Greystone Energy Systems CMD Series Catalog Page

CARBON MONOXIDE
(CO) DETECTORS
CMD Series
Precision gas control/sensing
FEATURES:
Space or duct mount models
Long-life electrochemical sensor
Various analog outputs
LCD display
Optional relay outputs & audible alarm
BACnet or Modbus communication
Peace of mind
through reliable
gas monitoring
DESCRIPTION:
The CMD5B1 Series carbon monoxide detector uses a superior electrochemical sensor for reliability and accuracy in even the most critical applications. The standard product features a 2-wire loop-powered output. Optionally, the device may congured with an alarm relay which operates in 3-wire sourcing mode and/or with Modbus communications.
85 mm
3.4 “
71 mm
2.8 “
52 mm
2 “
48 mm
1.9 “
104 mm
4.1 “
SPECIFICATION:
Sensor Type .........................................................Electrochemical
Sensor Agency Approvals .............................. Sensor is a UL Recognized Component for ANSI/UL-2034, UL-2075, E240671
Measurement Range........................................ Analog: 0-300 PPM Modbus: 0-500 PPM
Accuracy............................................................... ±5 PPM or 5% of reading for 0-300 PPM (whichever is greater)
Accuracy rated.................................................... 0˚ to 50˚C (32˚ to 122˚F), 15 to 95%
Life Expectancy.................................................. 5-7 years in air
Typical Coverage Area .....................................
Operating Conditions......................................-20˚ to 50˚C (-4˚ to 122˚F), 15 to 95% RH
Sample Method .................................................Diusion
Stability................................................................. <5% signal loss/year
Response Time ................................................... <35 seconds for 90% step change
Power Supply...................................................... 24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectifed) Modbus: 24 Vdc ±20%
Consumption......................................................20 mA max. with Relay option: 50 mA max. Modbus: 35 mA max.
Input Voltage Eect .......................................... Negligible over specied operating range
Protection Circuitry...........................................Reverse voltage protected and output limited
Output Signal...................................................... 4-20 mA loop-powered, 4-20 mA sourcing with relay option
Output Drive at Capability............................. 550 ohms max. @ 24 Vac/Vdc
Optional Relay Output ....................................
.................................................................................
.................................................................................
.................................................................................
Optional Modbus .............................................. Hardware..................................2-wire RS-485
Software ..................................... Native ModBus MS/TP protocol (RTU)
Baud Rate................................... 9600
Slave Address Range.................... Locally set to 1-255
Parity..................................................None
Stop Bits............................................ 1
CRC................................................A001 (CRC-16 reverse)
Wiring Connections.......................................... Screw terminal block (14 to 22 AWG)
External Dimensions ........................................71 x 104 x 48 mm (2.8” w x 4.1“ h x 1.9”d)
Enclosure Ratings..............................................ABS - UL94-V - IP65, (NEMA 4X)
Field Calibration................................................. By applying calibration gas standards (Contact Greystone for calibration kit)
Accessories ..........................................................Calibration kit, model# CMD-CALKIT-GS
700 m2 (7500 ft2) or 15m (50ft) radius
Form C contact (N.O. and N.C.) - Not available with Modbus Communications 5 amps @ 250 Vac, 5 amps @ 30 Vdc, p.f. = 1 Trip Point - 25, 60 or 150 PPM, jumper selectable Hysteresis - 3% or 9 ppm
PRODUCT ORDERING INFORMATION:
MODEL Description
CMD5B1 Carbon Monoxide Detector (CO), Electrochemical, Loop-powered
CODE Relay
000 No Relay 100 Relay (Not available with Modbus Communications)
CODE Options
MOD Modbus Communications
CMD5B1 -
Greystone Energy Systems Inc. reserves the right to make design modications without prior notice.
100
Typical Model Number
Loading...
+ 2 hidden pages