1 GRUNAIRE HX SERIES SERVICE MANUAL
SERVICE MANUAL
DC Inverter Multi-Split Air-Condition Unit
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg2.png)
2 GRUNAIRE HX SERIES SERVICE MANUAL
Table of Cont e n ts
1. INTRODUCTION ................................................................................................. 1-1
2. PRODUCT DATA SHEET ................................................................................... 2-1
3. RATING CONDITIONS ....................................................................................... 3-1
4. OUTLINE DIMENSIONS ..................................................................................... 4-1
5. PERFORMANCE DATA ...................................................................................... 5-1
6. PRESSURE CURVES ......................................................................................... 6-1
7. ELECTRICAL DATA ............................................................................................. 7-1
8. WIRING DIAGRAMS ........................................................................................... 8-1
9. REFRIGERATION DIAGRAMS .......................................................................... 9-1
10. TUBING CONNECTIONS ..................................................................................... 10-1
11. CONTROL SYSTEM ........................................................................................... 11-1
12. TROUBLESHOOTING ........................................................................................ 12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS ................................................ 13-1
14. APPENDIX A
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg3.png)
3 GRUNAIRE HX SERIES SERVICE MANUAL
1. INTRODUCTION
1.1 General
The new grunaire HX series minisplit is a high efficiency DC inverter technology outdoor unit,
It can be matched to several inverter indoor units such as wall mounted type with a capacity
range of 9000 – 12000 BTU for each single indoor unit.
1.2 Main Features
DC Inverter
R410a
sine wave form and 120 degree rectangular wave form in compressor driver
sensor less inverter compressor driver
high speed calculation for accurate sine wave form vector control
smart PFC control
fuzzy logic control
High SEER
Lego Concept
Pre-Charged.
Cooling operation at outdoor temperature down to 500F
Heating operation at outdoor temperature down to 50F.
Variable Speed outdoor fan.
Low noise level
EEV for each indoor unit
1.3 Tubing Connections
Flare type interconnecting tubing to be produced on site.
For further details please refer to APPENDIX A on this manual, and to the relevant indoor service
Manual,
1.4 Inbox Documentation
Each indoor unit is supplied with its own installation and operation manuals.
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg4.png)
4 GRUNAIRE HX SERIES SERVICE MANUAL
2. P RO D UC T D AT A S H EE T
2. 1 Out d oo r u n i t d a ta
2. 1 .1 DC I nve r t o r 1 :1 .
Remote control setting temp.range °F
Dehumidification (Pts/hr)
Current (A) Rated/Max Cooling
Power Consumption (KW)Rated/Max Cooling
Indoor Air Circulation: L / M / H(CFM)
Indoor Noise level dB(A): L / M / H
Outdoor Noise Level dB(A)
Service Port Connection (In.)
Indoor Dimensions W x D x H(In.)
Indoor Package Dimensions W x D x H(In.)
Indoor Gross Weight(lbs. )
Outdoor Dimensions W x D x H(In.)
Outdoor Package Dimensions W x D x H(In.)
Outdoor Net Weight (lbs.)
Outdoor Gross Weight(lbs. )
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg5.png)
5 GRUNAIRE HX SERIES SERVICE MANUAL
2.1. 2 DC I n ve r t e r 1 :2
Rated Current (RLA) (Heating/Cooling)
Capacity Invert Range (W)
Capacity Invert Range (W)
Declared COP / Actual COP
(w/w.h.)
Air Flow Volume of Outdoor Unit
(CFM)(M^3/h)
Tube Outside Dia. and Type
Coil Length x Height x Width
28.66 x 25.6 x .866
28.66 x 25.6 x .988
30.23 x 31.96 x .866
31.57 x 31.96 x .866
30.23 x 31.96 x .866
31.57 x 31.96 x .866
Unit Dimensions (W x H x D) (in)
Packing dimensions (W x H x D)
(in)
Charge over Design Length
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg6.png)
6 GRUNAIRE HX SERIES SERVICE MANUAL
2. 2 In d oo r U ni t s D at a
2.2.1 HXS- 2 5 V 9 A - A2 1 A S p e c i f ic a t io n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.2 HXS- 3 2 V 9 A - A2 1 A S p e c i f ic a t i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg7.png)
7 GRUNAIRE HX SERIES SERVICE MANUAL
2.2.3 HXS - 2 5V 9 A- A27 A S p e c i f i c a t io n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.4 HXS - 3 2V 9 A- A 27A S p e ci f i ca t i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg8.png)
8 GRUNAIRE HX SERIES SERVICE MANUAL
2.2.5 HXS - 2 5V 9 A- A 48A S p e ci f i ca t i o n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.6 HXS - 3 2V 9 A- A 48A S p e ci f i ca t i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg9.png)
9 GRUNAIRE HX SERIES SERVICE MANUAL
2.2.7 HX- V 2 5G 9 A/ A 3 0 S p e c i f ic a t i o n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.8 HX- V 3 2G 9 A/H 3 0 S p e c i f ic a t i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bga.png)
10 GRUNAIRE HX SERIES SERVICE MANUAL
2.2.9 HX- V 2 5G 9 A/ A 4 6 S p e c i f ic a t i o n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.10 HX- V 3 2 G 9 A / H 4 6 Sp e c i f i c at i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bgb.png)
11 GRUNAIRE HX SERIES SERVICE MANUAL
2.2.11 HX- V 2 5 G 9 A / A7 7 S p e c i f i ca t i o n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.12 HX- V 3 2 G 9 A / H 7 7 Sp e c i f i c at i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bgc.png)
12 GRUNAIRE HX SERIES SERVICE MANUAL
2.2.13 HX- V 2 5 G 9 A / A7 9 S p e c i f i ca t i o n s
Tube pitch row / pitch (in)
Tube outside dia.(in) / Type
Coil Length x height x width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
2.2.14 HX- V 3 2 G 9 A / H 7 9 S p e c i f i ca t i o n s
1200 / 950 / 850 (Cooling) 1200 / 950 / 750
(Heating)
Tube pitch row / pitch (in)
Tube outside dia.(in) /
Type
Coil Length x height x
width (in)
Air Flow (Hi/Med/Low) (CFM)
Unit Dimensions (W x H x D) (in)
Packing Dimensions W x H x D) (in)
Dehumidifying Volume (pt/hr)
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bgd.png)
13 GRUNAIRE HX SERIES SERVICE MANUAL
3. RA TI NG C O ND IT IO NS
Standard conditions in accordance with ANSI/AHAM RAC-1-2003, and UL 484.
Cooling:
Indoor: 80oFDB 67oF WB
Outdoor: 95oF DB 75oF WB
Heating:
Indoor: 70 oF DB 60 oF WB
Outdoor: 47
o
F DB 43 oF WB
3. 1 Op e ra t i n g L im i ts
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bge.png)
14 GRUNAIRE HX SERIES SERVICE MANUAL
4. OU TL IN E D IM EN SI O NS
4.1 outdoor Unit: GSU091HX
4.2 outdoor Unit: GSU121HX
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bgf.png)
15 GRUNAIRE HX SERIES SERVICE MANUAL
4.3 outdoor Unit: GSU181HX
4.4 outdoor Unit: GSU241HX
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg10.png)
16 GRUNAIRE HX SERIES SERVICE MANUAL
4.5 outdoor Unit:HX-50V9A-S
4.6 outdoor Unit:HX-V64T9AD
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg11.png)
17 GRUNAIRE HX SERIES SERVICE MANUAL
4.7 outdoor Unit:HX-V64WC9A
560
378
342
845
351
72
50
956
825
50×3(=150)
50
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg12.png)
18 GRUNAIRE HX SERIES SERVICE MANUAL
5. P E R FO RM AN CE DA T A
5.1 Indoor Units Data
5.1.1 Indoor Units Capacity For 9000BTU
5.1.1.1 Cooling Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at
high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [0F]
OUTDOOR
ENTERING AIR DB
TEMPERATURE[0F]
L E GE N D
TC – Total Cooling Capacity, BTU SC – Sensible Capacity, BTU PI – Power Input, kW
WB – Wet Bulb Temp., (
0
F
) DB – Dry Bulb Temp., (
0
F
) ID – Indoor OD – Outdoor
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg13.png)
19 GRUNAIRE HX SERIES SERVICE MANUAL
5.1.1.2 Heating Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at
high speed
ID COIL ENTERING AIR DB TEMPERATURE [0F]
OD COILENTERING
AIR DB/WB TEM
PERATU RE[0F]
5.1.1.3 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
77 86 95 104 115
90/73
84/70
81/66
75/63
72/59
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg14.png)
20 GRUNAIRE HX SERIES SERVICE MANUAL
Heating Capacity Ratio Vs. Outdoor Temperature
Heating Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
5 14 20 30 36 45 50 59
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg15.png)
21 GRUNAIRE HX SERIES SERVICE MANUAL
5.2.1 Indoor Units Capacity For 12000BTU
5.2.1.1 Cooling Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at
high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [0F]
OUTDOOR
ENTERING AIR DB
TEMPERATURE[0F]
![](/html/e2/e2f7/e2f7437f2b168795311c51059504398881ef3ad0ea3fe317225c45c05f5b1d86/bg16.png)
22 GRUNAIRE HX SERIES SERVICE MANUAL
5.2.1.2 Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at high
speed
ID COIL ENTERING AIR DB TEMPERATURE [0F]
OD COILENTERING
AIR DB/WB TEM
PERATU RE[0F]
5.2.1.3 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
Cooling Capacity Correction Factor
0
0.2
0.4
0.6
0.8
1
1.2
1.4
77 86 95 104 115
90/73
84/70
81/66
75/63
72/59