Greystone Energy Systems NT Series Catalog Page

HUMIDITY/TEMPERATURE SENSOR
BACnet® or Modbus Communication
NT Series
FEATURES:
BACnet® or Modbus communication
Temperature and RH monitoring
Room, Duct or Outside
LCD display (Room only)
Several optional features available
Peace of mind
through reliable
humidity/temperature
monitoring
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
DESCRIPTION (ROOM):
The NTRC Series Room Network Sensor features embedded BACnet® and Modbus communication and is
available in several congurations for the most ecient monitoring and control solution. The basic unit accurately measures room temperature. Optional features include RH measurement, up/down setpoint control, a local override function, a control relay output and fan speed switch.
The device connects to an RS-485 MS/TP network to oer a single-point solution for control of indoor air comfort. Features include a back-lit LCD and user menu for easy conguration, eld-proven sensors and user input controls to add optional local setpoint and override functions at the same network point.
SPECIFICATIONS (ROOM):
General Specications:
Power Supply...................................................................20-28 Vac/dc (non-isolated half-wave rectied)
Consumption...................................................................
Protection Circuitry........................................................Reverse voltage and over voltage protected
Operation Conditions...................................................0 - 50 °C (32 -122 °F), 0-95% RH, non-condensing
Wiring Connections.......................................................
External Dimensions .....................................................
Enclosure Ratings...........................................................IP30 (NEMA 1)
Communications Interface:
Hardware........................................................................... 2-wire RS-485
Software.............................................................................Native BACnet® or Modbus MS/TP protocol, menu selectable
Baud Rate .......................................................................... Locally set from 300 to 76800
Network Address Range ..............................................Locally set to 0-127 for BACnet® or 1-255 for Modbus
(Factory default is 3) (63 devices max on one daisy chain)
LCD Display:
Resolution.........................................................................
Size.......................................................................................
Backlight............................................................................
Displayed Values..................................................................... Temperature Only, RH Only or Alternating Temperature/RH
(RH requires optional RH Signal)
Temperature:
Sensing Element.............................................................
Range
....................................................................................................
Optional RH Signal:
Sensing Element.............................................................
Accuracy............................................................................± 2% RH
Range..................................................................................
Resolution......................................................................... 1% RH
Hysteresis .......................................................................... ± 3% RH
Response Time ................................................................
Stability..............................................................................
Optional Override Switch:
User Interface................................................................... Front panel
Override Status ...............................................................Via
Optional Setpoint Control:
User Interface................................................................... Front panel, up/down push-buttons
Setpoint Mode.................................................................
(Factory default is Temperature & ˚C)
Adjustable Setpoint Range.........................................
(Factory default is 18 ˚ to 24 ˚C)
Minimum Span........................................................................ 4 ˚C/F or 10% RH
Temperature Setpoint Resolution.................................... 0.5 ˚ or 1 ˚, menu selectable (Factory default is 1˚)
Optional Fanspeed Switch:
User Interface ..................................................................Side panel, 5 position switch
Indication ..................................................................................O, Auto, Low, Mid, High switch position
Optional Relay Output:
Contact Ratings...............................................................
Relay Activation ..............................................................
35 mA max @ 24 Vdc
Screw terminal block (14 to 22 AWG) 84 W x 119 H x 29 D mm (3.3” x 4.7” x 1.15”)
0.5 ˚ or 1 ˚C/F (selectable), 1% RH
38.1 W x 16.5 H mm (1.5” x 0.65” ), 3 digit Auto-dimming, enable/disable via jumper
10K thermistor, ±0.2 ˚C (±0.4 ˚F) 0 - 50 ˚C (32 - 122 ˚F)
Thermoset polymer based capacitive
0 - 100% RH, non-condensing
15 seconds typical ± 1.2% RH typical @ 50% RH in 5 years
push-button available via BACnet® or ModBus
BACnet® or ModBus.
Temperature (˚C/˚F) or RH, menu selectable
10 - 30 ˚C, 50 - 86 ˚F or 10 - 80% RH, menu selectable
Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc Via BACnet
® or Modbus
”OCC” segment lights on LCD
available via BACnet® or Modbus
available via BACnet® or Modbus