Greenwood AXS100, AXS100SELV, AXS125, AXS150, AXSK Installation Manual

Warning: The appliance is not intended
for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance.
Observe appropriate safety precautions
if working on steps or ladders. Wear eye protection when breaking out wall or window materials etc.
Siting Notes:
Where an open-flued oil or gas- fuelled appliance is installed in the kitchen, extract ventilation can cause the spillage of flue gases. Care must be taken to ensure ventilation is reduced as appropriate, as set out in the building regulations. The guide to the regulations suggests that the reduced provision should be an extract rate
20 l/s (72 m
3
/h) maximum. Kitchens with solid-fuel appliances should not have extract fans fitted.
The fans should not be sited where
it would be subject to a direct source of heat in excess of 40ºC.
When installing wall mounted fans,
ensure that there are no buried cables or pipes in the way. It is recommended that this fan is mounted 1.8m above floor level.
A clearance of 75mm to be allowed
on at least one side of the fan for the removal of the internal grille.
Cleaning Notes:
Always isolate from the mains before cleaning. Do not use solvents to clean the fan. Wipe the front grille clean using a damp cloth avoiding getting any water into the internal fan unit.
READ ALL INSTRUCTIONS BEFORE COMMENCING INSTALLATIONS
Remove one piece Internal Grille using screwdriver. Push in to free catch then twist to remove grille.
Cut the duct to width of the plasterboard or tiled wall with slight fall to exterior. (Make provisions for cable).
Using No 8 screws, secure fan body to ducting first making sure back draught shutter is fitted, if required, and electrical cable passes through as appropriate. Wire fan (See wiring details).
WALL MOUNTING (Using ED wall duct and EG external grille, 100mm and 150mm only)
1
4
Replace internal grille ensuring no wires are trapped.
5
Screw the protective wall grille over the external duct opening.
6
2
AXS100 Ø = 125mm
AXSK/150 Ø = 170mm
Fill in any gaps with mortar or foam and make good internal and external walls. Make sure that ducting remains circular and screw holes are horizontal.
3
CEILING MOUNTING
Remove one piece Internal Grille using screwdriver. Push in to free catch then twist to remove grille.
Cut an opening through the ceiling for the fan and electrical cable.
Place flexible ducting over the spigot of the fan.
1
4
Fit ducting to spigot using ties supplied, making sure impeller rotates freely.
Maximum duct length to comply with Building Regulations: AXS100: 3m AXSK/150: Wall mounting only
5
8
X
Ø 12 for cable
X = 67mm for AXS100 X = 78mm for AXS125 Ø = 105mm for AXS100 Ø = 130mm for AXS125
Ø
2
Secure to ceiling using suitable screws first making sure backdraught shutters are removed but shutter spider is left in position. Wire fan (See wiring details).
3
9
6
Detach the cord from the PCB by pulling the cord through the pull cord’s link.
Installation Instructions for Axial Fans
for Bathroom, Toilets, Utility Rooms and Kitchens
AXS100, AXS100SELV, AXS125, AXS150 & AXSK
Replace internal grille ensuring no wires are trapped.
7
2
3
1
8
WIRING DETAILS
The electrical connections must be carried out by a qualified electrician in accordance with IEE or local regulations.
WARNING: Isolate electricity supply before starting work.
The fans are double insulated and do not
require an earth connection.
The fans must be connected to a double
pole isolating switch having contact separation of at least 3 mm.
When supplied from a 6 amp lighting
circuit no local fuse is required.
Specification:
230V~50Hz.
Consumption: AXS100 16W AXS100SVI 19W AXS125 28W AXSK/150 33W Cable Sizes: Fixed flat wiring
2 core 1mm
2
3 core 1/1.5mm
2
Flexible round wiring 2 core 0.75mm
2
3 core 0.75mm
2
WIRING DIAGRAMS
L
N
Fan
Terminals
L
N
Double pole
isolating switch
Fuse
Light
Remote/Light
Switch
L
N
Fan
Terminals
L
N
Double pole
isolating switch
Fuse
L
N
Fan
Terminals
N
L
Double pole
isolating switch
Fuse
Light
Remote/Light
Switch
August 2010 (MCR 521) 05.10.270 Issue 6 BP13061
TO CLEAN OR SERVICE FAN
The only user servicing required with this fan is the removal and cleaning of the front grille.
l Remove one piece Internal Grille using
screwdriver. Push in to free catch then twist to remove grille.
l The fan may now be cleaned using
a brush or damp cloth. DO NOT IMMERSE IN WATER.
l After cleaning replace Internal Grille
by pushing home.
WARNING: Always isolate fan from mains supply before cleaning. Do not use solvents to clean this fan.
Greenwood Air Management Ltd Greenwood House, Brookside Avenue, Rustington, West Sussex, BN16 3LF
Tel: (01903) 771021 Fax: (01903) 782398 Web: www.greenwood.co.uk Email: info@greenwood.co.uk
AXS100, AXS125 & AXS150
L
N
Fan
Terminals
L
N
Double pole
isolating switch
Fuse
L
N
Fan
Terminals
N
L
Double pole
isolating switch
Fuse
L
N
Controller Terminals
12V Fan Terminals
N
SL
L
2
3
1
Double pole
isolating switch
1
2
3
Fuse
L
N
Controller Terminals
12V Fan
Terminals
N
SL
L
2
3
1
Double pole
isolating switch
1
2
3
Fuse
L
N
Fan
Terminals
Light Switch
Switch
Light
Light
Fuse
L1
N
L
Double pole
isolating switch
Remote/Light
Switch
AXS100SVIB
AXS100PC & AXSK
L
N
Fan
Terminals
L
N
Double pole
isolating switch
Fuse
L
N
Fan
Terminals
N
L
Double pole
isolating switch
Fuse
L
N
Fan
Terminals
Light Switch
Light
Light
Fuse
L1
N
L
Double pole
isolating switch
Remote/Light
Switch
AXS100T, AXS100TR, AXS100DT, AXS100HT, AXS125TR, AXSKMA,
AXS150TR & AXSKT
L
N
Fan
Terminals
L
N
Double pole
isolating switch
Fuse
L
N
Fan
Terminals
N
L
Double pole
isolating switch
Fuse
L
N
Controller Terminals
12V Fan
Terminals
N
SL
L
2
3
1
Double pole
isolating switch
1
2
3
Fuse
L
N
Controller Terminals
12V Fan
Terminals
N
SL
L
2
3
1
Double pole
isolating switch
1
2
3
Fuse
Controller Terminals
12V Fan
Terminals
N
SL
L
2
3
1
1
2
3
L
N
Fan
Terminals
Light Switch
Switch
Light
Light
Fuse
L1
N
L
Double pole
isolating switch
Remote/Light
Switch
L
N
Light Switch
Light (optional)
Fuse
Double pole
isolating switch
SELV Fans External wiring for operation in parallel with
room light or remote switch with or without pull cord
Remove the electrical cover. Make all connections to the connector blocks.
Note: Mains cable must be fixed back to the wall using appropriate cable cleats.
Replace electrical cover.
Note: Do not fit more than one fan to the controller or connect with any other product. This equipment must be sited away from direct water spray and heat in excess of 40˚C the controller must not be sited within reach of a person using a bath or shower nor within a shower cubicle/enclosure.
Mains
230 V ~ 50 Hz
To Fan 12 V
SELV FANS ONLY TO WIRE THE CONTROLLER
SVI 12 V Controller
(with switch line)
L
N
Fan
Terminals
L
N
Double pole
isolating switch
Fuse
L
N
Fan
Terminals
N
L
Double pole
isolating switch
Fuse
L
N
Controller Terminals
12V Fan
Terminals
N
SL
L
2
3
1
Double pole
isolating switch
1
2
3
Fuse
L
N
Fan
Terminals
Light Switch
Light
Light
Fuse
L1
N
L
Double pole
isolating switch
Remote/Light
Switch
SELV Fans
External wiring for pull cord only
3
4
5
6 7
AXS100/AXS125 Fans – before commencing wiring, cafefully remove safety cover with a screwdriver by gently prying open ‘hook mechanism’ (inset diagram 2a) and pulling off cover. After fitting do not forcibly remove this cover. Before replacing centre safety cover, after wiring, make sure the pull cord link is located correctly behind the PCB as shown (inset diagram
5). Refit safety cover on completion of wiring by pushing home.
Note: If cable is supplied with earth core this can be cut to the same length and ‘parked’ as shown in diagram 7.
If fixed flat cable is used or flexible cable which is secured with suitable wall fixings the cable clamp is not required.
If flexible cable is used without suitable fixings use cable clamp and screw supplied loose with the fan (diagram 8).
For SELV fans only Maximum cable length between fan and
controller: Conductor Size Maximum length
0.75mm
2
2.3m
1.00mm
2
3.0m
SENSOR/TIMER ADJUSTMENTS
Note: Isolate from mains before commencing work/adjusting timer.
The removal of the wiring cover and setting of temperature and humidity controls may only be carried out by a Qualified Electrician in accordance with local regulations.
1 Remove one piece Internal Grille using
screwdriver. Push in to free catch then twist to remove grille.
2 The timer is pre-set but may be adjusted
by using a screwdriver and rotating clockwise to increase time and anti­clockwise to reduce time overrun.
The humidity sensor is pre-set but may be adjusted by using a screwdriver and rotating clockwise to increase the sensitivity and anti-clockwise to reduce the sensitivity.
4 After adjustments replace Internal Grille
by pushing home.
Installation Instructions for AXS100, AXS100SELV, AXS125, AXS150 & AXSK Axial Fans
115mm
115mm
6mm
100mm
6mm
100mm
1
AXS100
AXSK, AXS125
& AXS150
2b2a
AXS100/AXS125 AXS150/AXSK