Greystone DH100ACDCPA, DH100ACDCIA Installation And Maintenance Manual

INSTALLATION AND MAINTENANCE
150 English Drive, Moncton, NB, E1E 4G7 CANADA
DH100ACDCIA & DH100ACDCPA
Air Duct Smoke Detector
tel: 506-853-3057 fax: 506-853-6014
e-mail: greystone@nbnet.nb.ca
www.greystoneenergy.com
Before Installing
ULC standard CAN/ULC-S524-M91 “Standard For The Installa­tion Of Fire Alarm Systems” should be referenced for Canadian Installations information. For additional reference the System Sensor
plications
Guide for Proper Use of Smoke Detectors in Duct Ap-
(I56-473), provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from System Sensor. NOTICE: This manual should be left with the owner/user of this equipment. IMPORT ANT: This detector must be tested and maintained regularly following CAN/ULC-S536-97 requirements. The detector should be cleaned at least once a year.
T able of Contents Page [1] General Description 1 [2] Limitations of Duct Smoke Detectors 1 [3] Exploded View of Duct Smoke Detector Components 2 [4] Contents of the Duct Smoke Detector Kit 2 [5] Installation Sequence 2 [6] Duct Smoke Detector Maintenance and T est Procedures5 [7] Detector Cleaning Procedures 7 [8] Board Replacement 8 [9] Specifications 8 [10] Warranty 8
[1] General Description
An HV AC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct sys­tem will be distributed to the entire building. Smoke detec­tors designed for use in air duct systems are used to sense the presence of smoke in the duct.
Model DH100ACDCA Air Duct Smoke Detectors are sup­plied as an ionization model or photoelectronic model. These two smoke detection methods are combined with an efficient housing design that samples air passing through a duct and allows detection of a developing hazardous condi­tion. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans, blowers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
DH100ACDCA detectors are designed to operate on 24 VDC/ V AC, 120 V AC, or 240 V AC. Alarm and supervisory relay con­tacts are available for control panel interface (alarm initiation), HVAC control, and other auxiliary functions. Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down. These detec-
tors are not designed for 2-wire applications.
D100-68-00 Revision Date: 12-06-99 1 I56-1525-000
For testing, the alarm can be enabled by a magnet activated test switch or by the optional remote test station. The duct smoke detector latches into alarm state when an alarm oc­curs. A green LED flashes to indicate power, a red LED signals local alarm indication, and optional accessories offer a variety of annunciation capabilities. The DH100ACDCA can be reset by a momentary power interrup­tion, the reset button on the front cover, the control panel, or remote reset accessory .
[2] Limitations Of Duct Smoke Detectors
WARNING
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUB­STITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system. System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. The DH100ACDCA Air Duct Smoke Detectors are listed per UL 268A & CAN/ULC-S529
WARNING
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The sys­tem safeguards should be discussed with your local fire pro­tection specialist.
WARNING
This device will not sense smoke unless the ventilation sys­tem is operating and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be protected from the elements and op­erated within ALL electrical and environmental specifica­tions listed in this manual. Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct.
[4] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2. T wo #10 machine screws for mounting
3. T wo sampling tube filters
4. One test magnet
5. Drilling template
6. T wo foam gaskets
7. Four #6-self tapping mounting screws for the metal sam-
pling tube and optional exhaust tube extension
8. T wo jack nuts
[3] Figure 1: Exploded View Of Duct Smoke Detector Components
FOAM
GASKETS
CONDUIT HOLES
PLASTIC
SAMPLING TUBE
PLASTIC SAMPLING TUBE
SELF-TAPPING SCREW
DETECTOR BOARD
SAMPLING TUBE
FILTERS
DETECTOR
COVER
COVER MOUNTING
SCREWS
9. One inlet tube end plug
10.One telescoping sampling tube
11. One #8 self-tapping screw for the telescoping sampling
tube
NOTE: For ducts over 11/2 feet, longer inlet sampling tubes
must be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the inlet tube required for different duct widths.
DETECTOR
HOUSING
TERMINAL STRIP
POWER BOARD
Tube Installation Chart:
Supplemental Duct Tube Holes Width
5 12”-14” 6 14”-16” 7 16”-18”
the supplemental tube matches the number as deter­mined in step 2. Secure with the #8 self-tapping screw into the bottom of the permanent tube.
NOTE: For ducts greater than 11/2 feet in width, refer to sec-
tions [5.4.1] and [5.4.2].
Figure 2. Sampling tube connected to duct smoke detector:
[5] Installation Sequence [5.1] Verify Duct Air Flow Direction And Velocity
Model DH100ACDCA detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these pa­rameters. If necessary , use a velocity meter to check the air velocity in the duct.
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template sup­plied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicat­ed on the template. Insert the two jack nut receptacles. Drive a #10 machine screw into jacket to flare the retainer, then back out the screw to use for detector mounting.
[5.2.1] Sampling Tube Installation for Ducts Less Than 11/2 Feet Wide (see Figure 2)
1. Remove the front cover.
2. Use the tube installation chart above to determine the set
screw setting.
3. Slide the sampling tube into the housing bushing.
4. Align the holes in the bushing with the holes in the sam-
pling tube. Make sure the number of exposed holes on
[5.3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two machine screws to screw the detector housing to the duct. CAUTION: Do not overtighten the screws.
Figure 3. Installation of foam gaskets over sampling tube bushings:
SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK.
D100-68-00 2 I56-1525-000
INLET TUBE END PLUG
AIR HOLES
ARROWS
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
AIR FLOW
DIRECTION
DETECTOR
HOUSING
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
INLET TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
EXHAUST
TUBE
INLET TUBE
INLET TUBE
EXHAUST
TUBE
DETECTOR
HOUSING
AIR FLOW
DIRECTION
EXHAUST
TUBE
INLET TUBE
DETECTOR
HOUSING
A.
B.
C.
D.
NOTE: Orientations C and D apply ONLY to metal sampling tubes.
HORIZONTAL MOUNTING OF HOUSING
VERTICAL MOUNTING OF HOUSING
WARNING
A78-2045-00
[5.4] Sampling Tube Installation for Ducts Greater Than 11/2 Feet Wide
The sampling tube is identified by a series of air inlet holes on the tube. A telescoping tube is included for ducts up to 18” in width. All other lengths must be purchased sepa­rately . Order the correct length, as specified in Table 1, for width of the duct where it will be installed. The exhaust tube is molded onto the base of the duct housing, and the A2440­00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not ex­tend at least 2 inches into the duct.
The inlet tube is always installed with the air inlet holes fac­ing into the air flow. To assist proper installation, the tube’s mounting flange is marked with arrows. Make sure the inlet tube is mounted so that the arrows point into the air flow (see Figure 4). Figure 5 shows the various combinations of tube mounting configurations with respect to air flow. Mount­ing the detector housing in a vertical orientation is accept­able, provided that the air flows directly into the sampling tube holes as indicated in Figure 4.
Table 1. Inlet tubes required for different duct widths:
Outside Duct Width Inlet Tube Required
1 to 2 ft. ST-1.5 2 to 4 ft. ST-3 4 to 8 ft. ST-5
8 to 12 ft. ST-10
[5.4.1] Installation For Ducts Greater Than 11/2
Feet But Less Than 8 Feet Wide
Figure 4. Air duct detector inlet sampling tube:
A78-2047-00
Figure 5. Tube mounting configurations with varying air flow direction:
In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube ex­posed to the air stream.
1.
If the tube is longer than the width of the air duct,
hole in the duct opposite the hole already cut for the inlet tube. Make sure the hole is 1” to 2” below the inlet hole on the opposite side of the duct to allow moisture drainage away from the detector.
of the air duct,
install the end plug into the inlet tube as
If the tube is shorter than the width
shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct detector.
2. Slide the tube into the housing bushing that meets the air
flow first. Position the tube so that the arrows point into the air flow.
3. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1” t o 2 ” of the tube extend outside the duct. Plug this end with the end plug and tape closed any holes in the protruding section of the tube. Be sure to seal the
duct where the tube protrudes.
D100-68-00 3 I56-1525-000
drill a 3/4
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install inlet tubes in ducts more than 8 feet wide,
work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accomplished by using the ST-10 inlet sampling tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4 and support the end opposite the duct smoke detector.
Install the inlet tube as follows:
1. Drill a 3/4” inch hole in the duct directly opposite the hole
already drilled for the inlet tube. Make sure the hole is 1 t o 2”below the inlet hole on the opposite side of the duct to allow for moisture drainage.
2. Slide the inlet tube with the flange into the housing bush­ing that meets the air flow first. Position the tube so that the arrows point into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other sections of the in­let tube to the section already installed using the 1/2-inch conduit fittings supplied. Make sure that the holes on both of the air inlet tubes are lined up and facing into the
Loading...
+ 5 hidden pages