Greystone Energy Systems ULP1, ULP2 Installation Instructions Manual

Ultra Low Pressure Transmitter
ULP
Installation Instructions
Introduction
The Ultra Low Pressure Transmitter is used to measure dierential pressure in the range of 0.125 to 1"wc (30 to 250 Pa). It combines precision high sensitivity silicon sensing capabilities and the latest ASIC technology to substantially reduce oset errors due to changes in temperature, stability to warmup, long term instability and position sensitivity. It is ideal for monitoring pressure for air or other clean inert gas. It features several eld selectable uni- or bi-directional pressure ranges and output signal types for the most exible application. The device has an on-board auto-zero function as well as a connection for remote zeroing. Options include an LCD to display the pressure value and an alarm relay with a variable trip point.
Before Installation Read these instructions carefully before installing and commission­ing the Pressure Transmitter. Failure to follow these instructions may result in product damage. Do not use in an explosive or hazard-
ous environment, with combustible or ammable gases, as a safety or emergency stop device or in any other application where failure of the product could result in personal injury. Take electrostatic discharge precautions during installation and do not exceed the device ratings.
Mounting
Mount the device using the four holes on the base of the unit. Leave enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations, excessive moisture or rapid temperature changes. It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the right. The enclosure has a standard ½” conduit opening and may be installed with either conduit and a conduit coupler or a cable gland type tting. Open the hinged cover by releasing the latch and connect the device according to the wiring instructions. After wiring and setup are complete, close and latch the cover. The cover may be secured with two self-tapping screws in the holes provided. as shown in gure 1.
The enclosure has a hinged cover with latch. Open cover by pulling slightly on the latch on the right side of the enclosure. At the same time pulling on the cover, as illustrated in gure 2.
Feed conduit/cable gland tting through the provided hole in side of enclosure and secure with a lock nut as show in gure 3. It is recom­mended that weatherproof conduit or cable gland ttings be used.
Make wiring connections as per the “Wiring” illustrations on Page 3.
Swing door closed until securely latched. For added security, 2 screws are provided that may be installed in the integrated screw tabs. See gure 4.
Figure 1
Figure 2
Figure 4Figure 3
Greystone Energy Systems, Inc. 150 English Drive, Moncton, NB E1E 4G7 Canada Tel: +1-506-853-3057 Tollfree (North America): +1-800-561-5611 Fax: +1-506-853-6014
Conduit
Email: support@greystoneenergy.com Web: www.greystoneenergy.com
Hardware Setup The analog output type must be set before the device is connected. Slide the switch labelled VOLT and mA to the correct
position for the required output signal type, either 4-20 mA or 0-5/10 Vdc. See gure 5. Other parameters may be set on the DIP switches before or after the device is connected. Any DIP switch change will have an immediate eect on the operation.
DIP Switch Conguration (See gure 6)
BL OFF / BL ON Sets the LCD backlight on or o "WC / Pa Sets the pressure units to “WC or Pascals HI Range / LO Range* Sets the pressure range (See chart below) +/- Max / 0 - Max Sets bi- or uni-directional pressure range LO Avg / HI Avg Sets pressure averaging to 5 or 30 seconds 10V / 5V Sets the voltage output scale to 0-5 or 0-10 Vdc (N/A when mA output is selected) LO Delay / HI Delay Sets the alarm delay to 10 or 60 seconds (N/A if no relay is ordered) Normal / Reverse Sets the alarm action (N/A if no relay is ordered)
*The eect of dierent DIP switch settings on the pressure range is shown in the following table.
Model
Pressure Pressure ULP*1 ULP*2 Units Range ± Max 0 - Max ± Max 0 - Max
"WC HI Range ± 1 "wc 0-1 "wc ± 0.25 "wc 0-0.25 "wc LO Range ± 0.5 "wc 0-0.5 "wc ± 0.125 "wc 0-0.125 "wc Pa HI Range ± 250 Pa 0-250 Pa ± 60 Pa 0-60 Pa LO Range ± 125 Pa 0-125 Pa ± 30 Pa 0-30 Pa
Figure 5
Output Type Selection Switch
mA = 4-20 mA
(Factory Default)
VOLT = Vdc
Figure 6
Wiring Instruction
The transmitter has standard screw block connectors. Use shielded twisted pair wiring of at least 22 AWG for all connections and do not run device wires in the same conduit with wiring used to supply inductive loads such as motors. Disconnect the power supply before making any connections to prevent electrical shock or equipment damage. Make all connections in accordance with national and local electrical codes.
This is a 3-wire sourcing device. Connect the positive dc or the ac voltage hot side (24 Vac/dc ± 10%) to the POWER terminal. The supply common is connected to the COMMON terminal. The device is reverse voltage protected and will not operate if connected backwards. It has a half-wave rectied power supply so the supply common is the same as the signal common. Several devices may be connected to one power supply and the output signals all share the same common. Use caution when grounding the secondary of a transformer or when wiring multiple devices to ensure the ground point is the same on all devices and the controller.
The analog output is available on the PRES OUT terminal. This signal is switch selectable for either voltage or 4-20 mA active output. In voltage mode the output is 0-5 or 0-10 Vdc. These options are indicated on the circuit board. The current output operates in the Active mode and does not require a loop power supply. This means the signal current is generated by the transmitter and must not be connected to a powered input or device damage will result. Check the controller Analog Input to determine the proper connection before applying power. Both current and voltage signals are referenced to the COMMON terminal. The voltage output signal has a minimum load that it is able to drive, similarly the current signal has a maximum load. Follow the ratings in the Specication section or inaccurate readings may result. See gure 7.
The RELAY output is a normally open dry contact. This signal can be used to directly control an alarm, ventilation fan or may be connected to a digital input of the BAS for status monitoring. Ensure any loads connected to the relay is within the relay rating in the Specication section. See gure 8.
The remote zero feature may be used by wiring a dry-contact (relay only) digital output between the ZERO IN and COMMON terminals. Do not apply voltage to the ZERO IN terminal. See gure 9.
Greystone Energy Systems, Inc. 150 English Drive, Moncton, NB E1E 4G7 Canada Tel: +1-506-853-3057 Tollfree (North America): +1-800-561-5611 Fax: +1-506-853-6014
Email: support@greystoneenergy.com Web: www.greystoneenergy.com
Loading...
+ 2 hidden pages