Grunbeck GENO-EDI-X Operation Manual

Page 1
Operation Manual
Electrodeionisation System GENO-EDI-X
with GENO-EDI-tronic
Version: December 2018 Order no. 024 770 901-inter
Page 2
GENO-EDI-X
Table of contents
AGENERAL INFORMATION .................................................................................................................................................................. 5
1 | P
REFACE
2 | H 3 | G
4 | S 5 | D
BBASIC INFORMATION ........................................................................................................................................................................ 9
1 | L 2 | W 3 | F
CPRODUCT DESCRIPTION (GENO-EDI-X) ........................................................................................................................................ 12
1 | T 2 | F 3 | B 4 | D 5 | T 6 | I
7 | A 8 | S
DINSTALLATION ................................................................................................................................................................................. 25
1 | G
2 | W 3 | H 4 | E
ECOMMISSIONING .............................................................................................................................................................................. 29
1 | G
2 | START EDI-X
FOPERATION ...................................................................................................................................................................................... 31
1 | I 2 | B
3 | S 4 | O 5 | O
GTROUBLESHOOTING ....................................................................................................................................................................... 56
1 | B 2| T
HMAINTENANCE ................................................................................................................................................................................. 5 8
1 | B 2 | I 3 | M
..................................................................................................................................................................................................... 5
OW TO USE THIS OPERATION MANUAL
ENERAL SAFETY INFORMATION
3.1
3.2
3.3
3.4
3.5
3.1 Functional principle of electrodeionisation ......................................................................................................................................... 10
3.2
NTENDED USE
6.1 | System shutdown ............................................................................................................................................................................ 19
8.1
8.2
8.3
1.1
1.1
NTRODUCTION
2.1
2.2
2.3
2.4
5.1
5.2
5.2.4System Configuration ............................................................................................................................................................ 37
5.2.5I/O Display ............................................................................................................................................................................... 38
5.2.6Error Memory .......................................................................................................................................................................... 38
5.2.7Basic Setting ........................................................................................................................................................................... 38
5.3
5.3.1Errors ...................................................................................................................................................................................... 3 9
5.3.2Warnings ................................................................................................................................................................................. 41
5.4
5.4.1User......................................................................................................................................................................................... 4 3
5.4.2Parameters .............................................................................................................................................................................. 43
5.4.3Times ...................................................................................................................................................................................... 46
5.4.4Errors ...................................................................................................................................................................................... 4 7
5.4.5Service Data ............................................................................................................................................................................ 50
5.4.6Reference Data ....................................................................................................................................................................... 51
5.4.7Basic Setting ........................................................................................................................................................................... 52
5.5
5.5.1User......................................................................................................................................................................................... 5 4
5.5.2Parameters .............................................................................................................................................................................. 54
5.5.3Errors ...................................................................................................................................................................................... 5 5
5.5.4Service Data ............................................................................................................................................................................ 55
5.5.5Basic Setting ........................................................................................................................................................................... 55
ROUBLESHOOTING
NSPECTION (FUNCTIONAL CHECK
3.1
Symbols and notes .................................................................................................................................................................... 6
Operating personnel .................................................................................................................................................................. 6
Designated application .............................................................................................................................................................. 6
Protection from water damage .................................................................................................................................................. 7
Description of specific dangers ................................................................................................................................................. 7
HIPPING AND STORAGE ISPOSAL
..................................................................................................................................................................................................... 8
AWS, REGULATIONS, STANDARDS
ATER
........................................................................................................................................................................................................ 9
UNCTIONAL PRINCIPLE OF ELECTRODEIONISATION
Components of the electrodeionisation module (EDI module) ................................................................................................. 11
YPE DESIGNATION PLATE LOW CHART DESIGN
ASIC FUNCTION OF THE ELECTRODEIONISATION SYSTEM ESCRIPTION OF THE COMPONENTS
ECHNICAL SPECIFICATIONS
PPLICATION LIMITS COPE OF SUPPLY
ENERAL INSTALLATION INFORMATION
ATER CONNECTION
OW TO CONNECT THE SYSTEM LECTRICAL WIRING
ENERAL INFORMATION
RIEF DESCRIPTION OF
WITCH CABINET
PERATING THE CONTROL UNIT PERATING THE CONTROL UNIT
ASIC INFORMATION
ASIC INFORMATION
AINTENANCE
............................................................................................................................................................................................ 1 9
  
   
 
...................................................................................................................................................................................... 21
Standard equipment ................................................................................................................................................................ 21
Optional features ..................................................................................................................................................................... 22
Wearing parts .......................................................................................................................................................................... 24
Preliminary work ...................................................................................................................................................................... 25
Preliminary work ...................................................................................................................................................................... 29
SYSTEM OPERATION
............................................................................................................................................................................................ 31
Field of application .................................................................................................................................................................. 31
Function .................................................................................................................................................................................. 31
Basic technical parameters – control panel ............................................................................................................................. 31
Basic technical parameters – MK200 basic module ................................................................................................................. 31
......................................................................................................................................................................................... 32
Basic information regarding the operation of the control unit ................................................................................................... 34
System menu .......................................................................................................................................................................... 34
Messages and signals ............................................................................................................................................................. 39
Electrodeionisation (GENO-EDI-X system) .............................................................................................................................. 4 2
Pressure booster (PB system) if activated in system menu ..................................................................................................... 53
............................................................................................................................................................................................ 5 9
Operation log ........................................................................................................................................................................... 59
............................................................................................................................................................ 5
..................................................................................................................................................................... 6
................................................................................................................................................................................ 7
.................................................................................................................................................................. 9
......................................................................................................................................... 10
............................................................................................................................................................................ 12
................................................................................................................................................................................... 12
.............................................................................................................................................................. 15
......................................................................................................................................................................... 18
.................................................................................................................................................................................... 20
.......................................................................................................................................................... 25
................................................................................................................................................................................... 26
.................................................................................................................................................................................... 28
.................................................................................................................................................................................... 56
..................................................................................................................................................................................... 57
.................................................................................................................................................................................... 58
.................................................................................................................................................................... 27
............................................................................................................................................................................... 29
.............................................................................................................................................................. 30
GENO-EDI-
TRONIC
.................................................................................................................................................. 31
.................................................................................................................................................................... 33
.................................................................................................................................................................... 34
) ................................................................................................................................................................ 58
GENO-EDI-X (
WITHOUT OPTIONS
) ............................................................................ 13
                                                                                
2
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 3
Publisher's information
All rights reserved.
Copyright by Grünbeck Wasseraufbereitung GmbH
Printed in Germany Effective with the date of edition indicated on the cover sheet.
-We reserve the right to modifications, especially with regard to technical progress-
Reprints, translations into foreign languages, electronic storage or digital copying of this operation manual – even in parts – may take place only with explicit written approval of Grünbeck Was­seraufbereitung GmbH.
Any type of duplication not authorised by Grünbeck Wasserauf­bereitung is a copyright violation and will be prosecuted.
Responsible for contents: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1 89420 Höchstädt/Do. Phone 09074 41-0  Fax 09074 41-100 www.gruenbeck.de service@gruenbeck.de
GENO-EDI-X
Printing: Grünbeck Wasseraufbereitung GmbH Josef-Grünbeck-Straße 1, 89420 Höchstädt/Do.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
3
Page 4
GENO-EDI-X
EC Declaration of Conformity
We hereby declare that the system designated below meets the safety and health requirements of the applicable European guidelines in terms of its design, construction and manufacture.
This certificate will become invalid if the system is modified in a way not approved by us.
Manufacturer: Grünbeck Wasseraufbereitung GmbH
Josef-Grünbeck-Str. 1 89420 Hoechstaedt/Germany
Responsible for documentation: Roland Rehberger
System designation:
System size: 100, 180, 360, 720, 1100, 1450, 2000, 2700
System number: Refer to type designation plate
Applicable directives: Machinery Directive (2006/42/EC)
Applied harmonised standards, in particular:
Applied national standards and technical specifications, in particular:
Place / Date / Manufacturer's signa­ture:
Function of signatory: Head of Technical Systems and Equipment
Electrodeionisation system GENO-EDI-X
EMC (2014/30/EU)
EN ISO 12100:2011-03, EN 61000-6-2:2006-03 EN 61000-6-3:2011-09
Höchstädt, 2018-10-11 p.p.a. P. Höß
4
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 5
A General information
GENO-EDI-X
1 | Preface
Thank you for opting for a Grünbeck product. Backed by
Advice and assistance
decades of experience in the area of water treatment, we provide solutions for all kind of processes.
All Grünbeck systems and devices are made of high-quality materials. This ensures trouble-free operation over many years, provided you treat your water treatment system with the required care. This operation manual assists you with important information. Therefore, please read the entire operation manual before installing, operating or maintaining the system.
Customer satisfaction is our prime objective and providing customers with qualified advice is crucial. If you have any questions concerning this device, possible extensions or general water and waste water treatment, our field service staff, as well as the experts at our headquarters in Hoechstaedt, are available to help you.
For advice and assistance please contact your local representative (refer to www.gruenbeck.de).
In case of emergency, please get in touch with our service hot­line at +49 9074 41-333. We can connect you with the appropri­ate expert more quickly if you provide the required system data.
To ensure that this information is to hand at all times, please keep the precise equipment data to hand (refer to the type plate in chapter C-1).
2 | How to use this operation manual
This operation manual is intended for the operators of our sys-
tems. It is divided into several chapters (a letter is assigned to each of them) which are listed in the table of contents on page 2 in alphabetical order. Check for the corresponding chapter on page 1 in order to find the specific information you need.
The headers and page numbers with chapter information make it easier to find your way around in the operation manual.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
5
Page 6
GENO-EDI-X
3 | General safety information
3.1 Symbols and notes
Important information in this operation manual is emphasised by symbols. Please pay particular attention to this information to ensure the hazard-free and safe handling of the system.
Danger! Failure to adhere to this information will cause serious or life-threatening injuries, extreme damage to property or inadmissible contamination of the drinking water.
Warning! Failure to adhere to this information may cause injuries, damage to property or contamination of the drinking water.
Caution! Failure to adhere to this information may result in damage to the system or other objects.
Note: This symbol emphasises information and tips that make your work easier.
Tasks with this symbol may only be performed by Grünbeck's technical service/authorised service company or by persons expressly authorised by Grünbeck.
Tasks with this symbol may only be performed by trained and quali­fied electrical experts according to the VDE guidelines or according to the guidelines of a similar local institution.
Tasks with this symbol may only be performed by water suppliers or approved installation companies. In Germany, the installation company must be registered in an installation directory of a water supplier as per §12(2) AVBWasserV (German Ordinance on General Conditions for the Supply of Water).
3.2 Operating personnel
3.3 Designated application
Only persons who have read and understood this operation manual are permitted to work with the system. Strictly observe the safety information.
The system may only be used for the purpose outlined in the product description (chapter C). The guidelines in this operation manual as well as the applicable local guidelines concerning drinking water protection, accident prevention and occupational safety must be observed.
In addition, intended use also implies that the system may only be operated when it is in proper working order. Any errors must be eliminated at once.
The GENO-EDI-X is exclusively designed for use in the indus­trial and commercial field.
6
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 7
3.4 Protection from water damage
3.5 Description of specific dangers
GENO-EDI-X
Warning! In order to properly protect the installation site against water damage:
A sufficiently dimensioned floor drain system must be
available or
a water stop device (refer to chapter C “Accessories”) must
be installed.
Warning! Floor drains that discharge to a lifting system will not work in case of a power failure.
Danger due to electrical energy! Do not touch electrical parts with wet hands! Disconnect the system from the mains before starting work on electrical system components. Have qualified experts replace damaged cables immediately.
Danger due to mechanical energy! System components may be subject to overpressure. Danger of injury and damage to property due to escaping water and unexpected movement of system components. Check pressure pipes regularly. Depressurise the system before starting repair or maintenance work on the system.
Hazardous to health due to contaminated drinking water! The system shall be installed only by a specialist company. Strictly observe the operation manual! Ensure that there is sufficient flow; the relevant guidelines must be followed for commissioning after extended periods of standstill. Inspections and maintenance must be performed at the intervals specified!
Note: By concluding a maintenance contract, you ensure that all
of the required tasks are performed on time. You may perform the interim inspections yourself.
4 | Shipping and storage
Caution! The system may be damaged by frost or high
temperatures. In order to avoid damage of this kind:
Protect from frost during transportation and storage! Do not install or store the system next to objects which radiate a lot of heat.
The system may only be transported and stored in its original
packing. Ensure that it is handled with care and placed the right side up (as indicated on the packaging).
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
7
Page 8
GENO-EDI-X
5 | Disposal
Comply with the applicable national regulations.
5.1 Packaging
5.2 Product
Dispose of the packaging in an environmentally friendly manner.
If this symbol (crossed out waste bin) is on the product, this product is subject to the European Directive 2012/19/EU. This means that this product or the electrical and electronic compo­nents must not be disposed with household waste.
Learn about the local regulations on the separate collection of electrical and electronic products.
For information on collection points for your product, contact your municipality, the public waste management authority, an authorised body for the disposal of electrical and electronic prod­ucts or your waste disposal service.
8
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 9
GENO-EDI-X
B Basic information
1 | Laws, regulations, standards
In the interest of good health, rules cannot be ignored when it
comes to the processing of drinking water. This operation manual takes into consideration the current guidelines and stipulates information that you will need for the safe operation of your water treatment system.
Among other things, the set of rules stipulate that
only approved specialist companies are permitted to make
major modifications to water supply systems
and that tests, inspections and maintenance on installed
devices are to be performed at regular intervals.
2 | Water
As a result of dynamic substance and water cycles, increasingly
polluting elements are being released into the natural environment. These are only partially and slowly broken down by natural effects. Consequently, these elements build up in the groundwater and surface water over the course of time. Removing them from natural water deposits again represents a particular challenge. Grünbeck faces this challenge with the aim of producing unpolluted drinking and industrial water.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
9
Page 10
GENO-EDI-X
3 | Functional principle of electrodeionisation
3.1 Functional principle of electrodeionisation
Function
The electrodeionisation represents a continuous, electrochemical membrane process that combines membrane technology and ion exchanger technology.
In this process, ion exchanger resin, ion-selective membranes and direct current are used to remove ions from the permeate of a reverse osmosis system.
The resulting diluate (ultra-pure water) has a residual conductivity of < 0.2 µS/cm. The residual conductivity depends on the quality of the feed water (permeate).
The advantage of this technology is the fact that the regeneration (by means of direct current) continuously takes place during operation and no chemicals (acids/bases) are required.
Contrary to common ion exchanger systems, the electrodeionisation system GENO-EDI-X considerably reduces the TOC values.
The core – the EDI module – consists of several chambers filled with layers of anion and cation exchanger resins. The chambers are separated from each other by anion and cation membranes.
The feed water (permeate) flows into the EDI module and is divided into a diluate, concentrate and electrolyte water flow. Due to the direct voltage applied, the ions move from the diluate chambers filled with ion exchanger resin to the concentrate chambers that are also filled with ion exchanger resin. While the water is in the diluate chambers is being fully demineralised, the direct current splits the water into hydrogen ions (H+) and hydroxide ions (OH exchanger resins are regenerated again.
A part (10 %) of the feed water volume (permeate) rinses the concentrate and the electrode chambers. The volume designated as concentrate (unpressurised) is then either directed to the drain or returned to the inlet of the reverse osmosis system to be fed again.
The electrodeionisation system GENO-EDI-X has a recovery of 90 - 95 %.
-
) by which in turn the ion
10
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 11
3.2 Components of the electrodeionisation module (EDI module)
GENO-EDI-X
Permeate inlet Diluate outlet
1 2
Concentrate outlet
3 4
Cathode (-)
5 6
Diluate chamber with ion exchanger resin
7
Cation membrane (C)
9
Anode (+)
Concentrate chamber with ion exchanger resin
Anion membrane (A)
8
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
11
Page 12
GENO-EDI-X
C Product description (GENO-EDI-X)
1 | Type designation
plate
Please specify the data shown on the type designation plate of your GENO-EDI-X electrodeionisation system in order to speed up the processing of enquiries or orders. Please add the necessary information to the overview below to have it readily available whenever necessary.
Electrodeionisation system GENO-EDI-X:
Serial number:
Order number:
     
     
    
2 | Flow chart design
Fig. C-1: Type designation plate of the electrodeionisation system GENO-EDI-X
Fig. C-2: Flow chart of GENO-EDI-X
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
12
Page 13
GENO-EDI-X
3 | Basic function of the electrodeionisation system GENO-EDI-X
(without options)
If the system is in standby mode and ready for operation, the inlet rejection valve and the inlet valve are closed. There is no voltage present at the EDI module. If available, the outlet rejection valve is open and the outlet valve closed. The electrodeionisation system receives its start signal from the level control system of the diluate tank. Then, the EDI controller transmits the start signal to the RO controller. The RO system starts operation and produces permeate. By means of the inlet rejection valve, the time-controlled discharge of the permeate to the drain takes place. In case the conductivity measuring cell for permeate is installed, the rejection can be terminated prema­turely if the max. permeate conductivity set is undershot.
Upon termination of the inlet rejection, the inlet valve opens and the inlet rejection valve closes. When the inlet valve opens, the EDI cell is supplied with voltage. From the moment the inlet valve opens, the flows diluate and concentrate, the diluate conductivity, the pressure of permeate, diluate and concentrate as well as the temperature and the diluate are monitored and trigger a time-delayed (adjustable) warning or an alarm. The diluate is rejected via time by means of the outlet rejection - if available (option) -, with premature termination in case the max. diluate conductivity set is undershot. Following the opening of the outlet valve, the outlet rejection valve is closed. The diluate produced is now directed to the diluate tank.
As soon as the tank is full, a stop signal is transmitted to the EDI controller. Within the electrodeionisation system, the voltage supplied to the EDI cell is interrupted and the monitoring function of the EDI system is deactivated. After a set rinsing sequence, the RO system receives its stop signal and the valves move to the following positions: Inlet rejection valve and inlet valve close and – if available – the outlet rejection valve is open and the out­let vale is closed. Now, the electrodeionisation system remains in standby mode until the next demand is made.
If the system is in standby mode, the inlet rejection valve Y8 and the inlet valve Y7 are closed. There is no voltage present at the EDI module.
The GENO-EDI-X system receives a start signal from the level control system of the diluate tank. Then, the EDI controller trans­mits the start signal to the RO controller.
The RO system starts operation and produces permeate. By means of the inlet rejection valve Y8, the discharge of the per­meate to the drain takes place over a pre-set time period. Upon termination of the inlet rejection, the inlet valve Y7 opens and the inlet rejection valve Y8 closes.
When the inlet valve Y7 opens, the EDI module is supplied with the divided partial permeate flows of diluate and concentrate. In addition, the voltage and current are switched to the EDI mod­ule.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
13
Page 14
GENO-EDI-X
From the moment the inlet valve Y7 opens, the diluate F7 and concentrate F8 flows, the diluate conductivity Q5, the pressure of permeate P4, diluate P5 and concentrate P6, as well as the temperature of the diluate T2 are monitored and trigger a time­delayed (adjustable) warning and/or an error.
The diluate produced is now directed to the diluate tank. As soon as the tank is full, a stop signal is transmitted to the EDI con­troler. Within the GENO-EDI-X electrodeionisation system, the voltage supplied to the EDI cell is interrupted and the monitoring function of the GENO-EDI-X system is deactivated.
After a set rinsing sequence, the RO system receives its stop signal and the valves move to the following positions: inlet rejec­tion valve Y8 and inlet valve Y7 closed.
Now, the GENO-EDI-X system remains in standby mode until the next request is made.
*Diluate = deionate, ultra-pure water
14
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 15
4 | Description of the components
GENO-EDI-X
Adjusting valve Operating
V4
1
2
3
4
5
6
7
pressure
(OPTION)
Adjusting valve
V5
Concentrate volume
Adjusting valve
V6
Diluate pressure
Adjusting valve
V7
Concentrate pressure
Permeate
V8
overflow valve (OPTION)
Sample valve of
Pr-P
feed water (Permeate)
Sample valve of
Pr-D
diluate
To throttle the permeate supply flow in case of excess capacity from on-site feed pumps.
Not required for agreed-upon RO/EDI system combinations.
For the adjustment of the concentrate volume conducted to the drain. This value corresponds with 10% of the permeate feed value.
For the adjustment of the diluate counter-pressure.
For the adjustment of the concentrate pressure to the diluate pressure.
Conducts the permeate from upstream RO systems to the drain; these systems work in forced operation mode. Protects the permeate side of the RO system in case the solenoid valves of the GENO-EDI-X system do not open. Adjustment: OPEN at 4 bar (g).
Possibilities of manual quality determination via sample valve.
Possibilities of manual quality determination via sample valve.
10
11
Registers the permeate quantity and sends pulses to the control electronics.
8
9
diluate
Flow sensor
F8
Concentrate
Permeate
P4
pressure sensor
Pressure sensor
P5
Diluate
Flow sensor of
F7
Visual indication of the diluate quantity in the control electronics. If the minimum flow of the diluate is undershot, an error is emit­ted. GENO-EDI-X system STOP
Registers the concentrate volume and sends pulses to the control electronics. Visual indication of the concentrate volume in the control electronics. If the minimum flow of the concentrate is undershot, an error is emitted. GENO-EDI-X system STOP
The maximum limit value is 4 bar(g) When the set maximum permeate pressure value is exceeded, the GENO-EDI-X system STOP takes place with a time delay. Visual indication in the control electronics.
Indicates the diluate pressure value in the control electronics. P5 must be at least 0.2 bar higher than P6! The alarm signal takes place with a time delay when the concentrate pressure value P6 is higher than/equal to the diluate pressure value P5. GENO-EDI-X system STOP
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
15
Page 16
GENO-EDI-X
Indicates the concentrate pressure in the control electronics. P5 must be at least 0.2 bar higher than P6! The alarm signal takes place with a time delay when the concentrate pressure value P6 is higher than/equal to the diluate pressure value P5. GENO-EDI-X system STOP
Always open during diluate production. Opens after a settable time interval (permeate rejection). Opens after inlet rejection at conductivity < 20 µS/cm measured via Q4 (option). Locked in case of errors in the GENO-EDI-X system. Visual indication in the control electronics.
Opens for an adjustable time after EDI start. Opens after start of EDI until a conductivity of 20 µS/cm meas­ured via Q4 is undershot (option). Closes after inlet rejection. Visual indication in the control electronics.
12
13
14
Concentrate
P6
pressure sensor
Inlet solenoid
Y7
valve of permeate
Permeate inlet re-
Y8
jection valve
15
16
17
18
Outlet solenoid valve of diluate
Y9
(OPTION)
Outlet rejection valve of diluate
Y10
(OPTION)
Conductivity measuring cell of
Q4
permeate
(OPTION)
Conductivity
Q5
measuring cell of diluate
Opens after diluate rejection from Y10 if the conductivity limit value for diluate is undershot. Closes after GENO-EDI-X system STOP, locked in case of errors in the GENO-EDI-X system. Visual indication in the control electronics.
Opens after GENO-EDI-X system START and completed inlet rejection, closes when the conductivity limit value for diluate is undershot. Visual indication in control electronics.
Indicates the quality of the permeate in the control electronics. Enables quality-controlled permeate rejection. Y8 CLOSED and Y7 OPEN if the set conductivity limit value is undershot. Visual alarm signal in the control electronics when the set con­ductivity limit value is exceeded. GENO-EDI-X system STOP.
Indicates the quality of the diluate in the control electronics. Enables quality-controlled diluate rejection. Y10 CLOSED and Y9 OPEN if the set conductivity limit value is undershot. Visual alarm signal in the control electronics when the set con­ductivity limit value is exceeded. GENO-EDI-X system STOP.
19
20
16
Conductivity measuring cell
Q6
Concentrate (OPTION)
Permeate temper­ature sensor
T1
(OPTION)
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Indicates the quality of the concentrate in the control electronics.
Indicates the temperature of the permeate in the control elec­tronics.
Y8 CLOSED and Y7 OPEN if the set temperature value is ex­ceeded. Visual alarm signal in the control electronics when the set limit value is exceeded. GENO-EDI-X system STOP.
Page 17
GENO-EDI-X
Indicates the temperature of the diluate in the control electronics.
21
22
23
Diluate temperature
T2
sensor
(OPTION)
Permeate feed
M8/
pump
P8/
Frequency­controlled
P9
(OPTION)
Level control
L4
system of diluate tank
Y9 CLOSED and Y10 OPEN if the set temperature value is exceeded.
Visual alarm signal in the control electronics when the set limit value is exceeded. GENO-EDI-X system STOP.
Increases the permeate feed pressure. Permeate pump M8 START through min. pressure contact P8. Permeate pump M8 STOP through max. pressure contact P8.
Alternatively, M8 is operated using pressure sensor P8 in a frequency-controlled manner.
M8 release always provided in case of inlet valve Y7 OPEN. M8 is locked in case of min. pressure switch P9 (min. pressure).
Visual alarm signal on the frequency converter and in the control electronics. GENO-EDI-X system STOP.
Visual indication in the control electronics. L4a+ full signal, GENO-EDI-X system STOP L4b- request, GENO-EDI-X system START L4c- additional and emergency feed (option) L4d+ empty signal, dry-run protection for PBS pump M6/M7, time-delayed release for PBS pump M6/M7 in case level is exceeded
Visual indication in the control electronics. Actuated by the pre-selector (H-O-A) in the control electronics.
Pressure booster
M6/
system
M7/
Diluate pressure switch
P7
(OPTION)
Pressure switch with min. and max. pressure contact. In case of automatic operation:
- M6/M7 ON via min. pressure contact of P7
- M6/M7 OFF via max. pressure contact of P7
- Time-controlled changeover operation of pumps M6/M7. M6/M7 re locked in case of dry-run protection L4d.
Visual alarm signal in control electronics.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
17
Page 18
GENO-EDI-X
5 | Technical specifications
Table C-1: Technical
Electrodeionisation system GENO-EDI-X
specifications
100 180 360 720 1100 1450 2000 2700
Connection data
Nominal connection diameter of permeate feed line (screw connection)
Nominal connection diameter of diluate outlet line (screw connection)
Nominal connection diameter of concentrate outlet line (screw connection)
Min. drain connection required [DN] 50
Connected load, approx.
Power supply [V/Hz] 1x 230 / 50
Protection type IP 54
Performance data
Feed water volume flow (nominal)
Diluate capacity at a feed water temperature 15°C and a recovery of approx. 90 % (nominal)
Concentrate volume flow at a recovery of approx. 90% (nominal)
Diluate capacity max.**** [l/h] 150 300 600 1000 1350 2100 2600 3750
Min. diluate flow*** required [l/h] 62,5 125 250 550 550 1100 1100 1400
Min. required flow of concentrate***
Operating voltage [V-DC] < 106 < 213 < 426 < 130 < 130 < 240 < 240 < 300
Operating current [A] < 2.5 < 2.5 < 2.5 < 5 < 5 < 5 < 5 < 5
Inlet flow pressure of permeate, min./max.
Outlet pressure of diluate, approx. [bar] 0.5/1.5
Max. operating pressure
Feed conductivity equivalent (FCE)**, max.
Diluate conductivity*
TOC reduction
SiO2 reduction
Recovery***
Dimensions and weights
Dimensions (w x h x d) [mm] 900 x 1700 x 675
Min. room/installation height required [mm] 2000
Operating weight, approx. [kg] 95 105 115 170 170 190 190 215
Ambient data
Temperature of feed water, min./max. [°C] 10/25
Ambient temperature, min./max. [°C] 5/35
Order no. 770 300 770 310 770 320 770 330 770 340 770 350 770 360 770 370
*
Subject to the feed water quality ** For calculation, refer to the formula under “Application limits” *** These volume flows must be considered as the absolute minimum for the flow rates of the EDI module! **** In case of maximum recoveries of 93 and/or 95 %, the following shall further apply with regard to the feed water
specification:
< 0.02 ppm and SiO2 < 0.5 ppm
CaCO
3
[DN] 15 25
[DN] 15 25
[DN] 15 15
0.5 1.0 1.5 1.0 1.0 1.5 1.5 1.5
[kW]
[l/h]
110 200 400 800 1200 1600 2200 3000
[l/h] 100 180 360 720 1100 1450 2000 2700
[l/h] 10 20 40 80 100 150 200 300
[l/h] 10 20 40 40 40 65 65 85
[bar] 2/5 3/7
bar OP] 5 7
[µS/cm] 40
[µS/cm]
< 0.2
60 - 80
90 - 99
90 - 93 90 - 95
18
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 19
GENO-EDI-X
6 | Intended use
The electrodeionisation system GENO-EDI-X is designed for the
further quality enhancement of permeate generated by a reverse osmosis system.
The most common areas of application for the diluate produced (ultra-pure water) are:
- Steam sterilisation
- Semi-conductor industry
- Generation of pure steam
- Laboratories
The system can be used only after a prior water analysis and corresponding pretreatment.
The continuous diluate output of the system is subject to the temperature and is defined at 15°C. The diluate outputs can fall (falling temperature) or rise (rising temperature) by up to 3 % for each °C the raw water temperature increases or decreases.
Only operate the system if all components are properly installed. Safety devices must NEVER be removed, bridged or otherwise tampered with.
Appropriate application of the device also implies that the information contained in this operation manual and all safety regulations applying at the installation site be observed. Furthermore, the maintenance and inspection intervals have to be observed.
6.1 | System shutdown
During decommissioning of the GENO-EDI-X system, the
necessary measures must be decided upon together with Grünbeck’s technical service.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
19
Page 20
GENO-EDI-X
7 | Application limits
Conductivity equivalent
FCE*: < 40 µS/cm (CO
included)
2
Range of pH value: 4 – 11
Cl
concentration: < 0.02 ppm
2
Fe concentration: < 0.01 ppm
Mn concentration: < 0.01 ppm
Sulphide concentration: < 0.01 ppm
Concentration of residual hardness (CaCO (^ 0.056 °dH)
TOC concentration < 0.5 ppm
Silicate concentration (SiO
Water temperature: 10 – 25°C
*FCE = permeate conductivity + (ppm CO + (ppm SiO
): < 1.0 ppm
3
x 1.94)
2
): < 1.0 ppm
2
x 2.79)
2
Note: The diluate from GENO-EDI-X system is not drinking
water!
*
For the determination of this value, the formulae in section E,
chapter 1 must be used!
20
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 21
8 | Scope of supply
GENO-EDI-X
8.1 Standard equipment
Device that is ready for connection for the continuous, electrochemical, residual demineralisation of permeate originating from a reverse osmosis system, completely pre-assembled to an anodised aluminium system rack.
Microprocessor controller with LCD graphic display
(70 x 38 mm backlit) Flow chart of the electrodeionisation system with collection tank including level control, pressure booster system for diluate as well as indication of the flow, pressure and conductivity values of the electrodeionisation system.
Version: Membrane keyboard with 12 buttons and serial interface RS 232, system piping within the electrodeionisation system equipped with pressure sensors, adjusting and/or solenoid valves, as well as sampling fittings. Integrated flow sensors to monitor the volume flows diluate and concentrate. The switch cabinet features all power units as well as the control electronics. Quality assurance of diluate by means of temperature-compensated conductivity measurement with digital indication at the display of the control electronics Piping within the system completely made of high-pressure resistant PE plastic pipes.
EDI module as the main core of process engineering.
Installation and operation manual.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
21
Page 22
GENO-EDI-X
8.2 Optional features
Note: It is possible to retrofit existing systems with optional
components. Please contact your local Grünbeck field service staff or Grünbeck’s headquarters in Hoechstaedt for more information.
GENO-EDI-Profibus DP
Module to provide system data
770 860
For GENO-EDI-X 100 through 360 770 815
For GENO-EDI-X 720 through 2700 770 875
For GENO-EDI-X 720 through 2700
GENO-EDI voltage-free single fault signals for DDC/central building and control system
Module for single fault signals (voltage-free) to control centre
Quality-controlled permeate rejection
Rejection of feed permeate in the inlet to the electrodeionisation system (conductivity-controlled)
Analogue outputs (4-20 mA) for conductivity and diluate temperature
Module for outputting measuring values to control centre
Quality-controlled diluate rejection Rejection of diluate prior to filling the pure water tank (conductivity-controlled)
Measuring of conductivity and temperature of EDI concentrate
Module to measure the conductivity / temperature in the EDI concentrate (waste water) in the feed water For GENO-EDI-X 100 through 360
GENO membrane degassing system MEC 500-1 (single-stage)
For removing CO of the electrodeionisation system Flow volume of feed water:
0.1 – 0.7 m³/h Amount of stripping gas* required:
0.2 – 1.8 Nm³/h
GENO membrane degassing system MEC 500-2 (2-stage)
For removing CO of the electrodeionisation system Flow volume of feed water:
0.1 – 0.7 m³/h Amount of stripping gas* required:
0.4 – 3.6 Nm³/h
from the feed water (permeate)
2
from the feed water (permeate)
2
770 855
770 800
770 810
770 805
770 870
770 200
770 205
22
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 23
GENO-EDI-X
GENO membrane degassing system MEC 2200-1 (single-stage)
For removing CO
from the feed water (permeate)
2
of the electrodeionisation system Flow volume of feed water:
0.5 – 3.41 m³/h Amount of stripping gas* required:
0.8 – 5.1 Nm³/h
GENO membrane degassing system MEC 2200-2 (two-stage)
For removing CO
from the feed water (permeate)
2
of the electrodeionisation system Flow volume of feed water:
0.5 – 3.41 m³/h Amount of stripping gas* required:
1.6 – 10.2 Nm³/h
*Stripping gas = oil-free, compressed air
Pure water tank for intermediate storage of the diluate flowing unpressurised from the GENO-EDI-X electrodeionisation systems
Tank version:
All tanks are pre-assembled, with PVC overflow pipe as well as connections for the inlet, diluate and the suction line of the pressure booster system. Grey PE. Hand-hole with removable screw cap. Level probe for installation into the tank, electrically connected to GENO-EDI-tronic controller.
Basic clean water tank X RT 1000 with sterile filter and level measuring probe
Net volume approx. 850 litres L 780 / W 990 / total H 2000 mm
1)
.
770 210
770 215
712 480
Additional tank RT for basic pure water tank
Net volume approx. 850 litres L 780 / W 780 / total H 2100 mm
1)
Tank height including connecting pieces.
1)
.
For larger tanks, please inquire
Additional tank without level control and overflow loop,
including 2 connecting lines, id=36 mm.
Note: A maximum of four supply tanks can be combined.
For larger CO
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
trap for pure water tank
CO
2
For the removal of free carbon dioxide from the tank's ventilating air.
traps, please inquire
2
712 405
712 800
23
Page 24
GENO-EDI-X
Pressure booster system GENO-FU-X 2/40-1 NE
Compact, pressure-controlled pump aggregate consisting of a centrifugal pump completely made of stainless steel as well as an integrated pressure and flow meter for pump control and dry-run protection. Special version for the delivery of diluate.
Delivery rate: Max. 1.2 - 4.4 m³/h Delivery head: max. 26.7 - 59.4 m
730 790
Power supply: 230 V / 50 Hz
Power consumption: 1.07 kW Connections: DN 25 / 1” Protection type: IP 55
For larger systems, please inquire
8.3 Wearing parts
Seals and valves are subject to a certain wear and tear. Wearing
Pressure booster system GENO-FU-X 2/40-2 NE
Description as for single pressure booster system, however, with the possibility for time-load switch-over.
parts are listed below.
Note: Although these parts are wearing parts, we grant a limited warranty period of 6 months. The same applies to electrical com­ponents.
Solenoid valves, adjusting valves (operating pressure, concen­trate volume, concentrate pressure, diluate pressure), sample valves and water meters
730 791
24
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 25
GENO-EDI-X
D Installation
1 | General installation information
The installation site must offer adequate space. For installation
and service work, sufficient clearance (> 50 cm, > 20 cm from the wall) must be provided around the system. A foundation of a sufficient size and adequate load carrying capacity must be pro­vided. The required connections must be provided prior to the installa­tion of the system. For dimensions and connection data, please refer to the table "Technical specifications".
The installation of an electrodeionisation system represents a major interference with the drinking water system. Therefore, only approved installation companies may install such systems.
Observe local installation guidelines and general regulations.
Install a drinking water filter upstream (e.g., pureliQ).
Install a system separator upstream.
Install a water softener upstream.
1.1 Preliminary work
Install an activated carbon filter upstream.
Install a reverse osmosis system upstream If the CO tion is too high, a membrane degassing system must be pro­vided in addition.
Provide a drain connection (at least DN 50) to discharge the concentrate.
For the electrical connection, a feed line to the system must be provided on site according to the electric circuit diagram. This line must be dimensioned according to the system type.
The installation site must have a floor drain. If no floor drain is available, an adequate safety device needs to be installed. Floor drains that discharge to a lifting system will not work in case of a power failure.
Safe unloading/placing of the system.
Unpacking of the system/system components.
Check of the system for any damage.
Erection of the electrodeionisation system.
Check of the mechanical and electrical connections; these
connections might have to be retightened after transport.
concentra-
2
Note: When installing systems with optional features, also
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
observe any additional operation manuals.
25
Page 26
GENO-EDI-X
2 | Water connection
Certain binding rules must always be observed when installing the electrodeionisation system. Additional recommendations are given in order to facilitate the handling of the system.
Mandatory regulations
The installation of the electrodeionisation system may be performed by an approved installation company only.
Observe local installation guidelines and general
regulations.
Establish the feed water connection (permeate).
Establish the concentrate connection.
Guarantee free access to the drain!
Establish the diluate connection.
Testing of the tightening torques on the bolts of the
EDI module Tighten any bolts according to specification. Applies to: GENO-EDI-X 720 / 1100 / 1450 / 2000 / 2700.
Provide a drain connection (minimum DN 50) to
discharge the concentrate.
Note: If the concentrate is directed to a lifting system, the
delivery rate of the lifting system must be > 500 l/h.
Warning! At the installation site, you must ensure that the depressurised waste water can flow off to the drain without obstruction.
Warning! The installation site must have an adequate exchange of air!
26
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 27
3 | How to connect the system
Remove the protective caps from system’s feed water (= per-
meate), diluate and concentrate-to-drain connections
Connect the feed water (= permeate).
Connect the concentrate to drain according to DIN 1988.
Establish the connection between diluate outlet and diluate
tank.
GENO-EDI-X
Mount CO
Limit of supply
Grünbeck
by others
Raw water
Diluate
Concentrate
Fig. D-1: Installation drawing
1
Drinking water filter BOXER K 1"
System separator DK 2
2
Delta-p water softener
3
4
GENO-softwatch Komfort
Activated carbon filter AKF
5
trap to vent the diluate tank
2
Reverse osmosis system GENO-OSMO-X
6
Electrodeionisation system GENO-EDI-X
7
(Optionally with integrated GENO membrane degassing system MEC)
8
Diluate tank with CO2 trap
9
Pressure booster system GENO-FU-X
Note: In the feed water (= permeate), concentrate and diluate
pipes provided by others on site, separable connections must be present (e.g. screw connections) to be able to separate the pipes.
Note: The feed water (= permeate), diluate and concentrate
pipes have to be made of corrosion-proof material.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
27
Page 28
GENO-EDI-X
4 | Electrical wiring
Note: The pertinent electric circuit diagrams are located
separately in the switch cabinet of the GENO-EDI-X system. The power feed line dimensions can be found there.
1. For the electrical connection, a supply line to the system must be provided on site according to the electric circuit diagram. This line must be dimensioned according to the system type.
2. Wire the level control of the collection tank according to the electric circuit diagram.
3. Testing of the earth connections of the EDI module
Each of the 4 connection pieces on the EDI module must
4. Any connection of a collective fault signal must take place on site.
be earthed!
28
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 29
K
GENO-EDI-X
E Commissioning
The work described below may only be performed by trained experts. For safety reasons, the commissioning must be performed by Grünbeck's trained and authorised technical customer service/authorised service company.
1 | General information
The GENO-EDI-X systems are factory-tested and pre-adjusted and
have undergone a test run.
1.1 Preliminary work
Commission the upstream RO system, guarantee the permeate inlet to the GENO-EDI-X system and disconnect the connection to the diluate tank.
Ensure the electrical power supply and activate the ON mains switch.
Determining the required current value for the regeneration of the GENO-EDI-X system.
For this purpose, the following is required:
a) CO
b) SiO
content in permeate
2
content in permeate
2
c) Total conductivity (conductivity of permeate)
d) Feed conductivity equivalent (FCE)
Calculation according to the following formula:
FCE = conductivity + (ppm CO
x 2.79) + (ppm SiO2 x 1.94)
2
e) The required current value for GENO-EDI-X 100 / 180 / 360
is then calculated as follows:
Q
xFCE
I
Diluate flow Q
in l/h
h
Feed Conductivity Equivalent FCE in µS/cm
EDI module index K = 3660 for EDI-X 100
EDI module index K = 7320 for EDI-X 180
EDI module index K = 14640 for EDI-X 360
The required current value for GENO-EDI-X 720 / 1100 / 1450 / 2000 / 2700 is then calculated as follows:
,
I

Diluate flow Q
in l/min
h
Feed Conductivity Equivalent FCE in µS/cm
EDI module index N = 10 for EDI-X 720 / 1100
EDI module index N = 18 for EDI-X 1450 / 2000
EDI module index N = 24 for EDI-X 2700
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
29
Page 30
GENO-EDI-X
2 | START EDI-X system operation
Switch on the GENO-EDI-X system on the control
electronics using the “ON” button.
Calibration of the flow sensors F7/F8 (gauging during
production).
Check of the flow values for diluate and concentrate.
Readjustment on the adjusting valves V5, V6, V7.
Check of the differential pressure between the diluate and
concentrate (set point dp > 0.2 bar and < 0.5 bar); reregulation at V6 and V7 as required.
Setting of the determined current value in the control
electronics (refer to section “F” in chapter 4.4.2 “Main menu/parameters”).
During the stable operation of the GENO-EDI-X system at
constant values, the parameters must be entered in the log sheet. This should stop after about 2 operating hours.
A stable operation for at least 12 h for the initial start-up
must be targeted to run in the EDI module.
Note:
The GENO-EDI-X system is switched off in the control
The most important parameters for EDI adjustment are as follows:
1. Inlet pressure
2. Differential pressure of diluate/concentrate
3. Operating current/voltage
Switching off the GENO-EDI-X system
electronics using the “0-ON” button.
After a brief run-down time, the GENO-EDI-X comes to a stop.
30
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 31
F Operation
1 | Introduction
Note: Instructions in bold are absolutely essential to ensure that
2 | Brief description of GENO-EDI-tronic
work can continue. All other instructions can be ignored if the value shown on the display remains unchanged.
Settings in the technical service programming level may only be performed by Grünbeck's technical customer service/authorised service company or by persons expressly authorised by Grünbeck.
Warning! Incorrect settings may lead to hazardous operating conditions which cause injury, illness or damage to property.
The operation manual must be strictly adhered to! Only make the settings described there!
GENO-EDI-X
2.1 Field of application
GENO-EDI-tronic constitutes the control electronics for all Grünbeck electrodeionisation systems GENO-EDI-X.
2.2 Function
GENO-EDI-tronic controls the operation of the electrodeionisation system in connection with optional pressure booster systems. In the system menu, the individual components can be activated and are available as a flow chart on the display ( visualisation system).
2.3 Basic technical parameters – control panel
Table F-1: Basic technical parameters
Membrane keyboard with 12 buttons
Graphic display with 128 x 64 pixels
Dimensions: approx. 70 x 35 mm and backlight
Serial interface RS-232
Used for the connection of a PC (software update)
and actuation of the EDI power supply unit
Interface For the MK200 system bus for the actuation of the
MK200 / MSR module and extensions
Supply voltage 10 VAC and 18 VAC, galvanically isolated
Control panel
2.4 Basic technical parameters – MK200 basic module
Table F-2: Basic technical parameters
Dimensions (w x h x d) 130 x 108 x 75 mm
Ambient conditions Working temperature 0...50°C
Storage temperature –20...85°C
Relative humidity: maximum 95%
10 VAC and 18 VAC, galvanically isolated
Noise immunity according to EN 50082-2
Emissions according to EN 50081-1
MK200 basic module
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
31
Page 32
GENO-EDI-X
3 | Switch cabinet
The switch cabinet contains the terminals for all connecting line, the power supply unit for the EDI module, the control transformers for the voltage supply, the fuses and the protective motor switch and the MK200 module, which controls the system in conjunction with the control panel.
Note: The electric circuit diagram of the system can be found here.
Fig. F-1 Switch cabinet
32
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 33
4 | Operating the control unit
GENO-EDI-X
Fig. F-2: Control panel
“Display” function in the respective menu
“Entry” function in the respective menu
Access to the “EDI System” menu
Access to the “PB System” menu or Exit
Access to the system menu
Switch the EDI system on/off (green pilot LED lights up when ON)
Acknowledge the malfunction/leave an open entry field without saving
Enter
Move the cursor to the left / right
Edit the values entered or move the cursor up and down
The red pilot LED lights up when the control unit detects an error.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
33
Page 34
GENO-EDI-X
5 | Operating the control unit
5.1 Basic information regarding the operation of the control unit
Fig. F-3: Menu access
Fig. F-3a EDI code entry
5.2 System menu
F1
The menu contains a few items that are not explained here. These include adjusting values for expansion modules. The documentation of these points is provided only together with these modules. In the basic version, the items have no function.
Two screens are available in the system menu and in the submenus of the respective system components.
On the "Display" screen, the parameters can be viewed,
but not changed.
In the "Entry" screen, all the parameters of the respective
menu level can be edited if the relevant code is entered.
Enter code: Move the cursor to the de sired point using the buttons ◄ and ► and set the desired value using the buttons ▲ and ▼. Confirm the entry with the button.
This menu includes the adjusting value related to the entire sys­tem. The system menu is called by pressing the button on any system display screen. On the next screen, the only choices still available are the display function (F1 button) and the entry function (F2 button). The F4 button takes you back to the previ­ous display screen. If the entry mode was selected with the F2 button, the code for the desired level must be entered and this entry must be confirmed by pressing the button.
The system menu is structured as below:
System menu > Input Logic
Output Logic I/O Configuration System Config. I/O Display Error Memory Basic Setting
The selection is made using the arrow buttons ▲ and ▼. The button takes you to the selected submenu. The F4 button (Exit) takes you to the previous screen.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
34
Page 35
5.2.1 Overview of the inputs and outputs
Input Function Output Function
1 P9 Low pressure switch for
pre-feed pump
2 L4a switch-off level
GENO-EDI-X
3 L4b switch-on level
GENO-EDI-X
4 L4c emergency and
additional feed
5 L4d dry-run protection
PB pump (diluate)
6 P8 pressure switch for
permeate pump M8
7 Error in permeate
pre-feed pump M8
8 “Standby” signal of RO
system (option)
9 P7 pressure switch of PB
pump (diluate) for rotary current of PB pumps
10 Error in PB pump M6
P7 pressure switch for alternating current of PB pumps
11 Error in PB pump M7
GENO-EDI-X
1
RO system release (option)
system
system
2
Supply of power supply unit
3
Solenoid valve Y11 Emergency feed
4
Collective fault
5
PB pump M6 (diluate)
6
PB pump M7 (diluate)
7
Solenoid valve Y7, inlet permeate
8
Solenoid valve Y8, rejection permeate
9
Solenoid valve Y10, rejection diluate
10
Permeate pre-feed pump M8
11
Solenoid valve Y9, discharge diluate
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
35
Page 36
GENO-EDI-X
Continuation Overview of inputs and outputs
Table F-4: Overview of inputs and outputs
5.2.2 Input Logic
Input Function Output Function
12 Error in power supply unit 1
(option)
13 Error in power supply unit 2
(option)
14 Error in power supply unit 3
(option)
15 Reserve
16 Programmable input
In this submenu, the logic of the digital inputs of the basic module can be inverted. This submenu has the following parameters:
Menu
Input Logic
Input XX: (XX = 1...16)
Setting range
Logic setting for digital inputs
1...16
Basic setting Level
0
0: Input is an NO contact
1: Input is an NC contact
Table F-5: Input Logic
5.2.3 I/O Configuration
In this submenu, the universal inputs/outputs can be configured.
This submenu has the following parameters:
Menu
I/O Config.
E04: Level L4c present
E16: Message text for input 16
E16 function: Function of input 16
E16 delay: Delay time for input 16
Table F-6: Configuration
Setting range
NO: No function
YES: Input for level switch L4c
Entry of up to 16 characters
FREE: No function
WARNING: Input leads to a warning
ERROR: Input leads to shut-down
Setting range: 0...999 seconds
Basic setting Level
NO
FREE
0 sec.
36
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 37
5.2.4 System Configuration
GENO-EDI-X
In this submenu, the existing system components can be defined. This submenu has the following parameters:
Menu
System Config.
Language: GERMAN
PB system
present
Signals
module
Profibus module Definition of the Profibus
Setting range
ENGLISH
Definition of pressure booster function
NO: No pressure booster present
YES: Pressure booster present
Definition of the Signals module.
NO: No Signals module present
YES: Signals module present
module
Basic setting Level
GERMAN Code
NO
NO
NO
0095
NO: No Profibus module present
YES: Profibus module
Flow
module
System data
printout
Table F-7: System Configuration
present
Definition of the Flow module
NO: No Flow module present
YES: Flow module present
Start of the system data printout through the serial interface by entering “1”. After the start, the value is automatically reset to “0”.
NO
0
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
37
Page 38
GENO-EDI-X
5.2.5 I/O Display
In this submenu, the current states of the inputs/outputs are displayed. This submenu has the following parameters:
Menu
I/O Display
Inputs
E16 – E01:
Outputs
A11 – A01:
Table F-8: I/O Display
Setting range
Input states of the individual inputs Input 16 left / Input 1 right 0: Input open 1: Input closed
Output states of the indivi­dual inputs Output 11 left / Output 1 right 0: Output not active 1: Output active
Basic setting Level
------ Code 0095
------ Code 0095
5.2.6 Error Memory
The error memory stores the last 16 messages whereby the last message always appears at the top (position 01). In addition to the position number and the message text, each line also in­cludes the value of the operating hour meter at the point in time at which the message was created. In the top line next to the menu header, the current value of the operating hour meter can be read. The contents of the error memory can be deleted by pressing the F1 button when the service password is entered.
5.2.7 Basic Setting
Basic settings can be made in this submenu. This submenu has the following parameters:
Menu
System Config.
Default values: When “1” is entered, the
Operating
hours
Table F-9: Basic setting
Setting range
system parameters and system-specific parameters are set to the basic setting values. After that, the value is automatically set to “0”.
When “1” is entered, the operating hour meter for the error memory is deleted. After that, the value is automatically set to “0”.
Basic setting Level
0
0
38
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 39
5.3 Messages and signals
5.3.1 Errors
Errors generally lead to the deactivation of at least part of the overall system.
Message text Description
ERROR
POWER FAILURE
ERROR
LOW PRESS.
This message appears in case of voltage recovery when the system has been switched on and the parameter “Restart: NO” has been set in the EDI system menu
This message appears when the permeate pressure when the inlet valve is open is too low for the set time at least and the number of repetition attempts has been reached
ERROR
MAX. PERM. COND.
ERROR
MIN. PERM. COND.
ERROR
TEMP. PERMEATE
ERROR
MAX. PERM. PRESS.
ERROR
MIN. PERM. PRESS.
This message appears when the conductivity of the permeate for the set time has been exceeded and the monitoring system is programmed for deactivation
This message appears when the conductivity of the permeate for the set time has not been reached and the monitoring system is programmed for deactivation
This message appears when the temperature of the permeate for the set time has been exceeded and the monitoring system is programmed for deactivation
This message appears when the pressure of the permeate is exceeded.
This message appears when the pressure of the permeate for the set time is not reached.
GENO-EDI-X
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
39
Page 40
GENO-EDI-X
Message text Description
ERROR
ELEKTR. FLOW
ERROR
DILUATE FLOW
ERROR
MAX. DIL. COND.
ERROR
F-PUMP M8
ERROR
CONCEN.
PRESS.
ERROR
DIF.PR.P5/P6
ERROR
DIL. TEMP.
ERROR
CONCEN. FLOW
ERROR
TLS M6/M7
ERROR
PB PUMP M6
ERROR
PB PUMP M7
ERROR
LEVEL SWITCH
ERROR
SENS. LEVEL
ERROR
SENS.TEMP.PERM
ERROR
SENS.TEMP.DIL.
ERROR
SENS.PRESS. PERM.
ERROR
SENS.PRESS.DIL.
This message appears when the flow volume of the electrolyte for the set time is too low
This message appears when the flow volume of the diluate for the set time is too low and the monitoring system is programmed for deactivation
This message appears when the conductivity of the diluate for the set time has been exceeded and the monitoring system is programmed for deactivation
This message appears when the monitoring input for pump M8 is closed
This message appears when the concentrate pressure for the set time is too high.
(Greater than the diluate pressure)
This message appears when the diluate/ concentrate differential pressure value for the set time is too low and the monitoring system is programmed for deactivation
This message appears when the temperature of the diluate for the set time has been exceeded and the monitoring system is programmed for deactivation
This message appears when the flow volume of the concentrate for the set time is too low and the monitoring system is programmed for deactivation
This error appears when the corresponding level on the permeate tank is undershot
This message appears when the monitoring input for pump M6 is closed (motor protection for rotary current pumps, pressure switch for alternating current pumps)
This message appears when the monitoring input for pump M7 is closed.
This message appears when the level switch reports an invalid level setting
This message appears when the measured value of the level sensor lies outside of a plausible range. (E.g., cable breakage)
This message appears when the measured value of the temperature sensor/permeate lies outside of a plausible range. (E.g., cable breakage)
This message appears when the measured value of the temperature sensor/diluate lies outside of a plausible range. (E.g., cable breakage)
This message appears when the measured value of the pressure sensor/permeate lies outside of a plausible range. (E.g., cable breakage)
This message appears when the measured value of the pressure sensor/diluate lies outside of a plausible range. (E.g., cable breakage)
40
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 41
Message text Description
ERROR
SENS.PRESS. CONC.
ERROR
E16 (text can be edited)
MSR-MODULE
MISSING
POW. SUP. UNIT 1
MISSING
Table F-10: Errors
5.3.2 Warnings
Warnings are shown on the display and saved in the error
This message appears when the measured value of the pressure sensor/concentrate lies outside of a plausible range. (E.g., cable breakage)
This message appears when input 16 is programmed for errors and open for the set time at minimum
This message appears when communication to the basic module fails
This message appears when communication to the power supply unit (power supply of EDI module) fails
memory. Non-acknowledged messages flash in the display.
Message text Description
MAINTAIN
EDI
WARNING
LOW PRESS.
WARNING
MAX. PERM. COND.
WARNING
MIN. PERM. COND.
WARNING
TEMP. PERMEATE
WARNING
FLOW DILUATE
WARNING
MAX. DIL. COND.
MAINTAIN
DIFF.PRESS. P5/P6
WARNING
TEMP. DILUATE
WARNING
CONCEN. FLOW
WARNING
E16 (text can be edited)
Table F-11: Warnings
This message appears when the maintenance interval has expired
This message appears when the permeate pressure when the inlet valve Y7 is open is too low for the set time at least and the number of repetition attempts has not yet been reached
This message appears when the conductivity of the permeate for the set time has been exceeded and the monitoring system is not programmed for deactivation
This message appears when the conductivity of the permeate for the set time has been undershot and the monitoring system is not programmed for deactivation
This message appears when the temperature of the permeate for the set time has been exceeded and the monitoring system is not programmed for deactivation
This message appears when the flow volume of the diluate for the set time is too low and the monitoring system is not programmed for deactivation
This message appears when the conductivity of the diluate for the set time has been exceeded and the monitoring system is not programmed for deactivation
This message appears when the diluate/ concentrate pressure difference for the set time is too low and the monitoring system is not programmed for deactivation
This message appears when the temperature of the diluate for the set time has been exceeded and the monitoring system is not programmed for deactivation
This message appears when the flow volume of the concentrate for the set time is too low and the monitoring system is not programmed for deactivation
This message appears when input E16 is programmed for warnings and open for the set time at minimum
GENO-EDI-X
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
41
Page 42
GENO-EDI-X
5.4 Electrodeionisation (GENO-EDI-X system)
This menu includes the adjusting values related to the GENO-EDI-X system. The EDI main menu is called by pressing the F3 button on any visualisation system view. On the next screen, the only choices still available are the display function (F2 button) and the entry function (F1 button). The F4 button takes you back to the visualisation system of the EDI system. If the entry mode was selected with the F3 button, the code for the desired level must be entered and this entry must be confirmed by pressing the button.
Fig. F-12: Visualisation system of the GENO-EDI-X system
The EDI main menu is structured as follows:
EDI menu >User
Parameters Times Errors Service Data Reference Data Basic Setting
The selection is made using the arrow buttons ▲ and ▼. The button takes you to the selected submenu. The F4 button (Exit) takes you to the previous screen.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
42
Page 43
5.4.1 User
GENO-EDI-X
This submenu contains the customer parameters. This submenu has the following parameters:
Menu
Table F-13: Customer user level
EDI User
Operating mode:
Setting range
OFF: The GENO-EDI-X system is not active
MANUAL: The GENO-EDI-X system always runs when no error is present.
AUTO: The GENO-EDI-X system runs depending on the level switch of the diluate tank.
5.4.2 Parameters
This submenu contains the general parameters of the GENO-EDI-X system. This submenu has the following parameters:
Menu
EDI system: STANDBY: The system is
EDI control
Restart: Restart after power failure
Voltage Direct voltage for EDI
Current Working voltage for EDI
M8 pres. Permeate feed pump resent
Forced op. Forced operation
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
EDI System
unit:
Description
ready for operation
LOCKED: The system is locked
Determination of the actuation of the EDI system
Level: Controlled via level switches
PS: Controlled via pressure switches
ANA: Controlled via analogue signals (4-20 mA)
Profi: Controlled via Profibus
NO: The system reports an error after a power failure YES: System acts as it did before power failure
module 0V – 300V
module 0.0A – 5.0A
NO YES
NO: No forced operation takes place.
YES: Forced operation takes place.
Basic setting Level
AUTO Code
0095
Basic setting Level
LOCKED
LEVEL
YES
200V
2.5A
NO
NO
43
Page 44
GENO-EDI-X
Min.
Run.Time:
Cond. disp.
dil.:
Flow Disp.Dil.: Flow display of the diluate in the
Flow
Disp.Conc.:
Flow Disp.El.
pres.
Flow
Disp.Elect.
Perm.Cond.
pres.
E-Perm.Cond. Limit value for the conductivity of
E-Diluate
Valve
E-Dil.Cond. Limit value for the conductivity of
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
44
Determination of minimum run time to trigger forced operation
SINGLE: The run time restarts at the activation of the GENO-EDI-X system.
SUM: The individual runtimes of the GENO-EDI-X system are cumulated.
Display of the conductivity measurement in: µS/cm megaohm
flow chart of the GENO-EDI-X sys­tem:
- l/h: Display in litres per hour
3
/h: Display in m3 per
- m hour
- NO: No display
Flow display of the concentrate in the flow chart of the GENO-EDI-X system:
- l/h: Display in litres per hour
3
/h: Display in m3 per
- m hour
- NO: No display
Flow display of the electrolyte in the flow chart of the GENO-EDI-X system:
- l/h: Display in litres per hour
3
/h: Display in m3 per
- m hour
- NO: No display
Flow display of the electrolyte in the flow chart of the GENO-EDI-X system present:
NO YES
Conductivity measurement in permeate inlet
NO: Conductivity measurement not present
YES: Conductivity measurement present
permeate rejection:
5 – 40 µS/cm
Solenoid valve Y10 for diluate rejection
NO: The valve is not present
YES: The valve is present
diluate rejection:
0.055 – 2.000 µS/cm
SINGLE
µs/cm
l/h
l/h
l/h
NO
NO
20µS/cm
NO
0.800µS/cm
Page 45
Conc.Cond.
pres.
Press.Perm.
pres.
Press.Dil.
pres.
Press.Conc.
pres.
Abort Forced
Op.:
Table F-14: Parameters
Conductivity measurement in concentrate NO: The conductivity measurement is not present YES: The conductivity measurement is present
Pressure measurement in permeate NO: Pressure measurement is not present
YES: Pressure measurement is present
Pressure measurement in diluate NO: Pressure measurement is
not present YES: Pressure measurement is present
Pressure measurement in concentrate NO: Pressure measurement is not present
YES: Pressure measurement is present
Abort command for forced operation.
When “1” is entered, any forced operation is interrupted. After that, the parameter is automatically reset to “0”.
GENO-EDI-X
NO
YES
YES
YES
0
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
45
Page 46
GENO-EDI-X
5.4.3 Times
This submenu contains the time parameters of the GENO-EDI-X system. This submenu has the following parameters:
Menu
EDI Times
Rinsing time: EDI module rinsing time:
E-Perm. Time: Latest time as of the EDI
Current delay:
PS Lev. A
Delay:
PS Lev. B
Delay:
Setting range
Setting range: 0 – 999 seconds
START after which the valve for the first permeate rejection is closed. (Required only if a first permeate valve is present)
Setting range: 0...999 seconds
Delay time for the activation of the regeneration current of the EDI module (after permeate rejection)
Setting range: 0...999 seconds
Delay time of the “A” level in case of control via pressure switch
Setting range: 0...999 seconds
Delay time of the “B” level in case of control via pressure switch
Setting range: 0...999 seconds
Basic setting Level
20 sec.
300 sec.
10 sec.
0 sec.
600 sec.
46
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 47
Max. idle time: Maximum idle time; time window
for the check of the system run time
Setting range: 1...48 hours
Min.
Run.Time:
E-Diluate
Time:
Maint. int.: Maintenance interval of the
Table F-15: Times
Minimum run time within the window set under “Max. idle time: xx”
Setting range: 1...48 hours
Latest time as of the “OPEN” permeate inlet valve after which the valve for the first diluate rejection is closed. (Required only if a first diluate valve is present)
Setting range: 0...999 seconds
GENO-EDI-X system Setting range: 0...365 days
GENO-EDI-X
48 hours
1 hour
30 sec.
365 days
5.4.4 Errors
This submenu contains the parameters for the errors of the GENO-EDI-X system. This submenu has the following parameters:
Menu
EDI Errors
Err.M8 delay: Delay time for a malfunction
Max. Dil.
Cond.:
Max. Dil.
Cond. Deact.:
Setting range
in the permeate pump M8
Setting range: 0...999 seconds
Limit value for the conductivity of diluate
Setting range: 0.055 – 2.000
µS/cm
Deactivation in case diluate conductivity is too high NO: Dil. Cond. Warning YES: Dil. Cond. Error
Basic setting Level
5 sec.
0.800 µS/cm
YES
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
47
Page 48
GENO-EDI-X
Max. Dil.
Cond. Del.:
Max. Perm.
Cond.:
Max. Perm.
Cond. Deact:
Max. Perm.
Cond. Del.:
Min. Perm.
Cond. Deact:
Delay time for monitoring the diluate conductivity
Setting range: 0...999 seconds
Limit value for the conductivity of permeate
Setting range: 5 – 40 µS/cm
Deactivation in case permeate conductivity is too high NO: Max. Perm. Cond. Warning YES: Max. Perm. Cond. Error:
Delay time for monitoring the maximum permeate conductivity
Setting range: 0...999 seconds
Deactivation in case permeate conductivity is too low NO: Min. Perm. Cond. Warning YES: Min. Perm. Cond. Error
600 sec.
20 µS/cm
YES
300 sec.
NO
48
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 49
Min. Perm.
Cond. Del:
Max. Perm.
Temp.:
Perm. Temp.
Deact.:
Perm. Temp.
Del.:
Error P9 delay: Delay time for the low pressure
P9 repet.: Number of repetition attempts for
P9 waiting
time:
Min. El. Flow: Minimum electrolyte flow
El. Flow Del.: Delay time for monitoring the
Min. Dil. Flow: Minimum diluate flow
Dil. Flow
Deact.:
Dil.Flow Del.: Delay time for monitoring the
Min. Perm.
Press.:
Perm. Press.
Del.:
Conc. Press.
Del.:
Dif.Press.D-C: Minimum differential pressure
Delay time for monitoring the minimum permeate conductivity
Setting range: 0...999 seconds
Limit value for the permeate temperature
Setting range: 0 - 40°C
Deactivation in case permeate temperature is too high NO: Warning Perm. Temp. YES: Error Perm. Temp.
Delay time for monitoring the maximum permeate temperature
Setting range: 0...999 seconds
switch – monitoring of the inlet
Setting range: 0...10 seconds
the low pressure monitoring of the inlet
Setting range: 0...99
Time between the repetition attempts for the low pressure monitoring of the inlet
Setting range: 0...999 seconds
Setting range: 10 -100 l/h
minimum electrolyte flow
Setting range: 0 - 15 minutes
Setting range: 0 - 20000 l/h
Deactivation in case diluate flow is too low NO: Warning Min. Dil. Flow YES: Error Min. Dil. Flow
minimum diluate flow
Setting range: 0 - 999 seconds
Minimum permeate inlet pressure
Setting range: 0.0 – 6.0 bar(g)
Delay time for monitoring the minimum permeate inlet pressure
Setting range: 0 – 999 seconds
Delay time for monitoring the minimum concentrate pressure
Setting range: 0 – 999 seconds
between diluate and concentrate (diluate > concentrate)
Setting range: 0.1 – 1.0 bar
GENO-EDI-X
10 sec.
30°C
NO
600 sec.
5 sec.
3
300 sec.
15 l/h
5 min.
1000 l/h
NO
10 sec.
2.5 bar(g)
10 sec.
30 sec.
0.2 bar
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
49
Page 50
GENO-EDI-X
Dif.Press.D-C
Deact.:
Dif.Press.D-C
Del.:
Max. Dil.
Temp.:
Dil. Temp.
Deact.:
Dil. Temp.
Del.:
Min. Conc.
Flow:
Conc. Flow
Deact.:
Conc. Flow
Del.:
Table F-16: Errors
5.4.5 Service Data
This submenu contains the parameters for the service information of the GENO-EDI-X system. These parameters can only be displayed and not changed. This submenu has the following parameters:
Deactivation in case differential pressure between diluate and concentrate is too low NO: Warning Min. Dil. Flow YES: Error Min. Dil. Flow
Delay time for monitoring the minimum differential pressure between the diluate and concentrate
Setting range: 0 – 999 seconds
Limit value for the diluate temperature
Setting range: 0 - 40°C
Deactivation in case diluate temperature is too high NO: Warning Dil. Temp. YES: Error Dil. Temp.
Delay time for monitoring the maximum diluate temperature
Setting range: 0...999 seconds
Minimum concentrate flow
Setting range: 0 - 2000 l/h
Deactivation in case concentrate flow is too low NO: Warning Min. Conc. Flow YES: Error Min. Conc. Flow
Delay time for monitoring the minimum concentrate flow
Setting range: 0 - 999 seconds
YES
30 sec.
30°C
NO
300 sec.
100 l/h
YES
30 sec.
Menu
RO Service
Oper. Hour
M8:
Diluate sum: Sum of diluate volume in
Conc. sum: Sum of concentrate volume
Electrolyte
sum:
Table F-17: Service data
Description
Operating hours of the permeate feed pump M8
3
/h
m
3
/h
in m
Sum of electrolyte volume in
3
/h
m
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
50
Basic setting Level
0 h Code
0095
3
0 m
Code
0095
3
Code
0 m
0095
3
0 m
Code
0095
Page 51
5.4.6 Reference Data
This submenu contains the parameters for calibrating the water meters and conductivity. This submenu has the following parameters:
Note: These values must be entered during production!
Menu
Diluate Ref.: Reference data for the diluate
Conc. Ref.: Reference data for the
Elect. Ref.: Reference data for the
Dil. Cond. Ref.: Reference data for diluate
Dil. Cond.
Dil. Cond.
Dil. Cond.
Perm. Cond.
Perm. Cond.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
RO Reference
Comp.:
Temp. Coeff.
Temp.:
Ref.:
Comp.:
Description
water meter. The externally determined, current flow through the water meter is entered here. Setting range: 0...20000 l/h
concentrate water meter. The externally determined, current flow through the water meter is entered here. Setting range: 0...2000 l/h
electrolyte water meter. The externally determined, current flow through the water meter is entered here. Setting range: 0...100 l/h
conductivity. The externally determined, current value for conductivity is entered here. Setting range: 0...2.000 µS/cm
Temperature determination for the temperature compensation of the diluate conductivity DEMAND: The temperature is entered AUTOM.: The temperature is determined by the sensor
Temperature coefficient for the temperature compensation of the diluate conductivity Setting range: 0.3...3.0%/K
Temperature in case of “Dil. Cond. Comp.: DEMAND” Setting range: 0...100°C
Reference data for permeate conductivity. The externally determined, current value for conductivity is entered here
Setting range: 0...100 µS/cm
Temperature determination for the temperature compensation of the permeate conductivity
Demand: The temperature is entered
Autom.: The temperature is determined by the sensor
GENO-EDI-X
Basic setting Level
1000 l/h
100 l/h
100 l/h
1.0 µS/cm
DEMAND
2.3%/K
25°C
30 µS/cm
DEMAND
51
Page 52
GENO-EDI-X
Perm. Cond.
Temp. Coeff.:
Perm. Cond.
Temp.:
Conc. Cond.
Ref.:
Table F-18: Reference Data
5.4.7 Basic Setting
This submenu contains the parameters for the basic settings of the GENO-EDI-X system. This submenu has the following parameters:
Temperature coefficient for the temperature compensation of the permeate conductivity
Setting range: 0.3...3.0%/K
Temperature in case of “Perm. Cond. Comp.: DEMAND”
Setting range: 0...99°C
Reference data for concentrate conductivity. The externally determined, current value for conductivity is entered here
Setting range: 0...500 µS/cm
2.5%/K
25°C
300 µS/cm
Menu
Default values: When “1” is entered, the
Maint. int.: When “1” is entered, the
Operating
Sums Water
Table F-19: Basic setting
EDI Basic Setting
hours:
Meter:
Description
setting parameters are reset to the basic setting values. After execution, the entry is reset to “0”.
maintenance interval is reset. After execution, the entry is reset to “0”.
When “1” is entered, the operating hours M8 are reset. After execution, the entry is reset to “0”.
When “1” is entered, the water meter sums are reset. After execution, the entry is reset to “0”.
Basic setting Level
0
0
0
0
Grünbeck
Grünbeck
52
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 53
5.5 Pressure booster (PB system) if activated in system menu
This menu includes the adjusting values related to the pressure booster. The PB main menu is called by pressing the F4 button on the visualisation system of the PB system. On the next screen, the only choices still available are the display function (F1 button) and the entry function (F2 button). The F4 button takes you back to the display screen of the PB system. If the entry mode was selected with the F2 button, the code for the desired level must be entered and this entry must be confirmed by pressing the button.
GENO-EDI-X
Fig. F-20: Visualisation system of the PB system
The PB main menu is structured as follows:
Menu Pressure Booster >User
Parameters Errors Service Data Basic Setting
The selection is made using the arrow buttons ▲ and ▼. The button takes you to the selected submenu. The F4 button (Exit) takes you to the previous screen.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
53
Page 54
GENO-EDI-X
5.5.1 User
This submenu contains the customer parameters. This submenu has the following parameters:
Menu
Operating
Table F-21: Operator
5.5.2 Parameters
PB User
mode:
This submenu contains the general parameters of the PB
Setting range
OFF: The PB system is not active
MANUAL: The pressure booster pump is always running if the system is on and no error is present.
AUTO: The pressure booster pump runs depending on the pertinent pressure switch.
system. This submenu has the following parameters:
Menu
PB Parameters
PB control unit Determination of the
TLS M6/M7: Delay time after response of
P7 delay: Delay time of the pressure
No. of PB
pumps:
M6/M7
switch-over
Filling level
stop:
Filling level
start:
Fill. lev.
Emerg. feed
Filling level
TLS:
Description
actuation of the PB control unit
PS: Controlled via pressure switches
Profi: Controlled via Profibus
the dry-run protection
Setting range: 0...999 seconds
switch of the PB pumps
Setting range: 0...30 seconds
Number of existing PB pumps
Setting range: 0...2
Switch-over time in case of 2 PB pumps (GLW)
Setting range: 1…99 h
Filling level in %; EDI system stop
Setting range: 0...100%
Filling level in %; EDI system start
Setting range: 0...100%
Filling level in %; EDI system emergency feed
Setting range: 0...100%
Filling level in %; PB system stop
Basic setting Level
AUTO Code
0095
Basic setting Level
3P
10 sec.
10 sec.
1
12 h
95%
70%
30%
30%
Table F-22: Parameters
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
54
Page 55
5.5.3 Errors
GENO-EDI-X
This submenu contains the parameters for the errors of the PB system. This submenu has the following parameters:
Menu
PB Errors
M6/M7 prot.
mot. sw.:
Err.M6.M7
Del.:
Table F-23: Errors
Setting range
Pressure booster pumps with protective motor switch
NO: No protective motor switch alternating current pump(s)
YES: Protective motor switch present  rotary current pump(s)
Delay time in case of an error in the pressure booster pumps during pressure monitoring Setting range: 0...999 seconds
Basic setting Level
YES
30 sec.
5.5.4 Service Data
This submenu contains the parameters for the service information of the PB system. These parameters can only be displayed and not changed. This submenu has the following parameters:
Menu
Oper. Hour
Oper. Hour
Table F-24: Service data
5.5.5 Basic Setting
PB Service
M6:
M7:
This submenu contains the parameters for the basic settings of the
Description
Operating hours of the pressure booster pump M6
Operating hours of the pressure booster pump M7
Basic setting Level
0 h Code
0095
0 h Code
0095
PB system. This submenu has the following parameters:
Menu
PB Basic Setting
Default values: When “1” is entered, the
Operating
hours:
Table F-25: Basic setting
Description
setting parameters of the PB system are reset to the basic setting values. After execution, the entry is reset to “0”.
When “1” is entered, the operating hours M6/M7 are reset. After execution, the entry is reset to “0”.
Basic setting Level
0
0
Grünbeck
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
55
Page 56
GENO-EDI-X
G Troubleshooting
1 | Basic information
Even carefully designed and manufactured technical systems
that are operated properly may experience malfunctions. Table G-1 provides an overview of possible problems that may occur during the operation of the systems and indicates the causes and their elimination.
The systems are equipped with an error detection and reporting system. If an error message is displayed:
1. Press the "DEBUG" button (= acknowledge malfunction).
2. Watch the display. If the message reappears, compare it with table G-1.
3. If necessary, notify Grünbeck’s technical customer service.
Note: The technical customer service definitely must be notified
in case of malfunctions that cannot be remedied with the information given in table G-1! When contacting the technical customer service, please indicate the system designation, order number and the error message displayed.
56
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 57
2| Troubleshooting
Table G-1: Errors
This is what you observe This is the cause This is what to do
Inlet pressure P4 too high Permeate supply flow
Malfunction
Check the RO system or permeate feed pump.
GENO-EDI-X
Flow capacity of the GENO-EDI-X system too low
Diluate conductivity too high
Diluate temperature T2 too high
Concentrate flow F8 too low
Water temperature too low
Incorrect setting of adjusting valve V4, V5, V6, V7
EDI module clogged
CO2 value in inlet too high
Flow F7 in diluate too high
Scaling
Bacterial growth
Change in the feed water value
The concentrate pressure P6 is higher than the diluate pressure P5
Temperature of RO system permeate and/or inlet water too high
Incorrect setting of adjusting valves V5, V7
Scaling
Check of temperature
Readjust adjusting valve V4, V5, V6, V7
Clean EDI module
Check RO system/NaOH dosing or membrane degassing
Readjust adjusting valve V6
Clean EDI module
Clean EDI module
Readjust operating
current/voltage
Setting of the pressure difference:
Diluate P5 > P6 concentrate (0.2 – 0.5 bar)
Check temperature of RO system permeate and/or inlet water
Readjust adjusting valves V5, V7
Clean EDI module
Concentrate flow F8 too high
Concentrate pressure P6 too high
Differential pressure of diluate/concentrate too high
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Incorrect setting of adjusting valves V5, V7
Incorrect setting of adjusting valves V6, V7
Scaling
Incorrect setting of adjusting valves V6, V7
Readjust adjusting valves V5, V7
Readjust adjusting valves V6, V7
Clean EDI module
Readjust adjusting valves V6, V7 Max. differential pressure 0.5 bar
57
Page 58
GENO-EDI-X
H Maintenance
1 | Basic information
In order to guarantee the reliable function of the systems over a
long period of time, some maintenance work has to be performed at regular intervals. All regulations and guidelines which apply at the installation site must be strictly adhered to.
A daily check of the quality and the system volume flows
must be performed.
The log sheets must be filled out daily on warranty
grounds. Conclusions regarding any problems/damage can also be derived from these documents.
Maintenance has to be performed by Grünbeck’s
technical service/authorised service company or by a specialised company. Maintenance is subject to the load, but at the latest has to be performed once a year.
An operation log and the corresponding test log must be
kept in order to document the maintenance work performed.
Note: By concluding a maintenance contract you ensure that all
maintenance work will be performed in due time.
The maintenance work performed must be documented in the checklist, refer to appendix "Operation log".
2 | Inspection (functional check)
You may perform the daily inspections yourself.
Please refer to the following overview for the tasks to be performed within the scope of an inspection.
Overview: Inspection work
Determine the feed water quality (inlet);
check any pretreatments.
Check the diluate quality.
Check the diluate flow volume.
Check the concentrate flow volume.
Check the current and voltage values.
Check the pressures and differential pressure
(diluate/concentrate).
Note: Minor deviations are normal and cannot be prevented technically. In case of considerable deviations from the standard, notify Grünbeck's technical customer service.
Check the seal tightness of the system.
58
Check the electrical connections on the EDI module.
Check the earthing connections on the EDI module (4 pieces).
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
Page 59
GENO-EDI-X
3 | Maintenance
According to DIN 1988 part 8 / A 12, maintenance work at the systems may only be performed by Grünbeck’s technical
For this kind of systems, an operation log - a checklist has to be
service/authorised service company or an approved specialist company.
kept. In this operation log, the customer service technician records all maintenance and repair work performed. In case of malfunctions, this log helps to identify possible sources of error. In addition, the log documents the proper system maintenance.
Make sure that all maintenance work is recorded in the operation log.
Overview: Maintenance work
Check the switching function of the solenoid valves.
Check the flow volumes and recalibrate the water meters.
3.1 Operation log
Check the state and seal tightness of the entire system.
Mechanical and/or electrical functional and performance test of
all aggregates (valves, EDI module).
Check of the electrical connections
Check of the tightening torques on the bolts of the EDI module.
Check the setting parameters (current, voltage, pressure).
Check the feed values for changes in regard to the following:
Prepare a written maintenance report on the state and function
When starting up the system, make sure to record all data on the cover sheet of the operation log and fill in the first column of the checklist.
The customer service technician will fill in a column of the check list whenever maintenance is performed. This document provides evidence of proper maintenance.
Retighten screw connections if necessary.
Retighten bolts if necessary.
1. The original values after initial start-up
2. The design basis
of the system and the maintenance work performed, including evaluation and assessment of the operating values and water analysis results.
Order no. 024 770 901-inter Edited by: rreh/bkop G:\BA-770901-inter_024_GENO-EDI-X.docx
59
Loading...