Greisinger EBG-CO2-1R User guide

T38.0.1X.6C-02a
Specification:
Operating Manual for CO2-transmitter
EBG-CO2-1R
Measuring range: standard 0 ... 2000 ppm CO
Accuracy: (at 20°C, 1013mbar)
Display: standard ± 50 ppm ± 2 % of meas. value
option: / 5000 ± 50 ppm ± 3 % of meas. value
Add. output signal: ± 0,2 % FS
Temperature dependence: typ. 2 ppm CO
Response time: t
Sampling rate: ca. 15 s
Output signal: EASY
Connection: 2-wire EASY Busload: 1 EASY
Auxiliary energy:
Reverse voltage protection: 50V permanent
Warm up time: < 5 min.
Adjusting: via keypress by editing offset and scale
Display: approx. 10 mm high, 4-digit LC-display
Min-/Max-Value Memory: min and max measured values are stored
Ambient conditions for electronics:
Nominal temperature: 25°C
Operating condition: -10 to 50°C 5 to 95 %RH (non-condensing) 850 ... 1100 hPa
Storage condition: -25 to 60°C 5 to 95 %RH (non-condensing) 700 ... 1100 hPa
(supply voltage)
< 180 s
63
BUS-
protocol
BUS
-devices
Uv = 12 - 30 V DC, max. 600 mA or refer to type plate
(time to reach specification values)
2
2
/ °C (at 0-50°C)
2
BUS
, polarity free
Housing: ABS (IP20)
Dimensions: 82 x 80 x 55 mm (without elbow-type plug and tube)
Mounting: With holes for wall mounting (in housing - accessible after cover has been removed)).
Mounting distance: 50 x 70mm, max. shaft diameter of mounting screws is 4 mm.
Electrical connection: elbow-type plug conforming to DIN 43650 (IP65),
max. wire cross section: 1.5 mm², wire/cable diameter from 4.5 to 7 mm
EMC: The devices corresponds to the essential protection ratings established in the
regulations of the council for the approximation of legislation for the member countries regarding electromagnetic compatibility (89/336/EWG).
In accordance with EN61326 +A1 +(appendix A, class B), additional errors: < 1% FS When connecting long leads adequate measures against voltage surges have to be
taken.
Operating advice
CO2 gas is outweigh than air (rel. density = 1.52). The suggested mounting level is near the ground floor.
GREISINGER
electronic GmbH
D - 93128 Regenstauf, Hans-Sachs-Straße 26
Tel.: +49 9402/9383-0, Fax: +49 9402/9383-33, eMail: info@greisinger.de
T38.0.1X.6C-02a User’s Manual EBG-CO2 page 2 of 4
Safety Requirements:
This device has been designed and tested in accordance with the safety regulations for electronic devices. However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and special safety advises given in this manual will be adhered to when using the device.
1. Trouble-free operation and reliability of the device can only be guaranteed if the device is not subjected to any other climatic conditions than those stated under "Specification". If the device is transported from a cold to a warm environment condensation may cause in a failure of the function. In such a case make sure the device temperature has adjusted to the ambient temperature before trying a new start-up.
2. General instructions and safety regulations for electric, light and heavy current plants, including domestic safety regulations (e.g. VDE), have to be observed.
3. If device is to be connected to other devices (e.g. via PC) the circuitry has to be designed most carefully. Internal connection in third party devices (e.g. connection GND and earth) may result in not-permissible voltages impairing or destroying the device or another device connected.
4. If there is a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked accordingly to avoid re-starting.
Operator safety may be a risk if:
- there is visible damage to the device
- the device is not working as specified
- the device has been stored under unsuitable conditions for a longer time
In case of doubt, please return device to manufacturer for repair or maintenance.
5. Warning: Do not use these products as safety or emergency stop devices, or in any other application where failure of the product could result in personal injury or material damage. Failure to comply with these instructions could result in death or serious injury and material damage.
Disposal instructions
The device must not be disposed in the regular domestic waste. Send the device directly to us (sufficiently stamped), if it should be disposed. We will dispose the device appropriate and environmentally sound.
1 Installation
1.1 Dimensions 1.2 Elbow-type plug installation instruction
To mount the connection cable (3-, or 4-wire depending on type of device) the elbow-type plug screw has to be loosened and the coupling insert has to be removed by means of a screw driver at the position indicated (arrow). Pull out connection cable through PG glanding and connect to the loose coupling insert as described in the wiring diagram. Replace loose coupling insert onto the pins at the transducer housing and turn cover cap with PG glanding in the direction desired till it snaps on (4 different starting positions at 90° intervals). Re-tighten the screw at the angle plug.