Greystone Energy Systems CS-6XX Series Catalog Page

SOLID CORE CURRENT SENSOR
CS-6XX Series
Precision Power control/sensing
FEATURES:
• Solid Core
• 0-5, 0-10 Vdc or 4-20 mA Output
• Selectable or Fixed Range Models
• Self-powered and Loop-powered Models
• Up to 200 amps Input Current
• Small Compact Size
Peace of mind
through reliable
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
AC CURRENT SENSORS CS-650 Series
DESCRIPTION:
The CS-650 Series current sensors monitor line current for electrical loads such as pumps, conveyors, machine tools, or fans and output a 0-5 Vdc signal to represent the load current.
The CS-650 require no external power as they are totally powered by induction from the AC line being monitored.
The sensors are typically used to monitor motor operation and can be used to determine motor failure, belt loss, machine feed rates or tool wear.
SPECIFICATION:
Measurement Range......................Up to 200 Amps - See ordering information
Maximum Input Current...............CS-650-R1: 100 Amps Continuous
CS-650-R2: 150 Amps Continuous CS-650-200: 250 Amps Continuous
Accuracy.............................................± 2% FSO (5-100% of range)
Signal Output....................................0-5 Vdc
Sensor Power....................................Self-powered
Insulation Class ................................600 Vac, insulated conductors
Frequency..........................................50/60 Hz
Response Time .................................200 mS Typical, 0-90 %
Output Load......................................1 MΩ typical
Loading Error....................................add 0.5% error with 100KΩ
Operating Temperature ................-15 to 60 °C (5 to 140 °F)
Operating Humidity.......................5 to 90% RH non-condensing
Terminal Block ..................................14 to 22 AWG
Dimensions........................................67 x 68.6 x 24.1 mm
(2.65 x 2.7 x 0.95 in)
Sensor Aperture...............................20.3 mm (0.8 in)
Enclosure Material...........................ABS/PC, UL94 V-0
Agency Approvals...........................cULus Listed
PRODUCT ORDERING INFORMATION
FEATURES:
• No eld adjustment necessary, factory calibrated
• Input / Output isolation via current transformer
• Solid-state reliability
• Small compact size
• Solid, reliable mounting method
MODEL Product Description
CS-650 0-5 Vdc, Self-powered
CODE Input Range Maximum Input Current
-R1 0-10/20/50 Amps - Switch Selectable 100 Amps Continuous
-R2 0-50/100/150 Amps - Switch Selectable 150 Amps Continuous
-200 0-200 Amps 250 Amps Continuous
CS-650 -R1
Greystone Energy Systems, Inc. reserves the right to make design modications without prior notice.