Procedure
1. Ramp down the BMS hs pump (6.1) according to factory settings.
2. Stop the seawater feed pump (1).
3. Start the fresh-water flush pump (16), and flush the system with fresh water (15) (min. 2 bar for flushing).
4. Flush the system for 5 to 10 minutes or until the salinity is lower than 1000 ppm TDS.
5. Stop the fresh-water pump (16).
6. Close all valves to keep the fresh water in the system during shutdown.
To flush the thrust bearing of the BMS hs pump, start the pump for 30 seconds to allow the fresh water to enter into the thrust bearing.
If the flushing takes more than 10 minutes, the flow must be reduced to maximum 10 % of the rated flow rate.
During periods of inactivity, the pump must be filled with clean fresh water.
Fig. 31 Example of BMSX system
Procedure
1. Ramp down and stop the BMS hs pump (6).
See section 7.1 BMS hs system.
2. Ramp down and stop the BM hp pump (14).
3. Stop the seawater feed pump (1).
4. Start the fresh-water flush pump (26), and flush the system with fresh water (15) (min. 2 bar for flushing).
5. Start the BM hp pump (14), ramp it up to 25 Hz and let it run for 5 to 10 minutes or until the salinity is lower than 1000 ppm TDS. To ensure efficient flushing of the system, open the valve (20).
6. Start the BMS hs pump (6) and ramp it up to minimum 1700 rpm or until the salinity is lower than 1000 ppm TDS.
If the flushing takes more than 10 minutes, the flow must be reduced to maximum 10 % of the rated flow rate.
During periods of inactivity, the pump must be
TM05 8856 3713
filled with clean fresh water.
7. Stop the BMS hs pump (6), the BM hp pump (14) and the fresh-water flush pump (26).
8. Close all valves to keep the fresh water in the system during shutdown.
9. If the system is taken out of operation for a longer period, precautions should be taken to inhibit biological growth. The system units should receive a final flush with the same solution used to preserve the membranes.
To flush the thrust bearing and shaft seal of the BMS hs pump, start the pump for minimum 30 seconds to allow the fresh water to enter into the thrust bearing housing.
16

7.4 Flushing

Note
Caution
Caution
BMS pumps can be flushed in the flow direction. Flushing of the booster pumps is very important, especially when
the pumps are used for pumping salt water or water with chemicals.
If salt water is left in the pumps while they are stopped, there is a risk of crevice corrosion of the stainless steel.
If water containing chemicals is left in the pumps while they are stopped, the rubber parts of the pump or motor may be affected.
In case the cleaning solution contains chemicals which may affect the rubber in the pump and motor, a bypass must be installed.

8. Operation

Check the following at suitable intervals:
• flow rate and pressure
• whether the noise level has changed. We recommend that you write the operating data in a log book as
they may be useful in connection with maintenance.

8.1 Motor bearings

The pumps are factory-fitted with a manual motor-bearing greasing system. For greasing intervals, etc., see the motor nameplate or the installation and operating instructions supplied with the motor.
8.1.1 Type of grease
As standard, the grease type is EXXON MOBILE POLYREX EM103, and we recommend that you use this type for subsequent lubrication.
Avoid mixing greases.

9. Periods of inactivity

Prior to periods of inactivity, various precautions must be taken to protect the system.
The specific precautions to be taken if the system is to be inactive for a certain period appear from the table:
Action
Flush the pump. See section
9.1.1 Frequency of starts and stops.
Fill the pump with fresh water.
Preserve the pump.* x x Rotate the pump
and motor shafts manually once a month.
* Use the same solution that is used to preserve the
membranes.
The normal stop procedure must be followed step by step.
More than
30 minutes
xxx
xxx

9.1 Startup after a period of inactivity

The normal startup procedure must be followed step by step. For greasing of motor bearings, see section 8.1 Motor bearings.

9.1.1 Frequency of starts and stops

We recommend: minimum 1 per year
maximum 5 per hour maximum 20 per day.
More than
1 month
More than
3 months
x
English (GB)
17

10. Fault finding

English (GB)

10.1 BMS hs and BMST

Fault Possible cause Remedy
1. The pump stops/starts occasionally during operation.
2. The pump stops during operation.
3. The pump runs, but generates no pressure and delivers no water.
4. The pump runs at reduced capacity.
Warnin g Before starting work on the product, switch off
the power supply. Make sure that the power supply cannot be accidentally switched on.
a) No water supply.
The low-pressure switch has cut out.
a) The fuses are blown. After a cut-out, the cause of a possible short circuit must
b) The frequency converter has tripped. Reset the frequency converter. c) The motor/supply cable is defective. Check the motor and cable. a) No or insufficient water supply to the pump. Check that the inlet pressure during operation is at least
b) The pipe system, pump or nozzle is clogged. Check the pipe system, pump and nozzle. c) The prefilter is clogged. Clean the prefilter. a) The valves on the discharge side are partly
closed or blocked.
b) The discharge pipe is partly blocked by
impurities.
c) The pump is partly blocked by impurities. Pull the pump out of the sleeve. Dismantle, clean and
d) The pump is defective. Pull the pump out of the sleeve. Dismantle, clean and
e) The prefilter is clogged. Clean the prefilter.
Check that the low-pressure switch functions normally and is adjusted correctly. Check that the minimum inlet pressure is correct. If not, check the feed pump. See section 6.1.2 Startup.
be found. If the fuses are hot when they are replaced, check that the load of the individual phases does not exceed the motor current during operation. Identify the cause of the load. If the fuses are not hot immediately after the cut-out, then identify the cause of a possible short-circuit. Check all fuses in the control circuit and replace defective fuses.
1 bar for BMS hs and 2 bar for BMST. If so, the water supply is OK. Stop and vent the system. Restart the pump as described in sections 6.1 BMS hs system and 6.2 BMST system. Check the functioning of the pump.
Check the valves.
Clean or replace the discharge pipe. Measure the discharge pressure and compare the value with the calculated data. See the "Technical specifications" supplied with the system.
check the pump. Replace any defective parts.
check the pump. Replace any defective parts.
18

10.2 BM hp

Warnin g Before starting work on the product, switch off
the power supply. Make sure that the power supply cannot be accidentally switched on.
Fault Possible cause Remedy
1. The pump stops occasionally during operation.
2. The pump does not run. a) The fuses are blown. After a cut-out, the cause of a possible short circuit must
3. The pump runs, but generates no pressure and delivers no water.
4. The pump runs at reduced capacity (flow and pressure).
a) No or insufficient water supply. The pressure
switch has cut out.
b) The capacity is too small. The flow switch
has cut out.
b) The frequency converter has tripped. Reset the unit. c) The motor/supply cable is defective. Check the motor and cable. See section 5. Electrical
a) No or insufficient water supply to the pump
or air in the system.
b) The inlet parts are blocked. Pull the pump out of the sleeve and clean the inlet parts. a) The valves on the discharge side are partly
closed or blocked.
b) The discharge pipe is partly blocked by
impurities.
c) The pump is partly blocked by impurities. Pull the pump out of the sleeve. Dismantle, clean and
d) The pump is defective. Pull the pump out of the sleeve. Dismantle, clean and
Check that the pressure switch functions normally (without delay) and is adjusted correctly. Check that the minimum inlet pressure is correct.
The discharge pipe is totally or partly blocked due to incorrect adjustment of a manually operated valve or failure in the solenoid valve or the motor-operated valve. Check these valves. The flow switch is faulty or incorrectly adjusted. Check/adjust the switch.
be found. If the fuses are hot when they are replaced, check that the load of the individual phases does not exceed the motor current during operation. Identify the cause of the load. If the fuses are not hot immediately after the cut-out, then identify the cause of a possible short-circuit. Check all fuses in the control circuit and replace defective fuses.
installation. Check that the inlet pressure during operation is at least
1 bar. If so, the water supply is OK. Stop and vent the system. Restart the system as described in section
6.3 B MSX system . If the pump is defective, dismantle and repair/replace it.
Check the valves.
Measure the discharge pressure and compare the value with the calculated data. Clean or replace the discharge pipe.
check the pump. Replace defective parts.
check the pump. Replace defective parts.
English (GB)
19

10.3 Pressure exchanger

English (GB)
Fault Possible cause Remedy
1. Excessive sound pressure level.
2. Excessively high recovery in the SWRO system.
3. High salinity in the high-pressure seawater feed stream.
4. The low-pressure flow is lower than the high­pressure flow which entails mixing and high feed-water salinity.
5. Stalled rotor (no audible rotation).
6. Low concentrate flow. a) Excessive pressure losses through the
Warning Before starting work on the product, switch off
the power supply. Make sure that the power supply cannot be accidentally switched on.
a) The pressure exchanger operates above the
rated flow rates on the low-pressure side, high-pressure side or both.
b) The pressure exchanger pump operates with
little or no backpressure.
c) Air in the system. Vent the system. a) The BMS hs pump is operating at a flow rate
that is too high.
b) Increased salinity or raw-water temperature. Adjust flow rates in the system. See section 7.3 BMSX
a) Unbalanced system. See section 6.3 BMSX system. b) A jammed or stalled rotor short-circuits the
high-pressure concentrate with the high­pressure feed water. No exchange occurs; no audible rotation.
a) Operating pressure exchanger pumps below
the rated flow rate results in low rotor rotation and increased mixing.
b) Malfunctioning and/or stalled BM hp pump. Check the rotation, operation, flow rates and pressures
a) The system operates above the rated
pressure or below the rated flow capacity.
b) Debris or foreign particles in the device. Contact Grundfos Service Department. c) The system is not properly flow-balanced. See section 6.3 BMSX system.
SWRO system.
b) Malfunctioning and/or stalled BM hp pump. Check the operation, flow rates and pressures of the BM
Immediately reduce the flow rate by adjusting the BM hp pump and control valve (13). Balance the system as described in section 6.3 BMSX system. To increase the system capacity, add pressure exchanger pump(s) in parallel to the existing pumps.
Increase the backpressure by adjusting the concentrate valve. Balance the system as described in section 6.3 BMSX system.
Check that the main BMS hs flow rate does not exceed the membrane array production capacity for a given temperature, salinity and fouling factor.
system.
See fault number 5.
Increase and balance the flows through the pressure exchanger pump. Do not exceed the recommended maximum flow rates. To increase the system capacity, add pressure exchanger pump(s) in parallel to the existing pumps. See section 6.3 BMSX system.
of the BM hp pump. See section 6.3 BMSX system.
Contact Grundfos.
hp pump.
20

11. Checking the motor and cable

1. Supply voltage
When the motor is loaded, the voltage should be within ± 5 % of the rated voltage. If the voltage varies more
than that, the motor may burn. Measure the voltage between the phases with a voltmeter. Connect the voltmeter to the terminals of the frequency converter.
If the voltage is constantly too high or too low, the
motor must be replaced by a motor that corresponds to
the supply voltage.
Large variations in the supply voltage indicate poor
power supply, and the pump should be stopped until
the defect has been found.
TM00 1371 3597
2. Current consumption
It may be necessary to reset the frequency converter.
The difference between the current of the phase with
the highest amp consumption and the one with the
lowest amp consumption must not exceed 10 % of the
Measure the current of each phase while the pump is operating at a constant discharge pressure (if possible at the capacity where the motor is most heavily loaded). For information on the normal operating current, see the "Technical specifications".
lowest amp consumption.
If it does, or if the current exceeds the full-load current,
check these possible faults:
• A damaged pump is causing the motor to be overloaded. Pull the pump out of the sleeve for overhaul.
• The motor windings are short-circuited or partly disjointed.
• Too high or too low supply voltage.
TM00 1372 3597
• Poor connection in leads. Weak cables.
Points 3 and 4: Measurement not needed if supply voltage and current consumption are normal.
3. Winding resistance
Remove the phase leads from the terminal box. Measure the winding resistance as shown in the drawing.
The highest value must not exceed the lowest value by more than 5 %. If the deviation is larger, and the supply cable is OK, the motor should be overhauled.
English (GB)
4. Insulation resistance
TM00 1373 3597
Remove the phase leads from the terminal box. Measure the insulation resistance from each phase to earth (frame). (Make sure that the earth connection is made carefully.)
TM00 1374 3597
The insulation resistance for a new, cleaned or repaired motor must be approx. 10 MΩ measured to earth. For a given motor the critical insulation resistance (R
) can be calculated as follows:
crit
R
= UN [kV] x 0.5 [MΩ/kV].
crit
If the measured insulation resistance is lower than R
, the motor must be overhauled.
crit
21

12. Technical data

English (GB)
See motor and pump nameplates.
Sound pressure level, inlet pressure and temperatures
Sound
Pump type
BMS 17-22 HS-E-C-P-A 88 BMS 17-22 HS-E-C-P-A 88 BMS 17-22 HS-E-C-P-A 88 BMS 17-22 HS-E-C-P-A 88 BMS 17-22 HS-E-C-P-A 83 BMS 17-22 HS-E-C-P-A 83 BMS 17-22 HS-E-C-P-A 83 BMS 17-22 HS-E-C-P-A 83 BMS 30-26 HS-E-C-P-A 88 BMS 30-26 HS-E-C-P-A 88 BMS 30-26 HS-E-C-P-A 83 BMS 30-26 HS-E-C-P-A 83 BMS 46-17 HS-E-C-P-A 88 BMS 46-17 HS-E-C-P-A 83 BMS 46-17 HS-E-C-P-A 83 BMS 46-17 HS-E-C-P-A 83 BMS 60-17 HS-E-C-P-A 83
Sound
Pump type
BMST 105 1 35
Pressure exchanger
* If the ambient temperature is higher than the values stated,
please contact Grundfos.
pressure
level
[dB(A)]
76-91
pressure
level
[dB(A)]
Min./max. inlet
Low
pressure
Min./max.
inlet
pressure
[bar]
1/35 40*
pressure
[bar]
High
pressure
2-7 80
Max. liquid/
ambient
temperature
[°C]
Max. liquid/
ambient
temperature
[°C]
40*

13. Disposal

This product or parts of it must be disposed of in an environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or service workshop.
Subject to alterations.
22
Argentina
Bombas GRUNDFOS de Argentina S.A. Ruta Panamericana km. 37.500 Centro Industrial Garin 1619 Garín Pcia. de B.A. Phone: +54-3327 414 444 Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155
Austria
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30
Belgium
N.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301
Belarus
Представительство ГРУНДФОС в Минске 220125, Минск ул. Шафарнянская, 11, оф. 56 Тел.: +7 (375 17) 286 39 72, 286 39 73 Факс: +7 (375 17) 286 39 71
E-mail: minsk@grundfos.com
Bosnia/Herzegovina
GRUNDFOS Sarajevo Trg Heroja 16, BiH-71000 Sarajevo Phone: +387 33 713 290 Telefax: +387 33 659 079 e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL Av. Humberto de Alencar Castelo Branco, 630 CEP 09850 - 300 São Bernardo do Campo - SP Phone: +55-11 4393 5533 Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD Slatina District Iztochna Tangenta street no. 100 BG - 1592 Sofia Tel. +359 2 49 22 200 Fax. +359 2 49 22 201 email: bulgaria@grundfos.bg
Canada
GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512
China
GRUNDFOS Pumps (Shanghai) Co. Ltd. 50/F Maxdo Center No. 8 XingYi Rd. Hongqiao development Zone Shanghai 200336 PRC Phone: +86 21 612 252 22 Telefax: +86 21 612 253 33
Croatia
GRUNDFOS CROATIA d.o.o. Cebini 37, Buzin HR-10010 Zagreb Phone: +385 1 6595 400 Telefax: +385 1 6595 499 www.grundfos.hr
Czech Republic
GRUNDFOS s.r.o. Čajkovského 21 779 00 Olomouc Phone: +420-585-716 111 Telefax: +420-585-716 299
Denmark
GRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: info_GDK@grundfos.com www.grundfos.com/DK
Estonia
GRUNDFOS Pumps Eesti OÜ Peterburi tee 92G 11415 Tallinn Tel: + 372 606 1690 Fax: + 372 606 1691
Finland
OY GRUNDFOS Pumput AB Mestarintie 11 FIN-01730 Vantaa Phone: +358-(0)207 889 900 Telefax: +358-(0)207 889 550
France
Pompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51
Germany
GRUNDFOS GMBH Schlüterstr. 33 40699 Erkrath Tel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799 e-mail: infoservice@grundfos.de Service in Deutschland: e-mail: kundendienst@grundfos.de
HILGE GmbH & Co. KG Hilgestrasse 37-47 55292 Bodenheim/Rhein Germany Tel.: +49 6135 75-0 Telefax: +49 6135 1737 e-mail: hilge@hilge.de
Greece
GRUNDFOS Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O . B o x 7 1 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273
Hong Kong
GRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664
Hungary
GRUNDFOS Hungária Kft. Park u. 8 H-2045 Törökbálint, Phone: +36-23 511 110 Telefax: +36-23 511 111
India
GRUNDFOS Pumps India Private Limited 118 Old Mahabalipuram Road Thoraipakkam Chennai 600 096 Phone: +91-44 2496 6800
Indonesia
PT GRUNDFOS Pompa Jl. Rawa Sumur III, Blok III / CC-1 Kawasan Industri, Pulogadung Jakarta 13930 Phone: +62-21-460 6909 Telefax: +62-21-460 6910 / 460 6901
Ireland
GRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business Park Ballymount Road Lower Dublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830
Italy
GRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4 I-20060 Truccazzano (Milano) Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461
Japan
GRUNDFOS Pumps K.K. Gotanda Metalion Bldg., 5F, 5-21-15, Higashi-gotanda Shiagawa-ku, Tokyo 141-0022 Japan Phone: +81 35 448 1391 Telefax: +81 35 448 9619
Korea
GRUNDFOS Pumps Korea Ltd. 6th Floor, Aju Building 679-5 Yeoksam-dong, Kangnam-ku, 135-916 Seoul, Korea Phone: +82-2-5317 600 Telefax: +82-2-5633 725
Latvia
SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60, LV-1035, Rīga, Tālr.: + 371 714 9640, 7 149 641 Fakss: + 371 914 9646
Lithuania
GRUNDFOS Pumps UAB Smolensko g. 6 LT-03201 Vilnius Tel: + 370 52 395 430 Fax: + 370 52 395 431
Malaysia
GRUNDFOS Pumps Sdn. Bhd. 7 Jalan Peguam U1/25 Glenmarie Industrial Park 40150 Shah Alam Selangor Phone: +60-3-5569 2922 Telefax: +60-3-5569 2866
Mexico
Bombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010
Netherlands
GRUNDFOS Netherlands Velu we zo om 35 1326 AE Almere Postbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 E-mail: info_gnl@grundfos.com
New Zealand
GRUNDFOS Pumps NZ Ltd. 17 Beatrice Tinsley Crescent North Harbour Industrial Estate Albany, Auckland Phone: +64-9-415 3240 Telefax: +64-9-415 3250
Norway
GRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50
Poland
GRUNDFOS Pompy Sp. z o.o. ul. Klonowa 23 Baranowo k. Poznania PL-62-081 Przeźmierowo Tel: (+48-61) 650 13 00 Fax: (+48-61) 650 13 50
Portugal
Bombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241 Apartado 1079 P-2770-153 Paço de Arcos Tel.: +351-21-440 76 00 Telefax: +351-21-440 76 90
Romania
GRUNDFOS Pompe România SRL Bd. Biruintei, nr 103 Pantelimon county Ilfov Phone: +40 21 200 4100 Telefax: +40 21 200 4101 E-mail: romania@grundfos.ro
Russia
ООО Грундф ос Россия, 109544 Москва, ул. Школьная
39
Тел. (+7) 495 737 30 00, 564 88 00 Факс (+7) 495 737 75 36, 564 88 11
E-mail grundfos.moscow@grundfos.com
Serbia
GRUNDFOS Predstavništvo Beograd Dr. Milutina Ivkovića 2a/29 YU-11000 Beograd Phone: +381 11 26 47 877 / 11 26 47 496 Telefax: +381 11 26 48 340
Singapore
GRUNDFOS (Singapore) Pte. Ltd. 25 Jalan Tukang Singapore 619264 Phone: +65-6681 9688 Telefax: +65-6681 9689
Slovenia
GRUNDFOS d.o.o. Šlandrova 8b, SI-1231 Ljubljana-Črnuče Phone: +386 1 568 0610 Telefax: +386 1 568 0619 E-mail: slovenia@grundfos.si
South Africa
GRUNDFOS (PTY) LTD Corner Mountjoy and George Allen Roads Wilbart Ext. 2 Bedfordview 2008 Phone: (+27) 11 579 4800 Fax: (+27) 11 455 6066 E-mail: lsmart@grundfos.com
Spain
Bombas GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465
Sweden
GRUNDFOS AB Box 333 (Lunnagårdsgatan 6) 431 24 Mölndal Tel.: +46 31 332 23 000 Telefax: +46 31 331 94 60
Switzerland
GRUNDFOS Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-1-806 8111 Telefax: +41-1-806 8115
Taiwan
GRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868 Telefax: +886-4-2305 0878
Thailand
GRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road, Dokmai, Pravej, Bangkok 10250 Phone: +66-2-725 8999 Telefax: +66-2-725 8998
Turkey
GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,
2. yol 200. Sokak No. 204 41490 Gebze/ Kocaeli Phone: +90 - 262-679 7979 Telefax: +90 - 262-679 7905 E-mail: satis@grundfos.com
Ukraine
ТОВ ГРУНДФОС УКРАЇНА 01010 Київ, Вул. Московська 8б,
Тел.:(+38 044) 390 40 50 Фах.: (+38 044) 390 40 59
E-mail: ukraine@grundfos.com
United Arab Emirates
GRUNDFOS Gulf Distribution P.O. Box 16768 Jebel Ali Free Zone Dubai Phone: +971 4 8815 166 Telefax: +971 4 8815 136
United Kingdom
GRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 4TL Phone: +44-1525-850000 Telefax: +44-1525-850011
U.S.A.
GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500
Uzbekistan
Grundfos Tashkent, Uzbekistan The Representative Office of Grundfos Kazakhstan in Uzbekistan 38a, Oybek street, Tashkent Телефон: (+998) 71 150 3290 / 71 150 3291 Факс: (+998) 71 150 3292
Addresses Revised 06.05.2013
Grundfos companies
98567337 1013
ECM: 1122748
www.grundfos.com
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S
Loading...