Green Mountain GMGWB045FE, GMGWB120FE, GMGWB070FE, GMGWB096FE, GMGWB170FE Installation Operation & Maintenance

...
GMGW
Cast Iron
Gas Fired Boilers
For Forced Hot Water
INSTALLATION, OPERATIONS AND MAINTENANCE
MANUAL
Models GMGWB045FE GMGWB120FE GMGWB070FE GMGWB145FE GMGWB096FE GMGWB170FE
GMGWB195FE GMGWB245FE
C.S.A. Certied
For Natural Gas Or Propane
An ISO 9001-2008 Certified Company
Tested For 100 psi
ASME
Working Pressure
GMGWB295FE
Manufactured by:
ECR International, Inc.
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
P/N# 240011109, Rev. C [07/22/2015]
1 - RATINGS & DATA - NATURAL GAS & PROPANE GAS
Model No.
Input
Mbh
(1)
Table 1
Heating
Capacity
Mbh
- Ratings and Capacities
(1)
Net AHRI
Rating Water
(2)
Mbh
**
AFUE Elect.
Ign.
No. Of
Burners
Recommended Air
Cushion Tank
(3)
Water
Content
(Gals.)
GMGWB045FE 45 37 32 82.0% 1 15 2.4
GMGWB070FE 70 57 50 82.0% 2 15 4.0
GMGWB096FE 96 79 69 82.0% 2 30 4.0
GMGWB120FE 120 98 85 82.0% 3 30 5.6
GMGWB145FE 145 119 103 82.0% 3 30 5.6
GMGWB170FE 170 140 122 82.0% 4 30 7.2
GMGWB195FE 195 160 139 82.0% 4 30 7.2
GMGWB245FE 245 201 174 82.0% 5 30 8.8
GMGWB295FE 295 242 210 82.0% 6 60 10.4
EXPLANATORY NOTES
-- All boilers are design certied for installation on noncombustible oor.
-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be reduced to 10 feet. Refer to the latest revision of NFGC part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
United States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every 1,000 ft (304m) above sea
level.
(2) Net AHRI Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer before selecting
boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected on basis of its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and
radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, High Limit Control, Intermittent Electric Ignition Pilot System, Vent Damper Relay, Circulator With Return Piping To Boiler, Main Gas Burners, Gas Control (Includes Automatic Gas Valve, Gas Pressure Regulator, Intermittent Pilot, Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Valve, Spill Switch, Rollout Switch, Combination Gas Control, Automatic Vent Damper. Not Shown Are: Wiring Harness,, Non­linting Safety Pilot.
2
P/N# 240011109, Rev. C [07/22/2015]
**
Dimensions
2 - DIMENSIONS
Table 2 - Dimensions
Model No.
Natural Gas
Inlet*
GMGWB045FE ½" 11¼ 5⅝ 4 27⅛ 207/16415/ GMGWB070FE ½" 15⅛ 7 5 28⅛ 2015/16415/ GMGWB096FE ½" 15⅛ 7 5 28⅛ 2015/16415/ GMGWB120FE ½" 19 6 29⅛ 217/1657/ GMGWB145FE ½" 19 6 29⅛ 217/1657/ GMGWB170FE ½" 22⅞ 113/ GMGWB195FE ½" 22⅞ 113/
GMGWB245FE ¾” 26¾ 136/ GMGWB295FE ¾” 30⅝ 155/
* Propane Gas Inlet (All Units) 1/2”
Dimensions (Inches)
A B C D E F
7 30⅛ 2115/16515/
16
7 30⅛ 2115/16515/
16
8 31⅛ 227/16615/
16
9 32⅛ 2215/16815/
16
3
Pump Size Supply &
Return Tappings
16
16
16
16
16
16
16
16
16
P/N# 240011109, Rev. C [07/22/2015]
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
1¼"
TABLE OF CONTENTS
1 - Ratings & Data - Natural Gas & Propane Gas ...........................................................2
2 - Dimensions .............................................................................................................3
3 - Installation Procedure ............................................................................................6
4 - Ventilation & Combustion Air ..................................................................................7
5 - Connecting Supply & Return Piping .........................................................................8
6 - Vent Installation ...................................................................................................14
7 - Vent System Modication ......................................................................................14
8 - Vent Damper Installation & Instructions ...............................................................15
9 - Connecting Gas Service .........................................................................................16
10 - Electrical Section .................................................................................................17
11 - Wiring Diagram ...................................................................................................18
12 - Lighting Instructions ...........................................................................................20
13 - Normal Sequence Of Operation ...........................................................................21
14 - General Instructions ...........................................................................................21
15 - Checking Gas Input Rate To Boiler ......................................................................23
Appendix A - Control Module ..................................................................................... 24
A.1 Installation Environment Considerations ................................................................ 24
A.2 Electrical Connections ......................................................................................... 24
A.3 Adjusting Settings .............................................................................................. 24
A.4 Display ............................................................................................................. 24
A.5 Operation .......................................................................................................... 25
A.6 Boiler High Limit Temperature Controller ................................................................ 26
A.7 Troubleshooting.................................................................................................. 26
A.8 Troubleshooting Error Codes ................................................................................ 26
A.9 Intermittent Pilot Ignition System Verication ......................................................... 27
4
P/N# 240011109, Rev. C [07/22/2015]
SAFETY MESSAGES
IMPORTANT: Read the following instructions COMPLETELY before installing!!
Safety Symbols & Warnings
The following dened symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
!
WARNING
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room. Modication, substitution or elimination of factory
equipped, supplied or specied components may result in personal injury or loss of life.
TO THE OWNER - Installation and service of this boiler must be performed by a qualied installer.
TO THE INSTALLER - Leave all instructions with boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
5
P/N# 240011109, Rev. C [07/22/2015]
3 - INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration, service or maintenance could result in death or serious injury.
1.
Installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane
Installation Code, CAN/CSA B149.1.
2.
Where required by authority having jurisdiction, installation must conform to the Standard for Controls and Safety Devices for Automatically red Boilers, ANSI/ASME CSD-1.
3.
Boiler series is classied as a Category I. Vent installation shall be in accordance with "Venting of Equipment ," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or "Venting Systems and Air Supply for Appliances," of the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
4.
Boiler has met safe lighting and other performance criteria with gas manifold and control assembly on boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Boiler shall be installed such that gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.).
6.
Locate boiler on level, solid base as near chimney as possible and centrally located with respect to heat distribution system as practical.
7.
Allow 24 inches (610mm) at front and right side for
servicing and cleaning.
8.
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as water heater.
!
WARNING
Fire hazard. Do not install boiler on combustible ooring or carpeting. Failure to follow these instructions could result in death or serious injury.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY - For installation on combustible
ooring special base must be used. (See Replacement
Parts Section.) Boiler can not be installed on carpeting. Minimum clearances to combustible
construction are:
TOP ....................................18 IN. (457mm)
FRONT .........................................ALCOVE *
FLUE CONNECTOR ................. 6 IN. (152mm)
REAR....................................8 IN. (229mm)
CONTROL SIDE ................... ..9 IN. (76mm)
OTHER SIDE............................3 IN. (76mm)
HOT WATER PIPING ................. 2 IN. (51mm)
NOTE: Greater clearances for access should supersede fire
protection clearances. * Denition of Alcove is three sided space with no wall in front of boiler. ANSI standard for alcove is 18 inches from front of appliance to leading edge of side walls as shown below.
Minimum Clearances To Combustible
Construction (As Seen From Above)
8"
3"
9"
Control
Side
BOILER
6
18"
Front
P/N# 240011109, Rev. C [07/22/2015]
4 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen ventilation equipment interfere with proper operation.
National Fuel Gas Code recognizes several methods of obtaining adequate ventilation and combustion air. Requirements of the authority having jurisdiction may override these methods.
Engineered Installations. Must be approved by authority having jurisdictions.
Mechanical Air Supply. Provide minimum of 0.35 cfm per Mbh for all appliances located within space. Additional requirements where exhaust fans installed. Interlock each appliance to mechanical air supply system to prevent main burner operation when mechanical air supply system not operating.
All Indoor Air. Calculate minimum volume for all appliances in space. Use a different method if minimum volume not available.
о Standard Method. Cannot be used if known air
inltration rate is less than 0.40 air changes per hour. See Table 3 for space with boiler only. Use equation for multiple appliances.
Volume ≥ 50 ft3 x Total Input [Mbh]
о Known Air Inltration Rate. See Table 3 for
space with boiler only. Use equation for multiple appliances. Do not use an air inltration rate (ACH) greater than 0.60.
Volume ≥ 21 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
National Gas and Propane Installation Code Requires providing air supply in accordance with:
All Outdoor Air. Provide permanent opening(s) communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure.
 Direct communication with outdoors or
communicating through vertical ducts. Provide minimum free area of 1 in2 per 4 Mbh of total input rating of all appliances in enclosure.
 Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2 Mbh of total input rating of all appliances in enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure. Provide minimum clearance of 1 inch on sides and back and 6 inches on front of boiler (does not supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements for louvers, grilles, screens and air ducts.
Combination Indoor and Outdoor Air. Refer to National Fuel Gas Code for application information.
Section 8.2 and 8.3 when combination of appliances has a total input of up to and including 400 Mbh (120 kW).
Section 8.4 when combination of appliances has total input exceeding 400 Mbh (120 kW).
Refer to Natural Gas and Propane Installation Code for specic air supply requirements for enclosure or structure where boiler is installed, including air supply openings and ducts.
Table 3 - Minimum Room Volume, Indoor Air Only*
Input Mbh
45 2250 9450 4725 3150 2363 1890 1575
70 3500 14700 7350 4900 3675 2940 2450
96 4800 20160 10080 6720 5040 4032 3360
120 6000 25200 12600 8400 6300 5040 4200
145 7250 30450 15225 10150 7613 6090 5075
170 8500 35700 17850 11900 8925 7140 5950
195 9750 40950 20475 13650 10238 8190 6825
245 12250 51450 25725 17150 12863 10290 8575
295 14750 61950 30975 20650 15488 12390 10325
* Table values based on boiler only. Add volume for any additional appliances.
Standard
Method
0.1 0.2 0.3 0.4 0.5 0.6
Known Air Inltration Rate Method (Air Changes Per Hour)
7
P/N# 240011109, Rev. C [07/22/2015]
5 - CONNECTING SUPPLY & RETURN PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum distance from oor or allowable safe point of discharge.
be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line;
have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or
place any obstruction in discharge line.
terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
allow complete drainage of the valve and the discharge line;
be independently supported and securely anchored to avoid applied stress on the relief valve;
be as short and straight as possible;
terminate with plain end (not threaded);
be constructed of material suitable for exposure to temperatures of 375° F (191°C); or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation requirements.
Figure 1 - Safety Relief Valve
Safety Relief Valve
Discharge Line
Check local codes for maximum distance from oor or allowable safe point of discharge.
8
P/N# 240011109, Rev. C [07/22/2015]
5 - CONNECTING SUPPLY & RETURN PIPING
Hydronic Piping - General
Install piping in accordance with authority having jurisdiction.
Support system piping and safety relief valve discharge piping.
Special Conditions
System piping exposed to freezing conditions: Use inhibited proplyene glycol solutions certied by uid manufacturer for use with closed water heating system. Do not use automotive or ethylene glycol.
Boiler installed above radiation level (or as required by authority having jurisdiction). Install low water cutoff.
Boiler used in connection with refrigeration system. Install piping in parallel with boiler, with appropriate valves to prevent chilled medium from entering boiler. See Figure 2, Page 10.
System piping connected to heating coils located in air handling unit exposed to refrigerated air circulation. Install ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
Safety Relief Valve
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. Install discharge piping per these instructions.
NOTICE
Boiler rated at 100 psig maximum allowable working pressure. Boiler provided with 30 psig safety relief valve. Field source safety relief valve for system pressures greater than 30 psig. Temperature­pressure gauge provided with boiler is satisfactory for 30-50 psig operation. Replace temperature­pressure gauge for system pressure over 50 psig. Scale on dial must be graduated to not less than 1½ nor more than 3½ time safety relief valve pressure
settings.
Do not install shutoff valve between boiler and safety
relief valve.
Systems with automatic ll valves require back ow prevention device.
Install discharge piping from safety relief valve. See Warning, Page 8.
When boiler is connected to heating system utilizing
multiple zoned circulators, each circulator must be supplied with ow control valve to prevent gravity circulation.
Hot water boilers and system must be lled with water and maintained to minimum pressure of 12 psi.
Bypass piping is an option which gives ability to adjust the supply boiler water temperature to t the system or condition of installation. This method of piping, however, is not typically required for baseboard heating systems. Typical installations where bypass piping is used are as follows:
A. This method is used to protect boilers from
condensation forming due to low temperature return water. Generally noticed in large converted gravity systems or other large water volume systems. Figures 3 & 4, Page 11.
B. These methods are used to protect systems using
radiant panels and the material they are encased in from high temperature supply water from the boiler and protect boiler from condensation.
NOTE#1: When using bypass piping, adjust valves V1 & V2 until desired system temperature is obtained.
NOTE#2: Bypass loop must be same size piping as the supply and return piping.
Installation using circulators and zone valves are shown in Figures 3-8 . For further piping information refer to AHRI Installation and Piping Guide.
For zone controls and indirect hot water, refer to appropriate manufacturer instructions.
For Low Water Cutoff, see Dimensions page 5 for minimum height. Use kit number 550009885. Follow
instructions enclosed with the kit.
For other LWCO's follow their specic manufacturer instructions.
9
P/N# 240011109, Rev. C [07/22/2015]
5 - CONNECTING SUPPLY AND RETURN PIPING
EXPANSION
TANK
CHECK VALVE
B
D
FEED
WATER
C
RETURN PIPING
FROM HEATING AND COOLING ELEMENT
WATER CHILLER
SUPPLY PIPING
TO HEATING
AND COOLING
ELEMENT
CIRCULATOR
A
PRESSURE REDUCING VALVE
PROPER BACKFLOW PROTECTION DEVICE
GATE VALVE
PURGE VALVE
NOTICE
Circulators in following illustrations are mounted on system supply side, mounting on system return side is also acceptable practice.
Figure 2 - Circulators Mounted on Supply System, Boiler Used In Conguration to Chiller System.
See Special Conditions, Page 9
10
P/N# 240011109, Rev. C [07/22/2015]
Loading...
+ 22 hidden pages