Parallel Inst a llation Guide
![](/html/24/2486/24860da22c2b669b09a4ac626fc4d1049d28138201ff3b27d4514fa225bc4c39/bg2.png)
1 Introduction
4 Mounting the Unit
This inverter can be used in parallel with maximum 3 units. The supported maximum
output power is 30KW/30KVA.
2 Parallel cable
You will find the following items in the package:
Parallel communication cable Current sharing cable
3 Overview
When installing multiple units, please follow below chart.
For proper air circulation to dissipate heat, it’s necessary to allow a clearance
NOTE:
of approx. 20 cm to the side and approx. 50 cm above and below the unit. Be sure to
install each unit in the same level.
5 Wiring Connection
Ring t erminal :
The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter:
1.Parallel communication port
2.Current sharing port
Ring Terminal
Model
Growatt 10000HYP
WARNING:
be voltage difference between inverter and battery to cause parallel inverters not
working.
Be sure the length of all battery cables is the same. Otherwise, there will
Wire Size
3/0 85 8.4 54.2 7~12 Nm
Dimensions
D (mm)
Torque valueCable mm2
L (mm)
21
![](/html/24/2486/24860da22c2b669b09a4ac626fc4d1049d28138201ff3b27d4514fa225bc4c39/bg3.png)
Reco mm ended A C in put and o ut put cab le s ize for e ac h inver te r:
Appr ox imate b ac k-up ti me t able
Model
Growatt 10000HYP
You need to connect the cables of each inverter together. Take the battery cables for
example. You need to use a connector or bus-bar as a joint to connect the battery
cables together, and then connect to the battery terminal. The cable size used from
joint to battery should be X times cable size in the tables above. “X” indicates the
number of inverters connected in parallel.
Regarding cable size of AC input and output, please also follow the same principle.
CAUTION!!
can be securely disconnected during maintenance and fully protected from
overcurrent of battery.
Reco mm ended b re aker sp ec ifica ti on of bat te ry for ea ch i nvert er :
* If you want to use only one breaker at the battery side for the whole system, the
rating of the breaker should be X times current of one unit. “X” indicates the number
of inverters connected in parallel.
Please install a breaker at the battery side. This will ensure the inverter
Model
Growatt 10000HYP 300A/60VDC
AWG no.
10~8 AWG
Conductor cross
-section
5.5~10 mm2 1.4~1.6Nm
One unit*
Torque
Load (W)
5,000
10,000
15,000
20,000
25,000
30,000
PV Connection
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.
Backup T ime @ 48Vdc
800Ah (min)
240
112
60
40
20
13
Backup T ime @ 48Vdc
1200Ah (min)
360
168
6 Inverters Configuration
Two inverte rs in paral lel:
Powe r Co nnect io n
90
60
30
20
Reco mm ended b at tery ca pa city
Inverter parallel numbers
Battery Capacity
CAUTION!
to choose the suitable battery. The wrong charging parameters will reduce the
battery lifecycle sharply.
3 4
Please follow the battery charging current and voltage from battery spec
2 3
800AH 1200AH