Greyline TTFM 6.1 User Manual

Page 1
USER'S GUIDE
Installation & Operation
Instructions
Transit Time Flow Meter
Model TTFM 6.1
www.greyline.com
Manual Series A.1.6
Page 2
Note: This page has been left blank intentionally.
Page 3
TTFM 6.1 Transit Time Flow Meter
INDEX
CONNECTIONS ...................................................................................................................................... 4
KEYPAD SYSTEM .................................................................................................................................. 6
MENU SYSTEM ...................................................................................................................................... 7
ICONS ...................................................................................................................................................... 8
MESSAGE ICON ..................................................................................................................................... 9
STATUS ................................................................................................................................................... 9
PASSWORD ........................................................................................................................................... 11
MENU SELECTIONS ............................................................................................................................ 11
UNITS/MODE ........................................................................................................................................ 12
SET UP ................................................................................................................................................... 14
CALIBRATION ..................................................................................................................................... 17
RELAY PARAMETERS ........................................................................................................................ 19
DATA LOGGING .................................................................................................................................. 20
COMMUNICATION (OPTIONAL) ...................................................................................................... 22
SPECIAL FUNCTIONS ......................................................................................................................... 24
TYPICAL SENSOR INSTALLATION .................................................................................................. 27
SENSOR MOUNTING ........................................................................................................................... 30
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B1 KIT .......................................................... 31
1 CROSS INSTALLATION OVERVIEW – TMK-B1 KIT ................................................................... 35
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B21 OR TMK-B22 KIT ................................ 42
1 CROSS INSTALLATION OVERVIEW – TMK-B21 OR TMK-B22 KIT ........................................ 46
SENSOR MOUNTING/COUPLING RECOMMENDATIONS ............................................................ 53
ENCLOSURE INSTALLATION ........................................................................................................... 54
FIELD TROUBLESHOOTING .............................................................................................................. 55
COMMON QUESTIONS AND ANSWERS .......................................................................................... 58
APPLICATIONS HOTLINE .................................................................................................................. 60
PRODUCT RETURN PROCEDURE .................................................................................................... 60
SPECIFICATIONS ................................................................................................................................. 64
APPENDIX A - CONVERSION TABLE .............................................................................................. 65
PIPE CHARTS ........................................................................................................................................ 66
APPENDIX C – LIQUID SPEED OF SOUND ...................................................................................... 71
APPENDIX D ......................................................................................................................................... 78
IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications. Please read this manual carefully before installation and operation. Any unauthorized repairs or modifications may result in a suspension of the warranty. If this product is not used as specified by the manufacturer, protection may be impaired.
Available in Adobe Acrobat pdf format
Page 4
TTFM 6.1 Transit Time Flow Meter
CONNECTIONS: POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz
10VA. No adjustments are necessary for voltages within this range. Connect L (Live) N (Neutral) and AC Ground.
Optional DC input model requires 9-32 VDC/10 Watts. Connect to + and - terminals. Optional Thermostat and Heater modules are available rated for specifically 115 VAC or specifically
230 VAC. IMPORTANT NOTE: To comply with electrical safety standards, AC power input and relay connection
wires must have conduit entry to the instrument enclosure. Installation requires a switch, overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections. Note: Use of instrumentation over 40°C ambient requires special field wiring. Note: Some models feature a user replaceable fuse. Fuse is 2 Amp 250V (T2AL250V), located on the
power supply.
Page 5
100-240 VAC Meter CONNECTIONS
TTFM 6.1 Transit Time Flow Meter
Page 6
TTFM 6.1 Transit Time Flow Meter
KEYPAD SYSTEM
The diagram on page 7 shows the TTFM 6.1 menu system. Arrows show the four directions to leave a menu box. Pressing a corresponding keypad arrow will move to the next item in the direction shown. Move the cursor (highlighted) under numerals and increase or decrease numerals with the and keys.
To store calibration values permanently (even through power interruptions), press the button.
Page 7
--24 hr log----------
USG/m
BPS 9600
-- -------
%
4.00 USG/m
emperature
Date Feb. 12/20
10
Total 50138 USG
34.82 USG/m Average
52.20 USG/m Maximum 11:08:00 Max Time
0.000 USG/m Minimum
9:15:00 Min Time
--Messages---------­L Data og Logging
dLog Use 0.00000%
Sensor Good
0.00
Tot 20130 USG Relays 1 2 3 4 5 6
--Status------------
Velocity ft/s
0.00 Flow 0.00 USG/m Min Flow 4.00 USG/m Signal Strength 100% Exp. SOS 4900 ft/s Meas. SOS 4900 ft/s
MENU SYSTEM
*
--Password----------
Password 0000
TTFM 6.1 Transit Time Flow Meter
--Units/Mode-------­Mode Flow
Linear in Volume USG Multiplier x1 Decimal 0s Velocity ft/s Flow USG/m Decimal 2s T F
Setup------
r SE16B
Senso
--Menu-------------­Units / Mode
Setup Calibration Relay Parameters Data Logging Communication Special Functions Simulation Configuration
Angle 37 Fluid Water Temp Mode Fixed Temp 77.0 F Pipe PVC OD 4.5000 in Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal Strength
100
--Calibration------­Mode Flow
20mA 500.00 USG/m 4mA 0.00 USG/m LOS Time 10 sec Min Flow Damping Mode FIR Percent 10% Window 1.0 ft/s Cal Constant 1.00
--Relay Parameters--
Relay 1
Function Flow On 1000 USG Off 0.000 USG
--Data Logging-------
Log Site ID 01
Mode Flow File Format .LG2 Date 6 7Jun 2 /201 Time 12:28:41 Interval 30sec Data Log Logging
--Communication-----
Protocol Modbus Address 001
Parity Even Stop Bits 1
°
optional features
* Menu only appears if "New Password" has been
changed from 0000 in "Special Functions" menu.
--Special Functions-
Language English
Analog Out 4-20mA
Backlight High Reset Totalizer NO Neg. Totals NO Rev. Flow OFF Capture Par NO Capture WF NO Restore Defaults NO New Password 0000
--Simulation--------
Test Actual Flow /m 250USG
Flow 4-20mA 5.60mA
Relays 1 2 3 4 5 6
--Configuration-----
Serial# 12345 Utility 1.25.0 .16
1. Transit Time 38.1
CommBoard 1. . 21 19 Relays 2
Analog Out 1
Page 8
ICONS
TTFM 6.1 Transit Time Flow Meter
1.
1.
1.
1.
2.
2.
2.
2.
3.
3.
4. USB file download .ing
Message waiting. Press . from main page to view
Data logging .off
Data logging .on
File download completed.
Download Error.
TTFM Echo OK.
TTFM - , Empty Pipe .Low Signal / No Echo or high Aeration
TTFM - No Sensors Attached / Wrong Settings
Page 9
TTFM 6.1 Transit Time Flow Meter
USG/m
0.00
Tot 20130 USG Relays 1 2 3 4 5 6
--Status-----------­Velocity ft/s 0.00
Flow 0.00 USG/m Min Flow 4.00 USG/m Signal Strength 100% Exp. SOS 4900 ft/s Meas. SOS 4900 ft/s
MAIN DISPLAY
The Main Display shows the units selected from the Units/Mode menu, flow rate or velocity rate being measured, totalizer, totalizer multiplier, and relay states. The TTFM 6.1 will go to this display after start-up.
MESSAGE ICON
Press from the Main Display to view status of the data logger and error/warning messages provided by the instrument. The Message Icon will appear on the Main Display if error messages are being generated by the instrument. Press to return to the Main Display.
STATUS
Press from the Main Display to view Status of the measurement. Press to return to the Main Display.
Velocity Displays flow velocity in ft/s or m/s, selected in the
Units/Mode menu.
Flow Displays flow rate in units selected in the Units/Mode
menu. A list of flow rate units is provided in the Units/Mode section of the manual.
Min Flow Displays a read-only value for the minimum flow cutoff,
in units which match the Flow selection. Measured flow rates below the Min Flow will result in the displayed flow rate on the LCD display to be 0.0. This parameter is used to suppress electrical noise at zero flow conditions, and it is typically set to the flow rate equivalent of 0.1 ft/sec in the programmed pipe size. The Min Flow can be adjusted in the Calibration menu.
Signal Strength Displays magnitude of signal being received by the
ultrasonic sensors. 100% is the ideal signal strength. Signal strengths less than 100% could indicate poor pipe conditions (corrosion), highly aerated water, or programmed setup parameters which don’t closely match field conditions. Consideration should be made to use 1-cross installation method in such cases, if not already using it.
Page 10
Status (cont.)
TTFM 6.1 Transit Time Flow Meter
--Status-----------­Velocity ft/s 0.00
Flow 0.00 USG/m Min Flow 4.00 USG/m Signal Strength 100% Exp. SOS 4900 ft/s Meas. SOS 4900 ft/s
Exp. SOS Displays the expected fluid speed of sound
measurement, in units that match the Velocity. The expected speed of sound is based on the pipe, fluid, and temperature selection in the Setup menu.
Meas. SOS Displays the measured fluid speed of sound, in units that
match Exp. SOS. The meter calculates this value based on the time it takes for the signal to arrive from one transducer to another. Large differences between expected and measured speed of sound (> 10%) typically indicate an error in the setup of the instrument. Verify the following are correct in the Setup menu and with the physical installation of the transducers:
- Pipe Material
- Pipe OD
- Pipe Wall Thickness
- Liner Type
- Liner Thickness
- Fluid Type
- Fluid Temperature
- Crossings
- Separation Distance
Page 10
Page 11
TTFM 6.1 Transit Time Flow Meter
24 HR LOG
Press from the Main Display to view a formatted flow report. Press to scroll down one day or repeatedly to scroll to a specific date. Up to 365 days will be stored. Newest date will overwrite the oldest. Press to return to the Main Display.
IMPORTANT: Inserting a USB drive into the meter while on this screen will transfer 24 HR Log data to the USB drive in .csv format.
PASSWORD
The Password (a number from 0000 to 9999) prevents unauthorized access to the Calibration menu.
From the Main Display press the key to get to Password. Factory default password is 0000 and if it has not been changed, this screen will be bypassed completely.
A new password can be stored by going to the Special Functions New
Password menu.
If a user password is required, press to place the cursor under the first digit and or to set the number, then to the second digit, etc. Press  or to proceed
to the Menu Selections screen.
MENU SELECTIONS
The Menu selections page is used to navigate to specific menus which are described in more detail on the following pages.
Press or to navigate to different menus, and to enter the selected menu.
Page 11
Page 12
store your selection then the
to the next menu
item
.
next menu item.
as an example. Press
to store your selection then
to the next menu i
tem.
menu item.
selection then
to the next menu item.
--Units/Mode-------­Mode Flow
Linear in Volume USG Multiplier x1
Decimal 0s
Velocity ft/s Flow USG/m
Decimal 2s
emperatureT F
TTFM 6.1 Transit Time Flow Meter
UNITS/MODE
At Mode, press the and then the or to select Flow or Velocity. Flow mode displays the flow rate in engineering units (e.g. gpm, litres/sec, etc.) Press the to store your selection then the to the next menu item.
At Linear press the key and then the or to select your units of measurement. The Linear units define what units the pipe dimensions and sensor spacing will be displayed in. Typically inches or mm is selected. Press the to
At Volume, press the  and then the  or  to select units for volume. Note: “bbl” denotes US oil barrels. Press the to store your selection then the to the
At Multiplier, press the  and then the  or  to select the totalizer multiplier. Multipliers are used when resolution down to single digit is not required, or when you don’t want to convert from gallons to thousands of gallons,
At Decimals (Volume), press the  and then the  or  to select the number of decimal points to be present on the totalizer display on the LCD screen. Default = 0. Options = 0, 1, 2. Press the to store your selection then the to the next
At Velocity, press the and then the  or  to select the engineering units for flow velocity and sonic velocity of the fluid. Press  to store your
Page 12
Page 13
TTFM 6.1 Transit Time Flow Meter
menu item
, orto
exit back to the Menu Selection screen
.
UNITS/MODE (cont.)
At Flow, press the and then the or to select the engineering units for flow rate. Press to store your selection then to the next menu item.
Available Flow Rate Engineering Units:
Abbreviation Description Abbreviation Description
USG/d US gallons per day L/d liters per day USG/h US gallons per hour L/h liters per hour USG/m US gallons per minute L/m liters per minute USG/s US gallons per second L/s liters per second ft3/d cubic feet per day m3/d cubic meters per day ft3/h cubic feet per hour m3/h cubic meters per hour ft3/m cubic feet per minute m3/m cubic meters per minute ft3/s cubic feet per second m3/s cubic meters per second bbl/d barrels per day (1 bbl = 42 USG) IG/d Imperial gallons per day bbl/h barrels per hour (1 bbl = 42 USG) IG/d Imperial gallons per day bbl/m bbl/d USMG/d US million gallons per day IMG/d Imperial million gallons per day USMG/h US million gallons per hour IMG/h Imperial million gallons per hour USMG/m US million gallons per minute IMG/m Imperial million gallons per minute USMG/s US million gallons per second IMG/s Imperial million gallons per second
barrels per minute (1 bbl = 42 USG) barrels per second (1 bbl = 42 USG)
IG/d Imperial gallons per day IG/d Imperial gallons per day
At Decimals (Flow), press the  and then the  or  to select the number of decimal points to be present on the flow rate display on the LCD screen. Default =
2. Options = 0, 1, 2. Press the to store your selection then the to the next menu item.
At Temperature, press the and then the or to select units for temperature. Press the to store your selection then the to go back to another
Page 13
Page 14
TTFM 6.1 Transit Time Flow Meter
-- -------Setup-----­r SE16B Senso
Angle 37°
Fluid Water Temp Mode Fixed
Temp 77.0 F
Pipe PVC
OD 4.5000 in
Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal
Strength100%
SET UP
Press or to position curser at Setup, and to enter. Use  or  to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Sensor Select
Angle
Choose SE16B.
Select angle which matches the transducer pair connected to the TTFM. Options: 35, 37, 39, and 41. Angle is determined by the part number on the SE16-B transducer label. Guide:
Part Number on SE16-B Label Corresponding Transducer Angle
SE16-B-35 35 SE16-B-37 37 SE16-B-39 39 SE16-B-41 41
Fluid
Vel@25C
Select fluid type.
When Fluid = Other, enter the fluid velocity at 25C from table or other reference. Engineering units may be m/s or ft/s depending on Units menu programming.
dV/C
Temp Mode
Temp
Pipe
Pipe Vel
OD
Wall
When Fluid = Other, Enter fluid velocity adjustment factor over change in temperature in units of m/s or ft/s per °C.
Choose Fixed.
Enter fluid operating temperature in displayed engineering units.
Select pipe material.
When Pipe = Other, enter pipe material speed of sound (consult factory).
Highlight the digits and then or  to change the numbers and decimal point. Pipe OD should be entered as the exact outside diameter of the pipe where the sensor is mounted. Refer to the Pipe Charts Appendix in this manual for outside diameter of common pipe types and sizes.
Enter pipe wall thickness. Pipe wall thickness should be entered as the exact wall thickness of the pipe where the sensor is mounted. Refer to the Pipe Charts Appendix in this manual for wall thicknesses of common pipe types and sizes.
Lining
Select liner material.
Page 14
Page 15
TTFM 6.1 Transit Time Flow Meter
2-24
Crossings = 2
> 24Crossings = 1
= 1 in cases such as these.
-- -------Setup-----­r SE16B Senso
Angle 37°
Fluid Water Temp Mode Fixed
Temp 77.0 F
Pipe PVC
OD 4.5000 in
Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal
Strength100%
SET UP (cont.)
Vel
Thick
Crossings
When Lining = Other, enter speed of sound of liner (consult factory).
When Lining ≠ None, enter liner thickness.
Crossings 1 = Z mounting
Crossings 2 = V mounting
Crossings 4 = W mounting
Nominal Pipe Size, Inches Recommended Crossings
Zero Tare
Sens Space
Velocity
Older pipes are often degraded or scaled on the inside. These conditions can hinder the ability to receive a strong signal when Crossings = 2. Greyline suggests starting with Crossings
Used to calibrate zero-flow measured by the TTFM 6.1 in process. Flow in the pipe should be confirmed as 0 before enabling, or significant errors in flow accuracy could occur.
Set Calibration/Damping to 0%, and under no flow conditions and with a full pipe, select Yes to force readings to zero.
After sensor, angle, fluid, and pipe material are defined, this displays the calculated sensor spacing. Also called the separation distance. The sensors will be set to this dimension when installed on the pipe, as described later in this manual.
Displays the measured velocity after the sensors have been connected at the specified separation distance.
Page 15
Page 16
TTFM 6.1 Transit Time Flow Meter
-- -------Setup-----­r SE16B Senso
Angle 37°
Fluid Water Temp Mode Fixed
Temp 77.0 F
Pipe PVC
OD 4.5000 in
Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal
Strength100%
SET UP (cont.)
Signal Strength
Displays magnitude of signal being received by the ultrasonic
sensor. Should be 100% under ideal operating conditions. Signal strengths less than 100% do not indicate that the meter is not reliable, however, the meter may be more susceptible to complete signal loss should process conditions like entrapped air worsen. When signal strength is less than 100%, consideration should be made to using 1-cross mounting method if this is not the current mounting mode.
Page 16
Page 17
TTFM 6.1 Transit Time Flow Meter
--Calibration------­Mode Flow
20mA 500.00 USG/m
4mA 0.00 USG/m LOS Time 10 sec Min Flow 4.00 USG/m Damping
Mode FIR
Percent 10%
Window 1.0 ft/s Cal Constant 1.00
CALIBRATION
Press or to position curser at Calibration menu, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Mode
Displays the Mode which was selected in the Units/Mode menu. This is read-only.
20mA
Press  then  or  to change the numbers and decimal point position. Use this menu to set the corresponding flow rate that will be represented by 20mA analog output. If maximum flow is unknown, enter an estimated flow rate and observe actual flow to determine the correct maximum value. Any velocity or flow rate up to +40 ft/sec (12.0 m/sec) may be selected.
4mA
Press  then  or  to set the flow rate corresponding to 4mA analog output. This setting may be left at zero or can be raised to any value less than the 20mA setting, or lowered to any velocity or corresponding flow rate down to -40 ft/sec (-12 m/sec).
LOS Time
Use LOS Time to suppress intermittent loss of signal. Example: systems with high concentrations of undissolved gasses will cause fluctuations in signal strength when the gasses move past the ultrasonic signal. If a complete loss of signal is experienced, the TTFM 6.1 will hold the last valid reading for the duration of the LOS Time. If the signal strength returns before the LOS Time is expired, because the ultrasonic signal is no longer being impeded, the meter will return to normal operation automatically. If signal strength does not return after the LOS Time has expired, then the meter will report zero flow on the LCD display and outputs, and produce a Low Signal alarm. Default LOS Time is 30 seconds, and the value can be set between 0 and 99 seconds.
Min Flow
Flow rates below this setting will be displayed as zero flow. Default flow rate is 0.1 ft/sec for the pipe size programmed in the Setup menu.
Page 17
Page 18
TTFM 6.1 Transit Time Flow Meter
av
erage, both the FIR and LOW PASS filter behave the same.
--Calibration-------
Mode Flow
20mA 500.00 USG/m
4mA 0.00 USG/m LOS Time 10 sec Min Flow 4.00 USG/m Damping
Mode FIR
Percent 10%
Window 1.0 ft/s Cal Constant 1.00
CALIBRATION (cont.)
Damping
Mode
Choose between OFF, FIR (Default), or LOW PASS.
When measured flows are outside the Window of the running average, the FIR filter will reduce the damping average so that a fast response can be made to the sudden change in flow rate.
The LOW PASS filter will ignore measured flow rates outside the Window, while holding the running average, until there are enough data points outside the Window to cause a step­response to the new measured value.
While measured flows are within the Window of the running
Percent
Higher percentages increase the number of measurements which are averaged together to produce a stable flow reading. Higher percentages also increase the time it takes for the meter to make a step-response to the measured flow rate outside the Window in the LOW PASS Mode.
Window
Defines the Window around the running average, in units of Velocity set in the Units/Mode menu. Measurements made inside the Window are added to the running average, and measurements outside the Window effect the response of the meter as described in the Mode section.
Cal Constant
Calibration constant defined when the TTFM was calibrated at the Greyline factory.
Press to return to Menu Selections.
Page 18
Page 19
TTFM 6.1 Transit Time Flow Meter
or
for this to work properly.
--Relay Parameters--
Relay 1
Function Flow On 1000 USG Off 0.000 USG
RELAY PARAMETERS
Press or to position curser at Relay Parameters, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Relay
Press  and  or  to select a corresponding relay number (2 relays are standard, 4 additional are optional).
Function
Pulse
Press  or  to select Off, On, Pulse,
Direction, or Flow.
Press  and set digits to the flow volume increment required between relay pulses. Use this feature for remote samplers, chlorinators or totalizers. Minimum time between pulses is
2.25 seconds and pulse duration is 350 milliseconds.
Return to Relay and change settings for each relay number.
Press to return to Menu Selections.
Direction
When flow is in the positive direction, the relay will be disengaged, when flow is negative, the relay engages. Note: Rev. Flow in the Special Functions menu must be ON
INVERT
Flow
Mode Select Pump
Pump mode provides separate On/Off settings where the
relay will energize at one flow rate and de-energize at another.
On Highlight the numerals and press or to set digits to
the required relay On set point.
Off set digits to the required Off set point.
Page 19
Page 20
TTFM 6.1 Transit Time Flow Meter
DATA LOGGING
Press or to position curser at Data Logging, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Log Site ID Enter a number from 00 to 99. The site ID will become part of
the downloaded file name to help distinguish downloads from different instruments. Press to store the setting.
Mode Select Velocity (e.g. ft/sec or m/sec) or Flow (e.g. USGPM or
l/sec). Press to store the setting. This setting cannot be changed after a log was started. To change, first stop the log, then change the mode.
File Format Choose .LG2 to download data in .lg2 format for viewing on
Greyline Logger software. Choose .CSV to download data in .csv format for import directly to Excel. This menu option can be changed at any time without adversely affecting existing data.
Date Press , and or to scroll and select Month, Day and
Year. Press to store the setting.
Time Press , and or to select the current time in Hours,
Minutes and Seconds. Press to store the setting.
Interval Press or to select the logging interval. Press to store
the setting. Greyline recommends choosing an interval which will give you as much resolution as required and no more. Choosing too often of an interval for what is required will result in larger data files, which may take a long time to download to USB. Reference page 18 for specific download times. In critical installations, data should be downloaded often.
Data Log Stop, Start or Delete the log file. Press or to select Delete
and to delete the log file. Press or to select Start and to start the logger.
Important Note: You MUST Delete an old log and Start a new log AFTER having made changes to Log Site ID, Mode, Date, Time and/or Interval for those changes to be applied.
Important Note: Changing any of the parameters in the Units/Mode menu will start a new log. It is recommended that you Delete and start a new log after changing any Units/Mode settings.
Page 20
Page 21
TTFM 6.1 Transit Time Flow Meter
RETRIEVING LOG FILE
Plug a USB Flash Memory Drive (one is included with the TTFM 6.1) into the USB output port on the Panel of the meter. The instrument display will show the data download icon until the log file is transferred to the memory card. The USB flash drive may be removed when the icon for download successful appears.
Download file names will appear in this format:
Tag is set according to the Log Site ID entered in the instrument Data
Logging menu.
Download letter will be A for the first download from an instrument. B for the second, then C etc. At the letter Z a - character will appear indicating that the maximum number of downloads for that instrument are on the USB flash drive. Older files can be erased or moved from the flash memory drive or a new memory drive can be used.
Note: Downloading files in .lg2 format will take approximately 35 seconds per
1% of internal log memory used. Downloading files in .csv format will take approximately 8 minutes per 1% of internal log memory used.
OPENING .LG2 FILES
Install Greyline Logger on your PC or laptop. Select File/Open/Instrument Log (.log) to open the log file from your USB flash drive. Greyline Logger software is available on Greyline’s website, www.greyline.com. Data can also be converted to .CSV via Greyline Logger software.
OPENING .CSV FILES
Use a datasheet program such as Microsoft Excel® to import data in a comma delimited format. Use Excel to manipulate or graph data.
Page 21
Page 22
TTFM 6.1 Transit Time Flow Meter
setting.
COMMUNICATION (Optional)
Press or to position curser at Communication, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
MODBUS Protocol Information:
Transceiver: 2-wire, half-duplex Data format: 8 Data Bits Floating Point Byte Order: ABCD
Termination: Jumper JP1 selectable 120Ω resistor. TB1 & TB2 = OFF,
TB2 & TB3 = ON
Biasing: None
HART® (Highway Addressable Remote Transducer) Protocol Information:
HART Version: 7.0
Device Description Files:
DD files allow the user’s handheld HART communicator to fully configure the TTFM 6.1 Greyline provides DD files for the Emerson 475 Communicator. The files are included in the USB drive provided with your TTFM 6.1 meter. You may also request the files from Greyline by calling or emailing us at [email protected]. Warning: The TTFM 6.1 and associated DDs are pending certification from the Fieldcomm Group.
Connections: HART Protocol uses a digital signal superimposed on the 4-
20mA output. When the 4-20mA output of the TTFM 6.1 is
connected with a load resistor (230Ω to 600Ω), the HART
communicator can be connected on the loop in order to communicate.
Protocol
Address
(Modbus)
Choose MODBUS or HART.
Device address for the TTFM. Valid range: 001-247 (Default:
001). This number should be unique across the bus. Press or to scroll, to select digits, and press to store the
Page 22
Page 23
TTFM 6.1 Transit Time Flow Meter
found in separate TTFM 6.1 Serial Communications Manual.
COMMUNICATION (Optional) (cont.)
BPS
(Modbus)
Baud rate for the MODBUS communications. Press  or to select, and to store the setting. Options: 4800, 9600, 19200, 38400, 57600, 76800, and 115200 (Default: 9600).
Parity
(Modbus)
Error checking parity for the MODBUS communications. Press or to select, and to store the setting. Options: None, Even, and Odd (Default: Even).
Stop Bits
(Modbus)
Press  or  to select, and to store the setting. Options: 1 or 2 (Default: 1).
Note: The Modbus register table, and HART configuration instructions can be
Page 23
Page 24
TTFM 6.1 Transit Time Flow Meter
--Special Functions-
Language English Analog Out 4-20mA Backlight High Reset Totalizer NO
Neg. Totals NO Rev. Flow OFF Capture Par NO
Capture WF NO
Restore Defaults NO
New Password 0000
SPECIAL FUNCTIONS
Press or to position curser at Special Functions, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Language
Analog Out
Backlight
Select English, French or Spanish
Select 4-20mA or 0-5V mode for the analog output.
Select High, Medium or Low for continuous backlight brightness.
Select Key Hi/Lo for high backlight lasting 1 minute after a keypress, and then Lo backlight until a key is pressed again.
Select Key High, Med or Low for backlight lasting 1 minute after a keypress and then backlight off until a key is pressed again.
Reset Totalizer
Select Yes to erase and restart the totalizer at zero.
Negative Totals
Rev. Flow
Capture Par
Select Yes to have reverse flow readings deducted from the totalizer. Select No to totalize forward flow only and ignore reverse flow.
Select On to enable flow direction measurement. Select Off to disable flow direction measurement so that flow in either direction is displayed and output as positive values. Select Invert to invert the sense of the flow measurement.
This function captures the programming parameters in the meter. Select Yes, wait for Insrt USB to appear, then insert a USB drive into the USB port to transfer the parameters. After Saving flashes, Done will appear on the screen, meaning it is safe to remove the USB,
Page 24
Page 25
to be sent to Greyline.
--Special Functions-
Language English
Analog Out 4-20mA
Backlight High
Reset Totalizer NO
Neg. Totals NO Rev. Flow OFF Capture Par NO
Capture WF NO
Restore Defaults NO
New Password 0000
SPECIAL FUNCTIONS (cont.)
Capture WF
This function should only be used when instructed by a Greyline representative to do so. The function captures the ultrasonic signal so that it can be evaluated by Greyline.
Select Yes to start the waveform download process. After pressing Yes , the screen will flash Working for approximately 20 seconds, until the message
Insrt USB appears. When Insrt USB is on the
screen, connect a flash drive to the USB port on the front of the meter. The screen will flash Saving for a couple seconds, and then return to Done . The waveform is now stored on your flash drive and ready
TTFM 6.1 Transit Time Flow Meter
Restore Defaults
Select Yes to erase all user settings and return the instrument to factory default settings. Note: does not reset factory calibration values.
New Password
Select any number from 0000 to 9999. Default setting of 0000 will allow direct access to the calibration menus. Setting any password other than 0000 will require the password to be entered to access the calibration menus.
Press to return to Menu Selections.
Page 25
Page 26
TTFM 6.1 Transit Time Flow Meter
screen.
SIMULATION
Press or to position curser at Simulation, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Changes made in the Simulation menu exercise the 4-20mA output, digital display and control relays.
Simulate a Flow /Velocity reading. Press and then or to change the simulated output. Press to begin simulation. The 4-20mA output and relay states will be displayed on the screen below.
Press the to terminate simulation and return to the Menu Selections
Page 26
Page 27
TYPICAL SENSOR INSTALLATION
TTFM 6.1 Transit Time Flow Meter
Page 27
Page 28
TTFM 6.1 Transit Time Flow Meter
Pipe Preparation and Bracket Mounting
Prepare an area 2" wide by 4" long (50mm x 100mm) for each sensor bonding by removing loose paint, scale and rust. The objective of site preparation is to eliminate any discontinuity between the sensor and the pipe wall, which would prevent acoustical coupling. A sanding block is included with every meter to facilitate proper pipe preparation.
A Sensor Mounting Kit is supplied with each Greyline flow meter. It includes recommended coupling compound and a stainless steel mounting bracket with adjustable pipe straps. Use the Alignment Bar (included) to align sensor brackets for V and W mode mounting.
IMPORTANT: The SE16-B transit-time transducers have arrows on the top of them. These should face each other at installation.
Page 28
Page 29
TTFM 6.1 Transit Time Flow Meter
SENSOR COUPLING
For permanent or temporary bonding, the following are recommended:
a) Super Lube® (supplied) Additional supply: order Greyline Option CC-SL30 or your local home improvement store. b) Water-based sonic compound: Order Greyline Option CC30 c) Electrocardiograph gel d) Petroleum gel (Vaseline)
The above are arranged in their order of preferred application. Option d is only good for temporary bonding at room temperature. DO NOT USE: Silicon RTV caulking compound (silicon rubber).
Use the pipe clamp and rail (supplied) as illustrated on previous page. Apply Super Lube® to the colored face of the sensor. A bead, similar to toothpaste on a toothbrush, is ideal. Do not overtighten (crush the sensor).
The sensor must be fixed securely to the pipe with coupling material between the sensor face and the pipe. Sensor installation with excessive coupling compound can result in gaps or voids in the coupling and cause errors or loss of signal. Insufficient coupling compound will create similar conditions.
Over time temporary coupling compounds (e.g. Petroleum Gel) may gradually sag away from the sensor resulting in reduced signal strength and finally complete loss of signal. Warm temperatures, moisture and vibration will accelerate this process. Super Lube® as supplied with the TTFM 6.1 (and available from Greyline Instruments or home improvement stores) is recommended for permanent installations.
Transducer Installation in Wet Locations
The TTFM 6.1 Transit Time Flowmeter transducers are rated for accidental submersion up to 10 psi (0.75 bar). The flowmeter will continue to operate and measure flow accurately during periods of submergence. Plastic seal jackets on the cables must be filled with coupling compound to provide additional moisture protection for the BNC cable connectors.
Page 29
Page 30
TTFM 6.1 Transit Time Flow Meter
SENSOR MOUNTING LOCATION
The position of the sensor is one of the most important considerations for accurate flow measurement. The same location guidelines apply to Transit Time as most other flow meter technologies.
VERTICAL OR HORIZONTAL PIPE - Vertical pipe runs are acceptable, and the transducers can be mounted in any orientation around the pipe. Downward flow should be avoided in case the pipe becomes partially filled or aerated. On Horizontal pipes and liquids with high concentrations of gas or solids, the sensors should be mounted on the side (1 to 5 o’clock positions) to avoid concentrations of gas at the top of the pipe, or solids at the bottom.
STRAIGHT RUN REQUIREMENTS – For best results, the transducers must be installed on a straight run of pipe, free of bends, tees, valves, transitions, insertion probes and obstructions of any kind. For
most installations, ten straight unobstructed pipe diameters upstream and five diameters downstream of the transducers is the minimum recommended distance for proper operation.
Additional considerations are outlined below.
• Do not, if possible, install the transducers downstream from a throttling valve, a mixing tank, the discharge of a positive displacement pump or any other equipment that could possibly aerate the liquid. The best location will be as free as possible from flow disturbances, vibration, sources of heat, noise, or radiated energy.
• Avoid mounting the transducers on a section of pipe with any external scale. Remove all scale, rust, loose paint, etc., from the location prior to mounting the transducers. A sanding block is included with every meter to facilitate proper pipe preparation.
• Do not mount the transducers on a surface aberration (pipe seam, etc.).
• Do not mount transducers from different ultrasonic flow meters on the same pipe.
• Do not run the transducer triaxial cables in common bundles with cables from other instrumentation. You can run these cables through a common conduit ONLY if they originate at the same flow meter.
• Never mount transducers under water.
IMPORTANT NOTE: In some cases, longer straight runs may be necessary where the transducers are placed downstream from devices which cause unusual flow profile disruptions or swirl. For example: modulating valves, or two elbows in close proximity and out of plane.
Page 30
Page 31
TTFM 6.1 Transit Time Flow Meter
SEPARATION DISTANCE (Sensor Spacing Distance)
Separation distance is automatically calculated by the TTFM 6.1 based on parameters entered in the Setup menu. Sens Space is parameter where this distance is given, and it is located in the Setup menu. Document this value for the following transducer installation procedure.
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B1 Kit
1. Prep the pipe per instructions on page 28, and mind the installation location requirements on page 30. Clean the location where the sensor is to be mounted on the opposite side of the pipe after we’ve marked where it will be installed. Picture below shows a very clean ductile iron pipe which did not require much cleaning. The outside paint is very well bonded and did not need to be removed:
2. Install the stainless steel mounting brackets on the pipe. Position them at approximately the correct separation distance. Exact measurement is not required at this time. Tip: Use a 5/16” nut driver to tighten the hose clamps.
Procedure continued on the next page…
Page 31
Page 32
TTFM 6.1 Transit Time Flow Meter
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B1 Kit (Cont.)
3. Use alignment bar to ensure the brackets are parallel. Completion of steps 2 & 3 is shown below.
4. Mark the position of the permanent bracket on the pipe. This is the bracket that will not be adjusted, and will be used as the reference for the separation distance and alignment. It is your choice which bracket is permanent. With a marker, mark the bracket position by placing the mark directly in front of the stainless side-rail.
Page 32
Page 33
TTFM 6.1 Transit Time Flow Meter
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B1 Kit (Cont.)
5. Measure the separation distance from the mark you created in step 4, and create a new mark on the pipe at the separation distance. It may be useful to mark your Greyline tape measure (included with every meter) at the separation distance point before marking the pipe. The marked pipe is shown below.
6. Move the non-permanent bracket to position at the mark you created at step 5, and tighten it completely. Apply coupling compound to the transducers, and install them in the brackets.
Tips for installing transducers:
a. Be sure the red knob on the brackets are loosened completely b. Put the transducer into the bracket by ensuring the bottom of the transducer and the
couplant does not touch the pipe as you slide it in. (Hover)
c. With the transducer hovering, tighten the red knob on the bracket until thight. The
transducer will be level with the surface of the pipe, and no grease will have smeared off.
(pictures of proper coupling application and finished installation on the next page)
Page 33
Page 34
TTFM 6.1 Transit Time Flow Meter
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B1 Kit (Cont.)
Proper coupling compound application:
Finished installation, ready for cable connection:
7. If you need to make fine adjustments (±0.25”) to the spacing at this point, you may do so by loosening the hose clamps slightly, and sliding the brackets while the transducers are installed inside them. Tighten hose clamps when done.
Page 34
Page 35
TTFM 6.1 Transit Time Flow Meter
SEPARATION DISTANCE (Sensor Spacing Distance)
Separation distance is automatically calculated by the TTFM 6.1 based on parameters entered in the Setup menu. Sens Space is parameter where this distance is given, and it is located in the Setup menu. Document this value for the following transducer installation procedure.
1 CROSS INSTALLATION OVERVIEW – TMK-B1 Kit
To assist with the proper installation of the transducers in a 1 cross installation, we provide a kit with every meter, which consists of the following:
Sanding block Tape measure Mylar sleeve Duct tape Level Black Sharpie
Follow along with the 1 cross installation instructions on the following pages for a description of where to use these tools.
1. Prep the pipe per instructions on page 28, and mind the installation location requirements on page 30. Clean the location where the sensor is to be mounted on the opposite side of the pipe after we’ve marked where it will be installed. The picture below shows a very clean ductile iron pipe which did not require much cleaning.
Page 35
Page 36
TTFM 6.1 Transit Time Flow Meter
2. Install one of the stainless steel mounting brackets on the pipe. This will be the stationary bracket not being rotated to the opposite side of the pipe. For a horizontal pipe, position the bracket at 3 or 9 o’clock. Hold the level up to the top of the bracket to ensure the angle is correct. For vertical pipes, the bracket can be at any orientation about the pipe. Tip: Use a 5/16” nut driver to tighten the hose clamp. Install the second bracket at approximately the distance specified by the Sens Space value in the Setup menu.
3. Use alignment bar to ensure that the brackets are parallel. Completion of steps 2 and 3 is shown below.
Page 36
Page 37
TTFM 6.1 Transit Time Flow Meter
4. Mark the position of the bracket on the pipe. Mark both where the front of the bracket is, as well as the center of the bracket.
5. Measure the separation distance from the marks you created in step 4, and create new marks on the pipe at the separation distance. It may be useful to mark your Greyline tape measure at the separation distance before holding it up to and marking the pipe.
Page 37
Page 38
TTFM 6.1 Transit Time Flow Meter
6. Using the mylar sleeve included with the installation kit, wrap it around the pipe, keep it taut, and with the Sharpie, draw a line anywhere the sleeve overlaps:
7. Lay the mylar sleeve flat, use duct tape to help hold it flat if you need to, and use the tape measure to measure half way between the two marks created when you wrapped the mylar around the pipe:
Page 38
Page 39
TTFM 6.1 Transit Time Flow Meter
8. Position the marked mylar back on the pipe, with the overlap marks on the center line of the transducer bracket that will be rotated to the other side of the pipe. Be sure the mylar is parallel with the face of the transducer. Use duct tape to hold the mylar together and to the pipe. While the mylar is in this position, mark the opposite side of the pipe where the mylar is marked from step 7:
Page 39
Page 40
TTFM 6.1 Transit Time Flow Meter
9. Sand the pipe at this position if it needs to be prepped because of scale or rust. After prepped, move the bracket to this 1 cross mark, and tighten it in place. Apply coupling compound to the transducers and place them in the brackets:
Tips for installing transducers:
a. Be sure the red knob on the brackets are loosened completely. b. Put the transducer into the bracket by ensuring the bottom of the transducer and the
couplant does not touch the pipe as you slide it in (hover).
c. With the transducer hovering, tighten the red knob on the bracket until tight. The
transducer will be level with the surface of the pipe, and no grease will have smeared off from inserting the transducer in the bracket.
Proper coupling compound application:
Page 40
Page 41
Finished installation:
TTFM 6.1 Transit Time Flow Meter
10. If you need to make fine adjustments (±0.25”) to the spacing at this point, you may do so by loosening the hose clamps slightly, and sliding the brackets while the transducers are installed inside them. Tighten the hose clamps when done.
Page 41
Page 42
TTFM 6.1 Transit Time Flow Meter
SEPARATION DISTANCE (Sensor Spacing Distance)
Separation distance is automatically calculated by the TTFM 6.1 based on parameters entered in the Setup menu. Sens Space is parameter where this distance is given, and it is located in the Setup menu. Document this value for the following transducer installation procedure.
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B21 or TMK-B22 Kit
1. Prep the pipe per instructions on page 23, and mind the installation location requirements on page 25. Clean the location where the sensor is to be mounted on the opposite side of the pipe after we’ve marked where it will be installed. Picture below shows a very clean ductile iron pipe which did not require much cleaning. The outside paint is very well bonded and did not need to be removed:
Page 42
Page 43
TTFM 6.1 Transit Time Flow Meter
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B21 or TMK-B22 Kit (Cont.)
2. Install the spacer bar onto the right bracket as shown below:
3. Insert the spacer bar into the left bracket, and position the bracket at the separation distance referenced earlier. Tighten the spacer bar clamp at this position:
Page 43
Page 44
TTFM 6.1 Transit Time Flow Meter
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B21 or TMK-B22 Kit (Cont.)
4. Place the bracket assembly on the pipe, tighten it in place with the two hose clamps:
5. Apply coupling compound to the transducers, and install them in the brackets.
Tips for installing transducers:
a. Be sure the tightening Philips screw on the top of the bracket is loosened completely. b. Put the transducer into the bracket by ensuring the bottom of the transducer and the
couplant does not touch the pipe as you slide it in. (Hover)
c. Tighten the Phillips screws on the bracket until tight. The transducer will be level with
the surface of the pipe, and no grease will have smeared off.
(pictures of proper coupling application and finished installation on the next page)
Page 44
Page 45
TTFM 6.1 Transit Time Flow Meter
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B21 or TMK-B22 Kit (Cont.)
Proper coupling compound application:
Finished installation, ready for cable and conduit connection:
6. If you need to make fine adjustments (±0.25”) to the spacing at this point, you may do so by loosening the hose clamps slightly, and sliding the brackets while the transducers are installed inside them. Tighten hose clamps when done.
Page 45
Page 46
TTFM 6.1 Transit Time Flow Meter
SEPARATION DISTANCE (Sensor Spacing Distance)
Separation distance is automatically calculated by the TTFM 6.1 based on parameters entered in the Setup menu. Sens Space is parameter where this distance is given, and it is located in the Setup menu. Document this value for the following transducer installation procedure.
1 CROSS INSTALLATION OVERVIEW – TMK-B21 or TMK-B22 Kit
To assist with the proper installation of the transducers in a 1 cross installation, we provide a kit with every meter, which consists of the following:
Sanding block Tape measure Mylar sleeve Duct tape Level Black Sharpie
Follow along with the 1 cross installation instructions on the following pages for a description of where to use these tools.
1. Prep the pipe per instructions on page 28, and mind the installation location requirements on page 30. Clean the location where the sensor is to be mounted on the opposite side of the pipe after we’ve marked where it will be installed. The picture below shows a very clean ductile iron pipe which did not require much cleaning.
Page 46
Page 47
TTFM 6.1 Transit Time Flow Meter
2. Install the spacer bar onto the right bracket as shown below:
3. Insert the spacer bar into the left bracket, and position the bracket at the separation distance referenced earlier. Tighten the spacer bar clamp at this position:
Page 47
Page 48
TTFM 6.1 Transit Time Flow Meter
4. Place the bracket assembly on the pipe, tighten it in place with the two hose clamps. For a horizontal pipe, position the bracket at 3 or 9 o’clock. Hold the level up to the top of the bracket to ensure the angle is correct. For vertical pipes, the bracket can be at any orientation about the pipe. Tip: Use a 5/16” nut driver to tighten the hose clamp.
5. Mark the position of the center line of the bracket which is to be moved to the opposite side of the pipe. It is up to you to determine which bracket is easier to move from the current position:
Page 48
Page 49
TTFM 6.1 Transit Time Flow Meter
6. Using the mylar sleeve included with the installation kit, wrap it around the pipe, keep it taut, and with the Sharpie, draw a line anywhere the sleeve overlaps:
7. Lay the mylar sleeve flat, and use the tape measure to measure half way between the two marks created when you wrapped the mylar around the pipe:
Page 49
Page 50
TTFM 6.1 Transit Time Flow Meter
8. Position the marked mylar back on the pipe, with the overlap marks on the center line of the transducer bracket that will be rotated to the other side of the pipe. Be sure the mylar is parallel with the face of the transducer. Use duct tape to hold the mylar together and to the pipe. While the mylar is in this position, mark the opposite side of the pipe where the mylar is marked from step 7:
Page 50
Page 51
TTFM 6.1 Transit Time Flow Meter
9. Sand the pipe at this position if it needs to be prepped because of scale or rust. After prepped, move the bracket to this 1 cross mark, and tighten it in place. Apply coupling compound to the transducers and place them in the brackets:
View from front of pipe:
View from back of pipe:
Tips for installing transducers:
a. Be sure the tightening screws on the brackets are loosened completely. b. Put the transducer into the bracket by ensuring the bottom of the transducer and the
couplant does not touch the pipe as you slide it in (hover).
c. With the transducer hovering, tighten the screws on the bracket until tight. The transducer
will be level with the surface of the pipe, and no grease will have smeared off from inserting the transducer in the bracket.
Page 51
Page 52
Proper coupling compound application:
TTFM 6.1 Transit Time Flow Meter
Finished installation:
10. If you need to make fine adjustments (±0.25”) to the spacing at this point, you may do so by loosening the hose clamps slightly, and sliding the brackets while the transducers are installed inside them. Tighten the hose clamps when done.
Page 52
Page 53
TTFM 6.1 Transit Time Flow Meter
SENSOR MOUNTING/COUPLING RECOMMENDATIONS
Page 53
Page 54
TTFM 6.1 Transit Time Flow Meter
ENCLOSURE INSTALLATION
Locate the enclosure within 25 ft (7.6 m) of the sensors (up to 100 ft - 30 m optional). The enclosure can be wall mounted with the four mounting screws (included) or panel mounted with Option PM Panel Mount kit from Greyline Instruments.
Avoid mounting the enclosure in direct sunlight to protect the electronics from damage due to overheating and condensate. In high humidity atmospheres, or where temperatures fall below freezing, Option TH Enclosure Heater and Thermostat is recommended. IMPORTANT: Seal conduit entries to prevent moisture from entering enclosure.
NEMA4X (IP66) WITH CLEAR COVER
1. Open hinged enclosure cover.
2. Insert #12 screws (supplied) through the four enclosure mounting holes to secure the enclosure to the wall or mounting stand.
Additional conduit holes can be cut in the bottom of the enclosure when required. Use a hole saw or Greenlee-type hole cutter to cut the required holes.
IMPORTANT: DO NOT make conduit/wiring entries into the top or sides of the enclosure.
Note: This non-metallic enclosure does not automatically provide grounding between conduit connections. Grounding must be provided as part of the installation. Ground in accordance with the requirements of the National Electrical Code. System grounding is provided by connecting grounding wires from all conduit entries to the steel mounting plate or another point which provides continuity.
CLEANING
Cleaning is not required as a part of normal maintenance.
Page 54
Page 55
FIELD TROUBLESHOOTING
METER READING WHEN THERE IS NO FLOW
?
C
ontact Greyline for further assistan
ce.
VSD
METER READING LOWER THAN EXPECTED
?
selection/fluid velocity.
instrument.
matches Setup menu values.
sensor spacing.
TTFM 6.1 Transit Time Flow Meter
Possible Causes:
Erratic measurement (set damping to 0% to check) due to electrical noise or poor signal quality.
Variable Speed Drive interference
Calibration Error
Corrective Action:
Set Calibration/ Damping to 0% with zero flow use
Setup / Tare function.
Ensure all Flowmeter wiring is in METAL conduit and sensor
shield is properly connected to Ground.
Ensure correct power input Ground connection (<1 ohm
resistance).
Ensure 4-20mA Shield connected to Instrument Ground stud. Adjust Calibration / Min Flow setting.
Follow Drive manufacturers wiring and Grounding instructions Relocate Flowmeter electronics, Sensor and wiring away from
Review calibration menu. Pipe dimensions and fluid
Lower flow rate than expected
Erratic measurement (set damping to 0% to check) due to electrical noise or poor signal quality.
NO ECHO INDICATION Icon: No Echo
Improper Installation
Sensors not mounted to Pipe or mounted improperly
Investigate pump/valves. Compare velocity with alternate
Ensure all Flowmeter wiring is in METAL conduit and sensor
shield is properly grounded.
Ensure correct power input Ground connection (<1 ohm
resistance).
Ensure 4-20mA Shield connected to Instrument Ground stud. Contact Greyline for further assistance.
Check Setup menu to ensure pipe material, size, thickness, liner
type, thickness, fluid type, and fluid temperature and configured properly. Check transducer mounting method and spacing
Apply coupling compound and mount sensors to pipe with proper
Page 55
Page 56
TTFM 6.1 Transit Time Flow Meter
obtain echoes.
Use
Super Lube
®
Silicone Compound
SENSOR CONNECTIONS
Connections steps
connections.
selection/fluid velocity.
instrument.
C
ontact Greyline for further assistance.
adjustment to Cal Const.
Possible Causes:
NO ECHO INDICATION Icon: No Echo (cont.)
Empty pipe or partially filled
Coupling compound washed out, or sensor loose on pipe.
OPEN/SHORT SENSOR ICON
Sensor Connections
METER READING HIGHER THAN EXPECTED?
Corrective Action:
Pipe must be fluid filled and acoustically transparent in order to
Remount sensor
No sensors attached Short in transducer, or in triax transducer cable. Follow Sensor
Check sensor connections at TTFM and at sensor junction box. Note: Refer to Sensor Cable Resistance Test to test final
Calibration Error
Higher flow rate than expected
Erratic measurement (set damping to 0% to check) due to electrical noise or poor signal quality.
High viscosity fluid
Review calibration menu. Pipe dimensions and fluid
Investigate pump/valves. Compare velocity with alternate
Ensure all Flowmeter wiring is in METAL conduit and sensor
shield is properly grounded.
Ensure correct power input Ground connection (<1 ohm
resistance).
Ensure 4-20mA Shield connected to Instrument Ground stud.
Laminar flow profile due to high viscosity fluid requires an
Page 56
Page 57
TTFM 6.1 Transit Time Flow Meter
SENSOR CABLE & TRANSDUCER RESISTANCE TEST
Unplug the green sensor terminal from the Transit Time board with the sensor wires still connected and the BNC end of the cable is connected to the transducer. With a multimeter, perform resistance checks for each set of wires. One single loose terminal may cause false readings.
Test across shield and core of each wire: TDR1 and TDR2. Resistance should be around 10K ohms for any cable length. High readings indicate an open circuit and low readings indicate a short or partial short in the sensor cable connections or transducer.
Note: The TTFM 6.1 will automatically detect connectivity to the sensors. Confirm that TTFM 6.1
indicates “Sensor Good” in the messages menu if your resistance measured is approximately 10K Ohms.
Page 57
Page 58
TTFM 6.1 Transit Time Flow Meter
COMMON QUESTIONS AND ANSWERS
The pipe vibrates. Will it affect the flow meter?
Common vibration frequencies are far lower than the sonic frequencies used by the Greyline flow meter, and will not normally affect accuracy or performance. However, applications where very weak Transit Time signal is present (when sensitivity is adjusted to maximum and signal strength is low), accuracy may be affected by pipe vibration, or the flow meter may show readings under no-flow conditions. Attempt to relocate the sensor on a pipe section where vibration is reduced, or arrange pipe mounting brackets to reduce vibration at the sensor mounting location.
The flow meter must be installed in a high noise environment. Will this affect operation?
Greyline flow meters are designed to discriminate between environmental noise and the Transit Time signal. High noise environments may affect the flow meter’s performance where low signal strength and/or low flow velocities are being measured. Relocate the sensor in a quieter environment if possible.
Will pipe corrosion affect accuracy of the flow meter?
Yes. Rust, loose paint etc. must be removed from the outside of the pipe to provide a clean mounting position when installing a Transit Time sensor. Severe corrosion/oxidation on the inside of the pipe may prevent the Transit Time signal from penetrating into the flow. If the pipe cannot be cleaned, a spool piece (PVC recommended) should be installed for sensor mounting.
What effect do pipe liners have on the flow meter?
The air gap between loose insertion liners and the pipe wall prevent the Transit Time signal from entering the flow. Better results can be expected with bonded liners such as cement, epoxy or tar, however an on site test is recommended to determine if the application is suitable for a Transit Time flow meter.
Why is Transit Time recommended for clean liquids?
The Transit Time sensor transmits sound across the flow stream in order to measure the time it takes to arrive at the other sensor, and therefore requires a fluid medium that is relatively transparent to the acoustic signal. The Transit Time system will not function when there is high volume of solids or aeration. As a guideline, Greyline Transit Time flow meters are recommended for clean liquids with solids or bubbles content less than 2% by volume.
Can the sensor be submerged in water?
Yes, for short periods of time or by accident, but it is not recommended for continuous operation. The sensor is constructed to withstand submersion to 10 psi (0.7 Bar) without damage provided the protective rubber boot is filled with Super Lube®.
Page 58
Page 59
TTFM 6.1 Transit Time Flow Meter
What is the purpose of the Signal Strength Display?
The primary function of the signal strength display is to assist as a feedback when mounting sensors. Signal Strength can also be a useful diagnostics tool when troubleshooting problems with an installation. A signal strength less than 100% may indicate a problem with the installation or other issues such as a mis-programmed pipe size, pipe material, fluid type or temperature, or wrong transducer spacing. A signal strength less than 100% may also simply indicate a lot of aeration, or deteriorated pipe. Consideration should be made to use a 1 cross installation in such a case.
Can I change the length of the sensor cable?
Yes. The Greyline Transit Time design allow cable lengths up to 100 ft (30 m) or extension up to 250 ft with extra cable and JB2X optional junction box. Replacement cable of different length may be installed in rigid or flexible conduit for mechanical protection. Use only Greyline shielded triaxial cable.
Does the TTFM 6.1 require periodic recalibration?
TTFM 6.1 calibration does not drift over time. The solid state sensor has no moving parts to wear and affect calibration. All Greyline timing/counting circuits use crystal-controlled frequency references to eliminate any drift in the processing circuitry.
ISO 9000 or similar quality management systems may require periodic and verifiable recalibration of flow meters. TTFM 6.1 Flow Meters may be returned to Greyline for factory calibration and issue of a new NIST traceable certificate. Refer to the ‘Product Return Procedure’ section of this manual for return instructions.
Page 59
Page 60
TTFM 6.1 Transit Time Flow Meter
APPLICATIONS HOTLINE
For applications assistance, advice or information on any Greyline Instrument contact your Sales Representative, write to Greyline or phone the Applications Hotline below:
United States: Tel: 315-788-9500 Fax: 315-764-0419 Canada: Tel: 613-938-8956 Fax: 613-938-4857 Toll Free: 888-473-9546 Email: [email protected] Web Site: www.greyline.com
Greyline Instruments Inc.
USA Canada 11451 Belcher Road South 16456 Sixsmith Drive Largo, FL 33773 Long Sault, Ont. K0C 1P0
PRODUCT RETURN PROCEDURE
Instruments may be returned to Greyline for service or warranty repair. 1 Obtain an RMA Number from Greyline -
Before shipping a product to the factory please contact Greyline by telephone, fax or email to obtain an RMA number (Returned Merchandise Authorization). This ensures fast service and correct billing or credit.
When you contact Greyline please have the following information available:
1. Model number / Software Version
2. Serial number
3. Date of Purchase
4. Reason for return (description of fault or modification required)
5. Your name, company name, address and phone number
2 Clean the Sensor/Product -
Important: unclean products will not be serviced and will be returned to the sender at their expense.
1. Rinse sensor and cable to remove debris.
2. If the sensor has been exposed to sewage, immerse both sensor and cable in a solution of 1 part household bleach (Javex, Clorox etc.) to 20 parts water for 5 minutes. Important: do not immerse open end of sensor cable.
3. Dry with paper towels and pack sensor and cable in a sealed plastic bag.
4. Wipe the outside of the enclosure to remove dirt or deposits.
5. Return to Greyline for service.
Page 60
Page 61
TTFM 6.1 Transit Time Flow Meter
LIMITED WARRANTY
_____________________________________
Greyline Instruments warrants, to the original purchaser, its products to be free from defects in material and workmanship for a period of one year from date of invoice. Greyline will replace or repair, free of charge, any Greyline product if it has been proven to be defective within the warranty period. This warranty does not cover any expenses incurred in the removal and re-installation of the product.
If a product manufactured by Greyline should prove defective within the first year, return it freight prepaid to Greyline Instruments along with a copy of your invoice.
This warranty does not cover damages due to improper installation or handling, acts of nature, or unauthorized service. Modifications to or tampering with any part shall void this warranty. This warranty does not cover any equipment used in connection with the product or consequential damages due to a defect in the product.
All implied warranties are limited to the duration of this warranty. This is the complete warranty by Greyline and no other warranty is valid against Greyline. Some states do not allow limitations on how long an implied warranty lasts or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Greyline Instruments Inc.
Page 61
Page 62
TTFM 6.1 Transit Time Flow Meter
ENCLOSURE HEATER AND THERMOSTAT - Option TH
Instruments can be factory-equipped with an Enclosure Heater and Thermostat or the module can be customer-installed. The Thermostat is factory set to turn ON at 40°F (4.5°C) and OFF at 60°F (15.5°C). Power consumption is 15 Watts.
ENCLOSURE SUNSCREEN - Option SCR
Do not mount instrument electronics in direct sunlight. Overheating will reduce the life of electronic components and condensate may form during the heat/cool cycles and cause electrical shorts.
Page 62
Page 63
TTFM 6.1 Transit Time Flow Meter
POWER INPUT OPTION 9-32VDC
TTFM 6.1 Flow Meters may be ordered factory-configured for 9-32VDC power input, or a 9-32VDC Power Input card can be installed in the place of the 100-240VAC card in the field.
CONNECTIONS:
POWER INPUT: Connect 9-32VDC to the + and - terminals. The Power Input GND terminal must be connected to the nearest Ground pole. A 1 amp fuse in line is recommended.
4-20mA
RLY2
RLY1
SERIAL COMMUNICATION OPTION
EXTRA RELAYS OPTION
NCCNONCCNONCCNONCC
RLY3 RLY4 RLY5 RLY6
9-32 VDC
POWER INPUT
+ -
– +
NO C NC
NO C NC
DC GND
SENSOR
GND
+ G
RS-485 Output
NO
SENSOR
GND
GND
TDR 1
TDR 2
Upstream
Downstream
Page 63
Page 64
SPECIFICATIONS
7.4
/ 1 88 mm
"
LOCATION
TTFM 6.1 Transit Time Flow Meter
Flow Rate Range: ±0.07 to 40 ft/sec (±0.02
6.46 / 16 4 mm"
to 12 m/sec)
Pipe Size: 2” to 48” (50 to 1200 mm)
Accuracy: ±1% of flow rate from 1.5
to 40 ft/sec, ±0.015 ft/sec below 1.5 ft/sec. Repeatability and Linearity: ±0.25%
Displays: White, backlit matrix -
displays flow rate, totalizer, relay states,
TTFM .61
Transit Time Ultrasonic Flow Meter
10.94" / 2 78 mm
operating mode and calibration menu
Calibration: built-in 5-key calibrator
with English, French or
CONDUIT ENT RY
Spanish language selection
Power Input: 100-240VAC, 50/60Hz, 10VA or
Optional 9-32VDC, 10 Watts Maximum
Output: Isolated 4-20mA (1000 ohm load max.). Can be changed to 0-5VDC in
programming
Data Logger: 128MB Data Storage
Control Relays: Qty 2, rated 5 amp 240VAC SPDT, programmable flow alarm and/or
proportional pulse
Enclosure: Watertight, dust tight NEMA4X (IP 66) polycarbonate with a clear
shatter-proof face
Environmental Conditions: Relative humidity up to 80%, -23 to 60°C ambient temperature,
maximum 5000 m altitude, pollution degree 4, Installation Category II.
Electrical Surge Protection: Sensor, 4-20mA output and AC power input
Approximate Shipping Weight: 12 lbs (5.5 kg)
5.12 / 13 0 mm"
10 / 2 54 mm"
SIDE VIEW
SE16 Transit Time Sensor
Pipe Diameter: 2” to 48” (50 to 1200 mm)
Operating Temperature: -40° to 300°F (-40° to 150°C)
Exposed Materials: 31655
Operating Frequency: 1.28 MHz
Sensor Cable: 25 ft (7.6 m)
Optional 50 ft (15 m) or 100 ft (30 m) available, extendable up to 500 ft
(150 m) with JB2X optional junction box.
Submersion Rating: Withstands accidental submersion pressure up to 10 psi (0.7 Bar)
Page 64
Page 65
TTFM 6.1 Transit Time Flow Meter
APPENDIX A - CONVERSION TABLE
CONVERSION GUIDE
FROM TO MULTIPLY BY US GALLONS CUBIC FEET 0.1337 US GALLONS IMPERIAL GALS 0.8327 US GALLONS LITRES 3.785 US GALLONS CUBIC METERS 0.003785 LITRES/SEC GPM 15.85 LITRES CUBIC METERS 0.001 BARRELS (bbl) US GALLONS 42 BARRELS (bbl) IMPERIAL GALS 34.9726 BARRELS (bbl) LITRES 158.9886 INCHES MM 25.4 DEGREES F DEGREES C (°F-32) x 0.556 POUNDS KILOGRAMS 0.453 PSI BAR 0.0676 FOOT² METER² 0.0929
Note: BARRELS (bbl) are U.S. oil barrels.
Page 65
Page 66
TTFM 6.1 Transit Time Flow Meter
PIPE CHARTS
Note: Not all pipe types allowed in programming have charts below. Pipe dimensions will need
to be acquired from pipe markings or the pipe manufacturer in such cases.
Carbon Steel & PVC Pipe
Pipe Pipe ScheduleStandard Extra Heavy Dbl. ExtraHeavy Schedule10 Schedule20 Schedule 30 Schedule40 Schedule80 Size O.D. I.D. WALL I.D. WALL I.D. WALL I.D. WALL I.D. WALL I.D. WALL I.D. WALL I.D. WALL
2 2.375 2.067 .154 1.939 .218 1.503 .436 2.067 .154 1.939 0.218
2½ 2.875 2.469 .203 2.323 .276 1.771 .552 2.469 .203 2.323 0.276
3 3.500 3.068 .216 2.900 .300 2.300 .600 3.068 .216 2.900 0.300
3½ 4.000 3.548 .226 3.364 .318 2.728 .636 3.548 .226 3.364 0.318
4 4.500 4.026 .237 3.826 .337 3.152 .674 4.026 .237 3.826 0.337 5 5.563 5.047 .258 4.813 .375 4.063 .750 5.047 .258 4.813 0.375 6 6.625 6.065 .280 5.761 .432 4.897 .864 6.065 .280 5.761 0.432
8 8.625 7.981 .322 7.625 .500 6.875 .875 8.125 .250 8.071 .277 7.981 .322 7.625 0.500 10 10.750 10.020 .365 9.750 .500 8.750 1.000 10.250 .250 10.136 .307 10.020 .365 9.564 0.593 12 12.750 12.000 .375 11.750 .500 10.750 1.000 12.250 .250 12.090 .330 11.938 .406 11.376 0.687 14 14.000 13.250 .375 13.000 .500 13.500 .250 13.376 .312 13.250 .375 13.124 .438 12.500 0.750 16 16.000 15.250 .375 15.000 .500 15.500 .250 15.376 .312 15.250 .375 15.000 .500 14.314 0.843 18 18.000 17.250 .375 17.000 .500 17.500 .250 17.376 .312 17.124 .438 16.876 .562 16.126 0.937 20 20.000 19.250 .375 19.000 .500 19.500 .250 19.250 .375 19.000 .500 18.814 .593 17.938 1.031 22 22.000 21.250 .375 21.000 .500 21.500 .250 21.250 .375 21.000 .500 24 24.000 23.250 .375 23.000 .500 23.500 .250 23.250 .375 22.876 .562 22.626 .687 21.564 1.218 26 26.000 25.250 .375 25.000 .500 25.376 .312 25.000 .500 28 28.000 27.250 .375 27.000 .500 27.376 .312 27.000 .500 26.750 .625 30 30.000 29.250 .375 29.000 .500 29.376 .312 29.000 .500 28.750 .625 32 32.000 31.250 .375 31.000 .500 31.376 .312 31.000 .500 30.750 .625 34 34.000 33.250 .375 33.000 .500 33.376 .312 33.000 .500 32.750 .625 36 36.000 35.250 .375 35.000 .500 35.376 .312 35.000 .500 34.750 .625 42 42.000 41.250 .375 41.000 .500 41.000 .500 40.750 .625
Ductile Iron Pipe – Standard Classes
Size OUT SIDE C l ass Cla ss Cl as s Cla ss Cl ass Class Class CE ME NT LINING
INCH DIA. 50 51 5 2 53 5 4 55 56 **S TD **DOUB LE
**REDUC E I.D. BY DIMENS ION SHO WN
INCH W ALL I.D. WA LL I.D. W ALL I .D. WAL L I.D. WALL I.D . WALL I.D. WA LL I.D . THICKN ESS THICKN ESS
3 3. 96 0.25 3.46 0.28 3 .40 0.31 3 .34 0.34 3 .28 0.37 3.2 2 0.41 3.14
4 4. 80 0.26 4.28 0.29 4 .22 0.32 4 .16 0.35 4 .10 0.38 4.0 4 0.44 3.93
6 6. 90 0. 25 6.40 0.28 6.34 0.31 6 .28 0.34 6 .22 0.37 6 .16 0.40 6.1 0 0.43 6.04 .125 .250
8 9. 05 0. 27 8.51 0.30 8.45 0.33 8 .39 0.36 8 .33 0.39 8 .27 0.42 8.2 1 0.45 8.15
10 11.10 0.39 10.32 0.3 2 10 .46 0.35 1 0.40 0.38 10.3 4 0.41 10.28 0.44 10.22 0 .47 1 0.16 12 13.20 0.31 12.58 0.3 4 12 .52 0.37 1 2.46 0.40 12.4 0 0.43 12.34 0.46 12.28 0 .49 1 2.22 14 15.30 0.33 14.64 0.3 6 14 .58 0.39 1 4.52 0.42 14.4 6 0.45 14.40 0.48 14.34 0 .51 1 4.28 16 17.40 0.34 16.72 0.3 7 16 .66 0.40 1 6.60 0.43 16.5 4 0.46 16.48 0.49 16.42 0 .52 1 6.36 18 19.50 0.35 18.80 0.3 8 18 .74 0.41 1 8.68 0.44 18.6 2 0.47 18.56 0.50 18.50 0 .53 1 8.44 .18 75 .375 20 21.60 0.36 20.88 0.3 9 20 .82 0.42 2 0.76 0.45 20.7 0 0.48 20.64 0.51 20.58 0 .54 2 0.52 24 25.80 0.38 25.04 0.4 1 24 .98 0.44 2 4.92 0.47 24.8 6 0.50 24.80 0.53 24.74 0 .56 2 4.68 30 32.00 0.39 31.22 0.4 3 31 .14 0.47 3 1.06 0.51 30.9 8 0.55 30.90 0.59 30.82 0 .63 3 0.74 36 38.30 0.43 37.44 0.4 8 37 .34 0.62 3 7.06 0.58 37.1 4 0.63 37.04 0.68 36.94 0 .73 3 6.84 42 44.50 0.47 43.56 0.5 3 43 .44 0.59 4 3.32 0.65 43.2 0 0.71 43.08 0.77 42.96 0 .83 4 2.84 .250 .500 48 50.80 0.51 49.78 0.5 8 49 .64 0.65 4 9.50 0.72 49.3 6 0.79 49.22 0.86 49.08 0 .93 4 8.94 54 57.10 0.57 55.96 0.6 5 55 .80 0.73 5 5.64 0.81 55.4 8 0.89 55.32 0.97 55.16 1 .05 5 5.00
Page 66
Page 67
TTFM 6.1 Transit Time Flow Meter
Stainless Steel, Hastelloy "C" & Titanium Pipe
Pipe
Pipe
Scheule 5 S (a)
Schedule 10 S (a)
Schedule 40 S
Schedule 80 S
Size
O.D.
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
2
2.375
2.245
.065
2.157
.109
2.067
.154
1.939
.218
2½
2.875
2.709
.083
2.635
.120
2.469
.203
2.323
.276
3
3.500
3.334
.083
3.260
.120
3.068
.216
2.900
.300
3½
4.000
3.834
.083
3.760
.120
3.548
.226
3.364
.318
4
4.500
4.334
.083
4.260
.120
4.026
.237
3.826
.337
5
5.563
5.345
.109
5.295
.134
5.047
.258
4.813
.37566.625
6.407
.109
6.357
.134
6.065
.280
5.761
.432
8
8.625
8.407
.109
8.329
.148
7.981
.322
7.625
.5001010.750
10.482
.134
10.420
.165
10.020
.365
9.750
.5001212.750
12.438
.156
12.390
.180
12.000
.375
11.750
.500
14
14.000
13.688
.156
13.624
.188
16
16.000
15.670
.165
15.624
.188
18
18.000
17.670
.165
17.624
.188
20
20.000
19.634
.188
19.564
.218
22
22.000
21.624
.188
21.564
.218
24
24.000
23.563
.218
23.500
.250
Pipe
Pipe
Schedule 60
Schedule 80
Schedule 100
Schedule 120
Schedule 140
Schedule 160
Size
O.D.
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
2½
2.875
2.323
.276
2.125
.375
3½
4.000
3.364
.318
5
5.563
4.813
.375
4.563
.500
4.313
.625
6
6.625
5.761
.432
5.501
.562
5.189
.718
8
8.625
7.813
.406
7.625
.500
7.439
.593
7.189
.718
7.001
.812
6.813
.9061010.750
9.750
.500
9.564
.593
9.314
.718
9.064
.843
8.750
1.000
8.500
1.125
12
12.750
11.626
.562
11.376
.687
11.064
.843
10.750
1.000
10.500
1.125
10.126
1.312
14
14.000
12.814
.593
12.500
.750
12.126
.937
11.814
1.093
11.500
1.250
11.188
1.406
16
16.000
14.688
.656
14.314
.843
13.938
1.031
13.564
1.218
13.124
1.438
12.814
1.593
18
18.000
16.500
.750
16.126
.937
15.688
1.156
15.250
1.375
14.876
1.562
14.438
1.781
20
20.000
18.376
.812
17.938
1.031
17.438
1.281
17.000
1.500
16.500
1.750
16.064
1.968
22
22.000
20.250
.875
19.750
1.125
19.250
1.375
18.750
1.625
18.250
1.875
17.750
2.125
24
24.000
22.064
.968
21.564
1.218
20.938
1.531
20.376
1.812
19.876
2.062
19.314
2.343
2 2.375 1.939 .218 1.689 .343
3 3.500 2.900 .300 2.624 .438
4 4.500 3.826 .337 3.624 .438 3.438 .531
Page 67
Page 68
TTFM 6.1 Transit Time Flow Meter
Cast Iron Pipe
-
ASA Standard
Pipe
Pipe
Class 50
Class 100
Class 150
Class 200
Class 250
Class 300
Class 350
Size
O.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
WALL
I.D.
3
3.96
0.32
3.32
0.32
3.32
0.32
3.32
0.32
3.32
0.32
3.32
0.32
3.32
0.32
3.3244.80
0.35
4.10
0.35
4.10
0.35
4.10
0.35
4.10
0.35
4.10
0.35
4.10
0.35
4.1066.90
0.38
6.14
0.38
6.14
0.38
6.14
0.38
6.14
0.38
6.14
0.38
6.14
0.38
6.14
8
9.05
0.41
8.23
0.41
8.23
0.41
8.23
0.41
8.23
0.41
8.23
0.41
8.23
0.41
8.23
10
11.10
0.44
10.22
0.44
10.22
0.44
10.22
0.44
10.22
0.44
10.22
0.48
10.14
0.52
10.06
12
13.20
0.48
12.24
0.48
12.24
0.48
12.24
0.48
12.24
0.52
12.16
0.52
12.16
0.56
12.081415.30
0.48
14.34
0.51
14.28
0.51
14.28
0.55
14.20
0.59
14.12
0.59
14.12
0.64
14.02
16
17.40
0.54
16.32
0.54
16.32
0.54
16.32
0.58
16.24
0.63
16.14
0.68
16.04
0.68
16.04
18
19.50
0.54
18.42
0.58
18.34
0.58
18.34
0.63
18.24
0.68
18.14
0.73
18.04
0.79
17.92
20
21.60
0.57
20.46
0.62
20.36
0.62
20.36
0.67
20.26
0.72
20.16
0.78
20.04
0.84
19.92
24
25.80
0.63
24.54
0.68
24.44
0.73
24.34
0.79
24.22
0.79
24.22
0.85
24.10
0.92
23.96
Cast Iron Pipe
-
AWWA Standard
Pipe
Class A
Class B
Class C
Class D
100 Ft. 43 PSIG
200 Ft. 86 PSIG
300 Ft. 130 PSIG
400 Ft. 173 PSIG
Size
O.D.
WALL
I.D.
O.D.
WALL
I.D.
O.D.
WALL
I.D.
O.D.
WALL
I.D.
3
3.80
0.39
3.02
3.96
0.42
3.12
3.96
0.45
3.06
3.96
0.48
3.00
4
4.80
0.42
3.96
5.00
0.45
4.10
5.00
0.48
4.04
5.00
0.52
3.96
6
6.90
0.44
6.02
7.10
0.48
6.14
7.10
0.51
6.08
7.10
0.55
6.00
8
9.05
0.46
8.13
9.05
0.51
8.03
9.30
0.56
8.18
9.30
0.60
8.10
10
11.10
0.50
10.10
11.10
0.57
9.96
11.40
0.62
10.16
11.40
0.68
10.041213.20
0.54
12.12
13.20
0.62
11.96
13.50
0.68
12.14
13.50
0.75
12.00
16
17.40
0.60
16.20
17.40
0.70
16.00
17.80
0.80
16.20
17.80
0.89
16.02
20
21.60
0.67
20.26
21.60
0.80
20.00
22.06
0.92
20.22
22.06
1.03
20.002425.80
0.76
24.28
25.80
0.89
24.02
26.32
1.04
24.22
26.32
1.16
24.00
30
31.74
0.88
29.98
32.00
1.03
29.94
32.40
1.20
30.00
32.74
1.37
30.00
36
37.96
0.99
35.98
38.30
1.15
36.00
38.70
1.36
39.98
39.16
1.58
36.00
42
44.20
1.10
42.00
44.50
1.28
41.94
45.10
1.54
42.02
45.58
1.78
42.02
48
50.50
1.26
47.98
50.80
1.42
47.96
51.40
1.71
47.98
51.98
1.96
48.06
54
56.66
1.35
53.96
57.10
1.55
54.00
57.80
1.90
54.00
58.40
2.23
53.94
60
62.80
1.39
60.02
63.40
1.67
60.06
64.20
2.00
60.20
64.82
2.38
60.06
72
75.34
1.62
72.10
76.00
1.95
72.10
76.88
2.39
72.10
84
87.54
1.72
84.10
88.54
2.22
84.10
Pipe
Class E
Class F
Class G
Class H
500 Ft. 217 PSIG
600 Ft. 260 PSIG
700 Ft. 304 PSIG
800 Ft. 347 PSIG
Size
O.D.
WALL
I.D.
O.D.
WALL
I.D.
O.D.
WALL
I.D.
O.D.
WALL
I.D.
6
7.22
0.58
6.06
7.22
0.61
6.00
7.38
0.65
6.08
7.38
0.69
6.00
8
9.42
0.66
8.10
9.42
0.71
8.00
9.60
0.75
8.10
9.60
0.80
8.00
10
11.60
0.74
10.12
11.60
0.80
10.00
11.84
0.86
10.12
11.84
0.92
10.00
12
13.78
0.82
12.14
13.78
0.89
12.00
14.08
0.97
12.14
14.08
1.04
12.00
14
15.98
0.90
14.18
15.98
0.99
14.00
16.32
1.07
14.18
16.32
1.16
14.00
16
18.16
0.98
16.20
18.16
1.08
16.00
18.54
1.18
16.18
18.54
1.27
16.001820.34
1.07
18.20
20.34
1.17
18.00
20.78
1.28
18.22
20.78
1.39
18.00
20
22.54
1.15
20.24
22.54
1.27
20.00
23.02
1.39
20.24
23.02
1.51
20.00
24
26.90
1.31
24.28
26.90
1.45
24.00
27.76
1.75
24.26
27.76
1.88
24.00
30
33.10
1.55
30.00
33.46
1.73
30.00
14 15.30 0.57 14.16 15.30 0.66 13.98 15.65 0.74 14.17 15.65 0.82 14.01
18 19.50 0.64 18.22 19.50 0.75 18.00 19.92 0.87 18.18 19.92 0.96 18.00
36 39.60 1.80 36.00 40.04 2.02 36.00
Page 68
Page 69
TTFM 6.1 Transit Time Flow Meter
Copper Tubing
Pipe K L M Copper & Brass Pipe Aluminum Size O.D. I.D. WALL O.D. I.D. WALL O.D. I.D. WALL O.D. I.D. WALL O.D. I.D. WALL
2" 2.125 1.959 0.083 2.125 1.985 0.070 2.125 2.009 0.058 2.375 2.062 0.157
2 ½ 2.625 2.435 0.095 2.625 2.465 0.080 2.625 2.495 0.065 2.875 2.500 0.188 2.500 2.400 0.050
3" 3.125 2.907 0.109 3.125 2.945 0.090 3.125 2.981 0.072 3.500 3.062 0.219 3.000 2.900 0.050
3 ½" 3.625 3.385 0.120 3.625 3.425 0.100 3.625 3.459 0.083 4.000 3.500 0.250
4" 4.125 3.857 0.134 4.125 3.905 0.110 4.125 3.935 0.095 4.500 3.935 0.095 4.000 4.000 0.250
4 ½" 5.000 4.500 0.250
5" 5.125 4.805 0.160 5.125 4.875 0.125 5.125 4.907 0.109 5.563 5.063 0.250 5.000 4.874 0.063 6" 6.125 5.741 0.192 6.125 5.845 0.140 6.125 5.881 0.122 6.625 6.125 0.250 6.000 5.874 0.063 7" 7.625 7.062 0.282 7.000 6.844 0.078
8" 8.125 7.583 0.271 8.125 7.725 0.200 8.125 7.785 0.170 8.625 8.000 0.313 8.000 7.812 0.094 10" 10.125 9.449 0.338 10.125 9.625 0.250 10.125 9.701 0.212 10.000 9.812 0.094 12" 12.125 11.315 0.405 12.125 11.565 0.280 12.125 11.617 0.254
Page 69
Page 70
C900/C905 PVC AWWA Water Distribution Pipe (Blue)
TTFM 6.1 Transit Time Flow Meter
Pipe Size OD
4 4.80 0.343 4.114 0.267 4.266 0.192 4.416
6 6.90 0.493 5.914 0.383 6.134 0.276 6.348
8 9.05 0.646 7.758 0.503 8.044 0.362 8.326
10 11.10 0.793 9.514 0.617 9.866 0.444 10.212
12 13.20 0.943 11.314 0.733 11.734 0.528 12.144
14 15.30 0.850 13.600 0.729 13.842 0.612 14.076
16 17.40 0.967 15.466 0.829 15.742 0.696 16.008
18 19.50 1.083 17.334 0.929 17.642 0.780 17.94
20 21.60 1.200 19.200 1.029 19.542 0.864 19.872
24 25.80 1.433 22.934 1.229 23.342 1.032 23.736
DR14 DR18 DR-21 DR25
Wall ID Wall ID Wall ID Wall ID
Page 70
Page 71
APPENDIX C – Liquid Speed of Sound
Substance Form Index Specific Gravity Sound Speed
m/sec.
Acetic anhydride (22) (CH3CO)2O 1.082 (20ºC) 1180 2.5 Acetic acid, anhydride (22) (CH3CO)2O 1.082 (20ºC) 1180 2.5
Acetic acid, nitrile C2H3N 0.783 1290 4.1 Acetic acid, ethyl ester (33) C4H8O2 0.901 1085 4.4 Acetic acid, methyl ester C3H6O2 0.934 1211
Acetone C3H6O 0.791 1174 4.5 Acetonitrile C2H3N 0.783 1290 4.1 Acetonylacetone C6H10O2 0.729 1399 3.6 Acetylene dichloride C2H2Cl2 1.26 1015 3.8 Acetylene tetrabromide (47) C2H2Br4 2.966 1027
Acetylene tetrachloride (47) C2H2Cl4 1.595 1147 Alcohol C2H6O 0.789 1207 4.0
Alkazene-13 C15H24 0.86 1317 3.9 Alkazene-25 C10H12Cl2 1.20 1307 3.4 2-Amino-ethanol C2H7NO 1.018 1724 3.4 2-Aminotolidine (46) C7H9N 0.999 (20ºC) 1618
4-Aminotolidine (46) C7H9N 0.966 (45ºC) 1480 Ammonia (35) NH3 0.771 1729 6.68
Amorphous Polyolefin 0.98 962.6 t-Amyl alcohol C5H12O 0.81 1204 Aminobenzene (41) C6H5NO2 1.022 1639 4.0
Aniline (41) C6H5NO2 1.022 1639 4.0 Argon (45) Ar 1.400 (-188ºC) 853
Azine C6H5N 0.982 1415 4.1 Benzene (29,40,41) C6H6 0.879 1306 4.65 Benzol(29,40,41) C6H6 0.879 1306 4.65 Bromine (21) Br2 2.928 889 3.0 Bromo-benzene (46) C6H5Br 1.522 1170
1-Bromo-butane (46) C4H9Br 1.276 (20ºC) 1019 Bromo-ethane (46) C2H5Br 1.460 (20ºC) 900 Bromoform (46,47) CHBr3 2.89 (20ºC) 918 3.1
n-Butane (2) C4H10 0.601 (0ºC) 1085 5.8 2-Butanol C4H10O 0.81 1240 3.3 sec-Butylalcohol C4H10O 0.81 1240 3.3 n-Butyl bromide (46) C4H9Br 1.276 (20ºC) 1019
n-Butyl chloride (22,46) C4H9Cl 0.887 1140 4.57 tert Butyl chloride C4H9Cl 0.84 984 4.2 Butyl oleate C22H42O2 1404 3.0
2,3 Butylene glycol C4H10O2 1.019 1484 1.51 Cadmium (7) Cd 2237.7
Carbinol (40,41) CH4O 0.791 (20ºC) 1076 2.92 Carbitol C6H14O3 0.988 1458
Carbon dioxide (26) CO2 1.101 (-37ºC) 839 7.71 Carbon disulphide CS2 1.261 (22ºC) 1149
Carbon tetrachloride(33,35,47) CCl4 1.595 (20ºC) 926 2.48
v/°C - m/s/°C Δ
Page 72
TTFM 6.1 Transit Time Flow Meter
Substance Form Index Specific Gravity Sound Speed
v/°C - m/s/°C Δ
m/sec.
Carbon tetrafluoride (14) CF4 1.75 (-150ºC) 875.2 6.61 Cetane (23) C16H34 0.773 (20ºC) 1338 3.71
Chloro-benezene C6H5Cl 1.106 1273 3.6 1-Chloro-butane (22,46) C4H9Cl 0.887 1140 4.57 Chloro-diFluoromethane (3) (Freon 22) CHClF2 1.491 (-69ºC) 893.9 4.79 Chloroform (47) CHCl3 1.489 979 3.4 1-Chloro-propane (47) C3H7Cl 0.892 1058
Chlorotrifluoromethane (5) CClF3 724 5.26 Cinnamaldehyde C9H8O 1.112 1554 3.2
Cinnamic aldehyde C9H8O 1.112 1554 3.2 Colamine C2H7NO 1.018 1724 3.4 o-Cresol (46) C7H8O 1.047 (20ºC) 1541
m-Cresol (46) C7H8O 1.034 (20ºC) 1500 Cyanomethane C2H3N 0.783 1290 4.1
Cyclohexane (15) C6H12 0.779 (20ºC) 1248 5.41 Cyclohexanol C6H12O 0.962 1454 3.6 Cyclohexanone C6H10O 0.948 1423 4.0 Decane (46) C10H22 0.730 1252
1-Decene (27) C10H20 0.746 1235 4.0 n-Decylene (27) C10 H20 0.746 1235 4.0 Diacetyl C4H6O2 0.99 1236 4.6 Diamylamine C10H23N 1256 3.9
1,2 Dibromo-ethane (47) C2H4Br2 2.18 995 trans-1,2-Dibromoethene(47) C2H2Br2 2.231 935 Dibutyl phthalate C8H22O4 1408 Dichloro-t-butyl alcohol C4H8Cl2O 1304 3.8 2,3 Dichlorodioxane C2H6Cl2O2 1391 3.7 Dichlorodifluoromethane (3) (Freon 12) CCl2F2 1.516 (-40ºC) 774.1 4.24
1,2 Dichloro ethane (47) C2H4Cl2 1.253 1193 cis 1,2-Dichloro-Ethene(3,47) C2H2Cl2 1.284 1061 trans 1,2-Dichloro-ethene(3,47) C2H2Cl2 1.257 1010 Dichloro-fluoromethane (3) (Freon 21) CHCl2F 1.426 (0ºC) 891 3.97
1-2-Dichlorohexafluoro cyclobutane (47) C4Cl2F6 1.654 669 1-3-Dichloro-isobutane C4H8Cl2 1.14 1220 3.4
Dichloro methane (3) CH2Cl2 1.327 1070 3.94 1,1-Dichloro-1,2,2,2 tetra fluoroethane CClF2-CClF2 1.455 665.3 3.73 Diethyl ether C4H10O 0.713 985 4.87 Diethylene glycol, monoethyl ether C6H14O3 0.988 1458
Diethylenimide oxide C4H9NO 1.00 1442 3.8 1,2-bis(DiFluoramino) butane (43) C4H8(NF2)2 1.216 1000
1,2bis(DiFluoramino)- 2-methylpropane (43)
1,2bis(DiFluoramino) propane (43) C3H6(NF2)2 1.265 960 2,2bis(DiFluoramino) propane (43) C3H6(NF2)2 1.254 890 2,2-Dihydroxydiethyl ether C4H10O3 1.116 1586 2.4
C4H9(NF2)2 1.213 900
Page 72
Page 73
TTFM 6.1 Transit Time Flow Meter
Substance Form Index Specific Gravity Sound Speed
v/°C - m/s/°C Δ
m/sec.
Dihydroxyethane C2H6O2 1.113 1658 2.1 1,3-Dimethyl-benzene (46) C8H10 0.868 (15ºC) 1343
1,2-1.0Dimethyl-benzene(29,46) C8H10 0.897 (20ºC) 1331.5 4.1 1,4-Dimethyl-benzene (46) C8H10 1334
2,2-Dimethyl-butane (29,33) C6H14 0.649 (20ºC) 1079 Dimethyl ketone C3H6O 0.791 1174 4.5
Dimethyl pentane (47) C7H16 0.674 1063 Dimethyl phthalate C8H10O4 1.2 1463 Diiodo-methane CH2I2 3.235 980 Dioxane C4H8O2 1.033 1376 Dodecane (23) C12H26 0.749 1279 3.85
1,2-Ethanediol C2H6O2 1.113 1658 2.1 Ethanenitrile C2H3N 0.783 1290
Ethanoic anhydride (22) (CH3CO)2O 1.082 1180 Ethanol C2H6O 0.789 1207 4.0
Ethanol amide C2H7NO 1.018 1724 3.4 Ethoxyethane C4H10O 0.713 985 4.87 Ethyl acetate (33) C4H8O2 0.901 1085 4.4 Ethyl alcohol C2H6O 0.789 1207 4.0 Ethyl benzene (46) C8H10 0.867(20ºC) 1338
Ethyl bromide (46) C2H5Br 1.461 (20ºC) 900 Ethyliodide (46) C2H5I 1.950 (20ºC) 876 Ether C4H10O 0.713 985 4.87
Ethyl ether C4H10O 0.713 985 4.87 Ethylene bromide (47) C2H4Br2 2.18 995
Ethylene chloride (47) C2H4Cl2 1.253 1193 Ethylene glycol C2H6O2 1.113 1658 2.1
50% Glycol/ 50% H2O 1578 d-Fenochone C10H16O 0.947 1320 d-2-Fenechanone C10H16O 0.947 1320 Fluorine F 0.545 (-143ºC) 403 11.31
Fluoro-benzene (46) C6H5F 1.024 (20ºC) 1189 Formaldehyde, methyl ester C2H4O2 0.974 1127 4.02
Formamide CH3NO 1.134 (20ºC) 1622 2.2 Formic acid, amide CH3NO 1.134 (20ºC) 1622
Freon R12 774 Furfural C5H4O2 1.157 1444 Furfuryl alcohol C5H6O2 1.135 1450 3.4
Fural C5H4O2 1.157 1444 3.7 2-Furaldehyde C5H4O2 1.157 1444 3.7 2-Furancarboxaldehyde C5H4O2 1.157 1444 3.7 2-Furyl-Methanol C5H6O2 1.135 1450 3.4 Gallium Ga 6.095 2870 (@30ºC)
Glycerin C3H8O3 1.26 1904 2.2
Page 73
Page 74
TTFM 6.1 Transit Time Flow Meter
Substance Form Index Specific Gravity Sound Speed
v/°C - m/s/°C Δ
m/sec.
Glycerol C3H8O3 1.26 1904 2.2 Glycol C2H6O2 1.113 1658 2.1 Helium (45) He4 0.125(-268.8ºC) 183
Heptane (22,23) C7H16 0.684 (20ºC) 1131 4.25 n-Heptane (29,33) C7H16 0.684 (20ºC) 1180 4.0 Hexachloro-Cyclopentadiene(47) C5Cl6 1.7180 1150
Hexadecane (23) C16H34 0.773 (20ºC) 1338 3.71 Hexalin C6H12O 0.962 1454 3.6 Hexane (16,22,23) C6H14 0.659 1112 2.71 n-Hexane (29,33) C6H14 0.649 (20ºC) 1079 4.53 2,5-Hexanedione C6H10O2 0.729 1399 3.6 n-Hexanol C6H14O 0.819 1300 3.8 Hexahydrobenzene (15) C6H12 0.779 1248 5.41 Hexahydrophenol C6H12O 0.962 1454 3.6 Hexamethylene (15) C6H12 0.779 1248 5.41 Hydrogen (45) H2 0.071 (-256ºC) 1187
2-Hydroxy-toluene (46) C7H8O 1.047 (20ºC) 1541 3-Hydroxy-tolune (46) C7H8O 1.034 (20ºC) 1500 Iodo-benzene (46) C6H5I 1.823 1114 Iodo-ethane (46) C2H5I 1.950 (20ºC) 876 Iodo-methane CH3I 2.28 (20ºC) 978 Isobutyl acetate (22) C6H12O 1180 4.85 Isobutanol C4H10O 0.81 (20ºC) 1212 Iso-Butane 1219.8 Isopentane (36) C5H12 0.62 (20ºC) 980 4.8
Isopropanol (46) C3H8O 0.785 (20ºC) 1170 Isopropyl alcohol (46) C3H8O 0.785 (20ºC) 1170 Kerosene 0.81 1324 3.6 Ketohexamethylene C6H10O 0.948 1423 4.0
Lithium fluoride (42) LiF 2485 1.29 Mercury (45) Hg 13.594 1449 Mesityloxide C6H16O 0.85 1310 Methane (25,28,38,39) CH4 0.162 405(-89.15ºC) 17.5
Methanol (40,41) CH4O 0.791 (20ºC) 1076 2.92 Methyl acetate C3H6O2 0.934 1211
o-Methylaniline (46) C7H9N 0.999 (20ºC) 1618 4-Methylaniline (46) C7H9N 0.966 (45ºC) 1480 Methyl alcohol (40,44) CH4O 0.791 (20ºC) 1076 2.92
Methyl benzene (16,52) C7H8 0.867 1328 4.27 2-Methyl-butane (36) C5H12 0.62 (20ºC) 980
Methyl carbinol C2H6O 0.789 1207 4.0 Methyl-chloroform (47) C2H3Cl3 1.33 985
Methyl-cyanide C2H3N 0.783 1290 3-Methyl cyclohexanol C7H14O 0.92 1400
Page 74
Page 75
TTFM 6.1 Transit Time Flow Meter
Substance Form Index Specific Gravity Sound Speed
v/°C - m/s/°C Δ
m/sec.
Methylene chloride (3) CH2Cl2 1.327 1070 3.94 Methylene iodide CH2I2 3.235 980
Methyl formate (22) C2H4O2 0.974 (20ºC) 1127 4.02 Methyl iodide CH3I 2.28 (20ºC) 978
2-Methylphenol (46) C7H8O 1.047 (20ºC) 1541 3-Methylphenol (46) C7H8O 1.034 (20ºC) 1500 Milk, homogenized 1548 Morpholine C4H9NO 1.00 1442 3.8
Naphtha 0.76 1225 Natural Gas (37) 0.316 (-103ºC) 753 Neon (45) Ne 1.207 (-246ºC) 595 Nitrobenzene (46) C6H5NO2 1.204 (20ºC) 1415 Nitrogen (45) N2 0.808 (-199ºC) 962 Nitromethane (43) CH3NO2 1.135 1300 4.0
Nonane (23) C9H2O 0.718 (20ºC) 1207 4.04 1-Nonene (27) C9H18 0.736 (20ºC) 1207 4.0 Octane (23) C8H18 0.703 1172 4.14 n-Octane (29) C8H18 0.704 (20ºC) 1212.5 3.50 1-Octene (27) C8H16 0.723 (20ºC) 1175.5 4.10 Oil of Camphor Sassafrassy 1390 3.8
Oil, Car (SAE 20a.30) 1.74 870 Oil, Castor C11H10O10 0.969 1477 3.6
Oil, Diesel 0.80 1250 Oil, Fuel AA gravity 0.99 1485 3.7 Oil (Lubricating X200) 1530 5019.9 Oil (Olive) 0.912 1431 2.75 Oil (Peanut) 0.936 1458 Oil (Sperm) 0.88 1440 Oil, 6 1509 2,2-Oxydiethanol C4H10O3 1.116 1586 2.4
Oxygen (45) O2 1.155 (-186ºC) 952 Pentachloro-ethane (47) C2HCl5 1.687 1082 Pentalin (47) C2HCl5 1.687 1082 Pentane (36) C5H12 0.626 (20ºC) 1020 n-Pentane (47) C5H12 0.557 1006 Perchlorocyclopentadiene(47) C5Cl6 1.718 1150 Perchloro-ethylene (47) C2Cl4 1.632 1036 Perfluoro-1-Hepten (47) C7F14 1.67 583 Perfluoro-n-Hexane (47) C6F14 1.672 508 Phene (29,40,41) C6H6 0.879 1306 4.65
ß-Phenyl acrolein C9H8O 1.112 1554 3.2 Phenylamine (41) C6H5NO2 1.022 1639 4.0 Phenyl bromide (46) C6H5Br 1.522 1170
Page 75
Page 76
TTFM 6.1 Transit Time Flow Meter
Substance Form Index Specific Gravity Sound Speed
v/°C - m/s/°C Δ
m/sec.
Phenyl chloride C6H5Cl 1.106 1273 3.6 Phenyl iodide (46) C6H5I 1.823 1114
Phenyl methane (16,52) C7H8 0.867 (20ºC) 1328 4.27 3-Phenyl propenal C9H8O 1.112 1554 3.2 Phthalardione C8H4O3 1125
Phthalic acid, anhydride C8H4O3 1125 Phthalic anhydride C8H4O3 1125 Pimelic ketone C6H10O 0.948 1423 4.0
Plexiglas, Lucite, Acrylic 2651 Polyterpene Resin 0.77 1099.8 Potassium bromide (42) Kbr 1169 0.71 Potassium fluoride (42) KF 1792 1.03 Potassium iodide (42) KI 985 0.64 Potassium nitrate (48) KNO3 1.859 (352ºC) 1740.1 1.1
Propane (2,13)(-45 to -130ºC) C3H8 0.585 (-45ºC) 1003 5.7 1,2,3-Propanetriol C3H8O3 1.26 1904 2.2 1-Propanol (46) C3H8O 0.78 (20ºC) 1222
2-Propanol (46) C3H8O 0.785 (20ºC) 1170 2-Propanone C3H6O 0.791 1174 4.5
Propene (17,18,35) C3H6 0.563 (-13ºC) 963 6.32 n-Propyl acetate (22) C5H10O2 1280 (2ºC) 4.63
n-Propyl alcohol C3H8O 0.78 (20ºC) 1222 Propylchloride (47) C3H7Cl 0.892 1058 Propylene (17,18,35) C3H6 0.563 (-13ºC) 963 6.32
Pyridine C6H5N 0.982 1415 4.1 Refrigerant 11 (3,4) CCl3F 1.49 828.3 3.56 Refrigerant 12 (3) CCl2F2 1.516 (-40ºC) 774.1 4.24 Refrigerant 14 (14) CF4 1.75 (-150ºC) 875.24 6.61 Refrigerant 21 (3) CHCl2F 1.426 (0ºC) 891 3.97 Refrigerant 22 (3) CHClF2 1.491 (-69ºC) 893.9 4.79 Refrigerant 113 (3) CCl2F-CClF2 1.563 783.7 3.44 Refrigerant 114 (3) CClF2-CClF2 1.455 665.3 3.73 Refrigerant 115 (3) C2ClF5 656.4 4.42
Refrigerant C318 (3) C4F8 1.62 (-20ºC) 574 3.88 Selenium (8) Se 1072 0.68
Silicone (30 cp) 0.993 990 Sodium fluoride (42) NaF 0.877 2082 1.32
Sodium nitrate (48) NaNO3 1.884 (336ºC) 1763.3 0.74 Sodium nitrite (48) NaNO2 1.805 (292ºC) 1876.8
Solvesso 3 0.877 1370 3.7 Spirit of wine C2H6O 0.789 1207 4.0
Sulphur (7,8,10) S 1177 -1.13 Sulphuric acid (1) H2SO4 1.841 1257.6 1.43
Tellurium (7) Te 991 0.73
Page 76
Page 77
TTFM 6.1 Transit Time Flow Meter
Substance Form Index Specific Gravity Sound Speed
v/°C - m/s/°C Δ
m/sec.
1,1,2,2-Tetrabromo-ethane(47) C2H2Br4 2.966120 1027 1,1,2,2-Tetrachloro-ethane(67) C2H2Cl4 1.595 1147 Tetrachloroethane (46) C2H2Cl4 1.553 (20ºC) 1170 Tetrachloro-ethene (47) C2Cl4 1.632 1036 Tetrachloro-methane (33,47) CCl4 1.595 (20ºC) 926 Tetradecane (46) C14H3O 0.763 (20ºC) 1331
Tetraethylene glycol C8H18O5 1.123 1586/5203.4 3.0 Tetrafluoro-methane (14) (Freon 14) CF4 1.75 (-150ºC) 875.24 6.61 Tetrahydro-1,4-isoxazine C4H9NO 1442 3.8
Toluene (16,52) C7H8 0.867 (20ºC) 1328 4.27 o-Toluidine (46) C7H9N 0.999 (20ºC) 1618
p-Toluidine (46) C7H9N 0.966 (45ºC) 1480 Toluol C7H8 0.866 1308 4.2
Tribromo-methane (46,47) CHBr3 2.89 (20ºC) 918 1,1,1-Trichloro-ethane (47) C2H3Cl3 1.33 985 Trichloro-ethene (47) C2HCl3 1.464 1028 Trichloro-fluoromethane (3) (Freon 11) CCl3F 1.49 828.3 3.56
Trichloro-methane (47) CHCl3 1.489 979 3.4 1,1,2-Trichloro-1,2,2-Trifluoro-Ethane CCl2F-CClF2 1.563 783.7
Triethyl-amine (33) C6H15N 0.726 1123 4.47 Triethylene glycol C6H14O4 1.123 1608 3.8 1,1,1-Trifluoro-2-Chloro-2-Bromo-Ethane C2HClBrF3 1.869 693
1,2,2-Trifluorotrichloro- ethane (Freon 113) CCl2F-CClF2 1.563 783.7 3.44 d-1,3,3-Trimethylnor- camphor C10H16O 0.947 1320
Trinitrotoluene (43) C7H5(NO2)3 1.64 1610 Turpentine 0.88 1255 Unisis 800 0.87 1346 Water, distilled (49,50) H2O 0.996 1498 -2.4
Water, heavy D²O 1400 Water, sea 1.025 1531 -2.4 Wood Alcohol (40,41) CH4O 0.791 (20ºC) 1076 2.92
Xenon (45) Xe 630 m-Xylene (46) C8H10 0.868 (15ºC) 1343 o-Xylene (29,46) C8H10 0.897 (20ºC) 1331.5 4.1
p-Xylene (46) C8H10 1334 Xylene hexafluoride C8H4F6 1.37 879 Zinc (7) Zn 3298
Page 77
Page 78
Appendix D
Temp °F Temp °C Velocity ft/s Temp °F Temp °C Velocity ft/s Temp °F Temp °C Velocity ft/s
0.0 -17.8
2.0 -16.7
4.0 -15.6
6.0 -14.4
8.0 -13.3
10.0 -12.2
12.0 11.0
14.0 10.0
16.0 -8.9
18.0 -7.8
20.0 -6.7
22.0 -5.6
24.0 -4.4
26.8 -3.3
28.0 -2.2
30.0 -1.1
32.0 0.0
34.0 1.1
36.0 2.2
38.0 3.3
40.0 4.4
42.0 5.6
44.0 6.7
46.0 7.8
48.0 8.9
50.0 10.0
52.0 11.1
54.0 12.2
56.0 13.3
58.0 14.4
60.0 .15.56
62.0 16.7
64.0 17.9
66.0 18.9
68.0 20.0
70.0 21.1
72.0 22.2
74.0 23.3
76.0 24.4
78.0 25.6
80.0 26.7
82.0 27.8
84.0 28.9
86.0 30.0
88.0 31.1
90.0 32.2
92.0 33.3
94.0 34.4
96.0 35.6
98.0 36.7
TTFM 6.1 Transit Time Flow Meter
Sonic Velocity Relative to Temperature of Pure Water
4240 100.0 37.8 5003 200.0 93.3 5080 4267 102.0 38.9 5010 202.0 94.4 5077 4293 104.0 40.0 5016 204.0 95.6 5075 4319 106.0 41.1 5022 206.0 96.7 5077 4344 108.0 42.2 5028 208.0 97.8 5069 4368 110.0 43.3 5033 210.0 98.9 5066 4392 112.0 44.4 5038 212.0 100.0 5063 4416 114.0 45.6 5043 214.0 101.1 5059 4438 116.0 46.7 5048 216.0 102.2 5056 4460 118.0 47.8 5052 218.0 103.3 5052 4482 120.0 48.9 5057 220.0 104.4 5049 4503 122.0 50.0 5061 222.0 105.6 5045 4524 124.0 51.1 5065 224.0 106.7 5041 4544 126.0 52.2 5068 226.0 107.8 5037 4563 128.0 53.3 5072 228.0 108.9 5033 4582 130.0 54.4 5075 230.0 110.0 5029 4601 132.0 55.6 5078 232.0 111.1 5024 4619 134.0 56.7 5081 234.0 112.2 5020 4637 136.0 57.8 5084 236.0 113.3 5015 4654 138.0 58.9 5086 238.0 114.4 5011 4671 140.0 60.0 5089 240.0 115.6 5006 4687 142.0 61.1 5091 242.0 116.7 5001 4703 144.0 62.2 5093 244.0 117.8 4996 4719 146.0 63.3 5094 246.0 118.9 4991 4734 148.0 64.4 5096 248.0 120.0 4986 4748 150.0 65.6 5097 250.0 121.1 4981 4763 152.0 66.7 5098 260.0 126.7 4944 4776 154.0 67.8 5099 270.0 132.2 4911 4790 156.0 68.9 5100 280.0 137.8 4879 4803 158.0 70.0 5101 290.0 143.3 4843 4816 160.0 71.1 5102 300.0 148.9 4806 4828 162.0 72.2 5102 310.0 154.4 4767 4840 164.0 73.3 5102 320.0 160.0 4724 4852 166.0 74.4 5102 330.0 165.6 4678 4863 168.0 75.6 5102 340.0 171.1 4633 4874 170.0 76.7 5102 350.0 176.7 4587 4885 172.0 77.8 5101 360.0 182.2 4537 4895 174.0 78.9 5101 370.0 187.8 4488 4905 176.0 80.0 5100 380.0 193.3 4439 4915 178.0 81.1 5099 390.0 198.9 4386 4925 180.0 82.2 5098 400.0 204.4 4331 4934 182.0 83.3 5097 410.0 210.0 4272 4943 184.0 84.4 5096 420.0 215.6 4209 4951 186.0 85.6 5094 430.0 221.1 4147 4959 188.0 86.7 5093 440.0 226.7 4081 4967 190.0 87.8 5091 450.0 232.2 4003 4975 192.0 88.9 5089 460.0 237.8 3937 4983 194.0 90.0 5087 470.0 243.3 3871 4990 196.0 91.1 5085 480.0 248.9 3806 4997 198.0 92.2 5082 490.0 254.4 3740
Page 78
Page 79
TTFM 6.1 Transit Time Flow Meter
Sonic Velocity Relative to Temperature of Pure Water
Temp °F Temp °C Velocity m/s Temp °F Temp °C Velocity m/s Temp °F Temp °C Velocity m/s
0.0 -17.8
2.0 -16.7
4.0 -15.6
6.0 -14.4
8.0 -13.3
10.0 -12.2
12.0 11.0
14.0 10.0
16.0 -8.9
18.0 -7.8
20.0 -6.7
22.0 -5.6
24.0 -4.4
26.8 -3.3
28.0 -2.2
30.0 -1.1
32.0 0.0
34.0 1.1
36.0 2.2
38.0 3.3
40.0 4.4
42.0 5.6
44.0 6.7
46.0 7.8
48.0 8.9
50.0 10.0
52.0 11.1
54.0 12.2
56.0 13.3
58.0 14.4
60.0 .15.56
62.0 16.7
64.0 17.9
66.0 18.9
68.0 20.0
70.0 21.1
72.0 22.2
74.0 23.3
76.0 24.4
78.0 25.6
80.0 26.7
82.0 27.8
84.0 28.9
86.0 30.0
88.0 31.1
90.0 32.2
92.0 33.3
94.0 34.4
96.0 35.6
98.0 36.7
1292.45 100.0 37.8 1525.03 200.0 93.3 1548.38
1300.64 102.0 38.9 1526.99 202.0 94.4 1547.60
1308.63 104.0 40.0 1528.86 204.0 95.6 1546.78
1316.44 106.0 41.1 1530.67 206.0 96.7 1547.60
1324.06 108.0 42.2 1532.4 208.0 97.8 1545.02
1331.50 110.0 43.3 1534.06 210.0 98.9 1544.08
1338.77 112.0 44.4 1535.64 212.0 100.0 1543.11
1345.86 114.0 45.6 1537.16 214.0 101.1 1542.10
1352.78 116.0 46.7 1538.61 216.0 102.2 1541.05
1359.53 118.0 47.8 1539.99 218.0 103.3 1539.97
1366.12 120.0 48.9 1541.30 220.0 104.4 1538.85
1372.55 122.0 50.0 1542.55 222.0 105.6 1537.70
1378.82 124.0 51.1 1543.74 224.0 106.7 1536.51
1384.94 126.0 52.2 1544.86 226.0 107.8 1535.29
1390.90 128.0 53.3 1545.91 228.0 108.9 1534.03
1396.72 130.0 54.4 1546.91 230.0 110.0 1532.74
1402.39 132.0 55.6 1547.84 232.0 111.1 1531.42
1407.91 134.0 56.7 1548.72 234.0 112.2 1530.06
1413.30 136.0 57.8 1549.53 236.0 113.3 1528.67
1418.55 138.0 58.9 1550.29 238.0 114.4 1527.26
1423.66 140.0 60.0 1550.99 240.0 115.6 1525.81
1428.64 142.0 61.1 1551.63 242.0 116.7 1524.33
1433.48 144.0 62.2 1552.21 244.0 117.8 1522.83
1438.20 146.0 63.3 1552.74 246.0 118.9 1521.29
1442.80 148.0 64.4 1553.22 248.0 120.0 1519.73
1447.27 150.0 65.6 1553.64 250.0 121.1 1518.14
1451.62 152.0 66.7 1554.01 260.0 126.7 1507.00
1455.85 154.0 67.8 1554.32 270.0 132.2 1497.00
1459.97 156.0 68.9 1554.59 280.0 137.8 1487.00
1463.97 158.0 70.0 1554.80 290.0 143.3 1476.00
1467.86 160.0 71.1 1554.98 300.0 148.9 1465.00
1471.64 162.0 72.2 1555.07 310.0 154.4 1453.00
1475.31 164.0 73.3 1555.13 320.0 160.0 1440.00
1478.88 166.0 74.4 1555.15 330.0 165.6 1426.00
1482.34 168.0 75.6 1555.11 340.0 171.1 1412.00
1485.70 170.0 76.7 1555.03 350.0 176.7 1398.00
1488.96 172.0 77.8 1554.90 360.0 182.2 1383.00
1492.13 174.0 78.9 1554.72 370.0 187.8 1368.00
1495.19 176.0 80.0 1554.49 380.0 193.3 1353.00
1498.16 178.0 81.1 1554.22 390.0 198.9 1337.00
1501.04 180.0 82.2 1553.91 400.0 204.4 1320.00
1503.82 182.0 83.3 1553.55 410.0 210.0 1302.00
1506.52 184.0 84.4 1553.14 420.0 215.6 1283.00
1509.13 186.0 85.6 1552.70 430.0 221.1 1264.00
1511.65 188.0 86.7 1552.21 440.0 226.7 1244.00
1514.08 190.0 87.8 1551.67 450.0 232.2 1220.00
1516.44 192.0 88.9 1551.10 460.0 237.8 1200.00
1518.70 194.0 90.0 1550.48 470.0 243.3 1180.00
1520.89 196.0 91.1 1549.82 480.0 248.9 1160.00
1523.00 198.0 92.2 1549.12 490.0 254.4 1140.00
Page 79
Loading...