Grunbeck GENO-OSMO-X Operation Manual

Operation manual
Reverse osmosis system GENO-OSMO-X
with GENO-tronic operating element
and GENO-OSMO-X controller
starting from software version V1.11
Edition: April 2018 Order no. 124 750 927-inter
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
1
Table of contents
AGENERAL ............................................................................................................................................................................................ 4
1 | P
REFACE
..................................................................................................................................................................................................... 4
2 | H
OW TO USE THIS OPERATION MANUAL
............................................................................................................................................................ 4
3 | G
ENERAL SAFETY INFORMATION
..................................................................................................................................................................... 5
3.1Symbols and notes .............................................................................................................................................................................. 5
3.2Operating personnel ............................................................................................................................................................................ 5
3.3Appropriate application ........................................................................................................................................................................ 5
3.4Protection from water damage ............................................................................................................................................................. 6
3.5Indication of specific dangers ............................................................................................................................................................... 6
4 | S
HIPPING AND STORAGE
................................................................................................................................................................................ 6
5 | D
ISPOSAL OF USED PARTS AND MATERIALS
...................................................................................................................................................... 6
BBASIC INFORMATION ........................................................................................................................................................................ 7
1 | L
AWS, REGULATIONS, STANDARDS
.................................................................................................................................................................. 7
2 | W
ATER
........................................................................................................................................................................................................ 7
3 | F
UNCTIONAL PRINCIPLE OF REVERSE OSMOSIS
................................................................................................................................................. 8
CPRODUCT DESCRIPTION .................................................................................................................................................................. 9
1 | T
YPE DESIGNATION PLATE
.............................................................................................................................................................................. 9
2 | F
UNCTIONAL DESCRIPTION
........................................................................................................................................................................... 10
3 | T
ECHNICAL SPECIFICATIONS
......................................................................................................................................................................... 15
4 | A
PPROPRIATE APPLICATION
......................................................................................................................................................................... 16
4.1System idle time ................................................................................................................................................................................. 16
5 | A
PPLICATION LIMITS
.................................................................................................................................................................................... 17
6 | S
COPE OF SUPPLY
...................................................................................................................................................................................... 18
6.1Standard equipment ........................................................................................................................................................................... 18
6.2Optional accessories .......................................................................................................................................................................... 19
6.3Consumables ..................................................................................................................................................................................... 22
6.4Wearing parts .................................................................................................................................................................................... 23
DINSTALLATION ................................................................................................................................................................................. 24
1 | G
ENERAL INSTALLATION INSTRUCTIONS
........................................................................................................................................................ 24
1.1Preliminary work ................................................................................................................................................................................ 24
2 | W
ATER INSTAL LATION
.................................................................................................................................................................................. 24
3 | H
OW TO CONNECT THE SYSTEM
.................................................................................................................................................................... 25
4 | E
LECTRICAL INSTALLATION
........................................................................................................................................................................... 26
4.1Circuit diagram of power distribution .................................................................................................................................................. 26
4.2Connections within the GENO-OSMO-X control unit and the GENO-tronic operating element: ........................................................ 28
4.3Connections within the GENO-OSMO-X reverse osmosis system .................................................................................................... 29
4.4Connections to other subsystems - system output ............................................................................................................................. 30
4.5Connections to other subsystems – Residual hardness monitoring system NX1CQ1 for pre-treatment by water softener ................. 30
4.6Connections to other subsystems – Dosing pump RO1 P2 for antiscalant pre-treatment ....................................................................... 31
4.7Connections within the OSMO-X reverse osmosis system – AVRO pre-treatment RO1B5 ................................................................ 31
4.9Subsystems water softener and/or pressure booster interconnected via RS485 data line – Connection of terminating resistors ...... 32
4.10 Connections to other subsystems – Pre-treatment by water softener ................................................................................................. 32
4.11Connections to other sub-systems – Pressure booster installed downstream .................................................................................... 32
4.12Connections to other subsystems – Optional signals or accessories ................................................................................................. 33
ESTART-UP ......................................................................................................................................................................................... 34
1 | H
OW TO FLUSH THE SYSTEM
........................................................................................................................................................................ 34
1.1How to flush off the preservation agent .............................................................................................................................................. 34
FOPERATION ...................................................................................................................................................................................... 36
1 | I
NTRODUCTION
........................................................................................................................................................................................... 36
2 | S
CREEN LAYOUT OF THE
GENO-
TRONIC OPERATING ELEMENT
........................................................................................................................ 36
2.1Home screen ..................................................................................................................................................................................... 36
2.2Info level of GENO-OSMO-X.............................................................................................................................................................. 37
2.3Change, save, reject parameters ....................................................................................................................................................... 38
2.4Acknowledgement of errors/signals ................................................................................................................................................... 39
2.5Screen saver ...................................................................................................................................................................................... 40
3 | S
YSTEM RANGE
.......................................................................................................................................................................................... 40
3.1System menu I ................................................................................................................................................................................... 40
3.2Data logging on an SD card ............................................................................................................................................................... 42
3.2System menu II .................................................................................................................................................................................. 45
3.3Software version ................................................................................................................................................................................ 45
4 | SUB-
SYSTEM
GENO-OSMO-X
REVERSE OSMOSIS SYSTEM
........................................................................................................................... 45
4.1 User programming level ..................................................................................................................................................................... 46
4.2Installer level (Code 113) ................................................................................................................................................................... 48
4.3Customer service level ....................................................................................................................................................................... 54
4.4Extended customer service level I ...................................................................................................................................................... 54
4.5Extended customer service level II ..................................................................................................................................................... 54
4.6Counter readings, error memory ........................................................................................................................................................ 55
4.7Key operation ..................................................................................................................................................................................... 56
4.8Reset of counter readings .................................................................................................................................................................. 56
4.9Memory of operating parameters ....................................................................................................................................................... 56
5 | P
ERMEATE TANK
......................................................................................................................................................................................... 57
6 | PRE-
TREATMENT BY MEANS OF ANTISCALANT DOSING
..................................................................................................................................... 58
6.1Operator menu ................................................................................................................................................................................... 59
6.2Customer Service level ...................................................................................................................................................................... 5 9
GTROUBLESHOOTING ....................................................................................................................................................................... 60
1 | B
ASIC INFORMATION
.................................................................................................................................................................................... 60
2 | H
OW TO REMEDY WARNINGS
........................................................................................................................................................................ 61
3 | T
ROUBLESHOOTING
.................................................................................................................................................................................... 64
HMAINTENANCE ................................................................................................................................................................................. 7 0
1 | B
ASIC INFORMATION
.................................................................................................................................................................................... 70
2 | I
NSPECTION (FUNCTIONAL CHECK
) ................................................................................................................................................................ 70
3 | M
AINTENANCE
............................................................................................................................................................................................ 7 1
4 | O
PERATION LOG
......................................................................................................................................................................................... 72
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
2
Publisher's information
All rights reserved.
Copyright by Grünbeck Wasseraufbereitung GmbH
Printed in Germany Effective with the date of edition indicated on the cover sheet.
-We reserve the right to modifications, especially with regard to technical progress-
Reprints, translations into foreign languages, electronic storage or copying of this operation manual only with explicit written ap­proval of Grünbeck Wasseraufbereitung GmbH.
Any type of duplication not authorised by Grünbeck Wasserauf­bereitung is a copyright violation and subject to legal action.
Responsible for contents: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Str. 1, 89420 Hoechstaedt/Germany Phone +49 9074 41-0 Fax +49 9074 41-100 www.gruenbeck.de service@gruenbeck.de
Print: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Str. 1, 89420 Hoechstaedt/Germany
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
3
EU Declaration of Conformity
This is to certify that the system designated below meets the safety and health requirements of the applicable European guidelines in terms of its design, construction and execution.
If the system is modified in a way not approved by us, this certificate is void.
Manufacturer: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1 89420 Hoechstaedt/Germany
Responsible for documenta­tion:
Markus Pöpperl
System designation: Reverse osmosis system GENO-OSMO-X
System size: 200, 400, 800, 1200, 1600, 2200, 3000
Serial number: refer to type designation plate
Applicable guidelines: Machinery Directive (2006/42/EC)
EMC Directive (2014/30/EU)
Applied harmonised standards, in particular:
DIN EN ISO 12100: 2011-03 DIN EN 61000-6-2: 2006-03 DIN EN 61000-6-3: 2011-09
Applied national standards and technical specifications, in particular:
City, date and signature: Hoechstaedt, 30.04.2018 p.p.
M. Pöpperl Dipl.-Ing. (FH)
Function of signatory: Head of Department for Technical Product Design
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
4
A General
1 | Preface
Thank you for opting for a Grünbeck product. Backed by decades
of experience in the area of water treatment, we provide solutions for all kind of processes.
All Grünbeck systems and devices are made of high-quality mate­rials. This ensures reliable operation over many years, provided you treat your water treatment systems with the required care. This operation manual assists you with important information. Therefore, please read the entire operation manual before in­stalling, operating or maintaining the system.
Customer satisfaction is our prime objective and providing cus­tomers with qualified advice is crucial. If you have any questions concerning this device, possible extensions or general water and waste water treatment, our field staff, as well as the experts at our headquarters in Hoechstaedt, are available to help you.
Advice and assistance
For advice and assistance please contact your local representa­tive (see www.gruenbeck.de) or get in touch with our service centre which can be reached during office hours:
Phone: +49 9074 41-333
Fax: +49 9074 41-120
Email: service@gruenbeck.de
We can connect you with the appropriate expert more quickly if you provide the required system data.
2 | How to use this operation manual
This operation manual is intended for the operators of our sys-
tems. It is divided into several chapters and a letter is assigned to each of them in alphabetical order. In order to find the specific in­formation you are looking for, check for the corresponding chapter on page 3.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
5
3 | General safety information
3.1 Symbols and notes
Important information in this operation manual is characterised by symbols. Please pay particular attention to this information to ensure the hazard-free, safe and efficient handling of the sys­tem.
Danger! Failure to adhere to this information will cause serious or life-threatening injuries, extreme damage to property or inad­missible contamination of the drinking water.
Warning! Failure to adhere to this information may cause inju­ries, damage to property or contamination of the drinking water.
Attention! Failure to adhere to this information may result in damage to the system or other objects.
Note: This symbol characterises information and tips to make your work easier.
Tasks with this symbol may only be performed by Grünbeck's technical service/authorised service company or by persons ex­pressly authorised by Grünbeck.
Tasks with this symbol may only be performed by qualified elec­trical experts according to the VDE guidelines or according to the guidelines of a similar local institution.
Tasks with this symbol may only be performed by water compa­nies or approved installation companies. In Germany, the instal­lation company must be registered in a water company installa­tion directory as per §12(2) AVBWasserV (German Ordinance on General Conditions for the Supply of Water).
3.2 Operating personnel
Only persons who have read and understood this operation manual are permitted to work with the system. The safety guide­lines are to be strictly adhered to.
3.3 Appropriate application
The system may only be used for the purpose outlined in the product description (chapter C). The guidelines in this operation manual as well as the applicable local guidelines concerning the drinking water protection, accident prevention and occupational safety must be adhered to.
In addition, appropriate application also implies that the system may only be operated when it is in proper working order. Any malfunctions must be repaired at once.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
6
3.4 Protection from water damage
Warning! In order to properly protect the installation site against
water damage:
a sufficient floor drain system must be available or
a safety device (see chapter C Accessories) must be in-
stalled.
Warning! In case of a power failure, floor drains with a dis­charge to a lifting system will be out of operation.
3.5 Indication of specific dangers
Danger due to electrical energy! Do not touch electrical parts with wet hands! Disconnect the system from mains before start­ing work on electrical parts of the system. Have qualified experts replace damaged cables immediately.
Danger due to mechanical energy! System parts may be subject to overpressure. Danger of injury and damage to property due to escaping water and unexpected movement of system parts. Check pressure pipes regularly. Depressurise the system before starting repair or maintenance work on the system.
Hazardous to health due to contaminated drinking water! The system may only be installed by a specialist company. The oper­ation manual must be strictly adhered to! Ensure that there is sufficient flow. The pertinent guidelines must be followed for starting-up after extended periods of standstill. Inspections and maintenance must be performed at the intervals specified!
Note: By concluding a maintenance contract, you ensure that all of the required tasks are performed on time. You may perform the interim inspections yourself.
4 | Shipping and storage
Attention! The system may be damaged by frost or high tem-
peratures. In order to avoid damage of this kind:
Protect from frost during transportation and storage! Do not install or store system next to objects which radiate a lot of heat.
The system may only be transported and stored in its original
packing. Ensure that it is handled with care and placed the right side up (as indicated on the packing).
5 | Disposal of used parts and materials
Used parts and materials are to be disposed of, or made availa-
ble for recycling purposes, according to the applicable local guidelines.
If a material is subject to specific regulations, adhere to the in­structions indicated on the packing.
If in doubt, contact your local waste disposal authority or the manufacturer for more information.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
7
B Basic information
1 | Laws, regulations, standards
In the interest of good health, rules cannot be ignored when it
comes to the processing of drinking water. This operation man­ual takes into consideration the current regulations and stipu­lates information that you will need for the safe operation of your water treatment system.
Among other things, the regulations stipulate that
only approved companies are permitted to make major modi-
fications to water supply facilities
and that tests, inspections and maintenance on installed de-
vices are to be performed at regular intervals.
2 | Water
Due to dynamic substance and water cycles, harmful elements,
which are only partly and only slowly biodegradable are increas­ingly released into nature. Over time, these elements therefore accumulate in ground and surface water. Removing them again from natural water bodies represents a particular challenge. Grünbeck rises to this challenge and aims at generating unpol­luted drinking and process water.
The water works provide us with pure drinking water that is suit-
able for consumption. However, if the water is to be used for technical purposes, further treatment is frequently required.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
8
3 | Functional principle of reverse osmosis
Principle:
Pre-treated feed water
Concentrate:
Permeate
Fig. B-1: Functional principle
Osmosis Osmotic pressure Reversed osmosis
Solution of high concentration
Solution of low concentration
Solution of high concentration
Solution of low concentration
Solution of high concentration (concentrate)
Solution of low concentration (permeate)
Fig. B-2: Reverse osmosis principle
In the osmosis process, watery solutions of different concentra­tions are separated by a semi-permeable membrane. In keeping with the law of nature, the concentrations try to equalise. On the side of the higher original concentration, the so-called "osmotic" pressure is generated.
In case of reverse osmosis, this osmotic pressure is countered by a higher pressure. The consequence: the process proceeds in the reverse direction. A particular advantage of the reverse osmosis technology compared to other water treatment pro­cesses is the fact that - apart from the removal of dissolved salts
- bacteria, germs and dissolved organic substances are also re­duced.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
9
C Product description
1 | Type designation
plate
Please specify the data shown on the type designation plate of your GENO-OSMO-X reverse osmosis system in order to speed up the processing of enquiries or orders. Please copy the indi­cated information to the table below in order to have it handy whenever necessary.
Reverse osmosis system GENO-OSMO-X:     Serial number:     
Order no.:
     
Fig. C-1: Type designation plate of the reverse osmosis system GENO-OSMO-X
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
10
2 | Functional description
Feed water
Concentrate to drain
Permeate
Fig. C-2: System design of the reverse osmosis system GENO-OSMO-X
1
2
3
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
11
Feed water inlet BL1
Connection 1“ or 1¼ (male thread), flat sealing, for feed water connection by others on site
Note: Provide connection by means of water meter screw con­nection.
Solenoid valve for feed water RO1V1
During the permeate production, this valve is always open. Fol­lowing the system stop (tank full), the valve remains open for the programmed flushing volume of the membrane(s).
Fine filter RO1F1
Pre-filtration of the feed water incl. pressure reducer (pre-set)
4.0 bar and integrated pressure gauge for feed water pressure.
Flow sensor feed RO1CF2
Via pulse signal to the control unit. Feed = Concentrate recirculation + Permeate + Concentrate to drain.
Pressure switch for minimum pressure RO1CP1
To prevent the high-pressure pump from running dry. Switches time-delayed after opening the solenoid valve for feed water.
Flow sensor feed water RO1CF1
Via pulse signal to the control unit. Feed water = Permeate + Concentrate to drain.
Adjusting valve concen­trate to drain with drive RO1V3
To automatically adjust the volume flow concentrate to drain (re­covery). During the permeate production, this portion of the wa­ter flow permanently flows to the drain. The volume flow is sub­ject to the system size. In case of tank "full" as well as in case of a system failure, the valve always opens the entire cross section in combination with the solenoid valve for feed water.
Pressure reducer concentrate RO1H4
To improve the regulation accuracy of the adjusting valves (set to 6 bar)
Adjusting valve concentrate recirculation with drive RO1V2
For automatic adjustment of the volume flow concentrate recir­culation. The volume flow is subject to the system size.
Sampling valve concentrate RO1H1
Allows manual quality determination via sampling valve.
Connection concentrate to drain BL2
1“ male thread, flat sealing
Note: Provide for connection via water meter screw connection.
Permeate connection BL3
1“ male thread, flat sealing
Note: Provide for connection via water meter screw connection.
High-pressure pump RO1P1
Centrifugal pump system (frequency-controlled) that generates the operating pressure required for the membrane. Pump oper­ates upon permeate demand from the level control located in the permeate tank. By means of the frequency converter, the pump's revolution speed is adapted in a way that the nominal permeate capacity is achieved.
1
2
3
4
5
6
7
8
9
10
11
12
13
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
12
Pressure switch maximum pressure RO1CP3
Prevents the system's operating pressure from exceeding 16 bar.
Membrane RO1B1
Reverse osmosis membrane to generate the permeate.
Flow sensor permeate RO1CF3
Via pulse signal at the control unit.
Sampling valve permeate RO1H5
Allows manual quality determination via sampling valve.
Conductivity measurement RO1CQ1
Conductivity sensor according to the 2-electrode principle (tem­perature-compensated (RO1CT1)) for the continuous measure­ment of the permeate conductivity. The measuring results are in­dicated in the control unit.
Fig. C-3: Reverse osmosis system GENO-OSMO-X hydro module for feed water
14
15
16
17
18
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
13
Fig. C-4: Reverse osmosis system GENO-OSMO-X hydro module for concentrate
Fig. C-5: Reverse osmosis system GENO-OSMO-X hydro module for permeate
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
14
Fig. C-6: Reverse osmosis system GENO-OSMO-X 3000 with fine filter, hydraulic connections, membrane and high-pressure pump
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
15
3 | Technical specifications
Table C-1: Technical specifications Reverse osmosis system GENO-OSMO-X
200 400 800 1200 1600 2200 3000
Connection data
Nominal connection diameter (male thread) of feed water inlet
1“
1“ 1“ 1“ 1“
1 ¼“ 1 ¼“
Nominal connection diameter (male thread) of permeate outlet
1“
1“ 1“ 1“ 1“ 1“ 1“
Nominal connection diameter (male thread) of concentrate outlet
1“
1“ 1“ 1“ 1“ 1“ 1“
Min. drain connection Without optional AVRO DN 50 DN 50 DN 50 DN 50 DN 50 DN 50 DN 50
With optional AVRO DN 50 DN 50 DN 50 DN 100 DN 100 - -
Power supply [V/Hz] 3/N/PE, 400 V/50...60 Hz
Min. power outlet provided on site 5.5 kW / C 20 A / 2.5 mm²
Protection/protection class
IP 54/
Power input in case of unpressurised delivery of the permeate into a tank at a switching frequency of the frequency converter of 8 kHz and an inlet pressure of 4 bar in the feed water
Recovery of 80 % [kW] 0.53 0.87 0.94 1.40 1.74 2.10 2.30
Recovery of 50 % [kW] 0.53 0.88 0.94 1.30 1.60 - -
Power input if the permeate is delivered directly to the consumers with a supply pressure of 3.8 bar at a switching frequency of the frequency converter of 8 kHz and an inlet pressure of 4 bar in the feed water.
Recovery of 80 % [kW] 0.86 1.44 1.60 2.00 2.31 2.30 2.80
Recovery of 50 % [kW] 0.81 1.20 1.41 1.90 2.11 - -
Performance data
Permeate capacity at a Feed water temperature of 10 °C [l/h] 170 340 680 1020 1360 1870 2550
Feed water temperature of 15 °C [l/h] 200 400 800 1200 1600 2200 3000
Feed water temperature of 15 °C [m³/d] 4.8 9.6 19.2 28.8 38.4 52.8 72.0
Min. inlet flow pressure of feed water [bar] 2.5
Min. outlet pressure of permeate [bar] 0.5
Nominal pressure PN 16
Salt rejection 95 – 99 %
Total salt concentration in the feed wa­ter as NaCl, max.
[ppm] 1000
Recovery min./max. [%] 50-80 (adjustable) 65-80 (adjustable)
Volume flow concentrate to drain at a recovery of 80%. (at 15°C)
[l/h] 50 100 200 300 400 550 750
Feed water volume flow (15 °C) drain at a recovery of 80%.
[l/h] 250 500 1000 1500 2000 2750 3750
Filling volumes and consumption data
Number of modules (size 4") [pcs.] ½ 1 2 3 4 6 8
Dimensions and weights
System width [mm] 900 900 1035 1035 1170 1170 1170
System height [mm] 1700 1700 1700 1700 1700 1700 1700
System depth [mm] 675 675 675 675 675 675 675
Room height/installation height, min. [mm] 1800 1800 1800 1800 1800 1800 1800
Operating weight, approx. [kg] 100 115 145 170 195 240 290
General
Feed water temperature, min./max. [°C] 10/301)
Ambient temperature, min./max. [°C] 5/35
Order no. 750 200 750 210 750 220 750 230 750 240 750 250 750 260
1)
For temperatures of feed water > 20 °C a separate configuration of the system is required.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
16
4 | Appropriate application
The reserve osmosis system is designed for the demineralisa-
tion of drinking water according to the German Drinking Water Ordinance (TrinkwV). The generated water is primarily used for industrial applications.
A corresponding pre-treatment is required and the application limits (paragraph 5) must be adhered to.
Note: In case of water that does not comply with the stipulations of the German Drinking Water Ordinance (TrinkwV), a water analysis is required beforehand.
The continuous permeate capacity is subject to the temperature
and was defined at 15°C. The permeate capacity decreases by up to 3 % per degree centigrade of the feed water temperature .
Note: This reverse osmosis system adjusts the permeate capac­ity automatically subject to the temperature. The recovery (con­centrate to drain) as well as the concentrate recirculation are adapted to the modified permeate capacity.
The system is adjusted to the permeate requirements to be ex-
pected at the installation site, it is not suitable for major deviations.
The system may only be operated if all components are installed
properly. Safety devices and equipment must NEVER be re­moved, bridged or tampered with.
Appropriate application of the device also implies that the infor­mation contained in this operation manual and all safety guide­lines applying at the installation site be observed. Furthermore, the maintenance and inspection intervals have to be observed.
4.1 System idle time
If the system is out of operation for more than 14 days, it must
be preserved by Grünbeck's technical customer service/author­ised service company. The maximum time, the system can re­main in the preserved condition is 6 months.
In case the down time is longer, the system must be preserved again in regular intervals by Grünbeck's technical customer ser­vice/authorised service company. Prior to resuming operation, the preserving agent must be flushed from the system.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
17
5 | Application limits
For the application of the reverse osmosis system, the limit val-
ues stipulated in the German Drinking Water Ordinance repre­sent the upper limits for the admissible substances contained in the water.
Total hardness < 0.1 °dH
1)
(0.18 °f; 0.018 mmol/l)
Free chlorine not detectable
Iron < 0.10 mg/l
Manganese < 0.05 mg/l
Silicate < 15 mg/l
Chlorine dioxide not detectable
Turbidity < 1 FTU
Colloid index (SDI) < 3
pH range 3-9
1)
Different application limits for the total hardness do apply for
the optional pre-treatment AVRO resp. antiscalant.
Note: The permeate originating from the reverse osmosis sys­tem is not potable but requires additional treatment (blending, hardening) if it is to be used as drinking water.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
18
6 | Scope of supply
6.1 Standard equipment
Control unit with 4.3" graphics touch panel to indicate the op-
erating state and system values. Voltage-free contacts to re­lay advance warnings and safety shut-downs. Digital input for priority permeate production in times when electricity tariffs are low (smart metering). Fully automatic monitoring and con­trol of the system parameters permeate flow, monitoring of the permeate conductivity by means of limit value default set­tings in the control unit, recovery, concentrate recirculation and pump frequency (subject to the water temperature). Re­cording of measured data on integrated SD card. Possibility to interconnect systems installed upstream or downstream (water softener, dosing system, permeate tank, pressure booster) and to operate them by remote control.
Power distribution with mains switch and automatic circuit
breakers as feeding point for power supply provided by oth­ers on site.
High-pressure centrifugal pump made of stainless steel
1.4401 to supply the reverse osmosis membrane(s).
Ultra-low pressure reverse osmosis membrane(s), installed in
pressure pipe made of high-strength PE.
Three-part hydro module made of red bronze, chemically
nickel-plated, featuring pressure gauges, adjusting resp. so­lenoid valves and sampling valves. Flow sensors integrated in the hydro module, volume measurement of the system flows permeate, concentrate and concentrate recirculation. The permeate hydro module features a conductivity measur­ing cell (temperature-compensated).
Pipework between pump and reverse osmosis membrane
made of high-pressure resistant PE pipes and PP compres­sion fittings.
High-quality system rack made of anodised aluminium to
house all system components.
A ventilation device to be mounted onto the concentrate pipe
provided by others on site.
Fine filter incl. pressure reducer, completely preassembled in
system inlet.
Installation and operation manual.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
19
6.2 Optional accessories
Note: It is possible to retrofit existing systems with optional com­ponents. Please contact your local Grünbeck representative or Grünbeck’s headquarters in Hoechstaedt for details.
BOXER K 1" drinking water filter
Filter cartridge for pre-filtration
101 210
Euro system separator GENO-DK 2
To secure devices and systems endangering the drinking water according to DIN 1988, part 4
GENO-DK 2 DN 15 GENO-DK 2 DN 20
132 510 132 520
GENO-mat duo WE-X water softener
Fully automatic double water softener based on the ion exchange principle for the generation of fully softened water with volume-controlled regen­eration.
-For larger systems, please inquire-
186 100
Delta-p water softener
Fully automatic triple water softener based on the ion exchange principle for the generation of fully/ partially softened water with volume-controlled re­generation.
- For larger systems, please inquire -
185 100
GENO-softwatch Komfort
For automatic monitoring of the limit value for residual/total hardness (water hardness).
172 500
GENO-activated carbon filter AKF 600
To reduce the chlorine concentration contained in the water.
- For larger filters, please inquire -
109 160
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
20
Communication module Profibus DP
For connection to a Profibus DP „Master“
750 160
Communication module BACnet IP
For connection to a BACnet IP „Master“
750 170
Communication module Modbus RTU
For connection to a Modbus RTU „Master“
750 175
Voltage-free signals
For connection to a BMS/CMS
750 180
Analogue signals 4-20 mA
For connection to a BMS/CMS
750 185
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
21
Safety device protectliQ:A20
Product for protection against water damage in one and two-family homes.
- For additional versions, please inquire -
126 400
Pure water tank for intermediate storage of per­meate flowing unpressurised from GENO-re­verse osmosis systems Tank design:
All tanks are pre-assembled, with PVC overflow pipe as well as connections for the permeate inlet and the suction line of the pressure booster system. Grey PE. Hand hole with removable screw cap.
Basic pure water tank RT-X 1000 with sterile air filter and level sensor
Useful capacity approx. 850 litres l 780 / w 990 / total height 2000 mm
1)
712 480
Additional tank RT for basic pure water tank
Useful capacity approx. 850 litres l 780 / w 780 / total height 2100 mm
1)
712 405
Basic pure water tank RT-X 1000
2)
with level sensor
Useful capacity approx. 850 litres l 780 / w 1000 / total height 2050 mm
1)
712 490
1)
Tank height incl. connecting pieces.
For larger tanks, please inquire
2)
No sterile overflow as siphon
- overflow as down pipe
Additional tank without overflow loop, incl. 2 connecting lines, id=36 mm.
Note: A maximum of four supply tanks can be combined.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
22
Pressure booster system GENO FU-X 2/40-1 N
Compact, pressure-controlled pump aggregate consisting of a centrifugal pump completely made of stainless steel as well as an integrated pres­sure and contact water meter. Control electronics with increase in capacity, backlit graphical display. Operating switch, operating log via SD card, volt­age-free signal / fault contact, non-return valve, shut-off valve for every pump (suction and pres­sure side) and membrane pressure expansion vessel with forced flow. Delivery rate: max. 1.2-4.2 m³/h Delivery height max. 18.2 - 45.6 m Power supply: 230 V / 50 Hz Power input 1 kW Connections: DN 25 / DN 32 Protection: IP 55
730 640
Pressure booster system GENO FU-X 2/40-2 N
Description as for single pressure booster system, however, with the possibility for time-/load switch­over.
- For additional pressure booster systems, please inquire -
730 641
6.3 Consumables
Only use genuine consumables in order to ensure the reliable operation of the system.
GENO-replacement filter element, with protective cylinder
Packing unit: 2 pcs
103 061
RO-membrane with seal 4“ x 40“
Reverse osmosis system GENO-OSMO-X 400 - GENO-OSMO-X 3000 Packing unit: 1 pc
750 261
RO-membrane with seal 4“ x 21“
Reverse osmosis system GENO
-
OSMO-X 200
Packing unit: 1 pc
750 293
Activated carbon filter element MKCA
Reverse osmosis system GENO
-
OSMO-X 200
Packing unit: 1 pc
109 615
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
23
6.4 Wearing parts
Seals and valves are subject to a certain wear and tear. Wearing parts are listed below.
Note: Although these are wearing parts, we grant a limited war­ranty period of 6 months.
Solenoid valves, adjusting valves, water meters, seals
Fig. C-7: Hydro module
Face seal of high-pressure pump
Fig. C-8: High-pressure pump
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
24
D Installation
1 | General Installation Instructions
The installation site must provide adequate space. Only the left
side (pressure pipes) of the system may be placed flush to the wall. In front, behind and on the right side of the system, adequate clearance for installation and service work must be provided (> 50 cm). A foundation of a sufficient size and adequate load car­rying capacity must be provided. The required connections must be provided prior to the installation. For dimensions and connec­tion data, please refer to table C-1.
1.1 Preliminary work
Unpack all system components.
Check for completeness and soundness.
Place the reverse osmosis system at the designated location.
Note: Also observe the operation manuals that have been sup­plied with the optional accessories (see chapter C-6.2) for your system (if applicable).
2 | Water installation
Certain binding rules must always be observed when installing a reverse osmosis system. Additional recommendations are given in order to facilitate the handling of the system. The installation instructions described below are also illustrated in fig. D-1.
Binding rules
The installation of a reverse osmosis system represents a major interference with the drinking water system. Therefore, only au­thorised experts may install such systems.
Please observe the local installation guidelines and the gen-
eral regulations.
Install a drinking water filter upstream of the system (e.g.
BOXER K).
A system separator must be installed upstream as well.
Install a water softener upstream.
Mount an activated carbon filter, if necessary (take water
analysis into consideration).
Provide a drain connection (minimum DN 50) to discharge
the concentrate.
Note: If the concentrate is directed to a lifting system, the delivery rate of the lifting system should at least have the concentrate vol­ume flow indicated in table C-1.
Warning! The installation site must have a floor drain. If no floor drain is available, an adequate safety device needs to be in­stalled (refer to option C-9).
Warning! In case of a power failure, floor drains with a dis­charge to a lifting system will be out of operation.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
25
3 | How to connect the system
Remove the protective caps at the feed water, permeate and
concentrate to drain connections of the system.
Connect the feed water.
Connect the concentrate to drain according to DIN 1988 and
install the pipe aeration above system level.
Make the connection between permeate outlet and supply
tanks.
BOXER K 1" drinking water filter
Reverse osmosis system GENO-OSMO-X
System separator GENO-DK 2
Permeate tank with sterile air filter and level sensor
Delta-p water softener
Pressure booster system GENO FU-X 2/40-1 N
GENO-softwatch Komfort
Activated carbon filter AKF
Fig. D-1: Installation drawing
Note: The feed, concentrate resp. permeate pipe provided by others on site must feature a provision to separate the pipes (e. g. a screw connection).
Note: The permeate and concentrate pipes have to be made of corrosion-proof material.
1 6
2 7
3
8
4
5
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
26
4 | Electrical installation
As the reverse osmosis system GENO-OSMO-X features a fre­quency converter for the high-pressure pump, problems with the residual current circuit breaker installed in the feeder may occur. We therefore recommend:
Use of an AC/DC sensitive RCCB with a response threshold
of 300 mA.
For the power supply of the system, a power outlet 3 x 400 V / 50 Hz/L/N/PE with a fuse protection of 20 A has to be provided by others on site.
The aluminium system rack must be connected to the equipoten­tial bonding on-site. The earth wire must have a minimum cross section of 6 mm² Cu or 10 mm² Al.
The necessary connecting materials (screw, hammer nuts, washers, etc.) are located in a bag in the system power distribu­tor (see Chapter F-4.1).
The connection to the equipotential bonding is required because the speed-controlled high-pressure pump has a ground leakage current of > 10 mA during its designated operation.
4.1 Circuit diagram of power distribution
The power distribution features the mains switch of the GENO OSMO-X system and is accessible if the GENO-OSMO-X control unit is flipped downwards. If required, the entire "production line" (softening + residual hardness moni­toring or antiscalant dosing, reverse osmosis, pressure booster system) can be supplied by the power distribution.
The power line of an antiscalant dosing pump is plugged into the mains socket of the power distribution in order to be able to quickly replace it during servicing.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
27
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
28
4.2 Connections within the GENO-OSMO-X control unit and the GENO-tronic operating element:
The following connections are pre-set at the factory and must
not be modified: Linux operating element
Power supply of programming board
From terminal of circuit board to terminal of programming board
91 +24 V= 8
92 mass 7
Serial connection RS 485
88 RS 485 A 11
89 RS 485 B 10
90 RS 485 GND 9
Fuses of circuit board
F1 T2A Main fuse of power input
F2 T0.63 A 24 V = solenoid valves, step motors
F3 T0.5A Programming board 24 V=
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
29
4.3 Connections within the GENO-OSMO-X reverse osmosis system
The following connections are preset internally at the factory and
must not be modified:
From GENO-OSMO-X control unit
to component Line Signal
1 Mains switch housing lid H05VV-F 5G1.5 mm² L From mains
switch
2 N
3 L To mains
switch
4 N
PE PE
5 230 V~ feed from
power distribution RO1E2
38 H05VV-F 3G0.75 mm² L
6 39 N
PE 40 PE
12 Frequency converter
of high-pressure pump
RO1P1A1
1 LiYcY 7x0.25 mm² + 24 V= WH Release FU
13 2 IN BN
56 10 + 24 V= GY Fault signal
FU (
57 11 DI 6 PK
40 6 4-20 mA YE Desired value
FU
41 7 GND GN
PE Shield
20 Feed water solenoid valve
RO1V1
H05VV-F 2x0.5 mm² + 24 V= (clocked for power reduction
21 GND
28 Regulating valve concentrate
to drain RO1V3
(step motor)
LiYY 7x0.25 mm² (blue strand is not used)
Ph1 GN
29 Ph1 WH
30 Com1 BN
31 Ph2 PK
32 Ph2 YE
33 Com2 GY
34 Regulating valve concentrate
recirculation KR RO1V2 (step motor)
LiYY 7x0.25 mm² (white strand is not used)
Ph1 GN
35 Ph1 BU
36 Com1 BN
37 Ph2 PK
38 Ph2 YE
39 Com2 GY
42 Temperature measurement
RO1CT1
LiYcY 4x0.25 mm² Pt 100 BN
43 GN
PE Conductivity measuring cell
RO1CQ1 cell constant 0,1
K= 0.1 1/cm Shield
44 WH
45 YE
46 Conductivity measuring cell
RO1CQ1 cell constant 0,1
LiYcY 4x0,25 mm² K= 0,1 1/cm
47 WH
YE
54 Pressure switch for minimum
pressure RO1CP1
LiYY 2x0.5 mm² + 24 V= WH
55 DI 5 BN
58 Pressure switch for maximum
pressure RO1CP3
LiYY 2x0.5 mm² + 24 V= WH
59 DI 10 BN
73 Feed water flow sensor
RO1CF1
LiYY 3x0.25 mm² +12 V= WH
74 [pulse] GN
75 GND BN
76 Flow sensor Feed
RO1CF2
LiYY 3x0.25 mm² +12 V= WH
77 [pulse] GN
78 GND BN
79 Flow sensor ermeate
RO1CF3
LiYY 3x0.25 mm² +12 V= WH
80 [pulse] GN
81 GND BN
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
30
4.4 Connections to other subsystems - system output
From GENO-OSMO-X control unit
to component Line Signal Colour
System output Tank
68 Digital signals BB1 for regis-
tration of filling level of pure water tank BB1CL1
LiYY 5x0.25 mm² +24 V=
69 System OFF BB1CL1
70 System ON / bypass closed BB1CL2
71 Bypass closed / dry run pro-
tection of pressure booster OFF
BB1CL3
72 Dry-run protection of pressure
booster ON
BB1CL4
Or alternatively
86 Analogue signals BB1 for
registration of filling level of pure water tank BB1CL1
LiYY 3x0.34 mm² + 24 V= WH
87 IN BN
PE Shield YE-GN
24 RO1 V4 (first permeate)
or RO1 V7 (blending valve)
H05VV-F 2x0.5 mm² 24 V= BN
25 GND BU
System output Online
84 Pressure measuring transducer
RO1 CP2 0…6 bar
LiYcY 2x0.25 mm² + 24 V= WH
85 In BN
PE Shield
4.5 Connections to other subsystems – Residual hardness monitoring system NX1CQ1 for pre-treatment by water softener
From GENO-OSMO-X control unit
to component Line Signal
14 GENO-softwatch Komfort ter-
minals 16/17
LiYY 4x0.25 mm² Com
15 N.O.
66 GENO-softwatch Komfort ter-
minals 8/10 and wire jumper be­tween 7/12
+24 V=
67 DI9
4.5.1 Connections to other subsystems – Residual hardness monitoring system NX1CQ1 for pre-treatment by water softener (GENO-Softwatch Komfort, from serial no.
40342)
From GENO-OSMO-X control unit
to component Line Signal
14 GENO-softwatch Komfort ter-
minals 18/19
LiYY 4x0.25 mm² Com
15 N.O.
66 GENO-softwatch Komfort ter-
minals 10/12 and wire jumper between 9/14
+24 V=
67 DI9
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
31
4.6 Connections to other subsystems – Dosing pump RO1 P2 for antiscalant pre-treatment
From GENO-OSMO-X control unit
to component Line Signal Colour Connector
pin
16 Pulse input LiYY 2x0.25 mm² + WH 4
17 - BN 1
63 Signal/fault signal output LiYY 4x0.25 mm² +24 V= WH, BN 1.2
64 Empty/fault signal RO1CL2 YE 3
65 Pre-warning RO1CL1 GN 4
4.7 Connections within the OSMO-X reverse osmosis system – AVRO pre-treatment RO1B5
From GENO-OSMO-X control unit
to component Line Signal
82 AVRO treatment module(s) H05VV-F 2x0.5 mm² + 1
83 - 2
4.8 Connection to other subsystems – Dosing pump RO1P3 in case of pre-treatment by
means of antiscalant
From GENO-OSMO-X control unit
to component Line Signal Colour Connector
pin
18 Pulse input LiYY 2x0.25 mm² + WH 4
19 - BN 1
50 Signal/fault signal output LiYY 4x0.25 mm² +24 V= WH, BN 1,2
51 Pre-warning RO1CL3 GN 4
62 Empty/fault signal RO1CL4 YE 3
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
32
4.9 Subsystems water softener and/or pressure booster interconnected via RS485 data line – Connection of terminating resistors
If more than two subsystems are interconnected or if the length
of the line between the two is > approx. 20 m, the so-called ter­minating resistors have to be connected to the "endpoints". This is done by means of dip switches. If required as per the following table, both dip switches have to be set to "ON".
RS485 interconnection between Connection of terminating resistors for
GENO-mat duo WE + GENO-OSMO-X GENO-mat duo WE and GENO-OSMO-X (*) GENO-OSMO-X + pressure booster GENO-OSMO-X + pressure booster (*) GENO-mat duo WE-X + GENO-OSMO-X +
pressure booster GENO-FU (HR)-x
GENO-mat duo WE
pressure booster
(*) for line length RS485 > approx. 20 m
OSMO-X:
The terminating resistors are aligned below the sheet covering of the circuit board
Close to terminal 43 (connection to
GENO-mat duo WE water softener)
Close to terminal 47 (connection to the pressure booster)
IONO-matic WE controller resp. PBS controller:
Close to terminal 36
4.10 Connections to other subsystems – Pre-treatment by water softener
From GENO-OSMO-X control unit
to component Line Signal
93 IONO-matic WE
control unit
36 LiYcY 3x0.25 mm² (*)
RS485 A
94 37 RS485 B
95 GND2 GND
4.11 Connections to other sub-systems – Pressure booster installed downstream
From GENO-OSMO-X control unit
to component Line Signal
96 Control unit Pres-
sure booster system GENO-FU (HR)-X
38 LiYcY 3x0.25 mm² (*) RS485 A
97 39 RS485 B
98 GND2 GND
(*) A shielded line is required in case of line lengths of > 20 m. The shield has to be connected on one side to a free PE terminal.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
33
4.12 Connections to other subsystems – Optional signals or accessories
From GENO-OSMO-X control unit
to component Line Signal
7 The signals "collective fault sig-
nal" and "signal with joint control common" open in case of power failure or in case of error/signal
Voltage-free each, max. 230 V~/1 A
Error
8 Signal
9 Joint control
common
10 Programmable output
(volt.-free, max. 230 V~/1 A)
max. 1.5 mm²
11
22 RO1V5 (blending valve)
or RO1V6 (bypass valve)
RO1V8 (membrane degassing)
Oilflex-O 2x0.5 mm² 24 V= BN
23 GND BU
26 RO1V4 (first permeate)
RO1V7 (blending valve)
27
PE Reserve ----- -------- --------
48
49
52 Release - input max. 1.5 mm² + 24 V
53 DI4
60 Programmable fault signal input max. 1.5 mm² + 24 V
61 DI1
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
34
E Start-up
The work described below may only be performed by trained ex­perts. For safety reasons, the start-up must be performed by Grünbeck's trained and authorised technical customer service/ authorised service company.
Note: Incorrect parameter settings or still missing signal connec­tions may cause malfunctions due to which the flushing of the preserving agent cannot be started.
1 | How to flush the system
1.1 How to flush off the preservation agent
For the duration of storage and transport, the membrane(s) is (are) protected by means of a preserving agent. First of all, this preserving agent must be flushed off.
After switching on the power supply for the first time, select
the subsystem menu GENO-OSMO-X.
The following pop-up window will appear in the touch display
of the GENO-tronic control unit:
Tap on it.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
35
By tapping on "START", the feed water solenoid valve, the con-
trol valve concentrate to drain and sporadically the control valve concentrate recirculation open. The preservation agent is washed out to the drain.
Attention! While the preserving agent is being flushed off, the system is deaerated at the same time. When skipping or prema­turely aborting the step "flushing" and putting the system in oper­ation, there are the following two risks
High-pressure pump is running dry.
The preserving agent gets into the permeate tank or into the
permeate line provided by others on site - these can only be cleaned/flushed with difficulty.
Note: The flushing of the system can be restarted manually. Re­fer to chapter F-4.1: To do so, select the operating mode "flush­ing".
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
36
F Operation
1 | Introduction
Note: Instructions in bold are absolutely essential to ensure that work can continue. All other instructions can be ignored if the value shown on the display remains unchanged.
Settings in the technical service programming level may only be performed by Grünbeck's technical customer service/authorised service company or by persons expressly authorised by Grünbeck.
Warning! Incorrect settings may lead to hazardous operating conditions which cause injury, illness or damage to property.
The operation manual must be strictly adhered to! Only make the settings described in there!
2 | Screen layout of the GENO-tronic operating element
2.1 Home screen
The home screen is the superordinate screen for all subsystems connected to/interconnected with the control unit of the GENO­OSMO-X: Here, it is set out from left to right how the water flows through the individual treatment steps. On the far left, the system range (cogwheels) for fundamental settings is located.
Lightly tapping on a subsystem provokes a switch-over to the Info level of the respective subsystem.
Statusline,coloursignalsthe systemstatus
Systemrange
Subsystemrange
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
37
2.2 Info level of GENO-OSMO-X
If the subsystem features an ON/OFF function such as the re-
verse osmosis system OSMO-X, the Info level has an ON/OFF button, too: Green = subsystem ON, Red = subsystem OFF. With the Home button, you may return to the Home screen. By press­ing on the illustration, you may access the submenu.
The following information is stored in the Info level of the OSMO-X
(can be accessed via arrow keys ^/v):
Operating mode
(locked / flushing / manual operation / automatic)
Permeate flow [l/h]
Current set value for permeate capacity [l/h]
Permeate conductivity [µS/cm]
Permeate recovery [%]
Water temperature [°C]
Service in [d]
AVRO RO1 B5 (only in case of AVRO pre-treatment) [h]
Concentrate to drain [l/h]
Concentrate recirculation [l/h]
Permeate pressure (only for Online version) [bar]
AVRO RO1B5 treatment current
(only in case of AVRO pre-treatment) [mA]
Output of regulating valve RO1V3 [%]
Output of regulating valve RO1V2 [%]
Conductivity of inlet and concentrate (only if optional conduc-
tivity measurement is available) [µS/cm]
Feed water flow [l/h]
Feed flow [l/h]
Analogue signal output to frequency converter [%]
Home button
Operating mode, current measuring values
Access to the GENO-OSMO X menu
ON/OFF button
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
38
2.3 Change, save, reject parameters
In a menu with permanently stored selections, any choice (line) can be selected by tapping on it. The middle line is in slightly larger print, however.
Save your selection with this button.
Quit the menu with this button without changing the prior selection.
The numerical and the alpha-numerical menu each feature the same operating logic:
Save your selection with this button.
Quit the menu with this button without changing the prior selection.
Save your selection with this button.
Quit the menu with this button without changing the prior selection.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
39
2.4 Acknowledgement of errors/signals
In case of a pending signal or malfunction, the sta-
tus line changes its colour and on the home screen, the subsystem concerned has a coloured frame.
Yellow = signal
Red = error
Tap on the status line >> Switch to error list
The error list may show one or several entries.
Tap on the entry you are interested in >> switch to the acknowledgement window
Button to return to the Home screen
The acknowledgement window will show an illus­tration of the subsystem concerned.
Acknowledgement button of the signal/error
Button to call up a help text including the telephone number of the technical customer service.
Button to return to the error list
The error can either be acknowledged or left pend­ing. In any case, you will get back to the error list.
Acknowledge signal/error
Leave signal/error pending
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
40
2.5 Screen saver
The screen saver is displayed automatically if the screen is not touched for 5 minutes (or after an ad­justable period of time).
As soon as the touch screen is tapped on or a sig­nal or an error occurs, the display returns to the basic display.
3 | System range
3.1 System menu I
System menu I can be accessed without entering a Code. The parameters stored apply to all systems in case more subsystems than just the GENO-OSMO-X are present and are operated via the GENO-tronic operating element.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
41
Note: Prior to removing the SD card, make sure that the data logging was terminated with "Nein/No"!
Note: The SD card used must be formatted FAT32. We recom­mend proper formatting instead of quick formatting.
Note: The SD card socket is integrated in the operating element of the GENO-tronic - to insert the card, the control unit of the GENO-OSMO-X must be opened.
Parameters Factory
setting
Setting
range
Comment
Operating language German German
English
French
Dutch
Italian Russian Spanish
System designation 18 digits, alphanumerical,
text will appear in the upper left corner of the Home screen
Date, time Incl. automatic switch-over
from daylight saving time to standard time
Data logging Start Start/
Stop
All measured values of all subsystems (Info level) are logged on the SD card.
Interval [min] 1 ... 999 Indicates the frequency of
how often the measured val­ues are stored on the SD card
Load parameters Before doing so, load the pa-
rameter record stored on the SD card
Attention: Do not execute during permeate production!
Save parameters Save current parameter
record on the SD card
Screensaver [min] 1 0…99
Lock screensaver [sec] 30 10…99
Note: The protective foil over the touch screen may only be wiped with a damp cloth and a mild soapsuds solution at the most! Never use cleaning agents for plastics or stronger clean­ing agents! Otherwise there is a risk that the foil will assume a milky colour and therefore be difficult to read!
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
42
3.2 Data logging on an SD card
The measured values on the SD card theoretically comprise an
entire "production line", from the softening or anti-scaling dosing) to the reverse osmosis (electrodeionisation is still not possible at present) and via the pure water tanks up to the pressure booster.
The log files are not yet very clear when viewed with a text edi­tor:
It is recommended to open the file with a spreadsheet program
(e.g. MS Excel) so that the structuring is easier to identify.
The system serial number is included in cell B1. The assignment
of all other information can be found in the following table. Una­vailable sub-systems should be ignored.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
43
Table F-1: GENO-tronic data logging
Softening NX1 Residual hardness mon-
itoring system NX1CQ1
Dosing 1 P2/P3 Reverse osmosis 1
duo WE (refer to specifi­cations) or Delta-p
Softwatch Komfort or Softwatch Premium
Grundfos OSMO-X
Remaining capacity
exchanger* C XX,XX [m³]
Remaining capacity
exchanger** C XX,XX [m³] (Delta-p only)
Flow rate
Q XX,XX [m³/h]
Time since last regen-
eration T XXX [h]
Current regeneration step
R (0/1…5)
Time until service is due
S XXX [d]
Regeneration counter
R XXXXXX
Soft water meter
V XXXXXX m³ without data logging on SD card:
Software version
Softwatch Premium only
Current residual hardness
H XXX,XXXX hardness unit [°dH, °e, °f, mmol/l, ppm, mval/l]
Set limit value 1
HL XXX,XXXX
Remaining range of indi-
cator C XXX (Premium only)
Status (analysis running),
see document „transmis­sion range Softwatch Pre­mium“
Number of analyses until
service is due S XXX
Softwatch Komfort only
Status (ok/malfunction
)
RO1P2
Estimated range
of dosing chemi­cal V XXXX [m³]
RO1P3
Estimated range
of dosing chemi­cal V XXXX [m³]
Permeate flow
Q XXXX [l/h]
Permeate conductivity
C XX,X [µS/cm]
Recovery
A XX [%]
Water temperature
T XX [°C]
Permeate pressure
p X,XX [bar] (only for Online sys­tem outlet)
Operating mode
(off/operation/flushing/ forced operation/ forced stop/rejection of first permeate) Z (0…6)
Flow concentrate to
drain QKK XXXX [l/h]
Flow concentrate re-
circulation QKR XXXX [l/h]
AVRO treatment
current AVR XXX [mA] (only for AVRO pre­treatment, AVRO+DOS)
Inlet conductivity
CR XXXX [µS/cm] and concentrate con­ductivity CK XXXX [µS/cm] (only if conductivity meter in inlet + con­centrate active)
Time until service is
due S XXX [d]
Time until AVRO ser-
vice is due SAVR XXXX [h] (only for AVRO pre­treatment, AVRO+DOS)
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
44
Continuation of table F-1: GENO-tronic data logging
Electrodeionisation EDI1
Pure water tank BB1
Pressure booster DEA1P1/P2
Reverse osmosis 1 Permeate stage
EDI – deferred until EDI receives the hardware of the OSMO-X
Single or twin pres-
sure booster (see specifications)
OSMO-X
Diluate flow
Q XXXX [l/h]
Diluate conductivity
C X,XX [µS/cm] or R X,XX [MΩ*cm]
Diluate temperature
T XX [°C]
Recovery
A XX [%]
Pressure diluate inlet
p X,XX [bar]
Pressure diluate outlet
p X,XX [bar]
Pressure concentrate inlet
p X,XX [bar]
Pressure concentrate out-
let p X,XX [bar]
Voltage of power supply
unit U XXX [V]
Current of power supply
unit I XXX [A]
Operating mode (off/oper-
ation/forced operation/permeate rejec­tion/diluate rejection Z (0…5)
Flow concentrate to drain
QKK XXXX [l/h]
Inlet conductivity
CR X,XX [µS/cm] and concentrate conductivity CK XXXX [µS/cm] (not for all models)
Time until service is due
S XXX [d]
Filling level
L XXX [%]
Operating mode
DEA1 P1 (off/manual P1/manual P2/auto­matic)
Flow rate
Q XX,XX [m³/h]
Operating hours
DEA1 P1 XXXXX [h]
Operating hours
DEA1 P1 XXXXX [h] (twin pressure booster only)
Water volume
V XXXXX [m³]
Time until service is due
S XXX [d]
Permeate flow
Q XXXX [l/h]
Permeate
conductivity C XX,X [µS/cm]
Recovery
A XX [%]
Permeate
pressure p X,XX [bar] (of stage 1)
Flow concentrate
to stage 1 QKK XXXX [l/h]
Flow concentrate
recirculation inter­nally QKR XXXX [l/h]
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
45
3.2 System menu II
The purpose of the system menu II is to log on all existing com­ponents of the "production line" that are to be displayed in the GENO-tronic.
3.3 Software version
Not Code protected: Indication of the software version of the GENO-OSMO-X control unit and the GENO-tronic operating ele­ment.
4 | Sub-system GENO-OSMO-X reverse osmosis system
The menu of the reverse osmosis system GENO-OSMO-X is structured as follows:
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
46
4.1 User programming level
The user programming level can be accessed without entering a
Code.
Parameters Factory
setting
Setting
range
Comment
Operating mode Locked Locked/
Flushing/
Manual operation/
Automatic
The desired operating mode (except for Locked) has to be started in the Info level by means of the I/O button (the colour of the button changes from red to green):
Locked = delivery state, no system operation possible
Flushing = flushing volume stored in the system size will be flushed to the drain once
Manual operation (not possi­ble in case of system output Online) = permeate production continues as long as the sys­tem stays switched on via the I/O button. No switch-off com­mand via tank full detection will be processed.
Automatic operation = per­meate is produced subject to the level in the permeate tank or the permeate pressure
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
47
Parameters Factory set-
ting
Setting
range
Comment
Switch-on pressure (only in case of sys­tem output Online)
[bar] 3.0 1.0 ... 5.0 In automatic operation, the
system starts the permeate production if the switch-on pressure is undershot.
Switch-off pressure (only in case of sys­tem output Online)
[bar] 4.0 1.0 ... 4.0 In automatic operation, the
system terminates the perme­ate production if the switch-off pressure is exceeded.
Note: The systems are de­signed for 4.0 bar.
Automatic restart
No No/Yes What to do after a power
failure
No = after return of power, the system signals "Error power failure“; automatic resp. man­ual operation remains stored but is blanked.
YES = after return of power, the system continues running in the operating mode set pre­viously and does not indicate an error.
Forced operation Operation Operation/
flushing
Behaviour in case of a longer period without permeate pro­duction (also refer to the cus­tomer service level):
Operation = permeate pro­duction, switch-off command tank full is ignored (tank with overflow required)
Flushing = Factory setting in case of system output Online: Flushing to the drain, high­pressure pump is not running.
Conductivity monitoring RO1CQ1
Signal Signal/
error
Monitoring of permeate con­ductivity:
If the programmed conductivity limit value is exceeded for the set delay time, the following options can be programmed:
Signal: The system continues running although the limit value was exceeded.
Error: The system switches off.
Conductivity limit value RO1CQ1 Cell constant 0.1
[µS/cm] 30 0 ... 99
Conductivity limit value RO1CQ1 Cell constant 1.0
[µS/cm] 30 0 ... 999
Delay conductivity er­ror/signal RO1CQ1
[min.] 30 0 ... 999
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
48
4.2 Installer level (Code 113)
The installer level contains parameters that might have to be
adapted to the conditions on site during the start-up. Access to the menu is protected by Code 113.
Note: The parameters marked with (*) must not be modified in the reverse osmosis system series GENO-OSMO-X!
Parameters Factory
setting
Setting
range
Comment
Output logic Release FU pump RO1P1A1
NOC NOC/
NCC
The GENO-OSMO-X control unit has to establish a con­nection between its voltage­free contact terminals 12/13 and the frequency converter terminals 1/2 for the pump to work
Dosing Function RO1P2 and RO1P3 (*)
Pulse Pulse/
N.C./N.O.
Only Pulse is admissible as output signal to activate the dosing pump(s)!
Function Pulse outputs regulating valves(*)
Step Step/relay Only Step is admissible as
output signal to activate the regulating valves!
Function RO1V5/V6/V8
RO1V6 RO1V5
RO1V6 RO1V8
Connection terminals 22/23 are switchable:
RO1V6 = bypass (opens if level BB1CL3 is undershot, closes if level BB1CL2) is exceeded
RO1V5 = blending is always open when the high-pressure pump is running
RO1V8 = Membrane degas­sing (actuated when system in operation)
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
49
Parameters Factory
setting
Setting
range
Comment
Function RO1V4/V7 RO1V4 RO1V4
RO1V7
constant
RO1V4 = First permeate
RO1V7 = Draining of bypass
Constant = output continu-
ously produces 24 V DC. Switching capacity max. 5 W
Function programmable output
Operation Operation/
dry-run pro-
tection
Operation = contact closes upon start of RO1P1
Dry-run protection = contact opens if BB1CL4 is undershot and closes if BB1CL3 is ex­ceeded.
Redundancy RO1P2/RO1P3 (*)
No No/Yes If two dosing pumps are
present
No = the pumps have differ­ent dosing purposes
Yes = the pumps have the same dosing purpose and work redundantly
Operating duration in case of redundancy
6 h 1…9 h
Dosing, operation + flushing (*)
No
If dosing is se-
lected as pre-
treatment P2
No/P2/P3/
both
The dosing pump either only runs during the permeate pro­duction or in addition during the flushing at the end of pro­duction:
No = dosing only during per­meate production (one or two dosing pumps)
RO1P2 = two dosing pumps are present and P2 also runs during flushing
RO1P3 = two dosing pumps are present and P3 also runs during flushing
Both = two dosing pumps are present and both also run during flushing
Pulse division RO1P2/RO1P3
1 1 ... 99 Settings for antiscalant
(valid for both pulse outputs) MT 4010: 1 MT 4000: 10
Output logic Volt.-free contact Warning
NOC NOC/
NCC
Switching behaviour of signal contact terminals 8/9:
NCC = contact opens in case of Mains Off or in case a sig­nal occurs
NOC= contact closes if a sig­nal occurs
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
50
Parameters Factory
setting
Setting
range
Comment
Output logic Volt.-free contact Error
NOC NOC/
NCC
Switching behaviour of fault signal contact terminals 7/9:
NCC = contact opens in case of Mains Off or in case a sig­nal occurs
NOC= contact closes if an er­ror occurs
Output logic Release NX1Q1
NOC NOC/
NCC
Switching behaviour Release NX1Q1 terminal 14/15:
NOC = contact closes in case of release.
NCC = contact opens in case of release.
Input logic Minimum pressure switch RO1CP1(*)
NOC NOC/
NCC
Switching behaviour of low pressure switch terminals 54/55:
NOC = contact is closed by means of sufficient pressure in the inlet
NCC = contact is opened by means of sufficient pressure in the inlet
Input logic Fault signal RO1A1 (*)
NCC NOC/
NCC
If the frequency converter works properly, it has to es­tablish a connection between its voltage-free contact termi­nals 10/11 and terminals 56/57 of the GENO-OSMO-X control unit
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
51
Parameters Factory
setting
Setting
range
Comment
Function Programmable input
Signal Signal/
error/
forced stop
Forced stop
with signal +
delay of mem-
brane degas-
sing
Input function terminals 60/61:
Signal = signal contact termi­nals 8/9 switches and a pro­grammable text appears, the system continues running
Error = signal contact termi­nals 7/9 switches and a pro­grammable text appears, the system switches off
Forced stop = system switches off without prior warning or error and does not flush. If the input signal is re­moved again, the system starts running again.
Forced stop with signal and delay = interrupts forced op-
eration (overfill protection) and opens MV V4.
Membrane degassing = sys­tem switches off and text dis­played for prog. input is indi­cated.
Function Release input
0 0/1/2
Bus signal
Input terminals 52/53 reacts to NOC:
0 = no function stored
1 = function „Smart Metering“
for systems with large perme­ate tank and measurement of filling level with 4-20 mA sig­nal: In case of „favourable electricity tariffs“, the in­put/output level is increased, so that preferably permeate for stocks can be produced.
2 = „standard“ start / stop command (analogue button Info level) via release input.
Bus signal = „standard“ start / stop com-mand (analogue button Info level) via release from bus system on site (Mas­ter).
Text displayed for prog. input
20
alphanumeric
digits
If the programmed input is programmed to Signal or Er­ror, the text will be displayed if a signal occurs at terminals 60/61
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
52
Parameters Factory
setting
Setting
range
Comment
Input logic Error empty signal RO1CL.2 (*)
NOC NOC/
NCC
Contact type suction lance dosing pump RO1 P2 termi­nals 63/64 (empty signal) resp. 63/65 (pre-warning):
NOC = open contact means level has been undershot
NCC = closed contact means level has been undershot
Input logic Pre-warning RO1CL1 (*)
NOC NOC/
NCC
Input logic Residual hardness NX1CQ1(*)
NOC NOC/
NCC
Contact type alarm + limit value terminals 66/67 from monitoring device for residual hardness:
NOC = Contact opens in case of power failure, malfunction or if the limit value is exceeded
NCC = Contact is closed in case of alarm or if the limit value is exceeded.
Input logic Level BB1CL1 … CL4
CL1: NCC
CL2…4:
NOC
NOC/
NCC
The topmost level is declared as NCC by the factory, so that an error in the filling level measurement can be detected.
NOC = contact open means level has been undershot
NCC = contact closed means level has been undershot
Input logic Programmable fault signal input
NOC NOC/
NCC
Input logic terminals 60/61:
Input logic Error empty signal RO1CL4 (*)
NOC NOC/
NCC
Contact type suction lance dosing pump RO1P3 termi­nals 50/62 (empty signal) resp. 50/51 (pre-warning):
NOC = contact open means level has been undershot
NCC = contact closed means level has been undershot
Input logic Signal pre-warning RO1CL3(*)
NOC NOC/
NCC
Input logic Overpressure switch RO1 CP3
NCC NOC/
NCC
Contact type terminals 58/59:
NOC = too high system pres­sure closes contact
NCC = too high system pres­sure opens contact
Solenoid valve out­puts
intermittend intermittend/
constant
Applies to all valve outputs.
Intermittend = valve output with timed pulses.
Constant = valve output with constant pulses.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
53
Parameters Factory
setting
Setting
range
Comment
Source Switch on/off pressure
Internal Internal/
HMS/modbus
Internal = takes the values of the OSMO-X controller.
HMS = takes the values of the Profibus/BACnet Master con­troller.
Modbus = takes the values of the Modbus Master controller.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
54
4.3 Customer service level
The customer service level contains parameters that might have
to be adapted to the conditions on site during the start-up. Access to this level is protected by a Code.
4.4 Extended customer service level I
In the extended customer service level I, fundamental parameters
are stored that in general only have to be programmed in Grünbeck's manufacturing department but rarely on site. Access to this level is protected by a Code.
4.5 Extended customer service level II
In the extended customer service level II, fundamental parame-
ters are stored that in general only have to be programmed in Grünbeck's manufacturing department but rarely on site. Access to this level is protected by a Code.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
55
4.6 Counter readings, error memory
Here, the system's history is documented. Access to this level is
protected by Code 245.
Parameters Display Comment
Operating hours [h] Time during which the system
has been connected to the power supply
Sum permeate [m³] Permeate volume produced to
date
Sum concentrate to drain
[m³] Waste water volume pro-
duced to date
Run time of HP pump RO1P1
[h] Time during which permeate
has been produced
Run time of HP pump
2. stage RO1P4
[h]
Operating hours of AVRO RO1B1
[h]
Limit value for recovery exceeded
[h] Time during which the recov-
ery was > than the limit value (e. g. while the system was started)
Counter operating phases < 30 minutes
XXXXXX Three counters register how
often the system produced permeate between the switch­on and switch-off command. This helps the technical cus­tomer service to optimise the system parameters
Counter operating phases 30 ... 90 minutes
XXXXXX
Counter operating phases > 90 minutes
XXXXXX
1 Exxx … 20 Exxx
Error
date, time
Error memory containing the 20 most recent events
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
56
4.7 Key operation
Key operation is required during start-up and for service pur-
poses, if components need to be replaced. Access to this level is protected by a Code.
4.8 Reset of counter readings
After the completion of the maintenance work or the replacement
of a component, the respective counter reading can be deleted. Access to the menu is protected by a Code.
4.9 Memory of operating parameters
In the operating parameter memory, the last 30 parameter modi-
fications are documented. Access to the menu is not protected by a Code.
No. = consecutive number 1…30 of the operating parameter
memory
Code = affected Code level
Idx = index no. of the parameter within the Code level (0…)
Pre = former setting value
Post = new setting value
Time = time/date of the modification
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
57
5 | Permeate tank
As the permeate tank does not have any functions of its own,
only its Info level is displayed if the system output Tank is pro­grammed at the GENO-OSMO-X . Access is not limited via Code.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
58
6 | Pre-treatment by means of antiscalant dosing
If a pre-treatment by antiscalant dosing is used, its Info level can
be accessed via the dosing pump screen.
The estimated range of the dosing container’s content for the
permeate to be produced can be called up within the Info level:
By pressing on the illustration, the submenu may be accessed. It
is divided as follows:
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
59
6.1 Operator menu
The Operator menu can be accessed without a code query.
Parameter Factory
setting
Area Comment
Container size [l] 10 10 / 20 Dosing container content:
10 l: OSMO-X 200 … 1200 20 l: OSMO-X 1600 … 3000
Change dosing con­tainer P2
No No/yes This parameter must be repro-
grammed to "yes" if a full dosing container is used. This restarts the calculation of the estimated amount in the Info level.
6.2 Customer Service level
The Customer Service level contains parameters, which must be adapted to the conditions on-site if possible during the start-up procedure. Access to the level is protected by a code.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
60
G Troubleshooting
1 | Basic information
There is a difference between warnings and errors:
Warning = the status line in the GENO-tronic operating ele-
ment is high-lighted in yellow and the signal contact of the OSMO-X control unit (terminals 8/9) opens
Error = the status line in the GENO-tronic operating element
is high-lighted in red and the fault signal contact of the OSMO-X control unit (terminals 7/9) opens
As long as the power supply is on and no warnings/errors are pending, the signal contact and the fault signal contact are closed.
For troubleshooting in general, also refer to chapter F-2.4.
Note: A malfunction at one of the subsystems installed up­stream, in general causes the shut-off of the subsystems in­stalled downstream. Eliminating and acknowledging the malfunc­tions generally provokes the disconnected subsystems to restart automatically.
Even carefully designed and manufactured technical systems
that are operated properly, may experience malfunctions. Table G-1 provides an overview of possible problems that may occur during the operation of the systems and indicates the causes and their elimination.
Note: Grünbeck's technical customer service/authorised service company definitely must be notified in case of warnings or mal­functions that cannot be remedied with the information given in tables G-1 and G-2! When contacting the technical customer service, please indicate the system designation, serial number and the error message displayed.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
61
2 | How to remedy warnings
Table G-1: Warnings
This is what you observe This is the cause This is what to do
W006 Malfunction of parameter ad­justment EH (water softener)
Malfunction of parameter adjust­ment EH (water softener).
Different software versions of OSMO-X and water softener. Per­form an update.
Incorrect water softener selected. W007 Firmware of water softener out­of-date
Firmware of water softener out-of­date.
Software version of operating ele-
ment not compatible with basic cir-
cuit board. Update basic circuit
board. W008 Malfunction of parameter ad­justment DH (pressure booster)
Malfunction of parameter adjust­ment DH (pressure booster).
Different software versions of
OSMO-X and pressure booster sys-
tem.
Perform an update.
Incorrect pressure booster system
selected. W009 Firmware of pressure booster out-of-date
Firmware of pressure booster out­of-date.
Software version of operating ele-
ment not compatible with basic cir-
cuit board. Update basic circuit
board. W010 HMS bus module not sup­ported.
HMS bus module not supported. Module not recognized properly or a
module type that is not yet being
supported was plugged in. W021 LF permeate conductivity RO1CQ1
The conductivity monitoring of the permeate is programmed to “sig­nal“ and the conductivity continu­ously exceeded the threshold value for longer than the pro­grammed delay time.
Typical system behaviour: Following the start of the permeate production, the permeate conduc­tivity quickly and within minutes drops (first permeate) until a more or less constant value is reached. A non-functioning pre-treatment, adversely affects (scaling) this con­stant value.
Also refer to chapter F-4.1:
Conductivity limit value too low or
delay conductivity signal/error pro-
grammed too short.
If necessary notify Grünbeck’s tech-
nical customer service/authorised
service.
W022 DOS low RO1CL1
Only in case of DOS pre-treatment: Dosing agent will be used up soon.
Insert new tank with dosing agent
and confirm in subsystem menu, so
that the range estimate is restarted.
W023 DOS low RO1CL3
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
62
Continuation table G-1: Warnings
This is what you observe This is the cause This is what to do
W024 Text displayed for prog. fault signal input
Signal is pending at the pro­grammed fault signal input. As re­sponse “warning” is programmed.
Remedy the cause of the pending signal.
W025 Battery
Buffer battery on basic circuit board (stage 1) defective.
Notify Grünbeck’s technical cus­tomer service/authorised service
company. W026 Warning preserving agent
Indication during start-up. Refer to chapter E.
W027 Battery 2
Battery on basic circuit board (stage 2) defective.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. W028 Service due W029 Service AVRO
Only in case of AVRO pre-treatment: AVRO treatment modules have to be replaced soon.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
W030 Minimum pressure
Pressure switch for minimum pres­sure 1 CP1 has detected low water pressure in the inlet.
Subsystem GENO-OSMO-X was stopped and automatically restarts after a short period of time (>> here, an acknowledgement is not required but feasible).
Following the last, unsuccessful start attempt, the GENO-OSMO-X stops and indicates the error "low pressure" (here, an acknowledge­ment is required).
Release water supply for
GENO-OSMO-X.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
W031 Time for first permeate ex­ceeded
The quality of the first permeate is still too bad after expiration of the set time for first permeate.
Check in the customer service menu
whether the limit value for the con-
ductivity of the first permeate is too
high or whether the time for the first
permeate was set too short. W033 Communication error softening
The bus connection to the inter­connected subsystems water sof­tener WE-X resp. pressure booster system DEA-X is disturbed.
If necessary, restore the power sup-
ply of the respective subsystems.
Check bus wiring and restore, if nec-
essary.
W034 Communication error residual hardness W035 Communication error EDI W036 Communication error pressure booster
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
63
Continuation table G-1: Warnings
This is what you observe This is the cause This is what to do
W037 Stop filter sys. or overfill safety BB1
Tank has reached max. filling level.
Check filling level in tank and regu­late, if necessary.
W038 Comm. error MK200 12RA
Bus connection to MK200 12RA module disturbed.
Check bus cabling and restore, if
necessary. W039 Error KK200 12RA defective
MK200 12RA module disturbed. Check setting at the module, check
parametrisation. W040 Comm. error MK200 4AA
Bus connection to MK200 4AA module disturbed.
Check bus cabling and restore, if
necessary. W041 Error MK200 4AA defective
MK200 4AA module disturbed. Check setting at the module, check
parametrisation. W053 Communication error basic circuit board
Faulty connection between touch panel GENO-tronic and basic cir­cuit board.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
W055 Firmware basic circuit board out of date
Firmware basic circuit board out of date
Software version of operating ele-
ment does not match with the basic
circuit board W056 SD card removed
SD card missing, defective. Insert/replace SD card.
W057 SD card full
Memory of SD card full. Replace SD card.
W058 SD card E/A error
SD card defective. Replace SD card.
W060 EH (water softener) lack of salt
Not enough salt in brine tank. Check salt level in brine tank and re-
fill salt tablets as per DIN EN 973 A,
if necessary. W061 EH (water softener) service in­terval
Maintenance interval of water sof­tener has expired.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. W062 DEA (pressure booster system) service interval
Maintenance interval of pressure booster system has expired.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. W063 DEA ext. release signal lacking
Release signal selected incor­rectly.
Check parameter settings.
W064 DEA dry-run protection
Not enough water in the supply tank.
Signal acknowledges itself as soon
as sufficient water is available again. W065 DEA power failure
Power failure >1 minute. Check parameter setting in operator
menu. Ensure power supply.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
64
3 | Troubleshooting
Table G-2: Troubleshooting
This is what you observe This is the cause This is what to do
E080: Error OSMO-X
Control unit defective. Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E081: Error power failure
Power failure has occurred, sys­tem is not set to automatic restart. Whether this affects other sub­systems as well, has to be checked on site.
Ensure reliable power supply of
GENO-OSMO-X
Refer to chapter F-4.1:
If necessary, reprogram the param-
eter "automatic system restart".
E082 EEPROM
EEPROM defective. Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E083 Comm. error stage 1
Communication with data line RS485 to control unit installed up­stream/downstream is inter­rupted.
Check the lines for proper connec-
tion. Check whether the terminating
resistors (DIP switches) are set
properly.
E084 Comm. error stage 2 E085 Sensor error pressure
Malfunction at the sensor signal 4-20 mA of the pressure sensor.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E086 Sensor error level probe
Malfunction at the sensor signal 4-20 mA of the permeate tank’s level probe.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E087 Sensor error conductivity 1
Malfunction at the sensor signal LF/PT100 of the conductivity probe.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E090: Error recovery
For more than 30 minutes, the GENO-OSMO-X control unit in­cessantly was not able to regulate the system to the correct recovery (index value exceeded by more than 5 %).
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
E091: Error WZ permeate water me­ter defective
No signal is transferred from the permeate water meter to the GENO-OSMO-X control unit.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E092: Error flow over membrane
For more than 30 minutes, the GENO-OSMO-X control unit in­cessantly had not been able to regulate the system to correctly flowing over the membrane (win­dow +/- 5 % of the index value exceeded/undershot).
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
65
Continuation table G-2: Troubleshooting
This is what you observe This is the cause This is what to do
E093: Error LF permeate con­ductivity RO1CQ1
The monitoring of the perme­ate conductivity is pro­grammed to "error" and the conductivity continuously ex­ceeded the threshold value for longer than the pro­grammed delay time (also re­fer to "warning permeate con­ductivity RO1CQ1).
Also refer to chapter F-4.1: Conductivity limit value too low or delay time for conductivity signal/error programmed too short?
Notify Grünbeck’s technical cus­tomer service/authorised service
company. E094: Error AVRO current
Only in case of AVRO pre­treatment: The current in the AVRO treatment module is too low, the pre-treatment does not function any longer.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
E095: Error HP pump RO1P1
Frequency converter of high­pressure pump signals an er­ror.
Flip the GENO-OSMO-X control
unit towards the front. Report
the error message of the fre-
quency converter to Grünbeck’s
technical customer service/au-
thorised service company. E096: Error DOS empty RO1P2
Only in case of DOS pre­treatment: Dosing agent is used up.
Insert new tank with dosing
agent and confirm in subsystem
menu dosing, so that the range
estimate is restarted.
E097 Error DOS empty RO1P3 E098: Error residual hardness NX1CQ1
Only in case of a water sof­tener as pre-treatment: The residual hardness moni­toring system has detected hardness breaking through at the water softener.
If necessary, release a manual
regeneration at the water sof-
tener and perform a manual
analysis at the monitoring device
for residual hardness 5 minutes
later. E099: Error tank filling level BB1CL
Only in case the system out­let is a tank: An invalid signal was re­ceived from the level monitor­ing of the permeate tank.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
E100: Error overpressure RO1CP3
The pressure switch for maxi­mum pressure has reacted within the system.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E101: Error minimum pressure RO1P1
Also refer to „ low pressure warning“: The last automatic restart at­tempt was unsuccessful.
Release water supply for
GENO-OSMO-X.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company, if necessary. E102: Error permeate pressure RO1CP2
Only in case of Online system outlet: Permeate pressure continu­ously did not get beyond an alarm limit value for longer than the programmed time (possibly due to line breakage).
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
Delay time and alarm limit value
can be adapted to conditions
prevailing on site.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
66
Continuation table G-2: Troubleshooting
This is what you observe This is the cause This is what to do
E103: Text displayed at prog. fault signal input
Signal is pending at the pro­grammable fault signal input. The reaction is programmed to "error".
Remedy the cause of the pend­ing signal.
Correct the programming of the system reaction, if necessary
(refer to chapter F-4.2). E104: Error GENO-tronic
Operating element of the con­trol unit defective.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E107. Error temperature sensor
Temperature sensor of the permeate conductivity meas­uring cell defective or short­circuit at the conductivity measuring cell
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
E108: Error HP pump RO1P2
Frequency converter of high­pressure pump signals an er­ror.
Flip the GENO-OSMO-X control
unit towards the front. Report
the error message of the fre-
quency converter to Grünbeck’s
technical customer service/au-
thorised service company. E110: R01V1 does not close
V1 does not close, probably due to impurities or a defec­tive valve.
Clean R01V1. Replace solenoid
valve.
E111: Membrane degassing
Air flow is too low. Check compressed air supply.
E113: EH (water softener) Error power failure
Power failure > 5 minutes. If the power failure took longer,
start a manual regeneration to
be on the safe side. The water
flowing through the system in
the meantime, was not regis-
tered and the exchanger in oper-
ation might be overrun. E114: EH (water softener) Error valve motor
The next step positon at the control valve was not reached within the required time.
If the error occurs again within 5
minutes after it was
acknowledged, notify
Grünbeck’s technical customer
service/authorised service com-
pany. E116: Error hard water
While one exchanger tank has not yet been regener­ated, the other is already ex­hausted.
The error will acknowledge itself
as soon as a regenerated ex-
changer tank is available again.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
67
Continuation table G-2: Troubleshooting
This is what you observe This is the cause This is what to do
E120: Error micro-switch
Outside of the regeneration, the signal of micro-switch S2 is pending at terminal 14.
Check wiring and function of the switch and notify Grünbeck’s technical customer service/au­thorised service company, if
necessary. E124: Error motor current
Monitoring of the step motor current has reacted.
If the error occurs again within 5
minutes after it was acknowl-
edged, notify Grünbeck’s tech-
nical customer service/ author-
ised service company. E127: Bus error RO1 - DEA1
Communication with data line RS485 to control unit of the pressure booster installed downstream is interrupted.
Check the lines for proper con-
nection. Check whether the ter-
minating resistors (DIP
switches) are set properly. E150: Stage 2 Error OSMO-X
Control unit defective. Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E151: Stage 2 Error power fail­ure
Power failure has occurred, system is not set to automatic restart. Whether this affects other subsystems as well, has to be checked on site.
Ensure reliable power supply of
GENO-OSMO-X
Refer to chapter F-4.1:
If necessary, reprogram the pa-
rameter "automatic system re-
start".
E152: Stage 2 EEPROM
EEPROM defective. Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E153: Stage 2 Comm. error stage 1
Communication with data line RS485 to control unit installed upstream/downstream is in­terrupted.
Check the lines for proper con-
nection. Check whether the ter-
minating resistors (DIP
switches) are set properly.
E154: Comm. error stage 2 E155 Stage 2 sensor error pres­sure
Malfunction at the sensor sig­nal 4-20 mA of the pressure sensor.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E156 Stage 2 sensor error level probe
Malfunction at the sensor sig­nal 4-20 mA of the permeate tank’s level probe.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E157 Stage 2 sensor error RO1CQ2
Malfunction at the sensor sig­nal LF/PT100 of the conduc­tivity probe.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
68
Continuation table G-2: Troubleshooting
This is what you observe This is the cause This is what to do
E160: Stage 2 Error recovery
For more than 30 minutes, the GENO-OSMO-X control unit in­cessantly was not able to regu­late the system to the correct re­covery (index value exceeded by more than 5 %).
Notify Grünbeck’s technical cus­tomer service/authorised service company.
E161: Stage 2 Error WZ permeate water meter defective
No signal is transferred from the permeate water meter to the GENO-OSMO-X control unit.
Notify Grünbeck’s technical cus­tomer service/authorised service
company. E162: Stage 2 Error flow over the membrane
For more than 30 minutes, the GENO-OSMO-X control unit in­cessantly had not been able to regulate the system to correctly flowing over the membrane (win­dow +/- 5 % of the index value exceeded/ undershot).
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
E163: Stage 2 Error LF permeate conductivity RO1CQ1
The conductivity monitoring of the permeate is programmed to “error“ and the conductivity con­tinuously exceeded the threshold value for longer than the pro­grammed delay time. (Also refer to „warning LF permeate conduc­tivity RO1CQ1“)
Also refer to chapter F-4.1:
Conductivity limit value too low or
delay conductivity signal/malfunc-
tion programmed too short.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E095: Stage 2 Error HP pump RO1P4
Frequency converter of high­pressure pump signals an error.
Flip the GENO-OSMO-X control unit
towards the front. Report the error
message of the frequency converter
to Grünbeck’s technical customer
service/authorised service com-
pany. E170: Stage 2 Error low pressure RO1CP5
The pressure switch for maxi­mum pressure has reacted within the system.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E172: Stage 2 Error permeate pres­sure RO1CP5
Only in case of Online system outlet: Permeate pressure continuously did not get beyond an alarm limit value for longer than the pro­grammed time (possibly due to line breakage).
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
Delay time and alarm limit value can
be adapted to conditions prevailing
on site. E173: Stage 2 Text displayed at prog. fault signal input
Signal is pending at the program­mable fault signal input. The re­action is programmed to "error".
Remedy the cause of the pending
signal.
Correct the programming of the sys-
tem reaction, if necessary (refer to
chapter F-4.2) E174: Stage 2 Error GENO-tronic
Operating element of the control unit defective.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
69
Continuation table G-2: Troubleshooting
This is what you observe This is the cause This is what to do
E177. Error 2 Error temperature sensor
Temperature sensor of the perme­ate conductivity measuring cell de­fective or short-circuit at the con­ductivity measuring cell.
Notify Grünbeck’s technical cus­tomer service/authorised service company.
E178: Stage 2 Error HP pump RO1P4
Frequency converter of high-pres­sure pump signals an error.
Flip the GENO-OSMO-X control unit towards the front. Report the error message of the frequency converter to Grünbeck’s technical customer service/authorised ser-
vice company. E182 Tripped fuse 24V MV
Short-circuit/overload at the sole­noid valves.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E183 Short-circuit limit switch volt­age
Short-circuit/overload at the input signals.
Notify Grünbeck’s technical cus-
tomer service/authorised service
company. E184 Communication error water softener
Communication with data line RS485 to control unit of the water softener installed upstream is in­terrupted.
Check the lines for proper connec-
tion. Check whether the terminating
resistors (DIP switches) are set
properly.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
70
H Maintenance
1 | Basic information
In order to guarantee the reliable function of the systems over a
long period of time, some maintenance work has to be per­formed at regular intervals. All regulations and guidelines which apply at the installation site must be strictly adhered to.
Check the quality and the system volume flows every day.
Maintenance has to be performed by Grünbeck’s technical
customer service/authorised service company or a specialist company. Maintenance is subject to the load but at the latest has to be performed once a year.
An operation log and the corresponding test log must be kept
in order to document the maintenance work performed.
Note: A maintenance contract ensures that all the required maintenance work will be performed in due time.
The maintenance work performed must be documented in the checklist, refer to appendix "Operation log".
2 | Inspection (functional check)
You may perform the daily inspections yourself.
Please refer to the following summary for the tasks to be per­formed within the framework of an inspection.
Summary: Inspection work
Determine the feed water hardness (inlet).
(Water test kit "Total hardness“)
Determine the permeate quality. Either at the display if a con-
ductivity monitoring device is installed or by means of a man­ual conductivity meter
Read the recovery
Take the remaining time of the service interval into account
Chapter F-2.2 Read operating state. In case the remaining time of the service interval is < 30 days, notify Grünbeck's technical customer service about the impending service.
Note: Minor deviations are normal and cannot be prevented technically. In case of considerable deviations from the standard, notify Grünbeck's technical customer service/authorised service company.
Make sure that there are no leakages from the system to the
drain; the feed water solenoid valve is not tightened; visible at the display (fig. F-2). In this state, no water must creep to the drain.
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
71
3 | Maintenance
According to DIN 1988 part 8 / A 12, maintenance work at the systems may only be performed by Grünbeck’s technical cus­tomer service/authorised service company or an approved spe­cialist company.
For this kind of systems, an operation log - a checklist has to be
kept. In this operation log, the customer service technician records all maintenance and repair work performed. In case of malfunc­tions, this log helps to identify possible sources of error. In addi­tion the log documents the proper system maintenance.
Note: Make sure that all maintenance work is recorded in the operation log as well as in the corresponding test report.
Summary: Maintenance work
Replace the filter elements.
If necessary, replace the filter cartridge of the activated car-
bon filter.
Check the permeate quality; flush or replace the membrane,
if required. So-called flushing instructions (order no. 700 950) are available for authorised service personnel.
Clean the solenoid valves - check their function.
Check the flow volumes and recalibrate the conductivity
measurement.
Check the state of the entire system and check for tightness.
Mechanical resp. electrical functional and performance check
of all aggregates (pumps, valves).
Prepare a written maintenance log on the state and function
of the system and the maintenance work performed, incl. evaluation and assessment of the operating values and water analysis results.
Note: The maintenance work performed must be documented in the checklist, refer to appendix "Operation log".
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
72
4 | Operation log
Customer
Name: ....................................................................
Address: .................................................................
...............................................................................
...............................................................................
Reverse osmosis GENO-OSMO-X
(please check appropriate box)
Serial num­ber
....................................................................................................
Installed by
....................................................................................................
Drinking water filter:
Make/Type ....................................................... /
.........................................................................
System separator:
Make/Type ....................................................... /
.........................................................................
Water softener:
Make/Type ....................................................... /
.........................................................................
Activated carbon filter:
Make/Type ....................................................... /
.........................................................................
Fine filter:
Make/Type ....................................................... /
.........................................................................
200 400
800 1200 1600 2200 3000
Others ............................................
Connection data Drain connection DIN 1988
yes no
(please check appropriate box)
Floor drain available
yes no
Line upstream of reverse
osmosis
Galvanised
Copper
Plastic
Height of drain
. . . . cm from bottom edge of the
system
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
73
Reverse osmosis system GENO-OSMO-X
Checklist, start-up, maintenance
Please enter measured values. Confirm checks with OK or enter repair work performed.
Maintenance per­formed without re- placement of the module
Maintenance per­formed with re- placement of the module
Start-up Date
Module no. ................. Module
no.
.................................
Measured values
Water volumes and water qualities prior to or during start-up resp. / after replacement of the modules
Conductivity
(µS/cm)
Total
hardness
[dH]
Temperature
[C]
Volume flow
[l/h]
Recovery
[%]
before / after before / after before / after before / after before / after Feed water
/ / / /
Permeate / / / /
Concentrate to drain
/ / / / . . . . % / . . . . %
Confirmation Remarks
Water meter reading upstream of the system [m³]
Inlet water pressure (1-4 bar) checked
Drinking water filter upstream of the system checked Filter elements replaced
Controller settings checked: In particular pre-treatment, recovery, system outlet
Operating hours
Run time of high-pressure pump [h]
Concentrate volume accrued [m³]
Feed water volume [m³]
Permeate volume produced [m³]
Check all electrical lines for external damage
Check all hydraulic connections for external damage
Solenoid valve for feed water and flushing wa­ter cleaned and checked for tightness
Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
74
Confirmation Remarks
Pressure switch for minimum pressure checked for function
Conductivity sensor checked/cleaned
Visual check of electronics board
System checked for tightness
Only in case of installation of an electronic ballast for small-scale deferrisation
Miscellaneous
Notes
Customer service technician
Company
Work time certificate (no.)
Signature
Loading...