Grieve Corporation VLT 2803-2815 Installation Manual

Instruction Manual
VLT® 2800
VLT® 2800 Series
Introduction to VLT 2800
Software version 3
High voltage warning 4
These rules concern your safety. 4
Warning against unintended start 4
Installation
Mechanical dimensions 6
Mechanical installation 10
General information about electrical installation 11
EMC-correct electrical installation 12
Grounding of shielded/armored control cables 13
Diagram 14
Electrical installation 15
Safety clamp 17
Prefuses 17
AC line connection 17
Motor connection 18
Direction of motor rotation 19
Motor thermal protection 19
Parallel connection of motors 19
Motor cables 19
Brake connection 20
Ground connection 20
Load sharing 20
Tightening Torque, Power Terminals 21
Calculation of brake resistance 21
Access to control terminals 21
Electrical installation, control circuitry 21
Tightening torques, control cables 22
Electrical installation, control terminals 22
Relay connection 23
VLT Software Dialog 23
Connection examples 24
Control unit 26
Manual initialization 26
Automatic motor tuning 27
Display readout 29
Hand Auto 29
Warnings/alarms 30
Special conditions 31
Temperature-related switching frequency 31
Derating for long motor cables 31
3
6
MG.27.A2.22 - VLT® is a registered Danfoss trademark 1
VLT® 2800 Series
VLT 2800 start-up 31
Programming
Operation & Display 33
Load and Motor 41
References & Limits 52
Inputs and Outputs 59
Special functions 69
Enhanced Sleep Mode 79
Serial communication 84
Technical functions 93
All about VLT 2800
Warnings/alarm messages 98
Warning words, extended status words and alarmwords 102
Special conditions 103
Extreme environments 103
Galvanic Isolation (PELV) 103
UL Standard 104
General technical data 105
Technical data, mains supply 1 x 220 - 240 V/3 x 200-240V 110
Technical data, mains supply 3 x 380 - 480 V 111
Available literature 112
Supplied with the unit 112
33
98
2 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
VLT 2800
Instruction Manual
Software version: 3.1x
This Design Guide can be used for all VLT 2800 series adjustable frequency drives with software version 3.1x. The software version number is indicated in parameter 640.
Warning
It can be extremely dangerous to touch the electrical parts, even when the line supply has been disconnected. Also ensure that other voltage inputs are disconnected from load sharing through the DC bus. Wait at least 4 minutes after the input power has been removed before servicing the drive.
Introduction to VLT 2800
MG.27.A2.22 - VLT® is a registered Danfoss trademark 3
VLT® 2800 Series
High voltage warning
The voltage of the frequency converter is dangerous whenever the converter is con­nected to mains. Incorrect fitting of the motor or frequency converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this manual as well as local and national rules and safety regulations.
The Protective Extra Low Voltage (PELV) requirements stated in IEC 61800-5-1 are not fulfilled at altitudes above 2000 m (6562 ft.). For 200V frequency converters the requirements are not fulfilled at alti­tudes above 5000 m (16 404 ft.). Please contact Danfoss Drives for further infor­mation.
These rules concern your safety.
1. The adjustable frequency drive must be dis­connected from AC line if repair work is to be carried out. Ensure that the line supply has been disconnected and that the prescribed time has passed before removing motor and AC line plugs.
2. The [STOP/RESET] key on the control panel of the adjustable frequency drive disconnect the equipment from line power and is therefore switch.
3. The unit must be properly grounded, the user must be protected against the supply voltage, and the motor must be protected against overloading in accordance with prevailing na­tional and local regulations.
4. The ground leakage currents are higher than
3.5 mA.
5. Protection against motor overload is not in­cluded in the factory setting. If this function is required, set parameter 128 Motor thermal
protection to data value ETR trip or data value ETR warning. For the North American market:
The ETR functions provide overload protec-
not to be used as a safety
does not
tion of the motor, class 20, in accordance with NEC.
6. Do
7. Note that the adjustable frequency drive has
Warning against unintended start
1. The motor can be brought to a stop by means
2. While parameters are being changed, the
3. A motor that has been stopped may start if
not remove either the plugs for the motor or line supply while the adjustable frequency drive is connected to line power. Ensure that the line supply has been disconnected and that the prescribed time has passed before removing motor and AC line plugs.
more voltage inputs than L1, L2 and L3 when the DC bus terminals are used. Check that all voltage inputs are disconnected and that the prescribed time has passed before repair work is commenced.
of digital commands, bus commands, refer­ences or a local stop, while the frequency converter is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, stop functions are not sufficient.
motor may start. Consequently, [STOP/RESET] must always be activated, following which data can be modified.
faults occur in the electronics of the frequen­cy converter, or if a temporary overload or a fault in the supply mains or the motor con­nection ceases.
the stop key
these
4 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Motor overload protection
The electronic thermal relay (ETR) in UL listed VLTs provides Class 20 motor overload protection in ac­cordance with the NEC in single motor applications when parameter 128 is set for "ETR TRIP" and pa-
Warning
It can be extremely dangerous to touch the electrical parts, even when the line supply has been disconnected. Also ensure that other voltage inputs are disconnected from load sharing through the DC bus. Wait at least 4 minutes after the input power has been removed before servicing the drive.
rameter 105 Motor current is set for the rated motor current.
Introduction to VLT 2800
MG.27.A2.22 - VLT® is a registered Danfoss trademark 5
VLT® 2800 Series
Mechanical dimensions
The drawings below describe the mechanical dimen­sions. All dimensions are given in mm.
NOTE
Please note that all filter options must be vertically mounted.
VLT 2803-2815 200-240 Volt VLT 2805-2815 380-480 Volt
The drawing below gives the mechanical dimensions of VLT 2822 (3 HP) 200-240 Volts and VLT 2822-2840 (3 - 5 HP) 380-480 Volts. All dimensions are in inches.
VLT 2822 200-240 Volt VLT 2822-2840 380-480 Volt
VLT 2822 220 - 240 V, PD2 VLT 2840 200 - 240 Volt VLT 2855-2875 380 - 480 Volt
VLT 2840 220 - 240 V, PD2 VLT 2880-82 380 - 480 V
6 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Motor coils (195N3110)
RFI 1B filter (195N3103)
Terminal cover
The drawing below gives the dimensions for NEMA 1 terminal covers for VLT 2803-2875. Dimension 'a' depends on the unit type.
Installation
IP 21 solution
MG.27.A2.22 - VLT® is a registered Danfoss trademark 7
VLT® 2800 Series
Dimensions
Type Code number A B C VLT 2803-2815 200-240 V, VLT 2805-2815 380-480 V 195N2118 47 80 170 VLT 2822 200-240 V, VLT 2822-2840 380-480 V 195N2119 47 95 170 VLT 2840 200-240 V, VLT 2822 PD2, TR1 2855-2875 380-480 V TR1 2880-2882 380-480 V, VLT 2840 PD2 195N2126 47 205 245
EMC filter for long motor cables
195N2120 47 145 170
192H4719
8 MG.27.A2.22 - VLT® is a registered Danfoss trademark
192H4720
VLT® 2800 Series
Installation
192H4893
MG.27.A2.22 - VLT® is a registered Danfoss trademark 9
VLT® 2800 Series
Mechanical installation
The adjustable frequency drive is cooled by air circu­lation. For proper cooling, allow a minimum of 4 inches (100 mm) of open space above and below the unit. To protect the unit from overheating, ensure that both the ambient temperature and the 24-hour average tem­perature are not exceeded. The maximum tempera­ture and 24-hour average are listed in General technical data in this manual. If the ambient tempera­ture is in the range of 113°F - 131°F (45°C - 55°C), derating of the drive must be carried out. See Derating for ambient temperature in this manual. The service life of the unit will be reduced without applicable derating.
The requirements that apply to enclosures and remote mounting must be complied with to avoid serious injury or equipment damage, especially when installing large units.
Enclosures
In the USA and some other countries, a NEMA 1 ter­minal cover enclosing terminal connectors is required if the drive is not installed within another enclosure.
Side-by-side
All VLT 2800 units can be installed side-by-side and in any position, as the units do not require ventilation on the side.
Spacing for mechanical installation
All units require a minimum of 4 in of air from other components above and below the enclosure.
NOTE
With the IP 21 solution all units require a minimum of 4 in air on each side. This means that side-by-side mounting is allowed.
not
10 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
General information about electrical installation
High voltage warning
The voltage of the adjustable frequency drive is dangerous whenever the drive is connected to the AC line. Incorrect instal­lation of the motor or drive may cause damage to the equipment, serious injury or death. Comply with the safety instruc­tions in this manual as well as local and national rules and safety regulations. Touching electrical parts may be fatal ­even after the equipment has been dis­connected from the AC line. Wait at least 4 minutes for current to dissipate.
NOTE
It is the responsibility of the user or instal­ler to ensure correct grounding and pro­tection in accordance with national and local standards.
Earthing
Comply with the following at installation:
Safety earthing: The drive has a high leakage current and must be earthed properly for safety. Follow all local safety regulations.
High frequency earthing: Keep earthing con­nections as short as possible.
Connect all earthing SYSTEMs to ensure the lowest possible conductor impedance. The lowest possible conductor impedance is achieved by keeping the con­ductor as short as possible and by grounding with the greatest possible surface area. If multiple drives are installed in a cabinet, the cabinet backplate, which must be made of metal, should be used as a joint earth reference plate. The drives must be fitted to the back­plate at the lowest possible impedance.
To achieve low impedance, connect the drive to the backplate with the drive fastening bolts. Remove all paint from the contact points.
High voltage test
A high voltage test can be performed by short-circuit­ing terminals U, V, W, L1, L2 and L3, and applying a max. of 2,160 V DC in 1 sec. between this short-circuit and terminal 95.
Do not perform a high voltage test be­tween the control terminals and the chas­sis, because the voltage potential of the control card cannot exceed approximately 100 volts with respect to chassis due to a voltage limiting circuitry. The terminals are protected against direct hazardous access through barriers.
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 11
EMC-correct electrical installation
General points to be observed to ensure EMC-correct electrical installation.
Use only shielded/armoured motor cables
-
and shielded/armoured control cables.
Connect the screen to ground at both ends.
-
Avoid installation with twisted shield ends
-
(pigtails), since this ruins the shielding effect at high frequencies. Use cable clamps in­stead.
VLT® 2800 Series
It is important to ensure good electrical con-
-
tact from the installation plate through the installation screws to the metal cabinet of the variable frequency drive.
Use starwashers and galvanically conductive
-
installation plates.
Do not use unshielded/unarmoured motor
-
cables in the installation cabinets.
The illustration below shows EMC-correct electrical in­stallation, in which the variable frequency drive has been fitted in an installation cabinet and connected to a PLC.
12 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Grounding of shielded/armored control cables
In general, control cables must be shielded/armored, and the shield must be connected to the unit's metal cabinet with a cable clamp at each end.
The drawing below shows the correct way to perform the grounding, and what to do when in doubt.
1.
Correct grounding
Control cables and cables for serial commu­nication must be attached with cable clamps at both ends to ensure the maximum possible electrical contact.
2.
Incorrect grounding
Do not use twisted shield ends that are plai­ted together (pigtails), as these increase shield impedance at higher frequencies.
3.
Protection with respect to ground poten­tial between the PLC and VLT
If the ground potential between the VLT ad­justable frequency drive and the PLC, etc. is different, electric noise may occur that will disturb the whole system. This problem can be solved by fitting an equalizing cable next to the control cable. Minimum cable cross­section: 0.025 in
4.
In the event of a 50/60 Hz ground loop
2
[16 mm2].
If very long control cables are used, 50/60 Hz ground loops can arise, and these can inter­fere with the whole system. This problem is resolved by attaching one end of the shield to the ground via a 100 nF capacitor (short pin length).
VLT® 2800 Series
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 13
Diagram
* Integrated 1A RFI filter and brake is an option. ** VLT 2803-2815 200-240 V is not supplied with in­termediate circuit coils.
VLT® 2800 Series
14 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Electrical installation
See also the section Brake Connection.
VLT® 2800 Series
Install n
Installation
VLT 2822 200-240 V, 2822-2840 380-480 V
VLT 2803-2815 200-240 V, 2805-2815 380-480 V
MG.27.A2.22 - VLT® is a registered Danfoss trademark 15
VLT® 2800 Series
VLT 2840 200-240 V, VLT 2822 PD2, 2855-2875 380-480 V
VLT 2880-2882 380-480 V, VLT 2840 PD2
Please note that the units will be supplied with two bottom plates, one for metric glands and one for con­duits.
16 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
Safety clamp
To maintain the galvanic isolation (PELV) between the control terminals and high-voltage terminals, the ac­companying safety clamp must be attached to VLT 2803-2815, 200-240 V, and VLT 2805-2815, 380-480 V. Attach the safety clamp to the strain relief plate with the two screws provided.
For all unit types, external prefuses must be fitted in the line supply to the adjustable frequency drive. For UL/cUL applications with a line voltage of 200-240 Volt, use prefuses type Bussmann KTN-R (200-240 Volt) or Ferraz Shawmut type ATMR (max. 30A). For UL/cUL applications with a line voltage of 380-480 Volt, use prefuses type Bussmann KTS-R (380-480 Volt).
Prefuses for UL application /cUL
Prefuses
Alternative fuses 380-500 V drives VLT 2800 Bussmann
2805-
2855-
2880-
Alternative Fuses 200-240 V drives
VLT 2800 Bussmann
2803-2822 KTN-R20 JKS-20 JJN-20 5017906-020KLS-R20 ATM-R25 A6K-20R
E52273
RK1/JDDZ J/JDDZ T/JDDZ CC/JDDZ CC/JDDZ CC/JDDZ RK1/JDDZ RK1/JDDZ CC/JDDZ RK1/JDDZ
2820
2875
2882
2840 KTN-R25 JKS-25 JJN-25 5017906-025KLS-R25 ATM-R20 A6K-25R
KTS-R20 JKS-20 JJS-20 FNQ-R-20 KTK-R-20 LP-CC-20 5017906-020KLS-R20 ATM-R25 A6K-20R
KTS-R25 JKS-25 JJS-25 5017906-025KLS-R25 ATM-R20 A6K-25R
KTS-R50 JKS-50 JJS-50 5014006-050KLS-R50 - A6K-50R
E52273
RK1/JDDZ J/JDDZ T/JDDZ RK1/JDDZ RK1/JDDZ CC/JDDZ RK1/JDDZ
Bussmann E4273
Bussmann E4273
Bussmann E4273
Bussmann E4273
Bussmann E4273
Bussmann E4273
Bussmann E4273
SIBA E180276
SIBA E180276
Little Fuse E81895
Little Fuse E81895
Ferraz­Shawmut E163267/ E2137
Ferraz­Shawmut E163267/ E2137
Ferraz­Shawmut E163267/ E2137
Ferraz­Shawmut E163267/ E2137
Installation
AC line connection
All drives that are equipped with an RFI filter cannot be connected to a grounded
No.N
(L2)L1(L1) (L3)
L2 L1 L3
No.95 Ground connection
AC line voltage 3 x 220-240 V
DELTA or IT mains/AC line system.
No.91 92 93 AC line voltage 3 x 380-480 V
NOTE
Check that the AC voltage matches the
L1 L2 L3
No.95 Ground connection
voltage rating of the drive. The drive rating is on the drive nameplate. See Technical data in this manual for correct dimension­ing of cable cross-section.
380-460 Volt units with RFI-filters may not be connected to AC line supplies in
which the voltage between phase and For single phase 220-240 Volts input, attach the neu­tral wire to terminal N to terminal L1
No.N
(L2)L1(L1) (L3)
(L1)
.
and connect the phase wire
(L2)
AC line voltage 1 x 220-240 V
N L1
ground is more than 300 Volts. Please
note that for the AC line for IT and the delta
ground the AC line voltage can exceed
300 Volts between phase and ground.
Units with type code R5 can be connected
No.95 Ground connection
MG.27.A2.22 - VLT® is a registered Danfoss trademark 17
to mains supplies with up to 400 V be­tween phase and ground.
See Technical data for correct dimensioning of cable cross-section.
Motor connection
Connect the motor to terminals 96, 97, 98. Connect ground to terminal 99.
96 97 98 Motor voltage 0-100% of line
No.
voltage.
U V W
U1W2V1U2W1V26 wires out of motor, Delta-con-
U1 V1 W1 6 wires out of motor, Star-con-
3 wires of motor
nected
nected U2, V2, W2 to be interconnec­ted separately (optional termi­nal block)
VLT® 2800 Series
No. PE Ground connection
See Technical data for correct dimensioning of cable cross-section.
18 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
All types of three-phase asynchronous standard mo­tors can be connected to an adjustable frequency drive. Normally, small motors are star-connected (230/400 V, ǻ/ Y), while large motors are delta-con- nected (400/690 V, ǻ/ Y). The correct connection mode and voltage can be read from the motor name­plate.
NOTE
In motors without phase insulation paper, an LC filter should be fitted on the output of the adjustable frequency drive.
Direction of motor rotation
To change the direction of motor rotation, switch any two phases at the drive output or at motor terminals.
Motor thermal protection
The electronic thermal relay in UL approved variable frequency drives has received the UL approval for sin­gle motor protection, when parameter 128 Motor ther- mal protection has been set for ETR Trip and parameter 105 Motor current, I
has been program-
M, N
med to the rated motor current (see motor nameplate).
The adjustable frequency drive is able to control sev­eral motors connected in parallel. If the motors are to have different rpm values, use motors with different rated rpm values. Motor rpm is changed simultane­ously, which means that the ratio between the rated rpm values is maintained across the range. The total current consumption of the motors is not to exceed the maximum rated output current I
for the adjustable
INV
frequency drive.
Problems may arise at the start and at low rpm values if the motor sizes are widely different. This is because the small motors' relatively high ohmic resistance in the stator calls for a higher voltage at the start and at low rpm values.
In systems with motors connected in parallel, the elec­tronic thermal relay (ETR) of the adjustable frequency drive cannot be used as motor protection for the indi­vidual motor. For this reason, further motor protection must be used, such as thermistors in each motor or an individual thermal relay, for example (circuit breakers are not a suitable means of protection).
NOTE
Parameter 107 Automatic motor adapta-
tion, AMT cannot be used when motors
are connected in parallel. Parameter 101
Torque characteristic must be set to Spe-
cial motor characteristics [8] when motors
are connected in parallel.
Motor cables
See Technical data for correct dimensioning of motor cable cross-section and length. Always comply with national and local regulations on cable cross-section.
Installation
Parallel connection of motors
NOTE
If an unshielded/unarmored cable is used,
some EMC requirements are not com-
plied with, see EMC test results in the De-
sign Guide.
If the EMC specifications regarding emissions are to be complied with, the motor cable must be shielded/ armored unless otherwise stated for the RFI filter in question. It is important to keep the motor cable as short as possible so as to reduce the noise level and leakage currents to a minimum. The motor cable shield must be connected to the metal cabinets of the adjust-
MG.27.A2.22 - VLT® is a registered Danfoss trademark 19
VLT® 2800 Series
able frequency drive and the motor. The shield con­nections are to be made with the largest possible surface area (cable clamp). This is enabled by different installation devices in different adjustable frequency drives. Connecting with twisted shield ends (pigtails) is to be avoided, as these spoil the shielding effect at high frequencies. If it is necessary to break the shield to install a motor isolator or motor relay. The shield must be continued at the lowest possible HF impe­dance.
Brake connection
NOTE
Voltages up to 850 VDC occur on the ter-
minals.
No.
81 82 Brake resistor R- R+
terminals
Connect the brake resistor wiring to drive terminals 81 and 82. The connection cable to the brake resistor must be shielded/armored. Connect the shield to both the ground of the drive and the brake resistor by means of cable clamps. Dimension the cross-section of the brake cable to match the brake torque.
Ground connection
Since the leakage currents to ground may be higher than 3.5 mA, the adjustable frequency drive must al­ways be connected to ground in accordance with ap­plicable national and local regulations. To ensure that the ground cable has good mechanical connection to terminal 95, the cable cross section must be a mini-
2
mum 7 AWG (10 mm
). To improve protection even further, a Recidual Current Device (RCD) can be fitted to ensure that the adjustable frequency drive cuts out when the leakage currents get too high. Also see RCD Application note MN.90.GX.02.
Load sharing
Load sharing provides the facility to connect several frequency converters' DC intermediate circuits. This requires that the installation is extended using extra fuses and AC coils (see drawing below). For load shar­ing parameter 400 Brake function must be set to Load sharing [5]. Use 6.3 mm Faston Plugs for DC (Load Sharing). Contact Danfoss or see instructions no. MI.50.NX.02 for further information.
88 89 Loadsharing
No.
- +
20 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Note that voltage levels of up to 850 V DC may occur between terminals 88 and 89.
VLT® 2800 Series
Tightening Torque, Power Terminals
Power and ground terminals must be tightened with the following torques:
VLT 2803­2875 2880­2882, 2840 PD2
Calculation of brake resistance
In lifting/lowering applications you need to be able to control an electromagnetic brake. The brake is con­trolled using a relay output or digital output (terminal
46). The output must be kept closed (voltage-free) for the period of time during which the variable frequency drive is not able to 'support' the motor, for example due to the load being too great. Select Mechanical brake control in parameter 323 or 341 for applications with an electromagnetic brake. When the output frequency exceeds the brake cut out value set in par. 138, the brake is released if the motor current exceeds the preset value in parameter 140. When stopping the brake is engaged when the output frequency is less than the brake engaging frequency, which is set in par. 139. If the variable frequency drive is placed at alarm status or in an overvoltage situation the mechanical brake is cut in immediately.
Terminals Torque [Nm] Power AC line brake 0.5-0.6 Ground 2-3 Power AC line brake 1.2-1.5 Ground 2-3
Installation
NOTE
This application is only for lifting/lowering without a counterbalance.
Access to control terminals
All control terminals are located underneath the pro­tective plate on the front of the adjustable frequency drive. Remove the protective plate by sliding it down­wards (see drawing).
Electrical installation, control circuitry
NOTE
Using unshielded/unarmored cable may not comply with some EMI/RFI require­ments.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 21
Control wires must be shielded/armored. Connect the shield to the drive chassis with a clamp. Normally, the
VLT® 2800 Series
shield must also be connected to the chassis of the controlling device. (See the instructions for the specific device.) In analog signals or connections using very long wires, 50/60 Hz ground loops may occur because of noise transmitted from the AC line. It may be nec­essary to break the shield and insert a 100 ȝF capac­itor between the shield and the chassis.
Tightening torques, control cables
Control wires must be connected with a tightening tor­que of 0.22-0.25 Nm.
Electrical installation, control terminals
See section entitled Grounding of shielded/armored control cables in the VLT 2800 Design Guide for the
correct termination of control cables.
22 MG.27.A2.22 - VLT® is a registered Danfoss trademark
VLT® 2800 Series
No. Function 01-03 Relay outputs 01-03 can be used for
indicating status and alarms/warnings. 12 24 V DC voltage supply. 18-33 Digital inputs. 20, 55 Common frame for input
and output terminals. 42 Analog output for displaying frequency,
reference, current or torque. 46
Digital output for displaying status,
1
warnings or alarms, as well as
frequency output. 50 +10 V DC supply
voltage for potentiometer or thermistor. 53 Analogue voltage input 0-10 V DC. 60 Analogue current input 0/4 - 20 mA. 67
+ 5 V DC supply voltage
1
to Profibus. 68, 691RS-485, Serial communication. 70
Frame for terminals 67, 68 and 69.
1
Normally, this terminal is not to be used.
1. The terminals are not valid for DeviceNet/CANopen. See also the DeviceNet manual, MG.90.BX.YY for fur­ther details.
Profibus DIP switches setting
The dip switch is only on the control card with Profibus DP communication. The switch position shown is the factory setting. Switches 1 and 2 are used as cable termination for the RS-485 interface. If the adjustable frequency drive is located as the first or last (or only) unit in the bus system, switches 1 and 2 must be ON. On the remaining adjustable frequency drives, switches 1 and 2 must be OFF. Switches 3 and 4 are not applied.
VLT Software Dialog
Connection to terminals 68-70 or Sub D:
PIN 3 GND
-
PIN 8 P-RS 485
-
PIN 9 N-RS 485
-
Sub D plug
Installation
Relay connection
See parameter 323 Relay output for programming of relay output.
01 - 02 1 - 2 make (normally open)
Nr.
01 - 03
1 - 3 break (normally closed)
NOTE
Please note that the cable jacket for the relay must cover the first row of control card terminals - otherwise the galvanic isolation (PELV) cannot be maintained. Max. cable diameter: 4 mm. See drawing.
An LCP 2 control unit can be connected to the Sub D plug on the control card. Ordering number: 175N0131. The LCP control unit with ordering number 175Z0401 is not to be connected.
MG.27.A2.22 - VLT® is a registered Danfoss trademark 23
VLT® 2800 Series
Connection examples
Start/stop
Start/stop using terminal 18 and coasting stop using terminal 27.
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Coasting stop inver- ted [2]
For Precise start/stop the following settings are made:
Par. 302 Digital input = Precise start/stop [27]
Par. 304 Digital input = Coasting stop inver- ted [2]
Speed up/slow down
Speed up/slow down using terminals 29/33.
Par. 302 Digital input = Start [7]
Par. 303 Digital input = Freeze reference [14]
Par. 305 Digital input = Speed up [16]
Par. 307 Digital input = Slow down [17]
Potentiometer reference
Voltage reference via a potentiometer.
Pulse start/stop
Pulse start using terminal 18 and pulse stop using ter­minal 19. In addition, the jog frequency is activated via terminal 29.
Par. 302 Digital input = Pulse start [8]
Par. 303 Digital input = Stop inverted [6]
Par. 304 Digital input = Coasting stop inver- ted [2]
Par. 305 Digital input = Jog [13]
Par. 308 Analog input = Reference [1]
Par. 309 Terminal 53, min. scaling = 0 Volt
Par. 310 Terminal 53, max. scaling = 10 Volt
Connection of a 2-wire transmitter
Connection of a 2-wire transmitter as feedback to ter­minal 60.
24 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Par. 314 Analog input = Feedback [2]
Par. 315 Terminal 60, min. scaling = 4 mA
Par. 316 Terminal 60, max. scaling = 20 mA
VLT® 2800 Series
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 25
VLT® 2800 Series
Control unit
On the front of the variable frequency drive there is a control panel.
The control panel is divided into five functional groups:
1. Status LED
2. Keys for changing parameters and shifting display function.
3. LEDs.
4. Keys for local operation.
All displays of data are in the form of a six-digit LED display capable of showing one item of operating data continuously during normal operation. As a supple­ment to the display, there are three LEDs for indication of electrical connection (ON), warning (WARNING) and alarm (ALARM). Most of the variable frequency drive's parameter Setups can be changed immediately via the control panel, unless this function has been programmed as Locked [1] via parameter 018 Lock for data changes.
The [CHANGE DATA] key is also used for confirming a change of parameter settings.
[+] / [-] are used for selecting parameters and for changing parameter values. These keys are also used in Display mode for selecting the display of an operating value.
The [QUICK MENU] + [+] keys must be pressed at the same time to give access to all parameters. See Menu
mode.
[STOP/RESET] is used for stopping the connected motor or for resetting the variable frequency drive after a trip. Can be selected as Active [1] or Not active [0] via pa­rameter 014 Local stop/reset. In Display mode, the display will flash if the stop function is activated.
NOTE
If the [STOP/RESET] key is set at Not ac­tive [0] in parameter 014 Local stop/re­set,and there is no stop command via the
digital inputs or serial communication, the motor can only be stopped by disconnect­ing the electrical voltage to the variable frequency drive.
[START] is used for starting the variable frequency drive. It is always active, but the [START] key cannot override a stop command.
Manual initialization
To manually initialize the adjustable frequency drive to factory default settings, first disconnect AC line volt­age. Hold the [QUICK MENU] and [+] and [CHANGE DATA] keys down while simultaneously reconnecting the AC line voltage. Release the keys. The drive has now been programmed for factory settings.
Control keys
[QUICK MENU] allows access to the parameters used
for the Quick menu. The[QUICK MENU] key is also used if a change to a parameter value is not to be implemented. See also [QUICK MENU] + [+].
[CHANGE DATA] is used for changing a setting.
26 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Display readout states
Display mode
VLT® 2800 Series
In normal operation, one item of operating data can be displayed continuously at the operator's discretion. By means of the [+/-] keys, the following options can be selected in Display mode:
Output frequency [Hz]
-
Output current [A]
-
Output voltage [V]
-
Intermediate circuit voltage [V]
-
Output power [kW]
-
Scaled output frequency f
-
x p008
out
Menu mode
In order to enter the Menu mode, [QUICK MENU] + [+] must be activated at the same time. In Menu mode, most of the adjustable frequency drive parameters can be changed. Scroll through the pa­rameters using the [+/-] keys. While scrolling in the Menu mode proceeds, the parameter number will flash.
The display shows that the setting in parameter 102
Motor power P
is 0.75. In order to change the value
M,N
of 0.75, [CHANGE DATA] must first be activated; the parameter value can then be changed using the [+/-] keys.
If a given parameter display shows three dots to the right, it means that the parameter value has more than three digits. In order to see the entire value, activate [CHANGE DATA].
The display shows that in parameter 128 Motor thermal protection, the selection made is Thermistor trip [2].
Quick menu
Using the [QUICK MENU] key, it is possible to access the 12 most important parameters of the adjustable frequency drive. After programming, the adjustable frequency drive is, in most cases, ready for operation. When the [QUICK MENU] key is activated in Display mode, the Quick menu starts. Scroll through the quick menu using the [+/-] keys and change the data values by first pressing [CHANGE DATA] and then changing the parameter value with the [+/-] keys. TheQuick menu parameters are:
Par. 100 Configuration
Par. 101 Torque characteristic
Par. 102 Motor power P
Par. 103 Motor voltage U
Par. 104 Motor frequency f
Par. 105 Motor current I
Par. 106 Rated motor speed n
Par. 107 Automatic motor adaptation
Par. 202 Output frequency high limit f
Par. 203 Reference range
Par. 204 Minimum reference Ref
Par. 205 Maximum reference Ref
Par. 207 Ramp-up time
Par. 208 Ramp-down time
Par. 002 Local/remote operation
Par. 003 Local reference
M,N
M,N
M,N
M,N
M,N
MAX
MIN
MAX
Parameter 102 - 106 can be read out from the motor's nameplate.
Automatic motor tuning
Automatic motor tuning (AMT) is performed as follows:
Installation
MG.27.A2.22 - VLT® is a registered Danfoss trademark 27
1.
In parameter 107 Automatic motor tuning, se­lect data value [2]. "107" will now flash, and "2" will not flash.
2. AMT is activated by pressing start. "107" will now flash and dashes will move from left to right in the data value field.
3. When "107" appears once more with the data value [0], AMT is complete. Press [STOP/ RESET] to save the motor data.
4. "107" will then continue to flash with the data value [0]. You can now proceed.
NOTE
VLT 2880-2882 do not have AMT func­tion.
VLT® 2800 Series
28 MG.27.A2.22 - VLT® is a registered Danfoss trademark
Loading...
+ 94 hidden pages