![](/html/5e/5e36/5e366c76d49d8fa49f0992bd78a7deb2ad3e312f92d2e705219483067b48d265/bg1.png)
CARBON DIOXIDE & TEMPERATURE
DETECTORS
CDD4 Series
Room w/Setpoint,
Override & LCD
Duct Outside
Room w/ No Options
Precision carbon dioxide
control/sensing
FEATURES:
• Space, Duct & Outside Models
• 2 Available Ranges
• CO2, Temperature Outputs
• Optional Slidepot and/or Override
Optional On-board Relay
•
• Optional LCD Display
• Custom Logos Available
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
Peace of mind
through reliable
gas monitoring
![](/html/5e/5e36/5e366c76d49d8fa49f0992bd78a7deb2ad3e312f92d2e705219483067b48d265/bg2.png)
CO
DETECTOR w/ Optional Temperature Sensor
2
SPECIFICATIONS:
General Specications:
Power Supply..................................................... 20-28 Vac/dc (non-isolated half-wave rectied)
Output Signals................................................... 4-20 mA active (sourcing), 0-5 Vdc or 0-10 Vdc (eld selectable)
Consumption..................................................... Space/Duct/Outside: 100 mA max @ 24 Vdc,
185 mA max @ 24 Vac (with all options)
Outside w/ Heater: 1A max @ 24Vdc, 1.1A max @ 24 Vac
Output Drive Capability.........................................Current: 550 ohms max Voltage: 10 Kohm min
Output Resolution ........................................... 10 bit PWM
Protection Circuitry.......................................... Reverse voltage protected, overvoltage protected
Operation Conditions..................................... Space (10), Duct (20) and Outside (40): 0˚- 50°C (32˚-122°F),
0-95% RH non-condensing.
Outside w/ Heater (30): -40˚- 50°C (-40˚- 122°F), 0-95% RH non-condensing.
Sensor Coverage Area .................................... 100 m² (1000 ft²) typical
Wiring Connections.........................................
External Dimensions ....................................... Space:
Duct: 145mm W x 100mm H x 63mm D (5.7” x 3.95” x 2.5”)
Duct Probe: 177mm (7“) long x 25.4mm (1”) diameter
Enclosure Ratings............................................. Space: IP30 (NEMA 1)
Duct: IP65 (NEMA 4X)
Outside: IP65 (NEMA 4X)
CO2 Specications:
Measurement Type..................................................CDD4A: Non-Dispersive Infrared (NDIR), diusion sampling
CDD4B: Dual Channel Non-Dispersive Infrared (NDIR), diusion sampling
Measurement
CDD4B: 0 - 20,000 ppm, programmable span from 2000 to 20,000 ppm
Standard Accuracy........................................... CDD4A: ±30 PPM + 3% of reading with Auto Cal on.
CDD4B: ±75 PPM or 10% of reading (whichever is greater)
Temperature Dependence............................ 0.2% FS per °C
Stability................................................................ CDD4A: < 2 % FS over life of sensor (15 years typical)
CDD4B: < 5 % FS over life of sensor (15 years typical)
Pressure Dependence..................................... 0.13% of reading per mm Hg
Altitude Correction.......................................... Programmable from 0-5000 ft via keypad
Response Time................................................... <2 minutes for 90% step change typical
Warm-up Time................................................... <2 minutes
Range......................................... CDD4A: 0 - 2000 ppm
Screw terminal block (14 to 22 AWG)
84mm W x 119mm H x 29mm D (3.3” x 4.7” x 1.15”)
Outside:
110mm W X 180mm H X 89mm D (7.125” X 4.33” X 3.5”)
LCD Display:
Resolution...........................................................
Size.........................................................................
Backlight..............................................................
Optional Temperature Signal:
Sensing Element...............................................
Optional Setpoint Adjustment
Type....................................................................... Front panel slidepot, 2 wire resistance output
Range.................................................................... 0K to 10K Ω standard
Custom spans available ................................. 1K, 2K, 5K, 10K or 20K Ω
Optional Manual Override
Type....................................................................... Front panel, momentary pushbutton
Ratings.................................................................. 50 mA @12 Vdc, N.O., SPST
Optional Relay Output:
Contact Ratings.................................................
Relay Trip Point.................................................. CDD4A:
Relay Hysteresis ................................................ CDD4A:
1 ppm CO2
1.4” w x 0.6” h (35 mm x 15 mm) alpha-numeric 2 line x 8 character
Enable or disable via keypad
Various RTDs or thermistors as a 2-wire resistance output (See ordering chart)
Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc
Programmable 500-2000 ppm via keypad
CDD4B:
CDD4B:
Programmable 500-15,000 ppm via keypad
Programmable 25-200 ppm via keypad
Programmable 25-500 ppm via keypad