Greyline TTFM 6.1 User Manual

USER'S GUIDE
Installation & Operation
Instructions
Transit Time Flow Meter
Model TTFM 6.1
www.greyline.com
Manual Series A.1.6
Note: This page has been left blank intentionally.
TTFM 6.1 Transit Time Flow Meter
INDEX
CONNECTIONS ...................................................................................................................................... 4
KEYPAD SYSTEM .................................................................................................................................. 6
MENU SYSTEM ...................................................................................................................................... 7
ICONS ...................................................................................................................................................... 8
MESSAGE ICON ..................................................................................................................................... 9
STATUS ................................................................................................................................................... 9
PASSWORD ........................................................................................................................................... 11
MENU SELECTIONS ............................................................................................................................ 11
UNITS/MODE ........................................................................................................................................ 12
SET UP ................................................................................................................................................... 14
CALIBRATION ..................................................................................................................................... 17
RELAY PARAMETERS ........................................................................................................................ 19
DATA LOGGING .................................................................................................................................. 20
COMMUNICATION (OPTIONAL) ...................................................................................................... 22
SPECIAL FUNCTIONS ......................................................................................................................... 24
TYPICAL SENSOR INSTALLATION .................................................................................................. 27
SENSOR MOUNTING ........................................................................................................................... 30
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B1 KIT .......................................................... 31
1 CROSS INSTALLATION OVERVIEW – TMK-B1 KIT ................................................................... 35
2 OR 4 CROSS INSTALLATION OVERVIEW - TMK-B21 OR TMK-B22 KIT ................................ 42
1 CROSS INSTALLATION OVERVIEW – TMK-B21 OR TMK-B22 KIT ........................................ 46
SENSOR MOUNTING/COUPLING RECOMMENDATIONS ............................................................ 53
ENCLOSURE INSTALLATION ........................................................................................................... 54
FIELD TROUBLESHOOTING .............................................................................................................. 55
COMMON QUESTIONS AND ANSWERS .......................................................................................... 58
APPLICATIONS HOTLINE .................................................................................................................. 60
PRODUCT RETURN PROCEDURE .................................................................................................... 60
SPECIFICATIONS ................................................................................................................................. 64
APPENDIX A - CONVERSION TABLE .............................................................................................. 65
PIPE CHARTS ........................................................................................................................................ 66
APPENDIX C – LIQUID SPEED OF SOUND ...................................................................................... 71
APPENDIX D ......................................................................................................................................... 78
IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications. Please read this manual carefully before installation and operation. Any unauthorized repairs or modifications may result in a suspension of the warranty. If this product is not used as specified by the manufacturer, protection may be impaired.
Available in Adobe Acrobat pdf format
TTFM 6.1 Transit Time Flow Meter
CONNECTIONS: POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz
10VA. No adjustments are necessary for voltages within this range. Connect L (Live) N (Neutral) and AC Ground.
Optional DC input model requires 9-32 VDC/10 Watts. Connect to + and - terminals. Optional Thermostat and Heater modules are available rated for specifically 115 VAC or specifically
230 VAC. IMPORTANT NOTE: To comply with electrical safety standards, AC power input and relay connection
wires must have conduit entry to the instrument enclosure. Installation requires a switch, overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections. Note: Use of instrumentation over 40°C ambient requires special field wiring. Note: Some models feature a user replaceable fuse. Fuse is 2 Amp 250V (T2AL250V), located on the
power supply.
100-240 VAC Meter CONNECTIONS
TTFM 6.1 Transit Time Flow Meter
TTFM 6.1 Transit Time Flow Meter
KEYPAD SYSTEM
The diagram on page 7 shows the TTFM 6.1 menu system. Arrows show the four directions to leave a menu box. Pressing a corresponding keypad arrow will move to the next item in the direction shown. Move the cursor (highlighted) under numerals and increase or decrease numerals with the and keys.
To store calibration values permanently (even through power interruptions), press the button.
--24 hr log----------
USG/m
BPS 9600
-- -------
%
4.00 USG/m
emperature
Date Feb. 12/20
10
Total 50138 USG
34.82 USG/m Average
52.20 USG/m Maximum 11:08:00 Max Time
0.000 USG/m Minimum
9:15:00 Min Time
--Messages---------­L Data og Logging
dLog Use 0.00000%
Sensor Good
0.00
Tot 20130 USG Relays 1 2 3 4 5 6
--Status------------
Velocity ft/s
0.00 Flow 0.00 USG/m Min Flow 4.00 USG/m Signal Strength 100% Exp. SOS 4900 ft/s Meas. SOS 4900 ft/s
MENU SYSTEM
*
--Password----------
Password 0000
TTFM 6.1 Transit Time Flow Meter
--Units/Mode-------­Mode Flow
Linear in Volume USG Multiplier x1 Decimal 0s Velocity ft/s Flow USG/m Decimal 2s T F
Setup------
r SE16B
Senso
--Menu-------------­Units / Mode
Setup Calibration Relay Parameters Data Logging Communication Special Functions Simulation Configuration
Angle 37 Fluid Water Temp Mode Fixed Temp 77.0 F Pipe PVC OD 4.5000 in Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal Strength
100
--Calibration------­Mode Flow
20mA 500.00 USG/m 4mA 0.00 USG/m LOS Time 10 sec Min Flow Damping Mode FIR Percent 10% Window 1.0 ft/s Cal Constant 1.00
--Relay Parameters--
Relay 1
Function Flow On 1000 USG Off 0.000 USG
--Data Logging-------
Log Site ID 01
Mode Flow File Format .LG2 Date 6 7Jun 2 /201 Time 12:28:41 Interval 30sec Data Log Logging
--Communication-----
Protocol Modbus Address 001
Parity Even Stop Bits 1
°
optional features
* Menu only appears if "New Password" has been
changed from 0000 in "Special Functions" menu.
--Special Functions-
Language English
Analog Out 4-20mA
Backlight High Reset Totalizer NO Neg. Totals NO Rev. Flow OFF Capture Par NO Capture WF NO Restore Defaults NO New Password 0000
--Simulation--------
Test Actual Flow /m 250USG
Flow 4-20mA 5.60mA
Relays 1 2 3 4 5 6
--Configuration-----
Serial# 12345 Utility 1.25.0 .16
1. Transit Time 38.1
CommBoard 1. . 21 19 Relays 2
Analog Out 1
ICONS
TTFM 6.1 Transit Time Flow Meter
1.
1.
1.
1.
2.
2.
2.
2.
3.
3.
4. USB file download .ing
Message waiting. Press . from main page to view
Data logging .off
Data logging .on
File download completed.
Download Error.
TTFM Echo OK.
TTFM - , Empty Pipe .Low Signal / No Echo or high Aeration
TTFM - No Sensors Attached / Wrong Settings
TTFM 6.1 Transit Time Flow Meter
USG/m
0.00
Tot 20130 USG Relays 1 2 3 4 5 6
--Status-----------­Velocity ft/s 0.00
Flow 0.00 USG/m Min Flow 4.00 USG/m Signal Strength 100% Exp. SOS 4900 ft/s Meas. SOS 4900 ft/s
MAIN DISPLAY
The Main Display shows the units selected from the Units/Mode menu, flow rate or velocity rate being measured, totalizer, totalizer multiplier, and relay states. The TTFM 6.1 will go to this display after start-up.
MESSAGE ICON
Press from the Main Display to view status of the data logger and error/warning messages provided by the instrument. The Message Icon will appear on the Main Display if error messages are being generated by the instrument. Press to return to the Main Display.
STATUS
Press from the Main Display to view Status of the measurement. Press to return to the Main Display.
Velocity Displays flow velocity in ft/s or m/s, selected in the
Units/Mode menu.
Flow Displays flow rate in units selected in the Units/Mode
menu. A list of flow rate units is provided in the Units/Mode section of the manual.
Min Flow Displays a read-only value for the minimum flow cutoff,
in units which match the Flow selection. Measured flow rates below the Min Flow will result in the displayed flow rate on the LCD display to be 0.0. This parameter is used to suppress electrical noise at zero flow conditions, and it is typically set to the flow rate equivalent of 0.1 ft/sec in the programmed pipe size. The Min Flow can be adjusted in the Calibration menu.
Signal Strength Displays magnitude of signal being received by the
ultrasonic sensors. 100% is the ideal signal strength. Signal strengths less than 100% could indicate poor pipe conditions (corrosion), highly aerated water, or programmed setup parameters which don’t closely match field conditions. Consideration should be made to use 1-cross installation method in such cases, if not already using it.
Status (cont.)
TTFM 6.1 Transit Time Flow Meter
--Status-----------­Velocity ft/s 0.00
Flow 0.00 USG/m Min Flow 4.00 USG/m Signal Strength 100% Exp. SOS 4900 ft/s Meas. SOS 4900 ft/s
Exp. SOS Displays the expected fluid speed of sound
measurement, in units that match the Velocity. The expected speed of sound is based on the pipe, fluid, and temperature selection in the Setup menu.
Meas. SOS Displays the measured fluid speed of sound, in units that
match Exp. SOS. The meter calculates this value based on the time it takes for the signal to arrive from one transducer to another. Large differences between expected and measured speed of sound (> 10%) typically indicate an error in the setup of the instrument. Verify the following are correct in the Setup menu and with the physical installation of the transducers:
- Pipe Material
- Pipe OD
- Pipe Wall Thickness
- Liner Type
- Liner Thickness
- Fluid Type
- Fluid Temperature
- Crossings
- Separation Distance
Page 10
TTFM 6.1 Transit Time Flow Meter
24 HR LOG
Press from the Main Display to view a formatted flow report. Press to scroll down one day or repeatedly to scroll to a specific date. Up to 365 days will be stored. Newest date will overwrite the oldest. Press to return to the Main Display.
IMPORTANT: Inserting a USB drive into the meter while on this screen will transfer 24 HR Log data to the USB drive in .csv format.
PASSWORD
The Password (a number from 0000 to 9999) prevents unauthorized access to the Calibration menu.
From the Main Display press the key to get to Password. Factory default password is 0000 and if it has not been changed, this screen will be bypassed completely.
A new password can be stored by going to the Special Functions New
Password menu.
If a user password is required, press to place the cursor under the first digit and or to set the number, then to the second digit, etc. Press  or to proceed
to the Menu Selections screen.
MENU SELECTIONS
The Menu selections page is used to navigate to specific menus which are described in more detail on the following pages.
Press or to navigate to different menus, and to enter the selected menu.
Page 11
store your selection then the
to the next menu
item
.
next menu item.
as an example. Press
to store your selection then
to the next menu i
tem.
menu item.
selection then
to the next menu item.
--Units/Mode-------­Mode Flow
Linear in Volume USG Multiplier x1
Decimal 0s
Velocity ft/s Flow USG/m
Decimal 2s
emperatureT F
TTFM 6.1 Transit Time Flow Meter
UNITS/MODE
At Mode, press the and then the or to select Flow or Velocity. Flow mode displays the flow rate in engineering units (e.g. gpm, litres/sec, etc.) Press the to store your selection then the to the next menu item.
At Linear press the key and then the or to select your units of measurement. The Linear units define what units the pipe dimensions and sensor spacing will be displayed in. Typically inches or mm is selected. Press the to
At Volume, press the  and then the  or  to select units for volume. Note: “bbl” denotes US oil barrels. Press the to store your selection then the to the
At Multiplier, press the  and then the  or  to select the totalizer multiplier. Multipliers are used when resolution down to single digit is not required, or when you don’t want to convert from gallons to thousands of gallons,
At Decimals (Volume), press the  and then the  or  to select the number of decimal points to be present on the totalizer display on the LCD screen. Default = 0. Options = 0, 1, 2. Press the to store your selection then the to the next
At Velocity, press the and then the  or  to select the engineering units for flow velocity and sonic velocity of the fluid. Press  to store your
Page 12
TTFM 6.1 Transit Time Flow Meter
menu item
, orto
exit back to the Menu Selection screen
.
UNITS/MODE (cont.)
At Flow, press the and then the or to select the engineering units for flow rate. Press to store your selection then to the next menu item.
Available Flow Rate Engineering Units:
Abbreviation Description Abbreviation Description
USG/d US gallons per day L/d liters per day USG/h US gallons per hour L/h liters per hour USG/m US gallons per minute L/m liters per minute USG/s US gallons per second L/s liters per second ft3/d cubic feet per day m3/d cubic meters per day ft3/h cubic feet per hour m3/h cubic meters per hour ft3/m cubic feet per minute m3/m cubic meters per minute ft3/s cubic feet per second m3/s cubic meters per second bbl/d barrels per day (1 bbl = 42 USG) IG/d Imperial gallons per day bbl/h barrels per hour (1 bbl = 42 USG) IG/d Imperial gallons per day bbl/m bbl/d USMG/d US million gallons per day IMG/d Imperial million gallons per day USMG/h US million gallons per hour IMG/h Imperial million gallons per hour USMG/m US million gallons per minute IMG/m Imperial million gallons per minute USMG/s US million gallons per second IMG/s Imperial million gallons per second
barrels per minute (1 bbl = 42 USG) barrels per second (1 bbl = 42 USG)
IG/d Imperial gallons per day IG/d Imperial gallons per day
At Decimals (Flow), press the  and then the  or  to select the number of decimal points to be present on the flow rate display on the LCD screen. Default =
2. Options = 0, 1, 2. Press the to store your selection then the to the next menu item.
At Temperature, press the and then the or to select units for temperature. Press the to store your selection then the to go back to another
Page 13
TTFM 6.1 Transit Time Flow Meter
-- -------Setup-----­r SE16B Senso
Angle 37°
Fluid Water Temp Mode Fixed
Temp 77.0 F
Pipe PVC
OD 4.5000 in
Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal
Strength100%
SET UP
Press or to position curser at Setup, and to enter. Use  or  to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Sensor Select
Angle
Choose SE16B.
Select angle which matches the transducer pair connected to the TTFM. Options: 35, 37, 39, and 41. Angle is determined by the part number on the SE16-B transducer label. Guide:
Part Number on SE16-B Label Corresponding Transducer Angle
SE16-B-35 35 SE16-B-37 37 SE16-B-39 39 SE16-B-41 41
Fluid
Vel@25C
Select fluid type.
When Fluid = Other, enter the fluid velocity at 25C from table or other reference. Engineering units may be m/s or ft/s depending on Units menu programming.
dV/C
Temp Mode
Temp
Pipe
Pipe Vel
OD
Wall
When Fluid = Other, Enter fluid velocity adjustment factor over change in temperature in units of m/s or ft/s per °C.
Choose Fixed.
Enter fluid operating temperature in displayed engineering units.
Select pipe material.
When Pipe = Other, enter pipe material speed of sound (consult factory).
Highlight the digits and then or  to change the numbers and decimal point. Pipe OD should be entered as the exact outside diameter of the pipe where the sensor is mounted. Refer to the Pipe Charts Appendix in this manual for outside diameter of common pipe types and sizes.
Enter pipe wall thickness. Pipe wall thickness should be entered as the exact wall thickness of the pipe where the sensor is mounted. Refer to the Pipe Charts Appendix in this manual for wall thicknesses of common pipe types and sizes.
Lining
Select liner material.
Page 14
TTFM 6.1 Transit Time Flow Meter
2-24
Crossings = 2
> 24Crossings = 1
= 1 in cases such as these.
-- -------Setup-----­r SE16B Senso
Angle 37°
Fluid Water Temp Mode Fixed
Temp 77.0 F
Pipe PVC
OD 4.5000 in
Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal
Strength100%
SET UP (cont.)
Vel
Thick
Crossings
When Lining = Other, enter speed of sound of liner (consult factory).
When Lining ≠ None, enter liner thickness.
Crossings 1 = Z mounting
Crossings 2 = V mounting
Crossings 4 = W mounting
Nominal Pipe Size, Inches Recommended Crossings
Zero Tare
Sens Space
Velocity
Older pipes are often degraded or scaled on the inside. These conditions can hinder the ability to receive a strong signal when Crossings = 2. Greyline suggests starting with Crossings
Used to calibrate zero-flow measured by the TTFM 6.1 in process. Flow in the pipe should be confirmed as 0 before enabling, or significant errors in flow accuracy could occur.
Set Calibration/Damping to 0%, and under no flow conditions and with a full pipe, select Yes to force readings to zero.
After sensor, angle, fluid, and pipe material are defined, this displays the calculated sensor spacing. Also called the separation distance. The sensors will be set to this dimension when installed on the pipe, as described later in this manual.
Displays the measured velocity after the sensors have been connected at the specified separation distance.
Page 15
TTFM 6.1 Transit Time Flow Meter
-- -------Setup-----­r SE16B Senso
Angle 37°
Fluid Water Temp Mode Fixed
Temp 77.0 F
Pipe PVC
OD 4.5000 in
Wall 0.2500 in Lining None Crossings 2 Zero Tare No Sens Space 2.299in Velocity 0.00 ft/s
Signal
Strength100%
SET UP (cont.)
Signal Strength
Displays magnitude of signal being received by the ultrasonic
sensor. Should be 100% under ideal operating conditions. Signal strengths less than 100% do not indicate that the meter is not reliable, however, the meter may be more susceptible to complete signal loss should process conditions like entrapped air worsen. When signal strength is less than 100%, consideration should be made to using 1-cross mounting method if this is not the current mounting mode.
Page 16
TTFM 6.1 Transit Time Flow Meter
--Calibration------­Mode Flow
20mA 500.00 USG/m
4mA 0.00 USG/m LOS Time 10 sec Min Flow 4.00 USG/m Damping
Mode FIR
Percent 10%
Window 1.0 ft/s Cal Constant 1.00
CALIBRATION
Press or to position curser at Calibration menu, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Mode
Displays the Mode which was selected in the Units/Mode menu. This is read-only.
20mA
Press  then  or  to change the numbers and decimal point position. Use this menu to set the corresponding flow rate that will be represented by 20mA analog output. If maximum flow is unknown, enter an estimated flow rate and observe actual flow to determine the correct maximum value. Any velocity or flow rate up to +40 ft/sec (12.0 m/sec) may be selected.
4mA
Press  then  or  to set the flow rate corresponding to 4mA analog output. This setting may be left at zero or can be raised to any value less than the 20mA setting, or lowered to any velocity or corresponding flow rate down to -40 ft/sec (-12 m/sec).
LOS Time
Use LOS Time to suppress intermittent loss of signal. Example: systems with high concentrations of undissolved gasses will cause fluctuations in signal strength when the gasses move past the ultrasonic signal. If a complete loss of signal is experienced, the TTFM 6.1 will hold the last valid reading for the duration of the LOS Time. If the signal strength returns before the LOS Time is expired, because the ultrasonic signal is no longer being impeded, the meter will return to normal operation automatically. If signal strength does not return after the LOS Time has expired, then the meter will report zero flow on the LCD display and outputs, and produce a Low Signal alarm. Default LOS Time is 30 seconds, and the value can be set between 0 and 99 seconds.
Min Flow
Flow rates below this setting will be displayed as zero flow. Default flow rate is 0.1 ft/sec for the pipe size programmed in the Setup menu.
Page 17
TTFM 6.1 Transit Time Flow Meter
av
erage, both the FIR and LOW PASS filter behave the same.
--Calibration-------
Mode Flow
20mA 500.00 USG/m
4mA 0.00 USG/m LOS Time 10 sec Min Flow 4.00 USG/m Damping
Mode FIR
Percent 10%
Window 1.0 ft/s Cal Constant 1.00
CALIBRATION (cont.)
Damping
Mode
Choose between OFF, FIR (Default), or LOW PASS.
When measured flows are outside the Window of the running average, the FIR filter will reduce the damping average so that a fast response can be made to the sudden change in flow rate.
The LOW PASS filter will ignore measured flow rates outside the Window, while holding the running average, until there are enough data points outside the Window to cause a step­response to the new measured value.
While measured flows are within the Window of the running
Percent
Higher percentages increase the number of measurements which are averaged together to produce a stable flow reading. Higher percentages also increase the time it takes for the meter to make a step-response to the measured flow rate outside the Window in the LOW PASS Mode.
Window
Defines the Window around the running average, in units of Velocity set in the Units/Mode menu. Measurements made inside the Window are added to the running average, and measurements outside the Window effect the response of the meter as described in the Mode section.
Cal Constant
Calibration constant defined when the TTFM was calibrated at the Greyline factory.
Press to return to Menu Selections.
Page 18
TTFM 6.1 Transit Time Flow Meter
or
for this to work properly.
--Relay Parameters--
Relay 1
Function Flow On 1000 USG Off 0.000 USG
RELAY PARAMETERS
Press or to position curser at Relay Parameters, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Relay
Press  and  or  to select a corresponding relay number (2 relays are standard, 4 additional are optional).
Function
Pulse
Press  or  to select Off, On, Pulse,
Direction, or Flow.
Press  and set digits to the flow volume increment required between relay pulses. Use this feature for remote samplers, chlorinators or totalizers. Minimum time between pulses is
2.25 seconds and pulse duration is 350 milliseconds.
Return to Relay and change settings for each relay number.
Press to return to Menu Selections.
Direction
When flow is in the positive direction, the relay will be disengaged, when flow is negative, the relay engages. Note: Rev. Flow in the Special Functions menu must be ON
INVERT
Flow
Mode Select Pump
Pump mode provides separate On/Off settings where the
relay will energize at one flow rate and de-energize at another.
On Highlight the numerals and press or to set digits to
the required relay On set point.
Off set digits to the required Off set point.
Page 19
TTFM 6.1 Transit Time Flow Meter
DATA LOGGING
Press or to position curser at Data Logging, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Log Site ID Enter a number from 00 to 99. The site ID will become part of
the downloaded file name to help distinguish downloads from different instruments. Press to store the setting.
Mode Select Velocity (e.g. ft/sec or m/sec) or Flow (e.g. USGPM or
l/sec). Press to store the setting. This setting cannot be changed after a log was started. To change, first stop the log, then change the mode.
File Format Choose .LG2 to download data in .lg2 format for viewing on
Greyline Logger software. Choose .CSV to download data in .csv format for import directly to Excel. This menu option can be changed at any time without adversely affecting existing data.
Date Press , and or to scroll and select Month, Day and
Year. Press to store the setting.
Time Press , and or to select the current time in Hours,
Minutes and Seconds. Press to store the setting.
Interval Press or to select the logging interval. Press to store
the setting. Greyline recommends choosing an interval which will give you as much resolution as required and no more. Choosing too often of an interval for what is required will result in larger data files, which may take a long time to download to USB. Reference page 18 for specific download times. In critical installations, data should be downloaded often.
Data Log Stop, Start or Delete the log file. Press or to select Delete
and to delete the log file. Press or to select Start and to start the logger.
Important Note: You MUST Delete an old log and Start a new log AFTER having made changes to Log Site ID, Mode, Date, Time and/or Interval for those changes to be applied.
Important Note: Changing any of the parameters in the Units/Mode menu will start a new log. It is recommended that you Delete and start a new log after changing any Units/Mode settings.
Page 20
TTFM 6.1 Transit Time Flow Meter
RETRIEVING LOG FILE
Plug a USB Flash Memory Drive (one is included with the TTFM 6.1) into the USB output port on the Panel of the meter. The instrument display will show the data download icon until the log file is transferred to the memory card. The USB flash drive may be removed when the icon for download successful appears.
Download file names will appear in this format:
Tag is set according to the Log Site ID entered in the instrument Data
Logging menu.
Download letter will be A for the first download from an instrument. B for the second, then C etc. At the letter Z a - character will appear indicating that the maximum number of downloads for that instrument are on the USB flash drive. Older files can be erased or moved from the flash memory drive or a new memory drive can be used.
Note: Downloading files in .lg2 format will take approximately 35 seconds per
1% of internal log memory used. Downloading files in .csv format will take approximately 8 minutes per 1% of internal log memory used.
OPENING .LG2 FILES
Install Greyline Logger on your PC or laptop. Select File/Open/Instrument Log (.log) to open the log file from your USB flash drive. Greyline Logger software is available on Greyline’s website, www.greyline.com. Data can also be converted to .CSV via Greyline Logger software.
OPENING .CSV FILES
Use a datasheet program such as Microsoft Excel® to import data in a comma delimited format. Use Excel to manipulate or graph data.
Page 21
TTFM 6.1 Transit Time Flow Meter
setting.
COMMUNICATION (Optional)
Press or to position curser at Communication, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
MODBUS Protocol Information:
Transceiver: 2-wire, half-duplex Data format: 8 Data Bits Floating Point Byte Order: ABCD
Termination: Jumper JP1 selectable 120Ω resistor. TB1 & TB2 = OFF,
TB2 & TB3 = ON
Biasing: None
HART® (Highway Addressable Remote Transducer) Protocol Information:
HART Version: 7.0
Device Description Files:
DD files allow the user’s handheld HART communicator to fully configure the TTFM 6.1 Greyline provides DD files for the Emerson 475 Communicator. The files are included in the USB drive provided with your TTFM 6.1 meter. You may also request the files from Greyline by calling or emailing us at info@greyline.com. Warning: The TTFM 6.1 and associated DDs are pending certification from the Fieldcomm Group.
Connections: HART Protocol uses a digital signal superimposed on the 4-
20mA output. When the 4-20mA output of the TTFM 6.1 is
connected with a load resistor (230Ω to 600Ω), the HART
communicator can be connected on the loop in order to communicate.
Protocol
Address
(Modbus)
Choose MODBUS or HART.
Device address for the TTFM. Valid range: 001-247 (Default:
001). This number should be unique across the bus. Press or to scroll, to select digits, and press to store the
Page 22
TTFM 6.1 Transit Time Flow Meter
found in separate TTFM 6.1 Serial Communications Manual.
COMMUNICATION (Optional) (cont.)
BPS
(Modbus)
Baud rate for the MODBUS communications. Press  or to select, and to store the setting. Options: 4800, 9600, 19200, 38400, 57600, 76800, and 115200 (Default: 9600).
Parity
(Modbus)
Error checking parity for the MODBUS communications. Press or to select, and to store the setting. Options: None, Even, and Odd (Default: Even).
Stop Bits
(Modbus)
Press  or  to select, and to store the setting. Options: 1 or 2 (Default: 1).
Note: The Modbus register table, and HART configuration instructions can be
Page 23
TTFM 6.1 Transit Time Flow Meter
--Special Functions-
Language English Analog Out 4-20mA Backlight High Reset Totalizer NO
Neg. Totals NO Rev. Flow OFF Capture Par NO
Capture WF NO
Restore Defaults NO
New Password 0000
SPECIAL FUNCTIONS
Press or to position curser at Special Functions, and to enter. Use or to position cursor before each menu item and to enter. When settings are completed press to store and again to return to the Main Menu.
Language
Analog Out
Backlight
Select English, French or Spanish
Select 4-20mA or 0-5V mode for the analog output.
Select High, Medium or Low for continuous backlight brightness.
Select Key Hi/Lo for high backlight lasting 1 minute after a keypress, and then Lo backlight until a key is pressed again.
Select Key High, Med or Low for backlight lasting 1 minute after a keypress and then backlight off until a key is pressed again.
Reset Totalizer
Select Yes to erase and restart the totalizer at zero.
Negative Totals
Rev. Flow
Capture Par
Select Yes to have reverse flow readings deducted from the totalizer. Select No to totalize forward flow only and ignore reverse flow.
Select On to enable flow direction measurement. Select Off to disable flow direction measurement so that flow in either direction is displayed and output as positive values. Select Invert to invert the sense of the flow measurement.
This function captures the programming parameters in the meter. Select Yes, wait for Insrt USB to appear, then insert a USB drive into the USB port to transfer the parameters. After Saving flashes, Done will appear on the screen, meaning it is safe to remove the USB,
Page 24
Loading...
+ 55 hidden pages