General information about electrical installation11
EMC-correct electrical installation12
Grounding of shielded/armored control cables13
Diagram14
Electrical installation15
Safety clamp17
Prefuses17
AC line connection17
Motor connection18
Direction of motor rotation19
Motor thermal protection19
Parallel connection of motors19
Motor cables19
Brake connection20
Ground connection20
Load sharing20
Tightening Torque, Power Terminals21
Calculation of brake resistance21
Access to control terminals21
Electrical installation, control circuitry21
Tightening torques, control cables22
Electrical installation, control terminals22
Relay connection23
VLT Software Dialog23
Connection examples24
Control unit26
Manual initialization26
Automatic motor tuning27
Display readout29
Hand Auto29
Warnings/alarms30
Special conditions31
Temperature-related switching frequency31
Derating for long motor cables31
3
6
MG.27.A2.22 - VLT® is a registered Danfoss trademark 1
VLT® 2800 Series
VLT 2800 start-up31
Programming
Operation & Display33
Load and Motor41
References & Limits52
Inputs and Outputs59
Special functions69
Enhanced Sleep Mode79
Serial communication84
Technical functions93
All about VLT 2800
Warnings/alarm messages98
Warning words, extended status words and alarmwords102
Special conditions103
Extreme environments103
Galvanic Isolation (PELV)103
UL Standard104
General technical data105
Technical data, mains supply 1 x 220 - 240 V/3 x 200-240V110
Technical data, mains supply 3 x 380 - 480 V111
Available literature112
Supplied with the unit112
33
98
2 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
VLT 2800
Instruction Manual
Software version: 3.1x
This Design Guide can be used for all VLT 2800 series adjustable frequency drives with software version 3.1x.
The software version number is indicated in parameter 640.
Warning
It can be extremely dangerous to touch the electrical parts, even when the line supply has been disconnected.
Also ensure that other voltage inputs are disconnected from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been removed before servicing the drive.
Introduction to VLT 2800
MG.27.A2.22 - VLT® is a registered Danfoss trademark 3
VLT® 2800 Series
High voltage warning
The voltage of the frequency converter is
dangerous whenever the converter is connected to mains. Incorrect fitting of the
motor or frequency converter may cause
damage to the equipment, serious injury
or death. Consequently, it is essential to
comply with the instructions in this manual
as well as local and national rules and
safety regulations.
The Protective Extra Low Voltage (PELV)
requirements stated in IEC 61800-5-1 are
not fulfilled at altitudes above 2000 m
(6562 ft.). For 200V frequency converters
the requirements are not fulfilled at altitudes above 5000 m (16 404 ft.). Please
contact Danfoss Drives for further information.
These rules concern your safety.
1.The adjustable frequency drive must be disconnected from AC line if repair work is to be
carried out. Ensure that the line supply has
been disconnected and that the prescribed
time has passed before removing motor and
AC line plugs.
2.The [STOP/RESET] key on the control panel
of the adjustable frequency drive
disconnect the equipment from line power
and is therefore
switch.
3.The unit must be properly grounded, the user
must be protected against the supply voltage,
and the motor must be protected against
overloading in accordance with prevailing national and local regulations.
4.The ground leakage currents are higher than
3.5 mA.
5.Protection against motor overload is not included in the factory setting. If this function is
required, set parameter 128 Motor thermal
protection to data value ETR trip or data value
ETR warning. For the North American market:
The ETR functions provide overload protec-
not to be used as a safety
does not
tion of the motor, class 20, in accordance with
NEC.
6.Do
7.Note that the adjustable frequency drive has
Warning against unintended start
1.The motor can be brought to a stop by means
2.While parameters are being changed, the
3.A motor that has been stopped may start if
not remove either the plugs for the motor
or line supply while the adjustable frequency
drive is connected to line power. Ensure that
the line supply has been disconnected and
that the prescribed time has passed before
removing motor and AC line plugs.
more voltage inputs than L1, L2 and L3 when
the DC bus terminals are used. Check that all
voltage inputs are disconnected and that the
prescribed time has passed before repair
work is commenced.
of digital commands, bus commands, references or a local stop, while the frequency
converter is connected to mains. If personal
safety considerations make it necessary to
ensure that no unintended start occurs,
stop functions are not sufficient.
motor may start. Consequently,
[STOP/RESET] must always be activated,
following which data can be modified.
faults occur in the electronics of the frequency converter, or if a temporary overload or a
fault in the supply mains or the motor connection ceases.
the stop key
these
4 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Motor overload protection
The electronic thermal relay (ETR) in UL listed VLTs
provides Class 20 motor overload protection in accordance with the NEC in single motor applications
when parameter 128 is set for "ETR TRIP" and pa-
Warning
It can be extremely dangerous to touch the electrical parts, even when the line supply has been disconnected.
Also ensure that other voltage inputs are disconnected from load sharing through the DC bus.
Wait at least 4 minutes after the input power has been removed before servicing the drive.
rameter 105 Motor current is set for the rated motor
current.
Introduction to VLT 2800
MG.27.A2.22 - VLT® is a registered Danfoss trademark 5
VLT® 2800 Series
Mechanical dimensions
The drawings below describe the mechanical dimensions. All dimensions are given in mm.
NOTE
Please note that all filter options must be
vertically mounted.
VLT 2803-2815 200-240 Volt
VLT 2805-2815 380-480 Volt
The drawing below gives the mechanical dimensions
of VLT 2822 (3 HP) 200-240 Volts and VLT 2822-2840
(3 - 5 HP) 380-480 Volts. All dimensions are in inches.
VLT 2822 200-240 Volt
VLT 2822-2840 380-480 Volt
VLT 2822 220 - 240 V, PD2
VLT 2840 200 - 240 Volt
VLT 2855-2875 380 - 480 Volt
VLT 2840 220 - 240 V, PD2
VLT 2880-82 380 - 480 V
6 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Motor coils (195N3110)
RFI 1B filter (195N3103)
Terminal cover
The drawing below gives the dimensions for NEMA 1
terminal covers for VLT 2803-2875.
Dimension 'a' depends on the unit type.
Installation
IP 21 solution
MG.27.A2.22 - VLT® is a registered Danfoss trademark 7
8 MG.27.A2.22 - VLT® is a registered Danfoss trademark
192H4720
VLT® 2800 Series
Installation
192H4893
MG.27.A2.22 - VLT® is a registered Danfoss trademark 9
VLT® 2800 Series
Mechanical installation
The adjustable frequency drive is cooled by air circulation. For proper cooling, allow a minimum of 4 inches
(100 mm) of open space above and below the unit. To
protect the unit from overheating, ensure that both the
ambient temperature and the 24-hour average temperature are not exceeded. The maximum temperature and 24-hour average are listed in Generaltechnical data in this manual. If the ambient temperature is in the range of 113°F - 131°F (45°C - 55°C),
derating of the drive must be carried out. See Deratingfor ambient temperature in this manual. The service life
of the unit will be reduced without applicable derating.
The requirements that apply to enclosures
and remote mounting must be complied
with to avoid serious injury or equipment
damage, especially when installing large
units.
Enclosures
In the USA and some other countries, a NEMA 1 terminal cover enclosing terminal connectors is required
if the drive is not installed within another enclosure.
Side-by-side
All VLT 2800 units can be installed side-by-side and in
any position, as the units do not require ventilation on
the side.
Spacing for mechanical installation
All units require a minimum of 4 in of air from other
components above and below the enclosure.
NOTE
With the IP 21 solution all units require a
minimum of 4 in air on each side. This
means that side-by-side mounting is
allowed.
not
10 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
General information about electrical installation
High voltage warning
The voltage of the adjustable frequency
drive is dangerous whenever the drive is
connected to the AC line. Incorrect installation of the motor or drive may cause
damage to the equipment, serious injury
or death. Comply with the safety instructions in this manual as well as local and
national rules and safety regulations.
Touching electrical parts may be fatal even after the equipment has been disconnected from the AC line. Wait at least
4 minutes for current to dissipate.
NOTE
It is the responsibility of the user or installer to ensure correct grounding and protection in accordance with national and
local standards.
Earthing
Comply with the following at installation:
•Safety earthing: The drive has a high leakage
current and must be earthed properly for
safety. Follow all local safety regulations.
•High frequency earthing: Keep earthing connections as short as possible.
Connect all earthing SYSTEMs to ensure the lowest
possible conductor impedance. The lowest possible
conductor impedance is achieved by keeping the conductor as short as possible and by grounding with the
greatest possible surface area. If multiple drives are
installed in a cabinet, the cabinet backplate, which
must be made of metal, should be used as a joint earth
reference plate. The drives must be fitted to the backplate at the lowest possible impedance.
To achieve low impedance, connect the drive to the
backplate with the drive fastening bolts. Remove all
paint from the contact points.
High voltage test
A high voltage test can be performed by short-circuiting terminals U, V, W, L1, L2 and L3, and applying a
max. of 2,160 V DC in 1 sec. between this short-circuit
and terminal 95.
Do not perform a high voltage test between the control terminals and the chassis, because the voltage potential of the
control card cannot exceed approximately
100 volts with respect to chassis due to a
voltage limiting circuitry.
The terminals are protected against direct
hazardous access through barriers.
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 11
EMC-correct electrical installation
General points to be observed to ensure EMC-correct
electrical installation.
Use only shielded/armoured motor cables
-
and shielded/armoured control cables.
Connect the screen to ground at both ends.
-
Avoid installation with twisted shield ends
-
(pigtails), since this ruins the shielding effect
at high frequencies. Use cable clamps instead.
VLT® 2800 Series
It is important to ensure good electrical con-
-
tact from the installation plate through the
installation screws to the metal cabinet of the
variable frequency drive.
Use starwashers and galvanically conductive
-
installation plates.
Do not use unshielded/unarmoured motor
-
cables in the installation cabinets.
The illustration below shows EMC-correct electrical installation, in which the variable frequency drive has
been fitted in an installation cabinet and connected to
a PLC.
12 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Grounding of shielded/armored control cables
In general, control cables must be shielded/armored,
and the shield must be connected to the unit's metal
cabinet with a cable clamp at each end.
The drawing below shows the correct way to perform
the grounding, and what to do when in doubt.
1.
Correct grounding
Control cables and cables for serial communication must be attached with cable clamps
at both ends to ensure the maximum possible
electrical contact.
2.
Incorrect grounding
Do not use twisted shield ends that are plaited together (pigtails), as these increase
shield impedance at higher frequencies.
3.
Protection with respect to ground potential between the PLC and VLT
If the ground potential between the VLT adjustable frequency drive and the PLC, etc. is
different, electric noise may occur that will
disturb the whole system. This problem can
be solved by fitting an equalizing cable next
to the control cable. Minimum cable crosssection: 0.025 in
4.
In the event of a 50/60 Hz ground loop
2
[16 mm2].
If very long control cables are used, 50/60 Hz
ground loops can arise, and these can interfere with the whole system. This problem is
resolved by attaching one end of the shield to
the ground via a 100 nF capacitor (short pin
length).
VLT® 2800 Series
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 13
Diagram
* Integrated 1A RFI filter and brake is an option.
** VLT 2803-2815 200-240 V is not supplied with intermediate circuit coils.
VLT® 2800 Series
14 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Electrical installation
See also the section Brake Connection.
VLT® 2800 Series
Installn
Installation
VLT 2822 200-240 V, 2822-2840 380-480 V
VLT 2803-2815 200-240 V, 2805-2815 380-480 V
MG.27.A2.22 - VLT® is a registered Danfoss trademark 15
VLT® 2800 Series
VLT 2840 200-240 V, VLT 2822 PD2, 2855-2875
380-480 V
VLT 2880-2882 380-480 V, VLT 2840 PD2
Please note that the units will be supplied with two
bottom plates, one for metric glands and one for conduits.
16 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Safety clamp
To maintain the galvanic isolation (PELV) between the
control terminals and high-voltage terminals, the accompanying safety clamp must be attached to VLT
2803-2815, 200-240 V, and VLT 2805-2815, 380-480
V. Attach the safety clamp to the strain relief plate with
the two screws provided.
For all unit types, external prefuses must be fitted in
the line supply to the adjustable frequency drive. For
UL/cUL applications with a line voltage of 200-240
Volt, use prefuses type Bussmann KTN-R (200-240
Volt) or Ferraz Shawmut type ATMR (max. 30A). For
UL/cUL applications with a line voltage of 380-480
Volt, use prefuses type Bussmann KTS-R (380-480
Volt).
Prefuses for UL application /cUL
Prefuses
Alternative fuses 380-500 V drives
VLT 2800Bussmann
All drives that are equipped with an RFI
filter cannot be connected to a grounded
No.N
(L2)L1(L1) (L3)
L2L1L3
No.95Ground connection
AC line voltage 3 x 220-240 V
DELTA or IT mains/AC line system.
No.91 92 93 AC line voltage 3 x 380-480 V
NOTE
Check that the AC voltage matches the
L1 L2 L3
No.95Ground connection
voltage rating of the drive. The drive rating
is on the drive nameplate. See Technicaldata in this manual for correct dimensioning of cable cross-section.
380-460 Volt units with RFI-filters may
not be connected to AC line supplies in
which the voltage between phase and
For single phase 220-240 Volts input, attach the neutral wire to terminal N
to terminal L1
No.N
(L2)L1(L1) (L3)
(L1)
.
and connect the phase wire
(L2)
AC line voltage 1 x 220-240 V
NL1
ground is more than 300 Volts. Please
note that for the AC line for IT and the delta
ground the AC line voltage can exceed
300 Volts between phase and ground.
Units with type code R5 can be connected
No.95Ground connection
MG.27.A2.22 - VLT® is a registered Danfoss trademark 17
to mains supplies with up to 400 V between phase and ground.
See Technical data for correct dimensioning of cable
cross-section.
Motor connection
Connect the motor to terminals 96, 97, 98. Connect
ground to terminal 99.
96 97 98 Motor voltage 0-100% of line
No.
voltage.
UVW
U1W2V1U2W1V26 wires out of motor, Delta-con-
U1 V1 W16 wires out of motor, Star-con-
3 wires of motor
nected
nected
U2, V2, W2 to be interconnected separately (optional terminal block)
VLT® 2800 Series
No. PE Ground connection
See Technical data for correct dimensioning of cable
cross-section.
18 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
All types of three-phase asynchronous standard motors can be connected to an adjustable frequency
drive. Normally, small motors are star-connected
(230/400 V, ǻ/ Y), while large motors are delta-con-
nected (400/690 V, ǻ/ Y). The correct connection
mode and voltage can be read from the motor nameplate.
NOTE
In motors without phase insulation paper,
an LC filter should be fitted on the output
of the adjustable frequency drive.
Direction of motor rotation
To change the direction of motor rotation, switch any
two phases at the drive output or at motor terminals.
Motor thermal protection
The electronic thermal relay in UL approved variable
frequency drives has received the UL approval for single motor protection, when parameter 128 Motor ther-mal protection has been set for ETR Trip and
parameter 105 Motor current, I
has been program-
M, N
med to the rated motor current (see motor nameplate).
The adjustable frequency drive is able to control several motors connected in parallel. If the motors are to
have different rpm values, use motors with different
rated rpm values. Motor rpm is changed simultaneously, which means that the ratio between the rated
rpm values is maintained across the range. The total
current consumption of the motors is not to exceed the
maximum rated output current I
for the adjustable
INV
frequency drive.
Problems may arise at the start and at low rpm values
if the motor sizes are widely different. This is because
the small motors' relatively high ohmic resistance in
the stator calls for a higher voltage at the start and at
low rpm values.
In systems with motors connected in parallel, the electronic thermal relay (ETR) of the adjustable frequency
drive cannot be used as motor protection for the individual motor. For this reason, further motor protection
must be used, such as thermistors in each motor or an
individual thermal relay, for example (circuit breakers
are not a suitable means of protection).
NOTE
Parameter 107 Automatic motor adapta-
tion, AMT cannot be used when motors
are connected in parallel. Parameter 101
Torque characteristic must be set to Spe-
cial motor characteristics [8] when motors
are connected in parallel.
Motor cables
See Technical data for correct dimensioning of motor
cable cross-section and length. Always comply with
national and local regulations on cable cross-section.
Installation
Parallel connection of motors
NOTE
If an unshielded/unarmored cable is used,
some EMC requirements are not com-
plied with, see EMC test results in the De-
sign Guide.
If the EMC specifications regarding emissions are to
be complied with, the motor cable must be shielded/
armored unless otherwise stated for the RFI filter in
question. It is important to keep the motor cable as
short as possible so as to reduce the noise level and
leakage currents to a minimum. The motor cable shield
must be connected to the metal cabinets of the adjust-
MG.27.A2.22 - VLT® is a registered Danfoss trademark 19
VLT® 2800 Series
able frequency drive and the motor. The shield connections are to be made with the largest possible
surface area (cable clamp). This is enabled by different
installation devices in different adjustable frequency
drives. Connecting with twisted shield ends (pigtails)
is to be avoided, as these spoil the shielding effect at
high frequencies. If it is necessary to break the shield
to install a motor isolator or motor relay. The shield
must be continued at the lowest possible HF impedance.
Brake connection
NOTE
Voltages up to 850 VDC occur on the ter-
minals.
No.
81 82 Brake resistor
R- R+
terminals
Connect the brake resistor wiring to drive terminals 81
and 82. The connection cable to the brake resistor
must be shielded/armored. Connect the shield to both
the ground of the drive and the brake resistor by means
of cable clamps. Dimension the cross-section of the
brake cable to match the brake torque.
Ground connection
Since the leakage currents to ground may be higher
than 3.5 mA, the adjustable frequency drive must always be connected to ground in accordance with applicable national and local regulations. To ensure that
the ground cable has good mechanical connection to
terminal 95, the cable cross section must be a mini-
2
mum 7 AWG (10 mm
). To improve protection even
further, a Recidual Current Device (RCD) can be fitted
to ensure that the adjustable frequency drive cuts out
when the leakage currents get too high. Also see RCD
Application note MN.90.GX.02.
Load sharing
Load sharing provides the facility to connect several
frequency converters' DC intermediate circuits. This
requires that the installation is extended using extra
fuses and AC coils (see drawing below). For load sharing parameter 400 Brake function must be set to Loadsharing [5].
Use 6.3 mm Faston Plugs for DC (Load Sharing).
Contact Danfoss or see instructions no. MI.50.NX.02
for further information.
8889Loadsharing
No.
-+
20 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Note that voltage levels of up to 850 V DC
may occur between terminals 88 and 89.
VLT® 2800 Series
Tightening Torque, Power Terminals
Power and ground terminals must be tightened with
the following torques:
VLT
28032875
28802882, 2840
PD2
Calculation of brake resistance
In lifting/lowering applications you need to be able to
control an electromagnetic brake. The brake is controlled using a relay output or digital output (terminal
46). The output must be kept closed (voltage-free) for
the period of time during which the variable frequency
drive is not able to 'support' the motor, for example due
to the load being too great. Select Mechanical brakecontrol in parameter 323 or 341 for applications with
an electromagnetic brake.
When the output frequency exceeds the brake cut out
value set in par. 138, the brake is released if the motor
current exceeds the preset value in parameter 140.
When stopping the brake is engaged when the output
frequency is less than the brake engaging frequency,
which is set in par. 139.
If the variable frequency drive is placed at alarm status
or in an overvoltage situation the mechanical brake is
cut in immediately.
TerminalsTorque [Nm]
Power AC line brake0.5-0.6
Ground2-3
Power AC line brake1.2-1.5
Ground2-3
Installation
NOTE
This application is only for lifting/lowering
without a counterbalance.
Access to control terminals
All control terminals are located underneath the protective plate on the front of the adjustable frequency
drive. Remove the protective plate by sliding it downwards (see drawing).
Electrical installation, control circuitry
NOTE
Using unshielded/unarmored cable may
not comply with some EMI/RFI requirements.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 21
Control wires must be shielded/armored. Connect the
shield to the drive chassis with a clamp. Normally, the
VLT® 2800 Series
shield must also be connected to the chassis of the
controlling device. (See the instructions for the specific
device.) In analog signals or connections using very
long wires, 50/60 Hz ground loops may occur because
of noise transmitted from the AC line. It may be necessary to break the shield and insert a 100 ȝF capacitor between the shield and the chassis.
Tightening torques, control cables
Control wires must be connected with a tightening torque of 0.22-0.25 Nm.
Electrical installation, control terminals
See section entitled Grounding of shielded/armored
control cables in the VLT 2800 Design Guide for the
correct termination of control cables.
22 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
No.Function
01-03Relay outputs 01-03 can be used for
indicating status and alarms/warnings.
1224 V DC voltage supply.
18-33Digital inputs.
20, 55Common frame for input
and output terminals.
42Analog output for displaying frequency,
reference, current or torque.
46
Digital output for displaying status,
1
warnings or alarms, as well as
frequency output.
50+10 V DC supply
voltage for potentiometer or thermistor.
53Analogue voltage input 0-10 V DC.
60Analogue current input 0/4 - 20 mA.
67
+ 5 V DC supply voltage
1
to Profibus.
68, 691RS-485, Serial communication.
70
Frame for terminals 67, 68 and 69.
1
Normally, this terminal is not to be used.
1. The terminals are not valid for DeviceNet/CANopen.
See also the DeviceNet manual, MG.90.BX.YY for further details.
Profibus DIP switches setting
The dip switch is only on the control card with Profibus
DP communication. The switch position shown is the
factory setting. Switches 1 and 2 are used as cable
termination for the RS-485 interface. If the adjustable
frequency drive is located as the first or last (or only)
unit in the bus system, switches 1 and 2 must be ON.
On the remaining adjustable frequency drives,
switches 1 and 2 must be OFF. Switches 3 and 4 are
not applied.
VLT Software Dialog
Connection to terminals 68-70 or
Sub D:
PIN 3 GND
-
PIN 8 P-RS 485
-
PIN 9 N-RS 485
-
Sub D plug
Installation
Relay connection
See parameter 323 Relay output for programming of
relay output.
01 - 02 1 - 2 make (normally open)
Nr.
01 - 03
1 - 3 break (normally closed)
NOTE
Please note that the cable jacket for the
relay must cover the first row of control
card terminals - otherwise the galvanic
isolation (PELV) cannot be maintained.
Max. cable diameter: 4 mm. See drawing.
An LCP 2 control unit can be connected to the Sub D
plug on the control card. Ordering number: 175N0131.
The LCP control unit with ordering number 175Z0401
is not to be connected.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 23
VLT® 2800 Series
Connection examples
Start/stop
Start/stop using terminal 18 and coasting stop using
terminal 27.
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coasting stop inver-ted [2]
For Precise start/stop the following settings are made:
Par. 302 Digital input = Precise start/stop [27]
Par. 304 Digital input = Coasting stop inver-ted [2]
Speed up/slow down
Speed up/slow down using terminals 29/33.
Par. 302 Digital input = Start [7]
Par. 303 Digital input = Freeze reference [14]
Par. 305 Digital input = Speed up [16]
Par. 307 Digital input = Slow down [17]
Potentiometer reference
Voltage reference via a potentiometer.
Pulse start/stop
Pulse start using terminal 18 and pulse stop using terminal 19. In addition, the jog frequency is activated via
terminal 29.
Par. 302 Digital input = Pulse start [8]
Par. 303 Digital input = Stop inverted [6]
Par. 304 Digital input = Coasting stop inver-ted [2]
Par. 305 Digital input = Jog [13]
Par. 308 Analog input = Reference [1]
Par. 309 Terminal 53, min. scaling = 0 Volt
Par. 310 Terminal 53, max. scaling = 10 Volt
Connection of a 2-wire transmitter
Connection of a 2-wire transmitter as feedback to terminal 60.
24 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Par. 314 Analog input = Feedback [2]
Par. 315 Terminal 60, min. scaling = 4 mA
Par. 316 Terminal 60, max. scaling = 20 mA
VLT® 2800 Series
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 25
VLT® 2800 Series
Control unit
On the front of the variable frequency drive there is a
control panel.
The control panel is divided into five functional groups:
1.Status LED
2.Keys for changing parameters and shifting
display function.
3.LEDs.
4.Keys for local operation.
All displays of data are in the form of a six-digit LED
display capable of showing one item of operating data
continuously during normal operation. As a supplement to the display, there are three LEDs for indication
of electrical connection (ON), warning (WARNING)
and alarm (ALARM). Most of the variable frequency
drive's parameter Setups can be changed immediately
via the control panel, unless this function has been
programmed as Locked [1] via parameter 018 Lock fordata changes.
The [CHANGE DATA] key is also used for confirming
a change of parameter settings.
[+] / [-] are used for selecting parameters and for
changing parameter values.
These keys are also used in Display mode for selecting
the display of an operating value.
The [QUICK MENU] + [+] keys must be pressed at the
same time to give access to all parameters. See Menu
mode.
[STOP/RESET] is used for stopping the connected
motor or for resetting the variable frequency drive after
a trip.
Can be selected as Active [1] or Not active [0] via parameter 014 Local stop/reset. In Display mode, the
display will flash if the stop function is activated.
NOTE
If the [STOP/RESET] key is set at Not active [0] in parameter 014 Local stop/reset,and there is no stop command via the
digital inputs or serial communication, the
motor can only be stopped by disconnecting the electrical voltage to the variable
frequency drive.
[START] is used for starting the variable frequency
drive. It is always active, but the [START] key cannot
override a stop command.
Manual initialization
To manually initialize the adjustable frequency drive to
factory default settings, first disconnect AC line voltage. Hold the [QUICK MENU] and [+] and [CHANGE
DATA] keys down while simultaneously reconnecting
the AC line voltage. Release the keys. The drive has
now been programmed for factory settings.
Control keys
[QUICK MENU] allows access to the parameters used
for the Quick menu.
The[QUICK MENU] key is also used if a change to a
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
[CHANGE DATA] is used for changing a setting.
26 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Display readout states
Display mode
VLT® 2800 Series
In normal operation, one item of operating data can be
displayed continuously at the operator's discretion. By
means of the [+/-] keys, the following options can be
selected in Display mode:
Output frequency [Hz]
-
Output current [A]
-
Output voltage [V]
-
Intermediate circuit voltage [V]
-
Output power [kW]
-
Scaled output frequency f
-
x p008
out
Menu mode
In order to enter the Menu mode, [QUICK MENU] + [+]
must be activated at the same time.
In Menu mode, most of the adjustable frequency drive
parameters can be changed. Scroll through the parameters using the [+/-] keys. While scrolling in the
Menu mode proceeds, the parameter number will
flash.
The display shows that the setting in parameter 102
Motor power P
is 0.75. In order to change the value
M,N
of 0.75, [CHANGE DATA] must first be activated; the
parameter value can then be changed using the [+/-]
keys.
If a given parameter display shows three dots to the
right, it means that the parameter value has more than
three digits. In order to see the entire value, activate
[CHANGE DATA].
The display shows that in parameter 128 Motor thermalprotection, the selection made is Thermistor trip [2].
Quick menu
Using the [QUICK MENU] key, it is possible to access
the 12 most important parameters of the adjustable
frequency drive. After programming, the adjustable
frequency drive is, in most cases, ready for operation.
When the [QUICK MENU] key is activated in Display
mode, the Quick menu starts. Scroll through the quick
menu using the [+/-] keys and change the data values
by first pressing [CHANGE DATA] and then changing
the parameter value with the [+/-] keys.
TheQuick menu parameters are:
•
Par. 100 Configuration
•
Par. 101 Torque characteristic
•
Par. 102 Motor power P
•
Par. 103 Motor voltage U
•
Par. 104 Motor frequency f
•
Par. 105 Motor current I
•
Par. 106 Rated motor speed n
•
Par. 107 Automatic motor adaptation
•
Par. 202 Output frequency high limit f
•
Par. 203 Reference range
•
Par. 204 Minimum reference Ref
•
Par. 205 Maximum reference Ref
•
Par. 207 Ramp-up time
•
Par. 208 Ramp-down time
•
Par. 002 Local/remote operation
•
Par. 003 Local reference
M,N
M,N
M,N
M,N
M,N
MAX
MIN
MAX
Parameter 102 - 106 can be read out from the motor's
nameplate.
Automatic motor tuning
Automatic motor tuning (AMT) is performed as follows:
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 27
1.
In parameter 107 Automatic motor tuning, select data value [2]. "107" will now flash, and
"2" will not flash.
2.AMT is activated by pressing start. "107" will
now flash and dashes will move from left to
right in the data value field.
3.When "107" appears once more with the data
value [0], AMT is complete. Press [STOP/
RESET] to save the motor data.
4."107" will then continue to flash with the data
value [0]. You can now proceed.
NOTE
VLT 2880-2882 do not have AMT function.
VLT® 2800 Series
28 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Loading...
+ 94 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.