Grunbeck GENO-EDI-X Operation Manual

Operation Manual
Electrodeionisation System GENO-EDI-X
with GENO-EDI-tronic
Version: December 2018 Order no. 024 770 901-inter
GENO-EDI-X
Table of contents
AGENERAL INFORMATION .................................................................................................................................................................. 5
1 | P
REFACE
2 | H 3 | G
4 | S 5 | D
BBASIC INFORMATION ........................................................................................................................................................................ 9
1 | L 2 | W 3 | F
CPRODUCT DESCRIPTION (GENO-EDI-X) ........................................................................................................................................ 12
1 | T 2 | F 3 | B 4 | D 5 | T 6 | I
7 | A 8 | S
DINSTALLATION ................................................................................................................................................................................. 25
1 | G
2 | W 3 | H 4 | E
ECOMMISSIONING .............................................................................................................................................................................. 29
1 | G
2 | START EDI-X
FOPERATION ...................................................................................................................................................................................... 31
1 | I 2 | B
3 | S 4 | O 5 | O
GTROUBLESHOOTING ....................................................................................................................................................................... 56
1 | B 2| T
HMAINTENANCE ................................................................................................................................................................................. 5 8
1 | B 2 | I 3 | M
..................................................................................................................................................................................................... 5
OW TO USE THIS OPERATION MANUAL
ENERAL SAFETY INFORMATION
3.1
3.2
3.3
3.4
3.5
3.1 Functional principle of electrodeionisation ......................................................................................................................................... 10
3.2
NTENDED USE
6.1 | System shutdown ............................................................................................................................................................................ 19
8.1
8.2
8.3
1.1
1.1
NTRODUCTION
2.1
2.2
2.3
2.4
5.1
5.2
5.2.4System Configuration ............................................................................................................................................................ 37
5.2.5I/O Display ............................................................................................................................................................................... 38
5.2.6Error Memory .......................................................................................................................................................................... 38
5.2.7Basic Setting ........................................................................................................................................................................... 38
5.3
5.3.1Errors ...................................................................................................................................................................................... 3 9
5.3.2Warnings ................................................................................................................................................................................. 41
5.4
5.4.1User......................................................................................................................................................................................... 4 3
5.4.2Parameters .............................................................................................................................................................................. 43
5.4.3Times ...................................................................................................................................................................................... 46
5.4.4Errors ...................................................................................................................................................................................... 4 7
5.4.5Service Data ............................................................................................................................................................................ 50
5.4.6Reference Data ....................................................................................................................................................................... 51
5.4.7Basic Setting ........................................................................................................................................................................... 52
5.5
5.5.1User......................................................................................................................................................................................... 5 4
5.5.2Parameters .............................................................................................................................................................................. 54
5.5.3Errors ...................................................................................................................................................................................... 5 5
5.5.4Service Data ............................................................................................................................................................................ 55
5.5.5Basic Setting ........................................................................................................................................................................... 55
ROUBLESHOOTING
NSPECTION (FUNCTIONAL CHECK
3.1
Symbols and notes .................................................................................................................................................................... 6
Operating personnel .................................................................................................................................................................. 6
Designated application .............................................................................................................................................................. 6
Protection from water damage .................................................................................................................................................. 7
Description of specific dangers ................................................................................................................................................. 7
HIPPING AND STORAGE ISPOSAL
..................................................................................................................................................................................................... 8
AWS, REGULATIONS, STANDARDS
ATER
........................................................................................................................................................................................................ 9
UNCTIONAL PRINCIPLE OF ELECTRODEIONISATION
Components of the electrodeionisation module (EDI module) ................................................................................................. 11
YPE DESIGNATION PLATE LOW CHART DESIGN
ASIC FUNCTION OF THE ELECTRODEIONISATION SYSTEM ESCRIPTION OF THE COMPONENTS
ECHNICAL SPECIFICATIONS
PPLICATION LIMITS COPE OF SUPPLY
ENERAL INSTALLATION INFORMATION
ATER CONNECTION
OW TO CONNECT THE SYSTEM LECTRICAL WIRING
ENERAL INFORMATION
RIEF DESCRIPTION OF
WITCH CABINET
PERATING THE CONTROL UNIT PERATING THE CONTROL UNIT
ASIC INFORMATION
ASIC INFORMATION
AINTENANCE
............................................................................................................................................................................................ 1 9
  
   
 
...................................................................................................................................................................................... 21
Standard equipment ................................................................................................................................................................ 21
Optional features ..................................................................................................................................................................... 22
Wearing parts .......................................................................................................................................................................... 24
Preliminary work ...................................................................................................................................................................... 25
Preliminary work ...................................................................................................................................................................... 29
SYSTEM OPERATION
............................................................................................................................................................................................ 31
Field of application .................................................................................................................................................................. 31
Function .................................................................................................................................................................................. 31
Basic technical parameters – control panel ............................................................................................................................. 31
Basic technical parameters – MK200 basic module ................................................................................................................. 31
......................................................................................................................................................................................... 32
Basic information regarding the operation of the control unit ................................................................................................... 34
System menu .......................................................................................................................................................................... 34
Messages and signals ............................................................................................................................................................. 39
Electrodeionisation (GENO-EDI-X system) .............................................................................................................................. 4 2
Pressure booster (PB system) if activated in system menu ..................................................................................................... 53
............................................................................................................................................................................................ 5 9
Operation log ........................................................................................................................................................................... 59
............................................................................................................................................................ 5
..................................................................................................................................................................... 6
................................................................................................................................................................................ 7
.................................................................................................................................................................. 9
......................................................................................................................................... 10
............................................................................................................................................................................ 12
................................................................................................................................................................................... 12
.............................................................................................................................................................. 15
......................................................................................................................................................................... 18
.................................................................................................................................................................................... 20
.......................................................................................................................................................... 25
................................................................................................................................................................................... 26
.................................................................................................................................................................................... 28
.................................................................................................................................................................................... 56
..................................................................................................................................................................................... 57
.................................................................................................................................................................................... 58
.................................................................................................................................................................... 27
............................................................................................................................................................................... 29
.............................................................................................................................................................. 30
GENO-EDI-
TRONIC
.................................................................................................................................................. 31
.................................................................................................................................................................... 33
.................................................................................................................................................................... 34
) ................................................................................................................................................................ 58
GENO-EDI-X (
WITHOUT OPTIONS
) ............................................................................ 13
                                                                                
2
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Publisher's information
All rights reserved.
Copyright by Grünbeck Wasseraufbereitung GmbH
Printed in Germany Effective with the date of edition indicated on the cover sheet.
-We reserve the right to modifications, especially with regard to technical progress-
Reprints, translations into foreign languages, electronic storage or digital copying of this operation manual – even in parts – may take place only with explicit written approval of Grünbeck Was­seraufbereitung GmbH.
Any type of duplication not authorised by Grünbeck Wasserauf­bereitung is a copyright violation and will be prosecuted.
Responsible for contents: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1 89420 Höchstädt/Do. Phone 09074 41-0  Fax 09074 41-100 www.gruenbeck.de service@gruenbeck.de
GENO-EDI-X
Printing: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1, 89420 Höchstädt/Do.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
3
GENO-EDI-X
EC Declaration of Conformity
We hereby declare that the system designated below meets the safety and health requirements of the applicable European guidelines in terms of its design, construction and manufacture.
This certificate will become invalid if the system is modified in a way not approved by us.
Manufacturer: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1 89420 Hoechstaedt/Germany
Responsible for documentation: Roland Rehberger
System designation:
System size: 100, 180, 360, 720, 1100, 1450, 2000, 2700
System number: Refer to type designation plate
Applicable directives: Machinery Directive (2006/42/EC)
Applied harmonised standards, in particular:
Applied national standards and technical specifications, in particular:
Place / Date / Manufacturer's signa­ture:
Function of signatory: Head of Technical Systems and Equipment
Electrodeionisation system GENO-EDI-X
EMC (2014/30/EU)
EN ISO 12100:2011-03, EN 61000-6-2:2006-03 EN 61000-6-3:2011-09
Höchstädt, 2018-10-11 p.p.a. P. Höß
4
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
A General information
GENO-EDI-X
1 | Preface
Thank you for opting for a Grünbeck product. Backed by
Advice and assistance
decades of experience in the area of water treatment, we provide solutions for all kind of processes.
All Grünbeck systems and devices are made of high-quality materials. This ensures trouble-free operation over many years, provided you treat your water treatment system with the required care. This operation manual assists you with important information. Therefore, please read the entire operation manual before installing, operating or maintaining the system.
Customer satisfaction is our prime objective and providing customers with qualified advice is crucial. If you have any questions concerning this device, possible extensions or general water and waste water treatment, our field service staff, as well as the experts at our headquarters in Hoechstaedt, are available to help you.
For advice and assistance please contact your local representative (refer to www.gruenbeck.de).
In case of emergency, please get in touch with our service hot­line at +49 9074 41-333. We can connect you with the appropri­ate expert more quickly if you provide the required system data.
To ensure that this information is to hand at all times, please keep the precise equipment data to hand (refer to the type plate in chapter C-1).
2 | How to use this operation manual
This operation manual is intended for the operators of our sys-
tems. It is divided into several chapters (a letter is assigned to each of them) which are listed in the table of contents on page 2 in alphabetical order. Check for the corresponding chapter on page 1 in order to find the specific information you need.
The headers and page numbers with chapter information make it easier to find your way around in the operation manual.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
5
GENO-EDI-X
3 | General safety information
3.1 Symbols and notes
Important information in this operation manual is emphasised by symbols. Please pay particular attention to this information to ensure the hazard-free and safe handling of the system.
Danger! Failure to adhere to this information will cause serious or life-threatening injuries, extreme damage to property or inadmissible contamination of the drinking water.
Warning! Failure to adhere to this information may cause injuries, damage to property or contamination of the drinking water.
Caution! Failure to adhere to this information may result in damage to the system or other objects.
Note: This symbol emphasises information and tips that make your work easier.
Tasks with this symbol may only be performed by Grünbeck's technical service/authorised service company or by persons expressly authorised by Grünbeck.
Tasks with this symbol may only be performed by trained and quali­fied electrical experts according to the VDE guidelines or according to the guidelines of a similar local institution.
Tasks with this symbol may only be performed by water suppliers or approved installation companies. In Germany, the installation company must be registered in an installation directory of a water supplier as per §12(2) AVBWasserV (German Ordinance on General Conditions for the Supply of Water).
3.2 Operating personnel
3.3 Designated application
Only persons who have read and understood this operation manual are permitted to work with the system. Strictly observe the safety information.
The system may only be used for the purpose outlined in the product description (chapter C). The guidelines in this operation manual as well as the applicable local guidelines concerning drinking water protection, accident prevention and occupational safety must be observed.
In addition, intended use also implies that the system may only be operated when it is in proper working order. Any errors must be eliminated at once.
The GENO-EDI-X is exclusively designed for use in the indus­trial and commercial field.
6
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
3.4 Protection from water damage
3.5 Description of specific dangers
GENO-EDI-X
Warning! In order to properly protect the installation site against water damage:
A sufficiently dimensioned floor drain system must be
available or
a water stop device (refer to chapter C “Accessories”) must
be installed.
Warning! Floor drains that discharge to a lifting system will not work in case of a power failure.
Danger due to electrical energy! Do not touch electrical parts with wet hands! Disconnect the system from the mains before starting work on electrical system components. Have qualified experts replace damaged cables immediately.
Danger due to mechanical energy! System components may be subject to overpressure. Danger of injury and damage to property due to escaping water and unexpected movement of system components. Check pressure pipes regularly. Depressurise the system before starting repair or maintenance work on the system.
Hazardous to health due to contaminated drinking water! The system shall be installed only by a specialist company. Strictly observe the operation manual! Ensure that there is sufficient flow; the relevant guidelines must be followed for commissioning after extended periods of standstill. Inspections and maintenance must be performed at the intervals specified!
Note: By concluding a maintenance contract, you ensure that all
of the required tasks are performed on time. You may perform the interim inspections yourself.
4 | Shipping and storage
Caution! The system may be damaged by frost or high
temperatures. In order to avoid damage of this kind:
Protect from frost during transportation and storage! Do not install or store the system next to objects which radiate a lot of heat.
The system may only be transported and stored in its original
packing. Ensure that it is handled with care and placed the right side up (as indicated on the packaging).
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
7
GENO-EDI-X
5 | Disposal
Comply with the applicable national regulations.
5.1 Packaging
5.2 Product
Dispose of the packaging in an environmentally friendly manner.
If this symbol (crossed out waste bin) is on the product, this product is subject to the European Directive 2012/19/EU. This means that this product or the electrical and electronic compo­nents must not be disposed with household waste.
Learn about the local regulations on the separate collection of electrical and electronic products.
For information on collection points for your product, contact your municipality, the public waste management authority, an authorised body for the disposal of electrical and electronic prod­ucts or your waste disposal service.
8
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
GENO-EDI-X
B Basic information
1 | Laws, regulations, standards
In the interest of good health, rules cannot be ignored when it
comes to the processing of drinking water. This operation manual takes into consideration the current guidelines and stipulates information that you will need for the safe operation of your water treatment system.
Among other things, the set of rules stipulate that
only approved specialist companies are permitted to make
major modifications to water supply systems
and that tests, inspections and maintenance on installed
devices are to be performed at regular intervals.
2 | Water
As a result of dynamic substance and water cycles, increasingly
polluting elements are being released into the natural environment. These are only partially and slowly broken down by natural effects. Consequently, these elements build up in the groundwater and surface water over the course of time. Removing them from natural water deposits again represents a particular challenge. Grünbeck faces this challenge with the aim of producing unpolluted drinking and industrial water.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
9
GENO-EDI-X
3 | Functional principle of electrodeionisation
3.1 Functional principle of electrodeionisation
Function
The electrodeionisation represents a continuous, electrochemical membrane process that combines membrane technology and ion exchanger technology.
In this process, ion exchanger resin, ion-selective membranes and direct current are used to remove ions from the permeate of a reverse osmosis system.
The resulting diluate (ultra-pure water) has a residual conductivity of < 0.2 µS/cm. The residual conductivity depends on the quality of the feed water (permeate).
The advantage of this technology is the fact that the regeneration (by means of direct current) continuously takes place during operation and no chemicals (acids/bases) are required.
Contrary to common ion exchanger systems, the electrodeionisation system GENO-EDI-X considerably reduces the TOC values.
The core – the EDI module – consists of several chambers filled with layers of anion and cation exchanger resins. The chambers are separated from each other by anion and cation membranes.
The feed water (permeate) flows into the EDI module and is divided into a diluate, concentrate and electrolyte water flow. Due to the direct voltage applied, the ions move from the diluate chambers filled with ion exchanger resin to the concentrate chambers that are also filled with ion exchanger resin. While the water is in the diluate chambers is being fully demineralised, the direct current splits the water into hydrogen ions (H+) and hydroxide ions (OH exchanger resins are regenerated again.
A part (10 %) of the feed water volume (permeate) rinses the concentrate and the electrode chambers. The volume designated as concentrate (unpressurised) is then either directed to the drain or returned to the inlet of the reverse osmosis system to be fed again.
The electrodeionisation system GENO-EDI-X has a recovery of 90 - 95 %.
-
) by which in turn the ion
10
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
3.2 Components of the electrodeionisation module (EDI module)
GENO-EDI-X
Permeate inlet Diluate outlet
1 2
Concentrate outlet
3 4
Cathode (-)
5 6
Diluate chamber with ion exchanger resin
7
Cation membrane (C)
9
Anode (+)
Concentrate chamber with ion exchanger resin
Anion membrane (A)
8
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
11
GENO-EDI-X
C Product description (GENO-EDI-X)
1 | Type designation
plate
Please specify the data shown on the type designation plate of your GENO-EDI-X electrodeionisation system in order to speed up the processing of enquiries or orders. Please add the necessary information to the overview below to have it readily available whenever necessary.
Electrodeionisation system GENO-EDI-X:
Serial number:
Order number:
     
     
    
2 | Flow chart design
Fig. C-1: Type designation plate of the electrodeionisation system GENO-EDI-X
Fig. C-2: Flow chart of GENO-EDI-X
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
12
GENO-EDI-X
3 | Basic function of the electrodeionisation system GENO-EDI-X
(without options)
If the system is in standby mode and ready for operation, the inlet rejection valve and the inlet valve are closed. There is no voltage present at the EDI module. If available, the outlet rejection valve is open and the outlet valve closed. The electrodeionisation system receives its start signal from the level control system of the diluate tank. Then, the EDI controller transmits the start signal to the RO controller. The RO system starts operation and produces permeate. By means of the inlet rejection valve, the time-controlled discharge of the permeate to the drain takes place. In case the conductivity measuring cell for permeate is installed, the rejection can be terminated prema­turely if the max. permeate conductivity set is undershot.
Upon termination of the inlet rejection, the inlet valve opens and the inlet rejection valve closes. When the inlet valve opens, the EDI cell is supplied with voltage. From the moment the inlet valve opens, the flows diluate and concentrate, the diluate conductivity, the pressure of permeate, diluate and concentrate as well as the temperature and the diluate are monitored and trigger a time-delayed (adjustable) warning or an alarm. The diluate is rejected via time by means of the outlet rejection - if available (option) -, with premature termination in case the max. diluate conductivity set is undershot. Following the opening of the outlet valve, the outlet rejection valve is closed. The diluate produced is now directed to the diluate tank.
As soon as the tank is full, a stop signal is transmitted to the EDI controller. Within the electrodeionisation system, the voltage supplied to the EDI cell is interrupted and the monitoring function of the EDI system is deactivated. After a set rinsing sequence, the RO system receives its stop signal and the valves move to the following positions: Inlet rejection valve and inlet valve close and – if available – the outlet rejection valve is open and the out­let vale is closed. Now, the electrodeionisation system remains in standby mode until the next demand is made.
If the system is in standby mode, the inlet rejection valve Y8 and the inlet valve Y7 are closed. There is no voltage present at the EDI module.
The GENO-EDI-X system receives a start signal from the level control system of the diluate tank. Then, the EDI controller trans­mits the start signal to the RO controller.
The RO system starts operation and produces permeate. By means of the inlet rejection valve Y8, the discharge of the per­meate to the drain takes place over a pre-set time period. Upon termination of the inlet rejection, the inlet valve Y7 opens and the inlet rejection valve Y8 closes.
When the inlet valve Y7 opens, the EDI module is supplied with the divided partial permeate flows of diluate and concentrate. In addition, the voltage and current are switched to the EDI mod­ule.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
13
GENO-EDI-X
From the moment the inlet valve Y7 opens, the diluate F7 and concentrate F8 flows, the diluate conductivity Q5, the pressure of permeate P4, diluate P5 and concentrate P6, as well as the temperature of the diluate T2 are monitored and trigger a time­delayed (adjustable) warning and/or an error.
The diluate produced is now directed to the diluate tank. As soon as the tank is full, a stop signal is transmitted to the EDI con­troler. Within the GENO-EDI-X electrodeionisation system, the voltage supplied to the EDI cell is interrupted and the monitoring function of the GENO-EDI-X system is deactivated.
After a set rinsing sequence, the RO system receives its stop signal and the valves move to the following positions: inlet rejec­tion valve Y8 and inlet valve Y7 closed.
Now, the GENO-EDI-X system remains in standby mode until the next request is made.
*Diluate = deionate, ultra-pure water
14
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
4 | Description of the components
GENO-EDI-X
Adjusting valve Operating
V4
1
2
3
4
5
6
7
pressure
(OPTION)
Adjusting valve
V5
Concentrate volume
Adjusting valve
V6
Diluate pressure
Adjusting valve
V7
Concentrate pressure
Permeate
V8
overflow valve (OPTION)
Sample valve of
Pr-P
feed water (Permeate)
Sample valve of
Pr-D
diluate
To throttle the permeate supply flow in case of excess capacity from on-site feed pumps.
Not required for agreed-upon RO/EDI system combinations.
For the adjustment of the concentrate volume conducted to the drain. This value corresponds with 10% of the permeate feed value.
For the adjustment of the diluate counter-pressure.
For the adjustment of the concentrate pressure to the diluate pressure.
Conducts the permeate from upstream RO systems to the drain; these systems work in forced operation mode. Protects the permeate side of the RO system in case the solenoid valves of the GENO-EDI-X system do not open. Adjustment: OPEN at 4 bar (g).
Possibilities of manual quality determination via sample valve.
Possibilities of manual quality determination via sample valve.
10
11
Registers the permeate quantity and sends pulses to the control electronics.
8
9
diluate
Flow sensor
F8
Concentrate
Permeate
P4
pressure sensor
Pressure sensor
P5
Diluate
Flow sensor of
F7
Visual indication of the diluate quantity in the control electronics. If the minimum flow of the diluate is undershot, an error is emit­ted. GENO-EDI-X system STOP
Registers the concentrate volume and sends pulses to the control electronics. Visual indication of the concentrate volume in the control electronics. If the minimum flow of the concentrate is undershot, an error is emitted. GENO-EDI-X system STOP
The maximum limit value is 4 bar(g) When the set maximum permeate pressure value is exceeded, the GENO-EDI-X system STOP takes place with a time delay. Visual indication in the control electronics.
Indicates the diluate pressure value in the control electronics. P5 must be at least 0.2 bar higher than P6! The alarm signal takes place with a time delay when the concentrate pressure value P6 is higher than/equal to the diluate pressure value P5. GENO-EDI-X system STOP
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
15
GENO-EDI-X
Indicates the concentrate pressure in the control electronics. P5 must be at least 0.2 bar higher than P6! The alarm signal takes place with a time delay when the concentrate pressure value P6 is higher than/equal to the diluate pressure value P5. GENO-EDI-X system STOP
Always open during diluate production. Opens after a settable time interval (permeate rejection). Opens after inlet rejection at conductivity < 20 µS/cm measured via Q4 (option). Locked in case of errors in the GENO-EDI-X system. Visual indication in the control electronics.
Opens for an adjustable time after EDI start. Opens after start of EDI until a conductivity of 20 µS/cm meas­ured via Q4 is undershot (option). Closes after inlet rejection. Visual indication in the control electronics.
12
13
14
Concentrate
P6
pressure sensor
Inlet solenoid
Y7
valve of permeate
Permeate inlet re-
Y8
jection valve
15
16
17
18
Outlet solenoid valve of diluate
Y9
(OPTION)
Outlet rejection valve of diluate
Y10
(OPTION)
Conductivity measuring cell of
Q4
permeate
(OPTION)
Conductivity
Q5
measuring cell of diluate
Opens after diluate rejection from Y10 if the conductivity limit value for diluate is undershot. Closes after GENO-EDI-X system STOP, locked in case of errors in the GENO-EDI-X system. Visual indication in the control electronics.
Opens after GENO-EDI-X system START and completed inlet rejection, closes when the conductivity limit value for diluate is undershot. Visual indication in control electronics.
Indicates the quality of the permeate in the control electronics. Enables quality-controlled permeate rejection. Y8 CLOSED and Y7 OPEN if the set conductivity limit value is undershot. Visual alarm signal in the control electronics when the set con­ductivity limit value is exceeded. GENO-EDI-X system STOP.
Indicates the quality of the diluate in the control electronics. Enables quality-controlled diluate rejection. Y10 CLOSED and Y9 OPEN if the set conductivity limit value is undershot. Visual alarm signal in the control electronics when the set con­ductivity limit value is exceeded. GENO-EDI-X system STOP.
19
20
16
Conductivity measuring cell
Q6
Concentrate (OPTION)
Permeate temper­ature sensor
T1
(OPTION)
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Indicates the quality of the concentrate in the control electronics.
Indicates the temperature of the permeate in the control elec­tronics.
Y8 CLOSED and Y7 OPEN if the set temperature value is ex­ceeded. Visual alarm signal in the control electronics when the set limit value is exceeded. GENO-EDI-X system STOP.
GENO-EDI-X
Indicates the temperature of the diluate in the control electronics.
21
22
23
Diluate temperature
T2
sensor
(OPTION)
Permeate feed
M8/
pump
P8/
Frequency­controlled
P9
(OPTION)
Level control
L4
system of diluate tank
Y9 CLOSED and Y10 OPEN if the set temperature value is exceeded.
Visual alarm signal in the control electronics when the set limit value is exceeded. GENO-EDI-X system STOP.
Increases the permeate feed pressure. Permeate pump M8 START through min. pressure contact P8. Permeate pump M8 STOP through max. pressure contact P8.
Alternatively, M8 is operated using pressure sensor P8 in a frequency-controlled manner.
M8 release always provided in case of inlet valve Y7 OPEN. M8 is locked in case of min. pressure switch P9 (min. pressure).
Visual alarm signal on the frequency converter and in the control electronics. GENO-EDI-X system STOP.
Visual indication in the control electronics. L4a+ full signal, GENO-EDI-X system STOP L4b- request, GENO-EDI-X system START L4c- additional and emergency feed (option) L4d+ empty signal, dry-run protection for PBS pump M6/M7, time-delayed release for PBS pump M6/M7 in case level is exceeded
Visual indication in the control electronics. Actuated by the pre-selector (H-O-A) in the control electronics.
Pressure booster
M6/
system
M7/
Diluate pressure switch
P7
(OPTION)
Pressure switch with min. and max. pressure contact. In case of automatic operation:
- M6/M7 ON via min. pressure contact of P7
- M6/M7 OFF via max. pressure contact of P7
- Time-controlled changeover operation of pumps M6/M7. M6/M7 re locked in case of dry-run protection L4d.
Visual alarm signal in control electronics.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
17
GENO-EDI-X
5 | Technical specifications
Table C-1: Technical
Electrodeionisation system GENO-EDI-X
specifications
100 180 360 720 1100 1450 2000 2700
Connection data
Nominal connection diameter of permeate feed line (screw connection)
Nominal connection diameter of diluate outlet line (screw connection)
Nominal connection diameter of concentrate outlet line (screw connection)
Min. drain connection required [DN] 50
Connected load, approx.
Power supply [V/Hz] 1x 230 / 50
Protection type IP 54
Performance data
Feed water volume flow (nominal)
Diluate capacity at a feed water temperature 15°C and a recovery of approx. 90 % (nominal)
Concentrate volume flow at a recovery of approx. 90% (nominal)
Diluate capacity max.**** [l/h] 150 300 600 1000 1350 2100 2600 3750
Min. diluate flow*** required [l/h] 62,5 125 250 550 550 1100 1100 1400
Min. required flow of concentrate***
Operating voltage [V-DC] < 106 < 213 < 426 < 130 < 130 < 240 < 240 < 300
Operating current [A] < 2.5 < 2.5 < 2.5 < 5 < 5 < 5 < 5 < 5
Inlet flow pressure of permeate, min./max.
Outlet pressure of diluate, approx. [bar] 0.5/1.5
Max. operating pressure
Feed conductivity equivalent (FCE)**, max.
Diluate conductivity*
TOC reduction
SiO2 reduction
Recovery***
Dimensions and weights
Dimensions (w x h x d) [mm] 900 x 1700 x 675
Min. room/installation height required [mm] 2000
Operating weight, approx. [kg] 95 105 115 170 170 190 190 215
Ambient data
Temperature of feed water, min./max. [°C] 10/25
Ambient temperature, min./max. [°C] 5/35
Order no. 770 300 770 310 770 320 770 330 770 340 770 350 770 360 770 370
*
Subject to the feed water quality ** For calculation, refer to the formula under “Application limits” *** These volume flows must be considered as the absolute minimum for the flow rates of the EDI module! **** In case of maximum recoveries of 93 and/or 95 %, the following shall further apply with regard to the feed water
specification:
< 0.02 ppm and SiO2 < 0.5 ppm
CaCO
3
[DN] 15 25
[DN] 15 25
[DN] 15 15
0.5 1.0 1.5 1.0 1.0 1.5 1.5 1.5
[kW]
[l/h]
110 200 400 800 1200 1600 2200 3000
[l/h] 100 180 360 720 1100 1450 2000 2700
[l/h] 10 20 40 80 100 150 200 300
[l/h] 10 20 40 40 40 65 65 85
[bar] 2/5 3/7
bar OP] 5 7
[µS/cm] 40
[µS/cm]
< 0.2
60 - 80
90 - 99
90 - 93 90 - 95
18
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Loading...
+ 41 hidden pages