Greenheck Fan TCB User Manual

This supplement to the TCB Installation Operation and Maintenance Manual is intended to provide additional information when dealing with fans used in applications involving grease laden air. Refer to the TCB Installation, Operation and Maintenance Manual (PN 456557) for items that are not specifically addressed (handling, storage, start-up, troubleshooting and maintenance) in this supplement.
READ AND SAVE THESE INSTRUCTIONS
PN 464115
Installation Operation and Maintenance Manual
Supplement for UL-762 Listed (Restaurant Exhaust) Fans
Installation Practices
• All units used in applications with grease laden air are to be installed in accordance to NFPA 96, IMC 2203 and local codes. Consult local code authorities for your specific requirements.
• Fans shall be located in an easily accessible area of adequate size to allow for service or removal. Exhaust fans with ductwork connected to both ends shall have access for cleaning and inspection within 3 ft (0.92 m) of each end of the fan (NFPA 96).
• Maintain a minimum clearance of at least 18 inches (457 mm) to combustible material and 6 inches (125.4 mm) to either limited-combustible or noncombustible material (NFPA 96).
• Fans are to be installed with the motors in the 3 or 9 o’clock (C or G) positions. Motors located in this configuration may cause an unbalanced load that should be considered if isolators are to be used. Equalized loading between isolators can be achieved through the use of mounting rails. Refer to the TCB IOM for details and installation instructions involving mounting rails.
• It is recommended to install the fan near the end of the duct run. This limits the amount of positive pressure in the system. The diagram below illustrates an inline fan exhausting air near the final termination point. See local codes and NFPA 96 for any restrictions and requirements for wall terminations.
• A drain is provided for single-point drainage of water and residue. When installed correctly, one of the two housing drains will be located on the bottom. This drain is used to remove any accumulated grease and / or cleaning solutions. Some means for collection of this residue must be provided, either a container directly under the drain or use an adapter and pipe to carry the residue to a remote collection point. Remove drain plug prior to connection to grease collection device.
• Provision to open and remove the access door is required for periodic cleaning and maintenance. The access door is clearly labeled and indicates that access to this location must be maintained. Any enclosure openings required to reach the access panel shall be large enough to allow for the removal of the panel.
E
xhaus
t air exiting the b
uildin
g
M
inimu
m duct
at discharge
F
a
n
E
xterio
r Wa
ll
A
irflo
w
®
Fan flange
Fan flange
Minimum 1 inch
(25.4 mm) flange
1/4 inch (6.25 mm) carbon
or stainless steel bolts
1/4 inch (6.25 mm)
carbon or stainless steel
bolts
Welded companion flange or 1x1x1/4 inch (25.4x25.4x6.25
mm) angle
Gasket rated for
1500
o
F (815oC)
Sealant rated for
1500oF (815oC)
Over-lapping Connection
Sealant Connection
Cleaning, Maintenance and Repair
Cleaning of Internal Components
• Entire wheel should be cleaned during routine duct cleaning. Partial cleaning may result in an unbalanced wheel that can cause premature bearing failure or excessive vibration.
• Grease / cleaning solution should drain freely through the provided drain connection. Remove any obstructions inhibiting proper drainage.
• Only the access door is removed during routine duct cleaning. The bearing cover is not removed during routine cleaning. The bearing cover is removed only when inspecting or changing the bearings, fan shaft or driven pulley.
Bearing Lubrication
See bearing manufacturer’s instructions or label on the fan housing for lubrication schedule. Lubricate bearings with high temperature grease conforming to NLGI grade 2 such as Mobil Mobilith SHC 100 or 200.
Sealant / Gasket / Seal Replacement
Fan to Duct Sealant / Gasket Replacement
Repair or replace sealant / gasket as needed. Replacement sealant or gasket shall be rated for 1500oF (815oC) and shall be grease tight such as 3M Fire Barrier 2000+ Silicone Sealant. See Sealant and Over-lapping Connection figures for proper installation.
Access Door / Bearing Cover Gasket Replacement
Replace access door or bearing cover gasket material as needed. Gasket material for the access door is 1/2 x 1/2 inch (12.7 x 12.7 mm) Greenheck part number 220145. Gasket for the bearing cover is 1/8 x 1/2 inch (3.17 x 12.7 mm) Greenheck part number 220144. Both items are ordered by the foot.
Mechanical Seal
A mechanical seal, located inside the bearing cover, is used to keep grease from penetrating into this area. Contact Greenheck with the fan’s serial number for appropriate sizing and part number for a replacement mechanical seal.
Refer to the TCB IOM (PN 456557) for other maintenance procedures.
TCB with UL-762 Supplement IOM
Rev. 1 March 2004
Copyright © 2004 Greenheck Fan Corp.
• Inline fans shall be connected to the exhaust duct by flanges securely bolted as shown in the figures below (NFPA 96). Flexible connectors shall not be used. Units supplied with matching companion flanges are to have this part welded to the ductwork and then bolted to the fan. Gaskets used in the Over-lapping Connection style shall not be positioned in a manner to have direct contact with the grease.
Installation Practices (Continued)
Airflow
Loading...