![](/html/55/55af/55af14514c1341a64f4ca20050ee09f4e4f17b52bc4bdddfd1cf7f71274539f5/bg1.png)
RELATIVE HUMIDITY
TRANSMITTER
RH Series
Precision humidity
control/sensing
FEATURES:
• Highly stable RH sensor element
• Humidity range: 0-100%
• Accuracy available 2%, 3%, & 5%
• Choice of precision temperature sensors
• LCD display available
• Field selectable outputs
• AC/DC operation
• Custom logo available
Peace of mind
through reliable
humidity monitoring
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
![](/html/55/55af/55af14514c1341a64f4ca20050ee09f4e4f17b52bc4bdddfd1cf7f71274539f5/bg2.png)
DESCRIPTION:
The RH series of humidity transmitters are designed for use in environmental monitoring and control
systems where high performance and stability are demanded. It’s state-of-the-art design combines
digital linearization and temperature compensation with a world class capacitive sensor for reliability
and accuracy in even the most critical applications. Various models cover many aspects of RH
measurement and several optional features are available to meet virtually all HVAC applications.
SPECIFICATION:
Sensor Type ..................................................Thermoset Polymer based capacitive
Accuracy........................................................ ±2, 3, or 5% RH, (5% to 95% RH)
Measurement Range................................. 0 to 100% RH
Temperature Dependence...................... ±0.05% RH/ ˚C
Hysteresis ...................................................... ±1.5% RH maximum
Repeatability................................................ ±0.5% RH typical
Linearity......................................................... ±0.5% RH typical
Sensor Response Time.............................. 15 seconds typical
Stability.......................................................... ±1% RH typical at 50% RH in 5 yrs.
Operating Temperature ........................... 0˚ to 70˚C (32˚ to 158˚F) for RH100
-40˚ to 85˚C (-40˚ to 185˚F) for RH200/RH300
Operating Humidity.................................. 0 to 95% RH non-condensing
Power Supply............................................... 18 to 30 Vdc, 15 to 26 Vac
Consumption............................................... 22 mA maximum
Input Voltage Eect ................................... Negligible over specied operating range
Protection Circuitry....................................Reverse voltage protected and out limited
Output Signal............................................... 4-20 mA current loop, 0-5 or 0-10 Vdc (jumper-selectable)
Output Drive at 24 Vdc ............................. 550 ohms max for current output
10K ohms min for voltage output
Internal Adjustments ................................ Clearly marked ZERO and SPAN pots
Wiring Connections................................... Screw terminal block (14 to 22 AWG)
Optional LCD Display................................ RH200A Only
3 digit for 00.0 to 99.9% RH, 24 x 11mm (0.95”w x 0.45”h)
Optional Temperature Sensor................Various RTDs and thermistors available as two-wire
resistance output (See Ordering Chart)
Enclosures..................................................... RH100B (Designer), IP20 (Nema 1), 70x114x30mm, (2.75”w x 4.5”h x 1.2”d)
RH200A (ABS), IP61 (Nema 2),114x84x53mm (4.5”w x 3.3”h x 2.1”d)
RH200E (Round), IP65 (Nema 4X), 91mm (3.6”) diameter x 53mm (2.1”) deep
RH200M (Metal), IP50 (Nema 1), 102x63x58mm (4”w x 3.3”h x 2.1”d)
RH200W (Metal WP) IP64 (Nema 3X),115x72x56mm (4.5”w x 2.8”h x 2.5”d)
RH300A (ABS WP) IP65 (Nema 4X),122x112x63mm (4.8”w x 4.8”h x 2.5”d)
RH200 Probe ................................................230 mm (9”) probe length x 12.7 mm (1/2”) diameter
stainless steel with porous lter